Anda di halaman 1dari 18

P R O F I

B U S
PROCESS FIELD BUS

I
T
I
P
M
Operate
IT
Engineer
IT
Control
IT
Field
IT
PROFIBUS DP/DPV1
Ethernet
F
Remote
I/O
M
PID
M
Data Sheet
10/630.47 EN
Industrial
Devices overview
PROFIBUS DP
IT
Field
IT
Flowmeter
Field
IT
Electrical Actuator
Field
IT
Redundancy Link Module
Inform
IT
Process Recorder
Analyze
IT
Analyzer
Power
IT
Power Transducer
Protect
IT
MNS Motor Management INSUM

Drive
IT
Frequency Converter
Drive
IT
DC Drives
Control
IT
Process Controller
Control
IT
Motor Management, Motor Starter
Control
IT
Remote I/O and I/O System
Control
IT
Distributed Automation
2
Devices overview 10/630.47 EN
PROFIBUS DP

Field
IT
Flowmeter
FXM2000-DM. (COPA/MAG-XM) FXE4000 (COPA/MAGXE) FXM2000-DC. (COPA/MAGCM)
Data Sheet D184S031U02 D184S044U02 D184S007U02
Internet www.abb.com/instrumentation www.abb.com/instrumentation www.abb.com/instrumentation
Industrial
IT
enabled
Application Electromagnetic Flowmeter.
Suitable for universal use. Available in
compact or split architecture.
Accuracy:
0.4 % (optionally 0.2 %) of rate
Meter size:
DN 3...2400 (flange)
DN 1...100 (variable connections)
Electromagnetic Flowmeter.
Affordable standard instrument
in flanged and adapterflanged
versions.
Option: Stainless steel with variable
process connections.
Precision:
0.5 % of rate
Range:
DN 3...1000 (flanged)
DN 3...100 (adapterflanged)
Electromagnetic Flowmeter.
With capacitive electrodes,
used with measured mediums
with insulating deposits and low
conductivity > 0.05 s/cm.
Accuracy:
1 % of rate
Meter size:
DN 25...300 (flange)
Ambient temperature 25...+60 C 25...+60 C 25...+60 C
Type of protection IP 67 (IP 68) IP 67 (IP 68) IP 67 (IP 68)
Explosion protection
Registration CE 3A, EHEDG, CE CE
Physics RS 485 RS 485 RS 485
Protocol PROFIBUS DP PROFIBUS DP PROFIBUS DP
Max. Baud Rate 1.5 Mbit/s 1.5 Mbit/s 1.5 Mbit/s
Ident. No. 6666 HEX 6666 HEX 6666 HEX
PNO Certificate No.
Bus adress
local adjustment
central adjustment
0...126 (default 126)
Keypad
Software (e.g.: PLC)
0...126 (default 126)
Keypad
Software (e.g.: PLC)
0...126 (default 126)
Keypad
Software (e.g.: PLC)
Data length cyclical
read
write
fix 16 Byte
fix 16 Byte
fix 16 Byte
fix 16 Byte
fix 16 Byte
fix 16 Byte
Profil
Transducer Block
Function Block
(only for profil
conforming devices)
DP device only:
rate, status, counter
DP device only:
rate, status, counter
DP device only:
rate, status, counter
Device configuration
central adjustment
local adustment
Software (e.g.: PLC)
Keypad and display
Software (e.g.: PLC)
Keypad and display
Software (e.g.: PLC)
Keypad and display
External supply Yes Yes Yes
3
Devices overview 10/630.47 EN
PROFIBUS DP

Field
IT
Flowmeter
FSM1000 FMC2000-MM2 (TRUMASS) FMC2000-MM2 (TRIOMASS)
Data Sheet D184S034U02 D184S020U02 D184S068U02
Internet www.abb.com/instrumentation www.abb.com/instrumentation www.abb.com/instrumentation
Industrial
IT
enabled
Application Electromagnetic Flowmeter.
Especially suitable for fast response
times, liquids with higher
concentration of hard solid particles,
twophase fluids.
Accuracy:
1 % of rate
Meter size:
DN 3...1000 (flange)
DN 1...100 (variable connections)
Coriolis Mass Flowmeter.
Simultaneous determination of mass,
density and temperature;
singletubedesign, selfemptying,
spacesaving, robust, inexpensive.
Temperature of fluid:
50...+180 C
Accuracy:
Flow: 0.25 % of rate
Density: 5 g/l, 1 g/l
Meter size: DN 10, DN 15, DN 20,
DN 25, DN 40, DN 50
Coriolis Mass Flowmeter.
Simultaneous determination of mass,
density and temperature;
paralleltubedesign, selfemptying,
spacesaving, robust, inexpensive.
Temperature of fluid:
50...+180 C
Accuracy:
Flow: 0.15 %, 0.25 %, 0.4 % of rate
Density: 5 g/l, 1 g/l
Meter size: DN 10...DN 150 (...6)
Ambient temperature 25...+60 C 20...+60 C 20...+60 C
Type of protection IP 67 (IP 68) IP 67 IP 67
Explosion protection
Registration CE CE 3A, CE
Physics RS 485 RS 485 RS 485
Protocol PROFIBUS DP PROFIBUS DP PROFIBUS DP
Max. Baud Rate 1.5 Mbit/s 1.5 Mbit/s 1.5 Mbit/s
Ident. No. 6666 HEX 6666 HEX 6666 HEX
PNO Certificate No.
Bus adress
local adjustment
central adjustment
0...126 (default 126)
Keypad
Software (e.g.: PLC)
0...126 (default 126)
Keypad
Software (e.g.: PLC)
0...126 (default 126)
Keypad
Software (e.g.: PLC)
Data length cyclical
read
write
fix 16 Byte
fix 16 Byte
fix 16 Byte
fix 16 Byte
fix 16 Byte
fix 16 Byte
Profil
Transducer Block
Function Block
(only for profil
conforming devices)
DP device only:
rate, status, counter
DP device only:
rate, status, counter
DP device only:
rate, status, counter
Device configuration
central adjustment
local adustment
Software (e.g.: PLC)
Keypad and display
Software (e.g.: PLC)
Keypad and display
Software (e.g.: PLC)
Keypad and display
External supply Yes Yes Yes
4
Devices overview 10/630.47 EN
PROFIBUS DP

