Anda di halaman 1dari 95

Head Office/Factory :

Jl. Gatot Subroto Km 7,8 Kel Pasir Jaya, Kec. Jati Uwung, Tangerang 15135-Indonesia
Phone : (62-21) 5922404, 5928066 (Hunting) Fax. : (62-21) 59301979, 5922576, 5901469
c
Copyright Sumi Indo Kabel 2012
All rights reserved. This catalogue is the copyright work of PT. Sumi Indo Kabel Tbk. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form or by means, electronic, mechanical, photocopying, recording or otherwise, without prior permission of PT. Sumi Indo Kabel.
All information contained in this catalogue is believed to be accurate at the time issue. PT. Sumi Indo Kabel reserve the right to change information or specification at any time
in the light of technical developments or revisions.
Issue : 5 Date: August 2012

Section 1 - Contents &Information
Low Voltage Catalogue Index
Page Number
SECTION1 - Contents &Information
Index Page 1
General Cable Specification 2
SECTION2 - PVC Insulated Cables
Unarmoured Cables
450/750 Volts PVC Insulated Cables (Cu/PVC, NYA) 5
450/750 Volts PVC Insulated Cables (Flexible Cu/PVC, NYAF) 6
300/500 Volts PVC Insulated and PVC Sheathed Cables (PVC/PVC, NYM) 8
300/500 Volts PVC Insulated and PVC Sheathed Cables (Flexible PVC/PVC, NYMHY) 10
450/750 Volts PVC Insulated and PVC Sheathed Cables (Flexible PVC/PVC, NYYHY) 11
600/1000 Volts PVC Insulated and PVC Sheathed Cables (PVC/PVC, NYY) 18
600/1000 Volts PVC Insulated, Copper Tape Shielded and PVC Sheathed Cables (PVC/PVC-S, NYSY) 30
Armoured Cables
600/1000 Volts PVC Insulated, Steel Wire Armoured and PVC Sheathed Cables (PVC/SWA/PVC, NYRY) 35
600/1000 Volts PVC Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (PVC/FSWA/PVC, NYFGbY) 41
600/1000 Volts PVC Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (PVC/DSTA/PVC, NYBY) 46
SECTION3 - XLPE Insulated Cables
Unarmoured Cables
600/1000 Volts XLPE Insulated and PVC Sheathed Cables (XLPE/PVC, N2XY) 52
600/1000 Volts XLPE Insulated, Copper Tape Shielded and PVC Sheathed Cables (XLPE/PVC-S, N2XSY) 62
Armoured Cables
600/1000 Volts XLPE Insulated, Steel Wire Armoured and PVC Sheathed Cables (XLPE/SWA/PVC, N2XRY) 67
600/1000 Volts XLPE Insulated, Flat Steel Wire Armoured and PVC Sheathed Cables (XLPE/FSWA/PVC, N2XFGbY) 73
600/1000 Volts XLPE Insulated, Double Steel Tape Armoured and PVC Sheathed Cables (XLPE/DSTA/PVC, N2XBY) 78
SECTION4 - General Information
Current Carrying Capacity for XLPE Insulated cable (single core) 83
Current Carrying Capacity for XLPE Insulated cable (multicore) 84
Current Carrying Capacity for PVC Insulated cable (single core) 85
Current Carrying Capacity for PVC Insulated cable (multicore) 86
Correction factor of Curent carrying capacity 87
Cable arrangement for Installation purpose 88
Explanation of Flame Retardant / Fire Resistant Characteristic 91
Page - 1
Section 1 - Contents &Information
1 Scope
2 Conductor
The conductor shall be solid, circular stranded, compacted stranded or sector shape
3 Insulation
4 Identification of cores
Below is standard reference for core identification :
A. IEC 60445 - 2010 Phasa / AC System : Black, Brown or Grey
Neutral : Blue
Grounding : Green and Yellow
B. SNI Standard 3 Core ( 2 Alternative ) a. Green / Yellow, Blue, Brown
b. Blue, Black, Brown
4 Core ( 3 Alternative ) a. Gren / Yellow, Blue, Black, Brown
b. Blue, Black, Brown, Black
c. Blue, Brown, Black, Brown
5 Core System I : Green/Yellow, Blue, Black, Black, Brown
System O : Blue, Black, Brown, Black, Brown
Number of core Identification of cores
Single core Brown
Two cores Brown, Blue
Three cores Brown, Black, Grey
Four cores Brown, Black, Grey, Blue
Five cores Brown, Black, Grey, Blue, Green / Yellow stripe
Six core or more Black insulation with white numbered code.
Note : *) : Sumi Indo Kabel can comply for color identification as Request
Page - 2
General Cable Specification
Thesespecificationapply to material andconstructions of cross-linked thermosettingpolyethylene
(XLPE) or Polivinyl chloride(PVC) insulated wireand cables for rated voltages 0.3/0.5 kV up to
0.6/1(1.2) kV inaccordanceto IEC 60502-1, SNI or SPLN ( Standardof IndonesiaElectric Power
Company )
The conductor shall be formed fromplain annealed copper or aluminiumcomplying with IEC
60228
The insulation shall be cross-linked polyethylene (XLPE) or Polivinyl chloride (PVC) in
accordance to IEC 60502-1.
Such that, theproposal cables shall beidentified by color or numbered printed on the surfaceof
insulation in accordance with the following sequence or other sequence as follows *) :
1
1
Section 1 - Contents &Information
5 Cabling and filling
6 Metallic Shielding (if required)
The metallic shielding shall consist of either one or more Copper tapes or a concentric layer of
copper wires or aluminium mylar tape and drain wire
7 Inner sheath (armour cable only).
8 Metallic armour
9 Outer sheath
Thearmour of singlecorecablesshall consist of singlelayer of aluminiumwireor doublelayersof
aluminium tape as non magnetic material.
The outer sheath shall consist of a thermoplastic compound such as polyvinyl chloride (PVC),
polyethylene (PE), halogen free (LSOH), etc in accordance with IEC 60502-1.
Page - 3
The multi cores shall be laid up together with suitable filler to give the completed cable a
substantially circular cross section and bound with suitable binder tape.
The inner sheath shall consist of extruded thermoplastic compound such as :polyvinyl chloride
(PVC), polyethylene (PE),halogen free (LSOH), etc in accordance to IEC 60502-1.
Themetallic armour shall consist of singlelayer of round galvanized steel wireor flat galvanized
steel wire and steel tape or double layer of galvanized steel tapes in accordance to IEC 60502-1.
Section 2- PVC Insulated Cables
Unarmoured Cables
450/750V PVC INSULATED WIRE (Cu/PVC)
acc. to IEC 60227
PVC Insulation Copper Conductor (Solid)
PVC Insulation Copper Conductor (Stranded)
Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Grey, Green-yellow
450/750V PVC INSULATED WIRE (Cu/PVC Flexible)
acc. to IEC 60227
PVC Insulation Copper Conductor (Flexible)
Colour of Insulation : Red, White, Black, Green, Brown, Blue, Yellow, Grey, Green-yellow
Page - 4
Note : Special application upon request
* Available product in accordance to : SPLN or other requirement.
* Tin coated Copper conductor.
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 450/750 V
Insulation : PVC Compound type C Operating Temperature
Colour Ident. : Red, White, Black, Green, Grey Maximum 70C
Brown, Blue, Yellow, Green-yellow
1.5 RE 1 1.38 0.7 3.0 25 12.1 0.011 2500
1.5 RM 7 1.6 0.7 3.2 25 12.1 0.010 2500
2.5 RE 1 1.78 0.8 3.6 35 7.41 0.010 2500
2.5 RM 7 2.0 0.8 3.8 35 7.41 0.009 2500
4 RE 1 2.26 0.8 4.1 50 4.61 0.0085 2500
4 RM 7 2.6 0.8 4.4 55 4.61 0.0077 2500
6 RE 1 2.77 0.8 4.6 70 3.08 0.0070 2500
6 RM 7 3.1 0.8 4.9 75 3.08 0.0065 2500
10 RE 1 3.57 1.0 5.8 115 1.83 0.0070 2500
10 RM 7 4.1 1.0 6.3 120 1.83 0.0065 2500
16 RM 7 5.1 1.0 7.3 180 1.15 0.0050 2500
25 RM 7 6.4 1.2 9.0 280 0.727 0.0050 2500
35 RM 7 7.6 1.2 10.5 380 0.524 0.0040 2500
50 RM 19 9.2 1.4 12.5 530 0.387 0.0045 2500
70 RM 19 10.9 1.4 14.0 730 0.268 0.0035 2500
95 RM 19 12.6 1.6 16.5 985 0.193 0.0035 2500
120 RM 37 14.2 1.6 18.0 1220 0.153 0.0032 2500
150 RM 37 15.9 1.8 20.0 1525 0.124 0.0032 2500
185 RM 37 17.6 2.0 22.0 1875 0.0991 0.0032 2500
240 RM 61 20.3 2.2 25.5 2465 0.0754 0.0032 2500
300 RM 61 22.7 2.4 28.0 3055 0.0601 0.0030 2500
400 RM 61 25.7 2.6 31.5 3930 0.0470 0.0028 2500
Note *) RE : Round Solid Class 1
RM : Circular Stranded Class 2
Page - 5
V/5 min
Maximum AC
Test
Voltage
Minimum
Insulation
M.km
Thickness
Nominal
Resistance Resistance
wire
Conductor
of
Nominal
Number Cross-
Diameter Shape
of
(Approx.)
Conductor section of wire conductor Insulation
mm mm
area (approx.)
Number
Weight
Nominal
Overall
/km kg/km
(Approx.)
mm mm
450/750 V PVC INSULATED WIRE
CU/PVC (IEC 60227)
Conductor
at 70C at 20C
of Diameter of
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type C Operating Temperature
Colour Ident. : Red, White, Black, Green, Grey Maximum 70C
Brown, Blue, Yellow, Green-yellow
1.5 1.6 0.7 3.2 25 13.30 0.010 2500
2.5 0.26 2.0 0.8 3.8 35 7.98 0.009 2500
4 0.31 2.6 0.8 4.4 50 4.95 0.007 2500
6 0.31 3.5 0.8 5.3 75 3.30 0.006 2500
10 0.41 4.6 1.0 6.8 130 1.91 0.0056 2500
16 0.41 5.7 1.0 7.9 190 1.21 0.0046 2500
25 0.41 7.1 1.2 9.7 290 0.78 0.0044 2500
35 0.41 8.4 1.2 11.0 395 0.554 0.0038 2500
50 0.41 10.1 1.4 13.5 550 0.386 0.0037 2500
70 0.51 12.0 1.4 15.0 760 0.272 0.0032 2500
95 0.51 13.7 1.6 17.5 1010 0.206 0.0032 2500
120 0.51 15.5 1.6 19.5 1270 0.161 0.0029 2500
150 0.51 17.6 1.8 22.0 1605 0.129 0.0029 2500
185 0.51 19.2 2.0 24.0 1915 0.106 0.0029 2500
240 0.51 22.0 2.2 27.0 2495 0.0801 0.0028 2500
Page - 6
Maximum Minimum
Nominal Diameter
Nominal Nominal
Thickness Overall Insulation
Cross- of of Diameter of Resistance Resistance
Weight Conductor
at 70C
area (Approx.) (Approx.) (approx.)
section Conductor
mm kg/km /km
0.26
mm
Insulation wire at 20C
mm mm V/5 min M.km
Conductor AC
Maximum Test
Diameter Voltage
of wire
mm
450/750 V PVC INSULATED WIRE
CU/PVC-Flexible (IEC 60227)
Section 2- PVC Insulated Cables
Unarmoured Cables
300/500V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC (NYM) - IEC 60227, SPLN42-2
Conductor PVC Inner covering
PVC Insulation PVC Sheath
300/500V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC Flexible (NYMHY) - IEC 60227, SPLN42-2
Conductor
PVC Insulation PVC Sheath
450/750V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC Flexible (IEC 60227, SPLN42-6-3)
Tape (manufacturer's option)
Conductor PVC Sheath
PVC Insulation
Filler (Polyprophylene yarn,or extruded filler up to request)
Page - 7
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 and 2) Uo/U - 300/500 V
Insulation : PVC Compound Type C Operating Temperature
Inner covering : PVC Compound Maximum 70C
Sheath : PVC Compound type ST4
Colour Ident. : Insulation : Two cores - Brown, Blue
Three cores - Brown, Black, Grey
Sheath - White
TWO ANDTHREE CORES
No.
of
Core
-
1.5 RE 1 1.38 0.7 0.4 1.2 9.5 130 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 10.0 140 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 11.0 175 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 11.0 185 7.41
4 RE 1 2.26 0.8 0.4 1.2 12.0 225 4.61
2 4 RM 7 2.6 0.8 0.4 1.2 12.5 240 4.61
6 RE 1 1 0.8 0.4 1.2 13.0 295 3.08
6 RM 7 3.1 0.8 0.4 1.2 14.0 315 3.08
10 RE 1 3.57 1.0 0.6 1.4 16.0 455 1.83
10 RM 7 4.1 1.0 0.6 1.4 17.0 495 1.83
16 RM 7 5.1 1.0 0.6 1.4 19.0 670 1.15
25 RM 7 6.4 1.2 0.8 1.4 23.0 1000 0.727
35 RM 7 7.6 1.2 1.0 1.6 26.0 1340 0.524
1.5 RE 1 1.38 0.7 0.4 1.2 10.0 150 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 10.5 160 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 11.5 205 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 12.0 220 7.41
4 RE 1 2.26 0.8 0.4 1.2 12.5 270 4.61
3 4 RM 7 2.6 0.8 0.4 1.2 13.0 290 4.61
6 RE 1 2.77 0.8 0.4 1.4 14.0 360 3.08
6 RM 7 3.1 0.8 0.4 1.4 14.5 385 3.08
10 RE 1 3.57 1.0 0.6 1.4 17.0 560 1.83
10 RM 7 4.1 1.0 0.6 1.4 18.0 600 1.83
16 RM 7 5.1 1.0 0.8 1.4 20.5 850 1.15
25 RM 7 6.4 1.2 0.8 1.6 24.5 1270 0.727
35 RM 7 7.6 1.2 1.0 1.6 27.5 1680 0.524
Note *) : RE : Round Solid Class 1
RM : Circular Stranded Class 2
/km
Conductor Nominal Nominal
of of
Number
Shape
of
Cond.
-
Weight diameter
cable cable
Thickness
at 20C
Conductor
Cross- number
of wire
Resistance
Thickness
Sheath
300/500 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC (NYM) - IEC 60227-4 , SPLN 42-2
of of of
Overall Maximum
Nominal Diameter
Conductor Insulation
(approx.)
mm kg/km mm
(approx.)
mm
section
Thickness
of Inner
covering
(approx.)
mm mm
(approx.)
mm
area
Page - 8
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 and 2) Uo/U - 300/500 V
Insulation : PVC Compound Type C Operating Temperature
Inner covering : PVC Compound Maximum 70C
Sheath : PVC Compound type ST4
Colour Ident. : Insulation : Four core - Brown, Black, Grey, Blue
Five core - Brown, Black, Grey, Blue, Green / Yellow stripe
Sheath - White
FOUR ANDFIVE CORES
No.
of
Core
-
1.5 RE 1 1.38 0.7 0.4 1.2 11.0 180 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 11.5 190 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 12.5 250 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 13.0 265 7.41
4 RE 1 2.26 0.8 0.4 1.4 14.0 340 4.61
4 4 RM 7 2.6 0.8 0.4 1.4 14.5 365 4.61
6 RE 1 2.77 0.8 0.4 1.4 15.5 460 3.08
6 RM 7 3.1 0.8 0.4 1.4 16.0 485 3.08
10 RE 1 3.57 1.0 0.6 1.4 18.5 690 1.83
10 RM 7 4.1 1.0 0.6 1.4 19.5 745 1.83
16 RM 7 5.1 1.0 0.8 1.4 22.5 1060 1.15
25 RM 7 6.4 1.2 1.0 1.6 27.5 1620 0.727
35 RM 7 7.6 1.2 1.0 1.6 30.0 2110 0.524
1.5 RE 1 1.38 0.7 0.4 1.2 11.5 210 12.1
1.5 RM 7 1.6 0.7 0.4 1.2 12.0 225 12.1
2.5 RE 1 1.78 0.8 0.4 1.2 13.5 295 7.41
2.5 RM 7 2.0 0.8 0.4 1.2 14.0 315 7.41
4 RE 1 2.26 0.8 0.6 1.4 15.5 425 4.61
5 4 RM 7 2.6 0.8 0.6 1.4 16.5 455 4.61
6 RE 1 2.77 0.8 0.6 1.4 17.0 550 3.08
6 RM 7 3.1 0.8 0.6 1.4 17.5 580 3.08
10 RE 1 3.57 1.0 0.6 1.4 20.0 840 1.83
10 RM 7 4.1 1.0 0.6 1.4 21.5 900 1.83
16 RM 7 5.1 1.0 0.8 1.6 25.0 1310 1.15
25 RM 7 6.4 1.2 1.0 1.6 30.0 1970 0.727
35 RM 7 7.6 1.2 1.2 1.6 33.5 2620 0.524
Note *) : RE : Round Solid Class 1
RM : Circular Stranded Class 2
of
Cond.
-
number
of wire
Number
300/500 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC (NYM) - IEC 60227-4 , SPLN 42-2
Conductor Nominal Nominal Overall Maximum
Nominal Diameter Thickness Shape
of Resistance
Thickness Thickness diameter Weight
of of Inner of of
area (approx.) (approx.) (approx.)
cable section Conductor Insulation at 20C
Conductor
Cross- of
(approx.)
covering Sheath cable
Page - 9
/km mm mm mm kg/km mm mm mm
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 300/500 V
Insulation : PVC Compound type D Operating Temperature
Sheath : PVC Compound type ST5 Maximum 70C
Colour Ident. : Insulation :Two core : Brown, Blue
Three core - Brown, Black, Grey
Four core - Brown, Black, Grey, Blue
Five core - Brown, Black, Grey, Blue, Green / Yellow stripe
Sheath - White
Number
of
Core
-
0.75 1.1 7.0 65 26.0
2
1 0.21 1.3 7.5 75 19.5
1.5 1.6 8.5 100 13.3
2.5 0.26 2.0 10.0 145 7.98
0.75 1.1 7.5 75 26.0
3
1 0.21 1.3 7.5 90 19.5
1.5 1.6 9.0 125 13.3
2.5 0.26 2.0 10.5 180 7.98
0.75 1.1 8.0 90 26.0
4
1 0.21 1.3 8.5 110 19.5
1.5 1.6 10.0 150 13.3
2.5 0.26 2.0 11.5 220 7.98
0.75 1.1 9.0 115 26.0
5
1 0.21 1.3 9.5 130 19.5
1.5 1.6 11.0 185 13.3
2.5 0.26 2.0 13.0 270 7.98
Note : Shape of conductor : Flexible stranded class 5
Conductor Nominal
Nominal Maximum Diameter Thickness
of of
Maximum
Thickness diameter Weight Conductor
Nominal Overall
Cross- Diameter of of
section of wire Conductor Insulation
of Resistance
cable at 20C Sheath cable
/km
(approx.)
kg/km mm mm
(approx.) (approx.) area
0.6 0.8
0.26 0.7 0.8
mm mm mm mm
0.21 0.6 0.8
0.8 1.0
0.21 0.6 0.8
0.6 0.8
0.26 0.7 1.0
0.26 0.7 1.1
0.8 1.1
0.21
300/500 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-2)
0.6 0.9
0.26 0.7 0.9
0.8 1.1
Page - 10
0.8 1.2
0.8 0.6
0.6 0.9
0.21 0.6 0.9
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Brown, Blue
Sheath - Black
TWO CORES
1.5 1.6 1.8 10.5 126 13.3
2.5 0.26 2.0 1.8 12.0 166 7.98
4 0.31 2.6 1.8 14.0 230 4.95
6 0.31 3.5 1.8 15.5 297 3.30
10 0.41 4.6 1.8 18.0 422 1.91
16 0.41 5.7 1.8 20.0 562 1.21
25 0.41 7.1 1.8 23.5 809 0.780
35 0.41 8.4 1.8 26.0 1061 0.554
50 0.41 10.1 1.8 30.5 1451 0.386
70 0.51 12.0 1.9 34.5 1949 0.272
95 0.51 13.7 2.0 39.0 2546 0.206
120 0.51 15.5 2.1 43.0 3160 0.161
Note : Shape of conductor : Flexible stranded class 5
Conductor
Maximum
Diameter
kg/km
1.6
450/750 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)
0.26
mm mm mm
(approx.) (approx.) (approx.)
mm mm mm
of
Insulation Sheath
area
Nominal Nominal
Conductor
/km
1.4
1.4
1.6
Maximum Overall
at 20C
diameter
Resistance
cable
of
Weight Thickness
of
Thickness
of wire
of
section Conductor
Nominal Diameter
Cross- of
cable
0.7
0.8
1.0
1.0
1.0
1.0
1.2
1.2
Page - 11
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black
THREE CORES
1.5 1.6 1.8 11.0 153 13.3
2.5 0.26 2.0 1.8 12.5 204 7.98
4 0.31 2.6 1.8 14.5 287 4.95
6 0.31 3.5 1.8 16.5 380 3.30
10 0.41 4.6 1.8 19.0 552 1.91
16 0.41 5.7 1.8 21.0 744 1.21
25 0.41 7.1 1.8 25.0 1085 0.780
35 0.41 8.4 1.8 28.0 1443 0.554
50 0.41 10.1 1.8 32.5 1986 0.386
70 0.51 12.0 2.0 37.0 2702 0.272
95 0.51 13.7 2.1 42.0 3542 0.206
120 0.51 15.5 2.2 46.0 4408 0.161
Note : Shape of conductor : Flexible stranded class 5
(approx.) area (approx.) (approx.)
at 20C section of wire Conductor Insulation Sheath cable cable
of Resistance of
Diameter Thickness
of Cross- Diameter of of
Nominal Maximum Thickness diameter Weight
450/750 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)
Conductor Nominal Nominal
Conductor
Overall Maximum
mm mm mm mm mm mm kg/km
0.26
0.8
1.0
1.0
1.0
1.0
1.2
/km
1.6
1.4
1.6
0.7
1.2
1.4
Page - 12
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black
FOUR CORES
1.5 1.6 1.8 12.0 181 13.3
2.5 0.26 2.0 1.8 13.5 247 7.98
4 0.31 2.6 1.8 16.0 353 4.95
6 0.31 3.5 1.8 18.0 471 3.30
10 0.41 4.6 1.8 20.5 696 1.91
16 0.41 5.7 1.8 23.5 942 1.21
25 0.41 7.1 1.8 27.5 1390 0.780
35 0.41 8.4 1.8 31.0 1856 0.554
50 0.41 10.1 1.9 36.0 2579 0.386
70 0.51 12.0 2.1 41.0 3517 0.272
95 0.51 13.7 2.2 47.0 4610 0.206
120 0.51 15.5 2.4 51.5 5769 0.161
Note : Shape of conductor : Flexible stranded class 5
450/750 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)
Overall Maximum
Thickness
Conductor Nominal Nominal
Nominal Maximum Diameter Thickness diameter Weight Conductor
Cross- Diameter of of of of of Resistance
cable at 20C section of wire Conductor Insulation Sheath cable
(approx.)
mm mm mm mm mm /km
0.26 0.7
(approx.) (approx.)
mm kg/km
area
1.0
1.2
1.2
1.4
0.8
1.0
1.0
1.0
1.4
1.6
1.6
Page - 13
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow stripe
Sheath - Black
FIVE CORES
1.5 1.6 1.8 13.0 215 13.3
2.5 0.26 2.0 1.8 14.5 290 7.98
4 0.31 2.6 1.8 17.0 425 4.95
6 0.31 3.5 1.8 19.5 567 3.30
10 0.41 4.6 1.8 22.5 847 1.91
16 0.41 5.7 1.8 25.5 1154 1.21
25 0.41 7.1 1.8 30.5 1703 0.780
35 0.41 8.4 1.9 34.0 2297 0.554
50 0.41 10.1 2.0 40.0 3200 0.386
Note : Shape of conductor : Flexible stranded class 5
Maximum
450/750 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)
Thickness diameter
Conductor Nominal Nominal Overall
Nominal Maximum Diameter Thickness Weight Conductor
Cross- Diameter of of of of of Resistance
at 20C section of wire Conductor Insulation Sheath cable
