Anda di halaman 1dari 25

Project:DERMA LAB

BOQ FOR ELECTRICIAL WORKS


PS Infracon, Bangalore
Sr. No ITEM
BOQ FOR ELECTRICIAL WORKS
PREAMBLE
The description of an item shall be deemed to include all preambles, headings, sub-headings and
references to other documents. The detailed description of work and materials, given in the Specification
are not necessarily repeated in the Bill of Quantities.
The dimensions shown in the drawings shall have to be verified by the contractor at site before execution
of the items and necessary allowance's) have to be made as per the actual dimensions available at site.
The contractor should refer to the detailed drawings for details. All the rates so quoted should be inclusive
of all hardware. In case of discrepancy between drawing and Bill of Quantity the drawing supersedes,
unless specifically mentioned in the BOQ.
Items of work provided in this schedule but not covered in the specifications shall be executed strictly as
per instructions of the engineer-in-charge(PSI)
Unless specifically mentioned otherwise in the contract, the tenderer shall quote for the finished items and
shall provide for the complete cost towards labour, materials, plant and machinery, operational costs,
levies, taxes, transport, repairs, rectification, maintenance till handing over, revenue expenses,
contingencies, overheads, profits and all incidental items not specifically mentioned but reasonably
implied and necessary to complete the works according to the contract.
The quantities of the various items mentioned in the schedule in the schedule of items and may vary up to
any extent or be deleted altogether. The quoted rates of each item shall remain firm for all works and
quantities. The contractor, in his own interest, should get an indication of the probable extent of the work
to be executed under any particular item in this schedule, before undertaking any preliminary and enabling
work or purchasing bought out components related to the work.
Rates shall be quoted both in figures and in words in clear legible writing. No overwriting is allowed. All
scoring and cancellations should be countersigned by the tenderer. In case of illegibility, the interpretation
of the engineer shall be final. All entries shall be in English language.
Engineer-in-charge's (PSI) decision shall be final and binding on the contractor regarding clarifications of
items in this schedule with respect to the other sections of the Contract.
It may be noted that the total work or any part / parts of the same may be awarded as mentioned in this
schedule of items.
The cost quoted to include providing general house-keeping support for the entire site inclusive of all
dedicated labour and supervisory personnel at all times of work, across the entire facility. Cost to include
all equipments, consumables, protective and safety measures at site and providing necessary amenities
like Water supply for drinking water, dedicated Human recourses for the sameand other office facilities as
instructed by Engineers (PSI)
All construction workers will be provided with proper PPE's without which the Engineer (PSI) has to right
to send the worker away until proper PPE's are present
To prevent dust entry from construction site to finished areas demarking with barricades has to be used
INTERNAL WIRING AND POWER POINTS
Light Point (Primary point): Supply
and wiring for light point with 2 runs
of1.5 sq.mm650V grade PVC
insulated Copper conductor
multi strand wires along with one run
PS Infracon, Bangalore
DESCRIPTION OF ITEMS
of 1.5sq.mm copper earth wire in 25mm dia
heavy guage PVC conduit concealed
in wall/ Ceiling including supply and fixing
of 5Amp modular type switch
In suitable anodised GI box complete with fixing 3 way
Ceiling rose including interconnections as required
PVC pipes :- VIP/PRECISION/NELCO, Wires:-Polycab, Switches and Modlar boxes
Anchor Roma, End termination lugs:- DOWELL/3D.
Glands:- SUNIL/HMI/BRACO/COMET
Secondary light point : Same as Item
1.1 But point looped from Primary
point.
Same As Above
Exhaust fan point Supply and wiring same
as item 1.1 above but for Exhaust fan point
Same As Above
5A Switch socket outlet (Independant
type) Supply and wiring same as item
1.1 above but for 5A2/3 pin socket
outlet with switch including the supply of the same
Switches and Modlar boxes:- Anchor Roma,
5Amp. Switch socket outlet:
(Dependant) Supply and fixing of
5Amp.2/3 pin combined switch
socket outlet in lighting control board
including interconnections.
Switches and Modlar boxes:- Anchor Roma,
15A Socket point : Supply and fixing of
15Amp. 5/15A Modular switch & Socket in suitable
anodised box
Switches and Modlar boxes:- Anchor Roma,
Supply and Installation of 3No's 6 Amps 5 pin sockets controlled by
16Amps switch fixed in appropriate factory made boxes excluding
wiring from distribution board to point .