Field
IT
, Analyze
IT
Flowmeter Analyzer Process Controller
FMT500-IG (Sensyflow iG) Advance Optima + PKV30-DPS D100 (Digitric 100)
Data Sheet 10/146.41 EN 10/241.10 EN 10/616.11 EN
Internet www.abb.com/instrumentation www.abb.com/analytical www.abb.com/control
Industrial
IT
enabled Yes Yes
Application Thermal mass flowmeter for air
and gases, determination of mass
flow / standard volume flow and
gas temperature.
Turn down ratio: 1:150
Temperature of fluid:
25...+300 C
Accuracy:
0.9% of reading + 0.05 % fs
Meter size:
DN 25...3000 mm (1"...120")
Modular product line for process
analytics and emission monitoring.
Offers a range of different analytical
principles: NDIR, IR UV, thermal
conductivity, O
2
(paramagnetic)
and flame ionization measurement
of Hydrocarbons (FID).
Industrial Controller,
1channel (1 PID algorithms).
Multifunctional, flexible I/O
configuration, extensive function library
with preconfigured control strategies.
Frontal dimensions:
96 mm x 96 mm
Ambient temperature 25...+50 C 20...+50 C (45 C Uras) 0...50 C
Type of protection IP 67 IP 20 / IP 54 Front.: IP 65; hous.: IP 30; term.: IP 20
Explosion protection II 2(1) G EEx de [ia] ib II C T3; II 2 D EEx
Registration CE, ATEX, FM, CSA CE, TV CE
Physics RS 485 RS 485 RS 485
Protocol PROFIBUS DPV1 PROFIBUS DP PROFIBUS DPV1
Max. Baud Rate 1.5 Mbit/s 12 Mbit/s 1.5 Mbit/s
Ident. No. 05CA HEX 7503 HEX 9651 HEX
PNO Certificate No. be applied Z00413
Bus adress
local adjustment
central adjustment
0...126 (default 126)
Keypad
Software (e.g.: SMART VISION)
0...99
Switches

1...125 (default 1)
Buttons, IBISR+ via TTL/RS 232/485

Data length cyclical


read
write
5...15 Byte
0... 9 Byte
up to 244 Byte
up to 244 Byte
0...224 Byte
0... 64 Byte
Profil V3.0
Transducer Block Flow
Function Block
(only for profil
conforming devices)
2 AI: flow, gas temperature
1 TOT, SET-, SET/MOD-TOT:
flow totalizer
1 Character Input: characteristic
curce, PRESETTOT value
Physical values,
analog/digitale I/O's
Status signals: error, maintenance
request, maintenance mode
Analog IN: process value, inputs
Analog OUT: set points, outs,
analog outputs
Digital IN/OUT: modes,
digital I/O and many more
Device configuration
central adjustment
local adustment
DTM
(for FDT V1.2)
Keypad and display
Full remote control with Ethernet
TCP/IP and HMI software
Keypad and display

