Anda di halaman 1dari 44

DEEP SEA ELECTRONICS

DSE332 / DSE333 Series ATS


Configuration Suite

Document Number 057-106

Author : Anthony Manton
COMPLEX SOLUTIONS
MADE SIMPLE
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

2

Deep Sea Electronics Plc
Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND

Sales Tel: +44 (0) 1723 890099
Sales Fax: +44 (0) 1723 893303

E-mail : sales@Deepseaplc.com
Website : www.deepseaplc.com


DSE300 Series configuration suite

Deep Sea Electronics Plc
All rights reserved. No part of this publication may be reproduced in any material form (including photocopying
or storing in any medium by electronic means or other) without the written permission of the copyright holder
except in accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Applications for the copyright holders written permission to reproduce any part of this publication should be
addressed to Deep Sea Electronics Plc at the address above.

The DSE logo and the names DSEUltra, DSEControl, DSEPower, DSEExtra, DSEMarine and DSENet are UK
registered trademarks of Deep Sea Electronics PLC.

Any reference to trademarked product names used within this publication is owned by their respective
companies.

Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.


Amendments List

Amd.
No.
Comments Module
version
Configuration Suite
Version
1.1 Added more desciption to breaker schemes and transfer timers. N/A N/A
1.2 Change of gen current to load current N/A N/A
2 Addition of DSE333 ATS and V2 332 2.0+ 2.0.8.100+














Typeface : The typeface used in this document is Arial. Care should be taken not to mistake the upper case
letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.

DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 3
TABLE OF CONTENTS
1 BIBLIOGRAPHY .......................................................................................... 4
2 DESCRIPTION ............................................................................................. 4
2.1 SOFTWARE INSTALLATION INSTRUCTIONS................................................................................. 5
3 HARDWARE INSTALLATION ...................................................................... 8
3.1 TROUBLESHOOTING INSTALLATION............................................................................................. 8
4 USING THE CONFIGURATION SUITE ......................................................... 9
5 MENUS AND TOOLBAR ............................................................................ 10
5.1 FILE MENU ....................................................................................................................................... 10
5.2 TOOLS MENU................................................................................................................................... 11
5.2.1 OPTIONS .................................................................................................................................. 11
5.2.2 ACCESS PERMISSIONS .......................................................................................................... 11
5.2.4 UPDATE FIRMWARE ............................................................................................................... 13
5.3 HELP MENU ..................................................................................................................................... 15
5.4 TOOLBAR ......................................................................................................................................... 15
6 EDIT CONFIG............................................................................................. 16
6.1 SCREEN LAYOUT ............................................................................................................................ 16
6.2 MODULE OPTIONS .......................................................................................................................... 17
6.3 APPLICATION OPTIONS ................................................................................................................. 18
6.3.1 BREAKER SCHEME A.............................................................................................................. 19
6.3.2 BREAKER SCHEME B.............................................................................................................. 20
6.4 DIGITAL INPUTS .............................................................................................................................. 22
6.4.1 INPUT FUNCTIONS .................................................................................................................. 23
6.5 OUTPUTS ......................................................................................................................................... 25
6.5.1 DIGITAL OUTPUTS .................................................................................................................. 25
6.5.2 OUTPUT SOURCES ................................................................................................................. 26
6.6 TIMERS ............................................................................................................................................. 28
6.6.1 START TIMERS ........................................................................................................................ 28
6.6.2 LOAD / STOPPING TIMERS..................................................................................................... 29
6.6.3 MODULE TIMERS..................................................................................................................... 29
6.7 GENERATOR.................................................................................................................................... 30
6.7.1 GENERATOR OPTIONS........................................................................................................... 30
6.7.2 GENERATOR ALARMS ............................................................................................................ 31
6.8 LOAD CURRENT .............................................................................................................................. 32
6.9 MAINS ............................................................................................................................................... 33
6.9.1 MAINS OPTIONS ...................................................................................................................... 33
6.9.2 MAINS ALARMS ....................................................................................................................... 34
6.10 PLANT BATTERY............................................................................................................................. 35
6.11 SCHEDULER .................................................................................................................................... 36
8 SCADA....................................................................................................... 37
8.2 MIMIC ................................................................................................................................................ 38
8.3 LANGUAGES.................................................................................................................................... 39
8.4 DIGITAL INPUTS .............................................................................................................................. 40
8.5 DIGITAL OUTPUTS .......................................................................................................................... 40
8.6 MAINS ............................................................................................................................................... 41
8.7 GENERATOR.................................................................................................................................... 41
8.8 LOAD ................................................................................................................................................ 42
8.9 PLANT BATTERY............................................................................................................................. 42
8.10 ALARMS ........................................................................................................................................... 42
8.11 STATUS ............................................................................................................................................ 43
8.12 EVENT LOG ...................................................................................................................................... 43
8.13 DATE AND TIME .............................................................................................................................. 44



DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

4

1 BIBLIOGRAPHY

This document refers to and is referred to by the following DSE publications which can be obtained from the
DSE website www.deepseaplc.com :

DSE PART DESCRIPTION
057-097 DSE332 ATS operator manual
057-118 DSE333 ATS operator manual


2 DESCRIPTION

The DSE300 Series configuration suite allows the 300 family of ATS control modules (DSE332 / DSE333)
to be connected to a PC via USB A USB B cable. Once connected the various operating parameters within
the module can be viewed or edited as required by the engineer.

