The document is a data sheet for the PD300 transformer, generator and motor protection relay from Ingeteam Technology. It provides information on the relay's model code selection, available protection and automation functions, measurements, communication protocols, and technical specifications. The functional description section outlines the settings and characteristics for the relay's differential protection, phase overcurrent protection, and residual overcurrent protection functions.
The document is a data sheet for the PD300 transformer, generator and motor protection relay from Ingeteam Technology. It provides information on the relay's model code selection, available protection and automation functions, measurements, communication protocols, and technical specifications. The functional description section outlines the settings and characteristics for the relay's differential protection, phase overcurrent protection, and residual overcurrent protection functions.
The document is a data sheet for the PD300 transformer, generator and motor protection relay from Ingeteam Technology. It provides information on the relay's model code selection, available protection and automation functions, measurements, communication protocols, and technical specifications. The functional description section outlines the settings and characteristics for the relay's differential protection, phase overcurrent protection, and residual overcurrent protection functions.
Data sheet DSE_PD300_eng_AP No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam Technology. One of the main aims of Ingeteam Technology lies in the continuous improvement of the companys equipment and, therefore, the information contained in this catalogue may be modified without prior notification. For further information, consult the corresponding manual or contact us directly.
INDEX Ingeteam Technology S.A. DSE_PD300_eng III MODEL CODE SELECTION ........................................................................................................... 4 FUNCTIONS TABLE ..................................................................................................................... 5 FUNCTIONAL DESCRIPTION AND CONFIGURATION ...................................................................... 6 General settings ........................................................................................................................................ 6 Protection settings .................................................................................................................................... 6 AUTOMATISM FUNCTIONS ........................................................................................................ 12 DATA ACQUISITION ................................................................................................................... 13 MEASUREMENTS ...................................................................................................................... 13 COMMUNICATION PROTOCOLS .................................................................................................. 14 KEYPAD/LOCAL DISPLAY ........................................................................................................... 15 TESTS ...................................................................................................................................... 15 TECHNICAL SPECIFICATIONS .................................................................................................... 16 ENVIRONMENTAL CONDITIONS ................................................................................................. 18 CONSTRUCTION FEATURES ...................................................................................................... 18 CONNECTION DIAGRAMS .......................................................................................................... 20
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 4 MODEL CODE SELECTION
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 5 FUNCTIONS TABLE
Note: X: Available function O: Optional function
PD300-2 PD300-3 PD300-G Protection functions Overexcitation (24) 5th harmonic or V/Hz 2 units. 5th harmonic 5th harmonic Undervoltage (27) X X Current unbalance (46) X X X Thermal image (49) X X X Instantaneous phase overcurrent (50) 2 units in each winding 2 units in each winding 2 units in each winding Time phase overcurrent (51) 1 unit in each winding 1 unit in each winding 1 unit in each winding Residual instantaneous overcurrent (50R) 2 units in each winding 2 units in each winding 2 units in each winding Residual time overcurrent (51R) 1 unit in each winding 1 unit in each winding 1 unit in each winding Instantaneous ground overcurrent (50G) 2 units in each winding 2 units in each winding Time ground overcurrent (51G) 1 unit in each winding 1 unit in each winding Breaker failure (50BF) X X X Overvoltage (59) X X Overfrequency (81M) 5 steps 5 steps Underfrequency (81m) 5 steps 5 steps Differential (87) In percentage and instantaneous In percentage and instantaneous In percentage and instantaneous Restricted earth (87G) X X Breaker monitoring X X X Trip and closure circuit surveillance (74TC/CC) X X X Power supply monitoring O O O External power supply monitoring O O O Temperature monitoring X X X
Automatisms and commands Breaker and closure commands X X X Programmable logic X X X Breaker closure lock (86) X X X TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 6 FUNCTIONAL DESCRIPTION AND CONFIGURATION GENERAL SETTINGS Setting Minimum Maximum Step Remarks Relay in operation YES/NO Breaker number 5 alphanum. characters PROTECTION SETTINGS Differential protection (87) Three-phase differential unit. Numeric ratio and connection group correction. Zero sequence component filter: Enables the elimination of the phase currents zero sequence component. Adjustable differential current instantaneous trip. 2nd, 2nd + 4th and 5th harmonic restraint, adjustable (Not available for PD300-G). Cross blocking (except in PD300-G).
