Anda di halaman 1dari 18

Introduction

Designers and installers of anchors face an unlimited variety of anchoring products. This guide provides an overview of the Hilti anchors available for this market and all design data relevant to our anchoring products. It is intended to make users work easier by providing a quick reference to solve fastening problems on site. The guidet includes an anchor selection chart where anchors are grouped depending on the method of transferring load into concrete. They are mechanical anchors and chemical or adhesive anchors. Two additional groups complete the range:light duty anchors and insulation fasteners.

The design data shown in this guide is the factored characteristic load of the fastener or Design Resistance to be compared with your factored load or Design Load. Design data is not included for light duty anchors or insulation fasteners. If you have any questions about this guide or any other technical enquiry, please contact Hilti Technical Advisory Service on GB - 0161 886 1144 / IRL - 01 886 4113 or visit the Tech Centre in our website www.hilti.co.uk / www.hilti.ie.

Design approach

Anchor design requires careful consideration of both the required loading capacity and the required safety of the anchorage. The safety aspect is taken care by the use of safety factors. Your factored load (or Design load) must not exceed the factored characteristic load of the fastener (or Design resistance) for a successful anchor design. Design load < Design resistance Design load = Working load x F The design resistance is the holding power of a fixing. Hilti establishes it by carrying out extensive anchor testing in accordance with recognised standards and building codes. We are therefore able to predict the performance of our fixings into concrete.

Design resistance = Characteristic value of resistance / M F and M are partial safety factors which allow for the uncertainty of the applied loads and inaccuracies when defining limiting conditions. Greater degrees of safety can be associated with critical parts of design. These are usually specified in standards and codes of practice.

Factors influencing action and resistance:


Both the direction and magnitude of an applied load can vary. In fixing design, the following terms are generally accepted: Load direction: A tensile load, N is a load acting in a direction that is axial with the anchor. A shear load, V is a load applied transversely to the anchor rod. A combined load, F is a load, which includes both tensile and shear components. The resistance of the anchor results from a combination of the properties of the base material and the anchor itself. Some of these are: Anchor spacing (s) The spacing is the distance from one anchor to another. If the spacings are small, the load capacity of the anchor decreases. Edge distance (c) If an anchor is placed close to an edge then the edge can cut into its zone of influence. This results in a reduction of the load capacity. Thickness of the structural components (h) If the thickness of the structural component is not adequate then the loading capacity of the anchorage will be reduced. The minimum reinforced base material thickness, h, is published for each product in this guide. Base material (fb) The holding power of an anchor is dependent on the integrity and strength of the base material. Within limits the stronger the base material the higher will be the failure load of the anchor. The loads stated under each anchor in this guide are for non cracked concrete of compressive strength fck,cube = 30 N/mm2.
N: tensile resistance V: shear resistance c: edge distance s: spacing between anchors h: concrete thickness fck,cube concrete compressive strength: 30 N/mm2

Please note that in order to use the data in this guide, minimum conditions for h and c must be met. Otherwise, consult Hilti Technical Advisory Service on 0161 886 1144.

Chemical anchors
HIT HY 150 Injection Adhesive
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size Tension HIT-HY 150 + HAS rod


M8 M10 M12 M16 M20 M24 M8 M10 M12 M16 M20 8 10 12 14 16 20 25 7.4 9.9 14.8 18.9 32.1 40.1 10.2 15.2 19.3 33.3 39.9 6.2 8.7 12.3 15.9 19.5 26.0 32.4

Shear
7.9 12.6 18.3 34.6 54.0 77.8 14.1 22.3 32.4 60.3 94.1 9.2 14.4 20.8 28.3 37.0 57.8 90.2

Edge c
235 365 425 850 855 1005 270 345 460 660 890 285 305 405 450 785 830 950

Spacing s
160 180 220 250 340 420 240 300 340 460 560 160 180 220 250 290 340 420