Keypad and display or


IBISR+ via TTL/RS 232/485
External supply Yes Yes Yes
5
Devices overview 10/630.47 EN
PROFIBUS DP
Control
IT
Process Controller
D500 (Digitric 500) P100 (Protronic 100) P500, P550 (Protronic 500/550)
Data Sheet 10/616.15 EN 10/626.11 EN 10/626.15 EN
Internet www.abb.com/control www.abb.com/control www.abb.com/control
Industrial
IT
enabled Yes Yes Yes
Application Industrial Controller with PLC functions,
1...4 channel (4 PID algorithms).
Multifunctional, flexible I/O
configuration, preconfigured and
userconfigurable control strategies
including PLC functions.
Frontal dimensions:
96 mm x 96 mm
Process Controller,
1 channel (2 PID algorithms).
Multifunctional, extensive library
of functions with preconfigured control
strategies, wide range of applications.
Frontal dimensions:
72 mm x 144 mm
Process Controller with PLC functions,
1...4 channel (4 PID algorithms).
Multifunctional, flexible I/O
configuration, preconfigured and
userconfigurable control strategies
including PLC functions.
Frontal dimensions:
72 mm x 144 mm
Ambient temperature 0...50 C 0...50 C 0...50 C
Type of protection Front.: IP 65; hous.: IP 30; term.: IP 20 Front.: IP 65; hous.: IP 30; term.: IP 20 Front.: IP 65; hous.: IP 30; term.: IP 20
Explosion protection
Registration CE CE CE, VdTV water level, DIN 3440
Physics RS 485 RS 485 RS 485
Protocol PROFIBUS DPV1 PROFIBUS DPV1 PROFIBUS DPV1
Max. Baud Rate 1.5 Mbit/s 1.5 Mbit/s 1.5 Mbit/s
Ident. No. 9651 HEX 9651 HEX 9651 HEX
PNO Certificate No. Z00413 Z00413 Z00413
Bus adress
local adjustment
central adjustment
1...125 (default 1)
Keypad, IBISR+ via TTL/RS 232/485

1...125 (default 1)
Keypad, IBISR+ via TTL/RS 232/485

1...125 (default 1)
Keypad, IBISR+ via TTL/RS 232/485

Data length cyclical


read
write
0...224 Byte
0... 64 Byte
0...224 Byte
0... 64 Byte
0...224 Byte
0... 64 Byte
Profil
Transducer Block
Function Block
(only for profil
conforming devices)
Analog IN: process value, inputs
Analog OUT: set points, outs,
analog ouputs
Digital IN/OUT: modes, digital I/O
and many more
Analog IN: process value, inputs
Analog OUT: set points, outs,
analog ouputs
Digital IN/OUT: modes, digital I/O
and many more
Analog IN: process value, inputs
Analog OUT: set points, outs,
analog ouputs
Digital IN/OUT: modes, digital I/O
and many more
Device configuration
central adjustment
local adustment

Keypad and display or


IBISR+ via TTL/RS 232/485

Keypad and display or


IBISR+ via TTL/RS 232/485

Keypad and display or


IBISR+ via TTL/RS 232/485
External supply Yes Yes Yes
6
Devices overview 10/630.47 EN
PROFIBUS DP
Inform
IT
Process Recorder
PM100 (PointMaster 100) PM200 (PointMaster 200) LM200 (LineMaster 200)
Data Sheet 10/411.10 EN 10/412.10 EN 10/432.10 EN
Internet www.abb.com www.abb.com www.abb.com
Industrial
IT
enabled Yes Yes Yes
Application 6 channel Multipoint Recorder.
Measurement and registration of
process signals, event marks,
limit value monitoring, alarm relays.
Data readout from PROFIBUS
master.
Frontal dimensions:
144 mm x 144 mm
6 channel Multipoint Recorder
with text printing facility.
Measurement and registration of
process signals, event marks,
limit value monitoring, alarm relays,
accounting functions, mathematical
functions. Data readout/write in from
PROFIBUS master. Text writing
from PROFIBUS master.
Frontal dimensions:
144 mm x 144 mm
4 channel Continuousline Recorder.
Measurement and registration of
process signals, text printing facility
(option), event marks, limit value
monitoring, alarm relays, data readout
from PROFIBUS master, text writing
from PROFIBUS master.
Frontal dimensions:
144 mm x 144 mm
Ambient temperature 0...50 C 0...50 C 0...50 C
Type of protection Front: IP 54; rear: IP 20 Front: IP 54; rear: IP 20 Front: IP 54; rear: IP 20
Explosion protection
Registration FM, CSA, UL, GOST, CE FM, CSA, UL, GOST, CE FM, CSA, UL, GOST, CE
Physics
Protocol
Max. Baud Rate
Ident. No.
PNO Certificate No.
Bus adress
local adjustment
central adjustment
via gateway BusCon via gateway BusCon via gateway BusCon
Data length cyclical
read
write
Profil
Transducer Block
Function Block
(only for profil
conforming devices)
Read: measurement channel 1...6,
status of the limits
Read: measurement channel 1...6,
status of the limits
Write: analog value channel 1...6,
free text up to 32 characters
Read: measurement channel 1...4,
status of the limits, binary input
Write: free text up to 16 characters
Device configuration
central adjustment
local adustment