General settings Minimum Maximum Step Remarks Rated voltage winding 1(kV) 1 1000 0,1 Rated voltage winding 2(kV) 1 1000 0,1 Rated voltage winding 3(kV) 1 1000 0,1 C.T. ratio winding 1 1 10000 0,1 C.T. ratio winding 2 1 10000 0,1 C.T. ratio winding 3 1 10000 0,1 Connection type winding 1/2/3 Y/D/Z Phase shift 1-2 0 11 1 Phase shift 1-3 0 11 1 Function 86 enabled YES/NO Grounding 1 C.T. ratio 1 10000 0,1 Grounding 2 C.T. ratio 1 10000 0,1 VT ratio 1 10000 0,1 Maximum power capacity (MVA) 0,0 5000 0,1 Tap winding 1 0,5 0,1 100 20 0,01 0,01 In = 5A In = 1A and PD300-G Tap winding 2 0,5 0,1 100 20 0,01 0,01 In = 5A In = 1A and PD300-G Tap winding 3 0,5 0,1 100 20 0,01 0,01 In = 5A In = 1A Differential 2/3 windings 2wind. /3wind.
Percentage charact. setting Minimum Maximum Step Remarks Enabled YES/NO Sensitivity (xTap) 0,15 2 0,01 Restraint current 1 (xTap) 0 2 0,01 Restraint current 2 (xTap) 0 20 0,01 1 (%) 5 100 1 2 (%) 5 200 1 Additional delay (s) 0 60 0,01 TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 7
Instantaneous differential setting Minimum Maximum Step Remarks Enabled YES/NO Trip (xTap) for PD300-2 and PD300-3 1,0 20 0,01 Trip (xTap) for PD300-G 0,60 4,00 0,01 Additional delay (s) 0 60 0,01 Harmonic restraint setting (disabled for PD300-G) Minimum Maximum Step Remarks 2nd harmonic restraint enabled NO / 2nd PHASE / 2nd GLOBAL/ 2nd+4th PHASE / 2nd+4th GLOBAL 2nd harmonic restraint threshold (%) 5 100 1 Differential threshold (xTap) 0,15 1 0,01 5th harmonic restraint enabled NO / PHASE / GLOBAL 5th harmonic restraint threshold (%) 5 100 1 Differential threshold (xTap) 0,15 1 0,01
Restricted earth (87G) - Models PD300-2 and PD300-G This function is applicable when one of the transformers windings is grounded. The function compares the residual current with the current flowing through the grounded transformer. Should the difference between both currents, following the application of the corresponding transformation ratios, exceed the set threshold, a trip signal is issued. The direction is taken into account when allowing the trip.