The configuration suite should only be used by competent, qualified personnel, as changes to the operation of
the module may have safety implications on the panel / generating set to which it is fitted. Access to critical
operational sequences and settings for use by qualified engineers, may be barred by a security code set by
the generator provider.
The information contained in this manual should be read in conjunction with the information contained in the
appropriate module documentation. This manual only details which settings are available and how they may
be used.
A separate manual deals with the operation of the individual module (See section entitled Bibliography
elsewhere in this document).


DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 5

2.1 SOFTWARE INSTALLATION INSTRUCTIONS
Minimum system requirements

Operating System Windows Vista, Windows XP or Windows 2000 with Microsoft .Net 2.0 framework
Monitor 17 inch recommended (1024 x 768 resolution)
Communications USB required o configure the module.

NOTE: - As 300 Series configuration software for Windows is a 32-Bit application requiring
Microsoft .net 2 framework, it will not operate on Windows 2.0, 3.0, 3.1,3.11, 95, 98 or Me.
NOTE: - Exit all other programs before installing the software. It is recommended that any earlier
releases of the software be uninstalled prior to installing this version.
NOTE: - Please register online at www.deepseaplc.com Once registered you will be able to
download updates to the software to ensure that you always have access to the latest features.

Insert the Software CD into the CD-ROM drive on the PC. The CD will then Auto-run if this feature is enabled
on your PC.

Alternatively:

Double click on Computer


Double click on CD-ROM Drive


Double click CDSetup








Click Next to continue


DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

6


Select Disk Cost to view remaining disk space, Click Next to continue.


Example showing the Disk Cost window.




DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 7



DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

8
3 HARDWARE INSTALLATION

Ensure the Configuration Suite Software is installed on the PC as described above.
The installation of the PC software also installs the DSE Controller USB Driver automatically.
Connect the USB cable (USB type A to Type B as commonly used on USB printers) to the module and to
the PC as shown below.




Windows detects the module when power is applied to it.

You are now ready to configure or monitor the module using the Configuration Suite Software.



3.1 TROUBLESHOOTING INSTALLATION


Occasionally USB devices are disabled by the Windows operating system, the following procedure will re-enable the
device in these i nstances.

Disconnect the Deep Sea Electronics Controller from the USB port. Wait a moment, then reconnect and try
again. If you still encounter problems then :
Try another USB cable. If you dont have one, its the same type of cable as usually used between a PC
and a USB pri nter. If you still encounter problems then :
Disconnect the Deep Sea Electronics Controller. Shutdown, then restart the PC. Reconnect the interface,
then try again. If you continue to experience problems then :
Check the USB port with another device (for instance a mouse, pri nter or digital camera).




DSE332 ATS USB socket
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 9
4 USING THE CONFIGURATION SUITE

To run the Configuration Suite Software for Windows program click the Windows start button
or depending upon your version of Windows.

Then select All Programs - Deep Sea Electronics PLC DSE Configuration Suite DSE Configuration
Suite

After a short delay to load the application, the splash screen is shown, after which the screen will
display:-





This is the initial start-up screen and can be disabled by checking the box Hide this screen at start-up.
The screen prompts the user to select between the three main uses for the software:

Creating a new configuration. Select the module type under Create new configuration. This allows
you to create a configuration for the latest module version. Use File | Convert to... to convert the
configuration to suit an earlier module version or use Tools | Update firmware to update an earlier
module to the latest firmware version.
Editing a configuration previously saved to disk or flash memory device. Select the configuration file
either from the Open recent configuration area or by clicking Open a configuration file and browsing
to the file.
Reading and changing the configuration of a connected module. Click Read configuration from a
module. The file is read from a currently connected controller and is available for editing in the
Configuration Suite.

Alternatively you can ignore this screen and continue to use the program in the background. Once you make a
connection or load/create a configuration, the start-up screen will disappear.
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

10

5 MENUS AND TOOLBAR

The menu and toolbar are located at the top of the screen:




5.1 FILE MENU


Create a new configuration file. You are prompted to select what kind of
module you want to create the configuration for.
The settings of the new configuration file match the factory settings for the
chosen module type.
You can only select to create a configuration file for the latest version of
controller. If you want to create a configuration for an earlier version of
controller, you can use Convert to... to make your configuration suitable for the
earlier controller or use Tools | Update firmware to update the earlier module
to the latest version.

Open an existing file from disk or flash memory device.

Close the currently open file.

Save the currently open file to the location it was loaded from previously. If this
is a new file, you are prompted to enter a filename.

Save the currently open file, under a new name. You will be prompted to enter
a filename.

Send the currently open configuration settings to the controller.

Read the settings out of the connected controller for viewing / editing.

Read the settings from the connected controller and convert to the currently
selected configuration type.

Read the settings from a configuration file on disk or flash memory device and
convert to the currently selected configuration type.

Convert the currently loaded configuration file to suit another module type or
another module version.

Print the currently open configuration file.

