SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

I 1 2 3 4 5 6 7 8 9 10 11 II 1, 2 3 4 5 6 7 8 9 III I 1 2 3 4 II 1, 2 3 4 5 6 IV V a) b) c) d) e) f)

SOLAR ARRAYS Installed Capacity Type of SPV module Rating of SPV module PCU(Inverters)

5 MWp - Grid interactive Mono/ Multicrystalline Minimum 200 wp Highly efficient as specified (Section- D) SCADA for diagnosing & monitoring As per latest technology Schematics and layout drawings As specified(As per drawing) Total capacity of modules to be installed 5.25MW (50KW extra for each MW) Array rating HT Transformers Area required Minimum Annual energy generation MOUNTING STRUCTURE Type Material Overall dimensions Design Coating Dip (galvanized)/Anodized Wind speed rating Tilt angle Foundation Number of Module structure Fixing type POWER CONDITIONING UNIT Input Data Max PV power (recommended) DC voltage range Max permissible DC voltage Max permissible DC current Output Data Nominal Ac power Operating grid voltage Utility type Operating frequency grid Voltage ripple PV voltage Efficiency LT INTERFACING PANEL 11KV SWITCHGEAR CUBICLE Normal system voltage Corresponding highest system voltage Frequency N umber of phases Neutral earthing Class indoor/outdoor 250 kw 1.25 MVA and 6.3 MVA 25 acres 8.322 mu(19% CUF)

Ground Mounting-Fixed Type Mild Steel As suitable Hot 150 Km/hr. 15 degree (as required) PCC (1:2:4) Adequate SS 304 fasteners

250 kWp 450 820 V 900 V 591 A 250 kW -20% TO 15% 4 wire 50 Hz +OR 3% < 3% 95 % AND ABOVE As per the Specifications in section D

11kV 12 kV 50 Hz ( + 3%, - 5%) 3 As per requirements outdoor

Page 1 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

g) h)

Rated short circuit withstand of the panels As per requirements Switchgear Free standing, Floor mounted, metal clad, fully compartmentalized draw-out type

Page 2 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

VI a)

11 KV CIRCUIT BREAKER DETAILS SF6 / Vacuum circuit Breaker re-strike free, trip free, stored energy operated and with electrical anti-pumping features Number of poles Rated voltage Rated normal current Rated frequency Rated short circuit breaking current Rated short time Rated Operating Duty Rated insulation level rated/min. power frequency withstand voltage (Rms value)

Draw out type

b) c) d) e) f) g) h) i)

3 12 kV As per system requirements 50 Hz + 3%/-5% As per requirements As per requirement 0-3 min co 3 min - co 28 kV

j) k) l) m) n) o)

p) q) r) s)

Rated lightning impulse withstand voltage 75 kV (peak value) Rated duration 1 second short circuit Rated supply voltage 110 V DC Control supply closing and opening 230 V AC Aux Supply devices & auxiliary circuits out Class indoor/outdoor door type No. of Auxiliary contacts 4No+4NC Contacts Current transformers rated Insulation level i) Rated/min power 28 kV frequency withstand voltage (rms value) ii) Rated lightning 75 kV impulse withstand voltage (peak value) Class of insulation Class E Instrument Safety Factor(ISF) less than 3 Minimum creepage 25 mm/kV of highest system voltage distance C.T. details i) Ratio- Primary : As per requirement (Refer Section-D) -Secondary Class of Accuracy i) Core I ii) Core II Purpose of each core i) Core I ii) Core II Burden i) Core I ii) Core II

t)

1.0 5P20 Metering Protection 30 VA 30 VA

u)

v)

Note: CTs shall be of reputed make with proven experience. REFER SECTION D VII 11 kv ISOLATORS

Page 3 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

Page 4 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

VIII 1

2 3 4 5 6 7 8 9 10 11 12

IX

11 KV POTENTIAL TRANSFORMERS Rated Insulation level. a, Rated/min power 28 kV frequency withstand voltage(rms value) b. Rated lightning 75 kV impulse withstand voltage (peak value) Class of insulation Class E Rated voltage factor 1.2 continuous & 1.9 for 30 seconds Clear height of bushing 370 mm Minimum creepage 25 mm/kV of highest system voltage distance Applicable standard IS: 3156 PT details Rating 11KV/3 / 110V/3 Burden 100 VA Class of Accuracy 1.0/3P Purpose Metering & protection Connection Star/Star Note : i) Potential transformers shall be single phase units. PTs shall be of reputed make with proven experience. ii) Each secondary shall be protected by 3 Amps. HRC fuse. Details of auxiliary supply for operation/control, protection, alarm, indication etc. DC supply - 110Volts +10% / - 15% AC supply 415 Volts + or-10% Three phase 4 wire system