Switches and Modlar boxes:- Anchor Roma,
TOTAL OF INTERNAL WIRING AND POWER POINTS
RUN OF SUBMAINS MAINS:
Supply and wiring with 2runs of 2.5
sq.mm copper conductor wires with
1run of 1.5sq.mm copper earth wire
from DB to switch boards as circuit
wires in 2mm thick PVC conduits
Supply and wiring with 2runs of
4sq.mm copper conductor wires with
1run of 2.5sq.mm copper earth wire
from DB to15A/20A sockets in 2mm
thick PVC conduits
Supply and wiring with 4runs of
6sq.mm copper conductor wires with
2runs of 4sq.mm copper earth wire
from Panel to DBs as circuit
wires in 2mm thick PVC conduits
TOTAL OF SUBMAINS MAINS:
DISTRIBUTION BOARDS:
Supply and installation of following size
TPN MCB double door distribution boards
with CRCA sheet steel enclosure dust and
vermin protected rated for 440V, 50HZ AC
supply operation inclusive of busbar of suitable
capacity, Neutral link with required outgoings
DIN bar, and earthing terminals including
MCBs conforming to IS:8828. The DBs
are to fixed in flush with the wall including
Incomer ELCB and all fixing materials
complete as required. ELDB shall conform
to IS : 12640. The rate shall be inclusive ofwiring adopter boxes
around the DB & the dummies required in the DB.
6 way TPNMCB DB with 12nos 6A/16A - Lighting
SPMCBs as outgoings and 25A DP MCBs -3Nos and 4pole 40Amp,100mA,sensitivity ELCB as incomer.
8way TPNMCB DB with 18nos.6A/16A - Rp-4, Ups-1,
SPMCBs as out goings and 25A DP MCBs -3Nos and 4pole 63Amp,100mA sensitivity ELCB as
incomer
For along with circuit wiring pipe only come to up to DB
8 way TPNMCB Vertical DB with
24nos 6-20A SP MCBs as outgoings and 63A FP 100mA ELCB as incomer. Hume
1 Phase 8 way DB for Emergency Lighting - Emergence
Incomer: 1 No. 32A DP ELMCB
Outgoings: 6 Nos. 6/16A SP MCBs.
For along with circuit wiring pipe only come to up to DB
MV PANELS
Supply, Installation, Testing and Commissioning of 3 phase 415V 4 wire Free Standing Floor mounted MV
panel made out of 14 SWG CRCA sheet after seventank process and painting with Epoxy powder coating
including all switchgear as detailed below. The panel shall consist of suitable rating TPN Aluminium
busbar (at the rating of 0.8A per Sq.mm) supported withDMC/ SMC barriers and colour coded with Heat
shrinkable sleeves. The Metering shall be
provided as specified. The panel shall have Short circuit with standing capacity of minimum 50KA and
consist of the switchgear as mentioned below. The panel shall be mounted on channels grouted to the
floor including all materials. The panel shall be got fabricated from manufacturers with CPRI Test
certificate only. All feeders shall be earthed with 2 GI flats of adequate size to the main earth bus of
50x6mm GI flat. The size of all Panel Mounting Meters shall be 96X96mm.The Panels shall be mounted
on U channels including supply and fixing of the same.All MCCBs shall have 80-100% thermal setting
plug. fuses shall be provided for Control purposes (All Panels Shall be Extendable type). All the incomer
breaker shall be provided with 2nos NO-NC contacts.(All MCBs shall be with 'C' curve)
Main Panel
Incoming : 200A 25KA TP MCCB with thermal setting plug & Earth leakage relay (300mA - 3000mA) with
resincast CBCT 1set
Busbars : 250A TPN Aluminium Busbars - 1Set
Outgoings :
100A 16KA FP MCCBs - 3Nos
63A 10KA FP MCBs ('C'-curve)- 3Nos
40A 10KA FP MCBs ('C'-curve)- 4Nos
20A 10KA FP MCBs ('C'-curve) 2Nos
i) 0 - 500V Voltmeter with Selector switch 1set
ii) 0-200A Ammeter with cast resin CTs and
selector switch-1set
iii) LED type Phase indication lamps with
individual MCB control and toggle switches -1set
TOTAL OF DISTRIBUTION BOARDA AND PANELS
LT CABLE WORK
Supply, Instalaltion, Testing & Commissioning of XLPE insulated sheathed steel tape
armoured Aluminium UG cable with pvc outer sheathing 1.1 KV class .