Preview what the configuration file will look like on the page after printing.

Select printer type and printer settings.

Exit the software. If the currently open file has changed since it was last
saved, you will be prompted to save it.


DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 11
5.2 TOOLS MENU

5.2.1 OPTIONS

Opens the Settings screen containing customisation options for the Configuration Suite.


5.2.2 ACCESS PERMISSIONS

Access permissions is an advanced Administration option to allow OEMS to setup the Configuration Suite
software to limit access for certain users.
For instance, the generator OEM can install the software on the End Users PC and then setup multiple
usernames to limit the customers access to only those functions that the OEM requires for the end user.
An example of this is to give only SCADA access to a user requiring monitoring, or to give access to read and
write configuration files, but not to edit a configuration file.



Create a new user type



Click the exit button if you dont
want to update your module.
Select Edit, then New to create
a new user
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

12



This example shows a new user
that is able to view, read and
write configurations but is not
able to edit the configuration.

When you exit this window you
are asked if you want to save
these changes and then
prompted to enter the password
for this user.
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 13

5.2.4 UPDATE FIRMWARE

Selecting Update Firmware initiates the update wizard:








Click the exit button if you dont
want to update your module.
Click next to continue.
Hint : Stopping the update process
once it begins could leave the
module inoperable! If this occurs,
simply run the update wi zard again
and let it complete correctly.
Ensure the modules supply is
removed, and then Click next to
continue.
Connect the USB cable to the
module and into your PC, then
Click next to continue.
Click to select the firmware update
file.
Then click next to
continue.
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

14






If the file you attempt to send to the
module is not compatible with the
currently connected module, the
update cannot continue.
In this example an attempt was
made to send a 7210 firmware file
to a 7220 module!
Power up the module. It will be
automatically detected and the
update process will begin.
The update is now in progress and will
take under one minute.

During this phase:

DO NOT DISCONNECT THE USB
CONNECTION

DO NOT TURN OFF YOUR PC


DO NOT REMOVE POWER
FROM THE CONTROLLER
The update is now complete.

The module will automatically restart
with the updated firmware (internal
software program).

It is now safe to disconnect the USB
lead and power down the module or
your PC.

Click OK to continue.
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 15
5.3 HELP MENU


Shows the version number of the configuration suite

5.4 TOOLBAR

The toolbar contains the most used commands from the menus and is often a quicker way of accessing these
commands.

Create a new configuration file

Open an existing file from disk or flash memory device

Save the currently open file to the location it was loaded from previously. If this is
a new file, you are prompted to enter a filename.

Print the currently open configuration file

Preview what the configuration file will look like on the page after printing.

Send the currently open configuration settings to the controller

Read the settings out of the connected controller for viewing / editing

Shows the version number of the configuration suite

Voltages are shown as phase to phase voltages in the configuration editor
Voltages are shown as phase to neutral voltages in the configuration editor

Select the communication method. The choices present are dependent upon your
PCs configuration.

USB To connect via USB directly to the controller, select USB :



DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

16
6 EDIT CONFIG

This menu allows module configuration, to change the function of Inputs, Outputs and LEDs, system timers
and level settings to suit a particular application.

6.1 SCREEN LAYOUT


















The type of
configuration
file being edited
Close this
configuration file
Move to the
Previous or Next
configuration page
The coloured
shading shows
the currently
selected page.
Click + or to
show or hide
the sub settings
within each
sections.
Click to select
the subsection
to view / edit
Click to return
to this page at
any time
Step forward or
backward through
previously viewed
pages
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 17
6.2 MODULE OPTIONS


This section allows the user to change the options related to the module itself.





Miscellaneous
Options

Lamp test at power
up
=Lamp test at power up is disabled.
=All module lamps illuminate when power is first applied.
Transfer by buttons =Fascia load control buttons are disabled.
=Fascia load control buttons are enabled when the module is in Manual Mode.




Allows the user to
select the function
of the modules
user configurable
LED indicators.
For details of
possible
selections, please
see section
entitled Output
sources
elsewhere in this
document.
Allows the user to
create logo and text
insert cards
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

18


6.3 APPLICATION OPTIONS



Miscellaneous
Options

Breaker type

Check Sync
See overleaf for description of the Breaker Type and Check Sync options
Return to
programmed
transition
This option is only available when Check Sync is enabled.
= Normal operation
=During load transfer if the check sync of the supplies does not occur within two minutes,
a break or open transition transfer will occur.
Elevator Post
Transfer
=Normal operation
=Any configurable output set to elevator control remains active for the duration of the
elevator delay after a load transfer has taken place.



DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 19

6.3.1 BREAKER SCHEME A

Breaker scheme A is suitable for contactors or ACBs.

NOTE : Generator Closed Auxiliary and Mains Closed Auxiliary inputs do not affect the operation
of the load switching in Breaker Scheme A

6.3.1.1 MAINS / GENERATOR LOAD INHIBIT

Activation of an input configured to mains load inhibit or generator load inhibit inputs cause the corresponding
breaker to be opened immediately. No other change in function will occur.
When the input is deactivated the breaker is closed again if appropriate.