Keypad or Software
Parapoint 100 via RS 485

Keypad or Software
Parapoint 200 via RS 485

Keypad or Software
Paraline 200 via RS 485
External supply Yes Yes Yes
7
Devices overview 10/630.47 EN
PROFIBUS DP
Power
IT
, Field
IT
Power Transducer Gateway
ESU (Contrans E SU) BusCon
Data Sheet 10/282.54 EN 10/497.20 EN
Internet www.abb.com www.abb.com
Industrial
IT
enabled Yes Yes
Application Universal Power Transducer.
Measurement of all power current
variables in single or three phase
mains, mains synchronization and
energy totalization.
PROFIBUS DP Gateway for
Recorder and Power Transducer.
Transmission of measured variables
without delay, 1...15 Recorders/Power
Transducers connectable.
Ambient temperature 20...+60 C 0...45 C
Type of protection IP 40 (terminals IP 20) IP 20
Explosion protection
Registration CE CE
Physics RS 485
Protocol PROFIBUS DP
Max. Baud Rate 12 Mbit/s
Ident. No. 2079 HEX
PNO Certificate No.
Bus adress
local adjustment
central adjustment
via gateway BusCon
0...126 (default 1)
Switch

Data length cyclical


read
write
0...228 Byte
0... 72 Byte
Profil
Transducer Block
Function Block
(only for profil
conforming devices)
Read: all parameters in the network
(U, I, P, Q, S, Phi, cos Phi, sin Phi, f),
up to 4 energy totalizers

Device configuration
central adjustment
local adustment

Software IBISE via


LCI adapter or RS 485

Switches
External supply Yes Yes
8
Devices overview 10/630.47 EN
PROFIBUS DP

Field
IT
, Drive
IT
Electrical Actuator Frequency Converter
Contrac ACS 160
Data Sheet 10/681.51 EN, 10/682.73 EN, 10/68
8.22 EN, 10/688.26 EN, 10/688.27 NE
3BFE64383671 EN
Internet www.abb.com/instrumentation www.abb.com/motors&drives
Industrial
IT
enabled Yes Yes
Application Intelligent electrical continuous
Actuators for modulating control.
Type: PME120, RHD..., LME620, RSD...
Part turn drives from 100...16000 Nm;
Linear drives from 4...200 kN;
digital communication, PC control.
Meter size:
Continuous positioning, precise,
longlived
Frequency Converter.
ACS 160 for universal applications,
in book shape, configuration possible
for constant and squarelaw load
torques.
Power connection:
3phase 380...500 V, 10 %,
50/60 Hz, 0.55...2.2 kW
Motor connection:
0...250 Hz
Ambient temperature 30...+65 C 10...+40 C (50 C)
Type of protection IP 66 IP 65 / NEMA 4
Explosion protection
Registration CE UL, CSA, CE
Physics RS 485
Protocol PROFIBUS DP via communication module
Max. Baud Rate 1.5 Mbit/s CFB-PDP
Ident. No. 9655 HEX
PNO Certificate No.
Bus adress
local adjustment
central adjustment
2...126 (default 126)
SMART VISION via RS 232

2...126 (default 2)
Panel, Software DriveWindows Light

Data length cyclical


read
write
3...10 Byte
fix 5 Byte
4...28 Byte
4...28 Byte
Profil V2.0, Class A V2.0
Transducer Block Electrical Actuator Adjustable Drives
Function Block
(only for profil
conforming devices)
1 AI: setpoint with status, position with
status, digital position, standard and
extended bit coded device information,
signal ready for operation
Reference and actual value,
speed, current, torque, frequency,
fault signals, PPO1PPO5 with
parameter transfer
Device configuration
central adjustment
local adustment

SMART VISION via RS 232


DTM in preparation
Panel or Software
DriveWindows Light via RS 232
External supply Yes Yes
9
Devices overview 10/630.47 EN
PROFIBUS DP
Drive
IT
Frequency Converter
ACS 400 ACS 600 ACS 800
Data Sheet 3BFE64226703 EN 3BFE64162021 EN 3AFE64572504 EN
Internet www.abb.com/motors&drives www.abb.com/motors&drives www.abb.com/motors&drives
Industrial
IT
enabled Yes Yes Yes
Application Frequency Converter.
ACS 400 for universal applications,
in book shape, configuration possible
for constant and squarelaw load
torques.
Power connection:
3phase 200...240 V, 10 %,
2.2...22 kW
3phase 380...480 V, 10 %,
2.2...37 kW
Frequency Converter.
Applications: pumps and ventilators,
centrifuges, mixers, winders, spinning
machines, materialshandling
technology, roller tables, packing
machines.
Power connection:
3phase 380...690 V, 48...63 Hz
2.2...3000 kW
Motor connection:
0...300 Hz
Frequency Converter.
Applications: pumps and ventilators,
centrifuges, mixers, winders,
spinning machines, materialshandling
technology, roller tables, packing
machines.
Power connection:
3phase 380...500 V, 48...63 Hz
1.1...3000 kW
Motor connection:
0...300 Hz
Ambient temperature 0...40 C (50 C) 0...40 C (50 C) 15...+40 C (50 C)
Type of protection IP 21 / IP 54 IP 22/IP 54 or IP 22/IP 42/IP 45 IP 21/IP 55 or IP 21/IP 22/IP 42/IP 45
Explosion protection
Registration UL, CSA, CE UL, CSA, CE UL, CSA, CE
Physics
Protocol via communication module via communication module via communication module
Max. Baud Rate NPBA-12 NPBA-12 NPBA-12 or RPBA-01
Ident. No.
PNO Certificate No.
Bus adress
local adjustment
central adjustment
2...126 (default 2)
Panel, Software DriveWindows Light

