Anda di halaman 1dari 183

Page 1 of 183

--;~-' --,-' -----'


--='--' -,',;
-,-;=--' ~'-;,~--' ,-,-
-'->- _--V' -=-' ~'-~';-
MINIMUM TECHNICAL REQUIREMENTS
(MTR)

Page 2 of 183

Table of Contents PAGE

1. INTRODUCTION .....4
1.1 General
1.2 Project scope

2. Site Work .6

3. ARCHITECTUR .......8
3.1 Codes and Standards .......9
3.2 Function requirements ........9
3.3 Internal Finishes ..9
3.4 External Finishes .....9
3.5 Fire & Life safety ......10
3.6 Material Standards .....14

4. STRUCTURAL
4.1 Codes and Standards....................................................................................................105
4.2 Reinforced Concrete Design........................................................................................106
4.3 Structural Steel Design .........106
4.4 Pre-stressed Concrete Design...........106
4.5 Masonry Design........107
4.6 Other Standards.........107
4.7 Design Criteria......107
4.8 Loads Assessment ....107
4.9 Load Combinations...........108
4.10 Vertical Deflection and Lateral Sway ....108
4.11 Computer Programs .....108
4.12 Structural Materials ......108
4.13 Structural Steel .....110
4.14 Structural systems.........111
4.15 Fire Protection..........112

5. GEOTECHNICAL ..........113
5.1 Codes and Standards....114
5.2 Geotechnical Detailed Design Requirements...114

6. MECHANICAL ..115
6.1 HVAC ......116
6.2 FIRE FIGHTING ....... 129
6.3 PLUMBING WORKS .....135

Page 3 of 183

7. ELECTRICAL ...146
I- ELECTRICAL (POWER & LIGHTING SYSTEMS).147
II- ELECTRICAL (LOW CURRENT SYSTEMS) ....164

Page 4 of 183

Minimum Technical Requirements (MTR)

1. Introduction

1.1 General
ThisMinimum Technical Requirementsdocument describes the technical
requirements that shall be adopted, as a minimum in the design and execution of the
work.
ThisMinimum Technical Requirementsshall be valid for the following:
i. The projects wherever the work is under Addendum No. (1) including the
design development and the construction of work.
ii. Any design work required for buildings, elements, site or system under the
Contract.
iii. The adaptation work and any modification required for the completion and /
or preparation of all construction documents.

1.2 Project scope

- The project scope includes the preparation of all construction documents for all
required disciplines according to the proposed design, executing, completing and
testing the required buildings, including parking and pavement outside the building,
in addition, all the building utilities connections up to the existing networks or utility
plants (including water supply, sewage, fire networks, electric networks, etc) are
deemed included in the project scope of work, contractor to perform necessary
surveys and studies to allow for the design and execution of the networks connections
as would be deemed necessary.

- Contractor need to submit all shop drawings and details showing all the final
requirements of all disciplines for the engineers approval.

- The proposed furniture selection shown on the design drawings for all spaces is
considered preliminary selection, contractor shall submit the following:
Contractor shall prepare, develop and submit full design detailing and final
furniture layout of all functions in the building in a comprehensive scheme
for the owners approval.
Complete and comprehensive list of furniture and equipments covering all
building areas showing all required details, dimensions and specifications.

- Contractor need to submit a complete acoustic study covering all project spaces
showing all requirements and treatments for the engineers approval.
Page 5 of 183

1.2.1 Architectural scope of work

The Architectural scope shall account for the following:
- Materials and finishes for interior, exterior and Furniture.
- Efficient design to optimize space usage.
- Design as per architectural codes and standards.
- Potential for future expansion.
1.2.2 Structural scope of work

The Structural system shall account for the following:
- Safety of the building users and systems.
- Durability of the structural elements, reducing thus the need for future
maintenance.
- Rationalization of structural of structural design.
- Aesthetical Values with special attention to adopt structural concepts in
harmony with the architectural requirements.

1.2.3 Mechanical scope of work

The Structural system shall account for the following:
- Safety and reliability of mechanical system.
- System durability for optimum life cycle.
- System efficiency for optimal power and save material consumption.
- Compatibility with architectural, layout/Interior Design, as appropriate.
1.2.4 Electrical scope of work
The Structural system shall account for the following:
- Safety reliability of optimum power consumption.
- Flexibility for future Expansion, where appropriate.
- Compatibility with architectural layout/Interior Design, as appropriate.

Page 6 of 183

2. Site Work

Page 7 of 183

2. Site Work
Roads
This section covers the;
1. Geometric design of Roads & Parking Layout.
2. Pavement Design.
3. Traffic Control Devices.

Geometric Design of Roads & Parking Layout
The Design criteria followed for the design of roads is based on
Highway Design manual Second Edition by Ministry of
Transportation Saudi Arabia and A Policy on Geometric Design
of Highways and Streets latest edition " by AASHTO.

Pavement Design
The structural design of the pavement will be accordance to with
AASTHO (American Association of State Highway and
Transportation officials) and Highway Design Manual by Ministry
of Transportaion, Saudi Arabia.

Traffic Control Devices
Pavement marking and signage should be according to Manual on
Uniform Traffic Control Devices for Streets and Highway by
Ministry of Transportation, kingdom of Saudi Arabia".

Landscaping
The used planters are to be chosen based on their suitability to the
climate of each site and to be as drought tolerant as possible, in
order to minimize the maintenance and reduce water consumption.

Page 8 of 183

3. ARCHITECTURE
Page 9 of 183

3. ARCHITECTURE
3.1 Codes and Standards
- The architectural systems shall be designed in accordance with Saudi Arabian
Standard Organization (SASO) Codes and standards; however the items which are
not covered in Saudi codes shall be designed in accordance with the requirements of
the following codes:
- International Code Council (ICC) Publications.
- IBC 2009 Code and all the related Referenced Standards indicated in Chapter
35 of the IBC 2009.
- US Green Building Council. IF Required
- The Code of Federal Regulations (CFR-USA)
- American Disability Association (ADA).
- American National Standards ICC/ANSI A11.71-2003.
- GCC codes for Educational occupancy
- National Fire Protection Association code (NFPA).
- The American Society of Testing and Materials (ASTM).
- American Correctional Association requirements (ACA).
- British Standards (BS).
- American Association of State Highway and Transportation (AASHTO).
3.2 Function requirements

- The criteria mentioned in the MTR, Specifications and shown on drawings are to be
followed during the design detailing developed by the contractor.

- The design detailing of all drawings is to be developed by the Contractor for the
Engineers review and approval. The developed design detailing shall be in full
compliance with the architectural concept design drawings and specified technical
requirements.

- The architecture layouts showing space areas, distribution and function relations,
tables of areas, number of floors shown on drawings are considered as fixed criteria
and to be used as the base for the design detailing developed by the contractor,
however, the contractor required to make the detailed coordination to all building
services with other trades based on the engineering MTR provided in the tender
documents, any changes would be required on the layouts or basic criteria to be
approved by the owner prior to modifications.

3.3 Internal Finishes

- The integration and compatibility between the finishing material, design and
maintenance requirements shall be the most important factor in selecting the
materials. The finish schedules shown on drawings are to be used as the bases for
final selection of finish materials together with the materials provisions indicated in
chapter 8 of the IBC-2009 and the NFPA.

3.4 External Finishes

- The exterior finish material shall be as per the provision of the exterior finish
materials indicated in chapter 14 of the IBC-2009 and the NFPA.

Page 10 of 183

3.5 FIRE AND LIFE SAFETY

Page 11 of 183

3.5 Fire & Life safety

- The contractor shall submit a complete and comprehensive fire and life safety study
using the below as the guidelines and covering the following as a minimum:

General Description:
- Title: Use and occupancy classification.
- Number of stories based on the Building Area and Height classification.

Regulations:
- Saudi Building Code (SBC).
- ICC publications 2009
- NFPA 101-2009
- Architectural Graphic standards (AIA)

1. Technical requirements:

1.1 Classification:
- Building Use Group (Occupancy).

1.2 Construction fire resistance: (As per Code Minimum Provisions)
- The minimum construction type required is Type II as per chapter 6 of the IBC 2009
code.
- Load bearing elements required to be 2H fire resistant.
- Floor construction required to be 2H fire resistant.

1.3 Compartmentation (subdivision of building spaces): (As per Code Minimum Provisions)
- Staircase protection: Walls 1H & Doors 1H for < 4 stories 2H &
Doors 1.5H for L 4 stories
- Vertical shafts protection: Walls 1H & Doors 1H for < 4 stories 2H &
Doors 1.5H for L 4 stories
- Elevator shafts: Walls 1H- Doors 1H
- (Staircase, vertical shafts and elevators continuing to basement levels:
- Walls 2H- Doors 1 1/2H
- Exit access corridor walls protection: Walls 1H- Doors 3/4H
- Fire compartment (2000m2): Walls 1H- Doors 3/4H
- Classrooms: Walls 1H- Doors 3/4H
- Corridor sub-division doors: Doors: 3/4H
- Fire resistant doors shall be self closing.

1.4 Hazardous areas: (As per Code Minimum Provisions)
- Moderate hazard containing premises separation: Walls 1H- Doors 3/4H.
- Concerned premises:
- Mechanical rooms, Electrical room, Archives room, Storage room,
- High hazard containing premises separation: Walls 2H- Doors 1 1/2H
- Concerned premises: Pump room,

1.5 Conduits and shafts: (As per Code Minimum Provisions)
- Conduits & pipes crossing fire resistant barriers shall be designed not to impair the
fire resistance of the barriers.
- Ducts and air-transfer openings penetrating walls or partitions having a fire resistance
rating of 2H and vertical shaft walls having a fire resistance of 1H shall be equipped
with fire dampers.

Page 12 of 183

1.6 Means of Egress: (As per Code Minimum Provisions)
- Minimum exit width:
- 1120 mm if serving occupant load more than 50 persons
- 915 mm if serving occupant load less than 50 persons
- Minimum door width: 810 mm

1.7 Common Path of Egress, Exit Access Travel distances and Corridor Dead-End verification:
(As per Code Minimum Provisions)

ELEMENTS
OF EGRESS
BUILDIN
G USE
GROUP
MAX. ALLOWABLE LENGTH
(METER) IBC ODE
REFERENE
ONDITIONS &
EXEPTIONS
NON-
SPRINKLERED
SPRINKLERED
OMMON
PATH OF
EGRESS
B




UA AD S
S

R-


E
I- S
EXIT
AESS
TRAEL
DISTANE
B A!
"#DD
S$ S"%
!UD$ &
UAS
R-
' A!
"#DD
S$ S"%
!UD$ &
UAS
E ' A!
I- ' A!
ORRIDOR
DEAD-END
B

' '

R-
'
( #A" !!% SUD
! D
$ &D
" ! UAS
E
'
Page 13 of 183

1.8 Discharge from exit: (As per Code Minimum Provisions)
- Fifty percent of both the number and capacity of exits is discharging directly outside
the building or through a protected exit passageway separated from the remainder of
the building with fire barriers of 1H fire resistance rating.

1.9 Interior Finish: (As per Code Minimum Provisions)
- Interior wall and ceiling finish will respect the following classification:
Class A for exits and class B for exit access corridors. .
Class A, class B or class C for all other areas.

- Interior floor finish shall be Class I or Class II in exit enclosures.

1.10 Illumination and Emergency Lighting: (As per Code Minimum Provisions)
- The illumination of the means of egress will be provided
- Exits and circulations of the buildings will be equipped with an emergency lighting
system.
- The marking of the means of egress will be provided.

1.11 Smoke Control: (As per Code Minimum Provisions)
- Communicating spaces will be provided with a smoke evacuation system.

1.12 Fire alarm system: (As per Code Minimum Provisions)
- The building will be equipped with an automatic fire alarm and detection system.
- Initiation shall be by manual means and/or by the automatic fire detection system.
- Notification shall be by a general alarm throughout the building.

1.13 Fire Fighting means: (As per Code Minimum Provisions)
- The building will be protected throughout by:
- Automatic extinguishing system (sprinkler)
- Wet risers (in every staircase)
- Hose reel system
- Portable fire extinguishers.

Page 14 of 183

3.6 MATERIAL STANDARDS
Page 15 of 183

SECTION 02518 PAVERS
ASTM International

ASTM C144: Specification for Aggregate for Masonry Mortar.
ASTM C150: Specification for Portland Cement.
ASTM C936: Specification for solid Concrete Interlocking Paving Units.

SECTION 02527 PRECAST CONCRETE CURBS
ASTM International

ASTM C 33: Standard Specifications for Concrete Aggregate.
ASTM C 67: Standard Test Method for Sampling and Testing Brick and Structural Clay Tile.
ASTM C 117: Test Methods for Materials Finer than No. 200 Sieve in Mineral Aggregates
by Washing.
ASTM C 136: Test Method for Sieve Analysis of Fine and Coarse Aggregate.
ASTM C 140: Standard Test Method for Sampling and Testing Concrete Masonry
Units and Related Units
ASTM C 150: Standard Specifications for Portland Cement.
ASTM C 293: Standard Test Method for Flexural Strength of Concrete.
ASTM C 642: Standard Test Method for Density, Absorption, and Voids in Hardened
Concrete.
ASTM D 1557: Test Methods for Moisture Density Relations of Soils and Soil- Aggregate
Mixtures Using 4.54 kg Rammer and 457 mm Drop.

