SR 1 (Synchronizing Relay)
141 - 180
101 - 140
101 - 140
141 - 180
68 - 100
10 - 21
10 - 21
22 - 40
68 - 100
22 - 40
41 - 67
41 - 67
0-9
RESET
ENTER
SR 1 : Synchronizing Relay
Synchronizing Operation
4.1 4.1.1 4.1.2 4.1.3 4.1.4 4.1.5
5 6
7 8
9 10 11 12 13
Technical
Data
14
Order Form
SR 1 : Synchronizing Relay
Wide selectable setting range with fine steps. Password security for parameter setting. Automatic as well as manual synchronizing mode of operation The synchronizing control is blocked when the closing command is issued and remains blocked if the phase difference is less than a user defined limit. Hooter assignment on different faults
Synchronizing Relay Type SR1 provides automatic as well as manual functions for the synchronizing of generators. It monitors difference between voltage/frequency of Busbar and generator and actuates AVR (Automatic Voltage Regulator)/Governor of generator in order to bring the voltage/frequency difference within user prescribed limits. SR1 takes into account the circuit breaker [CB] delay and issues closing command at such an instant that when CB actually closes contacts, the phase difference is less than 3 degrees. The SR1 offers the following functions: Synchronization of a generator to its reference Bus bar Dead bus operation. Kicker pulse control. Controlling output is available in terms of Potential free contact / voltage / current loop or any combination of them. For various types of controlling output combinations, please refer to section -14 The man-machine interface is designed to offer ease of operation and parameter setting, and a clear view of the ongoing processes. It consists of a synchroscope, an alphanumeric display, annunciation LEDs and soft touch keys arranged aesthetically on the front panel. The SR1 is used for bringing a running generator into synchronism with the system busbar i.e. other already running generator(s). The relay will ensure that the generator and bus are within programmable voltage/ frequency difference ranges, and then issues a close command to the CB. The breaker closing time is taken into account in this process. See the Block diagram in section 13.1.3 for SR1 arrangement.
3 3.1
Design Connections
Features
16-bit Microcontroller based automatic synchronizing relay LED Synchroscope Accurate synchronization to a phase difference of less than 3 degrees. Three types of control for voltage / frequency Correction are available: a. Potential free contact,
Table 1:
The hooter relay assignment feature is available in the MMI. There are seven types of faults on which Hooter relay can be configured. On pressing RESET key Hooter relay will de-energize but the fault LED will remain ON while fault lasts.
b. Voltage ( 1V/ 3V/ 9V/ 0-5V), c. Current (4-20mA). User can choose any combination of these options. Proportional as well as Adaptive control. for governor & automatic voltage regulator A user friendly MMI
SR 1 : Synchronizing Relay
LEDs
Sync Over Faster
OFF
Sync Over Relay Open
ON
Sync Over Relay Closed
FLASHING
X Gov. Inc. Section Unhealthy X Gov.Dec Section Unhealthy X X AVR Inc Section Unhealthy
No Increase Governor Inc Signal to Gov. Signal active Freq. Diff. Freq. Diff. in not in User User Settable Settable Band Band No Dec Signal Governor to Governor Dec Signal active
<F>
Slower
Gen CB Gen CB Relay Gen CB Open Relay Closed Fault No Fault Fault
Increase <U>
No Inc Signal AVR Inc to AVR Signal active Volt. Diff. not Voltage. Diff. in User in User Settable Band SettableBand
Decrease No Dec Signal AVR Dec to AVR Signal active Comm. No Comm. Comm. On
3.1.11 Keypad
The user-friendly interactive MMI has six soft-touch keys and the LCD as described above. The RESET key provides reset function to relay. Other five keys are used in edit operation. The keys are <, +, -, > and ENTER. The keys marked < and > are meant for backward and forward scrolling respectively. Data or function is selected by pressing ENTER key. The keys marked + and - are used for decrementing and incrementing selected parameter value.
3.1.9 LEDs
There are 23 LEDs for annunciation. The synch scope which has 13 LEDs displays phase difference between bus bar and generator. Remaining LEDs are for Freq Increase, Freq decrease, In-band frequency, Voltage Increase, Voltage decrease, In-band voltage, Generator CB, Synch Over, Fault and Communication. The functions of these LEDs are described in the Table 2.