Edge c min
40 45 55 65 90 110 45 55 65 90 110 40 45 55 65 65 90 110

Spacing s min
40 45 55 65 90 120 45 55 65 90 110 40 45 55 65 65 90 120

h
80 90 110 125 170 210 120 150 170 230 280 120 120 140 170 180 220 270
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

HIT HY 150 + HIS-N


3

HIT HY 150 + rebar (Anchor Theory - existing reinforcement is not being considered)
4

Chemical anchors
HIT RE 500 Injection Adhesive
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size Tension HIT RE 500 + rebar


8 10 12 14 16 20 25 28 32 36 40 11.9 16.9 24.7 32.8 37.5 63.7 98.3 123.5 145.2 165.5 185.5

Shear
11.1 17.3 24.9 33.9 44.3 69.3 108.0 135.3 176.7 237.3 276.4

Edge c
455 405 535 595 820 960 1245 1155 1365 1800 1875

Spacing s
160 180 220 250 250 340 420 540 600 660 720

Edge c min
40 45 55 65 65 85 105 135 150 165 180

Spacing s min
40 45 55 65 65 90 120 140 160 180 180

h
100 120 140 170 170 220 270 340 380 410 450
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

HIT-HY150 HIT -RE 500

Chemical anchors
HVU Adhesive Anchor
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size Tension HVU + HAS rods


M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39 M8 M10 M12 M16 M20 10.9 14.7 21.0 30.7 55.6 80.2 98.1 128.9 151.3 180.0 206.2 19.5 30.9 41.0 74.5 105.1

Shear
7.9 12.6 18.3 34.6 54.0 77.8 164.0 199.3 248.4 291.5 350.6 8.8 13.9 20.2 37.7 58.8

Edge c
185 275 335 645 670 790 1840 1925 2190 2375 2665 90 110 140 180 210

Spacing s
160 180 220 250 340 420 480 540 600 660 720 180 220 250 340 410

Edge c min
40 45 55 65 85 105 120 135 150 165 180 45 55 65 90 110

Spacing s min
40 45 55 65 85 105 120 135 150 165 180 45 55 65 90 110

h
100 120 140 170 220 270 300 340 380 410 450 120 150 170 230 280
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

HVU + HIS-N rods

Chemical anchors
HVZ Adhesive Anchor
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size Tension HVZ + HAS-TZ anchor rod


M10 M12 M16 M16L M20 9.8 19.0 27.3 35.6 53.0

Shear
14.9 21.6 40.2 40.2 62.7

Edge c
290 320 640 485 645

Spacing s
225 285 315 375 510

Edge c min
60 75 85 85 135

Spacing s min
60 75 85 85 135

h
150 190 210 250 340
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

HVU / HVZ

Metal anchors
HLC Sleeve Anchor and
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size Tension HLC Sleeve Anchor


M5 M6 M8 M10 M12 M16 0.7 1.4 2.1 2.8 4.2 5.6

Shear
1.1 2.5 4.5 7.3 8.8 10.5

Edge c
30 42 48 57 72 83

Spacing s
60 84 96 114 144 165

Edge c min
30 42 48 57 72 83

Spacing s min
60 84 96 114 144 165

h
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

60 70 80 90 100 120

HB Bolt Anchor
HB Hilti Bolt
M6 M8 M10 M12 M16 3.9 6.2 8.5 15.1 21.1 2.9 5.5 10.8 14.6 27.6 175 192 227 297 367 175 192 227 297 367 50 55 65 85 105 50 55 65 85 105 100 110 140 170 200
4 3

NOTE For brickwork and masonry, specific performance data cannot be assured owing to the wide diversity and variety of these materials. Contact Hilti Technical Advisory Service for guide values.