(approx.)
mm mm mm mm mm
cable
/km
0.26
(approx.) (approx.)
mm kg/km
area (approx.)
1.0
1.0
1.2
0.7
Page - 14
0.8
1.0
1.2
1.4
1.0
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 1.5mm
6 1.6 1.8 14.0 240 13.3
7 0.26 1.6 1.8 14.0 258 13.3
8 0.26 1.6 1.8 15.0 295 13.3
9 0.26 1.6 1.8 16.0 326 13.3
10 0.26 1.6 1.8 17.0 360 13.3
12 0.26 1.6 1.8 17.5 408 13.3
14 0.26 1.6 1.8 18.5 458 13.3
15 0.26 1.6 1.8 19.0 489 13.3
16 0.26 1.6 1.8 19.0 514 13.3
18 0.26 1.6 1.8 20.0 562 13.3
19 0.26 1.6 1.8 20.0 580 13.3
20 0.26 1.6 1.8 21.0 614 13.3
24 0.26 1.6 1.8 23.5 725 13.3
30 0.26 1.6 1.8 24.5 868 13.3
32 0.26 1.6 1.8 25.0 921 13.3
37 0.26 1.6 1.8 26.5 1034 13.3
40 0.26 1.6 1.8 27.5 1110 13.3
50 0.26 1.6 1.9 30.5 1374 13.3
52 0.26 1.6 1.9 31.5 1424 13.3
60 0.26 1.6 1.9 33.0 1617 13.3
61 0.26 1.6 1.9 33.0 1635 13.3
Note : Shape of conductor : Flexible stranded class 5
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
Diameter
of
0.7
0.7
0.7
0.7
0.7
0.7
(approx.)
mm mm mm mm mm /km
0.26 0.7
0.7
No Diameter of
kg/km
core (approx.) (approx.) (approx.)
Sheath cable at 20C of of wire Conductor Insulation cable
Thickness
450/750 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)
Nominal Nominal Overall
Weight Conductor
Conductor
Maximum
of of of Resistance
Page - 15
0.7
0.7
0.7
0.7
Maximum
Thickness diameter
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 5) Uo/U - 450/750 V
Insulation : PVC Compound type D Operating Temperature
Filler : Suitable material Maximum 70C
Sheath : PVC Compound type ST5
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 2.5mm
6 2.0 1.8 15.5 331 7.98
7 0.26 2.0 1.8 15.5 358 7.98
8 0.26 2.0 1.8 17.0 406 7.98
9 0.26 2.0 1.8 18.0 455 7.98
10 0.26 2.0 1.8 19.5 505 7.98
12 0.26 2.0 1.8 20.0 577 7.98
14 0.26 2.0 1.8 21.0 654 7.98
15 0.26 2.0 1.8 21.5 697 7.98
16 0.26 2.0 1.8 22.0 732 7.98
18 0.26 2.0 1.8 23.0 806 7.98
19 0.26 2.0 1.8 23.0 834 7.98
20 0.26 2.0 1.8 24.0 887 7.98
24 0.26 2.0 1.8 27.0 1049 7.98
30 0.26 2.0 1.8 28.5 1266 7.98
32 0.26 2.0 1.8 29.0 1342 7.98
37 0.26 2.0 1.9 31.0 1527 7.98
40 0.26 2.0 1.9 32.0 1644 7.98
50 0.26 2.0 2.0 35.5 2037 7.98
52 0.26 2.0 2.0 36.5 2115 7.98
60 0.26 2.0 2.1 39.0 2423 7.98
61 0.26 2.0 2.1 39.0 2450 7.98
Note : Shape of conductor : Flexible stranded class 5
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
/km
0.26 0.8
0.8
mm mm mm mm mm
of of wire Conductor Insulation
kg/km
core (approx.) (approx.) (approx.) (approx.)
cable at 20C
diameter Weight Conductor
of Resistance of of
Sheath cable
No Diameter of of
Thickness Thickness
450/750 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC Flexible (IEC 60227-5, SPLN 42-6-3)
Conductor Nominal Nominal Overall
Page - 16
Maximum
Maximum Diameter
0.8
0.8
0.8
0.8
Section 2- PVC Insulated Cables
Unarmoured Cables
Constructions :
Conductor (Annealed Copper)
Insulation (PVC Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC (acc. to IEC 60502-1)
Page - 17
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
1
2
4
5
3
1
2
5
3
4
1
2
5
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Sheath : PVC Compound type ST1 Maximum 70C
Colour Ident. : Insulation - Brown
Sheath - Black
SINGLE CORE
-
1.5 RE 1 1.38 0.8 1.4 5.6 50 12.1
1.5 RM 7 1.6 0.8 1.4 5.8 50 12.1
2.5 RE 1 1.78 0.8 1.4 6.0 60 7.41
2.5 RM 7 2.0 0.8 1.4 6.2 65 7.41
4 RE 1 2.26 1.0 1.4 6.9 85 4.61
4 RM 7 2.6 1.0 1.4 7.2 90 4.61
6 RM 7 3.1 1.0 1.4 7.7 115 3.08
10 RM 7 4.1 1.0 1.4 8.7 160 1.83
16 RM 7 5.1 1.0 1.4 9.7 225 1.15
25 RM 7 6.4 1.2 1.4 11.5 335 0.727
35 RM 7 7.6 1.2 1.4 12.5 440 0.524
50 RM 19 9.2 1.4 1.4 14.5 600 0.387
70 RM 19 10.9 1.4 1.4 16.5 810 0.268
95 RM 19 12.6 1.6 1.5 19.0 1090 0.193
120 RM 37 14.2 1.6 1.5 20.5 1335 0.153
150 RM 37 15.9 1.8 1.6 22.5 1660 0.124
185 RM 37 17.6 2.0 1.7 25.0 2025 0.0991
240 RM 61 20.3 2.2 1.8 28.0 2650 0.0754
300 RM 61 22.7 2.4 1.9 31.0 3275 0.0601
400 RM 61 25.7 2.6 2.0 35.0 4190 0.0470
500 RM 61 28.8 2.8 2.1 38.5 5200 0.0366
630 RM 91 32.6 2.8 2.2 42.5 6505 0.0283
800 RM 127 37.1 2.8 2.3 47.5 8285 0.0221
1000 RM 127 41.6 3.0 2.5 52.5 10360 0.0176
Note *) RE : Round Solid Class 1
RM : Circular Stranded Class 2
Page - 18
mm mm
Sheath
mm
(approx.)
cond. Conductor Insulation
/km mm
area
mm kg/km
(approx.) (approx.)
number
cable
of of
Conductor Thickness
at 20C
Thickness
cable
Nominal Overall Maximum
Weight
of Resistance
Nominal
Shape
of of of
diameter
PVC/PVC (IEC 60502-1)
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
Conductor
number
of wire
Nominal
Cross-
section
Diameter
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Blue
Sheath - Black
TWO CORES
-
1.5 RE 1 1.38 0.8 1.8 10.0 115 12.1
1.5 RM 7 1.6 0.8 1.8 10.5 125 12.1
2.5 RE 1 1.78 0.8 1.8 10.5 145 7.41
2.5 RM 7 2.0 0.8 1.8 11.0 155 7.41
4 RE 1 2.26 1.0 1.8 12.5 200 4.61
4 RM 7 2.6 1.0 1.8 13.0 215 4.61
6 RM 7 3.1 1.0 1.8 14.0 270 3.08
10 RM 7 4.1 1.0 1.8 16.0 375 1.83
16 RM 7 5.1 1.0 1.8 18.0 520 1.15
25 RM 7 6.4 1.2 1.8 21.5 765 0.727
35 RM 7 7.6 1.2 1.8 24.0 1000 0.524
50 RM 19 9.2 1.4 1.8 28.0 1370 0.387
70 RM 19 10.9 1.4 1.9 31.5 1825 0.268
95 RM 19 12.6 1.6 2.0 36.0 2440 0.193
120 RM 37 14.2 1.6 2.1 39.5 2990 0.153
150 RM 37 15.9 1.8 2.2 44.0 3715 0.124
185 RM 37 17.6 2.0 2.4 48.5 4545 0.0991
240 RM 61 20.3 2.2 2.6 55.0 5945 0.0754
300 RM 61 22.7 2.4 2.7 60.5 7325 0.0601
Note *) RE : Round Solid Class 1
RM : Circular Stranded Class 2
Page - 19
number mm mm
Insulation
(approx.)
Weight
of
Nominal Overall
mm
Maximum
Conductor
Resistance
(approx.)
/km kg/km
at 20C cable cable
Shape
of
Conductor
of
diameter
of
Sheath
mm
Conductor
mm
Conductor section area
(approx.)
Cross- number
of wire
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
Diameter
of
Nominal
Thickness
PVC/PVC (IEC 60502-1)
Nominal
of
Thickness
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black
THREE CORES
-
1.5 RE 1 1.38 0.8 1.8 10.5 140 12.1
1.5 RM 7 1.6 0.8 1.8 11.0 150 12.1
2.5 RE 1 1.78 0.8 1.8 11.5 180 7.41
2.5 RM 7 2.0 0.8 1.8 11.5 190 7.41
4 RE 1 2.26 1.0 1.8 13.0 260 4.61
4 RM 7 2.6 1.0 1.8 14.0 275 4.61
6 RM 7 3.1 1.0 1.8 15.0 350 3.08
10 RM 7 4.1 1.0 1.8 17.0 500 1.83
16 RM 7 5.1 1.0 1.8 19.0 700 1.15
25 RM 7 6.4 1.2 1.8 23.0 1045 0.727
35 RM 7 7.6 1.2 1.8 25.5 1380 0.524
50 SM 19 6.8 1.4 1.8 24.0 1710 0.387
70 SM 19 8.2 1.4 2.0 27.5 2365 0.268
95 SM 19 9.7 1.6 2.1 32.0 3265 0.193
120 SM 37 10.9 1.6 2.2 34.5 3905 0.153
150 SM 37 11.9 1.8 2.3 37.5 4785 0.124
185 SM 37 13.6 2.0 2.5 42.5 5965 0.0991
240 SM 37 15.8 2.2 2.7 48.0 7970 0.0754
300 SM 37 17.5 2.4 2.9 53.0 9920 0.0601
Note *) RE : Round Solid Class 1
RM : Circular Stranded Class 2
RM : Three Segmental Stranded Compacted Class 2
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC (IEC 60502-1)
at 20C section area Conductor Insulation Sheath
(approx.) (approx.) (approx.)
of wire conductor
kg/km mm mm mm mm mm /km Number
Page - 20
of
cable cable
Conductor
of
diameter Weight
Resistance of number
Shape Diameter Thickness Thickness
of Cross- of of
Nominal
Conductor Nominal Nominal Overall Maximum
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black
FOUR CORES
-
1.5 RE 1 1.38 0.8 1.8 11.0 170 12.1
1.5 RM 7 1.6 0.8 1.8 11.5 180 12.1
2.5 RE 1 1.78 0.8 1.8 12.0 220 7.41
2.5 RM 7 2.0 0.8 1.8 12.5 235 7.41
4 RE 1 2.26 1.0 1.8 14.5 320 4.61
4 RM 7 2.6 1.0 1.8 15.0 340 4.61
6 RM 7 3.1 1.0 1.8 16.5 435 3.08
10 RM 7 4.1 1.0 1.8 18.5 635 1.83
16 RM 7 5.1 1.0 1.8 21.0 900 1.15
25 RM 7 6.4 1.2 1.8 25.0 1345 0.727
35 RM 7 7.6 1.2 1.8 28.0 1780 0.524
50 SM 19 8.1 1.4 1.9 27.5 2210 0.387
70 SM 19 9.7 1.4 2.1 31.5 3090 0.268
95 SM 19 11.4 1.6 2.2 36.5 4255 0.193
120 SM 37 12.9 1.6 2.4 40.0 5100 0.153
150 SM 37 14.2 1.8 2.5 43.5 6265 0.124
185 SM 37 16.0 2.0 2.7 49.0 7815 0.0991
240 SM 37 18.2 2.2 2.9 54.5 10425 0.0754
300 SM 37 20.6 2.4 3.1 61.0 12985 0.0601
Note *) RE : Round Solid Class 1
RM : Circular Stranded Class 2
RM : Four Segmental Stranded Compacted Class 2
(approx.)
Sheath cable at 20C
Conductor
Page - 21
(approx.) (approx.)
/km mm mm mm Number mm kg/km mm
Nominal Diameter Thickness Shape
of number of
section area
Cross- of of of
cable Conductor Insulation conductor of wire
Thickness diameter
Overall
of Resistance
Maximum
Weight
Conductor Nominal Nominal
PVC/PVC (IEC 60502-1)
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black
FIVE CORES
-
1.5 RE 1 1.38 0.8 1.8 12.0 200 12.1
1.5 RM 7 1.6 0.8 1.8 12.5 215 12.1
2.5 RE 1 1.78 0.8 1.8 13.0 265 7.41
2.5 RM 7 2.0 0.8 1.8 14.0 280 7.41
4 RE 1 2.26 1.0 1.8 15.5 385 4.61
4 RM 7 2.6 1.0 1.8 16.5 410 4.61
6 RM 7 3.1 1.0 1.8 18.0 530 3.08
10 RM 7 4.1 1.0 1.8 20.5 775 1.83
16 RM 7 5.1 1.0 1.8 23.0 1100 1.15
25 RM 7 6.4 1.2 1.8 28.0 1655 0.727
35 RM 7 7.6 1.2 1.9 31.0 2200 0.524
50 RM 19 9.2 1.4 2.1 37.0 3080 0.387
Note *) RE : Round Solid Class 1
RM : Circular Stranded Class 2
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
Insulation conductor cable at 20C
Maximum
Page - 22
(approx.) (approx.)
PVC/PVC (IEC 60502-1)
Sheath cable
(approx.)
section area Conductor of wire
Resistance Cross-
mm mm mm mm Number
of of number
/km mm kg/km
of of of of
Conductor Nominal Diameter Thickness Thickness diameter Weight Shape
Conductor Nominal Nominal Overall
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 1.5mm (Solid conductor)
No Nominal
of Cross-section
core area
mm
6 1.5 RE 1 1.38 0.8 1.8 13.0 230 12.1
7 1.5 RE 1 1.38 0.8 1.8 13.0 245 12.1
8 1.5 RE 1 1.38 0.8 1.8 14.0 280 12.1
9 1.5 RE 1 1.38 0.8 1.8 15.0 310 12.1
10 1.5 RE 1 1.38 0.8 1.8 16.5 345 12.1
12 1.5 RE 1 1.38 0.8 1.8 17.0 395 12.1
14 1.5 RE 1 1.38 0.8 1.8 17.5 445 12.1
15 1.5 RE 1 1.38 0.8 1.8 18.0 470 12.1
16 1.5 RE 1 1.38 0.8 1.8 18.5 500 12.1
18 1.5 RE 1 1.38 0.8 1.8 19.5 550 12.1
19 1.5 RE 1 1.38 0.8 1.8 19.5 565 12.1
20 1.5 RE 1 1.38 0.8 1.8 20.0 600 12.1
21 1.5 RE 1 1.38 0.8 1.8 21.0 625 12.1
24 1.5 RE 1 1.38 0.8 1.8 22.5 710 12.1
30 1.5 RE 1 1.38 0.8 1.8 24.0 855 12.1
32 1.5 RE 1 1.38 0.8 1.8 24.5 905 12.1
37 1.5 RE 1 1.38 0.8 1.8 26.0 1025 12.1
40 1.5 RE 1 1.38 0.8 1.8 27.0 1105 12.1
50 1.5 RE 1 1.38 0.8 1.9 29.5 1350 12.1
52 1.5 RE 1 1.38 0.8 1.9 30.5 1405 12.1
60 1.5 RE 1 1.38 0.8 2.0 32.5 1615 12.1
61 1.5 RE 1 1.38 0.8 2.0 32.5 1635 12.1
Note RE : Round solid class 1
(approx.) (approx.) (approx.)
at 20C cable cable Insulation Sheath Conductor
kg/km /km
Page - 23
mm mm mm mm
of of of Resistance
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC (IEC 60502-1)
Conductor Nominal Nominal
Diameter Thickness Thickness Shape
Overall Maximum
diameter Weight Conductor
of of Number
of wire
Number
of
conductor
-
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 1.5mm (Stranded conductor)
No Nominal
of Cross-section
core area
mm
6 1.5 7 1.6 0.8 1.8 13.5 240 12.1
7 1.5 7 1.6 0.8 1.8 13.5 260 12.1
8 1.5 7 1.6 0.8 1.8 14.5 295 12.1
9 1.5 7 1.6 0.8 1.8 16.0 330 12.1
10 1.5 7 1.6 0.8 1.8 17.0 365 12.1
12 1.5 7 1.6 0.8 1.8 17.5 420 12.1
14 1.5 7 1.6 0.8 1.8 18.5 475 12.1
15 1.5 7 1.6 0.8 1.8 19.0 500 12.1
16 1.5 7 1.6 0.8 1.8 19.5 530 12.1
18 1.5 7 1.6 0.8 1.8 20.5 585 12.1
19 1.5 7 1.6 0.8 1.8 20.5 600 12.1
20 1.5 7 1.6 0.8 1.8 21.0 635 12.1
21 1.5 7 1.6 0.8 1.8 22.0 665 12.1
24 1.5 7 1.6 0.8 1.8 24.0 755 12.1
30 1.5 7 1.6 0.8 1.8 25.5 910 12.1
32 1.5 7 1.6 0.8 1.8 26.0 965 12.1
37 1.5 7 1.6 0.8 1.8 27.5 1090 12.1
40 1.5 7 1.6 0.8 1.8 28.5 1175 12.1
50 1.5 7 1.6 0.8 1.9 31.0 1440 12.1
52 1.5 7 1.6 0.8 1.9 32.0 1495 12.1
60 1.5 7 1.6 0.8 2.0 34.5 1720 12.1
61 1.5 7 1.6 0.8 2.0 34.5 1745 12.1
Note : RM : Circular Stranded Class 2
Page - 24
Shape Diameter
PVC/PVC (IEC 60502-1)
Conductor Nominal Maximum
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
at 20C cable
of of
Conductor Thickness Thickness
Nominal Overall
of of of
Conductor Insulation Sheath
Resistance
diameter Weight
- Number
cable
(approx.) (approx.) (approx.)
kg/km /km mm mm mm mm
RM
RM
RM
RM
RM
RM
RM
RM
of Number
conductor of wire
RM
RM
RM
RM
RM
RM
RM
RM
RM
RM
RM
RM
RM
RM
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 2.5mm (Solid conductor)
No Nominal
of Cross-section
core area
mm
6 2.5 RE 1 1.78 0.8 1.8 14.5 300 7.41
7 2.5 RE 1 1.78 0.8 1.8 14.5 330 7.41
8 2.5 RE 1 1.78 0.8 1.8 15.5 375 7.41
9 2.5 RE 1 1.78 0.8 1.8 16.5 420 7.41
10 2.5 RE 1 1.78 0.8 1.8 18.0 465 7.41
12 2.5 RE 1 1.78 0.8 1.8 18.5 535 7.41
14 2.5 RE 1 1.78 0.8 1.8 19.5 610 7.41
15 2.5 RE 1 1.78 0.8 1.8 20.0 645 7.41
16 2.5 RE 1 1.78 0.8 1.8 20.5 685 7.41
18 2.5 RE 1 1.78 0.8 1.8 21.5 755 7.41
19 2.5 RE 1 1.78 0.8 1.8 21.5 780 7.41
20 2.5 RE 1 1.78 0.8 1.8 22.0 825 7.41
21 2.5 RE 1 1.78 0.8 1.8 23.5 865 7.41
24 2.5 RE 1 1.78 0.8 1.8 25.0 985 7.41
30 2.5 RE 1 1.78 0.8 1.8 26.5 1195 7.41
32 2.5 RE 1 1.78 0.8 1.8 27.0 1265 7.41
37 2.5 RE 1 1.78 0.8 1.9 28.5 1435 7.41
40 2.5 RE 1 1.78 0.8 1.9 30.0 1545 7.41
50 2.5 RE 1 1.78 0.8 2.0 33.0 1920 7.41
52 2.5 RE 1 1.78 0.8 2.0 34.0 1995 7.41
60 2.5 RE 1 1.78 0.8 2.1 36.5 2295 7.41
61 2.5 RE 1 1.78 0.8 2.1 36.5 2325 7.41
Note : RE : Round Solid Class 1
Nominal Nominal
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC (IEC 60502-1)
Maximum Conductor Overall
Weight Conductor Shape Thickness Thickness
Number
Diameter
of of of
diameter
of of
Page - 25
of
Conductor Insulation Sheath cable
(approx.)
mm
(approx.) (approx.)
mm mm mm kg/km
Resistance
cable at 20C
/km Number -
conductor of wire
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 2.5mm (Stranded conductor)
No Nominal
of Cross-section
core area
mm
6 2.5 RM 7 2.0 0.8 1.8 15.0 320 7.41
7 2.5 RM 7 2.0 0.8 1.8 15.0 345 7.41
8 2.5 RM 7 2.0 0.8 1.8 16.0 395 7.41
9 2.5 RM 7 2.0 0.8 1.8 17.0 440 7.41
10 2.5 RM 7 2.0 0.8 1.8 18.5 490 7.41
12 2.5 RM 7 2.0 0.8 1.8 19.5 565 7.41
14 2.5 RM 7 2.0 0.8 1.8 20.5 640 7.41
15 2.5 RM 7 2.0 0.8 1.8 21.0 680 7.41
16 2.5 RM 7 2.0 0.8 1.8 21.5 725 7.41
18 2.5 RM 7 2.0 0.8 1.8 22.5 795 7.41
19 2.5 RM 7 2.0 0.8 1.8 22.5 825 7.41
20 2.5 RM 7 2.0 0.8 1.8 23.0 870 7.41
21 2.5 RM 7 2.0 0.8 1.8 24.0 910 7.41
24 2.5 RM 7 2.0 0.8 1.8 26.5 1040 7.41
30 2.5 RM 7 2.0 0.8 1.8 28.0 1260 7.41
32 2.5 RM 7 2.0 0.8 1.8 28.5 1335 7.41
37 2.5 RM 7 2.0 0.8 1.9 30.0 1515 7.41
40 2.5 RM 7 2.0 0.8 1.9 31.5 1635 7.41
50 2.5 RM 7 2.0 0.8 2.0 34.5 2025 7.41
52 2.5 RM 7 2.0 0.8 2.0 35.5 2105 7.41
60 2.5 RM 7 2.0 0.8 2.1 38.0 2420 7.41
61 2.5 RM 7 2.0 0.8 2.1 38.0 2455 7.41
Note : RM : Circular Stranded Class 2
Page - 26
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Diameter Thickness Thickness Shape
at 20C
of of of
Conductor
Conductor
of of Resistance
diameter Weight
- Number
Number
conductor of wire
(approx.)
Insulation Sheath
of
cable
/km mm mm mm mm kg/km
cable
(approx.) (approx.)
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 1) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 4mm (Solid conductor)
No Nominal
of Cross-section
core area
mm
6 4 RE 1 2.26 1.0 1.8 17.0 440 4.61
7 4 RE 1 2.26 1.0 1.8 17.0 485 4.61
8 4 RE 1 2.26 1.0 1.8 18.5 555 4.61
9 4 RE 1 2.26 1.0 1.8 20.0 625 4.61
10 4 RE 1 2.26 1.0 1.8 21.5 690 4.61
12 4 RE 1 2.26 1.0 1.8 22.0 800 4.61
14 4 RE 1 2.26 1.0 1.8 23.5 915 4.61
15 4 RE 1 2.26 1.0 1.8 24.0 970 4.61
16 4 RE 1 2.26 1.0 1.8 24.5 1035 4.61
18 4 RE 1 2.26 1.0 1.8 26.0 1140 4.61
19 4 RE 1 2.26 1.0 1.8 26.0 1185 4.61
20 4 RE 1 2.26 1.0 1.8 27.0 1250 4.61
21 4 RE 1 2.26 1.0 1.8 28.0 1310 4.61
24 4 RE 1 2.26 1.0 1.9 30.5 1495 4.61
30 4 RE 1 2.26 1.0 2.0 32.5 1840 4.61
32 4 RE 1 2.26 1.0 2.0 33.0 1950 4.61
37 4 RE 1 2.26 1.0 2.1 35.5 2235 4.61
40 4 RE 1 2.26 1.0 2.1 37.0 2410 4.61
50 4 RE 1 2.26 1.0 2.3 41.0 3010 4.61
52 4 RE 1 2.26 1.0 2.3 42.0 3130 4.61
60 4 RE 1 2.26 1.0 2.4 45.0 3575 4.61
61 4 RE 1 2.26 1.0 2.4 45.0 3625 4.61
Note RE : Round Solid Class 1
Page - 27
Insulation Sheath
kg/km /km mm mm mm mm
(approx.) (approx.)
cable cable
Weight
at 20C
of of of
Conductor
Conductor
of of Resistance
Thickness Thickness diameter Shape
of Number
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
PVC/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Diameter
conductor of wire
Number
(approx.)
-
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler (if necessary) : Suitable material Maximum 70C
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 4mm (Stranded conductor)
No Nominal
of Cross-section
core area
mm
6 4 RM 7 2.6 1.0 1.8 18.0 470 4.61
7 4 RM 7 2.6 1.0 1.8 18.0 515 4.61
8 4 RM 7 2.6 1.0 1.8 19.5 585 4.61
9 4 RM 7 2.6 1.0 1.8 21.0 660 4.61
10 4 RM 7 2.6 1.0 1.8 22.5 735 4.61
12 4 RM 7 2.6 1.0 1.8 23.5 850 4.61
14 4 RM 7 2.6 1.0 1.8 24.5 970 4.61
15 4 RM 7 2.6 1.0 1.8 25.5 1030 4.61
16 4 RM 7 2.6 1.0 1.8 26.0 1095 4.61
18 4 RM 7 2.6 1.0 1.8 27.5 1210 4.61
19 4 RM 7 2.6 1.0 1.8 27.5 1255 4.61
20 4 RM 7 2.6 1.0 1.8 28.5 1325 4.61
21 4 RM 7 2.6 1.0 1.8 30.0 1390 4.61
24 4 RM 7 2.6 1.0 1.9 32.5 1585 4.61
30 4 RM 7 2.6 1.0 2.0 34.5 1950 4.61
32 4 RM 7 2.6 1.0 2.0 35.0 2070 4.61
37 4 RM 7 2.6 1.0 2.1 37.5 2365 4.61
40 4 RM 7 2.6 1.0 2.1 39.0 2555 4.61
50 4 RM 7 2.6 1.0 2.3 43.5 3190 4.61
52 4 RM 7 2.6 1.0 2.3 44.5 3315 4.61
60 4 RM 7 2.6 1.0 2.4 47.5 3790 4.61
61 4 RM 7 2.6 1.0 2.4 47.5 3845 4.61
Note RM : Circular Stranded Class 2
600/1000 V PVC INSULATED AND PVC SHEATHED CABLES
of
Nominal
Page - 28
Overall
Diameter Thickness Thickness
PVC/PVC (IEC 60502-1)
Maximum Nominal
of
at 20C cable
Conductor
of of Resistance
- kg/km
conductor of wire
Conductor
/km mm mm mm mm
Weight
of
Shape
Number of
diameter
cable Insulation Sheath
Number
(approx.) (approx.)
Conductor
(approx.)
Section 2- PVC Insulated Cables
Unarmoured Cables
Constructions :
Conductor (Annealed Copper)
Insulation (PVC Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Copper Tape screen
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
600/1000V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
PVC/PVC-S (IEC 60502-1)
Page - 29
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Copper wire screen.
* Polyethylene / Low smoke Halogen Free sheathed
5
6
7
1
2
3
4
1
5
2
3
4
6
7
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Blue
Sheath - Black
TWO CORES
1.5 RE 1 1.38 0.8 0.1 1.8 10.5 145 12.1
1.5 RM 7 1.6 0.8 0.1 1.8 11.0 150 12.1
2.5 RE 1 1.78 0.8 0.1 1.8 11.5 175 7.41
2.5 RM 7 2.0 0.8 0.1 1.8 11.5 180 7.41
4 RE 1 2.26 1.0 0.1 1.8 13.0 240 4.61
4 RM 7 2.6 1.0 0.1 1.8 13.5 245 4.61
6 RM 7 3.1 1.0 0.1 1.8 14.5 305 3.08
10 RM 7 4.1 1.0 0.1 1.8 16.5 420 1.83
16 RM 7 5.1 1.0 0.1 1.8 18.5 570 1.15
25 RM 7 6.4 1.2 0.1 1.8 22.0 825 0.727
35 RM 7 7.6 1.2 0.1 1.8 24.5 1065 0.524
50 RM 19 9.2 1.4 0.1 1.8 28.5 1450 0.387
70 RM 19 10.9 1.4 0.1 1.9 32.0 1910 0.268
95 RM 19 12.6 1.6 0.1 2.0 36.5 2545 0.193
120 RM 37 14.2 1.6 0.1 2.1 40.0 3105 0.153