SR 1 : Synchronizing Relay
4. 4.1
b)
SR1 operates in one of the three selectable modes described below. Operating mode can be selected from the menu using keypad. These three modes are: Auto Manual Test Auto ModeIn Auto mode the correction of voltage and frequency is done automatically after receiving Start Sync command; CB is also closed automatically after taking into account the CB closing delay. This ensures that CB contacts close when phase difference is within 3 degrees and that the voltage and frequency are within the specified band. SR1 issues correction commands (signals) to AVR in order to bring voltage within band. Similarly it controls the governor to bring frequency of the generator within the set band; thereafter it operates the CB and Sync Over relay to effect synchronization within the set range of phase difference. Manual Mode In the manual mode, relay does not send correction signal to AVR / Governor to bring the voltage / frequency within the set band. For correction of voltage / frequency, manual correction is applied. For this + / -keys are used for increasing / decreasing voltage/frequency of generator through AVR /Governor respectively. When the voltage and frequency fall within set range, SR-1 issues a command for CB and Sync Over relays, within the set range of phase difference. This output can be utilized for closing the CB through another set of contacts for manual synchronization. Test ModeIn the test mode relay performs all the automatic functions as in auto mode except CB closing, which remains blocked in this mode. g) d) c)
SR1 measures TRUE RMS voltage and frequency of Bus as well as Generator and sends control (increase / decrease) pulses to governor until frequency is within the specified f band and greater than the bus bar frequency. (This will ensure that the generator under control will not experience reverse power, when synchronized and connected to the Bus.) It also compares the two voltages and sends control pulses to AVR (increase / decrease) until voltage is within the specified U band. When the voltage and frequency of generator both come within band, SR-1 identifies the instant at which to close contacts, based on present phase difference & CB closing delay; This ensures that phase difference is within set limits at the instant of actual closure of circuit breaker contacts. There are thirteen LEDs arranged horizontally above the LCD. The LEDs start glowing in sequence in accordance with the rate of change of phase difference (As shown in Fig:2).
Phase Diff.
141 - 180 101 - 140
e)
Phase Diff.
101 - 140 141 - 180
68 - 100
10 - 21
10 - 21
Fig: 2 f) In the Synch-check mode Relay executes the complete synchronization process but does not close the CB. It also takes into account the CB closing delay. It lights up central dot (LED marked by also called the NULL point) at the instant CB is supposed to be actually closed. If the moving dot arrives at NULL when the dot marked by lights up then synchronizing operation is going satisfactorily and it would be safe to perform CB closure. SR1 immediately releases the CB relay if voltage, freq or phase goes out of the set band. It will try to resynchronize the generator until the synchronizing time is over. In that case it will issue a Sync Failure fault. Synchronizing time is calculated by the two parameters in MMI i.e. Synch Attempt and Synch TimeOut. For example if Synch Attempt=2 and Synch TimeOut =5min, then SR1 will try to synchronize the generator within 10min (2* 5min).
22 - 40
68 - 100
22 - 40
41 - 67
41 - 67
0-9
SR 1 : Synchronizing Relay
Following thumb rule is generally used: Where large rotating flywheels are involved, the frequency difference of the two systems should possibly be low (<=0.1Hz.) because of the very high load inrushes at the instant of synchronism. When small flywheels are used, the frequency difference of the systems can be higher.
Vb <5% VN DeadBus Condition DeadBus DI Ready DeadBus = ON Status in MMI (CB Closing)
b)
F-NL : - 100%
to 105% of FN
When SR1 closes CB onto the bus, it controls governor and AVR to adjust frequency to F-NL and voltage to V-NL.
SR 1 : Synchronizing Relay
The maximum angular advance possible is limited to 45 degrees. If an angular advance is calculated larger than 45 degrees, CB is not switched but waits for a more exact frequency match.
0
0
Closing of the Main Contacts Range in which Sr1 closes CB in order that the main contacts at 0
45
90
So CB closing command is issued before the actual zero degree phase difference, depending on the CB delay and frequency difference. This effectively advances the angle at which the closing command is issued. This has been explained in figure 3.
Phase Diff.
Fig: 4 The relation between CB closing time and Slip frequency is shown in the following graph.
DEGREE F = 0.36 x TBC(ms) x Df(Hz)
Df=1Hz Df=0.7Hz Df=0.5Hz Df=0.4Hz Df=0.3Hz
100
Fp Fm
1/DF
90 80 70 60 50 40 30 20 10
q
Dt
TCB
Df=0.2Hz Df=0.1Hz
100
200
300
400
500
ms
Fig. : 3 Measured Phase Difference (m) is the angle at which SR1 issues CB command (i.e. excluding the CB operating delay). Projected Phase Difference Angle (p):- It is the Phase Diff at the instant of actual CB closure. p = m + (360* F * TCB)
Fig: 5 SR1 will display the CB/Slip Error if settings of Slip Freq Diff and CB time dont meet the advance angle of 45 degree. Once the closing command is issued CB relay remains energized as long as the closing conditions are met.
