Contents
1. Introduction 2. Fault analysis methods
a) Classical symmetrical components, b) Phase variable approach and c) Complete time-domain simulations
4. Conclusion 5. References
CERTIFICATE
This is certify that the seminar report titled FAULT ANALYSIS OF POWER DISTRIBUTION SYSTEMS submitted in partial fulfillment of requirements of the award of the degree of Master of Technology in Electrical Power System Management by KALYAN RANJAN (12 MEE-04) is a bonafide record of the candidates work out by him under my guidance.
Abstract
Fault resistance is a critical component of electric power systems operation due to its stochastic nature. If not considered, this parameter may interfere in fault analysis studies. The fault analysis of unbalanced three-phase distribution systems can be done by an iterative fault analysis algorithm considering a fault resistance estimate. This algorithm is composed by two sub-routines, namely the fault resistance and the bus impedance. The fault resistance sub-routine, based on local fault records, estimates the fault resistance. The bus impedance sub-routine, based on the previously estimated fault resistance, estimates the system voltages and currents.
Introduction
Electric power systems are daily exposed to service interruption due to either temporary faults or permanent faults. Fault will be take place when two or more conductors at different potentials are touches each other or a live conductor touching the ground either with zero resistance or with a substance of low resistance. A fault will cause currents of high value to flow through the network to the faulted point. The amount of current may be much greater than the designed thermal ability of the conductors in the power lines or machines feeding the fault. As a result, temperature rise may cause damage by annealing of conductors and insulation failure. In addition, the low voltage in the healthy phase of the faulty system will cause equipment to malfunction and affects systems reliability, security, and energy quality. When a distribution line short circuited, very large currents flow for a short time until a fuse or breaker or other interrupter breaks the circuit. One important aspect of overcurrent protection is to ensure that the fault arc and fault currents do not cause further, possibly more permanent, damage. The two main considerations are: Conductor annealing From the substation to the fault location, all conductors in the fault-current path must withstand the heat generated by the short-circuit current. If the relaying or fuse does not clear the fault in time, the conductor anneals and loses strength. Burn downs Right at the fault location, the hot fault arc can burn the conductor. If a circuit interrupter does not clear the fault in time, the arc will melt the conductor until it breaks apart. Today, three approaches are used in the industry for such analysis: classical symmetrical components, phase variable approach and time-domain simulations. There are many causes of faults on distribution circuits such as lightning, insulation breakdown, conductors slapping together in the wind, trees falling across lines, insulator flashovers caused by pollution, insulator failures, broken wires, equipment such as transformers or capacitors failures etc. The distribution of fault causes found in the EPRI study is shown in figure below.
Types of fault
(A) Single line-to-ground fault (B) Line-to-line fault (C) Double line-to-ground fault (D) Three phase fault (E) Three phase-to-ground fault
Distribution faults occur on one phase, on two phases, or on all three phases. Singlephase faults are the most common. Almost 80% of the faults measured involved only one phase either in contact with the neutral or with ground.
Fig. 3. Single line to ground fault Fault resistance represents the fault impedance path between phase or ground faults. The fault resistance sub-routine uses the sending-end voltages and currents as input data. Referring to the power system of fig. 3, the sending-end voltages are given by equation (1), considering the steady-state fault conditions.
Where, V sfm is the phase m sending-end voltage (V); x is the distance between the sending-end and the fault location (m);
Z mm is the phase m line self-impedance (ohm/m);
For the single line-to-ground fault (SLG) illustrated in Fig. 1, the faulted phase sending end voltage can be expanded to equation (2)
Whereas ZF is the fault impedance between line-to-ground, the sub-script p represents the faulted phase, and I Fp is the phase p fault current. Considering the fault impedance strictly resistive and constant, equation (2) may be expanded into its real and imaginary parts,
Where the subscripts r and i represent the real and imaginary components, RF is the fault resistance, and:
Evaluating equation (4), the fault distance and resistance may be calculated as function of the sending-end voltages and currents, as well as the line parameters, as given by equation (7):
From equation (7), fault resistance and distance independent mathematical expressions for single line-to-ground faults are obtained, given by equations (8) and (9), respectively:
As a result of the procedure described above, the fault distance and resistance may be estimated. To obtain such estimates, the system parameters, sending-end voltages and currents should be known. The fault current is the only unknown variable on such expressions and is calculated by an iterative procedure.
Where [ I sf ] is the sending-end three-phase current vector; [ I L ] is the three-phase load current vector. An iterative formulation is developed to estimate the fault current as shown in flowchart.
