03A Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
01.08.09 PB SMK






Operating Manual
For
ASHI DA Numerical Self-Powered
Protection Relay
Type: - ADR241S

Model: AM-104-04-X-X-XX-X


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 2 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09


User Notice

Ashida Electronics (P) Ltd. Reserve all right to make
improvements in the products described in this manual at any time
and without notice. All rights are reserved. No part of this manual may
be reproduce, copied, translated or transmitted in any form or by any
means without the prior written permission of Ashida Electronics (p.)
Ltd. Information in this manual is intended to be accurate and reliable.
However Ashida assumes no responsibility for its use; nor for any
infringements of rights of third parties that may result from its use.

























ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 3 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

INDEX
No. Topic Page No
1.0 Features 5
2.0 General 5
3.0 Protection Function 6
3.1 Over Current / Earth Fault Protection 6
4.0 Measurement & Communication Function 7
5.0 Impulse Output for Tripping Coil 7
6.0 Supervision Function 8
7.0 Electrical Noise Immunity 8
8.0 Setting Reliability 8
9.0 On Line Testing 8
9.1 On Line Testing using Test Block 9
10.0 Front Panel And Control 10
10.1 Ordering Information 12
11.0 Battery Function 13
12.0 Getting Started 14
13.0 To View Measurement Window 16
14.0 To Adjust Non Bank Setting 17
14.1 Password settings 17
14.2 New Password 18
14.3 Unit ID 18
14.4 Trip Test 18
14.5 Frequency Selection 18
14.6 External Relay 18
14.7 Trip Block 19
14.8 Save Settings 19
15.0 To View Non Bank Settings 19
16.0 To Adjust Bank Settings. 20
16.1 Password Settings 20
16.2 Bank Selection 21
16.3 Ip> (OC) 21
16.4 Ip TMS (OC) 22
16.5 Ip>> (OC) 22
16.6 IE> (EF) 22
16.7 IE TMS (EF) 23
16.8 IE>> (EF) 23
16.9 Ip> Curve Selection 23



ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 4 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

16.10 IE> Curve Selection 24
16.11 Ip> C6 Time Selection (Definite Time) 24
16.12 IE> C6 Time Selection (Definite Time) 24
16.13 Ip>> Delay 24
16.14 IE>> Delay 25
16.15 Save Settings 25
17.0 To View Bank Settings 25
18.0 To View Fault 26
19.0 To View Error Log 27
20.0 To View Status 28
21.0 To Adjust Date Time Settings 29
21.1 Password setting 29
21.2 Set Hours 29
21.3 Set Minutes 29
21.4 Set Seconds 30
21.5 Set Date 30
21.6 Set Month 30
21.7 Set Year 30
21.8 Save Settings 31
22.0 To View Date / Time Settings 31
23.0 To clear password and fault memory 31
24.0 Sample Test Report 33
25.0 Technical Specification 35
25.1 Conformance to Standard 36
26.0 Flow Chart 38
26.1 Flow Chart for Setting 38
26.2 Flow Chart to View Settings 39
27.0 Typical External Connection 40
28.0 Curve 1 41
29.0 Curve 2 42
30.0 Curve 3 43
31.0 Curve 4 44
32.0 Curve 5 45
33.0 Mechanical Details 46
34.0 Revision Notes 47


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 5 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

1.0 Features: -
Auxiliary Voltage supply is not required. (Relay can also be
operated on Aux. voltage supply, if required).
Low energy pulse output tripping for RMU, Shunt Trip & Series Trip
type Switchgear.
User friendly setting procedure with wide setting range.
4 Element (3 Phase + 1 Earth Fault) Over current IDMT/ Definite
time and Instant Trip.
RS232 and RS485 Communication Port for remote SCADA.
On line Test Terminal Block arrangement (By using D15 Type
Connector at the Back side of the Relay).
Programmable (Non Volatile) setting by local keyboard as well as
remote setting by communication port.
LCD Display for settings / parameters.
Display of Fault current as well as Load current.
Latching of last 5 fault with relay time.
Selectable Inverse Time Characteristics (Five selectable curves) :
Normal Inverse1 (C1), Normal Inverse2 (C2), Very Inverse (C3),
Extremely Inverse (C4), Long Time Inverse (C5), Define time (C6).
Separate curve setting for phase and EF.
Internal Battery for maintaining LCD display and communication
during fault condition.
Designed using DSP technology.
Latching of Fault Current and storing in a non-volatile memory
with time stamping.
External status input for Remote Trip & Three Status S1, S2 & S3 for
SCADA purpose.
External latching type potential free contacts.
Back-lit LCD display.

2.0 General: -
The ADR241S is member of ADITYA series designed to meet demand
of Ring Main Unit (RMU), Shunt Trip & Series Trip type Switchgear
where Auxiliary supply as well as PT voltage is not available. The relay
takes power from CTs and continuously monitors all 3 phases and
earth current, through CT connections. The high-speed micro-controller


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 6 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

samples this current through a 12 bit A/D converter. The micro
controller performs powerful Digital Algorithms to find out Amplitude
of fundamental current signal, and then these values are used for
protection and metering function. All the measurements are tuned to
fundamental frequency. Input current is displayed on 16 x 2 LCD
display for metering.
A battery for feeding the LCD display and SCADA communication
buffers the relay. After tripping operation relay maintains fault
indication on LCD display. During this time, the relay uses power
through internal battery. The relay can maintain fault indication till the
relay is manually reset by using + / key. Failure of the battery has no
effect on the protection function of the relay. The battery has a service
life of more than 5 years.

3.0 Protection Function: -
3.1 Over Current / Earth Fault Protection: -
The relay has inverse time over current / earth fault function as well as
instantaneous protection for both. Following is summary of different
protection functions provided by relay.

ANSI IEC Protection Function
50 I >> Instantaneous Over Current Protection.
50N IE >> Instantaneous Earth Fault Protection.
51 I>T, Ip Time Over Current Protection (Phase).
51N IE >t, IEP Time Over Current Protection (Earth).

The relay has 4 sensing elements 3 O/C and 1 E/F. The tripping current
can be set to 20% -240% in steps of 1% for phase and 10% - 100% in steps
of 1% for earth fault by keyboard provided on front panel. These
settings are available on display. The unit has selection of IDMT
characteristic of IEC standard, Normally Inverse1 (C1), Normally
Inverse2 (C2), Very Inverse (C3), Extremely Inverse (C4), Long Time
Inverse (C5) and define time (C6).



ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 7 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

The unit also has Time Multiplier Setting (TMS) from x0.1 to x1.2 in
steps of x0.05 (separate for phase and EF) for IDMT delay
multiplication. Separate operating curve can be programmed for phase
and EF. The instantaneous tripping function has range of 50% - 3200%
in steps of 50% for phase and 50% - 1200% in steps of 50% for earth
fault. The high speed CPU continuously monitors all four current inputs
and compares with IDMT as well as instantaneous setting. If any one
current is above instantaneous setting, the relay provides immediate
trip command bypassing IDMT delay.
If input current is less than instantaneous setting but more than IDMT
setting, CPU calculates IDMT delay as per selected IDMT characteristic,
multiplies it with TMS setting and issue trip command if fault is persist
even after this time delay.
For EF tripping there must be current greater than or equal to 20% of
the rated current in any one phase of the relay.

4.0 Measurements and Communication Function: -
In normal condition the relay displays all the current values. Using the
front keyboard the display can be programmed to show settings. If
current is in fault range the relay gives trip command. The type of the
fault is displayed on LCD display. During the fault condition, the relay
measures the fault current and stores it in non-volatile memory. The
fault current can be read using keyboard on LCD display. All settings
can be done locally as well as remotely via communication port and
saved in non-volatile memory.

5.0 Impulse Output for Tripping Coil: -
Low Energy tripping coil of the circuit breaker can be connected to the
coil terminal marked as (COIL + and ) at back terminal. The trip
energy (12 - 24 V DC 0.1 W/sec) is provided by a capacitor in the
protection relay. Length of the trip impulse is 40ms and pause between
the individual pulses depends on the impedance of the tripping coil and
the current level. Pulsing is continued until the CB operate and fault
current become zero.


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 8 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

6.0 Supervisory Function: -
The relay continuously keeps track on its internal hardware and the
moment it detects any failure of component, a message is displayed on
LCD display. The type of error can be checked by Error Log menu.
This feature is very useful for giving pre information to avoid mal
operation.

7.0 Electrical Noise Immunity: -
Utility and industrial environments are electrically very noisy.
Electronics protection equipment requires careful design and testing to
ensure reliable operation in switchgear. Ashida has applied its expertise
and more than 35 years of experience in field of electronics design to
ensure that the ADR241S operates when required, without nuisance
trips. Thanks to the latest micro-controller technology.

8.0 Setting Reliability: -
Any numerical or digital relay in which all settings are programmable
via key board or communication port, use some internal memory to
store these settings. Many relays use internal rechargeable batteries to
maintain these settings. In case of power supply fluctuation, batteries
are often unreliable, and settings get corrupted. In such situation, the
relay may mal- operate. Ashida use special non-volatile memory
technology, which do not require any power source to maintain settings
of the relay.
Once the relay is programmed, it maintains the settings for more than
10 years even in the absence of any power supply. In case if internal
fault is detected in this section during the self diagnosis, then relay
gives message.

9.0 On Line Testing: -
The ADR241S relays are provided with online testing facility. By
pressing TEST key (provided on front panel) the relay immediately
provides trip command. This trip command also gets extended to
breaker coil, thus entire trip operation from relay to circuit breaker can


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 9 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

be checked. This trip command is recorded as T flag on LCD display
as shown below.

I>> : t : 0002
I> : SF : T
If the CB (circuit breaker) operation is un-desirable then, pressing
BYPASS key, the relay trip command can be blocked from extending to
CB coil.
(Note: - This " Trip Test" function can be enabled through Non-bank
settings.)

9.1 On Line Testing by using Test Block.
The Relay is supplied with optional online Testing assignment i.e. Relay
is provided with D15 type connector at the backside of relay for
connection of Relay Testing Unit (TEST BLOCK). By connecting the Test
Block via 15-pin cable all the functions of the relay can be checked in
service. While testing, the Trip contact can be isolated by trip bypass
switch on Test Block to avoid any type of tripping operation. The
current injector and the Timer can be connected to relay and entire
verification of the relay can be done.


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 10 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

10.0 Front Panel and Control: -

1
2
3
4
9
10
6
8
7
5
14
12
11
13
1
2
3
4
9
10
6
8
7
5
14
12
11
13
1
2
3
4
9
10
6
8
7
5
14
12
11
13
1
2
3
4
9
10
6
8
7
5
14
12
11
13




No Legend Function
1. ON LED Power ON indicator. (Required 20%
of load Current).
2. PKP LED Relay PICKUP Indicator.
3. FAULT LED - FAULT Flag Indicator (HR) Type.
Output element status indicator of
Annunciation or Tele signaling


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 11 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

4. TRIP LED Relay TRIP indicator (SR) Type. Output
element status indicator of Trip coil or Spare
coil.
5.
/ /
The light symbol is for Back-lit ON indication
/ [ ] is for 'MODE'. i.e. To select setting
parameter in Main Menu and to SAVE settings.
6. RESET
+ /
Feather Touch Key RESET is for reseting the
Flag and to RESET the Annunciation / Tele
signalling element. [ + ] to INCREMENT the
values & [ ] to SCROLL the Main Menu.
7. - / Feather Touch Key [ - ] is to 'DECREMENT' the
values & [] to View current Settings (in case
of Bank & Non-Bank Setting window)or
recorded data (in case of faults, date &
measurement window.)
8. BAT. ON Feather Touch Key to switch ON the Battery.
9. TEST Feather Touch Key for online TESTING.
10. BYPASS Feather Touch Key for BYPASSING TRIP
command.
11. HW RESET Feather Touch Key for HARDWARE RESET of
the relay.
12. LCD
Display
To observe setting and parameters of the relay .
13. Battery Capacity 4.5Volt (1.5V x 3) AAA Alkaline non-
rechargeable battery.
14. RS 232
Connector
D type - 9 pin male Connector RS 232
Communication Port.

Feather Touch Keys
The function of relay is controlled by the Feather Touch Keys TEST,
BYPASS, HW RESET, , RESET + / , - / , and BAT. ON which are
provided on the front Plate.
(Note: - At the time of setting if changes are not carried within 100s then
the display will reset itself and return to the main menu and the settings
get lost.)




ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 12 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

10.1 Ordering Information:
The relay is available with nos. of different option. The option is
specified by model no. It is user responsibility to specify correct model
no. while ordering.
Whi l e Or de r i ng Spe c i f y t he f o l l o wi ng I nf o r ma t i o n f or ADR2 4 1 S Re l a y























Or d er i n g i n f o r mat i o n :
A D R 2 4 1 S - A M - X X X - X X - X - X - X X - X
Ex a mpl e
ADR2 4 1 S AM- 1 0 4 - 0 4 - 1 - 0 - 0 2 - 0

ADR2 4 1 S : Ty pe
AM : As hi da Mo de l Numb e r
1 0 4 : Ca bi ne t S i z e & Ty pe o f F unc t i o ns a nd O/C & E/F Tr i p s e t t i ng s .
0 4 : Ba c k Te r mi na l La yo ut ( S ui t a bl e f o r Te s t Bl o c k ) & Ty pe o f Tr i ppi ng
1 : Ty pe o f CT
0 : Ty pe o f PT
0 2 : Aux i l i a r y S uppl y
0 : Fo r F ut ur e us e

XX = Back Terminal Layout & Type of Tripping
01
Without Test Block, Series Trip or RMU
02
With Test Block, Shunt Trip
03
With Test Block, Series Trip
04
With Test Block, RMU
D e f i n i t i o n o f M o d e l N o o f A d i t y a S e r i e s o f R e l a y s
A M X X X X X X X X X X
Reserved For Future Use
X = PT Secondary
0 = No PT
XX = Auxiliary Supply
01 = 18 52 V dc / ac
X = CT Secondary
1 = 1 Amp.
2 = 5 Amp.
X = Cabinet Size
0
CSC - 120
1
CSG - 122
2
CSE - 130

XX = Specify type of Functions& O/C, E/F Trip Setting
01
RMU, Trip Setting O/C 20-200% & EF 10-80%
02
Shunt Trip, Trip Setting O/C 50-200% & EF 5-80%
03
Series Trip, Trip Setting O/C 50-200% & EF 5-80%
04
RMU, Trip Setting O/C 20-240% & EF 10-100%


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 13 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

11.0 Battery Function: -
Battery Specification: Capacity 4.5Volt (1.5 x 3) AAA Alkaline non-
rechargeable battery, Make Energizer, Panasonic or equivalent.
The ADR241S relay is Self Power relay, it takes power from CT Current for its
operation, after the tripping operation and when no current is available to
view the Fault Current in the different Phases of the relay, Relay takes power
from Battery. When there is no CT Current press BAT ON Key to view Fault
current. When BAT ON Key is pressed relay will remain ON for 1 Minute
and after 1 Minute relay becomes OFF to save the battery life, but if before
completion of 1 Minute any of the key (Excluding the HW Reset and the
Bypass key) is being pressed it will retriggered for 1 Minute time slab again.
When the CT current is at 20% the relay gets activated. Battery is located in the
battery box on the Front Plate and can be easily replaced by opening the cover.
Conditions of the relay getting switch over momentarily on battery are as follows.
1. If the relay is in ON Condition and current drops below 10%.
2. When the current exceeds to settings i.e. pkp condition but not tripped
and drops below 10%.
Condition of relay getting switch over on battery for 1 Minute is as follows.
1. When relay gets tripped and current becomes Zero.
Note: -
1. The relay uses battery only for indication purpose. Battery is not required
for protection purpose.
2. AAA Alkaline (1.5V x 3) non-rechargeable batteries are placed in Battery
Socket as shown below.









ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 14 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

12.0 Getting started: -
After Power ON or after pressing Bat. ON key the relay display
following message.
Ashi da Di gi t al
OC/ EF Rel ay

ADR 241S SD V1. 05
Uni t ID =0001
What is displayed is as follows: -
Relay Name Ashida Digital OC/EF Relay.
Relay Type ADR 241S RMU, Software Version SD V1.05
If Trip Block setting is set YES through Non Bank setting after
displaying software version, window will display as follows
Tri p Bl ock = YES
Uni t ID = 0001
If Trip Block setting is set NO through Non Bank setting after hardware
resetting window will display as follows
Ashi da Di gi t al
OC/ EF Rel ay

ADR 241S SD V1. 05
Uni t ID =0001

R =00. 00 Y = 00. 00
B =00. 00 N = 00. 00

Relay Display Online Current of (4) Four Phases R, Y, B & N.
The relay is capable of protection as well as metering function. After
Power ON the relay will start showing actual current flowing through
its coil.


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 15 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

In ASHIDA we believe in continuous improvement of our products. So
also implementing the valuable suggestions and feedback from actual
user. Whenever we do any relay firmware modification it is recorded as
version change. The relay has the facility to upgrade firmware at site.

(Note: - To view display in the dark or in low light conditions relay is
filled with back-lit. The back-lit will become ON whenever MODE
KEY () is pressed. Back-lit will remain ON of 30s).
Now, when the - /Key is pressed the first setting parameter in the
Main Menu will be displayed as shown below,
Measurement

Now, each time the + / Key is pressed the setting parameters in the
Main Menu will be displayed one by one respectively in the following
order.
Non Bank
Set t i ngs

Bank Set t i ngs


Faul t 1


Faul t 2


Faul t 3


Faul t 4




ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 16 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

Faul t 5


Error Log


St at us


Dat e / Ti me


Measurement


Measurement, Non Bank Settings, Bank Settings, Fault 1, Fault 2, Fault
3, Fault 4 and Fault 5, Error Log, Status & Date Time are the different
parameters available in the Main Menu.

13.0 To View the Measurement Window: -
By using the + / Key select to display Measurement in the Main
Menu.
Measurement

Now when the - / Key is pressed then following window is
displayed.
R =00. 00 Y = 00. 00
B =00. 00 N = 00. 00
What are displayed are the Current values of R, Y, B & N Phase at that
instant.
(Note: The relay displays secondary current values without considering
the CT ratio.)
Then, the - / Key is pressed again, the relay will return to Main Menu
to show,


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 17 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

Measurement

Now, by using the + / Key, select Non Bank Settings window in the
Main Menu.
14.0 Adjusting the Non Bank Settings: -

Non Bank
Set t i ngs

Now, when the Key is pressed the following message is displayed.
14.1 Password Settings: -
Password = 001
Use Inr / Dec
The + / Key is used to increment and the - / Key is used to
decrement the values. By using these Keys set the Password to match
the previously set password, by default this password is '0'. Hence to
go ahead user must select 0 Password initially using - / Key.
If 0 password is not selected and Key is pressed again, the user
cannot access the other settings parameters and the following error
message will be shown on the display
Password Fai l

The relay returns to the selected parameter in the main menu i.e. Non
bank setting window.
Non- Bank
Set t i ng
Now when the Key is pressed the following message is displayed
again.
Password = 001
Use INR / DEC
Now select default password i.e. 0 by pressing - / Key. Then press
Key and the following window is displayed


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 18 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

14.2 New Password: -
Password = 000
New Password
By using the + / Key or the - / Key New Password can be set, now when
the Key is pressed again the following window will be displayed.

14.3 Unit ID: -
Uni t ID = 001

By using the + / Key or the - / Key the desired Unit address can be
selected. The unit addresses will vary from 001 to 255, out of which 254
devices can be connected to single computer and the id 255 is reserved
for special command. These settings are required to communicate with
the SCADA System. Then when the Key is pressed again the
following window will be displayed.

