Power Factor
Power factor is the ratio between True Power (kW) and Apparent Power
(kVA) it is not expressed in a percentage but in a per unit form. In industry
such as in this project electric motors are used to drive fans pumps conveyer
and other plant. Generally the electrical drives which are used are Induction
motors typically these have a poor power factor which causes inefficiencies
in the electrical supply by drawing excess inductive reactive currents
increasing loads on cabling and switchgear other such loads are lighting
ballasts and welding plants ect. As it causes inefficiencies in the electrical
supply the supply authority will penalise the consumer financially for poor
power factor. Therefore the better the power factor the more cost efficient.
Power Factor = kW
KVAr
KW KVA
θ
θ
kVA
Typically power factor for industry is about 0.8 lagging for example a 500
kVA transformer can only supply up to 400 kW this means the consumer is
only getting 80% efficiency of there supply.
Now we can see the advantages of having good power factor. These excess
currents can reduced by means of power factor correction. It is achieved by
the delta connecting capacitors in parallel.
2) For larger installations the above method may not be so practical. This
is an alternative a large bank of capacitors is connected to the supply
at the distribution board they are switched in and out of the supply by
means of a timer. At peak time all capacitors would be switched in
and would be switched back out at a later time. It is only allowed to be
permanently connected in installations up to 25 kVAr
kW = 169.8 kW
Tanθ1 = cos-1 0.849 = 31.89° tan = 0.622
Tanθ2 = cos-1 0.98 = 11.47° tan = 0.203
The capacitor bank is located 15 meters from the supply the cable size
required to supply the capacitor is given as
16000 = 7.82mV/A/m
136.28*15
From the latest ECTI regulations a cable of 35mm2 XLPE would be adequate
to supply the capacitor.