Phase overcurrent protection (50/51) - All models A back-up protection for external or internal transformer faults. In the event of such faults not being cleared by the primary protections, the overcurrent protection acts. Serious damage to the transformer would be produced in the absence of such protection. Each winding is equipped with two instantaneous levels and one timed level. Time charactistic setting (6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (A) 0,1 0,02 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Curve type Definite time (TF) Inverse curve, very inverse, extremely inverse User curves Dial 0,05 0,5 1,09 30,0 0,01 0,1 For IEC curves For ANSI curves Definite delay (s) 0,0 600,0 0,01 Instantaneous charactistic setting (low-level - 6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (A) 0,1 0,02 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Additional delay (s) 0,00 60,00 0,01 Setting
Minimum
Maximum
Step
Remarks
Enabled
YES/NO
Pick up (A)
0,25 0,05 20 4 0,01 0,01 In = 5 A In = 1 A and Generator and motor
Additional time (s)
0 60 0,01 Winding comparison Wind. 1, Wind. 2 or Autotransformer TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 8
Instantaneous characteristic setting (high-level - -6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (A) 0,1 0,02 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Additional delay (s) 0,00 60,00 0,01 Residual overcurrent protection (50/51R) - All models An overcurrent function that is applied to the directional sum of the three phases in order to detect earth faults. It is equipped with independent units for each of the windings. Time characteristic settings (6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (A) 0,2 0,05 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Curve type Definite time (TF) Inverse curve, very inverse, extremely inverse User curves Dial 0,05 0,5 1,09 30,0 0,01 0,1 For IEC curves For ANSI curves Definite delay (s) 0,0 600,0 0,01 Instantaneous characteristic settings (low-level -6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (A) 0,2 0,05 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Additional delay (s) 0,0 60,00 0,01 Instantaneous characteristic settings (high-level -6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (A) 0,2 0,05 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Additional delay (s) 0,0 60,00 0,01
Current unbalance protection (46) - All models Protects the installation against current unbalances that occur as a consequence of anomalies in the power system, or against unbalanced loads. It is equipped with independent units for each of the windings. Time charactieristic setting (6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (A) 0,2 0,05 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Curve type Definite time (TF) Inverse curve, very inverse, extremely inverse User curves Dial 0,05 0,5 1,09 30,0 0,01 0,1 For IEC curves For ANSI curves Definite time (s) 0,0 600,0 0,01 Instantaneous charactistic setting (6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (A) 0,2 0,05 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Additional delay (s) 0,0 60,00 0,01
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 9
Earth overcurrent protection (50/51G) - Models PD300-2 and PD300-G Is applied to the power transformers grounding in order to detect earth faults. It may also be applied as a tank protection. Timed charactistic settings (6 groups) Minimum Maximum Step Remarks Enabled YES/NO/Pickup/YES+Drop-out Pick up (A) 0,1 0,02 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Curve type Definite time (TF) Inverse curve, very inverse, extremely inverse User curves Dial 0,05 0,5 1,09 30,0 0,01 0,1 For IEC curves For ANSI curves Definite time (s) 0,0 600,0 0,01 Delay if TF type Instantaneous charactistic setting Low-level (6 groups) Minimum Maximum Step Remarks Enabled YES/NO/ Pickup Pick up (A) 0,1 0,02 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Additional delay (s) 0,00 60,00 0,01 High level instantaneous characteristic settings (6 groups) Minimum Maximum Step Remarks Enabled YES/NO/ Pickup Pick up (A) 0,1 0,02 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Additional delay (s) 0,00 60,00 0,01
Overvoltage protection (59) - Models PD300-2 and PD300-G This function protects the transformer against overvoltages, issuing a trip command when the voltage exceeds the set value during a set period. Time charactistic setting (6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (V) 10 200 0,1 Curve type Definite time (TF) Inverse curve, very inverse, extremely inverse User curves Dial 0,05 0,5 1,09 30,0 0,01 0,1 For IEC curves For ANSI curves Definite time (s) 0,0 600,0 0,01 Instantaneous charactic setting (6 groups) Minimum Minimum Step Remarks Enabled YES/NO Pick up (V) 10 200 0,1 Additional delay (s) 0,00 60,00 0,01
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 10 Undervoltage protection (27) - Models PD300-2 and PD300-G Undervoltage may occur in the system during faults or similar situations. Time charactistic settings (6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (A) 10 200 0,1 Curve type Definite time (TF) Inverse curve, very inverse, extremely inverse User curves Dial 0,05 0,5 1,09 30,0 0,01 0,1 For IEC curves For ANSI curves Definite time (s) 0,0 600,0 0,01 Instantaneous charactistic setting (6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (V) 10 200 0,1 Additional delay (s) 0,00 60,00 0,01
Overexcitation protection (24) - All models This function prevents the transformers from working at a flux density higher to that for which they have been designed, thus avoiding overheating and the subsequent damage to the transformer resulting from overexcitation. It can be detected through 5 th harmonic current level or through the V/f ratio.
