Transformer, generator and motor protection


Data sheet
DSE_PD300_eng_AP
No part of this publication may be reproduced
by whatever means without the prior written
permission of Ingeteam Technology.
One of the main aims of Ingeteam Technology
lies in the continuous improvement of the
companys equipment and, therefore, the
information contained in this catalogue may
be modified without prior notification.
For further information, consult the
corresponding manual or contact us directly.

INDEX
Ingeteam Technology S.A.
DSE_PD300_eng III
MODEL CODE SELECTION ........................................................................................................... 4
FUNCTIONS TABLE ..................................................................................................................... 5
FUNCTIONAL DESCRIPTION AND CONFIGURATION ...................................................................... 6
General settings ........................................................................................................................................ 6
Protection settings .................................................................................................................................... 6
AUTOMATISM FUNCTIONS ........................................................................................................ 12
DATA ACQUISITION ................................................................................................................... 13
MEASUREMENTS ...................................................................................................................... 13
COMMUNICATION PROTOCOLS .................................................................................................. 14
KEYPAD/LOCAL DISPLAY ........................................................................................................... 15
TESTS ...................................................................................................................................... 15
TECHNICAL SPECIFICATIONS .................................................................................................... 16
ENVIRONMENTAL CONDITIONS ................................................................................................. 18
CONSTRUCTION FEATURES ...................................................................................................... 18
CONNECTION DIAGRAMS .......................................................................................................... 20


TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 4
MODEL CODE SELECTION

TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 5
FUNCTIONS TABLE

Note: X: Available function O: Optional function

PD300-2 PD300-3 PD300-G
Protection functions
Overexcitation (24) 5th harmonic or V/Hz 2 units. 5th harmonic 5th harmonic
Undervoltage (27) X X
Current unbalance (46) X X X
Thermal image (49) X X X
Instantaneous phase overcurrent (50) 2 units in each winding 2 units in each winding 2 units in each winding
Time phase overcurrent (51) 1 unit in each winding 1 unit in each winding 1 unit in each winding
Residual instantaneous overcurrent (50R) 2 units in each winding 2 units in each winding 2 units in each winding
Residual time overcurrent (51R) 1 unit in each winding 1 unit in each winding 1 unit in each winding
Instantaneous ground overcurrent (50G) 2 units in each winding 2 units in each winding
Time ground overcurrent (51G) 1 unit in each winding 1 unit in each winding
Breaker failure (50BF) X X X
Overvoltage (59) X X
Overfrequency (81M) 5 steps 5 steps
Underfrequency (81m) 5 steps 5 steps
Differential (87)
In percentage and
instantaneous
In percentage and
instantaneous
In percentage and
instantaneous
Restricted earth (87G) X X
Breaker monitoring X X X
Trip and closure circuit surveillance (74TC/CC) X X X
Power supply monitoring O O O
External power supply monitoring O O O
Temperature monitoring X X X

Automatisms and commands
Breaker and closure commands X X X
Programmable logic X X X
Breaker closure lock (86) X X X
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 6
FUNCTIONAL DESCRIPTION AND CONFIGURATION
GENERAL SETTINGS
Setting Minimum Maximum Step Remarks
Relay in operation YES/NO
Breaker number 5 alphanum. characters
PROTECTION SETTINGS
Differential protection (87)
Three-phase differential unit.
Numeric ratio and connection group correction.
Zero sequence component filter: Enables the elimination of the phase currents zero sequence component.
Adjustable differential current instantaneous trip.
2nd, 2nd + 4th and 5th harmonic restraint, adjustable (Not available for PD300-G).
Cross blocking (except in PD300-G).