SECTION 02820 CHAIN LINK FENCE GATES
ASTM International

Steel Plates, Shapes, and Bars: ASTM A 36M
Steel Tubing: Cold-formed steel tubing complying with ASTM A 500
Steel Pipe: ASTM A 53, standard weight (Schedule 40), unless another weight is indicated or
required by structural loads.
Round Steel Pipe: Standard weight, Schedule 40, galvanized steel pipe complying with
ASTM F 1083. Comply with ASTM F 1043, Material Design Group IA, external and internal
coating Type A, consisting of not less than 0.55-kg/sq. m zinc; and the following strength and
stiffness requirements
Steel Rails and Bars: Hot-rolled, carbon steel complying with ASTM A 29M, Grade 1010
Iron Castings: Malleable iron complying with ASTM A 47M, Grade 22010.
Brackets, Flanges, and Anchors: Cast or formed metal of same type of material and finish as
supported rails, unless otherwise indicated
ASTM A 36M: mild steel plate, Shapes, and Bars
ASTM A 500: Cold formed tubing
ASTM A 47M: Malleable-Iron Castings
Zinc coating per ASTM A 653M
Zinc coating per ASTM A 123M

SECTION 02841 VEHICLE BARRIER (Road Blocker and Gate Barrier)

American Association of State Highway and Transportation Officials

AASHTO M180: Standard Specification for Corrugated Sheet Steel Beams for Highway
Guardrail.
Page 16 of 183

ASTM International

ASTM A36/A36M - Standard Specification for Carbon Structural Steel.
ASTM A123/A123M - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on
Iron and Steel Products.
ASTM A153/A153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware.
ASTM A428/A428M - Standard Test Method for Weight [Mass] of Coating on Aluminum-
Coated Iron or Steel Articles.
ASTM A500 - Standard Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural Tubing in Rounds and Shapes

SECTION 03491 DECORATIVE GLASS FIBER REINFORCED CONCRETE
American National Standards Institute/American Institute of Steel Construction

ANSI/AISC 360-2005: Specification for Structural Steel Buildings

American Iron and Steel Institute

North American Specification for the Design of Cold-Formed Steel Structural Members.
2001(2004 Supplement)
American Welding Society

AWS D1.1/D1.1M-2006: Structural Welding Code - Steel
AWS D1.3-1998: Structural Welding Code - Sheet Steel

ASTM International

ASTM A 27/A 27M-05: Specification for Steel Castings, Carbon, for General Application
ASTM A 36/A 36M-05: Specification for Carbon Structural Steel
ASTM A 47/A 47M-99 (Reapproved 2004): Specification for Ferritic Malleable Iron Castings
ASTM A 108-03: Specification for Steel Bars, Carbon and Alloy, Cold-Finished
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 307-04: Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile
Strength
ASTM A 325-04b: Specification for Structural Bolts, Steel, Heat-Treated, 120/105 ksi
Minimum Tensile Strength
ASTM A 325M-05: Specification for Structural Bolts, Steel, Heat-Treated, 830 MPa
Minimum Tensile Strength [Metric]
ASTM A 500-03a: Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural
Tubing in Rounds and Shapes
ASTM A 513-06: Specification for Electric-Resistance-Welded Carbon and Alloy Steel
Mechanical
Tubing
ASTM A 653/A 653M-06: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron
Page 17 of 183

Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 780-01: Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized
Coatings
ASTM A 1003/A 1003M-05: Specification for Steel Sheet, Carbon, Metallic- and
Nonmetallic-
Coated for Cold-Formed Framing Members
ASTM A 1008/A 1008M-05b: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution
Hardened
and Bake Hardenable
ASTM A 1011/A 1011M-06: Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon,
Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability,
and
Ultra-High Strength
ASTM B 633-98: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C 33-03: Specification for Concrete Aggregates
ASTM C 144-04: Specification for Aggregate for Masonry Mortar
ASTM C 150-05: Specification for Portland Cement
ASTM C 185-02: Test Method for Air Content of Hydraulic Cement Mortar
ASTM C 260-01: Specification for Air-Entraining Admixtures for Concrete
ASTM C 494/C 494M-05a: Specification for Chemical Admixtures for Concrete
ASTM C 618-05: Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for
Use in
Concrete
ASTM C 947-03: Test Method for Flexural Properties of Thin-Section Glass-Fiber-
Reinforced
Concrete (Using Simple Beam with Third-Point Loading)
ASTM C 979-05: Specification for Pigments for Integrally Colored Concrete
ASTM C 1228-96 (Reapproved 2004): Practice for Preparing Coupons for Flexural and
Washout
Tests on Glass Fiber Reinforced Concrete
ASTM C 1229-94 (Reapproved 2001): Test Method for Determination of Glass Fiber Content
in
Glass Fiber Reinforced Concrete (GFRC) (Wash-Out Test)
ASTM C 1230-96 (Reapproved 2004): Test Method for Performing Tension Tests on Glass-
Fiber
Reinforced Concrete (GFRC) Bonding Pads
ASTM F 568M-04: Specification for Carbon and Alloy Steel Externally Threaded Metric
Fasteners

Master Painters Institute

MPI#79-2004: Alkyd Anti-Corrosive Metal Primer

Precast/Prestressed Concrete Institute

PCI MNL 128-2001: Recommended Practice for Glass Fiber Reinforced Concrete Panels
PCI MNL 130-2006: Manual for Quality Control for Plants and Production of Glass Fiber
Reinforced Concrete Products

Page 18 of 183

SSPC: The Society for Protective Coatings

SSPC-Paint 20 2002 (Revised 2004): Paint Specification No. 20 Zinc-Rich Primers (Type I,
"Inorganic," and Type II, "Organic")
SSPC-Paint 25 1997 (Revised 2004): Paint Specification No. 25: Zinc Oxide, Alkyd, Linseed
Oil
Primer for Use Over Hand Cleaned Steel, Type I and Type II
SSPC-SP 2 1982 (Revised 2004): Surface Preparation Specification No. 2: Hand Tool
Cleaning
SSPC-SP 6/NACE No. 3 2000 (Revised 2004): Joint Surface Preparation Standard
SSPCSSP 6/NACE No. 3: Commercial Blast Cleaning

SECTION 03532 - CONCRETE FLOOR TOPPING
American Association of State Highway and Transportation Officials

AASHTO M 182-2005: Specification for Burlap Cloth Made from Jute or Kenaf and Cotton
Mats

ASTM International

ASTM C 109/C 109M-05: Test Method for Compressive Strength of Hydraulic Cement
Mortars (Using 2-in. or [50-mm] Cube Specimens)
ASTM C 150-05: Specification for Portland Cement
ASTM C 171-03: Specification for Sheet Materials for Curing Concrete
ASTM C 309-06: Specification for Liquid Membrane-Forming Compounds for Curing
Concrete
ASTM C 404-06: Specification for Aggregates for Masonry Grout
ASTM C 881/C 881M-02: Specification for Epoxy-Resin-Base Bonding Systems for
Concrete
ASTM C 1059-99: Specification for Latex Agents for Bonding Fresh to Hardened Concrete
ASTM C 1077-06a: Practice for Laboratories Testing Concrete and Concrete Aggregates for
Use in Construction and Criteria for Laboratory Evaluation
ASTM D 1751-04: Specification for Preformed Expansion Joint Filler for Concrete Paving
and Structural Construction (Nonextruding and Resilient Bituminous Types)
ASTM D 1752-04a: Specification for Preformed Sponge Rubber Cork and Recycled PVC
Expansion Joint Fillers for Concrete Paving and Structural Construction
ASTM D 2240-05: Test Method for Rubber Property - Durometer Hardness
ASTM D 4263-83 (Reapproved 2005): Test Method for Indicating Moisture in Concrete by
the Plastic Sheet Method
ASTM E 329-07: Specification for Agencies Engaged in Construction Testing and/or
Inspection
ASTM E 1155-96 (Reapproved 2001): Test Method for Determining FF Floor Flatness and
FL Floor Levelness Numbers
ASTM E 1155M-96 (Reapproved 2001): Test Method for Determining FF Floor Flatness and
FL Floor Levelness Numbers [Metric]

Page 19 of 183

SECTION 03544 CEMENT BASED SCREED
ASTM International

ASTM A 185: Standard Specification for Steel Welded Wire Reinforcement, Plain, for
Concrete.
ASTM C 33: Standard Specification for Concrete Aggregates.
ASTM C 109M: Standard Test Method for Compressive Strength of Hydraulic Cement
Mortars (Using 50-mm Cube Specimens).
ASTM C 150-00: Specification for Portland cement.
ASTM C 881: Standard Specification for Epoxy-Resin-Base Bonding Systems for Concrete.
ASTM C 1059: Standard Specification for Latex Agents for Bonding Fresh To Hardened
Concrete.
ASTM D 1751: Standard Specification for Preformed Expansion Joint Filler for Concrete
Paving and Structural Construction.
ASTM D 1752: Standard Specification for Preformed Sponge Rubber and Cork expansion
Joint Fillers for Concrete Paving and Structural Construction.

SECTION 04810 - UNIT MASONRY ASSEMBLIES
American Concrete Institute

ACI 315-1999: Details and Detailing of Concrete Reinforcement.

American Concrete Institute, Structural Engineering Institute of the American Society of Civil
Engineers, and the Masonry Society

ACI 530.1/ASCE 6/TMS 602-2005: Specification for Masonry Structures

ASTM International

ASTM A 36/A 36M-05: Specification for Carbon Structural Steel
ASTM A 82/A 82M-05a: Specification for Steel Wire, Plain, for Concrete Reinforcement
ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 240/A 240M-07: Specification for Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 276-06: Specification for Stainless Steel Bars and Shapes
ASTM A 307-04: Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile
Strength
ASTM A 563-04: Specification for Carbon and Alloy Steel Nuts
ASTM A 563M-06: Specification for Carbon and Alloy Steel Nuts (Metric)
ASTM A 580/A 580M-06: Specification for Stainless Steel Wire
ASTM A 615/A 615M-07: Specification for Deformed and Plain Billet-Steel Bars for
Concrete Reinforcement
ASTM A 641/A 641M-03: Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A 653/A 653M-06a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 951/A 951M-06: Specification for Steel Wire for Masonry Joint Reinforcement
ASTM A 996/A 996M-06a: Specification for Rail-Steel and Axle-Steel Deformed Bars for
Concrete Reinforcement
ASTM A 1008/A 1008M-07: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
Page 20 of 183

High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution
Hardened, and Bake Hardenable
ASTM B 32-04: Specification for Solder Metal
ASTM B 117-07: Practice for Operating Salt Spray (Fog) Apparatus
ASTM B 370-03: Specification for Copper Sheet and Strip for Building Construction
ASTM B 633-07: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C 55-06: Specification for Concrete Building Brick
ASTM C 62-05: Specification for Building Brick (Solid Masonry Units Made from Clay or
Shale)
ASTM C 67-07: Test Methods for Sampling and Testing Brick and Structural Clay Tile
ASTM C 90-06b: Specification for Loadbearing Concrete Masonry Units
ASTM C 91-05: Specification for Masonry Cement
ASTM C 109/C 109M-05: Test Method for Compressive Strength of Hydraulic Cement
Mortars (Using 2-in. or [50-mm] Cube Specimens)
ASTM C 126-99 (Reapproved 2005): Specification for Ceramic Glazed Structural Clay
Facing Tile, Facing Brick, and Solid Masonry Units
ASTM C 140-06: Test Methods for Sampling and Testing Concrete Masonry Units and
Related Units
ASTM C 143/C 143M-05a: Test Method for Slump of Hydraulic Cement Concrete
ASTM C 144-04: Specification for Aggregate for Masonry Mortar
ASTM C 150-07: Specification for Portland Cement
ASTM C 199-84 (Reapproved 2005): Test Method for Pier Test for Refractory Mortars
ASTM C 207-06: Specification for Hydrated Lime for Masonry Purposes
ASTM C 212-00 (Reapproved 2006): Specification for Structural Clay Facing Tile
ASTM C 216-07: Specification for Facing Brick (Solid Masonry Units Made from Clay or
Shale)
ASTM C 270-07: Specification for Mortar for Unit Masonry
ASTM C 315-07: Specification for Clay Flue Liners and Chimney Pots
ASTM C 395-01 (Reapproved 2006): Specification for Chemical-Resistant Resin Mortars
ASTM C 404-06: Specification for Aggregates for Masonry Grout
ASTM C 476-02: Specification for Grout for Masonry
ASTM C 494/C 494M-05a: Specification for Chemical Admixtures for Concrete
ASTM C 503-05: Specification for Marble Dimension Stone
ASTM C 549-06: Specification for Perlite Loose Fill Insulation
ASTM C 568-03: Specification for Limestone Dimension Stone
ASTM C 578-07: Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM C 615-03: Specification for Granite Dimension Stone
ASTM C 616-03: Specification for Quartz-Based Dimension Stone
ASTM C 652-05a: Specification for Hollow Brick (Hollow Masonry Units Made from Clay
or Shale)
ASTM C 744-05: Specification for Prefaced Concrete and Calcium Silicate Masonry Units
ASTM C 780-06a: Test Method for Preconstruction and Construction Evaluation of Mortars
for Plain and Reinforced Unit Masonry
ASTM C 920-05: Specification for Elastomeric Joint Sealants
ASTM C 954-04: Specification for Steel Drill Screws for the Application of Gypsum Panel
Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84
mm) in Thickness
ASTM C 979-05: Specification for Pigments for Integrally Colored Concrete
ASTM C 1019-05: Test Method for Sampling and Testing Grout
ASTM C 1093-06: Practice for Accreditation of Testing Agencies for Unit Masonry
ASTM C 1261-05: Specification for Firebox Brick for Residential Fireplaces
ASTM C 1283-07: Practice for Installing Clay Flue Lining
ASTM C 1289-06: Specification for Faced Rigid Cellular Polyisocyanurate Thermal
Insulation Board
ASTM C 1314-03b: Test Method for Compressive Strength of Masonry Prisms
Page 21 of 183