Where equivalent admittance matrix between the load and the line impedance between the fault location and the receiving-end is calculated by (11) while the three-phase load current vector is updated using the equivalent admittance matrix obtained by equation (12).
The estimated value of fault current obtained from above iterative method would be used in equations (8) and (9), to estimate fault location and fault resistance respectively.
The off-diagonal sub-matrices are obtained from equation (29), where [Yabc ] p , j is the admittance matrix element between buses p and j.
From equations (13) and (14), 3n*3n three-phase admittance and impedance matrices are built, as presented in equations (15) and (16), respectively.
Solution Method Given the voltage at the root node and assuming a flat profile for the initial voltages at all other nodes, the iterative solution algorithm consists of three steps: 1. Nodal current calculation: At iteration k, the nodal current injection, I i ( k ) at network node i is calculated as,
I i (k ) ( S i / Vi (k 1)) * YiVi (k 1) ;
i= 1, 2, . , n.
(17)
Where Vi (k 1) is the voltage at node i calculated during the (k-l)th iteration Si is the specified power injection at node i. Yi is the sum of all the shunt elements at the node i. 2. Backward sweep: At iteration k, starting from the branches in the last layer and moving towards the branches connected to the root node the current in branch L, JL is calculated as:
J L (k ) I L2 i
L = b, b-1, . ,1.
.. (18)
Where I L 2 (k ) is the current injection at node L2. This is the direct application of the KCL.
3. Forward sweep: Nodal voltages are updated in a forward sweep starting from branches in the first layer toward those in the last. For each branch, L, the voltage at node L2 is calculated using the updated voltage at node L1 and the branch current calculated in the preceding backward sweep:
VL 2 (k ) VL1 (k ) Z L J L (k ) ;
L = 1, 2, . , b
.. (19)
Where Z L is the series impedance of branch L. This is the direct application of the KVL. Steps 1, 2 and 3 are repeated until convergence is achieved.
Convergence Criterion
We used the maximum real and reactive power mismatches at the network nodes as our convergence criterion. As described in the solution algorithm, the nodal current injections, at iteration k, are calculated using the scheduled nodal power injections and node voltages from the previous iteration (equation (17)). The node voltages at the same iteration are then calculated using these nodal current injections (equations (18) and (19)). Hence, the power injection for node i at k-th iteration, is calculated as:
S i (k ) Vi (k )( I i (k )) * Yi | Vi (k ) | 2
.. (20)
The real and reactive power mismatches at bus i are then calculated as:
Pi (k ) Re[S i (k ) S i ] Qi (k ) Im[S i (k ) S i ]
..... (21)
Fault calculation
For a single line-to-ground fault, Z Bus must be modified to include the fault resistance of the path between the faulted line and ground. The fault resistance is included in the bus impedance matrix through a fault node r. As result, a new impedance matrix Z new of dimension (3n+3)*(3n+ 3) is obtained. For a SLG fault, the fault current may be calculated using equation (22)
Where RF is the fault resistance, estimated by equation (9). The change in voltages at each bus due to the injected fault current ( I Fr ) may be calculated using the impedance matrix Z new :
Whereas i= from 1to (3n+ 3) represents the node index. Adding the change in voltages to each pre-fault bus voltage ( V PF ), the fault period bus voltages ( V F ) are estimated through equation (26):
Finally, from the three-phase bus voltages and the admittance matrix, it is possible to calculate the three-phase currents during the fault period at each feeder ( I gh ):
Where g, h = from 1to (n+ 1), in which n is the total bus number.
Conclusion
Fault resistance and fault location are stochastic in nature and hence needed to estimate these values. To estimate these values we use an iterative fault analysis algorithm. This fault algorithm composed by two sub-routine , one enable to estimate fault resistance and fault location while other one enable to estimate the system voltages and currents.
REFERENCES
[1] Filomena AD, Resener M, Salim RH, Bretas AS." Distribution systems fault analysis considering fault resistance estimation". Int J Electrical Power and Energy System 2011; 33(7): 13261335. [2] Liao Y." Generalized fault-location methods for overhead electric distribution systems". IEEE Trans Power Deliv 2011;26(1):5364. [3] Ngu EE, Krishnathevar R. "Generalized impedance-based fault location for distribution systems". IEEE Trans Power Deliv 2012; 27(1):44951. [4] Javad Sadeh, Ehsan Bakhshizadeh, Rasoul Kazemzadeh: "A new fault location algorithm for radial distribution systems using modal analysis". Int j Electrical Power and Energy Systems 2013; 45: 271278. [5] Turan Gonen,"Electric Power distribution system engineering". Taylor and Francis, CRC Press, 2010.