Anda di halaman 1dari 3

4/26/2012

Exercise 1
A 100 MVA, 13.9 kV, wye connected synchronous generator has a subtransient reactance X of 0.2 pu, a negative reactance X2 of 0.25 pu, a zero sequence reactance of 0.1 pu and negligible resistance. The neutral of generator is solidly grounded. Assume that the generator is initially unloaded and operating at rated voltage, and that a single line-to-ground fault occurs on phase a at the terminals of generator. Evaluate the voltages and currents in each phase during the subtransient period immediately after the fault occurs. Also, determine the line-to-line voltages at that time. Base : 100 MVA, 13.8 kV

Additional Exercises Unsymmetrical Fault


By Zetty Nurazlinda Zakaria

Exercise 1: ANSWERS

Exercise 2
A 100 MVA, 13.9 kV, wye connected synchronous generator has a subtransient reactance X of 0.2 pu, a negative reactance X2 of 0.25 pu, a zero sequence reactance of 0.1 pu and negligible resistance. The neutral of generator is solidly grounded. Assume that the generator is initially unloaded and operating at rated voltage, and that a line-to-line fault occurs between phase b and c at the terminals of generator. Evaluate the voltages and currents in each phase during the subtransient period immediately after the fault occurs. Also, determine the line-to-line voltages at that time. Base : 100 MVA, 13.8 kV

Line currents
Ia = 5.45590o = 22.82 kA Ib = 0 Ic = 0

Line-to-line voltages
Vab = Va Vb = 0.98674o Vbc = Vb Vc = 1.890 -90o Vca = Vc Va = 0.986 106o

Line Voltages
Va = 0 Vb = 0.983-106o Vc = 0.983+106o

4/26/2012

Exercise 2: ANSWERS

Exercise 3
A 100 MVA, 13.9 kV, wye connected synchronous generator has a subtransient reactance X of 0.2 pu, a negative reactance X2 of 0.25 pu, a zero sequence reactance of 0.1 pu and negligible resistance. The neutral of generator is solidly grounded. Assume that the generator is initially unloaded and operating at rated voltage, and that a double line to ground fault occurs between phase b and c to ground at the terminals of generator. Evaluate the voltages and currents in each phase during the subtransient period immediately after the fault occurs. Also, determine the line-to-line voltages at that time.
Base : 100 MVA, 13.8 kV

Line currents
Ia = 0 Ib = 3.849180o Ic = 3.8490 = 16.1 kA

Line-to-line voltages
Vab = Va Vb = 1.6680o Vbc = Vb Vc = 00o Vca = Vc Va = 1.668180o

Line Voltages
Va = 1.1120o Vb = 0.556180o Vc = 0.556180o

Exercise 3: ANSWERS

Exercise 4
Consider Figure 9. The motor is drawing 15 MW at 0.8 power factor leading and a terminal voltage of 10.6 kV when a symmetrical 3-phase fault occurs at the motor terminals. Determine:subtransient current in the generator, motor and fault for 3-phase fault subtransient current in the generator, motor and fault for single line to ground fault subtransient current in the generator, motor and fault for line to line fault subtransient current in the generator, motor and fault for double line to ground fault

Line currents
Ia = ? Ib = ? Ic = ?

Line-to-line voltages
Vab = Va Vb = ? Vbc = Vb Vc = ? Vca = Vc Va = ?

Line Voltages
Va = ? Vb = ? Vc = ?

4/26/2012

Exercise 4

Figure 9 Item Generator (Y-grounded) Transformer T1 &T2 ( -Y grounded) Motor (Y grounded) Line MVA 25 MVA 25 MVA Voltage 11 kV 11/66 kV 15% 10% Z1 15% 10% Z2 10% 5% Z0

25 MVA 25 MVA

11 kV 66 kV

15% 10%

15% 10%

10% 5%

Anda mungkin juga menyukai