ASTM C 1329-05: Specification for Mortar Cement
ASTM C 1405-05a: Specification for Glazed Brick (Single Fired, Brick Units)
ASTM C 1506-03: Test Method for Water Retention of Hydraulic Cement-Based Mortars and
Plasters
ASTM C 1623-06: Specification for Manufactured Concrete Masonry Lintels
ASTM C 1634-06: Specification for Concrete Facing Brick
ASTM D 226-06: Specification for Asphalt-Saturated Organic Felt Used in Roofing and
Waterproofing
ASTM D 1056-07: Specification for Flexible Cellular Materials - Sponge or Expanded
Rubber
ASTM D 2000-06a: Classification System for Rubber Products in Automotive Applications
ASTM D 2287-96 (Reapproved 2001): Specification for Nonrigid Vinyl Chloride Polymer
and Copolymer Molding and Extrusion Compounds
ASTM D 4637-04: Specification for EPDM Sheet Used in Single-Ply Roof Membrane
ASTM E 119-07: Test Methods for Fire Tests of Building Construction and Materials
ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM E 514-06: Test Method for Water Penetration and Leakage Through Masonry
ASTM F 568M-04: Specification for Carbon and Alloy Steel Externally Threaded Metric
Fasteners
ASTM F 593-02: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594-02: Specification for Stainless Steel Nuts
ASTM F 738M-02: Specification for Stainless Steel Metric Bolts, Screws, and Studs
ASTM F 836M-02: Specification for Style 1 Stainless Steel Metric Nuts
ASTM F 1941-00 (Reapproved 2006): Specification for Electrodeposited Coatings on
Threaded Fasteners (Unified Inch Screw Threads (UN/UNR))
ASTM F 1941M-05: Specification for Electrodeposited Coatings on Threaded Fasteners
(Metric)

The Brick Industry Association

BIA Technical Notes 20-2006: Cleaning Brickwork

Indiana Limestone Institute of America, Inc.

Indiana Limestone Handbook. 21st ed. 2003.

International Code Council

International Building Code. 2009.

Marble Institute of America

Dimensional Stone - Design Manual VI. 2003.

National Concrete Masonry Association

NCMA TEK 8-2A (1998): Removal of Stains from Concrete Masonry Walls

Sheet Metal and Air Conditioning Contractors' National Association

Architectural Sheet Metal Manual. 2003.

SECTION 04851 - DIMENSION STONE CLADDING
Page 22 of 183

ACI International; American Society of Civil Engineers; and The Masonry Society

ACI 530.1/ASCE 6/TMS 602-02: Specification for Masonry Structures

The Aluminum Association, Inc.

AA ADM-1-00: The Aluminum Design Manual

American Architectural Manufacturers Association

AAMA 501.2-2003: Field Check of Installed Storefronts, Curtain Walls, and Sloped Glazing
Systems for Water Leakage
American Institute of Steel Construction

Code of Standard Practice for Steel Buildings and Bridges. 2000.
Specification for Structural Steel Buildings - Allowable Stress Design and Plastic Design.
1989.

American Iron and Steel Institute

North American Specification for the Design of Cold-Formed Steel Structural Members.
2001.

American Society of Civil Engineers

ASCE 7-02: Minimum Design Loads for Buildings and Other Structures
ASCE 8-02: Specification for the Design of Cold-Formed Stainless Steel Structural Members

American Welding Society

AWS D1.1/D1.1M-02: Structural Welding Code - Steel
AWS D1.2/D1.2M-02: Structural Welding Code - Aluminum
AWS D1.3-98: Structural Welding Code - Sheet Steel

ASTM International

ASTM A 36/A 36M-03a: Specification for Carbon Structural Steel
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 276-03: Specification for Stainless Steel Bars and Shapes
ASTM A 307-02: Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile
Strength
ASTM A 500-03: Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural Tubing in Rounds and Shapes
ASTM A 513-00: Specification for Electric-Resistance-Welded Carbon and Alloy Steel
Mechanical Tubing
ASTM A 563-00: Specification for Carbon and Alloy Steel Nuts
ASTM A 563M-01: Specification for Carbon and Alloy Steel Nuts [Metric]
ASTM A 653/A 653M-03: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 780-01: Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized Coatings
Page 23 of 183

ASTM A1008/A 1008M-03: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High- Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability
ASTM B 221-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM C 97-02: Test Methods for Absorption and Bulk Specific Gravity of Dimension Stone
ASTM C 114-03: Test Methods for Chemical Analysis of Hydraulic Cement
ASTM C 119-03: Terminology Relating to Dimension Stone
ASTM C 144-03: Specification for Aggregate for Masonry Mortar
ASTM C 150-02a: Specification for Portland Cement
ASTM C 170-90 (Reapproved 1999): Test Method for Compressive Strength of Dimension
Stone
ASTM C 207-91 (Reapproved 1997): Specification for Hydrated Lime for Masonry Purposes
ASTM C 270-03: Specification for Mortar for Unit Masonry
ASTM C 503-99: Specification for Marble Dimension Stone (Exterior)
ASTM C 568-99: Specification for Limestone Dimension Stone
ASTM C 615-99: Specification for Granite Dimension Stone
ASTM C 616-99: Specification for Quartz-Based Dimension Stone
ASTM C 629-99: Specification for Slate Dimension Stone
ASTM C 880-98: Test Method for Flexural Strength of Dimensional Stone
ASTM C 1201-91 (Reapproved 2001): Test Method for Structural Performance of Exterior
Dimension Stone Cladding Systems by Uniform Static Air Pressure Difference
ASTM C 1242-03: Guide for the Selection, Design, and Installation of Exterior Dimension
Stone Anchors and Anchoring Systems
ASTM C 1354-96: Test Method for Strength of Individual Stone Anchorages in Dimension
Stone
ASTM C 1526-02: Specification for Serpentine Dimension Stone
ASTM C 1527-02: Specification for Travertine Dimension Stone
ASTM E 72-02: Methods of Conducting Strength Tests of Panels for Building Construction
ASTM E 283-91 (Reapproved 1999): Test Method for Determining the Rate of Air Leakage
through Exterior Windows, Curtain Walls, and Doors under Specified Pressure Difference
across the Specimen
ASTM E 329-02: Specification for Agencies Engaged in Testing and/or Inspection of
Materials Used in Construction
ASTM E 331-00: Test Method for Water Penetration of Exterior Windows, Skylights, Doors,
and Curtain Wallsby Uniform Static Air Pressure Difference
ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM F 436-02: Specification for Hardened Steel Washers
ASTM F 436M-93 (Reapproved 2000): Specification for Hardened Steel Washers [Metric]
ASTM F 568M-02: Specification for Carbon and Alloy Steel Externally Threaded Metric
Fasteners
ASTM F 593-02: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594-02: Specification for Stainless Steel Nuts
ASTM F 738M-02: Specification for Stainless Steel Metric Bolts, Screws, and Studs
ASTM F 836M-02: Specification for Style 1 Stainless Steel Metric Nuts

Page 24 of 183

Indiana Limestone Institute of America, Inc.

Indiana Limestone Handbook. 21st ed. 2003.

Marble Institute of America

Dimension Stone - Design Manual IV. 1991.

Master Painters Institute

MPI#76-00: Quick Dry Alkyd Metal Primer
MPI#96-00: Quick Dry Enamel, Gloss

Metal Framing Manufacturers Association

MFMA-3-1999: Metal Framing Standards Publication

National Building Granite Quarries Association, Inc.

Specifications for Architectural Granite. 1997.

SSPC: The Society for Protective Coatings

SSPC-PA 1 2000: Paint Application Specification No. 1: Shop, Field, and Maintenance
Painting of Steel
SSPC-Paint 20 1982 (Revised 1991): Paint Specification No. 20: Zinc-Rich Primers (Type I,
"Inorganic," and Type II, "Organic")
SSPC-Paint 29 1991 (Revised 2000): Paint Specification No. 29: Zinc Dust Sacrificial
Primer, Performance-Based
SSPC-SP 6/NACE No. 3 2000: Joint Surface Preparation Standard SSPC-SP 6/NACE No. 3:
Commercial Blast Cleaning

SECTION 05500 - METAL FABRICATIONS
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Standards for Anodized Architectural Aluminum

American Institute of Steel Construction

Specification for Structural Steel Buildings. 2005.

American National Standards Institute

ANSI A14.3-2002: American National Standard for Ladders-Fixed-Safety Requirements

American Welding Society

AWS D1.1/D1.1M-2006: Structural Welding Code - Steel
AWS D1.2/D1.2M-2003: Structural Welding Code - Aluminum
AWS D1.6-1999: Structural Welding Code - Stainless Steel

Page 25 of 183

ASME International

ASME A17.1-2004: Safety Code for Elevators and Escalators
ASME B18.2.1-1996: Square and Hex Bolts and Screws Inch Series
ASME B18.2.3.8M-1981 (Reaffirmed 2005): Metric Hex Lag Screws
ASME B18.6.1-1981 (Reaffirmed 1997): Wood Screws (Inch Series)
ASME B18.6.3-2003: Machine Screws and Machine Screw Nuts
ASME B18.6.7M-1999 (Reaffirmed 2005): Metric Machine Screws
ASME B18.21.1-1999 (Reaffirmed 2005): Lock Washers (Inch Series)
ASME B18.21.2M-1999 (Reaffirmed 2005): Lock Washers (Metric Series)
ASME B18.22M-1981 (Reaffirmed 2005): Metric Plain Washers
ASME B18.22.1-1965 (Reaffirmed 2003): Plain Washers

ASTM International

ASTM A 27/A 27M-05: Specification for Steel Castings, Carbon, for General Application
ASTM A 36/A 36M-05: Specification for Carbon Structural Steel
ASTM A 47/A 47M-99 (Reapproved 2004): Specification for Ferritic Malleable Iron Castings
ASTM A 48/A 48M-03: Specification for Gray Iron Castings
ASTM A 53/A 53M-06a: Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated,
Welded and Seamless
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 240/A 240M-06: Specification for Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 276-06: Specification for Stainless Steel Bars and Shapes
ASTM A 283/A 283M-03: Specification for Low and Intermediate Tensile Strength Carbon
Steel Plates
ASTM A 307-04: Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile
Strength
ASTM A 325-06: Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi
Minimum Tensile Strength
ASTM A 325M-05: Specification for Structural Bolts, Steel, Heat Treated 830 MPa
Minimum Tensile Strength [Metric]
ASTM A 489-04: Specification for Carbon Steel Lifting Eyes
ASTM A 500-03a: Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural Tubing in Rounds and Shapes
ASTM A 563-04a: Specification for Carbon and Alloy Steel Nuts
ASTM A 563M-06: Specification for Carbon and Alloy Steel Nuts [Metric]
ASTM A 653/A 653M-06: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 780-01: Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized Coatings
ASTM A 786/A 786M-05: Specification for Hot-Rolled Carbon, Low-Alloy, High-Strength
Low- Alloy, and Alloy Steel Floor Plates
ASTM A 793-96 (Reapproved 2001): Specification for Rolled Floor Plate, Stainless Steel
ASTM A 1008/A 1008M-06a: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution
Hardened, and Bake Hardenable
ASTM B 26/B 26M-05: Specification for Aluminum-Alloy Sand Castings
ASTM B 36/B 36M-06: Specification for Brass Plate, Sheet, Strip, and Rolled Bar
Page 26 of 183

ASTM B 151/B 151M-05: Specification for Copper-Nickel-Zinc Alloy (Nickel Silver) and
Copper-Nickel Rod and Bar
ASTM B 209-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 221-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 455-05: Specification for Copper-Zinc-Lead Alloy (Leaded-Brass) Extruded Shapes
ASTM B 584-06a: Specification for Copper Alloy Sand Castings for General Applications
ASTM B 632/B 632M-02: Specification for Aluminum-Alloy Rolled Tread Plate
ASTM B 633-98: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C 1107-05: Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM D 1187-97 (Reapproved 2002): Specification for Asphalt-Base Emulsions for Use as
Protective Coatings for Metal
ASTM E 119-05a: Test Methods for Fire Tests of Building Construction and Materials
ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM F 568M-04: Specification for Carbon and Alloy Steel Externally Threaded Metric
Fasteners
ASTM F 593-02: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594-02: Specification for Stainless Steel Nuts
ASTM F 738M-02: Specification for Stainless Steel Metric Bolts, Screws, and Studs
ASTM F 836M-02: Specification for Style 1 Stainless Steel Metric Nuts
ASTM F 1554-04: Specification for Anchor Bolts, Steel, 36, 55, and 105-ksi Yield Strength
ASTM F 1941-00 (Reapproved 2006): Specification for Electrodeposited Coatings on
Threaded Fasteners [Unified Inch Screw Threads (UN/UNR)]
ASTM F 1941M-05: Specification for Electrodeposited Coatings on Threaded Fasteners
[Metric]
ASTM F 2329-05: Specification for Zinc Coating, Hot-Dip, Requirements for Application to
Carbon and Alloy Steel Bolts, Screws, Washers, Nuts, and Special Threaded Fasteners

International Code Council

International Building Code. 2009.