14.4 Trip Test: -
Tri p Test = 002
01 = Yes 02 = No
By using the + / Key or the - / Key the desired Trip Test can be set,
that is 01 or 02. In which case 1 corresponds to Yes i.e. Trip Test is
enabled and 2 corresponds to No i.e. Trip Test is blocked Now,
when the Key is pressed again the following message will be
displayed.

14.5 Frequency Selection: -
Frequency = 001
50Hz = 1 , 60Hz = 2
By using the + / Key or the - / Key the desired frequency can be
changed that is 1 or 2. In which case 1 corresponds to 50Hz and 2
corresponds to 60Hz, and now when the Key is pressed again the
following message will be displayed.
14.6 External Relay: -
Ext . Rel ay = 001
ON = 1 OFF = 2



ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 19 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

By using the + / Key or the - / Key the External Relay can be set
that is 1 or 2. By selecting 1 relay is enable (ON), and selecting 2
relay is disable (OFF), when the Key is pressed again the following
message will be displayed.

14.7 Trip Block: -
Tri p Bl ock = 002
01 : YES 02 : NO
By using the + / Key or the - / Key the Trip Block can be set that is
1 or 2. By selecting 1 relay tripping will be blocked, and by selecting
2 relay tripping will not be blocked (i.e. Relay will trip), when the
Key is pressed again the following message will be displayed.

14.8 Save Settings: -
Save Set t i ngs?
Mode For Save
The relay will now ask if you would like to save the changes made to
the various setting parameters by you.
(Note: In this relay all the settings are done in foreground and the relay
works in background i.e. the relay will take the new settings only after
completion of all settings and the confirmation by the user, then the
relay will use these settings for actual operation.) When the Key is
pressed again then the relay will Save the new settings made and
returns to the Non Bank setting's window as shown below.
Non Bank
Set t i ngs

15.0 To View Non Bank Settings: -
By using the + / Key select to display Non Bank Settings in the Main
Menu.
Non Bank
Set t i ngs
Now when the - /Key is pressed then following data is displayed.
Uni t Id = 0001
Tri p Test = No


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 20 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

Then, when the - / Key is pressed again, the following data is
displayed.
Frequency = 0050Hz
Ext . Rel ay En = OFF
Then, when the - / Key is pressed again, the following data is
displayed.
Tri p Bl ock = YES

Now, when the - / Key is pressed again, the relay with no other
settings to be displayed will return to Main Menu to show
Non Bank
Set t i ngs
Now, by using the + / Key select to display Bank Settings in the Main
Menu.

16.0 To Adjust Bank Settings: -
Bank Set t i ngs

Now, when the Key is pressed the following message is displayed.
16.1 Password Setting: -
Password = 001
Use Inr/ Dec
By using the + / Key or the - / Key set the Password to match the
previously set password, by default this password is '0'. Hence to go
ahead user must decrement this pass using - / Key. Now When the
Key is pressed again and if the set password is not matching to the
previously set password, the following message will be displayed.
Password Fai l

Now, it returns to the Main Menu parameter and displays the 'Bank
Setting' window as follows,
Bank Set t i ngs



ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 21 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

Now, when the Key is pressed again, the following message will be
displayed.
Password = 001
Use Inr/ Dec
By using the + / Key or the - / Key set the Password to match the
previously set or default password and press Key. If the Password
matches the following window is shown.
16.2 Bank Selection: -
Bank = 001
Bank 1 To 4
By using the + / Key or the - / Key the desired Bank can be selected
to do necessary changes to the settings. The Bank range will vary from 1
to 4, only one Bank will be active at a time.
Then when Key is pressed following message will be displayed.
Bank Change
Mode For Save
Then when the Key is pressed again the following window will be
displayed.
Bank Set t i ngs

All changes carried out after selection of the particular bank will
pertain to that selected bank only, while all the other respective banks
setting will remain unchanged.
If in case without changing Bank the Key is pressed the following
message will be displayed.
16.3 Ip> (OC)Trip Setting (IEC notation I>): -
Ip> = 020
Range 20240%
By using the + / Key or the - / Key the desired Ip> OC can be set.
The setting range is from 20% (min) to 240% (max) in steps of 1%. If any
of the Keys is remained pressed for more than 1 sec. the selected value
will start incrementing or decrementing with high speed in steps of


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 22 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

10%. If +/ or -/ key is pressed then display value will roll between
min. & max. in forward or reverse direction respectively.
For example if required value to be set is 100% then press + / Key till
you get reading 95, then releases the + / Key and increment one by
one till 100%. Or vice versa if - /key is used.
This setting is common to all three phases. Then when the Key is
pressed again the following message will be displayed.
16.4 Ip TMS (OC) (Time Multiplier Setting): -
Ip TMS = x1. 00
Range x0. 1- x1. 20

By using the + / Key or the - / Key the desired Ip TMS OC can be
set. The range will be from x0.1 x1.20 and can be adjusted in steps of
x0.05. This setting is common to all three phases. Then when the
Key is pressed again the following window will be displayed.

16.5 Ip>> (OC) (High Fault IEC notation I >>): -
Ip>> = 01. 5
Mul t i pl y by 100
This is instantaneous setting for phase. The moment input current crosses
this value; relay gives instant trip command (provided HF operating delay
is set at instant i.e. Ip>> Del ay = 0.05) bypassing IDMT delay timing. By
using the + / Key or the - / Key the desired Ip >> OC can be set. The HF
value can be adjusted between 00.0 to 32.0 times of the CT secondary and
can be adjusted in steps of 0.5. To get setting in terms of % multiply it by
100. The 00.0 HF value corresponds to bypass, i.e. adjusting it to 00.0 will
bypass the instantaneous element.
Then when the Key is pressed again the following message will be
displayed.

16.6 IE> EF Trip setting (IEC notation IE>t): -
IE> = 010
Range 10100%
By using the + / Key or the - / Key the desired IE> Tri p can be set.
The EF trip value can be adjusted in between 10% (min) to 100% (max)
of the CT secondary and can be adjusted in steps of 1%. Then when the


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 23 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

Key is pressed again the following message will be displayed.

16.7 IE TMS (IE Time Multiplier Setting):-
IE TMS = x1. 15
Range x0. 1- x1. 20
By using the + / Key or the - / Key the desired IE TMS can be set.
The minimum value of TMS is x 0.1 and maximum value is x 1.20 and
can be adjusted in steps of x0.05.
Now, when the Key is pressed again the following message will be
displayed.

