Atelier Management and Design Consultancy (Vietnam) Co.

,Ltd

SEL11-EMER E!C" EVAC#A$%&! L% '$%! (1

SECTION 11: EMERGENCY EVACUATION LIGHTING 11.1 11.1.1 GENERAL Functional description The emergency evacuation lighting scope of work covers a system of battery backed exit signs for evacuation purposes in the event of power failure. 11.1.2 Cross references General Comply with the General requirements worksection. Related workse t!ons Refer to the following worksections Electrical General Requirements, Adhesives, Sealants, Fasteners, Fire Stopping, Power Cables, Cable Support & uct S!stems, Electrical Commissioning 11.1.! "tandard #ith respect to alternative standards$ please refer to section !.1 of this "pecification %& worksection General '" (2)) "ystem design$ installation and operation %"*+," 22-!.1. .nspection and maintenance To %"*+," 22-!.2. 11." 11.2.1 #UALITY "ubmissions $rod% t data "ubmit manufacturer/s data for each type of exit sign including tables indicating the maximum luminaire spacing for a given mounting height. T&'e test data "ubmit the following 0uminaire classification to %"*+," 22-!.! or '" (2)) 1art 1. 'attery and charger performance test reports$ including discharge and charging characteristics. S(o' draw!n)s "ubmit the following Construction details$ overall dimensions and wiring arrangement for each type of luminaire and exit sign.

Atelier Management and Design Consultancy (Vietnam) Co.,Ltd

SEL11-EMER E!C" EVAC#A$%&! L% '$%! ()

0anguage 2 signage for exit and direction signage. 11.* 11.!.1 COM$ONENTS "ingle3point system luminairesl General 4isual indicator lights 1rovide a red or green indicator$ readily visible when the luminaire is in its operating location$ which indicates that the battery is being charged. .nverter system 1rovide protection of the inverter system against damage in the event of failure$ removal or replacement of the lamp$ while in normal operation. 0ocal test switches 1rovide a momentary action test switch$ accessible from below the ceiling$ on each luminaire to temporarily disconnect the mains supply and connect the battery to the lamp. +atter!es Type 0ead3acid or nickel3cadmium batteries capable of operating each lamp at its rated output continuously at least 2 hours during acceptance tests and 1.( hours during subse5uent tests. 'attery life %t least ! years when operating under normal conditions at an ambient temperature of 2(oC and sub6ected to charging and discharging at ) monthly intervals. 7arking .ndelibly mark each battery with its date of manufacture. Lan)%a)e 8nglish language on signs. "ubmit for approval. 11., INSTALLATION E-er)en & L%. le/els 0uminaires shall provide an average illumination level of ( lux. $ower s%''l& to s!n)le0'o!nt s&ste-s 1rovide a 2&9 4 unswitched active supply to each exit sign. 11.1 11.(.1 COM$LETION Commissioning Ma!ns s%''l& 'efore commissioning$ ensure mains supply has been continuously connected for at least 2& hours. S!n)le0'o!nt s&ste-s :isconnect the mains supply to each general lighting final sub3circuit and verify the correct operation of luminaires and exit signs for a continuous period of at least 2 hours. Then restore normal supply and verify the operation of the

Atelier Management and Design Consultancy (Vietnam) Co.,Ltd

SEL11-EMER E!C" EVAC#A$%&! L% '$%! (*

indicator lights on each luminaire. 11.(.2 Completion tests S!n)le0'o!nt s&ste-s Carry out the )3monthly procedures before practical completion and again before the end of the maintenance period. 11.(.! 7aintenance General Carry out the )3monthly procedures

Anda mungkin juga menyukai