2...126 (default 2)
Panel, Software DriveWindows

2...126 (default 2)
Panel, Software DriveWindows

Data length cyclical


read
write
4...28 Byte
4...28 Byte
4...28 Byte
4...28 Byte
4...28 Byte
4...28 Byte
Profil V2.0 V2.0 V2.0
Transducer Block Adjustable Drives Adjustable Drives Adjustable Drives
Function Block
(only for profil
conforming devices)
Reference and actual value, speed,
current, torque, frequency, fault signals,
PPO1PPO5 with parameter transfer
Reference and actual value, speed,
current, torque, frequency, fault signals,
PPO1PPO5 with parameter transfer
Reference and actual value, speed,
current, torque, frequency, fault signals,
PPO1PPO5 with parameter transfer
Device configuration
central adjustment
local adustment
DTM in preparation
Panel or Software
DriveWindows Light via RS 232
DTM in preparation
Panel or Software
DriveWindows via FOC
DTM in preparation
Panel or Software
DriveWindows via FOC
External supply Yes Yes Yes
10
Devices overview 10/630.47 EN
PROFIBUS DP
Drive
IT
DC-Drives
DCS 400 DCS 500 DCS 600
Data Sheet 3ADW000095 EN/FR/ES/IT 3ADW000066 EN/FR/ES/IT 3ADW000072 EN/FR/ES/IT
Internet www.abb.com/dc www.abb.com/dc www.abb.com/dc
Industrial
IT
enabled Yes Yes Yes
Application DC DRIVE: optimal for machine
builders or replacement; compact,
fast commissioning, easy installation
via configuration macros,
regenerative or nonregenerative.
Applications: extruder, mixer, wire
drawing, ski lifts, etc.
Power connection:
3phase 230...500 V, 50...60 Hz,
12...520 kW, 4...1000 A
DC DRIVE: for demanding
applications; free function block
programming, 2Q and 4Q,
12 pulse parallel up to 20,000 A.
Applications: extruder, mixer,
printing machines, conveyor belts,
cranes, test riggs, ski lifts, metals,
marines, field excitation.
Power connection:
3phase 220...1000 V 10%,
45...65 Hz, 5.5...20,000 kW
DC Drive cabinets for complex
multidrive applications, 2Q und 4Q,
12 pulses parallel/serial/sequential
applications up to 20,000 A.
Applications: conveyor belts and
cranes, test riggs, plant construction,
metallurgy, field excitation.
Power connection:
3phase 220...1200 V 10 %,
45...65 Hz, 5.5...20,000 kW
Ambient temperature 0...40 C (55 C) 0...40 C (55 C) 0...40 C (55 C)
Type of protection IP 00 IP 00, Cabinet IP 21 IP 00, Cabinet IP 21
Explosion protection
Registration cULus, CE, Ctick cULus, CSA, CE CSA, CE, (cULus)
Physics
Protocol via communication module via communication module via communication module
Max. Baud Rate NPBA-12 NPBA-12 NPBA-12
Ident. No.
PNO Certificate No.
Bus adress
local adjustment
central adjustment
2...126 (default 2)
Panel, Software DriveWindows Light

2...126 (default 2)
Panel, Software CMTool

2...126 (default 2)
Panel, Software DriveWindows

Data length cyclical


read
write
4...28 Byte
4...28 Byte
4...28 Byte
4...28 Byte
4...28 Byte
4...28 Byte
Profil V2.0 V2.0 V2.0
Transducer Block Adjustable Drives Adjustable Drives Adjustable Drives
Function Block
(only for profil
conforming devices)
Reference and actual value, speed,
current, torque, power, fault signals,
PPO1PPO4 (PPO5) with parameter
transfer
Reference and actual value, speed,
current, torque, power, fault signals,
PPO1PPO4 (PPO5) with parameter
transfer
Reference and actual value, speed,
current, torque, power, fault signals,
PPO1PPO4 (PPO5) with parameter
transfer
Device configuration
central adjustment
local adustment
DTM in preparation
Panel or Software
DriveWindows Light via RS 232
DTM in preparation
Panel or Software
CMTool via FOC
DTM in preparation
Panel or Software
DriveWindows via FOC
External supply Yes Yes Yes
11
Devices overview 10/630.47 EN
PROFIBUS DP
Drive
IT
Communication Module
NPBA-12 RPBA-01 CFB-PDP
Data Sheet 3BFE64341588 EN 3AFE64504215 EN 3BFE64383671 EN
Internet www.abb.com/motors&drives www.abb.com/motors&drives www.abb.com/motors&drives
Industrial
IT
enabled Yes Yes Yes
Application PROFIBUS communication module PROFIBUS communication module PROFIBUS communication module
Ambient temperature +5...+40 C (55 C) 15...+40 C (50 C) +5...+50 C (55 C)
Type of protection IP 20 IP 20 IP 20
Explosion protection
Registration UL, CSA, CE UL, CSA, CE UL, CSA, CE
Physics RS 485 RS 485 RS 485
Protocol PROFIBUS DPV1 PROFIBUS DP PROFIBUS DP
Max. Baud Rate 12 Mbit/s 12 Mbit/s 12 Mbit/s
Ident. No. 6012 HEX 0812 HEX 1612 HEX
PNO Certificate No.
Bus adress
local adjustment
central adjustment
Data length cyclical
read
write
Profil see
Transducer Block ACS 400, ACS 600, ACS 800, see ACS 800 see ACS 160
Function Block
(only for profil
conforming devices)
DCS 400, DCS 500 oder DCS 600
Device configuration
central adjustment
local adustment
External supply Yes
12
Devices overview 10/630.47 EN
PROFIBUS DP
Protect
IT
MNS Motor Management INSUM

