Page 1 of 8

P.O. Box 151652 Arlington, Texas 76015
Metro 972-572-4500 Metro 817-467-0213
www.a-action.com


PHASE 1
PROPERTY INSPECTION REPORT


Buyers Name __ _______________ Phone #___________________
Property Address ___ _________________ Lot No. _______ Block No. _______
City ________________________________ Texas, Zip __75063_____


Builder Name _____________________________________ Phone #___________________
Builder Address ____________________________________
City _____________________________________________ Texas, Zip _______ County ___________
Site Foreman ____________________________ Phone #___________



Part 1: TYPE OF HOME
Two Story

Part 2: DESIGN CRITERIA
1. Are the foundation plans on site?... No
2. Has the foundation system for this structure been designed by an engineer, architect or other design professional. Not Determined
If yes, provide name and registration number of the engineer as specified on the plans: _____
3. Have the plans been reviewed during the inspection. No

Part 3: BEARING SOIL CONDITIONS
1. Type:
Virgin
Compacted Fill
Combination
2. Are soils loose or poorly compacted? ..No
3. Are trees and shrubbery within 20 of the foundation? ... No
4. Have Root shields been installed? ... No
5. Excavations free from debris ... No

Part 4: SLAB ON GRADE
A. SLAB TYPE:
Post Tension
B. SLAB FORM WORK
1. Is stringline in place? Yes
1. Average thickness of slab __4-inches_______
2. Are boards straight and properly braced? . Yes
3. Is slab properly thickened to support the fireplace? . N/A
(Minimum 12 thickness)

2007 A-Action Home Inspection Group (972) 572-4500 (817) 467-0213 www.a-action.com
Page 2 of 8

C. BEAM
Measurements: Approximate Depth __28-inches Perimeter 24 to 28-inches interior______ Approximate Width __13-inches__
1. Is there water in the beam excavation? .... No
2. Are there any cave-ins? .... No
3. Do beams extended a minimum of 6 into undisturbed soil or compacted fill? .. Yes
4. Are Beams spaced as per planes? . Yes

D. MOISTURE BARRIER
1. Is the barrier 6 mil., and over lapped ? (6 Minimum) ... No
2. Is the polyethylene barrier taped at over laps . No
3. Are the plumbing penetrations covered with mastic? .. No

E. REINFORCING STEEL
1. Exterior Beam No
2. Corner Bars Yes
3. Shear Supports ... N/A
4. Proper Supports . No
5. Proper Splices (12 in.) Yes
6. Proper Coverage . No
7. Deep Beams .... Yes
8. Dowell Bars N/A
9. 6x6 6-gauge Wire Mesh. N/A
10. #3 Rebar . N/A

F. TENDONS (POST TENSION CABLES)
1. Quantity: Front to Back ___23_____ Side to Side ___32_____
2. Are the tendons per plan? .. Not Determined
3. Are the tendons ? ...... Yes
4. Have the tendons been installed with live and dead ends? .... Yes
5. Are the tendons in good condition (sheathing, nicks, abrasions, etc.) with exposed cable taped? No
6. Is there a sand cushion? .. Yes
7. Are the tendons properly raised above the finished grade? No

Part 6 ROUGH-IN PLUMBING
A. MAIN WATER SUPPLY LINE
1. Material used for city water supply line. ___ 1-inch Pex_______
2. Depth of the city water supply line. ___12 to 16 inches_______
3. Size of the water supply line. _1-inch_________
4. Location of the main water shutoff. __Front Curb________

B. MAIN SEWER LINE
1. Size of the main sewer line. __4-inch________
2. Material used main sewer line. ___40 gauge PVC plastic_______
3. Location of the main cleanout. _Exterior Wall front curb side of the house___
4. Drain properly sloped downward toward city sewer connection? . Yes
(Does drain maintain a minimum of one fourth unit vertical in 12 unit horizontal (2%) slope)

C. DISTRIBUTION WATER SUPPLY LINE
5. Material used for water distribution lines. __Pex (plastic)________
6. Size of water distribution line. _3/4, 5/8, 1/2 water lines_________
7. Depth of water distribution lines. __10 to 12 inches________
8. Are the water supply lines properly protected from concrete contact? . No