Master Painters Institute

MPI#20-2002: Epoxy Zinc-Rich Primer
MPI#79-2004: Alkyd Anti-Corrosive Metal Primer

Metal Framing Manufacturers Association

MFMA-4-2004: Metal Framing Standards Publication

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

SSPC: The Society for Protective Coatings

SSPC-PA 1 2000 (Revised 2004): Paint Application Specification No. 1: Shop, Field, and
Maintenance Painting of Steel
SSPC-Paint 20 2002 (Revised 2004): Paint Specification No. 20: Zinc-Rich Primers (Type I,
Page 27 of 183

"Inorganic," and Type II, "Organic")
SSPC-SP 3 1982 (Revised 2004): Surface Preparation Specification No. 3: Power Tool
Cleaning
SSPC-SP 6/NACE No. 3 2000 (Revised 2004): Joint Surface Preparation Standard SSPCSP
6/NACE No. 3: Commercial Blast Cleaning

SECTION 05521 - PIPE AND TUBE RAILINGS
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Standards for Anodized Architectural Aluminum
AAMA 2604-2005: Voluntary Specification, Performance Requirements and Test Procedures
for High Performing Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2005: Voluntary Specification, Performance Requirements and Test Procedures
for Superior Performing Organic Coatings on Aluminum Extrusions and Panels

American Welding Society

AWS D1.1/D1.1M-2006: Structural Welding Code - Steel
AWS D1.2/D1.2M-2003: Structural Welding Code - Aluminum
AWS D1.6-99: Structural Welding Code - Stainless Steel

ASTM International

ASTM A 36/A 36M-05: Specification for Carbon Structural Steel
ASTM A 47/A 47M-99 (Reapproved 2004): Specification for Ferritic Malleable Iron Castings
ASTM A 48/A 48M-03: Specification for Gray Iron Castings
ASTM A 53/A 53M-05: Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated,
Welded and Seamless
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 240/A 240M-06: Specification for Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 312/A 312M-01a: Specification for Seamless, Welded, and Heavily Cold Worked
Austenitic Stainless Steel Pipes
ASTM A 500-03a: Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural Tubing in Rounds and Shapes
ASTM A 510-06: Specification for General Requirements for Wire Rods and Coarse Round
Wire, Carbon Steel
ASTM A 510M-06: Specification for General Requirements for Wire Rods and Coarse
Round Wire, Carbon Steel [Metric]
ASTM A 513-06a: Specification for Electric-Resistance-Welded Carbon and Alloy Steel
Mechanical Tubing
ASTM A 554-03: Specification for Welded Stainless Steel Mechanical Tubing
ASTM A 580/A 580M-06: Specification for Stainless Steel Wire
ASTM A 653/A 653M-06: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 743/A 743M-06: Specification for Castings, Iron-Chromium, Iron-Chromium-
Nickel, Corrosion-Resistant, for General Application
ASTM A 780-01: Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Page 28 of 183

Galvanized Coatings
ASTM A 1008/A 1008M-06a: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability
ASTM A 1011/A 1011M-06b: Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon,
Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability,
Solution Hardened, and Bake Hardenable
ASTM B 26/B 26M-05: Specification for Aluminum-Alloy Sand Castings
ASTM B 209-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 210-04: Specification for Aluminum and Aluminum-Alloy Drawn Seamless Tubes
ASTM B 210M-05: Specification for Aluminum and Aluminum-Alloy Drawn Seamless
Tubes [Metric]
ASTM B 211-03: Specification for Aluminum and Aluminum-Alloy Bar, Rod, and Wire
ASTM B 211M-03: Specification for Aluminum and Aluminum-Alloy Bar, Rod, and Wire
[Metric]
ASTM B 221-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 247-02a: Specification for Aluminum and Aluminum-Alloy Die Forgings, Hand
Forgings, and Rolled Ring Forgings
ASTM B 247M-02a: Specification for Aluminum and Aluminum-Alloy Die Forgings, Hand
Forgings, and Rolled Ring Forgings [Metric]
ASTM B 429/B 429M-06: Specification for Aluminum-Alloy Extruded Structural Pipe and
Tube
ASTM B 633-98: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C 1107-05: Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM D 1187-97 (Reapproved 2002): Specification for Asphalt-Base Emulsions for Use as
Protective Coatings for Metal
ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM E 894-88 (Reapproved 2004): Test Method for Anchorage of Permanent Metal
Railing Systems and Rails for Buildings
ASTM E 935-00 (Reapproved 2006): Test Methods for Performance of Permanent Metal
Railing Systems and Rails for Buildings
ASTM F 593-02: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594-02: Specification for Stainless Steel Nuts
ASTM F 738M-02: Specification for Stainless Steel Metric Bolts, Screws, and Studs
ASTM F 836M-02a: Specification for Style 1 Stainless Steel Metric Nuts
ASTM F 1267-06: Specification for Metal, Expanded, Steel
ASTM F 1941-00 (Reapproved 2006): Specification for Electrodeposited Coatings on
Threaded Fasteners [Unified Inch Screw Threads (UN/UNR)]
ASTM F 1941M-05: Specification for Electrodeposited Coatings on Threaded Fasteners
[Metric]
ASTM F 2329-05: Specification for Zinc Coating, Hot-Dip, Requirements for Application to
Carbon and Alloy Steel Bolts, Screws, Washers, Nuts, and Special Threaded Fasteners

Page 29 of 183

Master Painters Institute

MPI#20-2002: Epoxy Zinc-Rich Primer
MPI#25-2002: Etching Cleaner
MPI#26-2003: Cementitious Galvanized Metal Primer
MPI#72-2006: Polyurethane, Two-Component Pigmented, Gloss
MPI#77-2002: Epoxy Cold Cured, Gloss
MPI#79-2004: Alkyd Anti-Corrosive Metal Primer
MPI#80-2000: Vinyl Wash Primer
MPI#134-2006: Waterborne Galvanized Primer

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

SSPC: The Society for Protective Coatings

SSPC-PA 1 2000 (Revised 2004): Paint Application Specification No. 1: Shop, Field, and
Maintenance Painting of Steel
SSPC-Paint 20 2002 (Revised 2004): Paint Specification No. 20: Zinc-Rich Primers (Type I,
"Inorganic," and Type II, "Organic")
SSPC-Paint 29 2002: Paint Specification No. 29: Zinc Dust Sacrificial Primer, Performance-
Based
SSPC-SP 3 1982 (Revised 2004): Surface Preparation Specification No. 3: Power Tool
Cleaning
SSPC-SP 6/NACE No. 3 2000 (Revised 2004): Joint Surface Preparation Standard SSPCSP
6/NACE No. 3: Commercial Blast Cleaning

SECTION 05530 - GRATINGS
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Standards for Anodized Architectural Aluminum

American Society of Civil Engineers/Structural Engineering Institute

ASCE/SEI 7-2005: Minimum Design Loads for Buildings and Other Structures

American Welding Society

AWS D1.1/D1.1M-2006: Structural Welding Code - Steel
AWS D1.2/D1.2M-2003: Structural Welding Code - Aluminum
AWS D1.3-1998: Structural Welding Code - Sheet Steel
AWS D1.6-1999: Structural Welding Code - Stainless Steel

ASME International

ASME B18.21.1-1999 (Reaffirmed 2005): Lock Washers (Inch Series)
ASME B18.21.2M-1999 (Reaffirmed 2005): Lock Washers (Metric Series)
ASME B18.22.1-1965 (Reaffirmed 2003): Plain Washers
ASME B18.22M-1981 (Reaffirmed 2005): Metric Plain Washers

Page 30 of 183

ASTM International

ASTM A 36/A 36M-05: Specification for Carbon Structural Steel
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 276-06: Specification for Stainless Steel Bars and Shapes
ASTM A 307-04: Specification for Carbon Steel Bolts and Studs, 60,000 PSI Tensile
Strength
ASTM A 510-06: Specification for General Requirements for Wire Rods and Coarse Round
Wire, Carbon Steel
ASTM A 510M-03: Specification for General Requirements for Wire Rods and Coarse
Round Wire, Carbon Steel [Metric]
ASTM A 563-04a: Specification for Carbon and Alloy Steel Nuts
ASTM A 563M-06 Specification for Carbon and Alloy Steel Nuts [Metric]
ASTM A 653/A 653M-06: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 780-01: Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized Coatings
ASTM A 1011/A 1011M-06b: Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon,
Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability,
and Ultra-High Strength
ASTM A 1018/A 1018M-06: Specification for Steel, Sheet and Strip, Heavy-Thickness Coils,
Hot-Rolled, Carbon, Commercial, Drawing, Structural, High-Strength Low-Alloy, High-
Strength Low-Alloy with Improved Formability, and Ultra-High Strength Steel
ASTM B 209-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 221-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 633-98: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM D 1187-97 (Reapproved 2002): Specification for Asphalt-Base Emulsions for Use as
Protective Coatings for Metal
ASTM E 84-06: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 488-96 (Reapproved 2003): Test Method for Strength of Anchors in Concrete and
Masonry Elements
ASTM F 568M-04: Specification for Carbon and Alloy Steel Externally Threaded Metric
Fasteners
ASTM F 593-02: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594-02: Specification for Stainless Steel Nuts
ASTM F 738M-02: Specification for Stainless Steel Metric Bolts, Screws, and Studs
ASTM F 836M-02: Specification for Style 1 Stainless Steel Metric Nuts
ASTM F 1267-06: Specification for Metal, Expanded, Steel
ASTM F 1554-04: Specification for Anchor Bolts, Steel, 36, 55, and 105-ksi Yield Strength
ASTM F 1941-00 (Reapproved 2006): Specification for Electrodeposited Coatings on
Threaded Fasteners [Unified Inch Screw Threads (UN/UNR)]
ASTM F 1941M-05: Specification for Electrodeposited Coatings on Threaded Fasteners
[Metric]

Page 31 of 183

Master Painters Institute

MPI#20-2002: Epoxy Zinc-Rich Primer
MPI#79-2004: Alkyd Anti-Corrosive Metal Primer

National Association of Architectural Metal Manufacturers

NAAMM MBG 531-2000: Metal Bar Grating Manual
NAAMM MBG 532-2000: Heavy-Duty Metal Bar Grating Manual
Metal Finishes Manual for Architectural and Metal Products. 1988.