MCU1 MCU2 MMI


Data Sheet 1TGC901007B0201 1TGC901007B0201 1TGC901007B0201
Internet www.abb.com/mns www.abb.com/mns www.abb.com/mns
Industrial
IT
enabled Yes Yes Yes
Application Motor Control Unit 1:
controls, monitors and protects single
and three phase motors in accordance
with set parameters. MCU1 provides
control for standard drive types with
two contactor control and current
based motor protection and 12 pre
defined digital inputs for field contacts.
Motor Control Unit 2: see MCU1.
MCU2 additionally provides voltage
based protection functions. MCU2
provides control for drive types with
three contactor control and 15 pre
defined and 2 general purpose digital
inputs for field contacts.
ManMachineInterface for INSUM

.
6digit LCDdisplay:
For a clear display of data from all
128 connected field devices.
Encoder wheel and funtion keys:
Simple and clear menudriven
operation.
Ambient temperature 5...+55 C 5...+55 C 5...+70 C
Type of protection IP 20 IP 20 IP 30
Explosion protection PTB Ex 0130061 PTB Ex 0130061
Registration CE, IEC 4391, PTB CE, IEC 4391, PTB CE, IEC 4391
Physics
Protocol
Max. Baud Rate
Ident. No.
PNO Certificate No.
Bus adress
local adjustment
central adjustment
via INSUM

-Gateway
Data length cyclical
read
write
Profil
Transducer Block
Function Block
(only for profil
conforming devices)
Measurement: current, temperature
Operating commands:
Messages: time meter, status, service,
warnings, errors, etc.
Measurement: current, voltage, power,
cosphi, temperature
Operating commands:
Messages: time meter, status, service,
warnings, errors, etc.
see MCU1 and MCU2
Device configuration
central adjustment
local adustment
DTM in preparation
Via Software
OS on Ethernet TCP/IP
DTM in preparation
Via Software
OS on Ethernet TCP/IP

External supply Yes Yes Yes


PROFIBUS DP
LON 78 kBaud
LON 1.25 MBaud
Ethernet TCP/IP
13
Devices overview 10/630.47 EN
PROFIBUS DP
Protect
IT
MNS Motor Management INSUM

Backplane, Double Router Gateway


Data Sheet 1TGC901007B0201 1TGC901007B0201
Internet www.abb.com/mns www.abb.com/mns
Industrial
IT
enabled Yes Yes
Application The INSUM Communication Unit (ICU)
is the switchgear communication hub
for both internal and external communi
cation. Internally it allows four subnet
connections via routers for 32 devices/
subnet. The ICU can provide three
communication links for external
communication. Besides this, the
Local MMI and INSUM OS software
are also directly connected to ICU.
Gateway serves for protocol
conversion from LON (INSUM system)
to PROFIBUS (DCS). The PROFIBUS
Gateway can provide 24 binary bits
of status information and current
information to DCS.
Ambient temperature 5...+70 C 5...+70 C
Type of protection IP 30 IP 30
Explosion protection
Registration CE, IEC 4391 CE, IEC 4391
Physics RS 485
Protocol PROFIBUS DP
Max. Baud Rate fix 1.5 Mbit/s
Ident. No. 067E HEX (Software Version 2.3)
PNO Certificate No.
Bus adress
local adjustment
central adjustment
via INSUM

-Gateway 1...126 (default 126)


MMI, Software OS

Data length cyclical


read
write
0...244 Byte
0... 49 Byte
Profil
Transducer Block
Function Block
(only for profil
conforming devices)
see MCU1 and MCU2 see MCU1 and MCU2
Device configuration
central adjustment
local adustment