16.8 IE>> ( IE High Fault IEC notation IE >>): -
IE>> = 010
Mul t i pl y by 100
By using the + / Key or the - / Key the desired IE >> HF can be set.
The HF value can be adjusted in between 00.0 to 12.0 times of the CT
secondary and can be adjusted in steps of 0.5. To get setting in turns of
%, multiply it by 100. The 00.0 HF value is corresponding to bypass.
Setting the HF value to 00.0 will bypass the instantaneous element.
Then when the Key is pressed again the following window will be
displayed.
Ip> Curve = 001
Range C1 C6

16.9 Ip>Curve Selection: -
By using the + / Key or the - / Key the desired IDMT curve for
Phase can be selected. Six different types of curves are provided C1 to
C6. When the given value is 001 curve 1 is selected and when the given
value 002 curve 2 is selected. In similar manner any desired curve can
be selected giving value from 001 to 006 i.e. C1 to C6.
Curve Description
C1 Normal Inverse 1 (10N = 3.0 sec)
C2 Normal Inverse 2 (10N = 1.3 sec)
C3 Very Inverse (10N = 1.5 sec)
C4 Extremely Inverse (10N = 0.8 sec)
C5 Long Time Inverse (10N = 13.3 sec)
C6 Definite Time (00.1 To 99.9 sec)


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 24 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

Then when the Key is pressed again the following message will be
displayed.

16.10 IE> Curve Selection: -
IE> Curve = 002
Range C1 C6
By using the + / Key or the - / Key the desired IDMT curve for EF
can be selected.
Then when the Key is pressed again the following window will be
displayed.

16.11 Ip> C6 Time Selection ( Definite Time): -
Ip> C6 Ti me = 00. 1
Range 00. 1 - 99. 9 S
By using the + / Key or the - / Key the desired Definite Time Delay can
be selected. Range for definite time is from 00.1 to 99.9 sec in steps of 0.1
secs. This setting is effective only when C6 curve is selected for phase.
Selection of curve C6 will bypass IDMT TMS time delay for phase. Then
when the Key is pressed again the following window will be displayed.

16.12 IE> C6 Time Selection (Definite Time): -
IE> C6 Ti me = 00. 1
Range 00. 1 - 99. 9 S
By using the + / Key or the - / Key the desired Definite Time Delay
can be selected. Range for definite time is from 00.1 to 99.9 sec in steps
of 0.1 secs. This setting is effective only when C6 curve is selected for
EF. Selection of curve C6 will bypass IDMT TMS time delay for phase.
Now, when the Key is pressed again the following message will be
displayed.

16.13 Ip>> Delay: -
Ip>> Del ay = 0. 05
Range 0. 05- 1. 00 S
By using the + / Key or the - / Key the desired HF Operating Delay
for Phase can be selected. Range for Phase HF operating time is from
inst (0.05) to 1.00 sec in steps of 0.05 sec.


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 25 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

Then when the Key is pressed again the following window will be
displayed.

16.14 IE>> Delay: -
IE>> Del ay = 0. 05
Range 0. 05- 1. 00 S
By using the + / Key or the - / Key the desired " HF Operating
Delay" for EF can be selected. Range for Earth HF operating time is
from inst (0.05) to 1.00 sec in steps of 0.05 sec.
Then when the Key is pressed again the following message will be
displayed.

16.15 Save Settings: -
Save Set t i ngs?
Mode For Save
The relay will now ask if you would like to save the changes made to
the various setting parameters by you.
(Note: In this relay all the settings are done in foreground and the relay works
in background i.e. the relay will take the new settings only after completion of
all the settings and the confirmation by the user, then the relay will use these
setting for actual operation.)
When the Key is pressed again then the relay will save the new
settings made and the following message will be displayed and returns
to the Bank Setting window as shown below.

17.0 To View Bank Setting: -
Bank Set t i ngs

Now, when the - / Key is pressed then following data is displayed.
Ip> = Normal Inv. 1
IE> = Normal Inv. 2
When the - / Key is pressed again the following data is displayed.
Ip>200% t >1. 00
Ip>>0000% T : 0.05


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 26 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

When the - / Key is pressed again the following data is displayed.
IE>080% t >1. 00
IE>>0000% T: 0.05
Then when the - / Key is pressed again, the relay with no other
settings to be displayed will return to Main Menu to show
Bank Set t i ngs


18.0 To View FAULTS: -
By using the + / Key select to display Fault 1 in the Main Menu.
Faul t 1

Now when the - /Key is pressed then following data is displayed.
I>> : t : 0002
I> : SF : T
Explanation:-
I>> i ndi cat es Type of HF Fault (e.g. RE for phase to Earth
fault, RY for phase to phase fault).
t indicates Trip Counter
I> Indicates TYPE of IDMT fault (e.g. RE for phase to Earth fault,
RY for phase to phase fault).
SF indicates Status Flag. When there is non- fault trip such as trip
due to TEST push button or Remote trip etc. it is displayed at SF

Following are the status fault and there meanings:-
T : Trip due to TEST push button.
R : Trip due to Remote Trip.

(Note:- Fault 1 is always treated as most recent occurred fault and the
data stored in these fault windows keep on shifting sequentially i.e.
when any new fault occurs, the data related to the fault gets stored in
Fault 1 and earlier stored data in Fault 1 gets shifted to Fault 2 and so
on till Fault 5 and previously stored data in Fault 5 gets lost.)



ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 27 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

When the - /Key is pressed then following data is displayed.
FR = 00. 00 Y = 00. 00
B = 00. 00 N = 00. 00
Explanation:
The R Phase Current measured at the time of the fault.
The Y Phase Current measured at the time of the fault.
The B Phase Current measured at the time of the fault.
The N Phase (Earth) Current measured at the time of the fault.
When the - /Key is pressed again then the following data is displayed,
Tri p Ti mi ng
001. 70 Sec
Explanation:-
The Trip Timing is measured from relay pick up condition to relay
tripping.
When the - / Key is pressed then following data is displayed,
13/ 03/ 09
10: 15: 10. 123
Explanation:-
The Date / Time of the fault.
Then when the - / Key is pressed again, the relay with no other data to
be displayed will return to Main Menu to show,
Faul t 1

To Display of (FAULT 2), (FAULT 3), (FAULT 4), and (FAULT 5) follow
step as given above.

19.0 To View Error Log: -
By using the + / Key select to display Error Log window in the Main
Menu.
Error Log

Now, when the - / Key is pressed then following message is
displayed.