2007 A-Action Home Inspection Group (972) 572-4500 (817) 467-0213 www.a-action.com
Page 3 of 8
ITEMS IN NEED OF REPAIR BEFORE POURING THE CONCRETE

1. There is damaged and missing post tension cable sheathing at the ends in various locations. The tension
cables should be covered at all points from beginning to end. This condition should be corrected prior to
pouring the concrete. All of the exposed post tension cable ends should be wrapped with Teflon tape
and/or 6-mil plastic. These help prevent the concrete from adhering to the post tension cables.
2. One of the beams needs to be widened in the front porch area. The beam measured 10-inches. The beam
should be a minimum of 12-inches wide.
3. The steel rebar is in contact with the post tension cable at the front porch area. The tension cable should
be wrapped with plastic or Teflon tape before the concrete is poured.
4. All of the post tension cables need to be properly raised off of the pad floor and suspended a minimum
of 2-inches off the finished grade at and around the back porch area.
5. The plastic vapor barrier is applied over the top of some of the cables. This condition should be
corrected to help prevent air-pocket from occurring in the beam areas.
6. All openings in the plastic vapor barrier should be closed and taped.
7. The plastic vapor barrier does not extend fully into the beam area and overlap by 6-inches. This should
be corrected before the concrete is poured.
8. All debris in the foundation beam trenches needs to be cleaned out before the concrete is poured.
9. It is recommended to add two addition steel rebar stands in the lower portion of the large footer in the
back porch.
10. It is recommended to add two addition steel rebar strands in the lower portion of the front porch footer.
11. Backfill dirt is needed on the south former board.
12. The Pex water lines are not properly protected and/or covered with insulation. This condition should be
corrected prior to pouring the concrete.
13. The waste pipes are not properly protected and/or covered with insulation. This condition should be
corrected prior to pouring the concrete.

2007 A-Action Home Inspection Group (972) 572-4500 (817) 467-0213 www.a-action.com
Page 4 of 8
Photo Log


Debris needs to be removed from the crawl space. Cable ends need to be wrapped. Plumbing lines need to be insulated.


Cable ends need to be wrapped. Debris needs to be removed from the crawl space.


Recommend adding rebar in the lower footer.

2007 A-Action Home Inspection Group (972) 572-4500 (817) 467-0213 www.a-action.com
Page 5 of 8


Chairs are needed under the cables and steel near the back porch are.



The plumbing needs to be covered with insulation.


2007 A-Action Home Inspection Group (972) 572-4500 (817) 467-0213 www.a-action.com
Page 6 of 8

The plumbing needs to be covered with insulation.



Cable ends need to be wrapped. Fill needed against the former boards.


2007 A-Action Home Inspection Group (972) 572-4500 (817) 467-0213 www.a-action.com
Page 7 of 8

The beam needs to be widened in the front porch area.



It is recommended to have two additional steel rebar strands in the beam footer at the front porch.


2007 A-Action Home Inspection Group (972) 572-4500 (817) 467-0213 www.a-action.com
Page 8 of 8
It has been a pleasure providing this inspection service for you. If you have any questions at all, please feel free
to email me or call my cell phone @ 972-743-5588.
You Can Visit Our Website at: www.a-action.com
Brian P. Murphy
A-Action Home Inspection Group
817-467-0213 or 972-572-4500
Professional Real Estate Inspector TREC #3948
brian@a-actionhomeinspection.com
www.a-action.com
Your Home Consultant for Life




Brian Murphy - Operator & Lead Inspector of A-Action Home Inspection Group
Licensed Professional Real Estate Inspector #3948 (Texas Real Estate Commission)
Licensed Certified Applicator (Structural Pest Control Board)
Member of International Code Council (ICC)
Certified Code Inspector - ICC #5186355-R5 International Residential Code for One- and Two-Family Dwelling
Certified Residential Electrical Inspector ICC #5186355-E1
Certified Exterior Insulation and Finish System (EIFS) Third Party Inspector Exterior Design Institute (EDI)
Certified Third Party Moisture Analysis Inspector Exterior Design Institute (EDI)