SSPC: The Society for Protective Coatings

SSPC-PA 1 2000 (Revised 2004): Paint Application Specification No. 1: Shop, Field, and
Maintenance Painting of Steel
SSPC-Paint 20 2002 (Revised 2004): Paint Specification No. 20: Zinc-Rich Primers (Type I,
"Inorganic," and Type II, "Organic")
SSPC-SP 6/NACE No. 3 2000 (Revised 2004): Joint Surface Preparation Standard SSPCSP
6/NACE No. 3: Commercial Blast Cleaning
SSPC-SP 7/NACE No. 4 2000 (Revised 2004): Joint Surface Preparation Standard SSPCSP
7/NACE No. 4: Brush-off Blast Cleaning

SECTION 05700 - ORNAMENTAL METAL
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Standards for Anodized Architectural Aluminum
AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 2604-2005: Voluntary Specification, Performance Requirements and Test Procedures
for High Performing Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2005: Voluntary Specification, Performance Requirements and Test Procedures
for Superior Performing Organic Coatings on Aluminum Extrusions and Panels

American Welding Society

AWS D1.1/D1.1M-2006: Structural Welding Code - Steel
AWS D1.2/D1.2M-2003: Structural Welding Code - Aluminum
AWS D1.3-1998: Structural Welding Code - Sheet Steel
AWS D1.6-1999: Structural Welding Code - Stainless Steel

ASTM International

ASTM A 29/A 29M-05: Specification for Steel Bars, Carbon and Alloy, Hot-Wrought,
General Requirements for
ASTM A 36/A 36M-05: Specification for Carbon Structural Steel
ASTM A 47/A 47M-99 (Reapproved 2004): Specification for Ferritic Malleable Iron Castings
ASTM A 48/A 48M-03: Specification for Gray Iron Castings
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 276-06: Specification for Stainless Steel Bars and Shapes
ASTM A 312/A 312M-06: Specification for Seamless, Welded, and Heavily Cold Worked
Page 32 of 183

Austenitic Stainless Steel Pipes
ASTM A 492-95 (Reapproved 2004): Specification for Stainless Steel Rope Wire
ASTM A 500-03a: Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural Tubing in Rounds and Shapes
ASTM A 513-06b: Specification for Electric-Resistance-Welded Carbon and Alloy Steel
Mechanical Tubing
ASTM A 554-03: Specification for Welded Stainless Steel Mechanical Tubing
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 743/A 743M-06: Specification for Castings, Iron-Chromium, Iron-Chromium-
Nickel, Corrosion-Resistant, for General Application
ASTM A 780-01 (Reapproved 2006): Practice for Repair of Damaged and Uncoated Areas of
Hot-Dip Galvanized Coatings
ASTM A 1008/A 1008M-07: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution
Hardened, and Bake Hardenable
ASTM B 26/B 26M-05: Specification for Aluminum-Alloy Sand Castings
ASTM B 36/B 36M-06: Specification for Brass Plate, Sheet, Strip, and Rolled Bar
ASTM B 43-98 (Reapproved 2004): Specification for Seamless Red Brass Pipe, Standard
Sizes
ASTM B 62-02: Specification for Composition Bronze or Ounce Metal Castings
ASTM B 75-02: Specification for Seamless Copper Tube
ASTM B 75M-99 (Reapproved 2005): Specification for Seamless Copper Tube [Metric]
ASTM B 135-02: Specification for Seamless Brass Tube
ASTM B 135M-00 (Reapproved 2006): Specification for Seamless Brass Tube [Metric]
ASTM B 152/B 152M-06a: Specification for Copper Sheet, Strip, Plate, and Rolled Bar
ASTM B 209-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 210-04: Specification for Aluminum and Aluminum-Alloy Drawn Seamless Tubes
ASTM B 210M-05: Specification for Aluminum and Aluminum-Alloy Drawn Seamless
Tubes [Metric]
ASTM B 221-06: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-06: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 247-02a: Specification for Aluminum and Aluminum-Alloy Die Forgings, Hand
Forgings, and Rolled Ring Forgings
ASTM B 247M-02a: Specification for Aluminum and Aluminum-Alloy Die Forgings, Hand
Forgings, and Rolled Ring Forgings [Metric]
ASTM B 249/B 249M-06: Specification for General Requirements for Wrought Copper and
Copper-Alloy Rod, Bar, Shapes and Forgings
ASTM B 265-06b: Specification for Titanium and Titanium Alloy Strip, Sheet, and Plate
ASTM B 348-06a: Specification for Titanium and Titanium Alloy Bars and Billets
ASTM B 429/B 429M-06: Specification for Aluminum-Alloy Extruded Structural Pipe and
Tube
ASTM B 455-05: Specification for Copper-Zinc-Lead Alloy (Leaded Brass) Extruded Shapes
ASTM B 483/B 483M-03: Specification for Aluminum and Aluminum-Alloy Drawn Tubes
for General Purpose Applications
ASTM B 584-06a: Specification for Copper Alloy Sand Castings for General Applications
ASTM B 633-07: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM B 824-04: Specification for General Requirements for Copper Alloy Castings
ASTM D 1187-97 (Reapproved 2002): Specification for Asphalt-Base Emulsions for Use as
Protective Coatings for Metal
ASTM E 488-96 (Reapproved 2003): Test Method for Strength of Anchors in Concrete and
Page 33 of 183

Masonry Elements
ASTM F 593-02: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594-02: Specification for Stainless Steel Nuts
ASTM F 738M-02: Specification for Stainless Steel Metric Bolts, Screws, and Studs
ASTM F 836M-02: Specification for Style 1 Stainless Steel Metric Nuts
ASTM F 1941-00 (Reapproved 2006): Specification for Electrodeposited Coatings on
Threaded Fasteners (Unified Inch Screw Threads (UN/UNR))
ASTM F 1941M-05: Specification for Electrodeposited Coatings on Threaded Fasteners
[Metric]

Master Painters Institute

MPI#20-2002: Epoxy Zinc-Rich Primer
MPI#25-2002: Etching Cleaner
MPI#26-2003: Cementitious Galvanized Metal Primer
MPI#72-2006: Polyurethane, Two-Component Pigmented, Gloss
MPI#77-2002: Epoxy Cold Cured, Gloss
MPI#79-2004: Alkyd Anti-Corrosive Metal Primer
MPI#80-2000: Vinyl Wash Primer
MPI#134-2006: Waterborne Galvanized Primer

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

National Ornamental & Miscellaneous Metals Association (1535 Pennsylvania Ave., McDonough,
GA 30253; 888-516-8585)

Voluntary Joint Finish Standards. 1994.

SSPC: The Society for Protective Coatings

SSPC-PA 1 2000 (Revised 2004): Paint Application Specification No. 1: Shop, Field, and
Maintenance Painting of Steel
SSPC-Paint 20 2002 (Revised 2004): Paint Specification No. 20: Zinc-Rich Primers (Type I,
"Inorganic," and Type II, "Organic")
SSPC-SP 6/NACE No. 3 2000 (Revised 2004): Joint Surface Preparation Standard SSPCSP
6/NACE No. 3: Commercial Blast Cleaning
SSPC-SP 7/NACE No. 4 2004: Joint Surface Preparation Standard SSPC-SP 7/NACE No. 4:
Brush-off Blast Cleaning

SECTION 05721 - ORNAMENTAL RAILINGS
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Standards for Anodized Architectural Aluminum
AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 2604-2005: Voluntary Specification, Performance Requirements and Test Procedures
for High Performing Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2005: Voluntary Specification, Performance Requirements and Test Procedures
for Superior Performing Organic Coatings on Aluminum Extrusions and Panels
AAMA Aluminum Curtain Wall Series No. 12-1987: Structural Properties of Glass

Page 34 of 183

American Welding Society

AWS D1.1/D1.1M-2006: Structural Welding Code - Steel
AWS D1.2/D1.2M-2003: Structural Welding Code - Aluminum
AWS D1.6-1999: Structural Welding Code - Stainless Steel

ASTM International

ASTM A 29/A 29M-05: Specification for Steel Bars, Carbon and Alloy, Hot-Wrought,
General Requirements for
ASTM A 36/A 36M-05: Specification for Carbon Structural Steel
ASTM A 47/A 47M-99 (Reapproved 2004): Specification for Ferritic Malleable Iron Castings
ASTM A 48/A 48M-03: Specification for Gray Iron Castings
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 240/A 240M-06: Specification for Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 276-06: Specification for Stainless Steel Bars and Shapes
ASTM A 312/A 312M-06: Specification for Seamless, Welded, and Heavily Cold Worked
Austenitic Stainless Steel Pipes
ASTM A 492-95 (Reapproved 2004): Specification for Stainless Steel Rope Wire
ASTM A 500-03a: Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural Tubing in Rounds and Shapes
ASTM A 510-06: Specification for General Requirements for Wire Rods and Coarse Round
Wire, Carbon Steel
ASTM A 510M-06: Specification for General Requirements for Wire Rods and Coarse
Round Wire, Carbon Steel [Metric]
ASTM A 513-06b: Specification for Electric-Resistance-Welded Carbon and Alloy Steel
Mechanical Tubing
ASTM A 554-03: Specification for Welded Stainless Steel Mechanical Tubing
ASTM A 580/A 580M-06: Specification for Stainless Steel Wire
ASTM A 653/A 653M-06: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 743/A 743M-06: Specification for Castings, Iron-Chromium, Iron-Chromium-
Nickel, Corrosion-Resistant, for General Application
ASTM A 780-01 (Reapproved 2006): Practice for Repair of Damaged and Uncoated Areas of
Hot-Dip Galvanized Coatings
ASTM A 1008/A 1008M-07: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution
Hardened, and Bake Hardenable
ASTM A 1011/A 1011M-06b: Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon,
Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability,
and Ultra-High Strength
ASTM B 26/B 26M-05: Specification for Aluminum-Alloy Sand Castings
ASTM B 36/B 36M-06: Specification for Brass Plate, Sheet, Strip, and Rolled Bar
ASTM B 43-98 (Reapproved 2004): Specification for Seamless Red Brass Pipe, Standard
Sizes
ASTM B 62-02: Specification for Composition Bronze or Ounce Metal Castings
ASTM B 75-02: Specification for Seamless Copper Tube
ASTM B 75M-99 (Reapproved 2005): Specification for Seamless Copper Tube [Metric]
ASTM B 135-02: Specification for Seamless Brass Tube
Page 35 of 183

ASTM B 135M-00 (Reapproved 2006): Specification for Seamless Brass Tube [Metric]
ASTM B 152/B 152M-06a: Specification for Copper Sheet, Strip, Plate, and Rolled Bar
ASTM B 209-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 210-04: Specification for Aluminum and Aluminum-Alloy Drawn Seamless Tubes
ASTM B 210M-05: Specification for Aluminum and Aluminum-Alloy Drawn Seamless
Tubes [Metric]
ASTM B 211-03: Specification for Aluminum and Aluminum-Alloy Bar, Rod, and Wire
ASTM B 211M-03: Specification for Aluminum and Aluminum-Alloy Bar, Rod, and Wire
[Metric]
ASTM B 221-06: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-06: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 247-02a: Specification for Aluminum and Aluminum-Alloy Die Forgings, Hand
Forgings, and Rolled Ring Forgings
ASTM B 247M-02a: Specification for Aluminum and Aluminum-Alloy Die Forgings, Hand
Forgings, and Rolled Ring Forgings [Metric]
ASTM B 249/B 249M-06: Specification for General Requirements for Wrought Copper and
Copper-Alloy Rod, Bar, Shapes and Forgings
ASTM B 429/B 429M-06: Specification for Aluminum-Alloy Extruded Structural Pipe and
Tube
ASTM B 455-05: Specification for Copper-Zinc-Lead Alloy (Leaded Brass) Extruded Shapes
ASTM B 584-06a: Specification for Copper Alloy Sand Castings for General Applications
ASTM B 633-07: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM B 824-04: Specification for General Requirements for Copper Alloy Castings
ASTM C 1048-04: Specification for Heat-Treated Flat Glass - Kind HS, Kind FT Coated and
Uncoated Glass
ASTM C 1107-05: Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM C 1172-03: Specification for Laminated Architectural Flat Glass
ASTM D 1187-97 (Reapproved 2002): Specification for Asphalt-Base Emulsions for Use as
Protective Coatings for Metal
ASTM D 4802-02: Specification for Poly(Methyl Methacrylate) Acrylic Plastic Sheet
ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM E 894-88 (Reapproved 2004): Test Method for Anchorage of Permanent Metal
Railing Systems and Rails for Buildings
ASTM E 935-00 (Reapproved 2006): Test Methods for Performance of Permanent Metal
Railing Systems and Rails for Buildings
ASTM F 593-02: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594-02: Specification for Stainless Steel Nuts
ASTM F 738M-02: Specification for Stainless Steel Metric Bolts, Screws, and Studs
ASTM F 836M-02: Specification for Style 1 Stainless Steel Metric Nuts
ASTM F 1267-06: Specification for Metal, Expanded, Steel
ASTM F 1941-00 (Reapproved 2006): Specification for Electrodeposited Coatings on
Threaded Fasteners (Unified Inch Screw Threads [UN/UNR])
ASTM F 1941M-05: Specification for Electrodeposited Coatings on Threaded Fasteners
[Metric]

Page 36 of 183

Code of Federal Regulations

16 CFR 1201-2006: Safety Standard for Architectural Glazing Materials

Glass Association of North America

Engineering Standards Manual. 2001.

Master Painters Institute

MPI#20-2002: Epoxy Zinc-Rich Primer
MPI#25-2002: Etching Cleaner
MPI#26-2003: Cementitious Galvanized Metal Primer
MPI#72-2006: Polyurethane, Two-Component Pigmented, Gloss
MPI#77-2002: Epoxy Cold Cured, Gloss
MPI#79-2004: Alkyd Anti-Corrosive Metal Primer
MPI#80-2000: Vinyl Wash Primer
MPI#134-2006: Waterborne Galvanized Primer

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

National Ornamental & Miscellaneous Metals Association (1535 Pennsylvania Ave., McDonough,
GA 30253; 888-516-8585)

Voluntary Joint Finish Standards. 1994.

