Contract Title

Consultancy for Project Engineering and


Management Services Contract No. PD/035/CNSL
Document Title
Electrical Data Sheet For LV Switch Board
Work Order 035/MAA/WOR-033
AMEC ref
1 14 April 2010 KNP SG WH
0 02 December 2009 MG MHB MHB
A 14 August 2009 MG MHB MHB
Rev.
No.
Date
Prepared
by
Checked
by
Approved
by
Approved
by
KNPC
Consultancy Services for
North LPG Tank Farm Project
Document Number
D-035.033-208-2.80-7017
0223-070-208-DAT-7017
Revised by KNPC & Issued for ITB
For Tender
For Review
Issue Description
Issue History AMEC
CLIENT: KNPC EQUIPMENT No.: M49A-LSWG-208-001 Doc. No. D-035.033-208-2.80-7017
M49A-LSWG-208-51 REV. 1
M49B-LSWG-208-001
WORK ORDER No 035/MAA/WOR-03 EQUIPMENT TITLE : LV Switch Board DATE
PROJECT: North LPG Tank Farm REQUISITION No : BY KNP
SUPPLIER: QUOTATION REF. : CHECKED SG
Applicable To : Proposal Purchase As Built
Operating Mode : Continuous Intermittent Stand By
Manufacturer : Model :
Serial No. :
Specific Requirements : S-035.033-208-2.80-7110
Schedule : Refer to SLDs 035.033-208-7208, 7209, 7210-4 (from DEP 33.67.01.80-Gen)
Power System Type : Voltage: V Frequency : Hz Hz
No. of Phases :
Electrical Supply Characteristics : More Onerous; Details; (specify details)
Rated Insulation : V
Rated Current of Main Busbar System : A at 50
o
C; Copper Bus Bar Aluminium Bus Bar
Rated Current of Neutral Busbar System : A at 50
o
C; Copper Bus Bar Aluminium Bus Bar
Service conditions : More Onerous; Details; (specify details)
Location : Land Offshore Indoor Outdoor
Rated Short Time Withstand Current : kA 1 sec. 3 sec.
Rated Peak Withstand Current : kA
Rated Impulse Withstand Voltage : kV peak
Rated Power Frequency Withstand Voltage : kV
Earth Busbar Withstand Current & Time : kA 1 sec. 3 sec.
D f P t ti IP
3 +N
As Per Specification
2.5
6
600
65
65
51
NORTH LPG TANKFARM PROJECT
Data Sheet
for
LV SWITCHBOARD
50 (+/-) 5%
3200
as per IEC
400(+/-)10%
As Per Specification
50% of Main Bus
3
14/04/2010
REQUIREMENTS AND CONDITIONS
GENERAL
TN-S
Degree of Protection : IP
Spare Space Available : % minimum
Special Service Conditions : No Later
Pollution Degree : 3 (As per DEP)
Special Transport Conditions : No Later
IMCS Required : Yes No (details specified separately)
Measuring Instruments : Analogue Digital
Transducers Required for Signals to DCS : Yes No (details specified separately)
Transducers Required for Signals to ENMC : Yes No (details specified separately)
Language on Equipment : English
Language on Documentation : English
Busbar Arrangement : Single Double Duplex
Number of Sections : 1 2 3
Phase Segregated Busbar : Yes No
Busbar Identification : Color Coded (R-Y-B) Letter Coded (R-S-T)
