Anda di halaman 1dari 1

Technical Information Sheet SF3200

Novaris Pty Ltd ABN: 33 065 427 232


72 Browns Road, Kingston, TAS. 7050 TEL: +61 3 6229 7233
AUSTRALIA FAX: +61 3 6229 9245
Copyright 2000 Novaris E-mail: sales@novaris.com.au

SURGE FILTERS, HIGH CURRENT, THREE


Product Description

Novaris surge filters are designed for protection against
induced transient overvoltages caused by lightning and other
events on AC and DC power supply circuits.

Versions are available for voltage ratings up to 240V AC with
surge ratings to suit location categories A, B and C including
category C high exposure in accordance with AS1768 also
IEEE C62.41.

Operation

Multistage transient protection is utilized in every unit. Metal
oxide varistor surge arrester modules, as the first stage, absorb
the majority of the energy. These components are
continuously monitored for integrity with built in LED
indicators. For 40kA versions DINsafe surge diverters are
used. For versions up to 200kA, MULTIMOV surge diverters
with digital display of integrity are used. These surge arrester
modules are housed in rugged and safe metal cased and are
easily replaced should this be required.

The first stage is followed by a low pass LC filter which
further attenuates the let through voltage. The filter also
attenuates low level noise and harmonics.

The third stage consists of metal oxide varistor based surge
arrester modules. DINsafe surge diverters are used for all
models. These provide a final clamping circuit and protect
against impulses generated by the loads connected. This is
particularly important when multiple loads are connected.

In addition to the alarm indicators on each module a front
panel mounted mimic panel provides an instant indication of
the filter integrity. The mimic panel circuitry contains a lamp
test button and an external alarm is generated which allows for
remote monitoring. This is provided by a clean contact
either normally closed or normally open.
An optional surge counter is available. This provides a count
of surges diverted and has a sensitivity of 100A for an 8/20us
impulse.

Every filter is configured to suit all TN and TT power
distribution systems including TN-C-S (MEN).

Specifications

Description Multistage power surge filter
No phases: 3
Voltage drop: <2V at full load
Efficiency: 99%
Protection modes: Transverse and common mode
Protection stages: MOV / low pass filter / MOV
Filter configuration: LC, transverse and common modes
Capacitor type: Self healing polypropylene
Surge withstand: IEEE C62.41 cat. A, B, C
AS1768-1991 cat. A, B, C & C-High
Surge rating: 40kA to 200kA per line
(8/20us impulse)
Frequency response: 3dB point 800Hz
Performance: Typical let through voltage for all models
< 2 x mains peak voltage
Indicator: Internal LED / digital display
Front panel mimic panel
External alarm: N/O or N/C clean contact
Dimensions:
Backplane Mounting:
200A & 315A 955H x 740W x 200D
450A 955H x 740W x 200D
630A & 800A 955H x 740W x 200D
1200A & 1600A 1355H x 940W x 200D
Metal Enclosure Mounting:
200A & 315A 1000H x 800W x 300D
450A 1000H x 800W x 300D
630A & 800A 1000H x 800W x 300D
1200A & 1600A 1400H x 1000W x 300D

Steel cabinet IP65 available for all models

Note: Other current ratings and alternative surge ratings
are available. Backplane versions for direct switchboard
mounting are available for all models. On all models
input/output configuration and terminal details are
constructed to customer requirements.

Options
Cat No. Current Rating
SF3200-xxx 200A per phase xxxkA per phase
SF3315-xxx 315A per phase xxxkA per phase
SF3450-xxx 450A per phase xxxkA per phase
SF3630-xxx 630A per phase xxxkA per phase
SF3800-xxx 800A per phase xxxkA per phase
SF31200-xxx 1200A per phase xxxkA per phase
SF31600-xxx 1600A per phase xxxkA per phase
Surge rating:
xxx may be 40kA, 80kA, 120kA, 160kA, 200kA
For information on surge rating application refer to the Novaris
Handbook.
For steel enclosure add /E
For surge counter ass /C