General settings Minimum Maximum Step Remarks
Rated voltage winding 1(kV) 1 1000 0,1
Rated voltage winding 2(kV) 1 1000 0,1
Rated voltage winding 3(kV) 1 1000 0,1
C.T. ratio winding 1 1 10000 0,1
C.T. ratio winding 2 1 10000 0,1
C.T. ratio winding 3 1 10000 0,1
Connection type winding 1/2/3 Y/D/Z
Phase shift 1-2 0 11 1
Phase shift 1-3 0 11 1
Function 86 enabled YES/NO
Grounding 1 C.T. ratio 1 10000 0,1
Grounding 2 C.T. ratio 1 10000 0,1
VT ratio 1 10000 0,1
Maximum power capacity (MVA) 0,0 5000 0,1
Tap winding 1
0,5
0,1
100
20
0,01
0,01
In = 5A
In = 1A and PD300-G
Tap winding 2
0,5
0,1
100
20
0,01
0,01
In = 5A
In = 1A and PD300-G
Tap winding 3
0,5
0,1
100
20
0,01
0,01
In = 5A
In = 1A
Differential 2/3 windings
2wind.
/3wind.

Percentage charact. setting Minimum Maximum Step Remarks
Enabled YES/NO
Sensitivity (xTap) 0,15 2 0,01
Restraint current 1 (xTap) 0 2 0,01
Restraint current 2 (xTap) 0 20 0,01
1 (%) 5 100 1
2 (%) 5 200 1
Additional delay (s) 0 60 0,01
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 7

Instantaneous differential setting Minimum Maximum Step Remarks
Enabled YES/NO
Trip (xTap) for PD300-2 and PD300-3 1,0 20 0,01
Trip (xTap) for PD300-G 0,60 4,00 0,01
Additional delay (s) 0 60 0,01
Harmonic restraint setting (disabled for PD300-G) Minimum Maximum Step Remarks
2nd harmonic restraint enabled
NO / 2nd PHASE / 2nd GLOBAL/ 2nd+4th
PHASE / 2nd+4th GLOBAL
2nd harmonic restraint threshold (%) 5 100 1
Differential threshold (xTap) 0,15 1 0,01
5th harmonic restraint enabled NO / PHASE / GLOBAL
5th harmonic restraint threshold (%) 5 100 1
Differential threshold (xTap) 0,15 1 0,01

Restricted earth (87G) - Models PD300-2 and PD300-G
This function is applicable when one of the transformers windings is grounded. The function compares the residual
current with the current flowing through the grounded transformer. Should the difference between both currents, following
the application of the corresponding transformation ratios, exceed the set threshold, a trip signal is issued. The direction
is taken into account when allowing the trip.









Phase overcurrent protection (50/51) - All models
A back-up protection for external or internal transformer faults. In the event of such faults not being cleared by the
primary protections, the overcurrent protection acts. Serious damage to the transformer would be produced in the absence
of such protection. Each winding is equipped with two instantaneous levels and one timed level.
Time charactistic setting (6 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A)
0,1
0,02
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Curve type
Definite time (TF)
Inverse curve, very inverse, extremely
inverse
User curves
Dial
0,05
0,5
1,09
30,0
0,01
0,1
For IEC curves
For ANSI curves
Definite delay (s) 0,0 600,0 0,01
Instantaneous charactistic setting (low-level - 6 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A)
0,1
0,02
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Additional delay (s) 0,00 60,00 0,01
Setting

Minimum

Maximum

Step

Remarks

Enabled


YES/NO

Pick up (A)

0,25
0,05
20
4
0,01
0,01
In = 5 A
In = 1 A and Generator and motor

Additional time (s)

0 60 0,01
Winding comparison Wind. 1, Wind. 2 or Autotransformer
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 8

Instantaneous characteristic setting (high-level - -6 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A)
0,1
0,02
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Additional delay (s) 0,00 60,00 0,01
Residual overcurrent protection (50/51R) - All models
An overcurrent function that is applied to the directional sum of the three phases in order to detect earth faults. It is
equipped with independent units for each of the windings.
Time characteristic settings (6 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A)
0,2
0,05
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Curve type
Definite time (TF)
Inverse curve, very inverse, extremely
inverse
User curves
Dial
0,05
0,5
1,09
30,0
0,01
0,1
For IEC curves
For ANSI curves
Definite delay (s) 0,0 600,0 0,01
Instantaneous characteristic settings (low-level -6
groups)
Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A)
0,2
0,05
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Additional delay (s) 0,0 60,00 0,01
Instantaneous characteristic settings (high-level -6
groups)
Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A)
0,2
0,05
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Additional delay (s) 0,0 60,00 0,01