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 28 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

Error Code = 000
0000 0088
The relay continuously keeps track on its internal hardware and the
moment it detects any failure of component, a message is displayed on
LCD display. The type of error can be checked by Error Log menu.
This feature is very useful for giving pre information to avoid mal
operation.
Following are some of Error codes: -
Error Code Description
01 RAM Error
02 RTC Error
03 RAM + RTC Error
08 Setting Error
09 Setting + RAM Error
10 Setting + RTC Error
11 Setting + RAM + RTC Error
In case of ADC error relay will not work at all and will show directly
ADC Error and relay function will be locked.
(Note: - The second line of the above shown window gives 0000 0088
which is used while firmware upgradation hence its of no use for the
user.)
Then when the - / Key is pressed again, the relay with no other
settings to be displayed will return to Main Menu to show
Error Log


20.0 To View Status
By using the + / Key select to display Status window in the Main
Menu.
St at us

Now when the - /Key is pressed then following message is displayed.



ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 29 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

S1 = ON S2 =OFF
S3 = OFF
The three status S1, S2 an S3 can be enabled or disabled through
SCADA. For e.g. Status S1 is Enable if shown as S1 = ON and Status S2
is disable if shown as S2 = OFF.
Now when the - /Key is pressed then again the relay with no other
settings to be displayed will return to Main Menu to show.
St at us


21.0 To Adjust Date / Time: -
By using the + / Key select to display Date / Time window in the
Main Menu.
Dat e / Ti me

Now, when the Key is pressed the following message is displayed.

21.1 Password Setting: -
Password = 000
Use INR / DEC
By using the + / Key or the - / Key, set the Password to match the
previously set password. Then when the Key is pressed again the
following message will be displayed.

21.2 Set Hours: -
SET Hrs = 016
Range 0 - 23
By using the + / Key or the - / Key the desired Hour can be set.
The range will be form 0 hour to 23 hours.
Then when the Key is pressed again the following message will be
displayed.

21.3 Set Minutes: -
SET Mi ns = 010
Range 0 - 59


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 30 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

By using the + / Key or the - / Key the desired Minutes can be set.
The range will be from 0 minute to 59 minutes.
Then when the Key is pressed again the following message will be
displayed.

21.4 Set Seconds: -
SET Sec = 012
Range 0 59
By using the + / Key or the - / Key the desired Seconds can be set.
The range will be from 0 second to 59 seconds.
Then when the Key is pressed again, the following message will be
displayed.

21.5 Set Date: -
SET Dat e = 028
Range 1 31
By using the + / Key or the - / Key the desired Date can be set. The
range will be from 1 to 31.
Then when the Key is pressed again the following message will be
displayed.

21.6 Set Month: -
SET Mont h = 001
Range 1 12
By using the + / Key or the - / Key the desired Month can be set.
The range will be from 1 to 12.
Then when the Key is pressed again the following message will be
displayed.
21.7 Set Year: -
SET Year = 008
Range 00 99
By using the + / Key or the - / Key the desired Year can be set. The
range will be from 00 to 99.
Then when the Key is pressed again, the following message will be
displayed.


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 31 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

21.8 Save Settings: -
Save Set t i ngs?
Mode For Save
The relay will now ask if you would like to save the changes made at
various setting parameters by you, when the Key is pressed again
the relay will save the new settings made and the following message
will be displayed.
Dat e / Ti me


22.0 To View Date / Time: -
By using the + / Key select to display Date / Time window in the
Main Menu.
Dat e / Ti me

Now when the - /Key is pressed then following message is displayed.

Ti me : 17. 02. 55
Date : 13/03/09
Then when the - / Key is pressed again, the relay with no other
settings to be displayed will return to Main Menu to show,

Dat e / Ti me



23.0 To clear Password and Fault Memory : -
To clear password and fault memory, press Key & HW RESET
Key, and Bat ON key simultaneously & release HW RESET Key
only, keeping Key and Bat ON key pressed. Then the default
value for password i.e 000 gets loaded and data stored in all five (5)
Fault windows is cleared.
The following windows are displayed consecutively.





ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 32 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09


Password & Faul t
Memory Cl eared


Ashi da Di gi t al
OC/ EF Rel ay


ADR 241S SD V1. 05
Uni t ID =0001


R =00. 00 Y = 00. 00
B =00. 00 N = 00. 00

Now when the - / Key is pressed then following window is displayed.
Measurement

Press + / key to scroll the different setting parameters in the main
menu.
Note :
In case authorised person forgets the set password then by clearing password
as said above default password i.e. 000 is set. By entering 000 password new
password can be set through non-bank settings.












ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 33 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

24.0 Sample Test Report
C1: Reading By Curve 10N = 3 Sec. C2: Reading By Curve 10 = 1.3 Sec.
C3: Reading By Curve 10N = 1.5 Sec. C4: Reading By Curve 10N = 0.8 Sec.
C5: Reading By Curve 10N = 13.3 Sec.
CURVE : C1 CURVE : C2
Set
Current
Actual Max.
Time Sec.
Tolerance in
Sec.
Set
Current
Actual Max.
Time Sec.
Tolerance in
Sec.
2N 10.128 8.86 to 11.39 2N 4.389 3.84 to 4.93
5N 4.322 3.99 to 4.64 5N 1.873 1.73 to 2.01
10N 3.000 2.85 to 3.15 10N 1.300 1.23 to 1.36
20N 2.290 2.17 to 2.40 20N 0.992 0.94 to 1.04

CURVE : C3 CURVE : C4
Set
Current
Actual Max.
Time Sec.
Tolerance in
Sec.
Set
Current
Actual Max.
Time Sec.
Tolerance in
Sec.
2N 13.500 11.81 to 15.18 2N 26.667 23.33 to 30.00
5N 3.375 3.12 to 3.62 5N 3.333 3.08 to 3.58
10N 1.500 1.42 to 1.57 10N 0.808 0.76 to 0.84
20N 0.711 0.67 to 0.74 20N 0.201 0.19 to 0.21

CURVE : C5
Set
Current
Actual Max.
Time Sec.
Tolerance in
Sec.
2N 120.000 105 .00 to 135.00
5N 30.000 27.75 to 32.25
10N 13.333 12.66 to 13.99
20N 6.316 6.00 to 6.63

Note: TMS is considered: x1.0 for all above curve tables.