SR-1 identifies the CB closing command instant from the measured present rate of change of phase difference and CB closing delay time. Thus it is guaranteed that the contacts of the circuit breaker close at the time of phase coincidence within a tolerance of 3 degrees. With a small frequency difference or a small circuit breaker time delay, CB closes when the angular advance is low.
The voltage regulator control of the SR1 operates when the voltage of the generator is above or below the bus voltage by more than the set operational tolerance. That is: UG<UB OR UG>UB + U Where : UG = The Generator Voltage UB = The Bus Voltage U = The voltage control bandwidth
SR 1 : Synchronizing Relay
less than the time [AVRTWmin>=] and not longer than the time [<=AVRTWmax].
UG CORRECTION SIGNAL (U) UB+DU CB CLOSING ALLOWED UB CORRECTION SIGNAL (U)
R on
>= AVRTWmin
The actual pulse duration ON is proportional to the error according to the set value of the gain [Kpv in s/V].
R off
<= AVRTWmax
Characteristic
This Voltage correction is optional. User can Disable / Enable this Voltage correction by V-CORRECTION parameter in MMI. Other parameter related to the Voltage correction is the V-CONTROL i.e. Voltage Controlling strategy. There are two Controlling strategies offered by SR-1. One is Proportional Control (PC) and the other is Adaptive Control (AC). In Proportional Control(P) strategy the correction signal is sent in terms of PWM to Relay/ Current/ or voltage section. The Time period of the pulse is constant but the Pulse width of ON time of PWM is decided according to following method : Correction Pulse on Time = Kpv * Error Where Error. = [(Measured U) (set U)]. Kpv is decided by user through MMI. Unit of the Proportional Gain factor is s/V. Take the example of following setting: V-CORRECTN = ON V-CONTROL AVRTWmax Kpv = PC = 1.3s = 0.1s/V
The frequency regulator control of the SR1 operates when the frequency of the generator is below that of the bus frequency or above the set operational tolerance given by FG > [FB + F] Where: FG FB F = frequency of the generator = frequency of the bus = the frequency regulation bandwidth
Note : that this ensures that the circuit breaker is permitted to close only when the generator frequency is at or above the bus frequency thereby avoiding a motoring condition.
This means that on the error of 1volt, SR1 will generate a correction pulse with on period of 0.1sec & off period of 1.2 sec (1.3 - 0.1). The next correction pulse will be sent only after 1.2sec. Correction pulses will be sent in proportion to Error and proportional gain (Kpv) set by the user in MMI. In case of adaptive control strategy (AC), SR1 will generate the correction pulse according to the response of the AVR. It will dynamically check the response and according to the error will decide the ON period of the correction pulse. For this to become active, the user has to set the parameter V-CONTROL = AC.
Fig. 8: Speed (Frequency) Regulator Operating Characteristic The frequency correction is optional. User can Disable / Enable frequency correction by F-CORRECTION parameter in MMI. Other parameter related to the frequency correction is the F-CONTROL i.e. frequency controlling strategy. There are two Controlling strategies offered by SR1. One is Proportional Control (PC) other is Adaptive Control (AC). In Proportional Control (P) strategy the correction signal is sent in terms of PWM to Relay / Current / voltage section. The Time period of the pulse is constant but the ON time of PWM is decided according to following principle :
5.1
When one of the operating conditions is met (to either increase or decrease the voltage) the pulse cycle of the appropriate output relay is started. The cycle is repeated in every time period of [AVRTWmax] setting. The relay remains energized (pulse duration) not
8
SR 1 : Synchronizing Relay
Correction Pulse ON Time = Kpv * Error Where Error. = [(Measured F) (set F )]. Kpf is decided by user through MMI. Unit of the proportional gain factor is s/Hz. Take the example of following setting: F-CORRECTN = ON F-CONTROL= PC GOVTWmax = 1.3s Kpf= 0.1s/Hz This means that when the Error is 1Hz, SR1 will generate a correction pulse with on period of 0.1sec and Time period of 1.3sec. In this case the next correction pulse will be sent only after 1.2sec. In this way correction pulse will be sent in proportion to error and proportional gain (Kpf) set by the user in MMI. In case of adaptive control strategy (AC), SR1 will generate the correction pulse according to the response of the AVR. It will dynamically check the response and according to the error will decide the ON period of the correction pulse. This is achieved if the parameter VCONTROL = AC.