NFPA

NFPA 70-2005: National Electrical Code

SSPC: The Society for Protective Coatings

SSPC-PA 1 2000 (Revised 2004): Paint Application Specification No. 1: Shop, Field, and
Maintenance Painting of Steel
SSPC-Paint 20 2002 (Revised 2004): Paint Specification No. 20: Zinc-Rich Primers (Type I,
"Inorganic," and Type II, "Organic")
SSPC-SP 6/NACE No. 3 2000 (Revised 2004): Joint Surface Preparation Standard SSPCSP
6/NACE No. 3: Commercial Blast Cleaning
SSPC-SP 7/NACE No. 4 2004: Joint Surface Preparation Standard SSPC-SP 7/NACE No. 4:
Brush-off Blast Cleaning

SECTION 06105 - MISCELLANEOUS CARPENTRY
American Forest & Paper Association

WCD 1-2001: Details for Conventional Wood Frame Construction. (Available in PDF at
www.awc.org)
Page 37 of 183

American Wood Protection Association

AWPA M4-2001: Care of Preservative-Treated Wood Products
AWPA U1-2007: Use Category System: User Specification for Treated Wood

ASME International

ASME B18.2.1-1996: Square and Hex Bolts and Screws (Inch Series)
ASME B18.2.3.8M-1981 (Revised 1999): Metric Hex Lag Screws
ASME B18.6.1-1981 (Revised 1997): Wood Screws (Inch Series)

ASTM International

ASTM A 153/A 153M-05: Specification for Zinc-Coating (Hot-Dip) of Iron and Steel
Hardware
ASTM A 307-07b: Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile
Strength
ASTM A 563-07a: Specification for Carbon and Alloy Steel Nuts
ASTM A 563M-07: Specification for Carbon and Alloy Steel Nuts [Metric]
ASTM A 653/A 653M-07: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM B 633-07: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C 954-07: Specification for Steel Drill Screws for the Application of Gypsum Panel
Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84
mm) in Thickness
ASTM C 1002-07: Specification for Steel Self-Piercing Tapping Screws for the Application
of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
ASTM D 2898-07: Practice for Accelerated Weathering of Fire-Retardant-Treated Wood for
Fire Testing
ASTM D 3201-08: Test Method for Hygroscopic Properties of Fire-Retardant Wood and
Wood- Based Products
ASTM D 3498-03: Specification for Adhesives for Field-Gluing Plywood to Lumber Framing
for Floor Systems
ASTM D 5664-02: Test Method for Evaluating the Effects of Fire-Retardant Treatments and
Elevated Temperatures on Strength Properties of Fire-Retardant Treated Lumber
ASTM D 6841-03: Practice for Calculating Design Value Treatment Adjustment Factors for
Fire- Retardant-Treated Lumber
ASTM E 84-08a: Test Method for Surface-Burning Characteristics of Building Materials
ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM F 568M-07: Specification for Carbon and Alloy Steel Externally Threaded Metric
Fasteners
ASTM F 593-02: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594-02: Specification for Stainless Steel Nuts
ASTM F 738M-02: Specification for Stainless Steel Metric Bolts, Screws, and Studs
ASTM F 836M-02: Specification for Style 1 Stainless Steel Metric Nuts
ASTM F 1667-05: Specification for Driven Fasteners: Nails, Spikes, and Staples

Page 38 of 183

California Department of Health Services

Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using
Small- Scale Environmental Chambers. 2004.

Code of Federal Regulations

40 CFR - Protection of Environment, Chapter I - Environmental Protection Agency, Part 59 -
"National Volatile Organic Compound Emission Standards for Consumer and Commercial
Products," Subpart D - "National Volatile Organic Compound Emission Standards for
Architectural Coatings." 2007.

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

ICC Evaluation Service, Inc.

NES NER-272-2004: Power Driven Staples and Nails for Use in All Types of Building
Construction

International Code Council, Inc.

International Building Code. 2009.
International Residential Code for One- and Two-Family Dwellings. 2006.

National Lumber Grades Authority

Standard Grading Rules for Canadian Lumber. 2003.

Northeastern Lumber Manufacturers' Association

Standard Grading Rules for Northeastern Lumber. 2003. (Available in PDF at
www.nelma.org)

The Southern Pine Inspection Bureau

Standard Grading Rules for Southern Pine Lumber. 2002.

U.S. Department of Commerce, National Institute of Standards and Technology

DOC PS 1-1995: U.S. Product Standard for Construction and Industrial Plywood
DOC PS 20-1994: American Softwood Lumber Standard

West Coast Lumber Inspection Bureau

Standard No. 17-1996: Grading Rules for West Coast Lumber

Western Wood Products Association

Western Lumber Grading Rules. 1998.

Page 39 of 183

SECTION 06401 - EXTERIOR ARCHITECTURAL WOODWORK
American Hardboard Association

AHA A135.4-95: Basic Hardboard

American National Standards Institute

ANSI A208.2-2002: Medium Density Fiberboard (MDF) for Interior Applications

American Wood-Preservers' Association

AWPA C2-01: Lumber, Timbers, Bridge Ties and Mine Ties - Preservative Treatment by
Pressure Process
AWPA C9-00: Plywood - Preservative Treatment by Pressure Process
AWPA C20-99: Structural Lumber - Fire-Retardant Treatment by Pressure Processes
AWPA C27-99: Plywood - Fire-Retardant Treatment by Pressure Processes
AWPA M4-01: Care of Preservative-Treated Wood Products
AWPA N1-01: All Millwork Products - Preservative Treatment by Nonpressure Process
AWPA P8-00: Oil-Borne Preservatives

Architectural Woodwork Institute

Architectural Woodwork Quality Standards. 8th ed. Version 1.0. 2003.

ASTM International

ASTM D 523-89 (Reapproved 1999): Test Method for Specular Gloss

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

U.S. Department of Commerce, National Institute of Standards and Technology

DOC PS 1-95: U.S. Product Standard for Construction and Industrial Plywood

Woodwork Institute (formerly Woodwork Institute of California)

Manual of Millwork. 2003.

SECTION 06402 - INTERIOR ARCHITECTURAL WOODWORK
American Hardboard Association

AHA A135.4-95: Basic Hardboard

American National Standards Institute

ANSI A208.1-1999: Particleboard
ANSI A208.2-2002: Medium Density Fiberboard (MDF) for Interior Applications
Page 40 of 183

American Wood-Preservers' Association

AWPA C20-99: Structural Lumber - Fire-Retardant Treatment by Pressure Processes
AWPA C27-99: Plywood - Fire-Retardant Treatment by Pressure Processes

Architectural Woodwork Institute

Architectural Woodwork Quality Standards. 8th ed. Version 1.0. 2003.

ASTM International

ASTM C 1036-01: Specification for Flat Glass
ASTM C 1048-97b: Specification for Heat-Treated Flat Glass - Kind HS, Kind FT Coated
and Uncoated Glass
ASTM C 1503-01: Specification for Silvered Flat Glass Mirror
ASTM D 523-89 (Reapproved 1999): Test Method for Specular Gloss
ASTM D 2559-00: Specification for Adhesives for Structural Laminated Wood Products for
Use under Exterior (Wet Use) Exposure Conditions
ASTM D 5456-01a: Specification for Evaluation of Structural Composite Lumber Products
ASTM E 84-01: Test Method for Surface Burning Characteristics of Building Materials

Builders Hardware Manufacturers Association

BHMA A156.9-2003: Cabinet Hardware
BHMA A156.11-1999: Cabinet Locks
BHMA A156.18-2000: Materials and Finishes

Code of Federal Regulations

40 CFR, Part 59, Subpart D-2001: National Volatile Organic Compound Emission Standards
for Architectural Coatings

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

Glass Association of North America

Glazing Manual. 1997.

Hardwood Plywood & Veneer Association

HPVA HP-1-2000: Hardwood and Decorative Plywood
International Solid Surface Fabricators Association

ISSFA-2-01: Classification and Standards Publication of Solid Surfacing Material

Laminating Materials Association

LMA EDG-1-1992: Voluntary Product Standard and Typical Physical Properties of
Edgebanding Materials
LMA SAT-1-1998: Voluntary Product Standard and Typical Physical Properties of Saturated
Paper Overlays
Page 41 of 183

National Electrical Manufacturers Association

NEMA LD 3-00 (Revised 2002): High Pressure Decorative Laminates

NFPA

NFPA 252-99: Fire Tests of Door Assemblies

U.S. Department of Commerce, National Institute of Standards and Technology

DOC PS 1-95: U.S. Product Standard for Construction and Industrial Plywood

Woodwork Institute (formerly Woodwork Institute of California)

Manual of Millwork. 2003.

SECTION 06620 - CAST PLASTIC FABRICATIONS
ASTM International

ASTM D 256: Standard Test Methods for Determining the Izod Pendulum Impact Resistance
of Plastics.
ASTM D 638: Standard Test Method for Tensile Properties of Plastics.
ASTM D 648: Standard Test Method for Deflection Temperature of Plastics under Flexural
Load in the Edgewise Position.
ASTM D 695: Standard Test Method for Compressive Properties of Rigid Plastics.
ASTM D 790: Standard Test Methods for Flexural Properties of Unreinforced and Reinforced
Plastics and Electrical Insulating Materials.
ASTM E 84: Standard Test Method for Surface Burning Characteristics of Building
Materials.

SECTION 07130 - EPDM SHEET WATERPROOFING

ACI International

ACI 301-99: Specification for Structural Concrete

ASTM International

ASTM C 67-03a: Test Methods for Sampling and Testing Brick and Structural Clay Tile
ASTM C 140-02a: Test Methods of Sampling and Testing Concrete and Masonry Units and
Related Units
ASTM C 272-01: Test Method for Water Absorption of Core Materials for Structural
Sandwich Constructions
ASTM C 578-03: Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM D 1621-00: Test Method for Compressive Properties of Rigid Cellular Plastics
ASTM D 4258-83 (Reapproved 1999): Practice for Surface Cleaning Concrete for Coating
ASTM D 4263-83 (Reapproved 1999): Test Method for Indicating Moisture in Concrete by
the Plastic Sheet Method
ASTM D 5843-95 (Reapproved 2000): Guide for Application of Fully Adhered Vulcanized
Rubber Sheets Used in Waterproofing
ASTM D 5957-98: Guide for Flood Testing Horizontal Waterproofing Installations
Page 42 of 183

ASTM D 6134-97: Specification for Vulcanized Rubber Sheets Used in Waterproofing
Systems
ASTM D 6506-01: Specification for Asphalt Based Protection Board for Below-Grade
Waterproofing

SECTION 07141 - COLD FLUID-APPLIED WATERPROOFING
ACI International

ACI 301-1999: Specification for Structural Concrete

ASTM International

ASTM C 67-03a: Test Methods for Sampling and Testing Brick and Structural Clay Tile
ASTM C 140-03: Test Methods for Sampling and Testing Concrete and Masonry Units and
Related Units
ASTM C 272-01: Test Method for Water Absorption of Core Materials for Structural
Sandwich Constructions
ASTM C 578-04a: Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM C 836-03: Specification for High Solids Content, Cold Liquid-Applied Elastomeric
Waterproofing Membrane for Use with Separate Wearing Course
ASTM C 898-01: Guide for Use of High Solids Content, Cold Liquid-Applied Elastomeric
Waterproofing Membrane with Separate Wearing Course
ASTM C 920-02: Specification for Elastomeric Joint Sealants
ASTM C 1193-00: Guide for Use of Joint Sealants
ASTM C 1471-00: Guide for the Use of High Solids Content Cold Liquid-Applied
Elastomeric Waterproofing Membrane on Vertical Surfaces
ASTM D 1621-04a: Test Method for Compressive Properties of Rigid Cellular Plastics
ASTM D 4258-83 (Reapproved 1999): Practice for Surface Cleaning Concrete for Coating
ASTM D 4259-88 (Reapproved 1999): Practice for Abrading Concrete
ASTM D 4263-83 (Reapproved 1999): Test Method for Indicating Moisture in Concrete by
the Plastic Sheet Method
ASTM D 5957-98: Guide for Flood Testing Horizontal Waterproofing Installations
ASTM D 6506-01: Specification for Asphalt Based Protection Board for Below-Grade
Waterproofing

SECTION 07180 - TRAFFIC COATINGS
American Association of State Highway and Transportation Officials

AASHTO M 247-91 (Revised 2000): Specification for Traffic Beads Used in Traffic Paints
AASHTO M 248-91 (Revised 2000): Specification for Ready-Mixed White and Yellow
Traffic Paints

ASTM International

ASTM C 920-02: Specification for Elastomeric Joint Sealants
ASTM C 957-93 (Reapproved 1998): Specification for High-Solids Content, Cold Liquid-
Applied Elastomeric Waterproofing Membrane with Integral Wearing Surface
ASTM C 1127-01: Guide for Use of High Solids Content, Cold Liquid-Applied Elastomeric
Waterproofing Membrane with an Integral Wearing Surface
ASTM C 1193-00: Guide for Use of Joint Sealants
ASTM D 4258-83 (Reapproved 1999): Practice for Surface Cleaning Concrete for Coating
Page 43 of 183

ASTM D 4259-88 (Reapproved 1999): Practice for Abrading Concrete
ASTM D 4263-83 (Reapproved 1999): Test Method for Indicating Moisture in Concrete by
the Plastic Sheet Method
ASTM D 5957 (Reapproved 1998): Guide for Flood Testing Horizontal Waterproofing
Installations
ASTM E 108-00: Test Methods for Fire Tests of Roof Coverings

Code of Federal Regulations

40 CFR 59, Subpart D-2000: National Volatile Organic Compound Emission Standards for
Architectural Coatings

Federal Specification

FS TT-P-1952D: Paint, Traffic and Airfield Marking, Waterborne. 1994.