TIME ACCURACY CLASS 5 AS PER IS 3231
Current Multiplying Factor 2N 5N 10N 20N
Multiplying Factor 2.5 1.5 1 1
Percentage 12.5% 7.5% 5% 5%

1. Pickup Test for Phase & EF (Tolerance 1N 1.1N)
Keep Phase & EF TMS at x0.1
Set % R (Amp.) Y (Amp.) B (Amp.) Set % EF (Amp.)
20 10
240 100



ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 34 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

2. Testing for Phase & EF TMS (Tolerance 12.5%)
Phase EF
Trip setting = 100% , Current 2N Trip Setting = 100%, Current 2N
Curve = C1 Curve = C2
TMS Setting 0.50 1.00 1.20 0.50 1.00 1.20
Actual 5.064 10.128 12.153 2.194 4.389 5.266
Observed
Tolerance in Sec. 4.43 to
5.69
8.86 to
11.39
10.63 to
13.67
1.91 to 2.46 3.84 to
4.93
4.60 to
5.92

3. Operating Time Test for Phase & EF
Keep TMS Set at x1.0 position
Tolerance Set Curve EF Trip Phase Trip 50%
In Sec. Current 40% R Y B
8.86 to 11.39 2N 1
3.84 to 4.93 2N 2
3.12 to 3.62 5N 3
3.08 to 3.58 5N 4
12.66 to 13.99 10N 5
0.475 to 0.525
For set Time 0.5Sec
1.2N 6

4. HF Testing for Phase & EF (Tolerance 1N 1.1N)
Keep Trip setting maximum & TMS set Maximum
HF R (Amp.) Y (Amp.) B (Amp.) EF (Amp.)
200%
500%










ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 35 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

25.0 Technical Specification: -
Sr.
No.
Specification Particulars
I. Inputs : Suitable for CT secondary 1.0 Amp or 5.0
Amp. (To be specified) with selectable
frequency 5o Hz/ 60Hz.
: For Phase - 20 - 240 % in step of 1%.
: For EF - 10 - 100 % in step of 1%.
: Phase
Instantaneous:
- 50 - 3200% in steps of
50% and bypass.
II. Protection Relay
Setting Range
: EF
Instantaneous:
- 50 to 1200% in steps of
50%. And bypass.
III. Pickup Current : Within 1.1 times of set current value.
IV. Resetting Current : Within 90% of set value.
V. Operating Time : Time: 5 selectable IDMT curve C1, to C5. Or
define time C6
: Instantaneous Time <60ms on 2 times current
of setting. With supply ON.
VI. Time Accuracy : Within class 5 As per < IS: 3231.
VII. Burden on CTs : Less than 5.5 VA.
VIII. Impulse o/p for
tripping coil
: 12 V - 24 VDC (Energy < 0.1 W/sec). Suitable
for sensitive RMU tripping coil
IX. Potential Free
Output contact
: 2 Change over Latching type contact for Trip
(annunciation telesignaling).
X. Digital Status I/p : 3 optical isolated status
XI. Operational Indicators (Flags)
ON : Red LED indicates that the internal power
supply is healthy. (Required 20% of load
Current).
PKP : Red LED indicates OC/EF relay Pickup.
TRIP : Indicates that Trip pulse is being executed.

FAULT : Indicates that Fault occurred HR type
XII. Thermal Withstand
Capacity
: X20 times the rated current for 3sec.
: X2 Continuous.
XIII. Battery : Capacity 4.5Volt (1.5 x 3) AAA Alkaline non-
rechargeable battery:
Recommended Energizer, Panasonic or
equivalent.



ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 36 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09


XIV. Drawing
References
: For Cabinet Type - CSG -122
(MAC01401_C)
: For Operating
Characteristics
C1 - APR02201
C2 - APR01801
C3 - APR05101
C4 - APR05201
C5 - APR05301
: For Electrical Connection - APR08402

25.1 Conformance to Standards: -

I. High Voltage Test

: IEC 60255-5.
: At 2.5kV 50Hz between all terminal
connected together and earth for 1
minutes
II. Impulse Voltage
Test

: IEC60255-5.
: Test voltage: 5KV (peak) 1.2 / 50us,
: Energy :0.5 J,
: Polarity : + ve and Ve
: Nos. of impulses : 3 positive and 3
negative impulse
: Duration between Impulses : 5 sec.
III. High Frequency
test
: IEC 60255-22-1,
: Frequency : 1MHz Damped Oscillatory
: Longitudinal :5 KV (peak)
: Duration: sec duration 2 sec.
Between input current Terminal
IV. Electro static
Discharge
: IEC 60255-22-2 Class III and IEC 61000-4-2
class III.
: Contact discharge : 6kV,
: Air discharge: 8KV
: Polarity: both +ve and Ve polarities.




ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 37 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09


V. Fast transient
interference/
bursts
: IEC 60255-22-4 and IEC 61000-4-4, class III
: Amplitude 2Kv, pulse shape 5/50ns
: Burst duration = 15ms.
: Repetition rate 300ms; Both polarities; Ri =
50; duration 1 min.
VI. Vibration Test : IEC 60255-21-1 class 1
: Frequency Range = 10Hz 150Hz ,
acceleration. = 1g
n
(9.8 m/s
2
)
: Sweep rate 1 octave/min; 20 cycle in 3
orthogonal axis.
VII. Shock Test : IEC 60255-21-2 class 1
: Acceleration. = 15g
n
(15 x 9.8 m/s
2
)
: Half sine pulse width 11ms
Number of shocks per axis 3 per direction .
VIII. Serge Immunity
Test
: IEC 60255-22-5 / BS EN 61000-4-5:1995
: Differncial Mode = 2kV
: Common Mode = 4kV
: 1.2/50uS , 5 surges of each polarity
IX. Conducted
Emission Test
: BS EN 55011 : 1998
: Frequency 0.15MHz 30MHz
X. Radiated
Emission Test
: BS EN 55011 : 1998
: Frequency 30MHz 1GHz
XI. Power Frequency
Magnetic Test
: BS EN 61000-4-8: 1994.
: Freq. 50 Hz, Field 100 A/m for 1 min. 1000
A/m for 3 sec.,
XII. Conducted
Disturbance
induced by Radio
Frequency field
: IEC 60255-22-6 / BS EN 61000-4-6 : 1996
: Freq. 150kHz 80MHz, Amplitude 10 V,
Modulation 80% AM @ 1 KHz
XIII. Radiated
Electromagnetic
Field Disturbance
Test
: IEC 60255-22-3 / BS EN 61000-4-3 : 1995
: Freq. 80 MHz 1000 MHz, Amplitude 10
V / m, Modulation 80% AM @ 1 KHz



ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 38 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