The cable shall be either laid on existing cable trays or in existing trench.
The cable shall be tied with nylon ties on the cable tray and a overlapping 25x3mm
GI strip shall be fixed to the cable tray. The cost of the nylon tie and overlapping
GI strip shall be included in the cost of installation.
(Not to include the cost of cable trays/trench).
This cable shall be directly laid in ground including
escavation back filling of earth complete
Armoured Aluminium XLPE Cable:
3.5 Core, 120 Sqmm cable.
3.5 Core, 95 Sqmm cable.
4 Core, 25 Sqmm cable.
4 Core, 16 Sqmm cable.
3 Core, 6 Sqmm copper armoured cable.
4 Core, 4 Sqmm copper armoured cable.
Supply, Installation, Testing & Commissioning of End terminations for following cables using
double compression tinned brass glands with bronze lugs using hydraulic
crimping tools complete.
Aluminium cables:
3.5 Core, 120 Sqmm
3.5 Core, 95 Sqmm
4 Core, 25 Sqmm
4 Core, 16 Sqmm
3 Core, 6 Sqmm copper armoured cable
4 Core, 4 Sqmm copper armoured cable
TOTAL FOR LT CABLES
Light Fixtures
Supply, installation, testing & commissioning of following type LED light fixture assemblies:
Supply and installation - Wipro Cat. Ref. No :LC20-036-XXX-WH-XX or Equivalent.
Supply and installation - Wipro Cat. Ref. No :LM17-291-XXX-50-XX or Equivalent.
Exhaust Fans
Supply and Installation of Exhaust fans of following size sweep with gravity louvres shutters including all
accessories / Installation materials required.
305mm Sweep
TOTAL OF LIGHT FIXTURES
Floor Raceway
Supply and fixing of 2mm thick Aluminium Floor Raceways of the following sizes in the floor with cutting
the floor using floor cutting machine etc., 100x 40mm 2mm thick Aluminium Box section as raceway.
Supply and fixing of (for Aluminium Floor Raceway)100x100x50mm deep MS boxes in floor with top
removable cover made out of 18SWG MS Sheet including Painting with 2 coats of anti corrosive paint and
2 coats of synthetic enamel paint etc complete as required.
TOTAL OF RACEWAYS
DATA / TELEPHONE & TV DISTRIBUTION SYSTEM
Supply & Installation of moulded type telephone /data IC outlets 3 pin
socket in factory made 16Swg GI box to size 3"x3"x3" and fixed
at 2' 6" ht & at 1' 6" other areas from finished floor level.
Supply and Installation of 25mm dia pvc conduit with
16Swg GI fish wire from Telephone / data point to Telephone /data
draw box in shaft.
Supply and Installation of 19mm dia pvc conduit with
14 Swg GI fish wire from telephone/data draw box in each
floor to main tag block in Ground floor.
Supply and Installation of CAT 6 / AT and T
drawn in existing conduit from telephone/data point to tag block.
TOTAL DATA / TELEPHONE & TV DISTRIBUTION SYSTEM
EARTHING SYSTEM
Supply & Installation of Earth Electrode as per approval of EB
and the Earth electrodes shall be 40mm dia 3mm
thick GI long confirming to IS 1249, the entire earth
installation shall be as per Indian STD code of practice
IS 3043 with GI plate 2'x2'x1/4" & funnel arrangement.
Supply, installation, Testing and commissioning of Copper plate earth
station as per IS 3043 complete with 600 x 600 x 3mm Copper plate,
GI watering funnel, 450 mm x 450mm CI frame and CI cover, 300mm
brick masonary chamber etc. complete.
EARTH STRIPS
Supply and Laying / clamping of below listed GI/Copper earth tapes.
50 x 6mm GI Earth flat
25 x 3mm copper Earth flat
25 x 6mm GI Earth flat
Supply and Installation of 8 Swg GI wire of electrical
grade for connecting up of earthing of pump motors/
mains/equipments (single run).