6.3.1.2 LOAD SHEDDING

If an input configured to Load Shed is activated, outputs set to Open Mains and Open Gen will energise, and
inputs configured to Close Mains and Close Gen will de-energise. Open Mains Pulse and Open Gen Pulse
outputs will only energise if the corresponding supply was on load before application of the Load Shed input.
When the Load Shed input is deactivated, the load will be transferred back to the supply that was
disconnected before application of the input.

6.3.1.3 TIMING DIAGRAM

Open Mains
Close Gen
Close Mains
Open Gen
Open Mains Pulse
Close Gen Pulse
Close Mains Pulse
Open Gen Pulse
Transfer time Transfer Time
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

20
6.3.2 BREAKER SCHEME B

Breaker Scheme B is intended only for use with certain designs of transfer switch. If you are using contactors,
you MUST select Breaker Scheme A.

6.3.2.1 CHECK SYNCHRONISING IS DISABLED

6.3.2.1.1 TRANSFERRING TO GENERATOR

To open the mains breaker the Open Mains output energises, it then de-energises when the Mains Closed
Auxiliary indicates it has successfully opened, or after 1s whichever occurs first.
When the Mains Closed Auxiliary indicates the mains breaker has opened, the transfer timer begins.
When the transfer timer expires, the module attempts to close the generator breaker by energising the Open
Mains and Close Generator outputs simultaneously, it then de-energises these outputs when the Generator
Closed Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.

6.3.2.1.2 TRANSFERRING TO MAINS

To open the generator breaker the Open Gen output energises, it then de-energises when the Generator
Closed Auxiliary indicates it has successfully opened, or after 1s whichever occurs first.
When the Generator Closed Auxiliary indicates the generator breaker has opened, the transfer timer begins.
When the transfer timer expires, the module attempts to close the mains breaker by energising the Open Gen
and Close Mains outputs simultaneously, it then de-energises these outputs when the Mains Closed Auxiliary
input indicates it has successfully closed, or after 1s whichever occurs first

6.3.2.1.3 LOAD SHED INPUT

When the Load Shed input is activated while the generator is closed the Open Gen output energises, it then
de-energises when the Generator Closed Auxiliary input indicates that it has successfully opened, or after 1s
whichever occurs first.

When the Load Shed input is activated while the mains is closed the Open Mains output energises, it then de-
energises when the Mains Closed Auxiliary input indicates that it has successfully opened, or after 1s
whichever occurs first.

When the Load shed input is de-energised the load will be returned to the supply that was disconnected,
providing that supply is healthy.

6.3.2.1.4 TIMING DIAGRAM
Open Mains
Close Gen
Close Mains
Open Gen
Non-Sync Transfer Time Non-Sync Transfer Time
Gen has closed
Mains has closed
Mains has opened
Gen has opened
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 21
6.3.2.2 CHECK SYNCHRONISING IS ENABLED

NOTE : The module waits indefinitely for synchronisation unless the Return to programmed
transition function is active in which case after 2 minutes it performs a non-sync transfer as
described in the previous section.

NOTE : The transfer time is ignored during a check-sync but is used if the transfer fails and it
performs a non-sync transfer.


6.3.2.2.1 TRANSFER TO GENERATOR

When the module is about to transfer from mains to generator it activates the check sync function.
When the mains and generator are within the phase and frequency window the module energises the Open
Mains and Close Gen outputs simultaneously. These outputs are de-energised when the Generator Closed
Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.

6.3.2.2.2 TRANSFER TO MAINS

When the module is about to transfer from generator to mains it activates the check sync function.
When the mains and generator are within the phase and frequency window the module energises the Open
Gen and Close Mains outputs simultaneously. These outputs are de-energised when the Generator Closed
Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.

6.3.2.2.3 LOAD SHED INPUT

When the Load Shed input is activated while the generator is closed the Open Gen output energises, it then
de-energises when the Generator Closed Auxiliary input indicates that it has successfully opened, or after 1s
whichever occurs first.

When the Load Shed input is activated while the mains is closed the Open Mains output energises, it then de-
energises when the Mains Closed Auxiliary input indicates that it has successfully opened, or after 1s
whichever occurs first.

When the Load shed input is de-energised the load will be returned to the supply that was disconnected,
providing that supply is healthy.

6.3.2.2.4 TIMING DIAGRAM

Open Mains
Close Gen
Close Mains
Open Gen
Gen has closed
Mains has closed
In Sync
In Sync
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

22


6.4 DIGITAL INPUTS

The inputs page is subdivided into smaller sections.
Select the required section with the mouse.














Input function. See section
entitled Input functions for
details of all available functions
Close or open to activate
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 23
6.4.1 INPUT FUNCTIONS

Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor
devices and software programs. Where the DSE input functions can be represented by IEEE 37.2, the
function number is listed below.