Busbar Material : HDHC Copper
Clearance in Air : mm Vendor to Advise
Busbar Insulation : Non Tracking
Future Busbar Extension at Either End :
Cable/Bus Compartment Barrier : Required
Neutral Earth Link Installed :
Rated Diversity Factor : Vendor to Advise
Form of Internal Separation : Vendor to Advise
Type of Fuses : DIN BS
Switchboard Type : Air Insulated Metal Enclosed Withdrawable Fixed
Type of Mounting : Freestanding Floor Wall
Switchboard Arrangement : Single Front Double Front
Framework Required : Yes No
Anti Condensation Heaters Required : Yes Indication & Selector Switch Required
Cable Entries Cable Gland Plate : Brass Sheet Steel
- Incoming Supply : Bottom Top Cable Bus Duct : Drilled Undrilled
Heat Shrinkable - PVC
BUS BAR SYSTEM
20
Yes, Required at Both Ends
Yes, Required
51
PANEL CONSTRUCTION
Form 4
Incoming Supply : Bottom Top Cable Bus Duct : Drilled Undrilled
- Outgoing Feeder : Bottom Top Cable Glands Required : Yes No
- Control Cable : Bottom Top Glands Type :
Padlock Hasp Size : 5mm mm minimum
CLIENT: KNPC EQUIPMENT No.: M49A-LSWG-208-001 Doc. No. D-035.033-208-2.80-7017
M49A-LSWG-208-51 REV. 1
M49B-LSWG-208-001
WORK ORDER No 035/MAA/WOR-03 EQUIPMENT TITLE : LV Switch Board DATE
PROJECT: North LPG Tank Farm REQUISITION No : BY KNP
SUPPLIER: QUOTATION REF. : CHECKED SG
Circuit Breaker Type - Insulation : Air Insulated Control Voltage - Closing : V AC DC
- Mechanism : Single Throw - Tripping : V AC DC
- Mounting : Withdrawable Fixed - Spring Charging : V AC DC
No. of Poles - Incoming CB : 3-Pole 4-Pole Spring Charging : Automatic
- Bus-tie CB : 3-Pole 4-Pole Manual Spring Charging (Additional Req't : Required
- Outgoing Feeder CB : 3-Pole 4-Pole Circuit Breaker Closing Time : Vendor to Advise ms
Rated Duty : Uninterrupted Circuit Breaker Opening Time : Vendor to Advise ms
Rated Voltage : 600VAC Mechanical Endurance : Vendor to Advise
Rated Current : As per SLD Electrical Endurance : Vendor to Advise
Rated Short Circuit Breaking Capacity : 65kA Anti Pumping Device : Required
Rated Short Circuit Making Capacity : as per IEC Mechanical Operations Counter : Required
Duty Cycle of Breaker : O-3min-CO-3min-CO Manual Mechanical Operation Facility
Insulation Test Voltage : 2.5kV (rms) - Closing : Required
Method of Open & Closing - Method : Stored Energy - Tripping : Required
- Mechanism : Spring or Solenoid Closed / Open Position Indication : Required
Manual Operation Facility - Closing : Required Charged / Discharged Spring Indication : Required
- Tripping : Required Number or CB's : Refer to SLD
AIR CIRCUIT BREAKER & PANEL DATA
REQUIREMENTS AND CONDITIONS - CONT.