5 th harmonic setting Minimum Maximum Step Remarks Enabled YES/NO Minimum operating current 0,50 0,1 10 2 0,01 0,01 In = 5 A In = 1A and PD300-G Pick-up (%) 5 100 1 Additional delay (sec) 0 600 0,01 Setting for V/f (not available for PD300-3) Minimum Maximum Step Remarks Enabled YES/NO Minimum monitoring voltage (V) 50 150 1 Pick up (V/Hz) 1,00 4,00 0,01 Curve type Definite time (TF) Inverse curve, very inverse, extremely inverse User curves Dial 0,05 0,5 1,09 30,0 0,01 0,1 For IEC curves For ANSI curves Definite time (s) 0 600 0,01 Frequency protection (81M/m) - Models PD300-2 and PD300-G The frequency unit provides protection against overexcitation. It may also be employed in subfrequency load-shedding schemes, assisting operation in the event of network instability, for which there are 5 steps. The settings, which are independent for each step, are individualized for each step (6 groups): Minimum Maximum Step Remarks Enabled YES/NO Pick up (Hz) 45 65 0,01 Additional delay (s) 0 600,00 0,01 Type Maximum/Minimum
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 11 The common settings for all steps are as follows: Setting Minimum Maximum Step Remarks Minimum monitoring voltage (V) 40 200 1 N of frequency pick-up cycles 3 15 1 Thermal image (49) All models Protects the unit against thermal overloads by calculating the temperature in accordance with the protected units current and recent load conditions. Setting Minimum Maximum Step Remarks Enabled YES/NO Heating time constant (min) 3 60 1 Cooling time constant (min) 3 180 1 Alarm threshold (%) 60 100 1 Rated current (A) 0,2 0,04 0,04 10,0 2 10,0 0,01 0,01 0,01 In = 5A In = 1A PD300-G
Breaker failure protection (50BFI) - All models Verifies the correct operation of a breaker when clearing a fault. In case of an operation failure, the protection trips the adjacent breakers involved in the isolation of the area in fault. Setting Minimum Maximum Step Remarks Enabled YES/NO Phase restoration (A) 0,1 0,02 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Neutral restoration (A) 0,1 0,02 160,0 32,0 0,01 0,01 In = 5 A In = 1A and PD300-G Definite retrip time (sec) 0,05 60,00 0,01 Definite trip time BF (sec) 0,05 60,00 0,01 Breaker monitoring - All models A signal is generated when, following a trip, the kI2 counter exceeds the programmed threshold. The counter may be reset to the initial value by means of a command. Setting Minimum Maximum Step Remarks kI2 alarm threshold 0 65534 1 Initial kI2 value 0 65534 1 Operating logic - All models Verifies the correct operation of the breaker. Setting Minimum Maximum Step Remarks Trip contact sealing YES/NO Closure sealing YES/NO Breaker opening failure timing (s) 0,02 5,0 0,01 Breaker closure failure timing (s) 0,02 5,0 0,01 Coil monitoring - All models The monitoring of the trip and closure circuits allows to check the continuity of the trip and closure coil circuits to be monitored, both when the breaker is closed and when it is open. Setting Minimum Maximum Step Remarks Trip circuit monitoring enabled YES/NO Closure circuit monitoring enabled YES/NO TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 12 AUTOMATISM FUNCTIONS External power supply monitoring Only available in models equipped with the Battery voltage measurement option. Setting Minimum Maximum Step Remarks Enabled YES/NO Minimum threshold (V) 20 220 1 Maximum threshold (V) 24 280 1
Temperature monitoring Monitors the units temperature and generates an alarm when the temperature exceeds the set range. Setting Minimum Maximum Step Remarks Enabled YES/NO Minimum threshold () -40 0 1 Maximum threshold () 50 100 1