Underwriters Laboratories Inc.

UL 790-04: Standard Test Methods for Fire Tests of Roof Coverings

SECTION 07190 - WATER REPELLENTS
ASTM International

ASTM C 67-07: Test Methods of Sampling and Testing Brick and Structural Clay Tile
ASTM C 97-02: Test Methods for Absorption and Bulk Specific Gravity of Dimension Stone
ASTM C 140-07: Test Methods of Sampling and Testing Concrete Masonry Units and
Related Units
ASTM C 642-06: Test Methods for Density, Absorption, and Voids in Hardened Concrete
ASTM C 1195-03: Test Method for Absorption of Architectural Cast Stone
ASTM C 1515-01: Guide for Cleaning of Exterior Dimension Stone, Vertical and Horizontal
Surfaces, New or Existing
ASTM D 1653-03: Test Methods for Water Vapor Transmission of Organic Coating Films
ASTM D 5107-03: Practice for Preparatory Surface Cleaning of Architectural Sandstone
ASTM D 5703-95 (Reapproved 2007): Practice for Preparatory Surface Cleaning for Clay
Brick Masonry
ASTM D 6532-00 (Reapproved 2006): Test Method for Evaluation of the Effect of Clear
Water Repellent Treatments on Water Absorption of Hydraulic Cement Mortar Specimens
ASTM E 96/E 96M-05: Test Methods for Water Vapor Transmission of Materials
ASTM E 514-06: Test Method for Water Penetration and Leakage through Masonry
ASTM E 1857-97 (Reapproved 2004): Guide for Selection of Cleaning Techniques for
Masonry, Concrete, and Stucco Surfaces
ASTM G 154-06: Practice for Operating Fluorescent Light Apparatus for UV Exposure of
Nonmetallic Materials

Master Painters Institute

MPI Approved Products List. Updated quarterly. (See
www.paintinfo.com/mpi/approved/index.htm.)

Transportation Research Board; National Cooperative Highway Research Program

NCHRP Report 244-1981: Concrete Sealers for Protection of Bridge Structures. Series II

Page 44 of 183

SECTION 07210 - BUILDING INSULATION
ASTM International

ASTM C 552-03: Specification for Cellular Glass Thermal Insulation
ASTM C 553-02: Specification for Mineral Fiber Blanket Thermal Insulation for Commercial
and Industrial Applications
ASTM C 578-07: Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM C 612-04: Specification for Mineral Fiber Block and Board Thermal Insulation
ASTM C 665-06: Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame
Construction and Manufactured Housing
ASTM C 739-05b: Specification for Cellulosic Fiber Loose-Fill Thermal Insulation
ASTM C 764-06a: Specification for Mineral Fiber Loose-Fill Thermal Insulation
ASTM C 920-05: Specification for Elastomeric Joint Sealants
ASTM C 1015-06: Practice for Installation of Cellulosic and Mineral Fiber Loose-Fill
Thermal Insulation
ASTM C 1029-05a: Specification for Spray-Applied Rigid Cellular Polyurethane Thermal
Insulation
ASTM C 1149-06: Specification for Self-Supported Spray Applied Cellulosic Thermal
Insulation
ASTM C 1158-05: Practice for Installation and Use of Radiant Barrier Systems (RBS) in
Building Construction
ASTM C 1289-07: Specification for Faced Rigid Cellular Polyisocyanurate Thermal
Insulation Board
ASTM C 1313-05: Specification for Sheet Radiant Barriers for Building Construction
Applications
ASTM C 1320-05: Practice for Installation of Mineral Fiber Batt and Blanket Thermal
Insulation for Light Frame Construction
ASTM C 1321-04: Practice for Installation and Use of Interior Radiation Control Coating
Systems (IRCCS) in Building Construction
ASTM C 1371-04a: Test Method for Determination of Emittance of Materials near Room
Temperature Using Portable Emissometers
ASTM D 4397-02: Specification for Polyethylene Sheeting for Construction, Industrial, and
Agricultural Applications
ASTM D 5116-06: Guide for Small-Scale Environmental Chamber Determinations of
Organic Emissions from Indoor Materials/Products
ASTM E 84-07: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 136-04: Test Method for Behavior of Materials in a Vertical Tube Furnace at 750
deg C

Cellulose Insulation Manufacturers Association

Bulletin #2: Standard Practice for Installing Cellulose Insulation. 1998.

SECTION 07531 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING
American Society of Civil Engineers/Structural Engineering Institute

ASCE/SEI 7-2005: Minimum Design Loads for Buildings and Other Structures

Page 45 of 183

ASTM International

ASTM C 67-03a: Test Methods of Sampling and Testing Brick and Structural Clay Tile
ASTM C 140-03: Test Methods for Sampling and Testing Concrete Masonry Units and
Related Units
ASTM C 208-95 (Reapproved 2001): Specification for Cellulosic Fiber Insulating Board
ASTM C 552-03: Specification for Cellular Glass Thermal Insulation
ASTM C 578-05: Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM C 728-05: Specification for Perlite Thermal Insulation Board
ASTM C 1177/C 1177M-04: Specification for Glass Mat Gypsum Substrate for Use as
Sheathing
ASTM C 1278/C 1278M-03: Specification for Fiber-Reinforced Gypsum Panel
ASTM C 1289-05: Specification for Faced Rigid Cellular Polyisocyanurate Thermal
Insulation Board
ASTM C 1396/C 1396M-04: Specification for Gypsum Board
ASTM D 41-05: Specification for Asphalt Primer Used in Roofing, Dampproofing, and
Waterproofing
ASTM D 312-00: Specification for Asphalt Used in Roofing
ASTM D 448-03a: Classification for Sizes of Aggregate for Road and Bridge Construction
ASTM D 1079-05a: Terminology Relating to Roofing and Waterproofing
ASTM D 2178-04: Specification for Asphalt Glass Felt Used in Roofing and Waterproofing
ASTM D 4263-83 (Reapproved 1999): Test Method for Indicating Moisture in Concrete by
the Plastic Sheet Method
ASTM D 4397-02: Specification for Polyethylene Sheeting for Construction, Industrial, and
Agricultural Applications
ASTM D 4637-04: Specification for EPDM Sheet Used in Single-Ply Roof Membrane
ASTM D 5019-96: Specification for Reinforced Non-Vulcanized Polymeric Sheet Used in
Roofing Membrane
ASTM D 6152-99 (Reapproved 2005): Specification for SEBS-Modified Mopping Asphalt
Used in Roofing
ASTM E 108-05: Test Methods for Fire Tests of Roof Coverings
ASTM E 119-05a: Test Methods for Fire Tests of Building Construction and Materials
ASTM E 1980-01: Practice for Calculating Solar Reflectance Index of Horizontal and Low-
Sloped Opaque Surfaces

Code of Federal Regulations

40 CFR 59, Subpart D-2006: National Volatile Organic Compound Emission Standards for
Architectural Coatings

Cool Roof Rating Council (1738 Excelsior Ave.; Oakland, CA 94602; 866-465-2523; 510-485-7175;
www.coolroofs.org)

CRRC-1-2005: Product Rating Program

FM Approvals

FM Approvals 4450-1989: Approval Standard for Class 1 Insulated Steel Deck Roofs (with
1992 Supplement)
FM Approvals 4470-1986: Approval Standard Class 1 Roof Covers (with 1987 and 1992
Supplements) RoofNav. Undated.

Page 46 of 183

FM Global

FM Global Loss Prevention Data Sheet 1-28-2005: Design Wind Loads
FM Global Loss Prevention Data Sheet 1-29-2005: Roof Deck Securement and Above-Deck
Roof Components

SPRI

SPRI RP-4-2002: Wind Design Standard for Ballasted Single-Ply Roofing Systems (ANSI)

U.S. Department of Commerce, National Institute of Standards and Technology

DOC PS 2-2004: Performance Standard for Wood-Based Structural-Use Panels

U.S. Department of Energy

DOE Roof Products Qualified Product List. Undated.

SECTION 07720 - ROOF ACCESSORIES
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum
AAMA 620-2002: Voluntary Specifications for High Performance Organic Coatings on Coil
Coated Architectural Aluminum Substrates
AAMA 621-2002: Voluntary Specification for High Performance Organic Coatings on Coil
Coated Architectural Hot Dipped Galvanized (HDG) and Zinc-Aluminum Coated Steel
Substrates
AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Pigmented Organic Coatings on Aluminum Extrusions and Panels

American Wood Protection Association

AWPA C2-2002: Lumber, Timber, Bridge Ties, and Mine Ties - Preservative Treatment by
Pressure Processes

ASTM International

ASTM A 36/A 36M-05: Specification for Carbon Structural Steel
ASTM A 53/A 53M-06a: Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated,
Welded and Seamless
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 240/A 240M-07: Specification for Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 500-03a: Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural Tubing in Rounds and Shapes
ASTM A 653/A 653M-07: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
Page 47 of 183

ASTM A 755/A 755M-03: Specification for Steel Sheet, Metallic Coated by the Hot-Dip
Process and Prepainted by the Coil-Coating Process for Exterior Exposed Building Products
ASTM A 780-01 (Reapproved 2006): Practice for Repair of Damaged and Uncoated Areas of
Hot-Dip Galvanized Coatings
ASTM A 792/A 792M-06a: Specification for Steel Sheet, 55% Aluminum-Zinc Alloy-Coated
by the Hot-Dip Process
ASTM A 1011/A 1011M-06b: Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon,
Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved
Formability, and Ultra-High Strength
ASTM B 209-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-06: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 221-06: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-06: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 370-03: Specification for Copper Sheet and Strip for Building Construction
ASTM C 208-95 (Reapproved 2001): Specification for Cellulosic Fiber Insulating Board
ASTM C 726-05: Specification for Mineral Fiber Roof Insulation Board
ASTM C 920-05: Specification for Elastomeric Joint Sealants
ASTM C 1289-07: Specification for Faced Rigid Cellular Polyisocyanurate Thermal
Insulation Board
ASTM C 1311-02: Specification for Solvent Release Sealants
ASTM D 226-06: Specification for Asphalt-Saturated Organic Felt Used in Roofing and
Waterproofing
ASTM D 256-06a: Test Methods for Determining the Izod Pendulum Impact Resistance of
Plastics
ASTM D 1187-97 (Reapproved 2002): Specification for Asphalt-Base Emulsions for Use as
Protective Coatings for Metal
ASTM D 2244-07: Practice for Calculation of Color Tolerances of Color Differences from
Instrumentally Measured Color Coordinates
ASTM D 4214-07: Test Methods for Evaluating the Degree of Chalking of Exterior Paint
Films
ASTM D 4397-02: Specification for Polyethylene Sheeting for Construction, Industrial and
Agricultural Applications
ASTM D 4586-07: Specification for Asphalt Roof Cement, Asbestos-Free
ASTM D 4802-02: Specification for Poly(Methyl Methacrylate) Acrylic Plastic Sheet
ASTM F 2329-05: Specification for Zinc Coating, Hot-Dip, Requirements for Application to
Carbon and Alloy Steel Bolts, Screws, Washers, Nuts, and Special Threaded Fasteners

Code of Federal Regulations

29 CFR - Labor, Chapter XVII - Occupational Safety and Health Administration, Department
of Labor, Part 1910 - "Occupational Safety and Health Standards," Subpart 1910.23 -
"Guarding Floor and Wall Openings and Holes." 2006.

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

NFPA

NFPA 204-2007: Smoke and Heat Venting

Page 48 of 183

SSPC: The Society for Protective Coatings

SSPC-SP 5/NACE No. 1 2000 (Revised 2004): Joint Surface Preparation Standard SSPC-SP
5/NACE No. 1: White Metal Blast Cleaning
SSPC-SP 8 1982 (Revised 2000): Surface Preparation Specification No. 8: Pickling

Underwriters Laboratories Inc.

UL 793-2003 (Rev. 2004): Automatically Operated Roof Vents for Smoke and Heat
UL 972-2006: Standard for Burglary Resisting Glazing Material

SECTION 07841 - THROUGH-PENETRATION FIRESTOP SYSTEMS
ASTM International

ASTM E 84-07: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 814-06: Test Method for Fire Tests of Through-Penetration Fire Stops

Code of Federal Regulations

40 CFR 59, Subpart D-2005: National Volatile Organic Compound Emission Standards for
Architectural Coatings

FM Global

FM Global 4991-2001: Approval of Firestop Contractors (FCIA)
Building Materials Approval Guide. 2007.

Intertek ETL SEMCO

Directory of Listed Building Products. 2007.

Underwriters Laboratories Inc.

UL 1479-2003: Fire Tests of Through-Penetration Firestops (ANSI)
Fire Resistance Directory. 2007.
Qualified Firestop Contractor Program Requirements. 2006.