NORTH LPG TANKFARM PROJECT
Data Sheet
for
LV SWITCHBOARD
14/04/2010
110
110
AIR CIRCUIT BREAKER PANEL INDICATIONS
110
"Closed" Indication : Red Circuit Breaker in Test Position : Mechanical Indication
"Open" Indication : Green Spring Charged : Mechanical Indication
Circuit Breaker Tripped on Fault : Amber 110V DC Failure Indication : Amber
CB Trip Circuit Healthy : White Earth switch ON Indication : Required
Anti Condensation Heater ON : Blue
Incoming Feeders (Refer to SLD & Specifications): Outgoing Motor Feeders (Refer to SLD & Specifications):
Differential Protection : Not Required (MCU Unit shall include the following):
Feeder Protection (50/51) : Required Ins. Over Current (50) : Required
Neutral Time Overcurrent (51N) : Required Ground Ins. Over Current (50G) : Required
Ground Time Over Current (51G) : Required Motor Stall (51S) : Required
Lockout (86) : Required Thermal Over Current (49) : Required
Transformer Lockout (86T) : Required Phase Unbalance/Reverse (46) : Required
Intertrip Receive (85) : Required Reacceleration Relay (Aux. Relay) : Required
Under Voltage (27) : Required Ammeter : Required
Restricted Earth Fault (64/REF) : Required Run-up Time : Required
Transf. Winding Thermal (WTI) : Required Hour Run Meter : Refer to SLD
Transf. Oil Temperature (26) : Required Outgoing Feeders (Refer to SLD & Specifications):
Sudden Pressure (63) : Required (FCU Unit shall include the following):
Ammeter/Ammeter Switch : Required Ground Ins. Over Current (50G) : Required
Voltmeter/Voltmeter Switch : Required Lockout Relay (86) : Required
CT (Metering & Protection) : Required General:
VT : Required Trip Circuit Supervision : Required
kWH Meter : Required RR/TRM Relay Bases : Not Required
Control Circuit Supervision : Required
Type : Modular Withdrawable Method of Opening and Closing : Manual
No of Poles - Motor Feeder : 3-Pole 4-Pole Closed / Open Position Indication : Required
- Other Feeder : 3-Pole 4-Pole Protection Release
Rated Duty : Uninterrupted - Thermal Overload Release : Motor Feeders Power Feeders
Utilization Category : B - Short Circuit Release : Motor Feeders Power Feeders
Rated Current : As per SLD - Earth Fault Release : Motor Feeders Power Feeders >30A
Rated Short Circuit Breaking capacity : 65kA All undeground cable feeders
Rated Short Circuit Making Capacity : 65kA
MOULDED CASE CIRCUIT BREAKER
C CU C O S
RELAYS & METERING (Refer Typical schematic drawing # 035.033-208-2.80-7214-4)
CLIENT: KNPC EQUIPMENT No.: M49A-LSWG-208-001 Doc. No. D-035.033-208-2.80-7017
M49A-LSWG-208-51 REV. 1
M49B-LSWG-208-001
WORK ORDER No 035/MAA/WOR-03 EQUIPMENT TITLE : LV Switch Board DATE
PROJECT: North LPG Tank Farm REQUISITION No : BY KNP
SUPPLIER: QUOTATION REF. : CHECKED SG
Type : Modular Withdrawable Type : Modular Withdrawable
Make & Model No. : No. of Poles : 3-Pole 4-Pole
No. of Poles : 3-Pole Utilization Category : AC22
Utilization Category : AC22 Rated Current : As per SLD
Rated Current : As per SLD Rated Short Time Withstand Current : 65kA, 1 sec
Rated Short Time Withstand Current : 65kA, 1 sec
No. of Poles : 3-Pole 4-Pole
Utilization Category : AC3
Key Single Line Dwg : 035.033-208-2.00-7201-4
400V Switchgear Schematic Diagram (Typ.) : 035.033-208-2.80-7214-4
Specification for LV Switchgear : S-035.033-208-2.80-7110
T T t C tifi t R i d
NORTH LPG TANKFARM PROJECT
Data Sheet
for
LV SWITCHBOARD
14/04/2010
DOCUMENTS/DWGS
REQUIREMENTS AND CONDITIONS - CONT.
TEST REQUIREMENTS
CONTACTOR
AUTOMATIC TRANSFER SWITCH SWITCH
Type Tests : Certificates Required
Routine Tests : Required Not Required
Witness Inspection : Yes
Special Test Required : Required Not Required
1) Air circuit breaker shall have 2 nos. N.O. and 2 nos. N.C. aux. contacts as minimum.
2) Withdrawable circuit breakers of same voltage, current rating and feeder type shall be interchangeable.
3) Circuit breaker operating mechanisms shall be of the motor / manual spring charge, stored energy, manual / electrical release type.
4) Rated short time withstand & breaking currents for incomer & bus tie circuit breakers shall not be less than the ratings of the main busbar.
5) Ammeter & voltmeters with selector switch shall be provided on the incomers.
6) Relays shall be provided with built-in test facilities.