1250 KVA TRANSFORMER Designation step up transformer Installation outdoor Degree of protection as per Rating in KVA Number of Phases Frequency Type of cooling No-load voltage a) HV b) LV Vector group % impedance System voltage Nominal system voltage a) HV b) LV TEMPERATUE RISE Reference ambient Oil by thermometer

1, 2 3 4 5 6 7 8 9 10 11 12

Out door IP 55 IS:2147 1250KVA 3 Phase 50 Hz ONAN 11000V 415V Dyn11 5

11000 V 415V 40 oc o 35 c

1, 2

Page 5 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT 40 oc

SECTION-D DATA SHEETS-A1

Winding by resistance method

Page 6 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

1, 2 3 4 1, 2 3 4 5 6 7

TAP CHANGING GEAR Taps ( Off load) : Required Tappings on windings: HV Total tappings range: 5% Steps 2.50% OTHER FITTINGS REQUIRED FOR 1250 KVA TRANSFORMER Dial type thermometer with two contacts Required for oil tempr. Magnetic oil level gauge with low oil level Required alarm contacts Gas and oil actuated ( i.e. Bucholz ) relay Required Gas sampling device Winding temperature indicator Off circuit tap changing mechanism valves Four plain rollers in place of fixing channels Required Required Required Required

XI 1 1.1 1.2 1.3 1.4 2 2.1 2.2 2.3 2.4 2.5 2.6 3 3.1 3.2

NEUTRAL GROUNDING RESISTOR FOR TRANSFORMERS GENERAL Application / Designation Type & Quantity . Installation Outdoor/Indoor Enclosure RATING Rating KW: Ohmic Value Taps % Rated Current in Amps Duration of rating Voltage Class V Resistor earth, bushing terminal suitable for conductor of Material Size

Neutral Grounding Resistors a. Cast Grid b Wire wound OUTDOOR Tank Type, Weather proof with Aluminium covers As suitable As suitable 50,25 As suitable CONTINUOUS Bidders to specify

GS As suitable

XII

DC BATTERIES 3 sets of 110 VOLTS Batteries each 100 AH capacity of Plante make. Each set conisting of One main and one Stand by Battery bank with 1 nos each of float and boost chargers confirming to standards as detailed in section D.One set to be installed for each inverter room. FIRE FIGHTING EQUIPMENTS: 1 set consisting of following: Co2 cylinder(Big size) 25 Nos.
Page 7 of 21

XIII 1

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT 30 Nos. 20 Nos. 20 Nos. 20 Nos.(for control rooms)

SECTION-D DATA SHEETS-A1

2 3 4 5

Sand buckets Foam type fire extinguishers Dry chemecal powder type extinguishers Smoke sensors

Page 8 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

XIV 1 2

ILLUMINATION SYSTEM: 1 set consisting of following: Solar yard lights along pepiphery on poles70 Nos. sodium vapour lamps Control room, office, Amphitheater, Toilet, Building illumination(24Watts CFL) Quantity as per building design Yard Flood lights

3 4 XV 1 2 3 4 5 6 XVI Sl.No. 1 2 3 4 5 6 7

3 nos 20 Nos.

ODY illumination - Sodium Vapour lamps

SCADA SYSTEM: 1 set consisting of following: Suitable software and adequate database with suitable memory for all parameters 1 set of the plant Computers/ servers of latest version 3 Nos. (Branded make ) with accessories Laser Jet colour Printer-A3 2 Nos Devices for web based communication system As required LAN networking As required UPS As required 6300 KVA, 11/66 KV TRANSFORMER Technical Particulars Type No. of windings No. of Phases System frequency a) Rating of HV winding b) Rating of LV winding a)Low Voltage Winding b)High Voltage Winding a) H.V. Winding b) L.V. Winding c) Neutral Vector Group a) L.V. Terminals : Out door/Step Up Two Three 50 Hz+3%& - 5% 6.3 MVA 6.3 MVA 11 kV 66 kV Star Delta Effectively earthed. YNd11 12 KV Solid Porcelain bushings. Bushings shall be suitable for connecting 11 KV XLPE cables. 72.5 kV OIP condenser type bushing suitable for Lynx ACSR conductor Bushing of suitable rating, solid porcelain type Graded insulation Uniform insulation
Page 9 of 21