150 RM 37 15.9 1.8 0.1 2.2 44.5 3840 0.124
185 RM 37 17.6 2.0 0.1 2.4 49.0 4680 0.0991
240 RM 61 20.3 2.2 0.1 2.6 55.5 6100 0.0754
300 RM 61 22.7 2.4 0.1 2.7 61.5 7525 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
Page - 30
(approx.)
cable
mm mm
Sheath
mm
Insulation
(approx.) (approx.)
Copper tape
mm /km kg/km
Weight
of
Maximum
Conductor
Resistance
at 20C cable
of
Conductor
mm
Conductor section area
(approx.)
-
Nominal
Cross- of
Nominal
Thickness
of
Nominal
Thickness
600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
Diameter
Nominal
PVC/PVC-S (IEC 60502-1)
Shape
of
Thickness
Overall
diameter
of
Number
of number
of wire cond.
mm
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black
THREE CORES
1.5 RE 1 1.38 0.8 0.1 1.8 11.0 170 12.1
1.5 RM 7 1.6 0.8 0.1 1.8 11.5 175 12.1
2.5 RE 1 1.78 0.8 0.1 1.8 12.0 215 7.41
2.5 RM 7 2.0 0.8 0.1 1.8 12.5 220 7.41
4 RE 1 2.26 1.0 0.1 1.8 14.0 300 4.61
4 RM 7 2.6 1.0 0.1 1.8 14.5 305 4.61
6 RM 7 3.1 1.0 0.1 1.8 15.0 385 3.08
10 RM 7 4.1 1.0 0.1 1.8 17.5 545 1.83
16 RM 7 5.1 1.0 0.1 1.8 20.0 755 1.15
25 RM 7 6.4 1.2 0.1 1.8 23.5 1110 0.727
35 RM 7 7.6 1.2 0.1 1.8 26.0 1445 0.524
50 SM 19 6.8 1.4 0.1 1.9 25.0 1775 0.387
70 SM 19 8.2 1.4 0.1 2.0 28.0 2440 0.268
95 SM 19 9.7 1.6 0.1 2.1 32.5 3350 0.193
120 SM 37 10.9 1.6 0.1 2.2 35.0 3995 0.153
150 SM 37 11.9 1.8 0.1 2.4 38.5 4885 0.124
185 SM 37 13.6 2.0 0.1 2.5 43.0 6080 0.0991
240 SM 37 15.8 2.2 0.1 2.7 48.5 8095 0.0754
300 SM 37 17.5 2.4 0.1 2.9 53.5 10060 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2
Page - 31
(approx.) (approx.) (approx.)
Sheath cable cable
of
600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
PVC/PVC-S (IEC 60502-1)
section area
(approx.)
/km
Nominal
Thickness
of
Copper tape
mm
at 20C
of of Resistance
mm mm mm kg/km mm mm
Insulation cond. of wire
Cross- of of of number
Nominal Diameter Thickness Shape Thickness diameter Weight Conductor
Conductor Nominal Nominal Overall Maximum
- Number
Conductor
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black
FOUR CORES
1.5 RE 1 1.38 0.8 0.1 1.8 12.0 205 12.1
1.5 RM 7 1.6 0.8 0.1 1.8 12.5 210 12.1
2.5 RE 1 1.78 0.8 0.1 1.8 13.0 260 7.41
2.5 RM 7 2.0 0.8 0.1 1.8 13.5 265 7.41
4 RE 1 2.26 1.0 0.1 1.8 15.0 370 4.61
4 RM 7 2.6 1.0 0.1 1.8 15.5 380 4.61
6 RM 7 3.1 1.0 0.1 1.8 17.0 485 3.08
10 RM 7 4.1 1.0 0.1 1.8 19.5 685 1.83
16 RM 7 5.1 1.0 0.1 1.8 21.5 960 1.15
25 RM 7 6.4 1.2 0.1 1.8 26.0 1415 0.727
35 RM 7 7.6 1.2 0.1 1.8 28.5 1860 0.524
50 SM 19 8.1 1.4 0.1 2.0 28.5 2305 0.387
70 SM 19 9.7 1.4 0.1 2.1 32.0 3180 0.268
95 SM 19 11.4 1.6 0.1 2.2 37.0 4360 0.193
120 SM 37 12.9 1.6 0.1 2.4 40.5 5220 0.153
150 SM 37 14.2 1.8 0.1 2.5 44.5 6395 0.124
185 SM 37 16.0 2.0 0.1 2.7 49.5 7965 0.0991
240 SM 37 18.2 2.2 0.1 2.9 55.5 10595 0.0754
300 SM 37 20.6 2.4 0.1 3.1 61.5 13180 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Four Segmental Stranded Compacted Class 2
Page - 32
Thickness
of
Copper tape
mm
(approx.)
600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
PVC/PVC-S (IEC 60502-1)
(approx.) (approx.)
at 20C
mm mm mm mm mm kg/km /km
(approx.)
of Resistance
section area Conductor Insulation cond. of wire Sheath cable cable
diameter Weight Conductor
Cross- of of of number of of
Nominal Diameter Thickness Thickness Shape Minimum
Conductor Nominal Nominal Overall Maximum Nominal
- Number
Section 2- PVC Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue,, Green / Yellow Stripe
Sheath - Black
FIVE CORES
1.5 RE 1 1.38 0.8 0.1 1.8 12.5 240 12.1
1.5 RM 7 1.6 0.8 0.1 1.8 13.5 245 12.1
2.5 RE 1 1.78 0.8 0.1 1.8 14.0 305 7.41
2.5 RM 7 2.0 0.8 0.1 1.8 14.5 315 7.41
4 RE 1 2.26 1.0 0.1 1.8 16.5 435 4.61
4 RM 7 2.6 1.0 0.1 1.8 17.0 450 4.61
6 RM 7 3.1 1.0 0.1 1.8 18.5 580 3.08
10 RM 7 4.1 1.0 0.1 1.8 21.0 830 1.83
16 RM 7 5.1 1.0 0.1 1.8 24.0 1170 1.15
25 RM 7 6.4 1.2 0.1 1.8 28.5 1730 0.727
35 RM 7 7.6 1.2 0.1 1.9 31.5 2290 0.524
50 RM 19 9.2 1.4 0.1 2.1 37.5 3060 0.387
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
Page - 33
Thickness
of
Copper tape
mm
(approx.) (approx.) (approx.)
Maximum
Resistance
cable at 20C
Weight
mm kg/km /km
(approx.)
600/1000 V PVC INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
PVC/PVC-S (IEC 60502-1)
Sheath cable section area Conductor Insulation cond. of wire
mm mm mm mm -
Conductor
Cross- of of of number of of of
Diameter Thickness Thickness diameter
Nominal Nominal Overall Nominal
Number
Shape Minimum
Conductor
Nominal
Section 2 - PVC Insulated Cables
Armoured Cables
Constructions :
Conductor (Annealed Copper)
Insulation (PVC Compound)
Inner Covering (PVC Compound)
Round Aluminium Wire armour
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
Constructions :
Conductor (Annealed Copper)
Insulation (PVC Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Galvanized Round Steel Wire armour
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
600/1000 V PVC INSULATED, ALUMINIUMWIRE ARMOURED AND PVC SHEATHED CABLES
PVC / AWA / PVC (acc. to IEC 60502-1)
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (acc. to IEC 60502-1)
Page - 34
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
1
2
3
4
5
6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
1
2
3
4
5
6
7
8
Section 2 - PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Inner covering : PVC Compound ST1 Maximum 70C
Armour : AluminiumWire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown
Sheath - Black
SINGLE CORE
16 RM 7 5.1 1.0 1.0 0.8 1.8 14.5 370 1.15
25 RM 7 6.4 1.2 1.0 0.8 1.8 16.5 495 0.727
35 RM 7 7.6 1.2 1.0 0.8 1.8 17.5 620 0.524
50 RM 19 9.2 1.4 1.0 1.25 1.8 20.5 845 0.387
70 RM 19 10.9 1.4 1.0 1.25 1.8 22.0 1075 0.268
95 RM 19 12.6 1.6 1.0 1.25 1.8 24.5 1380 0.193
120 RM 37 14.2 1.6 1.0 1.6 1.8 27.0 1705 0.153
150 RM 37 15.9 1.8 1.0 1.6 1.8 29.0 2055 0.124
185 RM 37 17.6 2.0 1.0 1.6 1.8 31.0 2450 0.0991
240 RM 61 20.3 2.2 1.0 1.6 1.9 34.0 3110 0.0754
300 RM 61 22.7 2.4 1.0 2.0 2.0 38.0 3865 0.0601
400 RM 61 25.7 2.6 1.2 2.0 2.1 42.0 4885 0.0470
500 RM 61 28.8 2.8 1.2 2.0 2.2 46.0 5965 0.0366
630 RM 91 32.6 2.8 1.2 2.0 2.4 50.0 7335 0.0283
800 RM 127 37.1 2.8 1.4 2.5 2.5 56.0 9410 0.0221
1000 RM 127 41.6 3.0 1.4 2.5 2.7 61.0 11635 0.0176
RM : Circular Stranded Class 2
Page - 35
mm mm
Sheath cable
Diameter
cable
Aluminium
wire
diameter of
Conductor
Overall
Insulation
Maximum
(approx.) area
mm - Number /km mm
of
Thickness
at 20C
kg/km
(approx.) (approx.)
diameter
of
Conductor
Conductor
section
Weight
of
Nominal
of
Shape
PVC / AWA / PVC (IEC 60502-1)
600/1000 V PVC INSULATED,ALUMINIUMWIRE ARMOURED AND PVC SHEATHED CABLES
Nominal
Cross- Resistance
Nominal
Thickness
of
Nominal
mm
Nominal
Thickness
of inner
covering
(approx.)
mm
(approx.)
Note :
of number
Cond. of wire
mm
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Blue
Sheath - Black
TWO CORES
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 14.0 335 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 14.5 350 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 15.0 380 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 15.5 395 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 16.5 475 4.61
4 RM 7 2.6 1.0 1.0 0.8 1.8 17.5 495 4.61
6 RM 7 3.12 1.0 1.0 1.25 1.8 19.0 670 3.08
10 RM 7 4.1 1.0 1.0 1.25 1.8 21.0 840 1.83
16 RM 7 5.1 1.0 1.0 1.25 1.8 23.0 1020 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.8 27.5 1510 0.727
35 RM 7 7.6 1.2 1.0 1.6 1.8 30.0 1810 0.524
50 RM 19 9.2 1.4 1.0 1.6 1.9 34.0 2320 0.387
70 RM 19 10.9 1.4 1.0 2.0 2.0 38.0 3125 0.268
95 RM 19 12.6 1.6 1.2 2.0 2.2 43.5 3990 0.193
120 RM 37 14.2 1.6 1.2 2.0 2.3 47.0 4695 0.153
150 RM 37 15.9 1.8 1.2 2.5 2.4 52.0 5995 0.124
185 RM 37 17.6 2.0 1.4 2.5 2.6 57.0 7110 0.0991
240 RM 61 20.3 2.2 1.4 2.5 2.8 63.5 8830 0.0754
300 RM 61 22.7 2.4 1.6 2.5 2.9 70.0 10575 0.0601
RE : Round Solid Class 1
RM : Circular Stranded Class 2
Page - 36
of Galv.
Note :
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (IEC 60502-1)
Thickness
Sheath
Conductor
/km
Resistance
Weight diameter
Insulation
of of of
cable cable
of Inner
covering at 20C
(approx.)
Steel wire
(approx.)
Thickness
Cross- of of
section Conductor of wire
Nominal Shape
of
Cond.
number
Maximum
Diameter
Overall Nominal Nominal
Diameter Thickness
Nominal
Conductor
mm mm
area (approx.)
Number - mm mm mm kg/km mm mm
(approx.)
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black
THREE CORES
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 14.5 375 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 15.0 385 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 15.5 430 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 16.0 450 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 18.0 640 4.61
4 RM 7 2.6 1.0 1.0 1.25 1.8 18.5 660 4.61
6 RM 7 3.1 1.0 1.0 1.25 1.8 20.0 770 3.08
10 RM 7 4.1 1.0 1.0 1.25 1.8 22.0 975 1.83
16 RM 7 5.1 1.0 1.0 1.25 1.8 24.0 1230 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.8 29.0 1820 0.727
35 RM 7 7.6 1.2 1.0 1.6 1.8 31.5 2230 0.524
50 SM 19 6.8 1.4 1.0 1.6 2.0 30.5 2560 0.387
70 SM 19 8.2 1.4 1.2 2.0 2.1 34.5 3580 0.268
95 SM 19 9.7 1.6 1.2 2.0 2.2 39.0 4655 0.193
120 SM 37 10.9 1.6 1.2 2.0 2.3 42.0 5410 0.153
150 SM 37 11.9 1.8 1.4 2.5 2.5 46.0 6830 0.124
185 SM 37 13.6 2.0 1.4 2.5 2.7 51.0 8260 0.0991
240 SM 37 15.8 2.2 1.6 2.5 2.9 57.0 10635 0.0754
300 SM 37 17.5 2.4 1.6 2.5 3.1 62.0 12795 0.0601
RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2
Page - 37
covering Steel wire section
Note :
Conductor Insulation
Cross- of of number
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC / SWA / PVC (IEC 60502-1)
of of Galv. of of Inner
Diameter Thickness
of wire
of
Sheath cable
Conductor Nominal Nominal Overall Nominal
Nominal Diameter
cable at 20C
Resistance
diameter Weight Thickness Thickness
/km
(approx.) (approx.)
mm mm
Conductor
Maximum
area
mm mm
(approx.)
mm
(approx.)
mm mm kg/km Number
Shape
of
Cond.
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black
FOUR CORES
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 15.5 415 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 16.0 435 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 16.5 490 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 17.0 510 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 19.5 740 4.61
4 RM 7 2.6 1.0 1.0 1.25 1.8 20.0 765 4.61
6 RM 7 3.1 1.0 1.0 1.25 1.8 21.0 895 3.08
10 RM 7 4.1 1.0 1.0 1.25 1.8 23.5 1145 1.83
16 RM 7 5.1 1.0 1.0 1.6 1.8 27.0 1625 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.8 31.0 2185 0.727
35 RM 7 7.6 1.2 1.0 1.6 1.9 34.0 2700 0.524
50 SM 19 8.1 1.4 1.2 2.0 2.1 35.0 3470 0.387
70 SM 19 9.7 1.4 1.2 2.0 2.2 38.5 4455 0.268
95 SM 19 11.4 1.6 1.2 2.5 2.4 44.5 6225 0.193
120 SM 37 12.9 1.6 1.4 2.5 2.5 48.5 7250 0.153
150 SM 37 14.2 1.8 1.4 2.5 2.7 52.5 8665 0.124
185 SM 37 16.0 2.0 1.6 2.5 2.9 58.0 10505 0.0991
240 SM 37 18.2 2.2 1.6 2.5 3.1 63.5 13415 0.0754
300 SM 37 20.6 2.4 1.6 2.5 3.3 70.0 16300 0.0601
RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Four Segmental Stranded Compacted Class 2
mm
Page - 38
mm mm
of
mm /km mm mm kg/km
at 20C covering Steel wire Conductor Insulation of wire
(approx.) (approx.) (approx.)
mm
cable cable Sheath
(approx.)
Resistance Cross- of of of Inner of Galv. of of
Weight Conductor Nominal Diameter Thickness Thickness Diameter Thickness diameter
PVC / SWA / PVC (IEC 60502-1)
Maximum Nominal
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
Nominal Overall Conductor Nominal
Note :
Shape
of number
Cond.
area
section
Number
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black
FIVE CORES
1.5 RE 1 1.38 0.8 1.0 0.8 1.8 16.5 465 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 1.8 17.0 490 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 1.8 17.5 555 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 1.8 18.0 575 7.41
4 RE 1 2.26 1.0 1.0 0.8 1.8 20.5 835 4.61
4 RM 7 2.6 1.0 1.0 1.25 1.8 21.5 865 4.61
6 RM 7 3.1 1.0 1.0 1.25 1.8 22.5 1025 3.08
10 RM 7 4.1 1.0 1.0 1.6 1.8 26.5 1480 1.83
16 RM 7 5.1 1.0 1.0 1.60 1.8 29.0 1893 1.15
25 RM 7 6.4 1.2 1.0 1.6 1.9 33.5 2580 0.727
35 RM 7 7.6 1.2 1.0 2.0 2.0 38.0 3470 0.524
50 RM 19 9.2 1.4 1.2 2.0 2.2 44.0 4505 0.387
RE : Round Solid Class 1
RM : Circular Stranded Class 2
Page - 39
Nominal Overall Maximum Nominal
600/1000 V PVC INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
Diameter Thickness diameter Nominal Diameter Thickness Shape Weight Conductor
Cross- of of of Inner of Galv. of of
Thickness
of Resistance
section Conductor Insulation covering Steel wire Sheath cable cable at 20C
area (approx.) (approx.) (approx.) (approx.)
mm Number kg/km mm /km mm mm mm mm
PVC / SWA / PVC (IEC 60502-1)
Conductor Nominal
Note :
of number
Cond. of wire
mm
Section 2- PVC Insulated Cables
Armoured Cables
Constructions :
Conductor (Annealed Copper)
Insulation (PVC Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Galvanized Flat Steel Wire armour
Galvanized Steel Tape binding
Outer sheath (PVC Compound)
600/1000V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (acc. to IEC 60502-1)
Page - 40
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Blue
Sheath - Black
TWO CORES
Number
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 14.0 410 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 14.5 420 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 15.0 445 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 15.5 480 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 17.0 570 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 17.5 585 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 18.5 675 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 20.5 830 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 22.5 1040 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 26.0 1365 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.8 28.0 1675 0.524
50 RM 19 9.2 1.4 1.0 0.8 0.3 1.8 32.0 2135 0.387
70 RM 19 10.9 1.4 1.0 0.8 0.3 1.9 35.5 2695 0.268
95 RM 19 12.6 1.6 1.2 0.8 0.3 2.1 41.0 3485 0.193
120 RM 37 14.2 1.6 1.2 0.8 0.3 2.2 44.5 4150 0.153
150 RM 37 15.9 1.8 1.2 0.8 0.3 2.3 49.0 4995 0.124
185 RM 37 17.6 2.0 1.4 0.8 0.3 2.4 53.5 5970 0.0991
240 RM 61 20.3 2.2 1.4 0.8 0.3 2.6 60.0 7540 0.0754
300 RM 61 22.7 2.4 1.6 0.8 0.3 2.8 66.5 9180 0.0601
Note : RE : Round Solid Class 1
RM : Circular Stranded Class 2
Cond.
Minimum
thickness
of Galv.
Steel tape
mm
section
Nominal
Conductor
mm mm
area (approx.)
number
of wire
Shape
Cross- of of of of of Galv. of Inner
Overall Maximum
(approx.)
Conductor
of of
Weight diameter
cable Insulation
mm mm mm kg/km mm mm
Diameter Thickness thickness
Flat
Steel wire
Thickness
covering
(approx.) (approx.)
Resistance
cable at 20C
/km
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal Nominal Nominal
Page - 41
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black
THREE CORES
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 14.5 440 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 15.0 450 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 15.5 510 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 16.0 525 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 17.5 635 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 18.0 650 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 19.0 760 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 21.5 985 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 23.5 1230 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 27.0 1685 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.8 30.0 2090 0.524
50 SM 19 6.8 1.4 1.0 0.8 0.3 1.9 28.5 2385 0.387
70 SM 19 8.2 1.4 1.2 0.8 0.3 2.0 32.0 3150 0.268
95 SM 19 9.7 1.6 1.2 0.8 0.3 2.2 37.0 4185 0.193
120 SM 37 10.9 1.6 1.2 0.8 0.3 2.3 39.5 4905 0.153
150 SM 37 11.9 1.8 1.4 0.8 0.3 2.4 43.0 5890 0.124
185 SM 37 13.6 2.0 1.4 0.8 0.3 2.6 47.5 7215 0.0991
240 SM 37 15.8 2.2 1.6 0.8 0.3 2.8 54.0 9460 0.0754
300 SM 37 17.5 2.4 1.6 0.8 0.3 2.9 58.5 11520 0.0601
Note : RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2
/km mm mm mm
(approx.)
mm mm mm mm mm kg/km
area Steel wire Steel tape
of
Number -
Nominal Nominal
number of
Minimum
thickness
of Galv.
(approx.) (approx.)
Sheath cable covering Flat
(approx.)
Maximum
of of
Overall
Thickness thickness
of Inner of Galv.
Conductor
Nominal Diameter Thickness Shape Thickness diameter Weight Conductor
Resistance
section Conductor Insulation of wire Cond.
Cross- of
cable at 20C
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
Nominal
of
Page - 42
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black
FOUR CORES
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 15.5 500 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 16.0 510 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 16.5 560 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 17.0 605 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 18.5 735 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 19.5 755 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 20.5 890 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 23.0 1160 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 25.5 1500 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 29.5 2055 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.9 32.5 2570 0.524
50 SM 19 8.1 1.4 1.2 0.8 0.3 2.0 32.5 3045 0.387
70 SM 19 9.7 1.4 1.2 0.8 0.3 2.1 36.0 3995 0.268
95 SM 19 11.4 1.6 1.2 0.8 0.3 2.3 41.5 5310 0.193
120 SM 37 12.9 1.6 1.4 0.8 0.3 2.4 45.0 6290 0.153
150 SM 37 14.2 1.8 1.4 0.8 0.3 2.6 49.0 7570 0.124
185 SM 37 16.0 2.0 1.6 0.8 0.3 2.7 54.5 9310 0.0991
240 SM 37 18.2 2.2 1.6 0.8 0.3 3.0 60.5 12120 0.0754
300 SM 37 20.6 2.4 1.6 0.8 0.3 3.2 66.5 14865 0.0601
Note : RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Four Segmental Stranded Compacted Class 2
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
Minimum
thickness
of Galv.
Steel tape
Thickness thickness Nominal Diameter Thickness Shape diameter
Conductor Nominal
Thickness Conductor
Nominal Overall Maximum
Resistance Cross- of of of number of Inner of Galv. of
(approx.)
Conductor Insulation
mm mm
Cond. of wire
- Number mm
of
mm
covering
area
mm /km
section
kg/km
Nominal
mm
of
Sheath Flat
Weight
at 20C
(approx.)
cable
(approx.)
Page - 43
(approx.) Steel wire
mm mm
cable
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black
FIVE CORES
1.5 RE 1 1.38 0.8 1.0 0.8 0.3 1.8 16.5 540 12.1