7) T.N.C. switch on incomers & bus tie circuit breakers shall be provided.
8) Manual spring charging facility for Incomer & bus tie circuit breakers shall be provided.
9) Operating & maintenance tool set shall be supplied.
10) Auto restart of motor starters shall be selective as per schedule.
11) All protection relays shall be compatible for connection with the ENMC system.
Make and Type :
Manufacturing Location : Assembly : Main Components :
Rated Short-circuit Strength : Thermal : kA rms, 1s Dynamic : kA crest
IMCS Type : (see sheet 5)
Type of Enclosure :
Type of Mounting :
Degree of Protection : IP
Anti Condensation Heaters Included : Yes No
Rain Canopy : Yes No
Overall Dimensions of the Switchboard : x x (L x W x H)
Total Mass of Equipment : kg
Expected Assembly Heat Dissipation : kW
Specified Tender Documentation Attached : Yes No
Any Deviations from Specification (if yes, list deviations) : Yes No
SPECIAL REQUIREMENTS AND REMARKS
INFORMATION TO BE SUBMITTED WITH THE TENDER
CLIENT: KNPC EQUIPMENT No.: M49A-LSWG-208-001 Doc. No. D-035.033-208-2.80-7017
M49A-LSWG-208-51 REV. 1
M49B-LSWG-208-001
WORK ORDER No 035/MAA/WOR-03 EQUIPMENT TITLE : LV Switch Board DATE
PROJECT: North LPG Tank Farm REQUISITION No : BY KNP
SUPPLIER: QUOTATION REF. : CHECKED SG
Specific Requirements : DEP 33.67.01.31-Gen., Appendix 1
FCU's for Feeders Required : No All Selective As Per Schedule
Optional Requirements for Motor Starters :
- Auto Restart : Yes No
- Power Monitoring : Yes No
- Power Factor Monitoring : Yes No
- Under Current Protection : Yes No
- Under Voltage Protection : Yes No (only with latched contactors)
- Over Temperature Protection : Pt100 Thermistor No
Optional Requirements for Feeders :
- Power Monitoring : Yes No
- Power Factor Monitoring : Yes No
- Overcurrent Protection : Yes No
- Earthfault Protection : Yes No
Redundancy Connection CCU - MCU/FCU : Yes No (specify details as required)
Redundancy Connection CCU - DCS : Yes No (specify details as required)
NORTH LPG TANKFARM PROJECT
Data Sheet
for
LV SWITCHBOARD
14/04/2010
GENERAL
REQUIREMENTS AND CONDITIONS
Redundancy Connection CCU DCS : Yes No (specify details as required)
Number of Engineering Work Stations (EWS) Required : 0 1 2
Number of Hand Held Terminals (HHT) Required : 0 1 (combined with EWS)
Electrical Supply to MCU / FCU : Local Centralised Optional
UPS Supply Available : Yes No
Make and Type of DCS : Make : Type :
:
Witnessed Inspection Required : Yes No Site Installation : Yes No
: Commissioning : Yes No
: Start-up Assistance : Yes No
Language on Documentation : English Simulation Unit for Training : Yes No
Language on Equipment : English Quotation for Spare Parts Covering 2 Years : Yes No
1) Where Is limiters are included in the supply, specific requirements shall be specified by the Principal.
2) Detailed information shall be provided during detailed design stage.
Make and Type of IMCS :
Manufacturing Location : (specify separately for main components)
Nearest Service Organisation / Location :
Details of Electrical Supply Included : Yes No (specify for various components)
Overall Dimensions of the Switchboard : x x (L x W x H)
Total Mass of Equipment : kg
Expected Assembly Heat Dissipation : kW
Test Protocol Attached : Yes No
Specified Tender Documentation Attached : Yes No
Any Deviations from Specification (if yes, list deviations) : Yes No
INFORMATION TO BE SUBMITTED WITH THE TENDER
SPECIAL REQUIREMENTS AND REMARKS