Function Description
Not used The input is disabled
Alarm Mute This input is used to silence the audible alarm from an external source,
such as a remote mute switch.
Alarm Reset This input is used to reset any latched alarms from a remote location. It
is also used to clear any latched warnings which may have occurred (if
configured) without having to stop the generator.
Auto Restore Inhibit
IEEE 37.2 - 3 checking or
interlocking relay

In the event of a remote start/mains failure, the generator will be
instructed to start and take load. On removal of the remote start
signal/mains return the module will continue to run the generator on
load until the Auto Restore Inhibit input is removed. This input allows
the controller to be fitted as part of a system where the restoration to
mains is controlled remotely or by an automated system.
Auto start Inhibit
IEEE 37.2 - 3 checking or
interlocking relay

This input is used to provide an over-ride function to prevent the
controller from starting the generator in the event of a remote
start/mains out of limits condition occurring. If this input is active and a
remote start signal/mains failure occurs the module will not give a start
command to the generator. If this input signal is then removed, the
controller will operate as if a remote start/mains failure has occurred,
starting and loading the generator. This function can be used to give an
AND function so that a generator will only be called to start if the
mains fails and another condition exists which requires the generator to
run. If the Auto start Inhibit signal becomes active once more it will be
ignored until the module has returned the mains supply on load and
shutdown.
This input does not prevent starting of the engine in MANUAL or TEST
modes.
Auxiliary Generator Ready Allows an external device (such as the engine control module) to
instruct the ATS controller that the system is healthy and available to
take load. The ATS controller then monitors the voltage and frequency
to check they are within acceptable limits before performing the load
transfer function.

Input K is fixed to provide this function.
If not required, configure input k to open to activate and leave input K
disconnected. Alternatively, connect input K permanently to the DC
positive supply.
Auxiliary Mains Fail

The module will monitor the incoming single or three phase supply for
Over voltage, Under Voltage, Over Frequency or Under frequency. It
may be required to monitor a different mains supply or some aspect of
the incoming mains not monitored by the controller. If the devices
providing this additional monitoring are connected to operate this input,
the controller will operate as if the incoming mains supply has fallen
outside of limits, the generator will be instructed to start and take the
load. Removal of the input signal will cause the module to act if the
mains has returned to within limits providing that the mains sensing also
indicates that the mains is within limits.
Generator Closed Auxiliary
IEEE 37.2 - 3 Checking or
interlocking relay
(breaker acheme B)
This input is used to provide feedback to allow the controller to give true
indication of the contactor or circuit breaker switching status. It should
be connected to the generator load switching device auxiliary contact.

In Breaker Scheme A, Incorrect application of this signal does not
trigger an alarm condition, it is used solely for indication of the breaker
status.

In Breaker Scheme B this feedback is used for internal interlocking of
the breaker outputs.

DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

24
Generator Load Inhibit
IEEE 37.2 - 52 AC circuit breaker

This input is used to prevent the controller from loading the generator. If
the generator is already on load, activating this input will cause the 300
series controller to unload the generator. Removing the input will allow
the generator to be loaded again.
NOTE: -This input only operates to control the generator-
switching device if the 300 load switching logic is attempting to
load the generator. It will not control the generator-switching
device when the mains supply is on load.
Inhibit scheduled run This input is used to prevent operation of the set by the internal
Scheduler function.
Lamp Test This input is used to provide a test facility for the front panel indicators
fitted to the 300 module. When the input is activated all LEDs should
illuminate.
Load Shedding Opens both the mains and generator load switch devices. See the
section entitled Breaker Scheme for details of how this input interacts
with the load switching control.
Mains closed Auxiliary
IEEE 37.2 - 3 Checking or
interlocking relay
(breaker acheme B)

This input is used to provide feedback to allow the 300to give true
indication of the contactor or circuit breaker switching status. It should
be connected to the mains load switching device auxiliary contact.

In Breaker Scheme A, Incorrect application of this signal does not
trigger an alarm condition, it is used solely for indication of the breaker
status.

In Breaker Scheme B this feedback is used for internal interlocking of
the breaker outputs.
Mains Load Inhibit
IEEE 37.2 - 3 checking or
interlocking relay

This input is used to prevent the 300from loading the mains supply. If
the mains supply is already on load activating this input will cause the
300to unload the mains supply. Removing the input will allow the mains
to be loaded again.
NOTE: -This input only operates to control the mains
switching device if the 300load switching logic is attempting to
load the mains. It will not control the mains switching device when
the generator is on load.
Open / Close generator
IEEE 37.2 - 52 AC circuit breaker
Allows connection of an external signal to control open and closing of
the generator load switch device.
Open / Close mains
IEEE 37.2 - 52 AC circuit breaker
Allows connection of an external signal to control open and closing of
the mains load switch device.
Panel Lock Locks the module into the current operating mode.
Remote Start off load

If this input is active, operation will be similar to the Remote Start on
load function except that the generator will not be instructed to take the
load. This function can be used where an engine only run is required
e.g. for exercise.
Remote Start on load When in auto mode, the module will perform the start sequence and
transfer load to the generator.
In Manual mode, the load will be transferred to the generator if the
engine is already running, however in manual mode, this input will not
generate start/stop requests of the engine.
Simulate Mains available

This function is provided to override the modules internal monitoring
function. If this input is active, the module will not respond to the state of
the incoming AC mains supply.
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 25
6.5 OUTPUTS

6.5.1 DIGITAL OUTPUTS










Select if the relay is to
energise or de-energise
upon activation of the
source
Select what the
output is to be
used to control
These labels
match the
typical wiri ng
diagram
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

26

6.5.2 OUTPUT SOURCES

The list of output sources available for configuration of the module relay outputs also applies to the LED
configuration and expansion relay outputs (7300 series only).

Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor
devices and software programs. Where the DSE output functions can be represented by IEEE 37.2, the
function number is listed below.







Output source Activates Is not active.
Not Used The output will not change state (Unused)
Audible Alarm
IEEE 37.2 74 alarm relay
This output indicates that the internal
sounder is operating to allow it to feed an
external sounder. Operation of the Mute
pushbutton will reset this output once
activated.
Inactive if the internal sounder is not
operating.
Battery Over Voltage
IEEE 37.2 59DC overvoltage relay

This output indicates that a Battery Over
voltage alarm has occurred.
Inactive when battery voltage is not High
Battery Under Voltage
IEEE 37.2 27DC undervoltage relay

This output indicates that a Battery Under
Voltage alarm has occurred.
Inactive when battery voltage is not Low
Close Gen Output
IEEE 37.2 52 ac circuit breaker
Used to control the load switching device.
Whenever the 6100 module selects the
generator to be on load this control source
will be acti ve.
Inactive whenever the generator is not
required to be on load
Close Gen Output Pulse
IEEE 37.2 52 ac circuit breaker
Used to control the load switching device. Whenever the 6100 module selects the
generator to be on load this control source will be acti ve for the duration of the Breaker
Close Pulse timer, after which it will become inacti ve again.

This output is not available when Breaker Scheme B is selected, use Close Gen
Output instead.
Close Mains Output
IEEE 37.2 52 ac circuit breaker

Used to control the load switching device.
Whenever the 6100 module selects the mai ns to
be on load this control source will be active.
The output is inactive whenever
the mains is not required to be on
load
Close Mains Output Pulse
IEEE 37.2 52 ac circuit breaker

Used to control the load switching device. Whenever the 6100 module selects the mains
to be on load this control source will be active for the duration of the Breaker Close
Pulse timer, after which it will become i nacti ve again.

This output is not available when Breaker Scheme B is selected, use Close Mains
Output instead.
Combined Mains Failure

Active when the mains supply is out of limits OR the input for Auxiliary Mai ns Failure is
active
Common Warning Active when one or more Warning alarms are
active
The output is inactive when no
warning alarms are present
Cooling Down Active duri ng the off load cooling run
Digital Input A - K Active when the digital input is acti ve Inactive when :
If the input is not acti ve
If the input is active but
conditioned by activation delay,
safety timer or Arming
requirements.
Elevator control Active duri ng the elevator delay time before a
load transfer takes place and remai ns active
for the duration of the elevator delay after a
transfer takes place (when elevator post
transfer is enabled.
Inactive at all other times
Generator Available Becomes active when the generator is
available to take load.
Inactive when
Loading voltage and loading
frequency have not been reached
After electrical trip alarm
During the starti ng sequence
before the end of the warmi ng
timer.

The outputs are in alphabetical
order with the parameter first. For
instance for overspeed output, its
listed as Engine Overspeed.
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 27
Output source Activates Is not active.
Generator failure Latched Activates when the generator failure alarm is actived. Reset by digital input configured to
Alarm Reset
Generator failure Unlatched Activates when the generator failure alarm is actived. Reset automatically when the
generator becomes available
Generator available Activates when the generator becomes available, is within configured limits and the
auxiliary generator ready input is acti ve.
Generator load inhibited Indicates that an input configured to Generator Load Inhibit is acti ve, preventing the set
from taking load.
Generator available Activates when the generator becomes available. Ignores alarm conditions and the
generator transient delay
Mains failure Latched Activates when the mains failure alarm is actived. Reset by digital input configured to
Alarm Reset
Mains failure Unlatched Activates when the mains failure alarm is actived. Reset automatically when the mains
becomes available
Mains in limits Activates when the generator becomes available, is within configured limits and the
auxiliary generator ready input is acti ve.
Mains load inhibited Indicates that an input configured to Generator Load Inhibit is acti ve, preventing the set
from taking load.
Mains available Activates when the generator becomes available. Ignores alarm conditions and the
generator transient delay
Open Gen Output
IEEE 37.2 52 ac circuit breaker
Used to control the load switching device.
Whenever the 300 module selects the
generator to be off load this control source
will be acti ve.
Inactive whenever the generator is
required to be on load
Open Gen Output Pulse
IEEE 37.2 52 ac circuit breaker
Used to control the load switching device. Whenever the 300 module selects the
generator to be off load this control source will be acti ve for the duration of the Breaker
Open Pulse timer, after which it will become inactive agai n.

This output is not available when Breaker Scheme B is selected, use Open Gen
Output instead.
Open Mains Output
IEEE 37.2 52 ac circuit breaker
Used to control the load switching device.
Whenever the 300 module selects the
mains to be off load this control source will
be active.

The output is inactive whenever the mai ns
is required to be on load
Open Mains Output Pulse
IEEE 37.2 52 ac circuit breaker
Used to control the load switching device. Whenever the 300 module selects the mai ns
to be off load this control source will be acti ve for the duration of the Breaker Open
Pulse timer, after which it will become i nacti ve again.