1.5 RM 7 1.6 0.8 1.0 0.8 0.3 1.8 17.0 580 12.1
2.5 RE 1 1.78 0.8 1.0 0.8 0.3 1.8 17.5 635 7.41
2.5 RM 7 2.0 0.8 1.0 0.8 0.3 1.8 18.0 655 7.41
4 RE 1 2.26 1.0 1.0 0.8 0.3 1.8 20.0 835 4.61
4 RM 7 2.6 1.0 1.0 0.8 0.3 1.8 21.0 860 4.61
6 RM 7 3.1 1.0 1.0 0.8 0.3 1.8 22.0 1025 3.08
10 RM 7 4.1 1.0 1.0 0.8 0.3 1.8 25.0 1340 1.83
16 RM 7 5.1 1.0 1.0 0.8 0.3 1.8 27.5 1745 1.15
25 RM 7 6.4 1.2 1.0 0.8 0.3 1.8 32.0 2415 0.727
35 RM 7 7.6 1.2 1.0 0.8 0.3 1.9 35.5 3070 0.524
50 RM 19 9.2 1.4 1.2 0.8 0.3 2.1 41.5 4015 0.387
Note : RE : Round Solid Class 1
RM : Circular Stranded Class 2
thickness
of Galv.
Steel tape
Thickness thickness
Nominal Conductor Nominal Nominal Overall Maximum
600/1000 V PVC INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
PVC/FSWA/PVC (IEC 60502-1)
mm mm mm kg/km /km
of Resistance
cable
Weight
mm No./mm mm mm mm mm
cable at 20C
Steel wire (approx.) (approx.)
covering Flat Sheath
area (approx.) (approx.) (approx.)
section of wire Conductor Insulation
Conductor
Cross- Diameter of of of Inner of Galv. of of
Thickness diameter Minimum Nominal No./ Diameter Thickness
Page - 44
Section 2- PVC Insulated Cables
Armoured Cables
Constructions :
Conductor (Annealed Copper)
Insulation (PVC Compound)
Inner Covering (PVC Compound)
Double Aluminium Tape armour
Outer sheath (PVC Compound)
Constructions :
Conductor (Annealed Copper)
Insulation (PVC Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Double Galvanized Steel Tape armour
Outer sheath (PVC Compound)
Page - 45
600/1000V PVC INSULATED, ALUMINIUMTAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DATA/PVC (acc. to IEC 60502-1)
600/1000V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (acc. to IEC 60502-1)
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
1
2
3
4
5
1
2
3
4
5
6
7
6
1
2
3
4
5
1
2
3
4
5
6
7
6
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Inner covering : PVC Compound Maximum 70C
Armour : Double Aluminiumtape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown
Sheath - Black
SINGLE CORE
number
50 RM 19 9.2 1.4 1.0 0.5 1.8 19.5 820 0.387
70 RM 19 10.9 1.4 1.0 0.5 1.8 21.0 1045 0.268
95 RM 19 12.6 1.6 1.0 0.5 1.8 23.5 1345 0.193
120 RM 37 14.2 1.6 1.0 0.5 1.8 25.0 1610 0.153
150 RM 37 15.9 1.8 1.0 0.5 1.8 27.0 1950 0.124
185 RM 37 17.6 2.0 1.0 0.5 1.8 29.5 2340 0.0991
240 RM 61 20.3 2.2 1.0 0.5 1.9 32.5 2990 0.0754
300 RM 61 22.7 2.4 1.0 0.5 1.9 35.0 3630 0.0601
400 RM 61 25.7 2.6 1.2 0.5 2.1 39.5 4640 0.0470
500 RM 61 28.8 2.8 1.2 0.5 2.2 43.5 5695 0.0366
Note RM: Circular Stranded Class 2
Page - 46
(approx.)
Nominal
thickness of
Aluminium
tape
mm mm mm mm mm
section Conductor
mm mm
area (approx.)
of wire Cond.
Cross- of
(approx.)
Insulation
of of
600/1000 V PVC INSULATED, ALUMINIUMTAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DATA/PVC (IEC 60502-1)
of
at 20C cable
Nominal
of Inner
covering Sheath
Weight
/km
Resistance
kg/km
cable
(approx.)
of
Conductor Nominal Nominal Overall
Diameter Thickness
Maximum
Thickness diameter Conductor Thickness
number
Shape
of
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Blue
Sheath - Black
TWO CORES
RE 1 1.38 0.8 1.0 0.2 1.8 13.0 240 12.1
RM 7 1.6 0.8 1.0 0.2 1.8 13.0 250 12.1
RE 1 1.78 0.8 1.0 0.2 1.8 13.5 280 7.41
RM 7 2.0 0.8 1.0 0.2 1.8 14.0 290 7.41
RE 1 2.26 1.0 1.0 0.2 1.8 15.5 360 4.61
RM 7 2.6 1.0 1.0 0.2 1.8 16.0 375 4.61
RM 7 3.1 1.0 1.0 0.2 1.8 17.0 440 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 19.0 575 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 21.0 745 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 24.5 1030 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.8 27.0 1290 0.524
50 RM 19 9.2 1.4 1.0 0.2 1.8 31.0 1715 0.387
70 RM 19 10.9 1.4 1.0 0.2 1.9 34.0 2265 0.268
95 RM 19 12.6 1.6 1.2 0.2 2.1 39.0 2900 0.193
120 RM 37 14.2 1.6 1.2 0.5 2.2 43.5 3925 0.153
150 RM 37 15.9 1.8 1.2 0.5 2.3 48.0 4725 0.124
185 RM 37 17.6 2.0 1.4 0.5 2.4 52.5 5675 0.0991
240 RM 61 20.3 2.2 1.4 0.5 2.6 58.5 7170 0.0754
300 RM 61 22.7 2.4 1.6 0.5 2.8 64.5 8710 0.0601
Note RE : Round Solid Class 1
RM
: Circular Stranded Class 2
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal
Page - 47
Nominal
Nominal Diameter Thickness
Overall
Insulation
Nominal
of
/km
Resistance of
Maximum
(approx.)
Weight diameter
cable cable at 20C
(approx.)
Conductor
number of
section Conductor
Cross- of of
of wire
kg/km mm mm
Thickness
of Inner
covering
mm
(approx.)
mm mm mm
area (approx.)
mm number
Thickness
of Galv.
Steel tape
6
4
Shape
of
Cond.
1.5
2.5
4
1.5
2.5
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black
THREE CORES
RE 1 1.38 0.8 1.0 0.2 1.8 13.5 270 12.1
RM 7 1.6 0.8 1.0 0.2 1.8 13.5 285 12.1
RE 1 1.78 0.8 1.0 0.2 1.8 14.0 320 7.41
RM 7 2.0 0.8 1.0 0.2 1.8 14.5 335 7.41
RE 1 2.26 1.0 1.0 0.2 1.8 16.0 420 4.61
RM 7 2.6 1.0 1.0 0.2 1.8 16.5 445 4.61
RM 7 3.1 1.0 1.0 0.2 1.8 18.0 530 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 20.0 710 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 22.0 935 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 26.0 1330 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.8 28.5 1685 0.524
50 SM 19 6.8 1.4 1.0 0.2 1.9 27.0 2005 0.387
70 SM 19 8.2 1.4 1.2 0.2 2.0 30.5 2725 0.268
95 SM 19 9.7 1.6 1.2 0.5 2.2 36.5 4065 0.193
120 SM 37 10.9 1.6 1.2 0.5 2.3 39.5 4765 0.153
150 SM 37 11.9 1.8 1.4 0.5 2.4 42.5 5745 0.124
185 SM 37 13.6 2.0 1.4 0.5 2.6 47.5 7055 0.0991
240 SM 37 15.8 2.2 1.6 0.5 2.8 53.5 9255 0.0754
300 SM 37 17.5 2.4 1.6 0.5 2.9 58.0 11300 0.0601
RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2
of number
Cond. of wire
Shape
Page - 48
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
PVC/DSTA/PVC (IEC 60502-1)
of of of Cross-
cable
Nominal Diameter Thickness Thickness diameter Weight Conductor
at 20C
Maximum
of Resistance
Thickness Thickness
of Inner
cable Sheath
Nominal Nominal Overall Nominal
number mm
covering Steel tape section Conductor Insulation
(approx.)
mm mm
(approx.)
mm mm kg/km
(approx.)
of Galv.
/km mm mm
(approx.)
1.5
2.5
4
6
Note :
2.5
4
1.5
area
Conductor
of
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black
FOUR CORES
RE 1 1.38 0.8 1.0 0.2 1.8 14.0 310 12.1
RM 7 1.6 0.8 1.0 0.2 1.8 14.5 325 12.1
RE 1 1.78 0.8 1.0 0.2 1.8 15.0 375 7.41
RM 7 2.0 0.8 1.0 0.2 1.8 15.5 390 7.41
RE 1 2.26 1.0 1.0 0.2 1.8 17.5 500 4.61
RM 7 2.6 1.0 1.0 0.2 1.8 18.0 525 4.61
RM 7 3.1 1.0 1.0 0.2 1.8 19.0 640 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 21.5 860 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 24.0 1160 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 28.0 1650 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.8 31.0 2120 0.524
50 SM 19 8.1 1.4 1.2 0.2 2.0 31.0 2595 0.387
70 SM 19 9.7 1.4 1.2 0.5 2.1 36.0 3865 0.268
95 SM 19 11.4 1.6 1.2 0.5 2.3 41.0 5175 0.193
120 SM 37 12.9 1.6 1.4 0.5 2.4 44.5 6125 0.153
150 SM 37 14.2 1.8 1.4 0.5 2.6 49.0 7405 0.124
185 SM 37 16.0 2.0 1.6 0.5 2.7 54.0 9115 0.0991
240 SM 37 18.2 2.2 1.6 0.5 3.0 60.0 11900 0.0754
300 SM 37 20.6 2.4 1.6 0.5 3.2 66.5 14625 0.0601
RE : Round Solid Class 1
RM : Circular Stranded Class 2
SM : Three Segmental Stranded Compacted Class 2
of number
Cond. of wire
Page - 49
Shape
6
1.5
number
(approx.) (approx.)
/km mm mm
Insulation covering
(approx.)
mm mm mm mm mm kg/km
area
Sheath cable
(approx.)
cable at 20C
Nominal Nominal Overall
of
Nominal Maximum
Steel tape
Conductor
of of
Thickness
of
Thickness
of Inner
diameter Weight
of Galv.
PVC / DSTA / PVC (IEC 60502-1)
Conductor
1.5
2.5
4
4
section
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
Nominal Diameter Thickness
Resistance
Thickness
of
Note :
2.5
Cross-
Conductor
Section 2- PVC Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : PVC Compound type A Operating Temperature
Filler : Suitable material Maximum 70C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST1
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black
FIVE CORES
RE 1 1.38 0.8 1.0 0.2 1.8 15.0 350 12.1
RM 7 1.6 0.8 1.0 0.2 1.8 15.5 370 12.1
RE 1 1.78 0.8 1.0 0.2 1.8 16.0 425 7.41
RM 7 2.0 0.8 1.0 0.2 1.8 16.5 450 7.41
RE 1 2.26 1.0 1.0 0.2 1.8 18.5 580 4.61
RM 7 2.6 1.0 1.0 0.2 1.8 19.5 610 4.61
RM 7 3.1 1.0 1.0 0.2 1.8 20.5 750 3.08
10 RM 7 4.1 1.0 1.0 0.2 1.8 23.5 1025 1.83
16 RM 7 5.1 1.0 1.0 0.2 1.8 26.0 1390 1.15
25 RM 7 6.4 1.2 1.0 0.2 1.8 30.5 1995 0.727
35 RM 7 7.6 1.2 1.0 0.2 1.9 34.0 2580 0.524
50 RM 19 9.2 1.4 1.2 0.2 2.1 40.0 3400 0.387
RE : Round Solid Class 1
RM : Circular Stranded Class 2
Cond. of wire
Shape
of number
Page - 50
/km mm mm mm mm
Note :
Nominal
PVC/DSTA/PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
(approx.) (approx.)
mm mm kg/km
at 20C
(approx.) (approx.)
number
Resistance
section Conductor Insulation covering Steel tape Sheath cable cable
Conductor
Cross- of of of Inner of Galv. of of of
Thickness diameter Weight Diameter Thickness Thickness Thickness
4
6
600/1000 V PVC INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
4
2.5
1.5
2.5
mm
area
Nominal
1.5
Section 3- XLPE Insulated Cables
Unarmoured Cables
Constructions :
Conductor (Annealed Copper)
Insulation (XLPE Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
XLPE/PVC (IEC 60502-1)
Page - 51
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
1
2
4
5
3
1
2
4
5
3
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Sheath : PVC Compound type ST2 Maximum 90C
Colour Ident. : Insulation - Brown
Sheath - Black
SINGLE CORE
1.5 RE 1 1.38 0.7 1.4 5.4 45 12.1
1.5 RM 7 1.6 0.7 1.4 5.6 45 12.1
2.5 RE 1 1.78 0.7 1.4 5.8 55 7.41
2.5 RM 7 2.0 0.7 1.4 6.0 55 7.41
4 RE 1 2.26 0.7 1.4 6.3 75 4.61
4 RM 7 2.6 0.7 1.4 6.6 75 4.61
6 RM 7 3.1 0.7 1.4 7.1 100 3.08
10 RM 7 4.1 0.7 1.4 8.1 140 1.83
16 CM 7 4.7 0.7 1.4 8.7 195 1.15
25 CM 7 5.9 0.9 1.4 10.5 290 0.727
35 CM 7 7.1 0.9 1.4 11.5 385 0.524
50 CM 19 8.1 1.0 1.4 12.5 500 0.387
70 CM 19 9.7 1.1 1.4 14.5 700 0.268
95 CM 19 11.6 1.1 1.5 16.5 955 0.193
120 CM 37 12.9 1.2 1.5 18.0 1190 0.153
150 CM 37 14.3 1.4 1.6 20.0 1475 0.124
185 CM 37 16.0 1.6 1.6 22.5 1825 0.0991
240 CM 37 18.3 1.7 1.7 25.0 2360 0.0754
300 CM 61 20.7 1.8 1.8 27.5 2945 0.0601
400 CM 61 23.4 2.0 1.9 31.0 3740 0.0470
500 CM 61 26.5 2.2 2.0 34.5 4780 0.0366
630 CM 91 30.3 2.4 2.2 39.5 6165 0.0283
800 CM 91 34.3 2.6 2.3 44.0 7860 0.0221
1000 RM 127 41.6 2.8 2.4 52.0 10030 0.0176
Note RE : Round Solid Class 1, RM : Circular Stranded Class 2, CM : Circular Stranded Compacted Class 2
Number
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
XLPE / PVC (IEC 60502-1)
cable at 20C
(approx.)
mm mm
Maximum
Weight Conductor
Nominal Overall
Sheath cable
diameter
of of number
Thickness
of Resistance
(approx.) (approx.)
of of of
-
Conductor Nominal
Insulation
Cross-
Nominal Diameter Thickness Shape
section Conductor Cond. of wire
Page - 52
area
kg/km /km mm mm mm
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Blue
Sheath - Black
TWO CORES
1.5 RE 1 1.38 0.7 1.8 9.5 105 12.1
1.5 RM 7 1.6 0.7 1.8 10.0 110 12.1
2.5 RE 1 1.78 0.7 1.8 10.5 130 7.41
2.5 RM 7 2.0 0.7 1.8 10.5 135 7.41
4 RE 1 2.26 0.7 1.8 11.5 170 4.61
4 RM 7 2.6 0.7 1.8 12.0 180 4.61
6 RM 7 3.1 0.7 1.8 13.0 230 3.08
10 RM 7 4.1 0.7 1.8 15.0 330 1.83
16 CM 7 4.7 0.7 1.8 16.0 445 1.15
25 CM 7 5.9 0.9 1.8 19.5 660 0.727
35 CM 7 7.1 0.9 1.8 21.5 870 0.524
50 CM 19 8.1 1.0 1.8 24.0 1130 0.387
70 CM 19 9.7 1.1 1.8 27.5 1570 0.268
95 CM 19 11.6 1.1 2.0 31.5 2125 0.193
120 CM 37 12.9 1.2 2.1 35.0 2645 0.153
150 CM 37 14.3 1.4 2.2 38.5 3275 0.124
185 CM 37 16.0 1.6 2.3 43.5 4075 0.0991
240 CM 37 18.3 1.7 2.5 48.5 5270 0.0754
300 CM 61 20.7 1.8 2.7 54.5 6575 0.0601
400 CM 61 23.4 2.0 2.9 61.0 8355 0.0470
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Number
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
XLPE / PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal Nominal
/km
Resistance of of
Maximum
(approx.)
Nominal Diameter Thickness Shape Weight diameter
cable
Overall
cable
area (approx.) (approx.)
of number
Cond. Insulation
Conductor
Cross- of of of
section Conductor at 20C of wire
kg/km mm mm - mm mm mm
Page - 53
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black
THREE CORES
1.5 RE 1 1.38 0.7 1.8 10.0 125 12.1
1.5 RM 7 1.6 0.7 1.8 10.5 130 12.1
2.5 RE 1 1.78 0.7 1.8 11.0 160 7.41
2.5 RM 7 2.0 0.7 1.8 11.5 170 7.41
4 RE 1 2.26 0.7 1.8 12.0 215 4.61
4 RM 7 2.6 0.7 1.8 12.5 230 4.61
6 RM 7 3.1 0.7 1.8 13.5 295 3.08
10 RM 7 4.1 0.7 1.8 16.0 435 1.83
16 CM 7 4.7 0.7 1.8 17.0 605 1.15
25 CM 7 5.9 0.9 1.8 20.5 900 0.727
35 CM 7 7.1 0.9 1.8 23.0 1200 0.524
50 CM 19 8.1 1.0 1.8 25.5 1570 0.387
70 CM 19 9.7 1.1 1.9 29.5 2200 0.268
95 CM 19 11.6 1.1 2.0 34.0 2995 0.193
120 CM 37 12.9 1.2 2.1 37.5 3735 0.153
150 CM 37 14.3 1.4 2.3 41.5 4650 0.124
185 CM 37 16.0 1.6 2.4 46.5 5760 0.0991
240 CM 37 18.3 1.7 2.6 52.5 7500 0.0754
300 CM 61 20.7 1.8 2.8 58.5 9360 0.0601
400 CM 61 23.4 2.0 3.1 65.5 11900 0.0470
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Conductor
Shape
of
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
XLPE / PVC (IEC 60502-1)
Resistance
section Conductor Insulation Cond. of wire
number
diameter Weight Conductor
at 20C
(approx.)
Nominal Nominal Overall
Thickness
of of of
cable
Nominal Diameter Thickness
of
mm
Page - 54
area
Cross- of
- Number
Sheath cable
(approx.) (approx.)
mm
Maximum
/km mm kg/km mm mm
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black
FOUR CORES
1.5 RE 1 1.38 0.7 1.8 10.5 150 12.1
1.5 RM 7 1.6 0.7 1.8 11.0 155 12.1
2.5 RE 1 1.78 0.7 1.8 11.5 195 7.41
2.5 RM 7 2.0 0.7 1.8 12.0 205 7.41
4 RE 1 2.26 0.7 1.8 13.0 270 4.61
4 RM 7 2.6 0.7 1.8 13.5 280 4.61
6 RM 7 3.1 0.7 1.8 15.0 370 3.08
10 RM 7 4.1 0.7 1.8 17.5 550 1.83
16 CM 7 4.7 0.7 1.8 18.5 770 1.15
25 CM 7 5.9 0.9 1.8 22.5 1160 0.727
35 CM 7 7.1 0.9 1.8 25.5 1550 0.524
50 CM 19 8.1 1.0 1.9 28.5 2040 0.387
70 CM 19 9.7 1.1 2.0 33.0 2880 0.268
95 CM 19 11.6 1.1 2.1 37.5 3925 0.193
120 CM 37 12.9 1.2 2.3 41.5 4920 0.153
150 CM 37 14.3 1.4 2.4 46.0 6075 0.124
185 CM 37 16.0 1.6 2.6 52.0 7585 0.0991
240 CM 37 18.3 1.7 2.8 58.5 9870 0.0754
300 CM 61 20.7 1.8 3.0 65.0 12320 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
- Number /km
(approx.)
mm kg/km
area (approx.) (approx.)
mm mm mm mm
Sheath cable cable at 20C section Conductor Insulation Cond. of wire
Conductor
Cross- of of of number of of of Resistance
Maximum
Nominal Diameter Thickness Shape Thickness diameter Weight
Conductor Nominal Nominal Overall
Page - 55
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
XLPE / PVC (IEC 60502-1)
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black
FIVE CORES
1.5 RE 1 1.38 0.7 1.8 11.5 175 12.1
1.5 RM 7 1.6 0.7 1.8 12.0 185 12.1
2.5 RE 1 1.78 0.7 1.8 12.5 235 7.41
2.5 RM 7 2.0 0.7 1.8 13.0 245 7.41
4 RE 1 2.26 0.7 1.8 14.0 320 4.61
4 RM 7 2.6 0.7 1.8 15.0 340 4.61
6 RM 7 3.1 0.7 1.8 16.0 450 3.08
10 RM 7 4.1 0.7 1.8 19.0 675 1.83
16 CM 7 4.7 0.7 1.8 20.5 945 1.15
25 CM 7 5.9 0.9 1.8 25.0 1425 0.727
35 CM 7 7.1 0.9 1.8 28.0 1915 0.524
50 CM 19 8.1 1.0 2.0 31.5 2535 0.387
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Conductor
- Number
Shape
/km
(approx.)
mm mm mm mm mm kg/km
(approx.) area (approx.)
Sheath cable cable
of Resistance
at 20C section Conductor Insulation Cond. of wire
Weight Conductor
Cross- of of of number of of
Nominal Overall
Thickness diameter
Maximum
Nominal Diameter Thickness
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
XLPE / PVC (IEC 60502-1)
Nominal
Page - 56
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 1) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 1.5mm (Solid conductor)
No Nominal
of Cross-section
core area
mm
6 1.5 RE 1 1.38 0.7 1.8 12.5 200 12.1
7 1.5 RE 1 1.38 0.7 1.8 12.5 210 12.1
8 1.5 RE 1 1.38 0.7 1.8 13.5 240 12.1
9 1.5 RE 1 1.38 0.7 1.8 14.3 265 12.1
10 1.5 RE 1 1.38 0.7 1.8 15.5 295 12.1
12 1.5 RE 1 1.38 0.7 1.8 16.0 335 12.1
14 1.5 RE 1 1.38 0.7 1.8 16.5 380 12.1
15 1.5 RE 1 1.38 0.7 1.8 17.0 400 12.1
16 1.5 RE 1 1.38 0.7 1.8 17.5 425 12.1
18 1.5 RE 1 1.38 0.7 1.8 18.5 465 12.1
19 1.5 RE 1 1.38 0.7 1.8 18.5 480 12.1
20 1.5 RE 1 1.38 0.7 1.8 19.0 505 12.1
24 1.5 RE 1 1.38 0.7 1.8 21.5 600 12.1
30 1.5 RE 1 1.38 0.7 1.8 22.5 720 12.1
32 1.5 RE 1 1.38 0.7 1.8 23.0 760 12.1
37 1.5 RE 1 1.38 0.7 1.8 24.5 855 12.1
40 1.5 RE 1 1.38 0.7 1.8 25.5 920 12.1
50 1.5 RE 1 1.38 0.7 1.9 28.0 1125 12.1
52 1.5 RE 1 1.38 0.7 1.9 29.5 1210 12.1
60 1.5 RE 1 1.38 0.7 1.9 30.5 1330 12.1
61 1.5 RE 1 1.38 0.7 1.9 30.5 1350 12.1
Note RE : Round Solid Class 1
- Number
of number
Cond. of wire
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
XLPE / PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Diameter Thickness Thickness Shape
at 20C
of of of
Conductor Insulation Sheath cable cable
Conductor
of of Resistance
diameter Weight
(approx.) (approx.) (approx.)
Page - 57
kg/km /km mm mm mm mm
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 clas 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 1.5mm (Stranded conductor)
No Nominal
of Cross-section
core area
mm
6 1.5 RM 7 1.6 0.7 1.8 13.0 210 12.1
7 1.5 RM 7 1.6 0.7 1.8 13.0 220 12.1
8 1.5 RM 7 1.6 0.7 1.8 14.0 250 12.1
9 1.5 RM 7 1.6 0.7 1.8 15.0 280 12.1
10 1.5 RM 7 1.6 0.7 1.8 16.5 310 12.1
12 1.5 RM 7 1.6 0.7 1.8 17.0 355 12.1
14 1.5 RM 7 1.6 0.7 1.8 17.5 400 12.1
15 1.5 RM 7 1.6 0.7 1.8 18.0 420 12.1
16 1.5 RM 7 1.6 0.7 1.8 18.5 445 12.1
18 1.5 RM 7 1.6 0.7 1.8 19.5 490 12.1
19 1.5 RM 7 1.6 0.7 1.8 19.5 500 12.1
20 1.5 RM 7 1.6 0.7 1.8 20.0 530 12.1
24 1.5 RM 7 1.6 0.7 1.8 22.5 630 12.1
30 1.5 RM 7 1.6 0.7 1.8 24.0 755 12.1
32 1.5 RM 7 1.6 0.7 1.8 24.5 795 12.1
37 1.5 RM 7 1.6 0.7 1.8 26.0 900 12.1
40 1.5 RM 7 1.6 0.7 1.8 27.0 965 12.1
50 1.5 RM 7 1.6 0.7 1.9 29.5 1185 12.1
52 1.5 RM 7 1.6 0.7 1.9 30.5 1230 12.1
60 1.5 RM 7 1.6 0.7 1.9 32.5 1395 12.1
61 1.5 RM 7 1.6 0.7 1.9 32.5 1415 12.1
Note RM : Circular Stranded Class 2
of number
Cond. of wire
Shape
kg/km /km mm mm mm mm
Resistance
diameter Weight
- Number
cable
(approx.) (approx.) (approx.)
at 20C
of of of
Conductor Insulation Sheath cable
of of
Diameter Thickness Thickness
XLPE / PVC (IEC 60502-1)
Conductor Nominal Nominal Maximum
Conductor
Page - 58
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
Overall
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 2.5mm (Solid conductor)
No Nominal
of Cross-section
core area
mm
6 2.5 RE 1 1.78 0.7 1.8 13.5 265 7.41
7 2.5 RE 1 1.78 0.7 1.8 13.5 290 7.41
8 2.5 RE 1 1.78 0.7 1.8 14.5 330 7.41
9 2.5 RE 1 1.78 0.7 1.8 16.0 370 7.41
10 2.5 RE 1 1.78 0.7 1.8 17.0 410 7.41
