Power Line Carrier Equipment: Series ETL600
Upgrade Options for P4LT and P4LU



Contents

1 Purpose of document 2
2 Safety instructions 2
3 Upgrade P4LU with R1LA 2



List of equipment:
PC with Windows 2000 or XP

HMI600 software
PC P4LT/P4LU cable 1:1 serial RS-232
Torx screwdriver Size: 8

Note:
Please refer 1KHW001490 for compatibility between software HMI600, firmware and hardware of ETL600.

Revision: Language: Page:
_ EN 2/5
1KHW001757-EN

1 Purpose of document
This document describes mounting of upgrade options for P4LT and P4LU.

2 Safety instructions
ESD protection

Caution
The modules in this equipment contain devices, which can be damaged
by electrostatic discharges. Appropriate measures must be taken before
unpacking modules or withdrawing them from equipment racks. Essential
precautions to prevent ESD damage when handling or working on
modules are grounding straps for technical personnel and the provision of
anti-static workbenches. Modules may only be shipped either in their
original packing or installed in equipment racks.
ESD

3 Upgrade P4LU with R1LA
For new projects and systems the module P4LU with R1LA has to be
ordered if LAN600 functions are required, i.e. R1LA is already assembled
on P4LU ex works.
In the exceptional case when a P4LU shall be upgraded with R1LA (using
the optional R1LA upgrade kit), the following - rather unusual - procedure
may be applied to avoid completely disassembling of the module P4LU.
Note:

The module R1LA is only compatible with P4LUa, not with P4LU and
P4LT/P4LTa.
Note:


1. Switch off power to ETL600.
2. Unplug the P4LU board from ETL600 channel rack P7LC.
3. Remove the two torx screws ( Fig. 1).
4. Insert a 25 mm spacer between corner of P1LX and P4LT ( Fig. 2).
Fig. 3 5. Remove torx screw and washers from spacer at connector side of R1LA ( ) and
put them aside.
6. Insert R1LA board ( Fig. 4) and place it such that the connector pins marked in Fig. 3
are inserted into the corresponding sockets on P1LX.
7. Fix R1LA to P1LX with washer, spring washer and torx screw from step 5 ( Fig. 5, Fig.
6).
8. Remove the spacer inserted in step 4.
9. Remount the two torx screws removed in step 3 ( Fig. 7).
10. Plug P4LU back into ETL600 channel rack P7LC.
11. Switch on power to ETL600.




Revision: Language: Page:
_ EN 3/5
1KHW001757-EN



Fig. 1 Remove the two indicated torx screws


Max
25mm!


Fig. 2 Insert a spacer with a maximum height of 25mm.




Fig. 3 Bottom side of R1LA
Torx screw
and washers
to be
removed
Connector pins to
be inserted into
corresponding
sockets on P1LX

Revision: Language: Page:
_ EN 4/5
1KHW001757-EN





Fig. 4 Inserting R1LA between P1LX and P4LT




Fig. 5 Tightening screw to fix R1LA in place



Revision: Language: Page:
_ EN 5/5
1KHW001757-EN



Fig. 6 R1LA installed and fixed in place with screw




Fig. 7 Remount the two torx screws