Anda di halaman 1dari 5

SETRA Co.

UL: EX4986 FM: 1Y6A5.AF


RIYADH, K.S.A.
Phone: 01-4616141
TYCO (TEPG) FM-200 FLOW CALCULATION TEPG3.01
Project: General Auditing Bureau
File Name: Mohd. Al Rashid ( GAB) - MDB Room ( Bsmt.1 ) Rev.3
Customer Information
Company Name: Mohammad Al - Rashid
Address: Riyadh, K.S.A.
Phone:
Contact:
Title:
Project Data
Project Name: General Auditing Bureau
Designer: SETRA Co.
Number:
Account:
Location:
Description:
01-4616141
Riyadh, K.S.A.
MDB Room ( Basement 01 ) - FM 200 System
Consolidated Report
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Electronic Product Group
Page: 1 5 of
Calculation Date/Time: Saturday, March 22, 2014, 10:32:36 AM
Consolidated Report
Elevation: 0 m (relative to sea level)
Atmospheric Correction Factor: 1
Enclosure Information
Enclosure Number: 1
Name: Room Space
Enclosure Temperature...
Minimum: 20.0 C
Maximum: 50.0 C
Maximum Concentration: 8.066 %
Design Concentration...
Adjusted: 7.327 %
Minimum:
Minimum Agent Required:
Width:
Length:
Height:
Volume:
Non-permeable:
Total Volume:
Adjusted Agent Required:
Number of Nozzles:
7.170 %
35.2 kg
3.00 m
5.30 m
3.92 m
62.33 cubic m
0.00 cubic m
62.33 cubic m
36.0 kg
1
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Electronic Product Group
Page: 2 5 of
Calculation Date/Time: Saturday, March 22, 2014, 10:32:36 AM
Consolidated Report
Agent Information
Agent: FM-200 / Propellant N2
(FM-200 is a Trademark of Great Lakes Chemical Corp.)
Adjusted Agent Required: 36.0 kg
Container Name: 52L DOT Container Assy
Container Part Number: 303 205 018 TU/YU
Number of Main Containers:
Number of Reserve Containers:
1
0
Manifold: No Manifold
Horizontal Pipe Take Off Direction:
Agent Per Container: 36.0 kg
Fill Density: 0.676 kg / l
Container Empty Weight: 49.1 kg
Weight, All Containers + Agent: 85.1 kg
Floor Area Per Container: 0.13 square m
Floor Loading Per Container: 660 kg /square m
Pipe Network
Part 1 - Pipe
Description Start End Type Diameter Length Elevation
Pipe
Main Cyl. X 1 0 1 50 mm 0.60 m 0.60 m
Pipe 1 2 US40B
TS
25 mm 3.22 m 3.22 m
Pipe 2 3 US40B
TS
25 mm 2.08 m 0.00 m
Pipe 3 4 US40B
TS
25 mm 1.29 m 0.00 m
Pipe/E1-N1 4 5 US40B
TS
25 mm 0.10 m -0.10 m
Part 2 - Equivalent Length
Start End 90 45 Thru Side Union Other Added Total
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Electronic Product Group
Page: 3 5 of
Calculation Date/Time: Saturday, March 22, 2014, 10:32:36 AM
Consolidated Report
Part 2 - Equivalent Length
Start End 90 45 Thru Side Union Other Added Total
0 1 0 0 0 0 0 0.00 m 10.67 m
1 2 1 0 0 0 0 0.00 m 4.08 m
2 3 1 0 0 0 0 0.00 m 2.93 m
3 4 1 0 0 0 0 0.00 m 2.13 m
4 5 1 0 0 0 0 0.00 m 0.94 m
Part 3 - Nozzles
Start End Flow Name Size Type Nozzle Area
0 1 36.0 kg
1 2 36.0 kg
2 3 36.0 kg
3 4 36.0 kg
4 5 36.0 kg E1-N1 25 mm 8 Port-BR 307.88 square mm
Parts Information
Total Agent Required: 36.0 kg
Container Name: 52L DOT Container Assy (Part: 303 205 018 TU/YU)
Number Of Containers: 1
Nozzle Type Diameter Nozzle Area Part Number
E1-N1 8 Port-BR 25 mm 307.88 square mm 310 205 031
TU/YU
Nozzle Drill Diameter Drill Size
E1-N1 7.0000 mm 7 mm
Pipe: Type Diameter Length
US40BTS 25 mm 6.69 m

List of 90 degree elbows:
4 - 25 mm
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Electronic Product Group
Page: 4 5 of
Calculation Date/Time: Saturday, March 22, 2014, 10:32:36 AM
Consolidated Report
System Acceptance
7.3 seconds System Discharge Time:
Percent Agent In Pipe: 19.6%
Percent Agent Before First Tee: 0.0%
1 Enclosure Number:
Enclosure Name: Room Space
Minimum Design Concentration: 7.170%
Adjusted Design Concentration: 7.327%
Predicted Concentration: 7.328%
Maximum Expected Agent Concentration: 8.066% (At 50.0 C)
Minimum
Agent
Required Nozzle
Adjusted
Agent
Required
Predicted
Agent
Delivered
Nozzle
Pressure
(Average)
E1-N1 35.2 kg 36.0 kg 36.0 kg 10.054 bar
Drawing View: 2
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Electronic Product Group
Page: 5 5 of
Calculation Date/Time: Saturday, March 22, 2014, 10:32:36 AM

Anda mungkin juga menyukai