12 2.5 RE 1 1.78 0.7 1.8 17.5 465 7.41
14 2.5 RE 1 1.78 0.7 1.8 18.5 530 7.41
15 2.5 RE 1 1.78 0.7 1.8 19.0 565 7.41
16 2.5 RE 1 1.78 0.7 1.8 19.5 595 7.41
18 2.5 RE 1 1.78 0.7 1.8 20.5 655 7.41
19 2.5 RE 1 1.78 0.7 1.8 20.5 680 7.41
20 2.5 RE 1 1.78 0.7 1.8 21.0 715 7.41
24 2.5 RE 1 1.78 0.7 1.8 24.0 855 7.41
30 2.5 RE 1 1.78 0.7 1.8 25.5 1035 7.41
32 2.5 RE 1 1.78 0.7 1.8 26.0 1095 7.41
37 2.5 RE 1 1.78 0.7 1.8 27.5 1240 7.41
40 2.5 RE 1 1.78 0.7 1.9 28.5 1335 7.41
50 2.5 RE 1 1.78 0.7 2.0 31.5 1655 7.41
52 2.5 RE 1 1.78 0.7 2.0 32.5 1720 7.41
60 2.5 RE 1 1.78 0.7 2.0 34.5 1965 7.41
61 2.5 RE 1 1.78 0.7 2.0 34.5 1990 7.41
Note RE : Round Solid Class 1
Cond. of wire
- Number
(approx.)
mm kg/km /km
(approx.) (approx.)
mm mm mm
Shape
Resistance
Conductor Insulation Sheath cable cable at 20C
of of of of
Thickness
Overall
diameter Weight Thickness
Nominal Nominal
of number
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
XLPE / PVC (IEC 60502-1)
Maximum Conductor
Page - 59
Conductor Diameter
of
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler (if necessary) : Suitable material Maximum 90C
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
CONTROL CABLE : 2.5mm (Stranded conductor)
No Nominal
of Cross-section
core area
mm
6 2.5 RM 7 2.0 0.7 1.8 14.5 280 7.41
7 2.5 RM 7 2.0 0.7 1.8 14.5 300 7.41
8 2.5 RM 7 2.0 0.7 1.8 15.5 340 7.41
9 2.5 RM 7 2.0 0.7 1.8 16.5 385 7.41
10 2.5 RM 7 2.0 0.7 1.8 18.0 425 7.41
12 2.5 RM 7 2.0 0.7 1.8 18.5 485 7.41
14 2.5 RM 7 2.0 0.7 1.8 19.5 555 7.41
15 2.5 RM 7 2.0 0.7 1.8 20.0 585 7.41
16 2.5 RM 7 2.0 0.7 1.8 20.5 620 7.41
18 2.5 RM 7 2.0 0.7 1.8 21.5 685 7.41
19 2.5 RM 7 2.0 0.7 1.8 21.5 705 7.41
20 2.5 RM 7 2.0 0.7 1.8 22.0 745 7.41
24 2.5 RM 7 2.0 0.7 1.8 25.0 890 7.41
30 2.5 RM 7 2.0 0.7 1.8 26.5 1075 7.41
32 2.5 RM 7 2.0 0.7 1.8 27.0 1140 7.41
37 2.5 RM 7 2.0 0.7 1.8 28.5 1290 7.41
40 2.5 RM 7 2.0 0.7 1.9 30.0 1390 7.41
50 2.5 RM 7 2.0 0.7 2.0 33.0 1710 7.41
52 2.5 RM 7 2.0 0.7 2.0 34.0 1790 7.41
60 2.5 RM 7 2.0 0.7 2.0 36.0 2040 7.41
61 2.5 RM 7 2.0 0.7 2.0 36.0 2070 7.41
Note RM : Circular Stranded Class 2
- Number
of number
Cond.
kg/km /km mm mm mm mm
(approx.) (approx.) (approx.)
Conductor
of of Resistance
diameter Weight
at 20C
of of of
Conductor Insulation Sheath cable cable
Diameter Thickness Thickness
600/1000 V XLPE INSULATED AND PVC SHEATHED CABLES
XLPE / PVC (IEC 60502-1)
Conductor Nominal Nominal Overall Maximum
Page - 60
Shape
of wire
Section 3- XLPE Insulated Cables
Unarmoured Cables
Constructions :
Conductor (Annealed Copper)
Insulation (XLPE Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Copper Tape screen
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
600/1000V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
XLPE / PVC-S (IEC 60502-1)
Page - 61
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Copper wire screen.
* Polyethylene / Low smoke Halogen Free sheathed
1
2
4
5
3
1
2
4
5
3
6
7
6
7
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Blue
Sheath - Black
TWO CORES
1.5 RE 1 1.38 0.7 0.1 1.8 10.0 125 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 10.5 135 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 11.0 155 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 11.5 165 7.41
4 RE 1 2.26 0.7 0.1 1.8 12.0 200 4.61
4 RM 7 2.6 0.7 0.1 1.8 12.5 210 4.61
6 RE 1 2.77 0.7 0.1 1.8 13.0 250 3.08
6 RM 7 3.1 0.7 0.1 1.8 13.5 265 3.08
10 RM 7 4.1 0.7 0.1 1.8 15.5 370 1.83
16 CM 7 4.7 0.7 0.1 1.8 16.5 490 1.15
25 CM 7 5.9 0.9 0.1 1.8 20.0 715 0.727
35 CM 7 7.1 0.9 0.1 1.8 22.5 935 0.524
50 CM 19 8.1 1.0 0.1 1.8 24.5 1200 0.387
70 CM 19 9.7 1.1 0.1 1.9 28.5 1650 0.268
95 CM 19 11.6 1.1 0.1 2.0 32.5 2225 0.193
120 CM 37 12.9 1.2 0.1 2.1 35.5 2755 0.153
150 CM 37 14.3 1.4 0.1 2.2 39.5 3395 0.124
185 CM 37 16.0 1.6 0.1 2.3 44.0 4205 0.0991
240 CM 37 18.3 1.7 0.1 2.5 49.5 5425 0.0754
300 CM 61 20.7 1.8 0.1 2.7 55.0 6755 0.0601
400 CM 61 23.4 2.0 0.1 2.9 61.5 8545 0.0470
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Cond. of wire
/km mm
Sheath
mm kg/km
Insulation
(approx.)
Copper tape
mm
cable
mm
(approx.)
mm
Page - 62
(approx.)
- Number
Resistance
(approx.)
at 20C cable
of
600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
Diameter
Nominal
Thickness
Overall
diameter
Conductor Maximum
Conductor Shape
of
Nominal
Thickness
Nominal
Thickness
number of of of Cross-
Conductor section area
XLPE / PVC-S (IEC 60502-1)
Nominal Weight
of of
mm
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black
THREE CORES
1.5 RE 1 1.38 0.7 0.1 1.8 10.5 150 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 11.0 155 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 11.5 190 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 12.0 195 7.41
4 RE 1 2.26 0.7 0.1 1.8 12.5 250 4.61
4 RM 7 2.6 0.7 0.1 1.8 13.0 260 4.61
6 RE 1 2.77 0.7 0.1 1.8 13.5 320 3.08
6 RM 7 3.1 0.7 0.1 1.8 14.0 330 3.08
10 RM 7 4.1 0.7 0.1 1.8 16.5 480 1.83
16 CM 7 4.7 0.7 0.1 1.8 17.5 650 1.15
25 CM 7 5.9 0.9 0.1 1.8 21.0 960 0.727
35 CM 7 7.1 0.9 0.1 1.8 23.5 1275 0.524
50 CM 19 8.1 1.0 0.1 1.8 26.5 1645 0.387
70 CM 19 9.7 1.1 0.1 1.9 30.0 2285 0.268
95 CM 19 11.6 1.1 0.1 2.0 34.5 3110 0.193
120 CM 37 12.9 1.2 0.1 2.2 38.0 3870 0.153
150 CM 37 14.3 1.4 0.1 2.3 42.0 4775 0.124
185 CM 37 16.0 1.6 0.1 2.4 47.0 5910 0.0991
240 CM 37 18.3 1.7 0.1 2.6 53.0 7675 0.0754
300 CM 61 20.7 1.8 0.1 2.8 59.0 9565 0.0601
400 CM 61 23.4 2.0 0.1 3.1 66.0 12110 0.0470
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Diameter
- Number
(approx.)
mm mm
Copper tape
(approx.)
cable Sheath
Shape
of
600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
Thickness
of
section area Conductor Insulation Cond. of wire
Cross- of of of
Conductor Thickness
Maximum Overall
of number
Weight
of
Nominal Nominal
mm
(approx.)
mm
Conductor Nominal
Nominal
XLPE / PVC-S (IEC 60502-1)
mm
diameter
at 20C cable
kg/km /km
Thickness
(approx.)
mm
Resistance
Page - 63
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black
FOUR CORES
1.5 RE 1 1.38 0.7 0.1 1.8 11.5 175 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 12.0 185 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 12.5 230 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 13.0 240 7.41
4 RE 1 2.26 0.7 0.1 1.8 13.5 300 4.61
4 RM 7 2.6 0.7 0.1 1.8 14.0 320 4.61
6 RE 1 2.77 0.7 0.1 1.8 14.5 395 3.08
6 RM 7 3.1 0.7 0.1 1.8 15.5 410 3.08
10 RM 7 4.1 0.7 0.1 1.8 18.0 600 1.83
16 CM 7 4.7 0.7 0.1 1.8 19.5 825 1.15
25 CM 7 5.9 0.9 0.1 1.8 23.0 1230 0.727
35 CM 7 7.1 0.9 0.1 1.8 26.0 1635 0.524
50 CM 19 8.1 1.0 0.1 1.9 29.0 2120 0.387
70 CM 19 9.7 1.1 0.1 2.0 33.5 2980 0.268
95 CM 19 11.6 1.1 0.1 2.2 38.5 4075 0.193
120 CM 37 12.9 1.2 0.1 2.3 42.5 5055 0.153
150 CM 37 14.3 1.4 0.1 2.5 47.0 6245 0.124
185 CM 37 16.0 1.6 0.1 2.6 52.5 7755 0.0991
240 CM 37 18.3 1.7 0.1 2.8 59.0 10070 0.0754
300 CM 61 20.7 1.8 0.1 3.0 65.5 12550 0.0601
400 CM 61 23.4 2.0 0.1 3.3 73.5 15900 0.0470
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
(approx.)
Shape
(approx.) (approx.)
- Number
Conductor Nominal
of wire section area Conductor Insulation Copper tape
Thickness
of number
Cond. at 20C Sheath cable cable
Nominal
Thickness
mm mm kg/km /km mm mm mm mm
Resistance
diameter
of of of
Weight
of of of
600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
XLPE / PVC-S (IEC 60502-1)
Page - 64
Diameter Nominal
(approx.)
Overall Maximum Nominal
Conductor
Cross-
Thickness
Section 3- XLPE Insulated Cables
Unarmoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Metallic screen : Annealed Copper tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 RE 1 1.38 0.7 0.1 1.8 12.0 205 12.1
1.5 RM 7 1.6 0.7 0.1 1.8 12.5 215 12.1
2.5 RE 1 1.78 0.7 0.1 1.8 13.5 265 7.41
2.5 RM 7 2.0 0.7 0.1 1.8 14.0 280 7.41
4 RE 1 2.26 0.7 0.1 1.8 14.5 360 4.61
4 RM 7 2.6 0.7 0.1 1.8 15.5 380 4.61
6 RE 1 2.77 0.7 0.1 1.8 16.0 475 3.08
6 RM 7 3.1 0.7 0.1 1.8 17.0 490 3.08
10 RM 7 4.1 0.7 0.1 1.8 19.5 720 1.83
16 CM 7 4.7 0.7 0.1 1.8 21.0 1005 1.15
25 CM 7 5.9 0.9 0.1 1.8 25.5 1495 0.727
35 CM 7 7.1 0.9 0.1 1.9 28.5 2005 0.524
50 CM 19 8.1 1.0 0.1 2.0 32.0 2620 0.387
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
(approx.)
600/1000 V XLPE INSULATED, METALLIC SCREENED AND PVC SHEATHED CABLES
XLPE / PVC-S (IEC 60502-1)
Nominal
Shape
Cond.
(approx.)
of of
(approx.)
cable at 20C
of Resistance
Weight
Copper tape
of number
Diameter Thickness
Nominal
of
Conductor
mm
Maximum
Conductor
Overall
Sheath cable
Thickness diameter
mm
section area Conductor Insulation of wire
- Number mm mm mm mm kg/km /km
Cross- of
Nominal Thickness
of
Nominal
Page - 65
(approx.)
Section 3- XLPE Insulated Cables
Armoured Cables
Constructions :
Conductor (Annealed Copper)
Insulation (XLPE Compound)
Inner Covering (PVC Compound)
Round Aluminium Wire armour
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
Constructions :
Conductor (Annealed Copper)
Insulation (XLPE Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Galvanized Round Steel Wire armour
Binding tape (Manufacturer's option)
Outer sheath (PVC Compound)
Page - 66
600/1000V XLPE INSULATED, ALUMINIUMWIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/AWA/PVC (acc. to IEC 60502-1)
600/1000V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/SWA/PVC (acc. to IEC 60502-1)
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
1
2
4
5
3
6
1
2
4
5
3
6
7
1
2
4
5
3
6
1
2
4
5
3
6
7
8
8
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Inner covering : PVC Compound Maximum 90C
Armour : AluminiumWire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown
Sheath - Black
SINGLE CORE
16 CM 7 4.7 0.7 1.0 0.8 1.8 13.5 325 1.15
25 CM 7 5.9 0.9 1.0 0.8 1.8 15.5 435 0.727
35 CM 7 7.1 0.9 1.0 0.8 1.8 16.5 545 0.524
50 CM 19 8.1 1.0 1.0 1.25 1.8 18.5 715 0.387
70 CM 19 9.7 1.1 1.0 1.25 1.8 20.0 940 0.268
95 CM 19 11.6 1.1 1.0 1.25 1.8 22.0 1215 0.193
120 CM 37 12.9 1.2 1.0 1.6 1.8 24.5 1565 0.153
150 CM 37 14.3 1.4 1.0 1.6 1.8 26.5 1865 0.124
185 CM 37 16.0 1.6 1.0 1.6 1.8 28.5 2270 0.0991
240 CM 37 18.3 1.7 1.0 1.6 1.9 31.0 2860 0.0754
300 CM 61 20.7 1.8 1.0 1.6 1.9 34.0 3490 0.0601
400 CM 61 23.4 2.0 1.2 2.0 2.1 38.5 4385 0.0470
500 CM 61 26.5 2.2 1.2 2.0 2.2 42.0 5485 0.0366
630 CM 91 30.3 2.4 1.2 2.0 2.3 46.5 6930 0.0283
800 CM 91 34.3 2.6 1.4 2.5 2.5 52.5 8915 0.0221
1000 RM 127 41.6 2.8 1.4 2.5 2.5 60.5 11315 0.0176
Note RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 67
(approx.)
Nominal
diameter of
Aluminium
wire
mm mm mm
area (approx.)
Cross- of
section
Nominal Diameter
Maximum
(approx.)
Insulation
Conductor
of of of
Thickness
of Inner
covering
Shape
Conductor
of number
Cond. of wire
of
cable at 20C
Thickness Weight diameter
cable
/km
Resistance
kg/km - Number
Thickness
mm mm mm mm
(approx.)
Sheath
Conductor Nominal Nominal Overall
600/1000 V XLPE INSULATED, ALUMINIUMWIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / AWA / PVC (IEC 60502-1)
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Blue
Sheath - Black
TWO CORES
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 13.5 315 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 14.0 325 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 14.5 355 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 15.0 375 7.41
4 RE 1 2.26 0.7 1.0 0.8 1.8 15.5 425 4.61
4 RM 7 2.6 0.7 1.0 0.8 1.8 16.0 440 4.61
6 RE 1 2.77 0.7 1.0 0.8 1.8 16.5 485 3.08
6 RM 7 3.1 0.7 1.0 0.8 1.8 17.0 515 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 20.0 760 1.83
16 CM 7 4.7 0.7 1.0 1.25 1.8 21.0 910 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 25.0 1345 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.8 27.5 1630 0.524
50 CM 19 8.1 1.0 1.0 1.6 1.8 30.0 1965 0.387
70 CM 19 9.7 1.1 1.0 1.6 2.0 34.0 2550 0.268
95 CM 19 11.6 1.1 1.2 2.0 2.1 39.0 3520 0.193
120 CM 37 12.9 1.2 1.2 2.0 2.2 42.0 4160 0.153
150 CM 37 14.3 1.4 1.2 2.0 2.3 46.0 4970 0.124
185 CM 37 16.0 1.6 1.4 2.5 2.5 52.0 6435 0.0991
240 CM 37 18.3 1.7 1.4 2.5 2.7 57.5 7895 0.0754
300 CM 61 20.7 1.8 1.6 2.5 2.8 63.0 9545 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal Nominal
Resistance
Page - 68
Diameter Thickness Shape
Insulation section Conductor
mm mm
Overall Maximum
(approx.)
Weight diameter
cable cable at 20C
(approx.)
mm mm
Conductor
Cross- of of of of of
Nominal
area (approx.)
- mm mm /km mm kg/km
covering
(approx.)
Nominal
diameter
of
Steel wire
Thickness
of Inner of number
Cond. of wire
Number
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black
THREE CORES
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 14.0 345 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 14.5 360 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 15.0 400 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 15.5 420 7.41
4 RE 1 2.26 0.7 1.0 0.8 1.8 16.0 475 4.61
4 RM 7 2.6 0.7 1.0 0.8 1.8 17.0 505 4.61
6 RE 1 2.77 0.7 1.0 0.8 1.8 17.0 570 3.08
6 RM 7 3.1 0.7 1.0 0.8 1.8 18.0 595 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 20.5 890 1.83
16 CM 7 4.7 0.7 1.0 1.25 1.8 22.0 1090 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 26.5 1625 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.8 29.0 2015 0.524
50 CM 19 8.1 1.0 1.0 1.6 1.9 31.5 2465 0.387
70 CM 19 9.7 1.1 1.2 2.0 2.0 37.0 3525 0.268
95 CM 19 11.6 1.1 1.2 2.0 2.2 41.5 4495 0.193
120 CM 37 12.9 1.2 1.2 2.0 2.3 45.0 5385 0.153
150 CM 37 14.3 1.4 1.4 2.5 2.5 50.0 6920 0.124
185 CM 37 16.0 1.6 1.4 2.5 2.6 55.0 8285 0.0991
240 CM 61 18.3 1.7 1.6 2.5 2.8 61.5 10400 0.0754
300 CM 61 20.7 1.8 1.6 2.5 3.0 67.5 12550 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 69
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)
of Resistance
section Conductor Insulation Cond. of wire
of of of
Nominal Diameter Thickness Thickness diameter Weight Conductor
cable at 20C
Thickness Nominal
of Inner of
Maximum Conductor Nominal Nominal Overall
Cross-
area (approx.) (approx.)
Sheath cable covering of
(approx.) Steel wire
mm mm mm - Number /km mm mm
(approx.)
mm kg/km mm
diameter
Shape
of number
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey,, Blue
Sheath - Black
FOUR CORES
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 15.0 385 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 15.5 400 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 16.0 455 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 16.5 475 7.41
4 RE 1 2.26 0.7 1.0 0.8 1.8 17.0 550 4.61
4 RM 7 2.6 0.7 1.0 0.8 1.8 18.0 575 4.61
6 RE 1 2.77 0.7 1.0 1.25 1.8 19.0 755 3.08
6 RM 7 3.1 0.7 1.0 1.25 1.8 19.5 795 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 22.0 1040 1.83
16 CM 7 4.7 0.7 1.0 1.25 1.8 23.5 1295 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 28.5 1955 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.9 31.5 2440 0.524
50 CM 19 8.1 1.0 1.0 1.6 2.0 34.5 3040 0.387
70 CM 19 9.7 1.1 1.2 2.0 2.2 40.5 4345 0.268
95 CM 19 11.6 1.1 1.2 2.0 2.3 45.0 5580 0.193
120 CM 37 12.9 1.2 1.4 2.5 2.5 50.0 7195 0.153
150 CM 37 14.3 1.4 1.4 2.5 2.6 55.0 8600 0.124
185 CM 37 16.0 1.6 1.4 2.5 2.8 60.5 10390 0.0991
240 CM 37 18.3 1.7 1.6 2.5 3.0 67.5 13060 0.0754
300 CM 61 20.7 1.8 1.6 2.5 3.2 74.0 15810 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
/km
(approx.)
mm mm
Page - 70
kg/km
(approx.)
- Number mm mm mm
(approx.) Steel wire area
mm mm
(approx.)
at 20C section Conductor Insulation covering of of wire Sheath cable cable
diameter Weight Conductor
Cross- of of of of of Resistance
Nominal Diameter Thickness Thickness Thickness Nominal Shape
Conductor Nominal Nominal Overall Maximum
of Inner diameter number
Cond.
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)
of
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Galvanized Steel Wire
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black
FIVE CORES
1.5 RE 1 1.38 0.7 1.0 0.8 1.8 16.0 430 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 1.8 16.5 450 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 1.8 17.0 510 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 1.8 17.5 535 7.41
4 RE 1 2.26 0.7 1.0 1.25 1.8 19.0 730 4.61
4 RM 7 2.6 0.7 1.0 1.25 1.8 19.5 765 4.61
6 RE 1 2.77 0.7 1.0 1.25 1.8 20.5 905 3.08
6 RM 7 3.1 0.7 1.0 1.25 1.8 21.0 910 3.08
10 RM 7 4.1 0.7 1.0 1.25 1.8 24.0 1205 1.83
16 CM 7 4.7 0.7 1.0 1.6 1.8 26.5 1670 1.15
25 CM 7 5.9 0.9 1.0 1.6 1.8 30.5 2290 0.727
35 CM 7 7.1 0.9 1.0 1.6 1.9 34.0 2880 0.524
50 CM 19 8.1 1.0 1.2 2.0 2.1 39.0 3920 0.387
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Maximum
Page - 71
Overall
600/1000 V XLPE INSULATED, STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE / SWA / PVC (IEC 60502-1)
Conductor Nominal Nominal
Conductor Nominal Diameter Thickness Weight Shape
of Resistance Cross- of of of Inner of number diameter of of
Thickness Nominal Thickness diameter
of Sheath Cond. of wire section Conductor Insulation covering cable cable at 20C
area (approx.) (approx.) Steel wire (approx.) (approx.)
- mm mm mm Number /km mm mm mm mm kg/km
Section 3- XLPE Insulated Cables
Armoured Cables
Conductor (Annealed Copper)
Insulation (XLPE Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Galvanized Flat Steel Wire armour
Galvanized Steel Tape binding
Outer sheath (PVC Compound)
600/1000V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (acc. to IEC 60502-1)
Page - 72
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
1
2
4
5
3
6
1
2
4
5
3
6
7
8
8
7
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Black
Sheath - Black
TWO CORES
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 14.0 365 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 14.0 400 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 14.5 430 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 15.0 435 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 15.5 505 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 16.0 515 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 16.5 575 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 17.0 600 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 19.0 745 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 20.5 900 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 23.5 1190 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.8 26.0 1475 0.524
50 CM 6 8.1 1.0 1.0 0.8 0.3 1.8 28.5 1805 0.387
70 CM 12 9.7 1.1 1.0 0.8 0.3 1.9 32.0 2330 0.268
95 CM 15 11.6 1.1 1.2 0.8 0.3 2.0 36.5 3035 0.193
120 CM 18 12.9 1.2 1.2 0.8 0.3 2.1 39.5 3635 0.153
150 CM 18 14.3 1.4 1.2 0.8 0.3 2.2 43.5 4385 0.124