8 9

b)H.V. Terminals : c) H.V.Neutral 10 a) High Voltage Winding b) Low Voltage Winding

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

11 12 13

Type of cooling Impedance Voltage at normal tap Insulating Medium

ONAN 8.35% Mineral Oil (as per IEC:60296 and bid specification)

Page 10 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

14 A B C

Tap changing gear Details Type Tapping range as % of off load Rated KVA No. of tapping

OCTC on HV side +/- 5 % (5 Steps of 2.5% each tap) 5 Steps of 2.5% (including normal)

XVII Sl. No. 1 2 3 4 5 6 7

200 KVA, 11/0.440 KV AUXILIARY TRANSFORMER Technical Particulars Type No. of windings No. of Phases System frequency Rating a) HV Voltage b) LV Voltage a) HV Winding b) LV Winding c) Neutral Vector Group Type of cooling Impedance Voltage at normal tap Tap changing gear Type Tapping range as % of off load Rated KVA Power frequency withstand voltage for 1 minute For HV winding For LV winding Rated lightning impulse withstand voltage for 1.2/50 microsecond For HV winding For LV winding Insulation Class The maximum permissible temperature rise over maximum ambient temperature of 40oC Winding (measured by resistance method) Core, metallic parts and adjacent materials Indoor/ Outdoor/Step-down Two Three 50 Hz+3%& - 5% 200KVA 11kV 0.440kV Delta Star Effectively earthed Dyn11 AN 4.50% Off circuit -5% to +5% in steps of 2.5%

8 9 10 11 a) b) 12

28kV rms 3kV rms

13

14 15

75kV peak NA F

a) b)

90C The temperature shall in no case reach a value that will damage the core itself, other parts or adjacent materials

16

Terminal connections HV terminals

HV terminals shall be suitable for 11 kV bus

Page 11 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

LV terminals 17 18 19

The LV terminals shall be suitable for PVC / XLPE cables Insulation grading HV & LV winding shall be uniformly insulated Ability to withstand short circuit & duration According to IS 2026/ IS:11171 of short circuit Overloads According to IEC:60905

Page 12 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

XVIII Sl. No. 1 2 3 4 5 6

66 KV POTENTIAL TRANSFORMER Technical Particulars Rated voltage Rated frequency Accuracy class of Winding Voltage ratio Grade of oil Maximum phase angle error with 25% and 110% of rated burden at 0.8 p.f. lagging at any voltage between 80% and 120% Temperature rise at 1-1 times rated voltage with rated burden (OC) Rated voltage factor & time (based on system studies) Insulation Level (based on system insulation coordination)

72.5 kV 50 c/s as required 66 kV/3/110V/3 As per IS: 335 40 min.

7 8 9

As per IS: 3156 Continuous 1.2 ; 30 seconds-1.5 i) 1 minute power frequency (wet/dry) : 140 kV r.m.s. withstand test voltage (As per IS: 3156) ii) 1.2/50 micro seconds impulse wave : 325 kV (Peak) withstand test voltage

10

One minute power frequency withstand 2 kV test voltage on secondaries Minimum creepage distance of bushings 1815 mm

11

XIX 1 2 3 4 5 6 7 9 10 11 12 13 14 15 16

66 kV CIRCUIT BREAKER Number of poles Class Nominal System Voltage Rated Voltage Rated Insulation Level Rated Frequency Rated normal current Rated Cable Charging breaking current Rated S.C. breaking current First pole to clear factor S.C. making current Rated Operating Sequence Duration of short circuit Rated out of phase breaking current Automatic rapid re closing 3 Out Door Type 66 kV 72.5 kV 350 kV(peak) 50 Hz 1600 Amps. 140 Amps 31.5 kA 1.5 79 kAP O-0.3sec-CO-3min.-CO 3 sec. 7.9 kAmps 3 Ph.

