Annexure M/s SAIL-BSP- Lime and Dolomite Calcination Plant- Drawings/documents of M/s SPCL/Maerz/- Instrumentation.

Observations pertaining to instrumentation on the drawings/ documents are as follows: A. I. A ! Datas"eet of Pressure #educing Station for $itrogen S%stem &P#S-'( P!ID of Pressure #educing Station &P#S-'( &drg.no.BSP-SPCL-)*-)+,-'+--),-')D.-)+/*//A+/'0 #-'((

1. Profibus PA communication envisaged in this package and the same is not indicated the P&I diagram. Proper s mbol identification shall be provided. !. "ontrol room displa shall be corrected inline with the same followed in other main P&I#$s. II. A-P#S-' &drg.no.BSP-SPCL-)*-)+,-'+--),-')-D.-)+/*//A+/+0 #-'(

1. %ag no. of down stream pressure gauge not matching with that indicated in the P&I#. Please check & correct. !. &ake of the pressure transmitter indicated in the 'A drawing is not matching with datasheet. &/s (P") shall check and correct. *. &/s (P") shall ensure correctness of the details shown in the drawing. III. Pneumaticall% o1erated t%1e control 2al2e &drg.no.BSP-SPCL-)*-+,-'+--),-')D.-)+/*//A+/30 #-'( 1. +rom the submitted datasheets & catalogs, selection basis of control valve is not clear. %hrust calculations of valve shall be submitted as part of si-ing calculation. %his shall also include necessar tables for selection of corresponding actuators highlighting the actuator model selected. !. (tem travel at selected "v is not clear from the submitted. Please furnish proper valve characteristics curve wherein stem travel at selected "v has been indicated. *. "onsidering high pressure drop, valve steliting shall be done & rating shall be indicated. .. /alve t pe/ series indicated as 3+/' in the calculation sheet, whereas in the datasheet 0sl. no. +)1 this is indicated as 34*3. 2. #etails like inlet pressure, temperature, dp shutoff, percentage opening, bod si-e, port si-e, t pe of bonnet, trim material, and plug material shall be indicated in the datasheet. 3. Against an re4uirement of outlet pressure of ! 5g/ cm!, valve has been designed with outlet pressure of * kg/ cm!. "orrectness of the same shall be ensured b &/s (P")/ 6. (eat material indicated in the datasheet 7 (oft (eat8 whereas in the 'A drawing this is indicated as (( *13). Please check & correct. 9. :and wheel shall be provided for control valve operating and the details of the same shall be indicated at sl.no... of the datasheet. ;. Actuator model number shall be indicated in the datasheet.

Page 1 of 4

1<. +or positioner, aluminum enclosure shall be considered and accordingl the 6 th digit of model code shall be corrected. 11. Position transmitter is indicated as 7%es8 in the datasheet. %he same shall be clarified b &/s (P"). 1!. =hile airfilter regulator has been selected with . 5g/ cm! output, positioned re4uirement has been indicated as 3 5g/ cm!. Please check & correct. 1*. Positioner model indicated in the datasheet not matching with that indicated in the 'A drawing. Please check & correct. 1.. &/s (P")/ %herma> shall ensure that details indicated in the datasheet matches with supporting documents like calculation sheet, 'A drawings, etc. 12. "orrectness of valve characteristics selected for respective application shall be ensured b &/s (P")/ %herma>. 13. %he datasheet is stamped as 7Commented8. I/. Datas"eet for Pressure gauge&drg.no.BSP-SPCL-)*-)+,-'+--),-')-D.-)+/*// A+//0 #-'( 1. %hree wa gauge cock shall be provided. !. +or tag no PI?9;1, range shall be preferabl 7)-+- 5g/cm+8 instead of 7)-3+ 5g/cm+8. Please check & correct. *. #etail model no. shall be indicated in the datasheet. .. %he datasheet is stamped as 7Commented8 /. 1. !. *. .. 2. 3. B. I. Datas"eet for Pressure 6ransmitter&drg.no.BSP-SPCL-)*-)+,-'+--),-')-D.)+/*//A+//0 #-'( (tatic pressure limit shall be corrected at s.no.!* of the datasheet. (urge protection/ lightning protection indicated as 7$o8 at sl.no. *1 &*! of the datasheet. %he same shall be provided and the details like make, model number shall be indicated. Instrumentation range shall be indicated in the datasheet. @ote * & . indicated in the datasheet shall be removed. "orrectness of installation code selected a 7;8 shall be ensured b &/s (P"l/%herma> w.r.t pipeline orientation. %he datasheet is stamped as 7Commented8 A ! Datas"eet of Pressure #educing Station for $itrogen S%stem &P#S-+( P!ID of Pressure #educing Station &P#S-+( &drg.no.BSP-SPCL-)*-)+,-'+--)7-')D.-)+/*//B+/'0 #-'(8 @o observations pertaining to instrumentation. A-P#S-+ &drg.no.BSP-SPCL-)*-)+,-'+--)7-')-D.-)+/*//B+/+0 #-'(8 &/s (P") shall ensure correctness of the details shown in the drawing.