185 CM 30 16.0 1.6 1.4 0.8 0.3 2.4 48.5 5345 0.0991
240 CM 34 18.3 1.7 1.4 0.8 0.3 2.6 54.0 6725 0.0754
300 CM 34 20.7 1.8 1.6 0.8 0.3 2.7 60.0 8225 0.0601
400 CM 53 23.4 2.0 1.6 0.8 0.3 3.0 66.5 10210 0.0470
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Nominal
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
Conductor Nominal Overall Nominal
Diameter Thickness
Insulation
Nominal
of
thickness
of Galv.
Flat
/km
Resistance
Weight diameter
cable cable
mm mm mm
Maximum
(approx.)
Conductor
at 20C
(approx.)
of of
section Conductor
of Cross- of
Cond. of wire
mm
area (approx.)
- Number kg/km mm mm
Steel wire
Thickness
of Inner
covering
(approx.)
Thickness
Sheath
Minimum
thickness
of Galv.
Steel tape
mm
Page - 73
Shape Minimum
of number
mm
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue
Sheath - Black
THREE CORES
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 14.5 420 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 14.5 430 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 15.0 460 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 15.5 500 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 16.0 555 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 17.0 595 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 17.5 665 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 18.0 675 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 20.0 885 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 21.5 1090 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 25.0 1470 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.8 27.5 1845 0.524
50 CM 6 8.1 1.0 1.0 0.8 0.3 1.8 30.0 2285 0.387
70 CM 12 9.7 1.1 1.2 0.8 0.3 2.0 34.5 3070 0.268
95 CM 15 11.6 1.1 1.2 0.8 0.3 2.1 39.0 3990 0.193
120 CM 18 12.9 1.2 1.2 0.8 0.3 2.2 42.0 4820 0.153
150 CM 18 14.3 1.4 1.4 0.8 0.3 2.3 46.5 5875 0.124
185 CM 30 16.0 1.6 1.4 0.8 0.3 2.4 52.0 7165 0.0991
240 CM 34 18.3 1.7 1.6 0.8 0.3 2.7 58.0 9125 0.0754
300 CM 34 20.7 1.8 1.6 0.8 0.3 2.8 64.0 11130 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Shape
section Conductor Insulation
of
Thickness
of Resistance of Galv.
diameter Weight Conductor
Maximum
Cross- of of of number
Nominal Diameter Thickness
Nominal
Minimum
cable
of Inner
Sheath cable covering
Nominal Nominal Overall
Thickness thickness
area (approx.) (approx.) (approx.) Steel wire Steel tape
Flat
mm mm kg/km
at 20C
of
Minimum
thickness
of Galv.
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
/km mm
(approx.)
mm mm mm mm mm
Page - 74
Cond. of wire
Conductor
- Number
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Red,Yellow, Blue, Black
Sheath - Black
FOUR CORES
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 15.0 450 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 15.5 485 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 16.0 535 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 16.5 545 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 17.0 640 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 18.0 660 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 18.5 645 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 19.0 785 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 21.5 1040 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 23.0 1295 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 27.0 1795 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.8 30.0 2265 0.524
50 CM 6 8.1 1.0 1.0 0.8 0.3 1.9 32.5 2830 0.387
70 CM 12 9.7 1.1 1.2 0.8 0.3 2.1 38.0 3840 0.268
95 CM 15 11.6 1.1 1.2 0.8 0.3 2.2 42.5 5015 0.193
120 CM 18 12.9 1.2 1.4 0.8 0.3 2.3 47.0 6145 0.153
150 CM 18 14.3 1.4 1.4 0.8 0.3 2.5 51.5 7450 0.124
185 CM 30 16.0 1.6 1.4 0.8 0.3 2.7 57.5 9125 0.0991
240 CM 34 18.3 1.7 1.6 0.8 0.3 2.9 64.0 11670 0.0754
300 CM 34 20.7 1.8 1.6 0.8 0.3 3.1 70.5 14270 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Resistance
(approx.) Steel wire
Nominal
mm /km kg/km
of of of
cable
mm
at 20C Flat Sheath cable
diameter
mm
section
mm mm mm mm - Number
area (approx.) (approx.) (approx.)
Shape Minimum
of
Weight
of Galv.
Steel tape
mm
Conductor Insulation covering
Conductor
Cross- of of
Diameter Thickness Thickness
of Galv. thickness of Inner
Overall
Minimum
Nominal
Thickness thickness
Nominal Maximum
Nominal
Conductor
Page - 75
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
Cond. of wire
number
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 1 or 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : XLPE Compound
Armour : Galvanized Flat Steel Wire+Steel tape open helix
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Black with numbering code
Sheath - Black
FIVE CORES
1.5 RE 1 1.38 0.7 1.0 0.8 0.3 1.8 16.0 510 12.1
1.5 RM 7 1.6 0.7 1.0 0.8 0.3 1.8 16.5 520 12.1
2.5 RE 1 1.78 0.7 1.0 0.8 0.3 1.8 17.0 605 7.41
2.5 RM 7 2.0 0.7 1.0 0.8 0.3 1.8 17.5 615 7.41
4 RE 1 2.26 0.7 1.0 0.8 0.3 1.8 18.5 730 4.61
4 RM 7 2.6 0.7 1.0 0.8 0.3 1.8 19.0 750 4.61
6 RE 1 2.77 0.7 1.0 0.8 0.3 1.8 20.0 875 3.08
6 RM 7 3.1 0.7 1.0 0.8 0.3 1.8 20.5 900 3.08
10 RE 1 4.1 0.7 1.0 0.8 0.3 1.8 23.0 1200 1.83
16 CM 6 4.7 0.7 1.0 0.8 0.3 1.8 25.0 1512 1.15
25 CM 6 5.9 0.9 1.0 0.8 0.3 1.8 29.0 2100 0.727
35 CM 6 7.1 0.9 1.0 0.8 0.3 1.9 32.5 2700 0.524
50 CM 6 8.1 1.0 1.2 0.8 0.3 2.0 36.0 3435 0.387
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
diameter Minimum Nominal Diameter Thickness Thickness thickness Weight Conductor
Cross- of of of Inner of Galv. of of
Thickness
of Resistance
section Conductor Insulation covering Flat Sheath cable at 20C
area (approx.) (approx.) Steel wire (approx.) (approx.)
of Galv.
mm mm mm
cable
mm mm mm mm kg/km mm /km
Steel tape
thickness
Conductor Nominal Nominal Overall Maximum
Page - 76
600/1000 V XLPE INSULATED, FLAT STEEL WIRE ARMOURED AND PVC SHEATHED CABLES
XLPE/FSWA/PVC (IEC 60502-1)
Nominal
- Number
Minimum
of number
Cond. of wire
Shape
Section 3- XLPE Insulated Cables
Armoured Cables
Constructions :
Conductor (Annealed Copper)
Insulation (XLPE Compound)
Inner Covering (PVC Compound)
Double Aluminium Tape armour
Outer sheath (PVC Compound)
Constructions :
Conductor (Annealed Copper)
Insulation (XLPE Compound)
Filler (Polyprophylene yarn,or extruded filler
up to request)
Binding tape (Manufacturer's option)
Inner Covering (PVC Compound)
Double Galvanized Steel Tape armour
Outer sheath (PVC Compound)
Page - 77
600/1000V XLPE INSULATED, ALUMINIUMTAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DATA/PVC (acc. to IEC 60502-1)
600/1000V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (acc. to IEC 60502-1)
Note : Special application upon request
* Available product in accordance to : SPLN, ICEA/NEMA,
AS standard or other requirement.
* Flame retardant test acc to IEC 60332-3 Cat. A, B or C.
* Anti termite performance.
* Tin coated Copper conductor.
* Polyethylene / Low smoke Halogen Free sheathed
1
2
4
5
3
6
1
2
4
5
3
6
7
7
1
2
4
5
3
1
2
4
5
3
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Inner covering : PVC Compound Maximum 90C
Armour : Double Aluminiumtape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown
Sheath - Black
SINGLE CORE
16 CM 6 4.7 0.7 1.0 0.5 1.8 13.5 335 1.15
25 CM 6 5.9 0.9 1.0 0.5 1.8 15.0 455 0.727
35 CM 6 7.1 0.9 1.0 0.5 1.8 16.5 570 0.524
50 CM 6 8.1 1.0 1.0 0.5 1.8 17.5 705 0.387
70 CM 12 9.7 1.1 1.0 0.5 1.8 19.5 930 0.268
95 CM 15 11.6 1.1 1.0 0.5 1.8 21.5 1210 0.193
120 CM 15 12.9 1.2 1.0 0.5 1.8 23.0 1470 0.153
150 CM 15 14.3 1.4 1.0 0.5 1.8 24.5 1760 0.124
185 CM 30 16.0 1.6 1.0 0.5 1.8 27.0 2155 0.0991
240 CM 30 18.3 1.7 1.0 0.5 1.8 29.5 2735 0.0754
300 CM 30 20.7 1.8 1.0 0.5 1.9 32.0 3365 0.0601
400 CM 53 23.4 2.0 1.2 0.5 2.0 35.5 4240 0.0470
500 CM 53 26.5 2.2 1.2 0.5 2.1 39.5 5350 0.0366
630 CM 53 30.3 2.4 1.2 0.5 2.3 44.0 6670 0.0283
Page - 78
600/1000 V XLPE INSULATED, ALUMINIUMTAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DATA/PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal Nominal
Weight diameter Thickness
(approx.)
of of
cable
Overall
at 20C
Maximum
/km
Resistance
Nominal Diameter Thickness
(approx.)
Insulation
Conductor
cable
of Cross- of of
section Conductor Cond. of wire
- Number
of Inner
covering
Nominal
(approx.)
Thickness
of
mm mm
area (approx.)
mm kg/km mm mm
Shape Minimum
of number
Aluminium
tape
mm mm
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Blue
Sheath - Black
TWO CORES
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 12.5 220
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 13.0 230 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 13.0 260 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 13.5 270 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 14.0 315 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 15.0 330 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 15.0 375 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 16.0 390 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 18.0 515 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 19.0 645 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 23.0 895 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.8 24.5 1135 0.524
50 CM 6 8.1 1.0 1.0 0.2 1.8 27.0 1425 0.387
70 CM 12 9.7 1.1 1.0 0.2 1.9 30.5 1905 0.268
95 CM 15 11.6 1.1 1.2 0.2 2.0 35.0 2545 0.193
120 CM 18 12.9 1.2 1.2 0.5 2.1 39.5 3505 0.153
150 CM 18 14.3 1.4 1.4 0.5 2.3 43.5 4245 0.124
185 CM 30 16.0 1.6 1.4 0.5 2.4 48.5 5180 0.0991
240 CM 34 18.3 1.7 1.6 0.5 2.6 54.0 6530 0.0754
300 CM 34 20.7 1.8 1.6 0.5 2.7 59.5 8005 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 79
Thickness
of Inner
covering
(approx.)
Nominal
thickness
of
Steel tape
mm mm mm kg/km mm mm mm mm
area (approx.)
-
Insulation
Conductor
Cross- of of of of of
section Conductor
Nominal Diameter Thickness Shape Minimum
(approx.)
/km
Resistance
Overall Maximum
(approx.)
Weight diameter
cable cable at 20C
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
Thickness
Sheath
Conductor Nominal Nominal
of number
Cond. of wire
Number
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey
Sheath - Black
THREE CORES
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 13.0 250
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 13.5 260 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 13.5 295 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 14.0 310 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 15.0 265 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 15.5 385 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 16.0 445 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 16.5 465 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 18.5 630 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 20.0 815 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 23.5 1150 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.8 26.0 1485 0.524
50 CM 6 8.1 1.0 1.0 0.2 1.8 28.5 1885 0.387
70 CM 12 9.7 1.1 1.2 0.2 1.9 33.0 2590 0.268
95 CM 15 11.6 1.1 1.2 0.2 2.1 37.5 3460 0.193
120 CM 18 12.9 1.2 1.2 0.5 2.2 42.0 4670 0.153
150 CM 18 14.3 1.4 1.4 0.5 2.4 46.5 5710 0.124
185 CM 30 16.0 1.6 1.4 0.5 2.5 51.5 6965 0.0991
240 CM 34 18.3 1.7 1.6 0.5 2.7 58.0 8905 0.0754
300 CM 34 20.7 1.8 1.6 0.5 2.9 64.0 10920 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 80
Thickness Nominal
(approx.)
mm kg/km /km mm mm mm mm mm mm - Number
area (approx.) (approx.)
Sheath cable covering of
(approx.) Steel tape
section cable at 20C
Conductor Nominal Nominal Overall
of Inner thickness
Maximum
Nominal Diameter Thickness Thickness diameter Weight
of of Resistance Cross- of of
Insulation
of
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
Conductor
number
Cond. of wire Conductor
of
Shape Minimum
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue
Sheath - Black
FOUR CORES
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 13.5 280
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 14.0 295 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 14.5 345 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 15.0 360 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 16.0 430 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 16.5 450 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 17.0 535 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 17.5 555 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 20.0 765 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 21.5 1000 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 25.5 1435 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.8 28.5 1860 0.524
50 CM 6 8.1 1.0 1.0 0.2 1.9 31.5 2385 0.387
70 CM 12 9.7 1.1 1.2 0.2 2.0 36.0 3315 0.268
95 CM 15 11.6 1.1 1.2 0.5 2.2 42.5 4875 0.193
120 CM 18 12.9 1.2 1.4 0.5 2.4 46.5 5985 0.153
150 CM 18 14.3 1.4 1.4 0.5 2.5 51.0 7275 0.124
185 CM 30 16.0 1.6 1.4 0.5 2.7 57.0 8925 0.0991
240 CM 34 18.3 1.7 1.6 0.5 2.9 64.0 11430 0.0754
300 CM 34 20.7 1.8 1.6 0.5 3.1 70.5 14015 0.0601
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 81
Thickness Nominal
of Inner thickness
Overall Maximum
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
Thickness
Conductor Nominal Nominal
Nominal Diameter Thickness Shape Minimum diameter Weight Conductor
Cross- of of of number of of
Insulation covering of Cond.
of Resistance
cable at 20C
(approx.)
Sheath cable
(approx.) Steel tape
mm
of wire
area (approx.)
section Conductor
/km mm mm
(approx.)
mm mm mm kg/km - Number mm
Section 3- XLPE Insulated Cables
Armoured Cables
CONSTRUCTION TECHNICAL DATA
Conductor : Plain Annealed Copper Voltage
(to IEC 60228 class 2) Uo/U - 600/1000 V
Insulation : XLPE Compound Operating Temperature
Filler : Suitable material Maximum 90C
Inner covering : PVC Compound
Armour : Double Galvanized Steel tape
Sheath : PVC Compound type ST2
Colour Ident. : Insulation - Brown, Black, Grey, Blue, Green / Yellow Stripe
Sheath - Black
FIVE CORES
1.5 RE 1 1.38 0.7 1.0 0.2 1.8 14.5 320
1.5 RM 7 1.6 0.7 1.0 0.2 1.8 15.0 335 12.1
2.5 RE 1 1.78 0.7 1.0 0.2 1.8 15.5 390 7.41
2.5 RM 7 2.0 0.7 1.0 0.2 1.8 16.0 405 7.41
4 RE 1 2.26 0.7 1.0 0.2 1.8 17.0 500 4.61
4 RM 7 2.6 0.7 1.0 0.2 1.8 17.5 520 4.61
6 RE 1 2.77 0.7 1.0 0.2 1.8 18.5 620 3.08
6 RM 7 3.1 0.7 1.0 0.2 1.8 19.0 645 3.08
10 RM 7 4.1 0.7 1.0 0.2 1.8 22.0 900 1.83
16 CM 6 4.7 0.7 1.0 0.2 1.8 23.5 1200 1.15
25 CM 6 5.9 0.9 1.0 0.2 1.8 27.5 1720 0.727
35 CM 6 7.1 0.9 1.0 0.2 1.9 31.0 2255 0.524
50 CM 6 8.1 1.0 1.2 0.2 2.0 35.0 2950 0.387
Note RE : Round Solid Class 1
RM : Circular Stranded Class 2
CM : Circular Stranded Compacted Class 2
Page - 82
Conductor Nominal Nominal Overall Maximum
Nominal Thickness diameter Nominal Diameter Thickness Weight Conductor
Cross- of of of Inner thickness of of
Thickness
of Sheath cable at 20C section Conductor Insulation covering
(approx.) (approx.)
of Resistance
area (approx.) (approx.) Steel tape
cable
kg/km /km mm mm
Cond.
mm mm mm mm mm
of number
Shape Minimum
600/1000 V XLPE INSULATED, STEEL TAPE ARMOURED AND PVC SHEATHED CABLES
XLPE/DSTA/PVC (IEC 60502-1)
of wire
- Number
DC Minimum Conductor
In Conductor Insulation Short
InDucts Air Ground
1)
Resistance Nominal Resistance circuit
Flat Trefoil
Flat / Trefoil
Trefoil
at 20C Capacitance current /
Unarmour Armour Unarmour Armour Unarmour Armour Unarmour Armour Unarmour Armour
coretocore coretocore 1sec
A A A A / km / km / km / km / km / km / km / km / km / km / km F/ km M . km kA
1.5 re/rm 22 21 20 23 12.1 15.4 - 0.1395 - 0.1541 - 0.4442 - 0.4905 - 0.0520 3000 0.215
2.5 re/rm 30 29 28 30 7.41 9.45 - 0.1280 - 0.1425 - 0.4074 - 0.4536 - 0.0571 2500 0.358
4 re/rm 42 40 37 39 4.61 5.88 - 0.1190 - 0.1335 - 0.3788 - 0.4250 - 0.0621 2000 0.572
6 re/rm 55 53 48 49 3.08 3.93 - 0.1109 - 0.1254 - 0.3531 - 0.3993 - 0.0665 2000 0.858
10 re/rm 77 74 66 65 1.83 2.34 - 0.1028 - 0.1173 - 0.3273 - 0.3735 - 0.0721 1500 1.430
16 cm 105 101 88 84 1.15 1.47 1.47 0.0984 0.1264 0.1129 0.1409 0.3131 0.4024 0.3593 0.4486 0.0751 1500 2.288
25 cm 141 135 117 107 0.727 0.927 0.927 0.0946 0.1190 0.1091 0.1335 0.3011 0.3789 0.3473 0.4251 0.0752 1500 3.575
35 cm 176 169 144 129 0.524 0.669 0.668 0.0900 0.1123 0.1045 0.1268 0.2865 0.3575 0.3327 0.4037 0.0789 1000 5.005
50 cm 216 207 175 153 0.387 0.494 0.494 0.0879 0.1109 0.1024 0.1254 0.2798 0.3529 0.3260 0.3991 0.0796 1000 7.150
70 cm 279 268 222 188 0.268 0.342 0.342 0.0847 0.1052 0.0992 0.1198 0.2697 0.3350 0.3159 0.3812 0.0815 900 10.01
95 cm 342 328 269 226 0.193 0.247 0.247 0.0818 0.0995 0.0963 0.1140 0.2603 0.3166 0.3065 0.3628 0.0848 800 13.59
120 cm 400 383 312 257 0.153 0.196 0.196 0.0805 0.0996 0.0951 0.1141 0.2564 0.3169 0.3026 0.3631 0.0853 800 17.16
150 cm 464 444 342 287 0.124 0.159 0.159 0.0807 0.0975 0.0952 0.1121 0.2567 0.3105 0.3029 0.3567 0.0846 800 21.45
185 cm 533 510 384 324 0.0991 0.128 0.128 0.0804 0.0958 0.0949 0.1103 0.2559 0.3048 0.3021 0.3510 0.0833 900 26.46
240 cm 634 607 450 375 0.0754 0.0983 0.0978 0.0786 0.0926 0.0931 0.1071 0.2502 0.2947 0.2964 0.3409 0.0848 800 34.32
300 cm 736 703 514 419 0.0601 0.0794 0.0788 0.0776 0.0903 0.0921 0.1048 0.2469 0.2873 0.2931 0.3335 0.0860 800 42.90
400 cm 868 823 661 495 0.0470 0.0634 0.0627 0.0769 0.0904 0.0915 0.1049 0.2449 0.2877 0.2911 0.3339 0.0865 700 57.20
500 cm 998 946 760 559 0.0366 0.0511 0.0502 0.0762 0.0883 0.0907 0.1029 0.2425 0.2812 0.2888 0.3274 0.0871 700 71.50
630 cm 1151 1088 879 635 0.0283 0.0416 0.0411 0.0756 0.0862 0.0901 0.1007 0.2406 0.2743 0.2869 0.3205 0.0880 700 90.09
800 cm 1328 1252 1020 725 0.0221 0.0349 0.0337 0.0750 0.0860 0.0896 0.1005 0.2389 0.2738 0.2851 0.3200 0.0883 700 114.40
1000 rm 1511 1420 1173 819 0.0176 0.0305 0.0291 0.0730 0.0829 0.0876 0.0974 0.2325 0.2639 0.2787 0.3101 0.0902 600 143.00
Note: re : Roundsolidconductor IEC60228class 1 Thermal resistivity of soil : 2.5K.m/ W Note:
1)
Referencemethodeof installationtobeusedtoobtaincurrent carrying
rm : Circular strandedconductor IEC60228class 2 Depthof laying : 80cm capacity for : incableducting, incables conduit, cables direct inthe-
cm : Circular strandedcompactedconductor IEC60228class 2 Basetemperature : 20C groundwith/ without addedprotectionagainst mechanical damage
2)
TheInductancecalculatedfor armour cableis AmuminiumWire Armour (AWA)
CURRENT CARRYING CAPACITY FOR SINGLE CORE XLPE INSULATEDCABLE
Current CarryingCapacity
Reactance
2)
(50Hz) Inductance
2)
(50Hz)
Alternating
Current Conductor
Nominal
Area
mm
resistance
at 90C/ 50Hz
Trefoil
Underground :
Trefoil InTray
InAir ( 30C)
Flat Flat
S
e
c
t
i
o
n

