Simplicity of Short Circuit Calculation

3 Different Transformer
3 Different Generator
3 Different Motor
No Conductor Resistance Calculation

Short Circuit Value is:

IkT + IkG + IkM = 4.91 kA

Power System
Constant c 1.1 c IEC
Short Circuit Power S"kq 5000 MVA IEC

Transformer A Transformer B Transformer C

} ={ size8{c dotSr ub{size6{rT} }over{sqrt{3}cdotUrSub{size6{rT} cdotleft({ size6{urSb{kr} over{size6{10 %} +c dot{ size6{Sr ub{rT} over{size6{Sr ub{kQ}rSup{ Quantity 1 Pcs Quantity 0 Pcs Quantity 0 Pcs

IkT
Primary Voltage VP 6.6 kV Primary Voltage VP 6.6 kV Primary Voltage VP 6.6 kV

¿¿¿ Secondary Voltage


Rated Apparent Power
Rated Short Circuit
VS
Sr
ukr
20 kV
16 MVA
10 %
Secondary Voltage
Rated Apparent Power
Rated Short Circuit
VS
Sr
ukr
20 kV
40 MVA
11 %
Secondary Voltage
Rated Apparent Power
Rated Short Circuit
VS
Sr
ukr
20 kV
40 MVA
11 %
Total IkT Transformer 4.91 kA IkT Transformer A 4.91 kA IkT Transformer B 0.00 IkT Transformer C 0.00

Generator A Generator B Generator C


Quantity 0 Pcs Quantity 0 Pcs Quantity 0 Pcs
} } = { { size 8{c cdot S rSub { size 6{r} } } } over { sqrt {3} cdot U rSub { size 6{r} } cdot { { size 6{x rSub {d} rSup {
IkG Rated Voltage Ur 0.4 kV Secondary Voltage VS 0.4 kV Secondary Voltage VS 0.4 kV
10 % ¿¿ Rated Apparent Power Sr 10 MVA Rated Apparent Power Sr 10 MVA Rated Apparent Power Sr 10 MVA
Subtransient Reactance X"d 12 % Subtransient Reactance X"d 12 % Subtransient Reactance X"d 12 %
Total IkG Generator 0.00 kA IkG Generator A 0.00 kA IkG Generator B 0.00 IkG Generator C 0.00

Motor A Motor B Motor C


Quantity 0 Pcs Quantity 0 Pcs Quantity 0 Pcs
} ={ size8{c dot { size6{IrSub{LR} } over {size6{IrSub{r} } cdotPrSub{size6{r} } over {sqrt{3} cdotUrSub{size6{r} cdotcosϕrSub{size6{r} } }{¿ Rated Voltage 12 kV Rated Voltage 12 kV Rated Voltage 12 kV

IkM ¿ Active Power


Phase angle Ir and Ur
Pr
Cos jr
8 MW
0.85
Active Power
Phase angle Ir and Ur
Pr
Cos jr
8 MW
0.85
Active Power
Phase angle Ir and Ur
Pr
Cos jr
8 MW
0.85
Rotor Locked current 5 Ir Rotor Locked current 5 Ir Rotor Locked current 5 Ir
Total IkM Motor 0.00 kA IkM Motor A 0.00 kA IkM Motor B 0.00 kA IkM Motor C 0.00 kA