Current unbalance protection (46) - All models
Protects the installation against current unbalances that occur as a consequence of anomalies in the power system, or
against unbalanced loads. It is equipped with independent units for each of the windings.
Time charactieristic setting (6 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A)
0,2
0,05
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Curve type
Definite time (TF)
Inverse curve, very inverse, extremely
inverse
User curves
Dial
0,05
0,5
1,09
30,0
0,01
0,1
For IEC curves
For ANSI curves
Definite time (s) 0,0 600,0 0,01
Instantaneous charactistic setting (6 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A)
0,2
0,05
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Additional delay (s) 0,0 60,00 0,01

TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 9

Earth overcurrent protection (50/51G) - Models PD300-2 and PD300-G
Is applied to the power transformers grounding in order to detect earth faults. It may also be applied as a tank protection.
Timed charactistic settings (6 groups) Minimum Maximum Step Remarks
Enabled YES/NO/Pickup/YES+Drop-out
Pick up (A)
0,1
0,02
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Curve type
Definite time (TF)
Inverse curve, very inverse, extremely inverse
User curves
Dial
0,05
0,5
1,09
30,0
0,01
0,1
For IEC curves
For ANSI curves
Definite time (s) 0,0 600,0 0,01 Delay if TF type
Instantaneous charactistic setting Low-level (6 groups) Minimum Maximum Step Remarks
Enabled YES/NO/ Pickup
Pick up (A)
0,1
0,02
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Additional delay (s) 0,00 60,00 0,01
High level instantaneous characteristic settings (6 groups) Minimum Maximum Step Remarks
Enabled YES/NO/ Pickup
Pick up (A)
0,1
0,02
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Additional delay (s) 0,00 60,00 0,01

Overvoltage protection (59) - Models PD300-2 and PD300-G
This function protects the transformer against overvoltages, issuing a trip command when the voltage exceeds the set
value during a set period.
Time charactistic setting (6 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (V) 10 200 0,1
Curve type
Definite time (TF)
Inverse curve, very inverse, extremely
inverse
User curves
Dial
0,05
0,5
1,09
30,0
0,01
0,1
For IEC curves
For ANSI curves
Definite time (s) 0,0 600,0 0,01
Instantaneous charactic setting (6 groups) Minimum Minimum Step Remarks
Enabled YES/NO
Pick up (V) 10 200 0,1
Additional delay (s) 0,00 60,00 0,01

TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 10
Undervoltage protection (27) - Models PD300-2 and PD300-G
Undervoltage may occur in the system during faults or similar situations.
Time charactistic settings (6 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A) 10 200 0,1
Curve type
Definite time (TF)
Inverse curve, very
inverse, extremely
inverse
User curves
Dial
0,05
0,5
1,09
30,0
0,01
0,1
For IEC curves
For ANSI curves
Definite time (s) 0,0 600,0 0,01
Instantaneous charactistic setting (6 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (V) 10 200 0,1
Additional delay (s) 0,00 60,00 0,01

Overexcitation protection (24) - All models
This function prevents the transformers from working at a flux density higher to that for which they have been designed,
thus avoiding overheating and the subsequent damage to the transformer resulting from overexcitation. It can be detected
through 5
th
harmonic current level or through the V/f ratio.