Page 13 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

17

Total break time for any current up to the < 60 ms rated breaking current with limiting conditions of operating coil voltage, operating &quenching media pressures. No. of auxiliary contacts for purchasers 10 NO & 10 NC on each pole use System neutral earthing Effectively earthed

18 19

Page 14 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT <150 ms <50 ms 110 V+/-10% DC <=25 micro sec. 1815 mm

SECTION-D DATA SHEETS-A1

20 21 22 23 24

25

Closing time(max.) Opening time(max.) Trip & Closing coil Voltage Arcing time Creepage distance (min.) 1.2/50 micro sec. lightning impulse withstand voltage. i) to earth ii)across the open circuit voltage applied to one terminal Power frequency withstand voltage i) to earth ii) across terminals of open circuit breaker Type of operation Rated values of transient recovery voltage for terminal faults Rated values of transient recovery voltage for short line faults Rated characteristics for out of phase breaking current Small inductive current interrupting capacity Rated terminal load Difference in the instants of closing/opening of contacts at rated voltage and rated operating and quenching media pressure. i) with in a pole ii) between poles Insulation level of bushings i) 1 min. p.f. withstand voltage ii) 1.2 X 50 micro sec lightning impulse with standing voltage Partial discharge level Controls of switching surges Noise level of equipment Auxiliary power supply

325 kV(peak) 325 kV(peak)

140 kV (rms) 140 kV (rms) Spring As per IEC:56 (Latest edition) As per IEC:62271 - 100 As per IEC:62271 - 100 Any value from 0.5-10 Amps. Without switching over voltage exceeding 2.5 p.u. 100 Kg static

26 27 28 29 30

31 32

< 3.33 ms < 5 ms 140kV(rms) 325 kV(peak) As per IEC:62271 - 100 The switching surge voltage while energizing to be limited to 2.3p. u. < 140 dB 415V+/-10%,3ph,50Hz+/-5%,AC 240V+/-10%,1ph,50Hz+/-5%,AC 110V +/-10% DC

33

34 35 36 37

XX 1 2

66 KV ISOLATOR Rated voltage Nominal System voltage 72.5 kV 66 kV

Page 15 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT 50 Hz Effectively earthed Out door Horizontal double break 3

SECTION-D DATA SHEETS-A1

3 4 5 6 7

Rated frequency System neutral earthing Installation Type of disconnect Number of poles

Page 16 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT 1600 Amps

SECTION-D DATA SHEETS-A1

8 9

10 11

12

13

14 15

Rated normal current Rated short time with-stand current (KA rms) a) For 1 sec b) For 3 sec Rated peak withstand current for both main and earth switch (KA) peak Rated insulation level 1.2/50 micro second lightning impulse withstand voltage (kV) peak a)between live parts and ground b)across the open terminal of the same phase One minute dry/wet power frequency withstand voltage for complete assembled isolator /isolator cum earthing switch. a) against ground (kV) rms b) across terminals of open isolator (kV) rms Minimum clearance in open air (mm) a) Between phases b) Live parts and ground Rated magnetizing current/ capacitive current make/break capacity Rated mechanical terminal load a) Straight load (KGS) b) Across load (KGS) Operating mechanism Operating time Particulars of insulators a)Creepage distance (mm) i)Total ii) Protected b)Dielectric strength

31.5 31.5 78.75

325 (kV)peak 375 (kV) peak

140 160

1000 700 0.5 Amps

16 17 18

51 17.33 Motor operated 10 12 sec

1815 At least 50% of total Creepage distance

19

wet : 140 dry : 160 i)Minimum one minute power frequency 325 withstand voltage (kV)rms No. of auxiliary switch contacts 10 nos. each (NO , NC ) 66 KV CURRENT TRANSFORMER Particulars Nominal system voltage Rated Voltage Rated frequency System neutral earthing

XXI Sl. No. 1 2 3 4

66 KV 72.5 KV 50 Hz Effectively earthed


Page 17 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT Out door 31.5 KA

SECTION-D DATA SHEETS-A1

5 6

Installation Rated short circuit current

Page 18 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

8 1 2 3 4 5 6 7 8 9 10 11

Rated insulation level i)Impulse With stand voltage ii)1 minute power frequency withstand voltage Cont. Current Rating Description Ratio Rated primary current Rated sec. current Purpose Adopted ratio Accuracy Class Rating of VA burden Min Knee point voltage RCT @ 75 deg cen ISF Excitation current