II.

III. Datas"eet for Pressure gauge&drg.no.BSP-SPCL-)*-)+,-'+--)7-')-D.-)+/*// B+/30 #-'( 1. %hree wa gauge cock shall be provided. !. +or tag no PI?9;< & 96;, range shall be preferabl 7 )-+- 5g/cm+8 & 7 )-') 5g/cm+ 7 respectivel instead of 7)-3+ 5g/cm+8 & 7 )-'+ 5g/cm+8. Please check & correct. *. #etail model no. shall be indicated in the datasheet. .. %he datasheet is stamped as 7Commented8.

Page 2 of 4

C. I.

A ! Datas"eet of Pressure #educing Station for Steam S%stem &P#S-3( P!ID of Pressure #educing Station &P#S-3( &drg.no.BSP-SPCL-)*-)+,-'+--')-'*D.-)+-)-/B/'0 #-'(

1. Profibus PA communication envisaged in this package and the same is not clear from the P&I diagram. Proper s mbol identification shall be provided. !. "ontrol room displa shall be corrected inline with the same followed in other main P&I#$s. II. A-P#S-3 &drg.no.BSP-SPCL-)*-)+,-'+--')-'*-D.-)+-)-/B/+0 #-'(

1. &ake of the pressure transmitter indicated in the 'A drawing is not matching with datasheet. &/s (P") shall check and correct. !. &/s (P") shall ensure correctness of the details shown in the drawing. III. Pneumaticall% o1erated t%1e control 2al2e &drg.no.BSP-SPCL-)*-+,-'+--')-'+D.-)+-)*/B/30 #-'(8 1. It is noted that flange rating indicated as 7 A@(I A13.2 class B *<<8 in the datasheet whereas in the si-ing !. Aonnet shall be e>tended and same shall be indicated in the datasheet. *. +or other comments refer point no. A?III?1 ?12 0as applicable1. I/. Datas"eet for Pressure gauge&drg.no.BSP-SPCL-)*-)+,-'+--')-'*-D.-)+-)-/ B//0 #-'( 1. %hree wa gauge cock shall be provided. !. All fittings including siphon shall be IAC certified. *. #etail model no. shall be indicated in the datasheet. .. %he datasheet is stamped as 7Commented8. /. 1. !. *. .. 2. 3. Datas"eet for Pressure 6ransmitter&drg.no.BSP-SPCL-)*-)+,-'+--')-'+-D.)+-)-/B//0 #-'( (tatic pressure limit shall be corrected at s.no.!* of the datasheet. (urge protection/ lightning protection indicated as 7$o8 at sl.no. *1 &*! of the datasheet. %he same shall be provided and the details like make, model number shall be indicated. Instrumentation range shall be indicated in the datasheet. @ote * & . indicated in the datasheet shall be removed. "orrectness of installation code selected a 7;8 shall be ensured b &/s (P"l/%herma> w.r.t pipeline orientation. %he datasheet is stamped as 7Commented8.

/I. Datas"eet for 6em1erature gauge&drg.no.BSP-SPCL-)*-)+,-'+--')-'*-D.-)+-)-/ B/*0 #-'( 1. #etails like stem diameter, stem material, pointer, IP class shall be indicated in the datasheet. !. #etail model no. shall be indicated in the datasheet. *. "orresponding to each tag numbers, stem length, insertion length, e>tension length, and line si-e shall be indicated in the datasheet.

Page 3 of 4

.. %hermowell material shall be corrected as 7 SS3'*8 instead of 7SS3)/8 2. Dnder thermowell details like process connection, bore diameter, t pe of head, head diameter, shall also be indicated in the datasheet. 3. %hermowell model number, if an , shall be indicated in the datasheet. 6. IAC certification shall be provided for the thermowell and same shall be indicated in the datasheet.. 9. 'A drawing of temperature gauge & thermowell shall be submitted. ;. %he datasheet is stamped as 7Commented8.