PL 70

Software
All of the equipment in the INGEPAC
TM

family can be accessed using powerful
software tools developed by Ingeteam and
which run on Windows.
Application software specically designed
for simple and user-friendly access to the
equipment.
52 (89)
3
1 3
74TC
74CC
Signalling &
Command
Measurements
>V
Fault
pass-
through
50/51
50/51N
79
Automatism
OPTIONALS BASIC FUNCTIONS
Protection and control
Distribution automation
Automation and monitoring functions
Monitoring of the installations signals in
real time
Remote and local control of the switchgear
Voltage presence detection
Directional fault passage detection
Automatic clearance of faults
50/51 Phase overcurrent protection
50/51 Neutral overcurrent protection
79 Four-stage recloser
Breaker monitoring
74TC/CC trip and close circuit supervision
Openings, closures, kI2 counter
Excessive number of trips alarm
Command failure
Pulse opening/closure command or change
of status detection (latch)
Data Acquisition Functions
Measurements historical report (maximum/
minimum)
Events recording
Faults recording
Oscillography recording
Current measurement (fundamental and
sequences), voltage (fundamental and
sequences), power (active, reactive and
apparent), power factor, frequency, demand
maximeter
Digital inputs and outputs
Communications
DB9 RS232 PROCOME protocol front port
Up to 2 rear ports: RS232, RS485, Glass
Fibre Optic, Plastic Fibre Optic, Ethernet
PROCOME protocols, IEC60870-5-104
Synchronisation
Via communications protocol or via
demodulated IRIG-B input.
Local interface
Keypad (4 keys + 6 operating buttons) +
local display (2 rows x 8 characters)
SIPCON software running on Windows for
PC, front or rear port access.
INGEPAC
TM
PL70 equipment offers a wide variety of applications allowing for the distribution
automation.
When installed in different switching elements of the distribution grid, it allows for the data capture
and processing, as well as the operation and command of automatic sequences, reporting in real
time all the necessary information to the SCADA and DMS systems of the electric company.
Additionally, it allows its remote conguration and updating using software tools or web browsers,
taking voltage measurements from inductive, resistive or capacitive sensors and current
measurements with low power transformers. They are also equipped with event, failure reports and
oscillography recordings in order to analyse events.
Functions depending on model
T
h
e

t
e
c
h
n
i
c
a
l

d
a
t
a

i
n

t
h
i
s

c
a
t
a
l
o
g
u
e

i
s

s
u
b
j
e
c
t

t
o

c
h
a
n
g
e

w
i
t
h
o
u
t

p
r
i
o
r

n
o
t
i
c
e
.


F
Y
2
3
I
P
T
T
0
1
_
A
Main Features
Insulation and Electromagnetic Tests
Dielectric strength IEC 60255-5
Insulation resistance IEC 60255-5
Impulse voltage IEC 60255-5
DC power supply terminal
conducted radiolectrical
emissions measurement IEC 60255-25/
EN55022
Radiated radioelectrical
emission measurement IEC 60255-5/
EN55022/EN5511
Electrostatic discharge
immunity test IEC 61000-4-2
Immunity to
radiofrequency-radiated elds ENV 50204/
IEC 61000-4-3
Electrical fast transients
immunity test IEC 61000-4-4
Surge pulses immunity test IEC 61000-4-5
Immunity to radiofrequency
induced signals IEC 61000-4-6
Damped oscillatory wave
immunity test IEC 61000-4-12
1 MHz damped wave
immunity test IEC 60255-22-1
Immunity to interruptions,
dips and variations
in DC power supply IEC 61000-4-29/
IEC 60255-11
Immunity to 50Hz magnetic
elds IEC 61000-4-8
Immunity to industrial
frequencies IEC 60255-22-7
Surge Withstand capability test IEEE C37.90-1
Climatic
Cold low temperature test IEC 60068-2-1
Dry heat test IEC 60068-2-2
Humid heat continuous test IEC 60068-2-78
Thermal shock IEC 60068-2-14
Mechanical
Vibrations test IEC 60255-21-1
Shock and bump test IEC 60255-21-2
Seismic test IEC 60255-21-3
Specic models for each application (RTU, recloser, OCR, RMU, load break switch, circuit-breaker
switchgear)
Intuitive conguration and monitoring software supplied with the equipment. It does not require a previous
conguration to communicate with the equipment.
Web server incorporated for remote access to the browser. It allows for visualisation in real time,
command, changing settings and downloading recordings.
User-dened logic signals
Digital inputs and outputs and programmable LED indicators
Sensor voltage measurement
Serial and Ethernet communication
Real time monitoring and recording of the parameters of the breaker
Events and faults recording
Automatic reclosing functions
Several setting groups.
Synchronisation via demodulated IRIG-B or through communication protocols
Options
Available formats: Flush mount 266x79x230 mm / Wall mount or DIN rail 193x230x102 mm
Connections: for pin type terminals or ring type terminals
Field interfaces
Conguration Digital inputs Digital outputs Others
0
2 6
1
8 11
2
7 11 IRIG-B
3
8 6 Capacitive sensors
4
7 6 IRIG-B + capacitive sensors
5
22 5
6 / 8
12 6 Capacitive/resistive sensors
7 / 9
11 6 IRIG-B + capacitive/resistive sensors
A
42 6
B / D
32 6 Capacitive/resistive sensors
C / E
31 6 IRIG-B + capacitive/resistive sensors
Power supply 12 Vcc; 24/48 Vcc; 125/220 Vcc; 220 Vca
Power supply voltage measurement
Communications ports: All of the devices have a front RS232 port for local access and additionally: 1
serial; 2 serial; 1 serial + 1 Ethernet; 2 Ethernet
Communication ports connection types:
Serial: RS232, RS485, Glass Fibre Optic, Plastic Fibre Optic
Ethernet: RJ45
IP54 front lid
Models by protection functions:
PL70RC (2xI phases + 1xI neutral + 1xV(TT)): 50/51, 50/51N, 50/51NS, 79, Fault detection, 2nd
harmonic restraint, 74TC/CC
PL70SC (2xI phases + 1xI neutral + 1xV(TT)): Fault detection, 2nd harmonic restraint, Automatic fault
clearance, 74TC/CC
PL70RSF (3xI phases + 1xI neutral + 3xV(resistive/capacitive sensor)): Fault detection, 2nd harmonic
restraint, Automatic fault clearance, 74TC/CC
PL70CTU (1xI + 1xV(TT)): 74TC/CC
Applications
Recloser control and protection
Load Break Switch control
Ring Main Units and compact transformer stations control
Modular switchgear control in transformer stations and distribution centres
Remote terminal and communications hub for SCADA communication
General Description

Anda mungkin juga menyukai