External supply Yes Yes


14
Devices overview 10/630.47 EN
PROFIBUS DP
Control
IT
Motor Starter
MSD11-FBP MSR22-FBP MFI21-FBP
Data Sheet 2CDC133002D0202 2CDC133001D0202 2CDC131001D0202
Internet www.abb.com www.abb.com www.abb.com
Industrial
IT
enabled Yes Yes Yes
Application Motor Starter Direct:
Complete unit mainly to connect
threephase a.c. motors to line,
direct, for pumps, ventilators,
centrifuges, mixers, winding
machines, conveyors and others.
Line voltage:
400 V AC, 50 and 60 cps
Motor current range:
0.16...12 A
Motor Starter Reverse:
Complete unit mainly to connect
threephase a.c. motors to line,
reverse, for rotarytables in handling
and warehousing systems, lift devices
and others.
Line voltage:
400 V AC, 50 and 60 cps
Motor current range:
0.16...12 A
Motor Starter Fieldbus Interface:
Connection of manual motor starters
MS325 and contactors to fieldbuses.
Supports different switchgear
assemblies such as reverse starter,
stardelta starter, with dedicated
logical functions and timers.
Free digital inputs and outputs
e.g. for sensors.
Motor current range:
0.16...25 A (range of MS325)
Ambient temperature 0...55 C 0...55 C 0...55 C
Type of protection IP 20 IP 20 IP 20
Explosion protection
Registration CE, UL, CSA, GL, BV, LRS CE, UL, CSA, GL, BV, LRS CE, UL, CSA, GL, BV, LRS
Physics
Protocol
Max. Baud Rate via PROFIBUS Plug via PROFIBUS Plug via PROFIBUS Plug
Ident. No. PDP22-FBP PDP22-FBP PDP22-FBP
PNO Certificate No.
Bus adress
local adjustment
central adjustment
2...99 (default 0)
Software via adapter

2...99 (default 0)
Switch, software via adapter

2...99 (default 0)
Switch, software via adapter

Data length cyclical


read
write
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
Profil
Transducer Block
Function Block
(only for profil
conforming devices)
Control of the contactors and the
manual motor starter
Control of the contactors and the
manual motor starter
Control of the contactors and the
manual motor starter
Device configuration
central adjustment
local adustment
Fixed configuration
Fixed configuration
Fixed configuration
Fixed configuration
Software (e.g. PLC)
Potentiometer (time)
External supply Yes, but normally via hybrid bus cable Yes, but normally via hybrid bus cable Yes, but normally via hybrid bus cable
15
Devices overview 10/630.47 EN
PROFIBUS DP
Control
IT
, Field
IT
Motor Management PROFIBUS Plug
UMC22-FBP PDP22-FBP
Data Sheet 2CDC135001D0202 2CDC192001D0201
Internet www.abb.com www.abb.com
Industrial
IT
enabled Yes Yes
Application Universal Motor Controller:
Efficient control and protection of
threephase a.c. motors with
elecronic measurement of the motor
current and with some additional
features such as blocking detection
and others.
Motor current range:
0.2...63 A
(bartype current transformers)
PROFIBUS DP Plug:
Connection of devices with small to
medium complexity to the PROFIBUS
DP and to the 24 V AC supply (hybrid
cable).
Examples for devices:
Proximity switches, I/O modules, motor
starter, softstarter, circuit breakers.
Ambient temperature 0...55 C 0...55 C
Type of protection IP 20 IP 67
Explosion protection
Registration CE, UL, CSA, GL, BV, LRS CE, UL, CSA, GL, BV, LRS
Physics RS 485
Protocol PROFIBUS DP
Max. Baud Rate via PROFIBUS Plug 12 Mbit/s
Ident. No. PDP22-FBP be applied
PNO Certificate No. be applied
Bus adress
local adjustment
central adjustment
2...99 (default 0)
Panel

Data length cyclical


read
write
6 Byte
4 Byte
Profil see
Transducer Block MSD11FBP, MSR22FBP,
Function Block
(only for profil
conforming devices)
Control of the contactors and the
manual motor starter, motor current,
additional I/Os
MFI21FBP or UMC22FBP
Device configuration
central adjustment
local adustment
Software (e.g. PLC)
Panel
External supply Yes, but normally via hybrid bus cable Yes, via hybrid bus cable
16
Devices overview 10/630.47 EN
PROFIBUS DP

Field
IT
, Control
IT
Redundancy Link Module I/O System Remote I/O
RLM01 S900 S800
Data Sheet 3BDD011641R0301 3BDD010420R0101 3BSE020924R101
Internet www.abb.com/fieldbus www.abb.com/control www.abb.com/control
Industrial
IT
enabled Yes Yes Yes
Application PROFIBUS DP/FMS Redundancy
Link Module.
Converts a non redundant RS 485
PROFIBUS DP/FMS line to two
redundant RS 485 PROFIBUS DP/FMS
lines and vice versa (line redundancy).
Monitoring of communication
Transparent for DPV1 services
Status and error display
Repeater functionality
I/O system for Zone 1 or Zone 2
applications.
Modular design with hotpluggable
modules
Redundant in power supply,
communication interface and
internal bus
HART pass through
Remote I/O system for Zone 2 / Class 1
Div. 2 or NonEx applications.
Modular design
Comprehensive distributed system
Communication with parent
controllers over industrystandard
fieldbuses
Ambient temperature 0...50 C 20...+60 C +5...+55 C
Type of protection IP 20 IP 20 IP 20
Explosion protection II 2 (1) G EEx [ia] ib IIC T4 and further [EEx ia] IIC, Class 1 Div. 2
Registration CE, UL, CSA, Germanischer Lloyd for
operation in maritime systems
ATEX, FM, GOST, CE ATEX, CSA, FM, GOST, CE
Physics RS 485 RS 485 RS 485
Protocol PROFIBUS DP and FMS PROFIBUS DPV1 PROFIBUS DP
Max. Baud Rate 12 Mbit/s 1.5 Mbit/s 12 Mbit/s
Ident. No. (transparent) 04D2 HEX 047C HEX
PNO Certificate No.
Bus adress
local adjustment
central adjustment
(transparent)