5
th
harmonic setting Minimum Maximum Step Remarks
Enabled YES/NO
Minimum operating current
0,50
0,1
10
2
0,01
0,01
In = 5 A
In = 1A and PD300-G
Pick-up (%) 5 100 1
Additional delay (sec) 0 600 0,01
Setting for V/f (not available for PD300-3) Minimum Maximum Step Remarks
Enabled YES/NO
Minimum monitoring voltage (V) 50 150 1
Pick up (V/Hz) 1,00 4,00 0,01
Curve type
Definite time (TF)
Inverse curve, very inverse, extremely
inverse
User curves
Dial
0,05
0,5
1,09
30,0
0,01
0,1
For IEC curves
For ANSI curves
Definite time (s) 0 600 0,01
Frequency protection (81M/m) - Models PD300-2 and PD300-G
The frequency unit provides protection against overexcitation. It may also be employed in subfrequency load-shedding
schemes, assisting operation in the event of network instability, for which there are 5 steps.
The settings, which are independent for each step, are individualized for each step (6 groups):
Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (Hz) 45 65 0,01
Additional delay (s) 0 600,00 0,01
Type Maximum/Minimum

TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 11
The common settings for all steps are as follows:
Setting Minimum Maximum Step Remarks
Minimum monitoring voltage (V) 40 200 1
N of frequency pick-up cycles 3 15 1
Thermal image (49) All models
Protects the unit against thermal overloads by calculating the temperature in accordance with the protected units current
and recent load conditions.
Setting Minimum Maximum Step Remarks
Enabled YES/NO
Heating time constant (min) 3 60 1
Cooling time constant (min) 3 180 1
Alarm threshold (%) 60 100 1
Rated current (A)
0,2
0,04
0,04
10,0
2
10,0
0,01
0,01
0,01
In = 5A
In = 1A
PD300-G

Breaker failure protection (50BFI) - All models
Verifies the correct operation of a breaker when clearing a fault. In case of an operation failure, the protection trips the
adjacent breakers involved in the isolation of the area in fault.
Setting Minimum Maximum Step Remarks
Enabled YES/NO
Phase restoration (A)
0,1
0,02
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Neutral restoration (A)
0,1
0,02
160,0
32,0
0,01
0,01
In = 5 A
In = 1A and PD300-G
Definite retrip time (sec) 0,05 60,00 0,01
Definite trip time BF (sec) 0,05 60,00 0,01
Breaker monitoring - All models
A signal is generated when, following a trip, the kI2 counter exceeds the programmed threshold. The counter may be
reset to the initial value by means of a command.
Setting Minimum Maximum Step Remarks
kI2 alarm threshold 0 65534 1
Initial kI2 value 0 65534 1
Operating logic - All models
Verifies the correct operation of the breaker.
Setting Minimum Maximum Step Remarks
Trip contact sealing YES/NO
Closure sealing YES/NO
Breaker opening failure timing (s) 0,02 5,0 0,01
Breaker closure failure timing (s) 0,02 5,0 0,01
Coil monitoring - All models
The monitoring of the trip and closure circuits allows to check the continuity of the trip and closure coil circuits to be
monitored, both when the breaker is closed and when it is open.
Setting Minimum Maximum Step Remarks
Trip circuit monitoring enabled YES/NO
Closure circuit monitoring enabled YES/NO
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 12
AUTOMATISM FUNCTIONS
External power supply monitoring
Only available in models equipped with the Battery voltage measurement option.
Setting Minimum Maximum Step Remarks
Enabled YES/NO
Minimum threshold (V) 20 220 1
Maximum threshold (V) 24 280 1

Temperature monitoring
Monitors the units temperature and generates an alarm when the temperature exceeds the set range.
Setting Minimum Maximum Step Remarks
Enabled YES/NO
Minimum threshold () -40 0 1
Maximum threshold () 50 100 1

TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 13
DATA ACQUISITION
Type Description Non-volatile memory capacity
Events
Date and time: Day/month/year hour/min/sec. m.sec.
Description of the event
Currents of each winding per phase, differential currents per phase, earth currents
(PD300-2 and PD300-G) and voltage (PD300-2 and PD300-G)
400 events
Faults
Date and time: day/month/year hour/min/sec. m.sec
Description of the fault
Detail:
Available units
Units tripped during the fault
Units picked-up during the fault
Fault start date and -time
Trip date and time
Fault end date and time
Current opened by breaker
Setting group active during the fault
Fault and trip type
Differential current
Restraint current
Fault and pre-fault phase current
Neutral current
Fault and pre-fault voltage (PD300-2 and PD300-G)
Tripped phases
Differential and restraint currents of each phase at the time of the trip
Phase and neutral currents at the time of the trip
Fault start and finish date and time
20 faults
Measurement historical
reports
Date and time recording
Each recording contains the maximum and minimum average currents of each
winding
4000 recordings
Statistical data
kl2 sum (kA opened per breaker, squared)
Opening counters for each breaker
Trip counters for each breaker

Oscillograph data recorder
Up to 9 analog channels, the number of samples per analogical channel cycle is 32
Up to 32 digital channels
1200 cycles. The number of cycles
per disturbance can be programmed



MEASUREMENTS
Phase current for each winding (A)
Average current per winding (A)
Differential current (A) (1st, 2nd and 5th harmonic)
Current maximeter (A)
Ground current (A) (PD300-2 and PD300-G)
Voltage (kV) (PD300-2 and PD300-G)
Frequency (Hz) (PD300-2 and PD300-G)
Device temperature measurement (optional)
DC power supply voltage measurement (optional)

TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 14
COMMUNICATION PROTOCOLS
Front serial port RS232
PROCOME
Equipped with one or two serial outputs, or one serial output and one Ethernet output.
COM-1 rear serial port (RS232, RS485, G.F.O., P.F.O.)
PROCOME
COM-2 rear serial port (RS232, RS485, G.F.O., P.F.O)
PROCOME
DNP3.0
MODBUS
IEC 870-5-101 (except with RS485)
IEC 870-5-103
Ethernet communication (only for models with Ethernet port)
PROCOME encapsulated
Peer to peer communications
IEC 61850
IEC 61850 communication options
Single RJ45 Ethernet
Single FOC Ethernet
Double GFO or RJ45 Ethernet redundancy
These IEC 61850 models (R-type box) for serial communication include:
1 RS232 port Procome protocolCOM-6
1 GFO (unique option in case of double GFO or RJ45 Ethernet) or RS485 protocol DNP3.0.COM-2
For more information of redundancy see DSS_IEC61850 document.



















TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 15
KEYPAD/LOCAL DISPLAY















TESTS

16-KEY KEYBOARD
LCD 2 LINES WITH
16 CHARACTERS
7 RED LEDS AND 1
GREEN/RED
RS232C connector
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 16

TECHNICAL SPECIFICATIONS
Auxiliary power supply
24-48 Vdc
Range 18-60 Vdc
Ripple 20 % over the rated value
Burden 8W min/ 18W max
110-125-220 Vdc
Range 86-280Vdc
Ripple 20% over the rated value
Burden 8W min/ 18W max
Current circuits
Thermal capacity for phase/neutral I
Continuous 20 A
Short term (1 s.) 500 A
Very short term ( cycles) 1250 A
Burden at I = 5 A <0.2 VA
Burden at In= 1A <0.02 VA
Voltage circuits (PD300-2)
Thermal capacity
Permanent 260 V
Burden at 63.5 V 0.015 VA
Burden at 100 V 0.03 VA
Closed terminals for voltage and current inputs (optional)
Terminal pitch 9.5 mm
Digital inputs and outputs without extension board
Number of inputs 8
Number of outputs 7
Digital inputs and outputs with extension board 1
Number of digital inputs 17
Number of digital outputs 14
Optoisolated digital inputs
Range 18-160 Vdc
Inactive below 13 Vdc
Range 86-160 Vdc
Inactive below 60 Vdc
Burden < 3mA
Output contacts
Trip relays 1 to 6 (and 8 to 13)
Carry (permanent) 5 A at 25 C
Make and carry for 0.5 s 30 A
Breaking capacity (L/R=40 ms)
- 220 Vdc 0.2 A
- 125 Vdc 0.5 A
- 48 Vdc 0.5 A
Breaking capacity (resistive)
- 220 Vdc 0.4 A
- 125 Vdc 1 A
- 48 Vdc 3 A
Performance time 8 ms.
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 17