350 KVP 160 KV rms 120% of rated primary current Core 1 Core -2 Core 3 150-100-75-50/1 50 50 50 1 1 1 Protection Protection Metering 75/1 75/1 75/1 5P20 PS 0.2 20 20

<10 30 mA@Vk/4

XXII Sl. No. 1 2 3 4 5 6 7 8 9 10 11

60 KV LIGHTNING ARRESTERS Particulars Type Rated voltage Nominal system voltage Highest system voltage Nominal discharge current Maximum current through arresters at operating voltage Maximum continuos operating voltage Steep current impulse residual voltage Long duration discharge class One minute wet power frequency withstand Voltage of arresters housing Rated insulation level i)Impulse With stand voltage ii)1 minute power frequency withstand voltage of arrester housing Pressure relief device High current short duration test value Single impulse energy capability Creepage distance of arrester housing(minimum) Details Gap less metal oxide Out door type. 60 kV rms. 66 kV rms. 72.5 kV rms. 10 KA peak 20 ma 51 kV rms. 190 kV peak 3 160 kV rms.

350 KVP 160 KV rms Class A 100 KA peak 4.5 kJ per KV 1815 mm.

12 13 14 15

Page 19 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

XXIII Sl. No 1 2

ACSR conductor Code Name Complet dia of the conductor Stranding in mm Aluminium Number Dia of Each Steel Number Dia of each strand Minimum ultimate tensile strength (kG) Greasing required Yes/No SYSTEM DATA Voltage (kV) No. of Phases & Frequency (Hz) Ambient Temp.(oC) : Continuous Current Of the conductor Short Time Current per Sub-Conductor Seconds 10KW System- One set shall consist of PV Modules Inverter- power rating 10KW Battery Bank- 12 Volts, 150 AH,20 cells Charge Controller ACSR Lynx 19.53

30 2.79 7 2.79 7945 NO 110 3 50 50 475 31.5 1

XXIV 1 2 3 4

Required Nos. 1 Nos 1 set 1 Nos.

XXV

ESSENTIAL SPARES : 1 set shall consist of following items and during 3 year O&M period any additional spare required shall be supplied with no extra cost. PV Modules Solar PV Modules of 230W capacity Junction Boxes Terminal Boxes Power Conditioning Unit Main Unit AFC 500-48 Main Contactor Power supply unit Axial ventilator Rotary operating mechanism Over voltage protection PV Fuses

A 1 2 3 B 1 2 3 4 5 6 7

125 Nos. 5 Nos. 120 Nos.

3 Nos. 3 Nos. 3 Nos. 3 Nos. 3 Nos. 3 Nos. 25 Nos.

Page 20 of 21

CE(GSW)/SPV/BELAKAVADI

SOLAR PV POWER PLANT

SECTION-D DATA SHEETS-A1

C 1 2 3 4 5 6 7 8 9 10 11 12 D 1 2 3 4 5

6300 MVA Transformer HV Bushing. Neutral bushing. LV cable box complete with bushingGaskets Silical gel breather Buchholz relay MOG WTI with repeater OTI NCT Contacts of OFF circuit tap switch Pressure relief device

1set of 3 Nos.(One for each phase) 1 No. 1 set 1 set 1 No. 1 No. 1 No. 1 No. 1 No. 1 No. 2 Set (Both fixed and moving contacts suitable one phase) 1 No.

6 E 1 2 3 4 5 6 F 1 2 3 4 5 6 7 8

Breaker Spare pole with operating mechanism 1 No. Closing coil 4 Nos Tripping coil 4 Nos Spring charging motor for spring charging 1 No. mechanism Gaskets & o ring for one set of 3 pole 1 set breaker Gas filling unit comprising regulator with manometer and necessary coupling hose 1 No. for filling of SF6 gas Isolator Fixed contact assembly Moving contact blade Closing contactor Opening contactor Operating motor Solid core insulators

6 Nos. (1 set) 3 Nos. 2 Nos. 2 Nos. 1 No 9Stacks(1set)

Control and Protection panel Numerical integrated multifunctional 1 No. Transformer protection relay Numerical O/C & E/F transformer 1 No. protection relay Numerical E/F transformer protection 1 No. relay High speed trip relay 1 No. Breaker trip coil supervision relay 1 set High speed trip relay coil supervision 1 set relay Auxiliary relay 1 each type Contact multiplication relay for Breaker 1 each type and Isolator