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 13 DATA ACQUISITION Type Description Non-volatile memory capacity Events Date and time: Day/month/year hour/min/sec. m.sec. Description of the event Currents of each winding per phase, differential currents per phase, earth currents (PD300-2 and PD300-G) and voltage (PD300-2 and PD300-G) 400 events Faults Date and time: day/month/year hour/min/sec. m.sec Description of the fault Detail: Available units Units tripped during the fault Units picked-up during the fault Fault start date and -time Trip date and time Fault end date and time Current opened by breaker Setting group active during the fault Fault and trip type Differential current Restraint current Fault and pre-fault phase current Neutral current Fault and pre-fault voltage (PD300-2 and PD300-G) Tripped phases Differential and restraint currents of each phase at the time of the trip Phase and neutral currents at the time of the trip Fault start and finish date and time 20 faults Measurement historical reports Date and time recording Each recording contains the maximum and minimum average currents of each winding 4000 recordings Statistical data kl2 sum (kA opened per breaker, squared) Opening counters for each breaker Trip counters for each breaker
Oscillograph data recorder Up to 9 analog channels, the number of samples per analogical channel cycle is 32 Up to 32 digital channels 1200 cycles. The number of cycles per disturbance can be programmed
MEASUREMENTS Phase current for each winding (A) Average current per winding (A) Differential current (A) (1st, 2nd and 5th harmonic) Current maximeter (A) Ground current (A) (PD300-2 and PD300-G) Voltage (kV) (PD300-2 and PD300-G) Frequency (Hz) (PD300-2 and PD300-G) Device temperature measurement (optional) DC power supply voltage measurement (optional)
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 14 COMMUNICATION PROTOCOLS Front serial port RS232 PROCOME Equipped with one or two serial outputs, or one serial output and one Ethernet output. COM-1 rear serial port (RS232, RS485, G.F.O., P.F.O.) PROCOME COM-2 rear serial port (RS232, RS485, G.F.O., P.F.O) PROCOME DNP3.0 MODBUS IEC 870-5-101 (except with RS485) IEC 870-5-103 Ethernet communication (only for models with Ethernet port) PROCOME encapsulated Peer to peer communications IEC 61850 IEC 61850 communication options Single RJ45 Ethernet Single FOC Ethernet Double GFO or RJ45 Ethernet redundancy These IEC 61850 models (R-type box) for serial communication include: 1 RS232 port Procome protocolCOM-6 1 GFO (unique option in case of double GFO or RJ45 Ethernet) or RS485 protocol DNP3.0.COM-2 For more information of redundancy see DSS_IEC61850 document.
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 15 KEYPAD/LOCAL DISPLAY
TESTS
16-KEY KEYBOARD LCD 2 LINES WITH 16 CHARACTERS 7 RED LEDS AND 1 GREEN/RED RS232C connector TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 16
TECHNICAL SPECIFICATIONS Auxiliary power supply 24-48 Vdc Range 18-60 Vdc Ripple 20 % over the rated value Burden 8W min/ 18W max 110-125-220 Vdc Range 86-280Vdc Ripple 20% over the rated value Burden 8W min/ 18W max Current circuits Thermal capacity for phase/neutral I Continuous 20 A Short term (1 s.) 500 A Very short term ( cycles) 1250 A Burden at I = 5 A <0.2 VA Burden at In= 1A <0.02 VA Voltage circuits (PD300-2) Thermal capacity Permanent 260 V Burden at 63.5 V 0.015 VA Burden at 100 V 0.03 VA Closed terminals for voltage and current inputs (optional) Terminal pitch 9.5 mm Digital inputs and outputs without extension board Number of inputs 8 Number of outputs 7 Digital inputs and outputs with extension board 1 Number of digital inputs 17 Number of digital outputs 14 Optoisolated digital inputs Range 18-160 Vdc Inactive below 13 Vdc Range 86-160 Vdc Inactive below 60 Vdc Burden < 3mA Output contacts Trip relays 1 to 6 (and 8 to 13) Carry (permanent) 5 A at 25 C Make and carry for 0.5 s 30 A Breaking capacity (L/R=40 ms) - 220 Vdc 0.2 A - 125 Vdc 0.5 A - 48 Vdc 0.5 A Breaking capacity (resistive) - 220 Vdc 0.4 A - 125 Vdc 1 A - 48 Vdc 3 A Performance time 8 ms. TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 17