Metal anchors
HKD Flush Anchor
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size Tension HKD Flush Anchor


M6 x 25 M6 x 30 M8 x 30 M8 x 40 M10 x 30 M10 x 40 M12 M16 M20 3.4 3.4 5.3 5.3 5.3 7.0 11.9 16.1 22.4

Shear
2.8 2.8 4.5 4.5 5.6 6.2 11.3 18.1 27.3

Edge c
90 90 105 105 140 140 175 230 280

Spacing s
100 100 105 105 140 140 175 230 280

Edge c min
90 90 105 105 140 140 175 230 280

Spacing s min
50 50 60 60 60 80 100 130 160

h
100 100 100 100 100 100 120 140 180
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

HLC / HB / HKD

Metal anchors
HSA Stud Anchor
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size Tension Deep Embedement


M6 M8 M10 M12 M16 M20 M6 M8 M10 M12 M16 M20 3.9 6.1 6.1 10.9 21.3 30.5 1.6 5.0 5.6 6.3 11.1 16.7

Shear
3.6 6.5 9.9 14.2 26.5 41.5 3.6 6.5 9.9 14.2 26.5 41.5

Edge c
100 205 330 315 520 655 85 235 360 505 740 955

Spacing s
120 144 150 210 252 309 100 105 126 150 192 234

Edge c min
50 60 65 90 105 125 40 45 65 100 100 115

Spacing s min
40 50 55 75 90 105 35 35 55 100 100 100

h
100 100 100 140 170 210 100 100 100 100 130 160
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

Shallow Embedement
3

Metal anchors
HUS-H Screw Anchor and
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size Tension HUS-H Screw Anchor


10.5 (60) 10.5 (50) 12.5 (70) 12.5 (60) 5.2 3.9 6.8 5.6

Shear
10.3 10.3 14.4 14.4

Edge c
320 375 380 480

Spacing s
125 105 140 125

Edge c min
55 55 65 65

Spacing s min
55 55 65 65

h
110 100 130 110
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

HST Stud Anchor


HST Stud Anchor
M8 M10 M12 M16 M20 M24 6.1 7.6 11.1 17.2 25.2 33.3 7.5 11.7 17.0 26.3 41.4 61.8 255 330 420 555 705 845 138 174 204 246 303 375 55 65 75 110 140 170 115 155 170 215 270 295 100 120 140 160 200 250
3

HSA / HUS-H / HST

Metal anchors
HSC Safety Anchor
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size HSC-A
M8/40 M8/50 M10/40 M12/60

Tension
8.6 12.1 8.6 15.8 8.6 8.6 12.1 17.3 15.8

Shear
11.0 11.0 17.4 25.2 6.1 8.5 10.4 10.4 12.3

Edge c
140 160 160 180 140 140 160 180 180

Spacing s
140 160 160 180 140 140 160 180 180

Edge c min
40 50 40 60 40 40 50 60 60

Spacing s min
40 50 40 60 40 40 50 60 60

h
80 100 80 120 80 80 100 100 120
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

HSC-I
M6/40 M8/40 M10/50 M10/60 M12/60

Metal anchors
HSL Heavy Duty Anchor
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size HSL
M8 M10 M12 M16 M20 M24

Tension
9.6 14.5 20.9 35.8 48.3 63.5 11.5 16.9 23.3 38.9 52.2 71.1

Shear
13.7 23.3 34.2 59.4 81.8 106.9 13.3 21.1 31.4 57.1 76.4 112.5

Edge c
162 187 200 265 325 390 175 200 250 300 390 390

Spacing s
195 225 240 315 395 470 180 200 250 300 380 470

Edge c min
65 75 80 105 130 155 70 80 95 115 145 250

Spacing s min
65 75 80 105 130 155 65 75 85 100 130 155

h
120 140 160 180 220 270 120 140 160 180 220 270
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

HSL-TZ
M8 M10 M12 M16 M20 M24
3

HSC / HSL / HSL-TZ

Metal anchors
HDA Design Anchor
Design Resistance1 (kN) Optimum Distance2 (mm)
(No influence on design resistance)

Load data applies for concrete compressive strength 2 Fck, cube = 30 N / mm

Minimum Distance3 (mm)


(Apply reduction factor to design resistance)

Concrete thickness4 (mm)

Size Tension HDA-P (Pre fix)