One of the most important items to check during the commissioning of generators which will operate in parallel is that connection of cables associated with synchronizing equipment is correct. If voltage transformer connection is incorrect, malsynchronization can occur, with the risk of considerable damage since even though synchronizing equipment may give the correct indication it is possible that the two systems to be synchronized are out of phase. The usual method of ensuring that synchronizing connections are correct is as follows: 1) Remove the generator connections at the suitable location such that the generator circuit voltage transformer can be safely energized Put the relay in Test Mode The synchroscope of SR1 should indicate zero phase displacement and the centre green LED should light. This indicates that the two systems are within +/- 9 degrees. If, however, the any red LED glows instead of the green one, the following can be concluded: Reading 141-180 degrees: changeover connections Of generator voltage. Reading 101-140 degrees: Generator and bus bar voltages are derived from different phases. Reading 41-67 degrees: Generator and bus bar voltages are derived from different phases. In order to check the correct functioning of the synchronizing unit, frequency and voltage control facilities, put the SR-1 in test mode. With the generator running check if the automatic voltage control functions are operating correctly: With the generator running, temporarily connect the appropriate wires to governor control terminals 9 thru 12. Observe the difference between busbar and generator frequency LEDs Faster and Slower. If the frequency difference is reducing, this indicates correct functioning of the frequency control device. If the frequency difference is increasing, the connection on governor control (9 thru 12) must be reversed. This test should then be repeated to check the voltage control unit. In this case, however, the relevant terminals are 13 thru 16 and LED Increase and Decrease should be observed
6.1
When one of the operating conditions is met (to either increase or decrease the speed) the pulse cycle of the appropriate output relay is started. The cycle is repeated every period [GOVTWmax] The relay remains energized (pulse duration) not less than the time [GOVTWmin>=] and not longer than the time [<=GOVTWmax] The actual pulse duration (ON period) is proportional to the measured frequency difference according to the set value of the gain [ s/Hz] See Figure 9.
R on
>= GOVTWmin
2)
R off
<= GOVTWmax
SR 1 : Synchronizing Relay
8 8.1
MODE: splays selected mode> Vb XXX.X V Fb XX.XX Hz (Running Parameters) Vg XXX.X V Fg XX.XX Hz STATUS: <Present status of SR1> Menu 2 (Pressing Enter Key) MODE SELECTION EDIT/VIEW PARAMETERS HOOTER ASSIGNMENTLOAD DEFAULTS CHANGE PASSWORD BACK TO PREV PAGE # MODE SELECTION # AUTO MODE MANUAL MODE TEST MODE BACK TO PREV PAGE #MANUAL CORRECTION# AVR CORRECTION GOV CORRECTION BACK TO DEFAULT PAGE MODE: MANUAL Vb XXX.X V Fb XX.XX Hz Vg XXX.X V Fg XX.XX Hz BACK TO PREV PAGE # EDIT PARAMETERS # SLIP FREQ VOLTAGE DIFF PHASE DIFF CB DELAY SYNCH ATTEMPTS SYNCH TIMEOUT DEADBUS STATUS V-CORRECTN F-CORRECTN V-CONTROL F-CONTROL Kpv Kpf AVRTWmax GOVTWmax AVRTWmin GOVTWmin Vgmax Vgmin Fgmax Fgmin Vbmax Vbmin Fbmax Fbmin BACK TO PREV PAGE
# HOOTER ASSIGNMENT# [ ] AVR FAULT [ ]GOV FAULT [ ]GEN UNHEALTHY [ ]BUS UNHEALTHY [ ]SYNC FAILURE [ ]CB/SLIP FAULT BACK TO PREV PAGE Enter Password Loading . . .
Menu 8 (Pressing Enter Key on LOAD DEFAULT) Menu 9 (Pressing Enter Key on CHANGE PASSWORD) Menu 10 Menu 11 Menu 12
Menu 3 (Pressing Enter Key on MODE SELECTION) Menu 4 (Pressing Enter Key on MANUAL MODE) Menu 5 (Pressing Enter Key on AVR / GOV Correction Mode)
Enter PASSWORD Enter new PASSWORD Re-Enter PASSWORD SUCCESS : PASSWORD CHANGED! Save modification? YES NO CANCEL Enter PASSWORD SAVING Enter Password! INVALID PASSWORD!
