Anda di halaman 1dari 4

Diesel Generator Sets 250KVA

Powered by Cummins Engines

Ratings
Output Ratings 380V-415V Voltage
Ratings at 0.8 power factor 1) 2) 3) Ambient reference conditions: 1,000 mbar, 27 , 30% relative humidity; Standby Power Standby duty, operation under variable load, without over load; Prime Power-Continuous duty operation, under variable load 24/24h-10% over load permissible 1 hour/12 hours;

Prime Power 250kVA / 200kW 348A-380A 601A-656A 694A-760A

Standby Power 275kVA / 220kW

220V-240V 190V-208V

Performance Data
Engine Brand & Model Alternator Brand & Model Control System Standard Noise Level@7m (Soundproof Sets) Circuit Breaker Type Frequency & Phase Engine Speed (RPM) Tank (L) Open Sets Soundproof Sets 100% Load Fuel Consumption (l/hr) 75% Load 50% Load 25% Load Cummins & NT855-GA Stamford & UCDI274K DSE7220 / DSE8610 80 dBA 3 Pole MCCB 50Hz & 3PH 1500 315 465 54 / / /

Dimensions and Weights


Content L Dimensions: (mm) Weights (kg) W H Open Sets 3000 1120 1650 2800 Soundproof Sets 3900 1400 2000 3400

Engine Brand / Model : Cummins / NT855-GA


Typical Engine Data
No. of Cylinders / Alignment Cycle Bore / Stroke Induction Cooling Method Lubricant Oil 6 / In Line 4 Stroke 140 mm / 152 mm TCA Water 15W40-CF4 Upgrade Gross Engine Power Compression Ratio Displacement (L) Governing Type Net weight (kg) Prime Standby 205 225 15:1 14
Electronic

1270

Exhaust system
Standard Exhaust Pipe Diameter (mm) 127

Air induction system


Minimum Dirt Holding Capacity ( g/L/s ) Maximum Allowable Intake Air Temperature (!C) 53 17

Lubrication system
Oil pressure Idle Speed (kPa) ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... Governed speed (kPa) ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... Maximum Allowable Oil Temperature (!C) Maximum Oil Consumption (L/h) Oil Pan Capacity - Low / High (L) Total System Capacity (L) 103 241-345 ..121 . 0.24 ..28.4 / 36.0 .38.6

Fuel system
Minimum Fuel Supply Line Size (mm) Minimum Fuel Return Line Size (mm) Maximum Fuel Pump Supply (L) Maximum Fuel Temperature (!C) 16 13 214 71

Cooling system
Coolant Capacity - Engine Only (L) With Radiator (L) With Heat Exchanger (L) .. 20.8 60.6 .49.2

Electric system
Standard Cranking Motor (Heavy Duty , Positive Engagement) (V) Standard Battery Charging System , Negative Ground (A) ..24 .35

Alternator Brand / Model : Stamford / UCDI274K


Rated Output Rated Current Exciter THF(BS EN60034 " 1) Bearing Number Windings Silicon Steel Core Processing Insulation Class Winding Pitch Amortisseur Winding A.V.R. Model Voltage Regulation (no load- full load) Underspeed Protection Protection Phase Sequence TIF(NEMA MG 1-22) Excitation System Ambient Temp Stator Rated Temp 250 kVA 361 A Brushless ... ... ... ... ... ... ... <2% Single 100% Copper ... ... ... ... ... ... ... ..One Piece Punching ..H 2/3 Full ... ... ... ... ... ...AS480 .# 1.0% ..Standard IP23 A(U), B(V), C(W) ... ... ... ... ... ... ...<50 ... ... ... ... ... ... ... .Self-excited, SHUNT 50 .125

Control System :
The DSE7210 and DSE7220 are control modules for single gen-set applications. The modules incorporate a number of advanced features to meet the most demanding on-site applications. The DSE7210 is an Automatic Start Control Module and the DSE7220 is an Auto Mains (Utility) Failure Control Module. The DSE7220 includes the additional capability of being able to monitor a mains (utility) supply. Both modules have been designed to start and stop diesel and gas generating sets that include electronic and non-electronic engines. Bothmodules are simple to operate and feature a user friendlymenu layout for improved clarity. Enhanced features include a real time clock for improved event and performancemonitoring, the ability to display any language on screen and a 132 x 64 pixel LCD display.

DSE7220

The DSE8610 is an easy to use multi-generator loadshare system, designed to synchronise up to 32 generators including electronic and non-electronic engines. The DSE8610 monitors the generator and indicates operational status and fault conditions, automatically starting or stopping the engine on load demand or fault condition. System alarms are annunciated on the LCD screen (multiple language options available), illuminated LED and audible sounder. The event log will record 250 events to facilitate easy maintenance. An extensive number of fixed and flexible monitoring, metering and protection features are included as well as comprehensive communication and system expansion options.

DSE8610

Optional
Engine
! Water Jacket Preheater ! Oil Preheater

Alternator
! Winding Temperature ! Measuring Instrument ! Alternator Preheater ! PMG ! Anti-damp and anti-corrosion treatment ! Anti-condensation heater

Generator
Toolkit with the machine

Fuel System
! Low fuel level alarm ! Automatic fuel feeding system ! Fuel T-valves

Canopy
! Trailer ! Galvanized

Lubricating System
Oil with the machine

Exhaust System
Protection board from hotness

Cooling System
! Front heat protection ! Coolant (-30!C)

Control System
! Remote control panel ! ATS

Voltages
! 415/240V ! 400/230V ! 380/220V

The following lists are optional by the needs of customers. N Series 1000 Hour Maintaining List
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Part Name CARTRIDGE,LUB FILTER,FUEL CORROSION RESISTOR CLEANER"AIR BELT,V BELT,V RIBBED BELT,V TURBOCHARGER ,KIT SET,MAIN BEARING BEARING,CONNECTING NOZZLE,PISTION COOLING THERMOSTAT OIL PRESSURE TRANS DUCER TEMP TPANSDUCER GUAGE,PRESSURE SWITCH,MAGNETIC SET,UPPER ENGINE GSK SET,LOWER ENGINE GSK Part No. 3401544=LF9009 3315843=FS1212 4058965=WF2076 3021645=AF928M 178708 217638 3040303 3801523 3801260 214950 3013591 3076489 3015237 3015238 3034572 3050692 3801330 3801468 Qty 1 2 1 1 1 1 1 1 1 2 6 1 1 1 1 1 1 1 Remark

Anda mungkin juga menyukai