Anda di halaman 1dari 11

2.2 Voltage and reactive power 2.2.

Voltage and reactive power Heavy load situation:

Equality constraints for active


and reactive power:

PG = PL + Ploss
PG=10300 MW Ploss= 300 MW PL=10000 MW

QG = QL + Qloss QG= 3500 MVAR Qloss=1500 MVAR QL= 2000 MVAR

Low load situation:

PG= 5100 MW Ploss= 100 MW PL= 5000 MW


QG= -500 MVAR Qloss= -1500 MVAR QL=1000 MVAR

24.08.2006
2.2 Voltage and reactive power 2.2.2

The synchronous generator


jX aI

I
Xa Xσ R
Ef jXσ I

Ef Er Vg Er
RI
if

Vg

I
Xa armature reactance Ef excitation emf
Xσ leakage reactance Er air gap emf
R armature resistance Vg terminal voltage
if excitation current

24.08.2006
2.2 Voltage and reactive power 2.2.3

The synchronous generator

Active and reactive power supplied by the generator:

X d = X a + Xσ R << X a + X σ jX d I
I
Xd Ef

Ef Vg
Vg
if
δ

ϕ
Ef ⋅ Vg Vg2 I
Ef ⋅ Vg
Pg = ⋅ sin δ Qg = ⋅ cos δ −
Xd Xd Xd

24.08.2006
2.2 Voltage and reactive power 2.2.4

The synchronous generator


Over excitation Under excitation

jX d I jX d I

jX d I
Ef Vg Ef Vg Vg jX d I
Vg
Ef
Ef
ϕ
ϕ ϕ
I I
I I

Pg = 0 Qg > 0 Pg > 0 Qg > 0 Pg > 0 Qg < 0 Pg = 0 Qg < 0


Phase shifter Generator Generator Phase shifter
Lagging power factor Lagging power factor Leading power factor Leading power factor
(Synchronous capacitor) (Synchronous reactor)

24.08.2006
2.2 Voltage and reactive power 2.2.5

Automatic Voltage Regulator (AVR)

Synchronous Step-up
Excitation generator Transformer

1: t
if
Network

Vg
V −
Vref
Amplifier ∑
+

24.08.2006
2.2 Voltage and reactive power 2.2.6

Increase of reactive power supply (MVAR) Decrease of reactive power supply (MVAR)

- Change of reference voltage Vref - Change of reference voltage Vref


1
Vref > Vref
0 1
Vref < Vref
0

V >0; i 1f > i f0 ; V <0; i 1f < i f0 ;

Q1g > Qg0 Q1g < Qg0

- Change of tap setting t - Change of tap setting t


t1 > t 0 : t1 < t 0 :

Vg1 < Vg0 ; V >0; i 1f > i f0 Vg1 > Vg0 ; V <0; i 1f < i f0

Q1g > Qg0 Q1g < Qg0

24.08.2006
2.2 Voltage and reactive power 2.2.7

Voltage and reactive power control mechanisms

AVR
400 kV

Communication
Secondary AVR
Voltage 220 kV
Control

AVR

110 kV

AVC
20, 10 kV

24.08.2006
2.2 Voltage and reactive power 2.2.7 /7

Voltage and reactive power


Voltages at
boundary
nodes 220 kV

24.08.2006
2.2 Voltage and reactive power 2.2.7 /8

Voltage and reactive power


Voltages at
boundary
nodes 380 kV

24.08.2006
2.2 Voltage and reactive power 2.2.7 /9

Voltage and reactive power


Voltages drops
on 220 kV
boundary lines

24.08.2006
2.2 Voltage and reactive power 2.2.7 /10

Voltage and reactive power


Voltages drops
on 380 kV
boundary lines

24.08.2006

Anda mungkin juga menyukai