4

-

G
e
n
e
r
a
l

I
n
f
o
r
m
a
t
i
o
n
P
a
g
e

-

8
3
DC Alternating Minimum Conductor
Conductor Current Insulation Short
Resistance resistance Nominal Resistance circuit
2 3 / 4 * 2 3 / 4 * 2 3 / 4 * 2 3 / 4 * at 20C at 90C / 2 / 3 4 2 / 3 4 Capacitance current /
Core Core Core Core Core Core Core Core 50 Hz Core Core Core Core core to core core to core 1 sec
A A A A A A A A / km / km / km / km mH/ km mH/ km F / km M . km kA
1.5 re/rm 26 23 22 19.5 27 23 25 21 12.1 15.4 0.1044 0.1117 0.3323 0.3554 0.0520 3000 0.215
2.5 re/rm 36 32 30 26 35 30 33 28 7.41 9.45 0.0959 0.1031 0.3052 0.3283 0.0571 2500 0.358
4 re/rm 49 42 40 35 46 39 43 36 4.61 5.88 0.0906 0.0979 0.2884 0.3115 0.0621 2000 0.572
6 re/rm 63 54 51 44 58 49 53 44 3.08 3.93 0.0850 0.0923 0.2706 0.2937 0.0665 2000 0.858
10 re/rm 86 75 69 60 77 65 71 58 1.83 2.33 0.0807 0.0880 0.2570 0.2801 0.0721 1500 1.430
16 cm 115 100 91 80 100 84 91 75 1.15 1.47 0.0781 0.0853 0.2485 0.2716 0.0751 1500 2.288
25 cm 149 127 119 105 129 107 116 96 0.727 0.927 0.0779 0.0852 0.2480 0.2711 0.0752 1500 3.575
35 cm 185 158 146 128 155 129 139 115 0.524 0.669 0.0753 0.0826 0.2397 0.2628 0.0789 1000 5.005
50 cm 225 192 175 154 183 153 164 135 0.387 0.494 0.0747 0.0820 0.2379 0.2610 0.0796 1000 7.150
70 cm 289 246 221 194 225 188 203 167 0.268 0.342 0.0734 0.0806 0.2335 0.2566 0.0815 900 10.01
95 cm 352 298 265 233 270 226 239 197 0.193 0.247 0.0711 0.0783 0.2262 0.2493 0.0848 800 13.59
120 cm 410 346 305 268 306 257 271 223 0.153 0.196 0.0708 0.0781 0.2254 0.2485 0.0853 800 17.16
150 cm 473 399 334 300 343 287 306 251 0.124 0.160 0.0712 0.0785 0.2267 0.2498 0.0846 800 21.45
185 cm 542 456 384 340 387 324 343 281 0.0991 0.128 0.0720 0.0793 0.2292 0.2523 0.0833 900 26.46
240 cm 641 538 459 398 448 375 395 324 0.0754 0.0987 0.0711 0.0784 0.2264 0.2495 0.0848 800 34.32
300 cm 741 621 532 455 502 419 446 365 0.0601 0.0798 0.0704 0.0776 0.2240 0.2471 0.0860 800 42.90
400 cm 892 745 628 552 593 495 521 426 0.0470 0.0640 0.0701 0.0773 0.2231 0.2462 0.0865 700 57.20
Note : re : Round solid conductor IEC60228 class 1 Thermal resistivity of soil : 2.5 K.m/ W 4* : 3 Phasa + Netral / Ground
rm : Circular stranded conductor IEC60228 class 2 Depth of laying : 80 cm
cm : Circular stranded compacted conductor IEC60228 class 2 Base temperature : 20C
CURRENT CARRYING CAPACITY FOR MULTICORE XLPE INSULATEDCABLE
Reactance (50 Hz) Inductance (50 Hz)
Conductor In Air ( 30C)
Nominal
Area
mm
Underground :
Current Carrying Capacity
Direct Burried ground Burried ducts ground
Underground at 20C
In Tray In Ducts
S
e
c
t
i
o
n

