SWITCHGEAR

S A F E & S U R E
Motor Protection
Relay
MPR300
MPR300
Applications
MPR 300 Motor protection relay is suitable
for back panel surface mounting or DIN rail
mounting. It offers multiple protections to 3
phase induction motors. The R-Y-B phase
wires of the motor passes through the relay
(no need for external Cts).
The measurements are carried out through
integral CTs and electronics built inside the
relay. One set of trip contacts (1 N/O +1
N/C) is available for trip functions along with
individual LED indications. The relay is
ideally suitable for protection of motors
coupled to pumps, compressors, fans,
ventilators, cranes, elevators, escalators,
saw mills, paper mills, motorized valves,
conveyor belts etc. where frequent over
loads, rotor stalling, faulty bearings, and dry
running conditions are expected.
PROTECTIONS
a) Thermal over load protection :
b) Negative sequence protection
c) Earth Fault protection
d) Locked rotor protection
e) Under current protection
Each of the above faults are indicated by a
LED on the front panel. On occurrence of
fault, the relay provides two contacts 1 N/O
and 1 N/C. These contacts are manual reset
and can be used to open a contactor. The
LED fault indication is manual reset on
clearance of the fault, the LED has to be
reset by the front panel Reset PB.
TECHNOLOGY
MPR 300 uses state of the art digital
technology to measure the three phase
and residual currents in the motor feeder.
The current signals are sensed through
inbuilt CTs and evaluated by
microcontroller using advanced digital
sampling techniques. Special algorithms
are used for deriving the thermal status
and other parameters required for various
protections. The hardware design provides
high degree of accuracy and reliability.
The relay comes in 6 different models to
cover full range of motor rated currents
starting from 1A to 88A. In addition to
offering important protections, the relay is
most user friendly, simple to withstand
high level of EMI/EMC interferences which
are increasingly present in the present day
industrial environment.
Compact
Microcontroller based
design
6 models to cover motor
rated currents upto 88A
5 protections
3 integral Cts
DIP switch selection for
Thermal Characteristics
Trip indication
Test function
TECHNICAL SPECIFICATIONS
Input Connection R-Y-B wires of motor passes through relay
Basic Protections Thermal Over load, Negative Sequence (Phase Unbalance)
Locked Rotor, Earth Fault and Under Current
Thermal Over Load Protection
1. Current setting 1 to 88A in 6 different model s as follows :
1 to 2.75A 2 to 5.50A 4 to 11A
8 to 22A 16 to 44A 32 to 88A
2. Trip Time Characteristics Class 10A, 10, 20 and 30 as per LEC 947-4-1
Field selectable through front DIP switches.
3. Pre alarmAt 1.05 lm by flashing LED (lm =Motor rated current)
4. Thermal MemoryProvided.
Earth Fault Protection
1. Current setting 10 to 50% of Im field selectable by front panel pot.
2. Trip time delay 200 msec factory set
3. Disable feature Available from front panel pot.
Phase Unbal ance Protection
1. Unbalance current 50% of Im factory set
2. Trip time delay 3 sec factory set
Locked Rotor Protection
1. Locked rotor current3 Im factory set
2. Trip time delay 1sec factory set
3. Disable featureAvailable from front panel DIP switch
Under Current Protection
1. Under current threshold50% of Im factory set
2. Trip time delay3 sec factory set
3. Disable featureAvailable from front panel DIP switch
Operational Indi cators
LED indications for Power On
LED indications for trip on each of the 5 faults
LED starts flashing when fault is detected. Becomes steady on
When the relay trips after the preset time delay.
LEDs are manual reset.
Contacts 1 N/O +1 N/C manual reset
Rated Voltage 250 V AC / 30 V DC
Rated Current 5A
Rated breaking capacity 2000 VA / 240 W (resistive)
Auxiliary Power Suppl y 240 V AC +/- 20%
Operating Temperature 0 to 60 degrees C
Accuracy As per IEC 947-4-1
Reset Current 95% to 90% of Im
Reset Time Less than 160 millisec for O/L, N/S, U/C and L/R faults
Less than 80 milisec for Earth fault
Reference Standards IEC 60255, IEC 61000 and IEC 60068
TRIP
CLASS
Tripping Time at multiple of Ie
10A
10
20
30
120%
>2 hours
>2 hours
>2 hours
>2 hours
150%
2min
4min
6min
12min
720%
2-10 sec.
4-10 sec.
6-20 sec.
9-30 sec.
Wiring Diagram for MPR300
LARSEN & TOUBRO LIMITED
Powai Works, Saki Vihar Road, P.O. Box 8901
Mumbai 400 072