All keys can be used in selecting/specifying password Pressing Reset key for 3 sec, cursor will go back to the previous page.
10
SR 1 : Synchronizing Relay
Do not touch any key for View Run- 1 minutes; running paraning para- meters will appear on meters the screen after applying the auxiliary supply to SR1. If you are in menu 1 then Press ENTER key and using & keys bring cursor/blinking on EDIT/ VIEW PARAMETERS option. Select this menu by pressing ENTER key. Scrollthrough different funEdit ctions using &keys. By Parameters using INC & DEC keys of desired parameters value can be function increased or decreased. By pressing ENTER key SR1 will ask whether to save the edited parameter .Press or key to move to YES, NO or CANCEL. If YES is selected by pressing ENTER SR1 will ask for password. Enter the password and the parameter will be saved.
Menu 2
Menu 5
Menu 9
Menu 10,11
11
SR 1 : Synchronizing Relay
Technical
Data
Editable Parameters Description Frequency Difference between Bus bar and Generator in percentage of Nominal Freq Voltage Difference between Bus bar and Generator in percentage of Nominal voltage Phase difference between Bus bar and Generator Generator CB on Delay No of synchronizing attempts Interval over which relay will attempt to get synchronization, after getting the command of Sync Start Dead bus Enable/Disable Required Bus Voltage Displayed As Range Steps Size Default Setting 1.00%
SLIP FREQ
0.01%
0.1% 1o 1 msec 1 1min x 0.1% with 2% hysterisis 0.1% with 0.2% hysterisis x x x x
SYNCH ATTEMPTS 110 SYNCH TIMEOUT DEADBUS STATUS V-NL 1min 10min ON/OFF 100% to 115% of VN 100% to 105% of FN ON/OFF ON/OFF PC / AC PC/ AC
F-NL
Voltage Correction Frequency Correction Voltage Control Process (Proportional /Adaptive Control) Frequency Control Process (Proportional /Adaptive Control) Proportional Gain which determines how fast the SR1 responds to an error in voltage
Kpv
0.01 2 s /V
0.01 s/V
0.05 s/V
12
SR 1 : Synchronizing Relay
Proportional Gain which determines how fast the SR1 responds to an error in frequency Maximum Time period of correction pulse to AVR for voltage correction Maximum Time period of correction pulse to GOVERNOR for frequency correction Minimum ON period of correction pulse to AVR for voltage correction Minimum ON period of correction pulse to GOVERNOR for frequency correction Maximum Generator Voltage for considering the Generator healthy Minimum Generator Voltage for considering the Generator healthy Maximum Generator Frequency for considering the Generator healthy Minimum Generator Frequency for considering the Generator healthy Maximum Bus bar Voltage for considering the Generator healthy Minimum Bus bar Voltage for considering the Generator healthy Maximum Bus bar Frequency for considering the Generator healthy Minimum Bus bar Frequency for considering the Generator healthy
Kpf AVRTWmax
GOVTWmax AVRTWmin
Table 3: Different parameter settings in Edit mode Note : 1) Dont change the parameters while synchronization is going on. It is preferable to change the parameters in TEST mode or when relay is idle (In absence of Synch Start DI). 2) The Default Password for SR1 is ENTER-ENTER-ENTER-ENTER.
13
SR 1 : Synchronizing Relay
10
Functional Specifications
Parameter Auto Manual Mode Specification In Auto mode frequency control, voltage control and CB control functions are all automatic. Manual mode allows the user to manually adjust frequency and voltage. When the Voltages & Frequencies are within band, issues CB closing command. Similar to auto mode except No CB closing command. Test mode allows user to verify the controlling action of SR1. Generator & Bus bar Voltage XXX.XV (RMS value.) Generator & Bus bar Frequency XX.X Hz Relay Status : <Present processing of relay> View / Set all parameters described in the table of Section 9. SET function is protected by Password. Password can be modified. Protected by password. ( The Default Password for SR1 is 4-times Enter Key) Loads default parameters (described in the table of Section 9) including password and resets diagnostics parameters.