4

-

G
e
n
e
r
a
l

I
n
f
o
r
m
a
t
i
o
n
P
a
g
e

-

8
4
DC Minimum Conductor
In Conductor Insulation Short
InDucts Air Ground
1)
Resistance Nominal Resistance circuit
Flat Trefoil
Flat / Trefoil
Trefoil
at 20C Capacitance at 20C current /
Unarmour Armour Unarmour Armour Unarmour Armour Unarmour Armour Unarmour Armour
coretocore coretocore 1sec
A A A A / km / km / km / km / km / km / km / km / km / km / km F/ km M . km kA
1.5 re/rm 18 17.5 15.5 19 12.1 14.5 - 0.1418 - 0.1563 - 0.4513 - 0.4975 - 0.1391 50 0.174
2.5 re/rm 25 24 21 24 7.41 8.87 - 0.1300 - 0.1445 - 0.4139 - 0.4601 - 0.1531 50 0.290
4 re/rm 34 33 28 33 4.61 5.52 - 0.1245 - 0.1390 - 0.3962 - 0.4424 - 0.1553 50 0.464
6 re/rm 45 43 36 41 3.08 3.69 - 0.1160 - 0.1305 - 0.3693 - 0.4155 - 0.1671 50 0.696
10 re/rm 63 60 50 54 1.83 2.19 - 0.1073 - 0.1218 - 0.3416 - 0.3878 - 0.1827 50 1.160
16 rm 85 82 68 70 1.15 1.376 1.376 0.0997 0.1253 0.1142 0.1399 0.3172 0.3990 0.3634 0.4452 0.1966 40 1.856
25 rm 114 110 89 92 0.727 0.870 0.870 0.0956 0.1181 0.1101 0.1326 0.3044 0.3759 0.3506 0.4221 0.2001 40 2.900
35 rm 143 137 110 110 0.524 0.627 0.627 0.0914 0.1145 0.1059 0.1290 0.2908 0.3643 0.3370 0.4105 0.2100 40 4.060
50 rm 174 167 134 130 0.387 0.463 0.463 0.0886 0.1090 0.1031 0.1235 0.2821 0.3470 0.3283 0.3932 0.2127 30 5.800
70 rm 225 216 171 162 0.268 0.321 0.321 0.0848 0.1034 0.0993 0.1179 0.2700 0.3291 0.3162 0.3753 0.2223 30 8.120
95 rm 275 264 207 193 0.193 0.232 0.232 0.0844 0.1028 0.0989 0.1173 0.2687 0.3273 0.3149 0.3735 0.2205 30 11.02
120 rm 321 308 239 220 0.153 0.184 0.184 0.0820 0.0991 0.0965 0.1136 0.2609 0.3155 0.3072 0.3617 0.2270 30 13.92
150 rm 372 356 262 246 0.124 0.150 0.149 0.0817 0.0968 0.0962 0.1114 0.2600 0.3083 0.3062 0.3545 0.2274 20 17.40
185 rm 427 409 296 278 0.0991 0.120 0.120 0.0807 0.0947 0.0952 0.1092 0.2568 0.3014 0.3030 0.3476 0.2279 20 21.46
240 rm 507 485 346 320 0.0754 0.0925 0.0920 0.0796 0.0917 0.0941 0.1062 0.2533 0.2920 0.2995 0.3382 0.2308 20 27.84
0.0000
300 rm 587 561 394 359 0.0601 0.0746 0.0742 0.0823 0.0915 0.0968 0.1060 0.2618 0.2913 0.3080 0.3375 0.2323 20 34.80
400 rm 689 656 510 428 0.0470 0.0598 0.0591 0.0784 0.0905 0.0929 0.1050 0.2495 0.2880 0.2957 0.3342 0.2387 20 46.40
500 rm 789 749 587 485 0.0366 0.0483 0.0475 0.0777 0.0887 0.0922 0.1032 0.2472 0.2823 0.2934 0.3285 0.2355 20 58.00
630 rm 905 855 678 552 0.0283 0.0396 0.0386 0.0761 0.0870 0.0907 0.1015 0.2424 0.2768 0.2886 0.3230 0.2416 20 73.08
800 rm 1037 1027 788 631 0.0221 0.0335 0.0323 0.0746 0.0849 0.0891 0.0994 0.2375 0.2702 0.2837 0.3164 0.2476 20 92.80
1000 rm 1167 1173 906 715 0.0176 0.0292 0.0279 0.0738 0.0833 0.0883 0.0978 0.2348 0.2652 0.2810 0.3114 0.2500 20 116.00
Note: re : Roundsolidconductor IEC60228class 1 Thermal resistivity of soil : 2.5K.m/ W Note:
1)
Referencemethodeof installationtobeusedtoobtaincurrent carrying
rm : Circular strandedconductor IEC60228class 2 Depthof laying : 80cm capacity for : incableducting, incables conduit, cables direct inthe-
Basetemperature : 20C groundwith/ without addedprotectionagainst mechanical damage
2)
TheInductancecalculatedfor armour cableis AmuminiumWire Armour (AWA)
Nominal
mm
Area
Trefoil
Underground :
Alternating
Conductor
Current CarryingCapacity
resistance Trefoil Flat Flat
at 70C/ 50Hz
Reactance
2)
(50Hz)
Current
InAir ( 30C)
InTray
CURRENT CARRYING CAPACITY FOR SINGLE CORE PVC INSULATEDCABLE
Inductance
2)
(50Hz)
S
e
c
t
i
o
n

4

-

G
e
n
e
r
a
l

I
n
f
o
r
m
a
t
i
o
n
P
a
g
e

-

8
5
DC Alternating Minimum Conductor
Conductor Current Insulation Short
Resistance resistance Nominal Resistance circuit
2 3 / 4 * 2 3 / 4 * 2 3 / 4 * 2 3 / 4 * at 20C at 70C / 2 / 3 4 2 / 3 4 Capacitance at 20C current /
Core Core Core Core Core Core Core Core 50 Hz Core Core Core Core core to core core to core 1 sec
A A A A A A A A / km / km / km / km mH/ km mH/ km F / km M . km kA
1.5 re/rm 22 18.5 16.5 15 22 19 22 18 12.1 14.5 0.1082 0.1155 0.3444 0.3676 0.1391 50 0.174
2.5 re/rm 30 25 23 20 28 24 29 24 7.41 8.87 0.0993 0.1065 0.3160 0.3391 0.1531 50 0.290
4 re/rm 40 34 30 27 38 33 37 30 4.61 5.52 0.0990 0.1062 0.3151 0.3382 0.1553 50 0.464
6 re/rm 51 43 38 34 48 41 46 38 3.08 3.69 0.0926 0.0998 0.2946 0.3177 0.1671 50 0.696
10 re/rm 70 60 52 46 64 54 60 50 1.83 2.19 0.0870 0.0943 0.2770 0.3001 0.1827 50 1.160
16 rm 94 80 69 62 83 70 78 64 1.15 1.38 0.0818 0.0891 0.2604 0.2835 0.1966 40 1.856
25 rm 119 101 90 80 110 92 99 82 0.727 0.870 0.0808 0.0880 0.2571 0.2802 0.2001 40 2.900
35 rm 148 126 111 99 132 110 119 98 0.524 0.627 0.0781 0.0853 0.2485 0.2716 0.2100 40 4.060
50 rm/sm 180 153 133 118 156 130 140 116 0.387 0.464 0.0773 0.0846 0.2462 0.2693 0.2127 30 5.800
70 rm/sm 232 196 168 149 192 162 173 143 0.268 0.321 0.0748 0.0821 0.2382 0.2613 0.2223 30 8.120
95 rm/sm 282 238 201 179 230 193 204 169 0.193 0.232 0.0751 0.0823 0.2389 0.2620 0.2205 30 11.020
120 rm/sm 328 276 232 206 261 220 231 192 0.153 0.184 0.0734 0.0807 0.2337 0.2568 0.2270 30 13.920
150 rm/sm 379 319 258 225 293 246 261 217 0.124 0.150 0.0734 0.0806 0.2336 0.2567 0.2274 20 17.400
185 rm/sm 434 364 294 255 331 278 292 243 0.0991 0.121 0.0731 0.0804 0.2328 0.2559 0.2279 20 21.460
240 rm/sm 514 430 344 297 382 320 336 280 0.0754 0.0928 0.0725 0.0797 0.2307 0.2538 0.2308 20 27.840
300 rm/sm 593 497 394 339 427 359 379 316 0.0601 0.0752 0.0723 0.0795 0.2301 0.2532 0.2323 20 34.80
Note : re : Round solid conductor IEC60228 class 1 Thermal resistivity of soil : 2.5 K.m/ W 4* : 3 Phasa + Netral / Ground
rm : Circular stranded conductor IEC60228 class 2 Depth of laying : 80 cm
sm : Sector shape stranded conductor IEC60228 class 2 Base temperature : 20C
CURRENT CARRYING CAPACITY FOR MULTICORE PVC INSULATEDCABLE
Nominal
Area
Conductor
Direct Burried ground Burried ducts ground
Underground :
mm
Inductance (50 Hz) Reactance (50 Hz)
Underground at 20C In Air ( 30C)
In Tray In Ducts
Current Carrying Capacity
S
e
c
t
i
o
n

4

-

G
e
n
e
r
a
l

I
n
f
o
r
m
a
t
i
o
n
P
a
g
e

-

8
6
Correction factor of Curent carrying capacity
Ratingfactor relatingto openair temperature
Air temperatureC 10 15 20 25 30 35 40 45 50 55 60 65 70 80
PVCInsulation 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61 0.50 - - -
XLPEInsulation 1.15 1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.41
Ratingfactor relatingto Ground temperature
Ground temp C 10 15 20 25 30 35 40 45 50 55 60 65 70 80
PVCInsulation 1.10 1.05 1.00 0.95 0.89 0.84 0.77 0.71 0.63 0.55 0.45 - - -
XLPEInsulation 1.07 1.04 1.00 0.96 0.93 0.89 0.85 0.80 0.76 0.71 0.65 0.60 0.53 0.38
Ratingfactor relatingto themal groundresistivity
0.5 0.7 1 1.5 2 2.5 3.5
1.28 1.20 1.18 1.10 1.05 1 0.96
1.88 1.62 1.50 1.28 1.12 1 0.90
Thermal Resistivity of soil K.m/ W
Corection factor for cables in buried ducts
Corection factor for direct buried cables
Number of core
Rating factor based on 3 core cable for size 1.5 ~ 10 mm
Under ground In Air
5 0.70 0.75
7 0.60 0.65
10 0.50 0.55
14 0.45 0.50
19 0.40 0.45
24 0.35 0.40
40 0.30 0.35
61 0.25 0.30
P
a
g
e

-

8
7
S
e
c
t
i
o
n

4

-

G
e
n
e
r
a
l

I
n
f
o
r
m
a
t
i
o
n
Section 4- General Information
Number
of trays 1 2 3 4 6 9
1 1.00 0.88 0.82 0.79 0.76 0.73
2 1.00 0.87 0.80 0.77 0.73 0.68
3 1.00 0.86 0.79 0.76 0.71 0.66
6 1.00 0.84 0.77 0.73 0.68 0.64
1 1.00 1.00 0.98 0.95 0.91 -
2 1.00 0.99 0.96 0.92 0.87 -
3 1.00 0.98 0.95 0.91 0.85 -
1 1.00 0.88 0.82 0.78 0.73 0.72
2 1.00 0.88 0.81 0.76 0.71 0.70
1 1.00 0.91 0.89 0.88 0.87 -
2 1.00 0.91 0.88 0.87 0.85 -
1 0.97 0.84 0.78 0.75 0.71 0.68
2 0.97 0.83 0.76 0.72 0.68 0.63
3 0.97 0.82 0.75 0.71 0.66 0.61
6 0.97 0.81 0.73 0.69 0.63 0.58
1 1.00 0.87 0.82 0.80 0.79 0.78
2 1.00 0.86 0.80 0.78 0.76 0.73
3 1.00 0.85 0.79 0.76 0.73 0.70
6 1.00 0.84 0.77 0.73 0.68 0.64
1 1.00 1.00 1.00 1.00 1.00 -
2 1.00 0.99 0.98 0.97 0.96 -
3 1.00 0.98 0.97 0.96 0.93 -
NOTE 1 Values given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than 5 %.
NOTE 2 Factor apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each
other. Values for such installations may be significantly lower and has to be determined by an appropriate method
NOTE 3 Values are given for vertical spacing between cable trays of 300 mmand at least 20 mmbetween cable trays and wall. For closer spacing the
factors should be reduced.
NOTE 4 Values are given for horizontal spacing between cable trays of 225 mmwith cable trays mounted back to back. For closer spacing the factor
should be reduced.
Reduction factors for group of more than one multi-core cable
to be applied to reference current-carrying capacities for multi-core cables in free air
Number of cables per trays or ladder
Perforated
Unperforated
systems
Page - 88
Vertical
systems
cleats, etc
( note 3 )
Cable ladder
tray systems
Method of installation
Perforated Cable
systems
Cable tray
( note 4 )
Cable tray
( note 3 )
Touching
Spaced
Touching
Spaced
Touching
Touching
Spaced
Section 4- General Information
to be applied to reference current-carrying capacity for one circuit of single-core
Number of
trays 1 2 3
1 0.98 0.91 0.87
2 0.96 0.87 0.81
3 0.95 0.85 0.78
1 0.96 0.86 -
2 0.95 0.84 -
1 1.00 0.97 0.96
2 0.98 0.93 0.89
3 0.97 0.90 0.86
1 1.00 0.98 0.96
2 0.97 0.93 0.89
3 0.96 0.92 0.86
1 1.00 0.91 0.89
2 1.00 0.90 0.86
1 1.00 1.00 1.00
2 0.97 0.95 0.93
3 0.96 0.94 0.90
NOTE 1 Value given are averages for the cable types and range of conductor sizes considered. The spread of values is generally less than 5 %.
NOTE 2 Factor aer given for single layers of cables ( or trefoil groups ) as shown in the table and do not apply when cables are installed in more than one
layer touching each other. Values for such installations may be significantly lower and should be determined by an appropriate method.
NOTE 3 Values are given for vertical spacing between cable trays of 300 mmand at least 20 mmbetween cable trays and wall. For closer spacing the
factor should be reduced.
NOTE 4 Values are given for horizontal spacings between cable trays of 225 mmwith cable trays mounted back to back. For closer spacing the factors
should be reduced
NOTE 5 For circuits having more than one cable in parallel per phase, each three phase set of conductors should be considered as a circuit for the
purpose of this table
NOTE 6 If a circuit consists of mparallel conductors per phase, then for determining the erduction factor this circuit should be considered as mcircuits
Vertical perforated
( Note 3 )
Page - 89
( Note 4 ) trefoil formation
Cable ladder systems,
cleats, etc
Cable tray systems Three cables in
Perforated cable
tray systems
( Note 3 )
cleats, etc horizontal formation
( Note 3 )
cable tray systems vertcal formation
Cable ladder systems Three cables in
( Note 3 )
Vertically perforated Three cables in
Perforated cable Three cables in
tray systems horizontal formation
Reduction factors for groups of one or more circuits of single-core cables
Method of installation
Use as a multiplier to
Current carrying capacity for
( note 4 )
Touching
Touching
Touching
Spaced
Section 4- General Information
PERMISSIBLE PULLING TENSION
Pulling equipment Permissible pulling tension (kg)
PULLING EYE 7 x (Number of core) x (Cross section area of conductor)
CABLE NET About 500 kg, but the maximum tension shall not be more than one of
conductor (same calculation as using PULLING EYE)
Reference data on Aluminium conductor
Pulling equipment Permissible pulling tension (kg)
PULLING EYE 4 x (Number of core) x (Cross section area of conductor)
CABLE NET About 500 kg, but the maximum tension shall not be more than one of
conductor (same calculation as using PULLING EYE)
Note) Cable net shall be covered more than 500 mm in length
MINIMUMBENDING RADIUS
Reference data on other types of POWER cables D : Diameter of cable
Reference data on other types of INSTRUMENT cables
Note) Sheild tape shall be
AL mylar tape
PERMISSIBLE SIDE WALL PRESSURE
300kg/mis suggested as permissible side wall pressure to the cable during installation.
Side wall pressure (T1) can be calculated with below formula.
T1 = Pulling tension (T) / Bending radius (r)
CALCULATIONOF CABLE PULLING TENSIONDURING INSTALLATION
The cable pulling tension (T2) during installation can be calculated with below formula.
1) Horizontal straight part : W : Weight of cable (kg/m)
2) Horizontal curve part : L : Length of cable with straight part (m)
: Angle of curve part (rad)
: Friction factor T2 : Pulling tension (kg)
on pulley T3 : Pulling tension before curve part (kg)
underground T4 : Pulling tension after curve part (kg)
in pipe
0.2 - 0.3
0.5 - 0.7
Page - 90
Sheild cable (XLPE/PVC-S etc) 6D
Friction factor
0.2
Type of cable
Minimum bending radius
Multi core cable
Non shield cable ( XLPE/PVC etc ) 6D
Flat tape armored (XLPE/FSWA/PVC etc) 10D 12D 10D
Tape armored cable (XLPE/DSTA/PVC etc) 10D 12D 10D
Wire armored cable ( XLPE/SWA/PVC etc) 10D 12D 10D
Triplex type cable ( CVT etc ) - - 8D
Non Sheild cable ( XLPE/PVC etc ) 8D 12D 6D
Sheild cable ( XLPE/PVC-S etc ) 10D 12D 8D
Type of cable
Minimum bending radius
Single core cable
Multi core cable Round/Compacted
Sector conductor
conductor
T kg
r
L W T * *
2


e T T *
4 3

Section 4 - Contents &Information
Fire Performance Tests
1. Flame Propagation Tests
IEC 60332-1
Part 1 - Test on a single vertical insulated wire or cable
This is a relatively simple method for providing adequate indication of the flame-retardant characteristics of a single cable.
A 600 mm long cable sample is verticatlly suspended, placed in the middle of a three-sided metal screen.
This is subjected to the regulated flame of one (up to a cable diameter of 50 mm) or two (above 50 mm diameter) gas burners at an
angle of 45 to the cable. The flame is applied for a continuous time calculated according to an increasing with the cable weight
(from around 1-minute for a small control cable to about 7 minutes for a 4 core 300 mm power cable). The test is passed if the cable
has self-extinguished and the charred or flame affected portion of the cable has not reached the top of the sample.
IEC 60332-3
Part 3 - Test on bunched wire or cables
This test was developed to obtain a method to determine the flame propagation characteristics of bunched cables.
It can not be assumed that because a single vertical cable complies with the requirements of IEC 60332 part 1 it will also behave in
a similar manner when bunched with others cables.
The propagation of a flame along a bunch of cables depends on a number of features, such as :
The volume of combustible material exposed to the fire
The geometrical configuration of the cables
The temperature at which it is possible to ignite any gases emitted from the cables
The quantity of combustible gas released from the cables
The volume of air passing through the cable installation
The test consists of a vertical chamber, 1 x 2 x 4 m. Openings air inlet and outlet are provided in the base and the top of the test
chamber for a controlled air flow rate during the test. The cable samples to be tested are 3.5 m long and fixed to a steel ladder mounted
150 mm from the rear wall vertically with the test chamber. The number of lengths of cables in the test depends on the test categoty
based on the volume of combustible material.
Test Category Volume of combustible material Time of flame application
A 7 litres / m 40 Minutes
B 3.5 litres / m 40 Minutes
C 1.5 litres / m 20 Minutes
A ribbon gas burner of a set size and heat flow rate, operating at 800C is mounted horizontally in front of the cable samples at a set
distance and height. The test is passed if the charred or affected portion of the samples have not reached a height exceeding 2.5 m
above the bottom edge of the burner.
2. Fire Resistant Tests
IEC 60331 - 21 ( 1999-04 )
Fire resisting characteristics of electric cables Circuit Integrity Test
This test determines the circuit integrity of a cable during and after a prolonged fire :
A horizontally suspended sample 1200 mm long is placed 75 mm above a 610 mm long ribbon type gas burner, the flame temperature
of which is regulated to 750C. The conductors of the sample are connected to an AC voltage source, at the operating voltage, via fuses.
The flame and test voltage shall be applied continuously for a period of 90 min. 12 hours after the flame has been extinguished the cable
is energised again.
The test is passed if no failure of any of the fuses occurs.
Page - 91
1