This output is not available when Breaker Scheme B is selected, use Open Mains
Output instead.
Return delay Indicates that the set is on load, and the mains is available, during the return delay
timers.
Scheduled Run Active when the controller is requesting the set to run under control of the inbuilt
Scheduler.
Start Delay The controller is i n the start delay timer, after which the set wi ll be called to start.
System in Auto Mode When the controller is i n AUTO mode Inactive in any other mode.
System in Manual Mode When the controller is i n MANUAL mode Inactive in any other mode.
System in Prohibit return Mode Becomes active when the generator is on load and the mains supply is healthy but an
input configured to Manual Restore is active.
This can be used to signal to an operator that action is required before the set can
transfer back to the mains supply.
System in Test on load Mode When the controller is i n MANUAL mode Inactive in any other mode.
Waiting for generator

The controller has requested the generator to start and is waiting for it to become
available.
Waiting for Manual Restore

Becomes active when the generator is on load and the mains supply is healthy but an
input configured to Manual Restore is active.
This can be used to signal to an operator that action is required before the set can
transfer back to the mains supply.
Warming up

Active when the set is runni ng off load, during the warmi ng timer, before taking load.


DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

28
6.6 TIMERS

Many timers are associated with alarms. Where this occurs, the timer for the alarm is located on the same
page as the alarm setting. Timers not associated with an alarm are located on the timers page.
The timers page is subdivided into smaller sections. Select the required section with the mouse.



6.6.1 START TIMERS



Timer Description
Mains Transient Delay

Used to give a delay between the mai ns supply being measured out of limits, and acceptance
that the mai ns has failed. This can be used to prevent the generator starting caused by short
term events on the mai ns supply.
Start delay Used to give a delay before starti ng i n AUTO mode. This timer is activated upon a remote start
signal bei ng applied, or upon a start due to mai ns failure, scheduled run or any other automatic
start.
Typically this timer is applied to prevent starting upon fleeting remote start signals or short term
mains failures.
Warming up time The amount of time that the set wi ll run BEFORE bei ng allowed to take load. This is used to
warm the engine to prevent excessi ve wear.
Generator Fail Delay The 332 i nstructs the set to start and waits for the period of this timer for the set to become
available. If it is not available when the timer expires, the generator failure alarm is triggerred.
Elevator Delay Use to delay the elevator control output before and after load transfer takes place. See section
entitled Application for details of elevator control.


Click and drag to change the setting.
Timers increment in steps of 1 second up to
one minute, then in steps of 30 seconds up
to 30minutes, then in steps of 30 minutes
thereafter (where allowed by the limits of the
timer).
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 29
6.6.2 LOAD / STOPPING TIMERS



Timer Description
Transfer Time

The time between the generator load switch being opened and the mai ns load switch being
closed (or vice versa). Used to give time for the load switches to move to their correct
positions and to prevent the mechanical i nterlock from jammi ng.
This timer can also be used to give a dead time to ensure that any machinery stops fully after
removal of the supply, before applying the new supply to the equipment (for i nstance directly
driven AC motors).
Breaker close pulse The amount of time that Breaker Close Pulse signals will be present when the request to
close a breaker is given.
Breaker Trip pulse The amount of time that Breaker Open Pulse signals will be present when the request to open
a breaker is given.
Return delay A delay, used i n auto mode only, that allows for short term removal of the request to stop the
set before action is taken. This is usually used to ensure the set remains on load before
accepting that the start request has been removed.
Cooling time The amount of time that the set wi ll be made to run OFF LOAD before being stopped. This is
to allow the set to cool down and is particularly important for engi nes with turbo chargers.
Fail to stop delay If the set is called to stop and is still runni ng after the fail to stop delay, a Fail to Stop alarm is
generated.
Generator transient
delay
Used to delay the generator under/over volts/frequency alarms. Typically this is used to
prevent spurious shutdown alarms caused by large changes i n load levels.

6.6.3 MODULE TIMERS



Timer Description
LCD Page timer If the module is left unattended for the duration of the LCD Page Timer it will revert to show
the Status page.
LCD Scroll Timer The scroll time between parameters on a selected page

Click and drag to change the setting.
Timers increment in steps of 1second up
to one minute, then in steps of
30seconds up to 30minutes, then in steps
of 30minutes thereafter (where allowed
by the limits of the timer).

If you need to change the timer by a
small amount, try clicking with the
mouse to the side of the adjust handle
to the right (increase) or left (decrease).

Alternatively once youve selected the
timer, you can use the left (decrease) or
right (increase) keyboard keys.
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

30
6.7 GENERATOR

The generator page is subdivided into smaller sections.
Select the required section with the mouse.



6.7.1 GENERATOR OPTIONS







Select your AC
system. A schematic
is shown below with
connection details
from the alternator
to the DSE300
Series module.
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 31

6.7.2 GENERATOR ALARMS











Alarm IEEE designation
Generator Under voltage IEEE 37.2 - 27AC Undervoltage relay
Generator loading voltage The generator will not be permitted to take load until the loading voltage and loading
frequency have been reached.
Generator Under Frequency IEEE 37.2 -81 Frequency relay
Generator loading Frequency The generator will not be permitted to take load until the loading voltage and loading
frequency have been reached.