Auxiliary relay 7 (and 14)
Carry (permanent) 5 A at 25 C
Make and carry for 0.5 s 30 A
Breaking capacity (L/R=40 ms)
- 220 Vdc 0.15 A
- 125 Vdc 0.3 A
- 48 Vdc 0.5 A
Breaking capacity (resistive)
- 220 Vdc 0.2 A
- 125 Vdc 0.4 A
- 48 Vdc 0.2 A
Performance time 8 ms.
Frequency
Programmable system frequency 50 or 60 Hz
Operational range Fn 5 Hz
Communications ports
Front communication port
RS232C connector DTE 9 pin D type female
Cable length 3 m maximum
Baud rate 600-38400 bps
Insulation No
Types of rear communication ports (COM-1 and COM-2)
RS232
- RS232C connector DTE 9 pin D type female
- Cable type Shielded
- Cable length 15 m max.
- Insulation 500V
RS485
- RS485 connector DTE 9 pin D type female
- Cable type Shielded twisted pair
- Cable length 1,000 m max.
- Insulation 500V
G.F.O.
- Connector ST
- Wavelength 820nm
- Attenuation 8 db with 62.5 /125 m glass fibre
- Glass fibre optic Multimode 62.5 /125 m
- Maximum distance 1.5 Km
P.F.O.
- Connector HP standard
- Wavelength 660 nm
- Attenuation
24.7 db with 1mm plastic cable
22 db with 200 m silica cable
- Maximum distance
115 m with 1mm plastic cable
1.9 Km with 200 m silica cable
Ethernet RJ45
Connector RJ45 Female
Cable type Shielded
Cable length 100 m max.
Insulation 500V
Baud rate 10/100 Mbps
G.F.O. Ethernet
Connector ST
Wavelength 1300nm
Permitted attenuation 8 db with 62.5 /125 m glass fibre
Multimode glass optical fibre 62.5 /125 m
Maximum distance 1.5 Km
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 18

IRIG-B port
Input Demodulated
Input level TTL
Cable type 2-wire, shielded
Insulation 500 V
Maximum distance 1.5 Km
Accuracy
Accuracy Class 0.5 for V, I and P (up to 120% nominal)
Accuracy in the protected range 3%
Curve operation accuracy 5% or 30ms (the highest of the two values)
Battery voltage monitoring (optional)
24-48 Vdc
Range 18 to 60 Vdc
110-125-220 Vdc
Range 86 to 280 Vdc
Mechanical characteristics
Weight 2.8 Kg
Approx. weight with packaging and documentation 3.8 Kg
Front IP IP40
Optional front IP IP54

ENVIRONMENTAL CONDITIONS
Operating temperature -20C to 75C
Storage temperature -40C to 85C
Relative humidity Up to 95% without condensation

CONSTRUCTION FEATURES


PD300-H model dimensions


TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 19



PD300-V model dimensions









IEC61850 and TCP model dimensions
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 20
CONNECTION DIAGRAMS

2 winding, pin terminal models



TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 21

2 windings, closed-terminal models
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 22

3 windings, pin-terminal models
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 23

3 windings, closed-terminal models
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 24


Generator, pin-terminal models
TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 25

Generator, closed-terminal models

TRANSFORMER, GENERATOR AND MOTOR PROTECTION
Ingeteam Technology S.A.
DSE_PD300_eng 26

Ingeteam Technology, S.A.
www.ingeteam.com
Parque Tecnolgico de Bizkaia Edificio 110
48170 Zamudio, Bizkaia, Spain
Tel + 34 944 039 600
Fax +34 944 039 679