TOTAL FOR ANNEXURE - 3
QTY Rate in INR Amount in INR
Q R A = QxR
UNIT
no's 28 850.00 23,800.00
Nos 20 600.00 12,000.00
Nos 1 1,000.00 1,000.00
Nos 20 300.00 6,000.00
Nos 10 600.00 6,000.00
Nos 162 600.00 97,200.00
Nos 8 850.00 6,800.00
mtr 250 148.00 37,000.00
Mtr 420 190.00 79,800.00
Mtr 0 - -
Set
0
- -
Set 0 - -
Set 0 - -
Nos 0 - -
Nos 0 - -
Mtr 0 - -
Mtr 0
Mtr 0 - -
Mtr 0 - -
Mtr 0 - -
Mtr 0 - -
Nos. 0 800.00 -
Nos. 0 600.00 -
Nos. 0 500.00 -
Nos. 0 500.00 -
Nos. 0 200.00 -
Nos. 0 200.00 -
each 40 12,000.00 480,000.00
each 10 7,450.00 74,500.00
no
1
3,000.00 3,000.00

mtr
20
800.00 16,000.00
no
0
250.00 -
Nos. 40
Mtr 125
mtr 10
Mtr 950
set 0
set 4 - -
mtr 0
mtr 60 - -
Mtr 20 - -
mtr 50 - -
843,100.00
843,100.00
Description Unit Qty
12 way TPNMCB Vertical DB with Double Door(Legrand)
24nos 6-20A SP MCBs as outgoings and 63A FP 100mA ELCB as incomer.
Hume
2
Cable Trench 300 X 50
Mtrs 22.5
3
Cable Trench 200 X 50
Mtrs 40
4
Cable Trench 100 X 50
Mtrs 7.5
5
Floor Raceway 300 X 50
Mtrs 5
6
Floor Raceway 100 X 50
Mtrs 7.5
7
Cable Trench Joint patti
Mtrs 48
8
8 mm MS rods for Cable trench
NOS 50
9
Metal Junction box
NOS 40
10
Conduct Bends
NOS 150
11
Flexible Metal pipe
Mtrs 60
12
10 sq mm armoured cable raw power incoming
Mtrs 150
13
2.5 sq mm armoured cable for few modes
Mtrs 180
14
10 Sq mm flexible wire for DB earthing
Mtrs 360
15
10 mm Anchor Fastners
Mtrs 100
16
16 sq mm armoured
Mtrs 150
17
cable termination for 16 sqmm
NOS 10
18
cable termination for 10 sqmm
NOS 10
19
cable termination for 2.5 sqmm
NOS 10
20
1 inch Flexible Metal pipe
Mtrs 45
SR. No
1 NOS 2
GRAND TOTAL
Amt(Rs.)
16,450
16,000
2,250
4,000
4,500
1,440
3,000
1,400
3,600
1,500
87,000
54,000
57,600
3,000
860 129,000
800
8,000
600 6,000
400 4,000
1,350
UR(Rs.)
28,000 56,000
300
600
400
300
800
600
30
160
30
30
460,090.00
60
35
24
25
580
Description Unit Qty Amt(Rs.)
12 way TPNMCB Vertical DB with
Double Door(Legrand)
24nos 6-20A SP MCBs as outgoings and
63A FP 100mA ELCB as incomer.
Hume
2
Cable Trench 300 X 50
Mtrs 22.5 16,450
3
Cable Trench 200 X 50
Mtrs 40 16,000
4
Cable Trench 100 X 50
Mtrs 7.5 2,250
5
Floor Raceway 300 X 50
Mtrs 5 4,000
6
Floor Raceway 100 X 50
Mtrs 7.5 4,500
7
Cable Trench Joint patti
Mtrs 48 1,440
8
8 mm MS rods for Cable trench
NOS 50 3,000
9
Metal Junction box
NOS 40 1,400
10
Conduct Bends
NOS 150 3,600
11
Flexible Metal pipe
Mtrs 60 1,500
12
1 inch Flexible Metal pipe
Mtrs 45 1,350
13
Supply and wiring with 2runs of 2.5
sq.mm copper conductor wires with
Mtrs 540 148 79,920
1run of 1.5sq.mm copper earth wire
14
Supply and wiring with 2runs of 4
sq.mm copper conductor wires with
Mtrs 1980 190 376,200
1run of 2.5sq.mm copper earth wire
567,610
30
SR. No
UR(Rs.)
1 NOS 2 28,000 56,000
60
35
24
25
30
600
400
300
800
600

Anda mungkin juga menyukai