Click to enable or
disable the alarms.
The relevant values
below will appear
greyed out if the
alarm is disabled.
Click and drag to change the
setting.
Type the value
or click the up
and down
arrows to
change the
settings
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

32
6.8 LOAD CURRENT













Timer Description
Enable CT Support
Not available on DSE332 V1
= CTs are not fitted. The ATS module will not include Load Amps on the
instrumentation display.
= CTs are not fitted. The ATS module will display Load Amps.
CT Primary Primary rating of the Current Transformers
Full Load Rating This value should be set to the full load rating of the generator.



Click and drag to change the
setting.
Type the value
or click the up
and down
arrows to
change the
settings
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 33

6.9 MAINS

The mains page is subdivided into smaller sections.
Select the required section with the mouse.



6.9.1 MAINS OPTIONS



Timer Description
Immediate
Mains Dropout

= Upon mains failure, the mains load switch will be kept closed until the generator is up
to speed and volts.
= Upon mains failure, the mains load switch will be opened immediately, subject to the
setting of the mains transient timer.
AC System

These settings are used to detail the type of AC system to which the module is connected:
3 phase 4 wire, 1 phase 2 wire, 2 phase 3 wire L1-L2, 2 phase 3 wire L1-L3, 3 phase 3
wire, 3 phase 4 wire delta

This list is not exhaustive. DSE reserve the right to add to this list as part of our policy of
continual development

If three phase loads are
present, it is usually desirable
to set this parameter to to
enable Immediate Mains
Dropout.
This is read only for
information purposes. The AC
system is configured i n the
Generator Options page.
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

34

6.9.2 MAINS ALARMS





Alarm IEEE designation
Mains Under voltage IEEE 37.2 - 27AC Undervoltage relay
Mains Over voltage IEEE 37.2 - 59AC Overvoltage relay
Mains Under Frequency IEEE 37.2 -81 Frequency relay
Mains Over Frequency IEEE 37.2 -81 Frequency relay

Click and drag to change the
setting.
Type the value
or click the up
and down
arrows to
change the
settings
Click to enable or
disable the alarms.
The relevant values
below will appear
greyed out if the
alarm is disabled.
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 35
6.10 PLANT BATTERY






Alarm IEEE designation
Plant Battery Undervolts IEEE 37.2 -27 DC Undervoltage relay
Plant Battery Overvolts IEEE 37.2 -59 DC Overvoltage relay


Click and drag to change the
setting.
Type the value
or click the up
and down
arrows to
change the
settings
Click to enable or
disable the option.
The relevant values
below will appear
greyed out if the
alarm is disabled.
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

36

6.11 SCHEDULER

The Exercise Scheduler is used to give up to 16 scheduled runs. This run schedule is configurable to repeat
every 7 days (weekly) or every 28 days (monthly) . The run can be on load or off load.








Click to enable or
disable the option.
The relevant values
below will appear
greyed out if the
alarm is disabled.
Configure the
required start time
and run duration.
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 37



8 SCADA

SCADA stands for Supervisory Control And Data Acquisition and is provided both as a service tool and also
as a means of monitoring / controlling the generator set.
As a service tool, the SCADA pages is to check the operation of the controllers inputs and outputs as well as
checking the generators operating parameters.




When connection is made









The SCADA page is subdivided into smaller sections.
Select the required section with the mouse.



Click to connect to
the module
Click to close the
connection to the
module
The connected
modules firmware
revision number
DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

38
8.2 MIMIC

This screen provides a mimic of the control module and allows the operator to change the control mode of the
module.











Click the mimic buttons to
control the module remotely
Hint : Buttons may not operate if this has
been locked out by the Access security
feature of the Configuration Suite
Software.
Refer to your system supplier for details.

DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 39



8.3 LANGUAGES






Current language in
the module
Select new language.
DSE33x ATS shares
language files with the
DSE7000 series.
Click to send the
new language to the
module
During language upload, the
progress is shown. Total transfer
time is less than one minute.
During this process :

DO NOT DISCONNECT THE
USB LEAD

DO NOT TURN OFF YOUR PC

DO NOT DISCONNECT THE
MODULEs DC POWER
SUPPLY

DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

40
8.4 DIGITAL INPUTS











8.5 DIGITAL OUTPUTS












State of the input
(open or closed to
battery negative)
Shows if the input channel is active
or not.
State of the
output (open or
closed)
Shows if the output channel is active or not.
DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 41

8.6 MAINS

Shows the modules measurements of the mains supply.




8.7 GENERATOR


Shows the modules measurements of the generator supply.




DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

42

8.8 LOAD

Shows the modules measurements of the load.



8.9 PLANT BATTERY

Shows the measurement of the plant battery




8.10 ALARMS
Shows any present alarm conditions.



DSE300 Series ATS Configuration Suite
DSE300 Series configuration suite 057-106 ISSUE 2 AM 43
8.11 STATUS
Shows the modules current status.




8.12 EVENT LOG

Shows the contents of the modules event log.




DSE300 Series ATS Configuration Suite
DSE300 Series ATS Configuration Suite 057-106 ISSUE 2 AM

44
8.13 DATE AND TIME

Anda mungkin juga menyukai