S.No 1 2
3 4
Test Default Display Display Function View / Edit Parameters Change Password Load Default
5 6 7
11
Performance Specifications
Parameter Aux Supply Aux supply burden Nominal Voltage : Specification 20V DC to 360 V DC and 25V AC to 270V AC. < 6VA 110V / 80-150V 230V / 180-260V 400V / 340-460V 1% 0.5% 50 Hz 1o
S.No 1 2 3
4 5 6 7
Tolerance in Voltage Measurement Tolerance in Frequency Measurement Rated frequency Tolerance in phase difference measurement
14
SR 1 : Synchronizing Relay
12
Hardware Specifications
Parameter Display Annunciation using LEDs(23 numbers) Key Pad 6 Keys Controls: Opto-isolated I/Ps 2: Relays Specification 20 characters/row x 4 rows LCD display with built in controller Synchroscope(13 LEDs), <U>, <f>, CB , SYNC OVER, AVR AVR, GOV, GOV , Communication, Fault Select, Increment, Decrement, Enter, Cancel, Reset Start Sync, Dead Bus Enable 250VAC 10A / 24V DC 3-Relays in all models:-CB, Sync Over, Hooter (and optionally :-AVR , AVR , GOV, GOV ) 4-20mA (Max load resistance : 300R) Max. and min. input current : 5% for 4-20 mA, In analog voltage o/p options, there are four options: [-1 -0- +1]V or [-3-0- +3]V or [ -9 -0 -+9]V, [0-5]V Tolerance : 5% Min load resistance: 1k These options are available on specific demand. - 400C - +750C - 200C - +700C max 2.5 mm2 1. Flush mounting 2. Panel Cut-Out: (W x H) 178 x 140 mm 3. Dimensions: (W x H x D) 214 x 140 x 80 mm 4. Weight: 1.2 Kg appx. Recommended 2.5 mm2 conductor
S.No 1 2 3 4 5
6 7
8 9 10 11
13
Terminal Details
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8
7 6
5 4
3 2
SR1
24 25 26 27 28 29 30 31 32 33 34 35
Fig. 10
15
SR 1 : Synchronizing Relay
16
SR 1 : Synchronizing Relay
Aux. Supply
22 Aux. Supply 21
20 Gen CB 19
CB
AVR
GOV
11
SR-1
30
31
10 GOV 9 33 8 32
Hooter 7
34 35
6 5
X X
4 Gen. Volt 3
2 Busbar Volt 1
Fig. 11
17
Generator
Bus Bar
SR 1 : Synchronizing Relay
In SR-C x Model, all electrical connections are same as in SR1-R except AVR/GOV connections, as per shown figures
GND
Current
AVR/GOV
12 GND 11
T
In SR1V x Model, all electrical connections are same as in SR1-R except AVR/GOV connections, as per shown figures
AVR/GOV
GND UVoltage
12 GND 11 U-
Gen. 1 Gen. CB
Bus Bar
Gen. 2 Gen. CB
Gen. CB
Governer +
Generator SR-1
Fig. 12
18
SR 1 : Synchronizing Relay
13.1.4 Dimensions
214.0 +/- 0.5
22.5
14
Order Form SR1 R - 1 Voltage - 3 Voltage - 9 Voltage - 0-5 Voltage - Current (4-20mA) V1 V3 V9 V5 C R 1 Voltage - 3 Voltage - 9 Voltage - 0-5 Voltage - Current (4-20mA) V1 V3 V9 V5 C 110V 230V 400V
19
FUNCTIONAL RANGE
Genset Supervision & Control Auto Synchroniser Load Balancing & Control Related Protection
HIGH-TECH RANGE
Microprocessor based numerical protection Event & fault recording RS 485 communication Bright alpha-numeric display
INTEGERATED RANGE
Numeric protection, solution for sub-station in association with INGETEAM T&D, Spain Distance protection Comprehensive transformer protection a. Three winding transformer b. Two winding transformer Multi-functional relay: variety of protection combination
Marketing Offices :
AHMEDABAD: +91 79 30074534/35/36 FAX : +91 79 30074519 BANGALORE: +91 80 25586147, 25594939 FAX : +91 25584839 BHUBANESWAR : +91 674 2507265 FAX : +91 674 2507265 CHANDIGARH : +91 172 272613, 3062624 FAX : +91 172 2726153 CHENNAI : +91 44 39180531/32/33/34 FAX :+91 44 39180514 DELHI : +91 11 30838822-25 Fax :+91 11 30838826 HYDERABAD : +91 40 27813003 FAX : +91 40 27812987 KOLKATA : +91 33 22275850/51 FAX : +91 33 22275849 MUMBAI : +91 22 24114727/28 FAX : +91 22 24126631 NAGPUR : +91 712 5616651 FAX : +91 712 5616651 PUNE : +91 20 30283244/45 FAX : +91 20 30283245 RAIPUR : +91 771 320852433/34