M10 M12 M16 M20 M10 M12 M16 M20 30.7 44.7 84.0 127.6 30.7 44.7 84.0 127.6

Shear
17.6 24.0 49.6 78.4 43.3 53.3 93.3 140.0

Edge c
205 205 325 575 855 790 975 1470

Spacing s
300 375 570 750 300 375 570 750

Edge c min
80 100 150 200 80 100 150 200

Spacing s min
100 125 190 250 100 125 190 250

h
200 250 380 380 200 250 380 380
2

Factored characteristic load of the fastener (Design Resistance) to be compared with your factored load (Design Load). Optimum edge and spacing distances quoted in the table opposite are the allowable for the design resistance to apply. These are the dimensions required for a pair of anchors to achieve the loads in this table. If conditions are different, appropriate reduction factors must be applied. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) - 01 886 4113. Minimum edge and spacing distances quoted in the table opposite are the minimum allowable. If this distance is required, the resistance from the anchor is affected by reduction factors. Contact Hilti Technical Advisory Service on (GB) - 0161 886 1144 (IRL) 01 886 4113. Concrete thickness applies for both minimum and optimum conditions.

HDA-T (Through fix)

Best value for you

For more detailed technical literature and calculation software visit our website www.hilti.co.uk or call 0800 886 100

HDA / HDA-T

How to change specifications safely


HBS MCA 31 Clause 200 Where the specification by the use of the words or equivalent, permits substitution of a product of different manufacture to that specified and such substitution is desired, before ordering the product submit for approval documentary evidence that the alternative product is equivalent in respect of...

Material
Does the anchor have the same corrosion resistance properties? Have you carefully considered the environment in which the anchor is to be used? Have you considered the material of the part fastened for dissimilar materials? Is the resin styrene free, not a polyester and does it have a suitable curing time? Does the resin anchor have a durable foil capsule? Is the anchor a suitable grade of steel? 5.8 or 8.8? Has the anchor been designed taking into account fire requirements? Is the anchor cold formed making it more ductile and durable?

Safety
Has the anchor been designed taking into account load type and direction? Has the anchor been designed taking into account load edge distance? Has the anchor been designed taking into account load spacing between fixings? Has the anchor been designed taking into account load concrete strength? Has the anchor been designed taking into account load depth of embedment? Has the anchor been designed taking into account load thickness of the component fastened? Has the anchor been designed taking into account service temperature? Is the anchor suitable for the existing base material? Hard/soft/hollow?

Reliability
Has the anchor been tested and is the test data available/accurate? Is the anchor suitable for dynamic loads? Fatigue/shock/seismic? Does the anchor have the necessary approvals/ETAs/CE markings? Have you considered the ease of setting of the anchor to avoid poor workmanship? Does the anchor reliability pull down the part fastened? Does the fixing tighten up without rotating? Can the manufacturer of this anchor provide site support and testing?

Is the anchor suitable for the tensile zone/ cracked concrete? Is the anchor pre-assembled saving time?

Appearance
Does the anchor have a suitable head type? Countersunk/Torx/Hexagon? Does the anchor have a head marking for identification after setting? Will the anchor discolour over time through lack of corrosion resistance?

Fitness for purpose


Is a through fastening required? Is the anchor externally/internally threaded? Is the anchor suitable to accommodate shear loads? Can the anchor be used in diamond drilled holes or wet holes?

Unless you are confident that all the above questions have been considered and where relevant, answered in the affirmative, you can not reliably and safely change the specification. Should you require assistance please call Hilti Technical Advisory Services on 0161 886 1144.
Changing specifications Safely

Facsimile Message
To:

Hilti (Gt. Britain) Ltd Technical Advisory Service

Date: Fax No of Pages: Our Fax No. / email:

0161 877 7393

From: Company:

DETAILS / NATURE OF ENQUIRY / SKETCH


(For anchor enquiries please include design loads, direction and nature of loads and limiting factors such as edge distance, anchor spacing, thickness of base material and concrete strength.)

[Please photocopy this page as a template for your enquiry.]

Anda mungkin juga menyukai