26.0 Flow Charts: -
26.1 Flow Chart for Settings: -






Measurement
Fault 1
Fault 2
Fault 4 Fault 5
Password =000
Use Inr / Dec
Trip Test =001
01 : Yes 02 : No
Password =000
New Password
Non Bank
Settings
Non Bank
Settings
Unit ID =001
Password =000
Use Inr /Dec
Bank =001
Range 1 - 4
Ip>=020
Range 20 -240%
IE TMS =x1.15
Range x0.1 -1.2
IE>=010
Range 10 - 100%
Ip>Curve =002
Range C1 - C6
Ip>>=0.15
Multiply by 100
Bank Settings
IpTMS=x1.0
Range x0.1 - x1.2
Multiply by 100
Bank Settings
IE>Curve =002
Range C1 - C6
Ip>C6 Time =0.10
Range 00.1- 99.9S
IE>C6 Time=0.10
Range 00.1 99.9S
IE>>Delay =010
Range 0.05-1.00S
Save Settings?
Mode for Save
IP>>Delay =0.05
Range 0.05-1.00S
Error Log
Measurement
Password =000
Use Inr / Dec
SET Hrs =019
Range 0 - 23
Date / Time
Save Setting?
Mode for Save
SET Mins =015
Range 0 - 59
SET Sec =003
Range 0 - 59
SET Year =008
Range 00 - 99
SET Month =001
Range 1- 12
SET Date =028
Range 1- 31
Date / Time
Fault 3
R=00.00 Y=00.00
B=00.00 N=00.00
Frequency =001
50Hz =1 60Hz =2
Ext. Relay =002
ON =1, OFF =2
Status
IE>>=010
+/
Save Setting?
Mode for Save
Trip Block =01
01:YES 02:NO
+/
+/ +/
+/
+/
+/
+/
+/

+/
+/
+/
Measurement
Fault 1
Fault 2
Fault 4 Fault 5
Password =000
Use Inr / Dec
Trip Test =001
01 : Yes 02 : No
Password =000
New Password
Non Bank
Settings
Non Bank
Settings
Unit ID =001
Password =000
Use Inr /Dec
Bank =001
Range 1 - 4
Ip>=020
Range 20 -240%
IE TMS =x1.15
Range x0.1 -1.2
IE>=010
Range 10 - 100%
Ip>Curve =002
Range C1 - C6
Ip>>=0.15
Multiply by 100
Bank Settings
IpTMS=x1.0
Range x0.1 - x1.2
Multiply by 100
Bank Settings
IE>Curve =002
Range C1 - C6
Ip>C6 Time =0.10
Range 00.1- 99.9S
IE>C6 Time=0.10
Range 00.1 99.9S
IE>>Delay =010
Range 0.05-1.00S
Save Settings?
Mode for Save
IP>>Delay =0.05
Range 0.05-1.00S
Error Log
Measurement
Password =000
Use Inr / Dec
SET Hrs =019
Range 0 - 23
Date / Time
Save Setting?
Mode for Save
SET Mins =015
Range 0 - 59
SET Sec =003
Range 0 - 59
SET Year =008
Range 00 - 99
SET Month =001
Range 1- 12
SET Date =028
Range 1- 31
Date / Time
Fault 3
R=00.00 Y=00.00
B=00.00 N=00.00
Frequency =001
50Hz =1 60Hz =2
Ext. Relay =002
ON =1, OFF =2
Status
IE>>=010
+/
Save Setting?
Mode for Save
Trip Block =01
01:YES 02:NO
+/
+/ +/
+/
+/
+/
+/
+/

+/
+/
+/


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 39 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

26.2 Flow Chart to View Settings: -








































Measurement
R=00.00 Y=00.00
B=00.00 N=00.00
Measurement
Bank Settings
Bank Settings
Ip>=Normal Inv. 1
IE>=Normal Inv. 2
Ip>100% t>1.00
Ip>>1000% T:0.10
IE>080% t>1.00
IE>>0200% T:0.10
Fault 2 Fault 3
Fault 4
Note :
Fault 2, Fault 3, Fault 4 & Fault 5 Message
Displayed in similar format as that of Fault 1
Non Bank
Settings
Unit Id =0001
Trip Test =Yes
Non Bank
Settings
Fault 1
Fault 1
I>>: t : 0002
I>: SF : T
FR=00.00 Y=00.00
B =00.00 N =00.00
Trip Timing
000.04 sec
13/03/09
15:28:37.017
Fault 5
Measurement
Error Log
Error Log
Date / Time
Date / Time
Time : 19:46:10
Date 13/03/09
R=00.00 Y=00.00
B=00.00 N=00.00
- /
Error Code : 000
0000 0088
Frequency =0050Hz
Ext. Relay En =ON
Trip Block = YES
Status
Status
S1 =ON S2 =OFF
S3 =OFF
- /
- /
- /
+/
- /
- /
- /
- /
- /
- /
- /
- /
+ /
+ /
- /
- /
- /
- /
+/
+/
+/
+/
+/
- /
- /
+/
- /
- /
- /
- /
+/
+/
Measurement
R=00.00 Y=00.00
B=00.00 N=00.00
Measurement
Bank Settings
Bank Settings
Ip>=Normal Inv. 1
IE>=Normal Inv. 2
Ip>100% t>1.00
Ip>>1000% T:0.10
IE>080% t>1.00
IE>>0200% T:0.10
Fault 2 Fault 3
Fault 4
Note :
Fault 2, Fault 3, Fault 4 & Fault 5 Message
Displayed in similar format as that of Fault 1
Non Bank
Settings
Unit Id =0001
Trip Test =Yes
Non Bank
Settings
Fault 1
Fault 1
I>>: t : 0002
I>: SF : T
FR=00.00 Y=00.00
B =00.00 N =00.00
Trip Timing
000.04 sec
13/03/09
15:28:37.017
Fault 5
Measurement
Error Log
Error Log
Date / Time
Date / Time
Time : 19:46:10
Date 13/03/09
R=00.00 Y=00.00
B=00.00 N=00.00
- /
Error Code : 000
0000 0088
Frequency =0050Hz
Ext. Relay En =ON
Trip Block = YES
Status
Status
S1 =ON S2 =OFF
S3 =OFF
- /
- /
- /
+/
- /
- /
- /
- /
- /
- /
- /
- /
+ /
+ /
- /
- /
- /
- /
+/
+/
+/
+/
+/
- /
- /
+/
- /
- /
- /
- /
+/
+/


ASHI DA El ec t r o n i c s Pv t . L t d .
Operating Manual For Ashida Numerical Self-Powered
Protection Relay ADR 241S
Page: 47 of 47
Ref.: ADR241Sm_03A
Rev. : 03A Dt. 01.08.09

34.0 Revision Notes: -

Revision
No.
Date Revision Note
01 29.01.08 Original Revision for Software version V1.01
02 29.08.08 1. Software version changed i.e V1.02 to reduce HF
time Delay.
2. Change in Battery Specification.
02A 20.02.09 Software version changed to V1.03 to remove default
settings.
3 13.03.09 1. Software Version changed to SD V1.04 to revise
the Trip setting range for Saudi Electricity
Company.
2. Model No. Definition revised.
3A 01.08.09 Software version changed to V1.05 for Battery ON