0...126 (default 0)
Switch

0...79
Switch

Data length cyclical


read
write

together 0...216 Byte 0...244 Byte


0...244 Byte
Profil Remote I/O
Transducer Block
Function Block
(only for profil
conforming devices)
Analog: standard I/O, with/without
HART and temperature free
configurable
Digital: standard I/O and EEx i
low power valves incl. quitting
Analog: standard I/O and temperature
(RTD and TC)
Digital: standard I/O (24/48 V DC
and 120/230 V AC), impulse totalizer
(1.5 MHz) and relay output
Device configuration
central adjustment
local adustment

Baud rate via switches


DTM
(for FDT V1.2)

Software (e.g.: PLC)


(DTM in preparation)

External supply Yes (redundant) Yes Yes


17
Devices overview 10/630.47 EN
PROFIBUS DP

Control
IT
Distributed Automation
I/O S500 PLC AC31: KT97, KT98
Data Sheet 2CDC124003B0201 2CDC121008D0201
2CDC121009D0201
Internet www.abb.com www.abb.com
Industrial
IT
enabled Yes Yes
Application Remote I/O system:
modular system,
bus module expandable with
up to 7 I/O modules
small expansion by extension box
plugged into bus module
2/3wire connection, screw/spring
prepared for open fieldbus tech
nology with FieldBusPlug (FBP)
Compact PLC units for central and
decentralized use,
integrated 24 dig.In + 16 dig.Out
+ 8 config.dig. IO + 8 ana.In
+ 4 ana.Out, 2 serial interfaces
(Modbus integrated), integrated
CS31Bus and up to 2 fieldbus/
communicationinterfaces: PROFIBUS
DP (Master or Slave) / DeviceNet /
ARCNET / Ethernet
user memory: 480kB/1MB + 4MB SMC
direct connect. to OperateIT via OPC
Ambient temperature 0...55 C 0...55 C
Type of protection IP 20 IP 20
Explosion protection
Registration CE, cUL CE, UL, CSA, GL, DNV
Physics RS 485 RS 485
Protocol PROFIBUS DP PROFIBUS DP
Max. Baud Rate 12 Mbit/s 12 Mbit/s
Ident. No. 9520 HEX 7504 HEX
PNO Certificate No. Z00495, Z00496
Bus adress
local adjustment
central adjustment
1...125
DIP switch

0...126
DIP switch

Data length cyclical


read
write
0...128 Byte
0...128 Byte
0....244 Byte
0....244 Byte
Profil
Transducer Block
Function Block
(only for profil
conforming devices)
Standard digital IN/OUT and
configurable IN/OUT
Standard analog IN/OUT
INTERFAST connection is usable
Programmable according IEC611313,
multitasking with high performance,
open and closed loop control,
PI and PID controller, encoder input,
32bit integer and floatingpoint
Device configuration
central adjustment
local adustment
Fieldbus configurator SW FB1131
+ configurator integrated in PLC
programming system AC1131

Fieldbus configurator SW FB1131


+ configurator integrated in PLC
programming system AC1131

External supply Yes Yes


1
0
/
6
3

0
.
4
7

E
N
R
e
v
.

A
The Industrial
IT
wordmark and all mentioned
product names in the form XXXXXX
IT
are registered
or pending trademarks of ABB.
ABB has Sales & Customer Support
expertise in over 100 countries worldwide.
www.abb.com/fieldbus
E-Mail: fieldbus.support@de.abb.com
The Companys policy is one of continuous product
improvement and the right is reserved to modify the
information contained herein without notice.
Printed in the Fed. Rep. of Germany (12.02)
ABB 2002
ABB Ltd.
Howard Road, St. Neots
Cambridgeshire, PE19 8EU
UK
Tel: +44 (0)1480 475321
Fax: +44 (0)1480 217948
ABB Inc.
125 E. County Line Road
Warminster, PA 18974
USA
Tel: +1 215 674 6000
Fax: +1 215 674 7183
ABB Automation Products GmbH
Hoeseler Platz 2
42579 Heiligenhaus
Germany
Tel: +49 2056 125533
Fax: +49 2056 125095

Anda mungkin juga menyukai