Auxiliary relay 7 (and 14) Carry (permanent) 5 A at 25 C Make and carry for 0.5 s 30 A Breaking capacity (L/R=40 ms) - 220 Vdc 0.15 A - 125 Vdc 0.3 A - 48 Vdc 0.5 A Breaking capacity (resistive) - 220 Vdc 0.2 A - 125 Vdc 0.4 A - 48 Vdc 0.2 A Performance time 8 ms. Frequency Programmable system frequency 50 or 60 Hz Operational range Fn 5 Hz Communications ports Front communication port RS232C connector DTE 9 pin D type female Cable length 3 m maximum Baud rate 600-38400 bps Insulation No Types of rear communication ports (COM-1 and COM-2) RS232 - RS232C connector DTE 9 pin D type female - Cable type Shielded - Cable length 15 m max. - Insulation 500V RS485 - RS485 connector DTE 9 pin D type female - Cable type Shielded twisted pair - Cable length 1,000 m max. - Insulation 500V G.F.O. - Connector ST - Wavelength 820nm - Attenuation 8 db with 62.5 /125 m glass fibre - Glass fibre optic Multimode 62.5 /125 m - Maximum distance 1.5 Km P.F.O. - Connector HP standard - Wavelength 660 nm - Attenuation 24.7 db with 1mm plastic cable 22 db with 200 m silica cable - Maximum distance 115 m with 1mm plastic cable 1.9 Km with 200 m silica cable Ethernet RJ45 Connector RJ45 Female Cable type Shielded Cable length 100 m max. Insulation 500V Baud rate 10/100 Mbps G.F.O. Ethernet Connector ST Wavelength 1300nm Permitted attenuation 8 db with 62.5 /125 m glass fibre Multimode glass optical fibre 62.5 /125 m Maximum distance 1.5 Km TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 18
IRIG-B port Input Demodulated Input level TTL Cable type 2-wire, shielded Insulation 500 V Maximum distance 1.5 Km Accuracy Accuracy Class 0.5 for V, I and P (up to 120% nominal) Accuracy in the protected range 3% Curve operation accuracy 5% or 30ms (the highest of the two values) Battery voltage monitoring (optional) 24-48 Vdc Range 18 to 60 Vdc 110-125-220 Vdc Range 86 to 280 Vdc Mechanical characteristics Weight 2.8 Kg Approx. weight with packaging and documentation 3.8 Kg Front IP IP40 Optional front IP IP54
ENVIRONMENTAL CONDITIONS Operating temperature -20C to 75C Storage temperature -40C to 85C Relative humidity Up to 95% without condensation
CONSTRUCTION FEATURES
PD300-H model dimensions
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 19
PD300-V model dimensions
IEC61850 and TCP model dimensions TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 20 CONNECTION DIAGRAMS
2 winding, pin terminal models
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 21
2 windings, closed-terminal models TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 22
3 windings, pin-terminal models TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 23
3 windings, closed-terminal models TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 24
Generator, pin-terminal models TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 25
Generator, closed-terminal models
TRANSFORMER, GENERATOR AND MOTOR PROTECTION Ingeteam Technology S.A. DSE_PD300_eng 26
Ingeteam Technology, S.A. www.ingeteam.com Parque Tecnolgico de Bizkaia Edificio 110 48170 Zamudio, Bizkaia, Spain Tel + 34 944 039 600 Fax +34 944 039 679 technology@ingeteam.com