SECTION 07920 - JOINT SEALANTS

ASTM International

ASTM C 834-05: Specification for Latex Sealants
ASTM C 919-02: Practice for Use of Sealants in Acoustical Applications
ASTM C 920-05: Specification for Elastomeric Joint Sealants
ASTM C 1021-01: Practice for Laboratories Engaged in Testing of Building Sealants
ASTM C 1087-00: Test Method for Determining Compatibility of Liquid-Applied Sealants
with Accessories Used in Structural Glazing Systems
ASTM C 1193-05a: Guide for Use of Joint Sealants
ASTM C 1247-98 (Reapproved 2004): Test Method for Durability of Sealants Exposed to
Continuous Immersion in Liquids
ASTM C 1248-06: Test Method for Staining of Porous Substrate by Joint Sealants
Page 49 of 183

ASTM C 1311-02: Specification for Solvent Release Sealants
ASTM C 1330-02: Specification for Cylindrical Sealant Backing for Use with Cold Liquid
Applied Sealants
ASTM C 1521-02a: Practice for Evaluating Adhesion of Installed Weatherproofing Sealant
Joints
ASTM E 90-04: Method for Laboratory Measurement of Airborne Sound Transmission Loss
of Building Partitions and Elements

Code of Federal Regulations

21 CFR 177.2600-2005: Rubber Articles Intended for Repeated Use
40 CFR, Part 59, Subpart D-2003: National Volatile Organic Compound Emission Standards
for Architectural Coatings

SECTION 08110 - STEEL DOORS AND FRAMES
American National Standards Institute

ANSI/DHI A115 Series (ANSI A115.1-1990 through ANSI A115.18-1994): Specifications
for Steel Door and Frame Preparation for Hardware
ANSI/NAAMM-HMMA 861-2000: Guide Specifications for Commercial Hollow Metal
Doors and Frames
ANSI/SDI A250.3-1999: Test Procedure and Acceptance Criteria for Factory Applied Finish
Painted Steel Surfaces for Steel Doors and Frames
ANSI/SDI A250.4-2001: Test Procedure and Acceptance Criteria for Physical Endurance for
Steel Doors and Hardware Reinforcings
ANSI/SDI A250.6-2003: Recommended Practice for Hardware Reinforcing on Standard Steel
Doors and Frames
ANSI/SDI A250.8-2003: Recommended Specifications for Standard Steel Doors and Frames
ANSI/SDI A250.10-2004: Test Procedure and Acceptance Criteria for Prime Painted Steel
Surfaces for Steel Doors and Frames
ANSI/SDI A250.11-2001: Recommended Erection Instructions for Steel Frames

ASTM International

ASTM A 153/A 153M-04: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 591/A 591M-98: Specification for Steel Sheet, Electrolytic Zinc-Coated, for Light
Coating Weight [Mass] Application
ASTM A 653/A 653M-04a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 1008/A 1008M-04b: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability
ASTM A 1011/A 1011M-04b: Specification for Steel, Sheet and Strip, Hot Rolled, Carbon,
Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved
Formability
ASTM C 143/C 143M-03: Test Method for Slump of Hydraulic Cement Concrete
ASTM C 476-02: Specification for Grout for Masonry
ASTM C 665-01: Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame
Construction and Manufactured Housing
ASTM C 1363-97: Test Method for the Thermal Performance of Building Assemblies by
Means of a Hot Box Apparatus
ASTM E 136-04: Test Method for Behavior of Materials in a Vertical Tube Furnace at 750
Degree C
Page 50 of 183

Hollow Metal Manufacturers Association; Division of National Association of Architectural Metal
Manufacturers

HMMA 840-1999: Installation and Storage of Hollow Metal Doors and Frames

International Conference of Building Officials

UBC Standard 7-2-1997: Fire Tests of Door Assemblies
UBC Standard 7-4-1997: Fire Tests of Fire Window Assemblies

NFPA

NFPA 80-1999: Fire Doors and Fire Windows (ANSI)
NFPA 105-2003: Installation of Smoke-Control Door Assemblies (ANSI)
NFPA 252-2003: Fire Test of Door Assemblies (ANSI)
NFPA 257-2000: Fire Test for Window and Glass Block Assemblies (ANSI)

SSPC: The Society for Protective Coatings

SSPC-Paint 12 1982 (Revised 2000): Paint Specification No. 12: Cold-Applied Asphalt
Mastic (Extra Thick Film)

Steel Door Institute

SDI 111C-2000: Recommended Louver Details for Standard Steel Doors
SDI 117-2000: Manufacturing Tolerances for Standard Steel Doors and Frames

Underwriters Laboratories Inc.

UL 9-2000: Fire Tests of Window Assemblies
UL 10B-2001: Fire Tests of Door Assemblies
UL 10C-2001: Positive Pressure Fire Tests of Door Assemblies
UL 1784-2001: Air Leakage Tests of Door Assemblies

SECTION 08211 - FLUSH WOOD DOORS
American Hardboard Association (This association no longer exists, but its publications are available
from the Composite Panel Association. The publication below is available in PDF at
www.pbmdf.com)

AHA A135.4-1995: Basic Hardboard (ANSI)

American National Standards Institute

ANSI A208.1-1999: Particleboard
ANSI A208.2-2002: Medium Density Fiberboard (MDF) for Interior Applications

Architectural Woodwork Institute

Architectural Woodwork Quality Standards Illustrated. 8th ed. Version 1.0. 2003.

Page 51 of 183

Door and Hardware Institute

DHI A115-W (Various Dates): Wood Door Hardware Standards, Hardware Preparation
DHI-WDHS-3-1996: Recommended Locations for Architectural Hardware for Wood Flush
Doors

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

International Conference of Building Officials

UBC Standard 7-2-1997: Fire Tests of Door Assemblies

National Electrical Manufacturers Association

NEMA LD 3-2000 with Errata: High Pressure Decorative Laminates (available in PDF at
www.nema.org)

NFPA

NFPA 80-99: Fire Doors and Fire Windows
NFPA 252-03: Fire Tests of Door Assemblies

Underwriters Laboratories Inc.

UL 10B-2001: Fire Tests of Door Assemblies
UL 10C-2001: Positive Pressure Fire Tests of Door Assemblies

Window & Door Manufacturers Association (Formerly: National Wood Window and Door
Association)

WDMA I.S.1-A-04: Architectural Wood Flush Doors
WDMA I.S.10-99: Specification for Testing Cellulosic Materials for Use in Fenestration
Products
WDMA TM-6-88: Test Method for Determining the Performance of Adhesive Bonds in
Doors Under Accelerated Aging Conditions
Woodwork Institute

Manual of Millwork. 2003.

SECTION 08212 - STILE AND RAIL WOOD DOORS
American Hardboard Association (This association no longer exists, but its publications are available
from the Composite Panel Association. The publication below is available in PDF at
www.pbmdf.com)

AHA A135.4-1995: Basic Hardboard

Page 52 of 183

American National Standards Institute

ANSI A208.1-1999: Particleboard
ANSI A208.2-2002: Medium Density Fiberboard (MDF) for Interior Applications

Architectural Woodwork Institute

Architectural Woodwork Quality Standards. 8th ed. Version 1.0. 2003.

ASTM International

ASTM C 920-05: Elastomeric Joint Sealants
ASTM D 5572-95 (Reapproved 2005): Adhesives Used in Finger Joints in Nonstructural
Lumber Products
ASTM D 5751-99 (Reapproved 2005): Adhesives Used for Laminate Joints in Nonstructural
Lumber Products

Code of Federal Regulations

16 CFR 1201-2005: Safety Standard for Architectural Glazing Materials

Door and Hardware Institute

DHI A115-W (Various Dates): Wood Door Hardware Standards, Hardware Preparation
DHI-WDHS-3-1996: Recommended Hardware Locations for Wood Flush Doors

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

International Conference of Building Officials

UBC Standard 7-2-1997: Fire Tests of Door Assemblies

NFPA

NFPA 80-1999: Fire Doors and Fire Windows
NFPA 252-2003: Fire Tests of Door Assemblies

Underwriters Laboratories Inc.

UL 10B-2001: Fire Tests of Door Assemblies
UL 10C-2001: Positive Pressure Fire Tests of Door Assemblies

Window & Door Manufacturers Association (formerly: National Wood Window and Door
Association)

NWWDA T.M.-10-1990: Screwholding Capacity Test
WDMA I.S.4-1999: Water-Repellent Preservative Non-Pressure Treatment for Millwork
WDMA I.S.6-1997: Industry Standard for Wood Stile and Rail Doors
WDMA I.S.6A-1999: Industry Standard for Architectural Stile and Rail Doors

Page 53 of 183

Woodwork Institute

Manual of Millwork. 2003.

SECTION 08311 - ACCESS DOORS AND FRAMES
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum

American Association of State Highway and Transportation Officials

AASHTO H20-2002: Contained in Standard Specifications for Highway Bridges, 17th
Edition

American National Standards Institute

ANSI H35.2-1997: Dimensional Tolerances for Aluminum Mill Products
ANSI H35.2(M)-2000: Dimensional Tolerances for Aluminum Mill Products

ASTM International

ASTM A 36/A 36M-03a: Specification for Carbon Structural Steel
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 153/A 153M-03: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 283/A 283M-03: Specification for Low and Intermediate Tensile Strength Carbon
Steel Plates
ASTM A 591/A 591M-98: Specification for Steel Sheet, Electrolytic Zinc-Coated, for Light
Coating Weight [Mass] Applications
ASTM A 653/A 653M-03: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 780-01: Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized Coatings
ASTM A 786/A 786M-00b: Specification for Hot-Rolled Carbon, Low-Alloy, High-Strength
Low-Alloy, and Alloy Steel Floor Plates
ASTM A 793-96 (Reapproved 2001): Specification for Rolled Floor Plate, Stainless Steel
ASTM A 924/A 924M-99: Specification for General Requirements for Steel Sheet, Metallic-
Coated by the Hot-Dip Process
ASTM A 1008/A 1008M-03: Specifications for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability
ASTM B 209-02a: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-03: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 221-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 632/B 632M-02: Specification for Aluminum-Alloy Rolled Tread Plate
ASTM E 119-00a: Test Methods for Fire Tests of Building Construction and Materials

Page 54 of 183

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

NFPA

NFPA 80-99: Fire Doors and Fire Windows
NFPA 252-99: Standard Method of Fire Tests for Door Assemblies

SSPC: The Society for Protective Coatings

SSPC-SP 1 1982 (Revised 2000): Surface Preparation Specification No. 1: Solvent Cleaning
SSPC-SP 5/NACE No. 1 2000: Joint Surface Preparation Standard SSPC-SP 5/NACE No. 1:
White Metal Blast Cleaning
SSPC-SP 8 2000: Surface Preparation Specification No. 8: Pickling
SSPC-Paint 20 1982 (Revised 1991): Paint Specification No. 20: Zinc-Rich Primers (Type I,
"Inorganic," and Type II, "Organic")

Underwriters Laboratories Inc.

UL 10B-97: Fire Tests of Door Assemblies
UL 263-03: Fire Tests of Building Construction and Materials

SECTION 08346 - SOUND-CONTROL DOOR ASSEMBLIES
ASTM International

ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 653/A 653M-06: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 1008/A 1008M-06: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution
Hardened, and
Bake Hardenable
ASTM A 1011/A 1011M-06a: Specification for Steel, Sheet and Strip, Hot Rolled, Carbon,
Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability,
and Ultra-High Strength
ASTM C 143/C 143M-05a: Test Method for Slump of Hydraulic Cement Concrete
ASTM C 476-02: Specification for Grout for Masonry
ASTM E 90-04: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss of Building Partitions and Elements
ASTM E 336-05: Method for Measurement of Airborne Sound Insulation in Buildings
ASTM E 413-04: Classification for Rating Sound Insulation
ASTM E 1408-91 (Reapproved 2000): Test Method for Laboratory Measurement of the
Sound Transmission Loss of Door Panels and Door Systems
ASTM F 2329-05: Specification for Zinc Coating, Hot-Dip, Requirements for Applications to
Carbon and Alloy Steel Bolts, Screws, Washers, Nuts and Special Threaded Fasteners

Door and Hardware Institute

DHI WDHS.3-1993: Recommended Locations for Architectural Hardware for Wood Flush
Doors

Page 55 of 183

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

Hollow Metal Manufacturers Association; Division of National Association of Architectural Metal
Manufacturers

NAAMM-HMMA 820-1987: Hollow Metal Frames
NAAMM-HMMA 831-1997: Recommended Hardware Locations for Custom Hollow Metal
Doors and Frames
NAAMM-HMMA 865-2003: Guide Specifications for Swinging Sound Control Hollow
Metal Doors and Frames (ANSI)

NFPA

NFPA 80-2007: Fire Doors and Other Opening Protectives
NFPA 105-2007: Standard for the Installation of Smoke Door Assemblies and Other Opening
Protectives
NFPA 252-2003: Fire Tests of Door Assemblies

Steel Door Institute

SDI A250.3-2005: Test Procedure and Acceptance Criteria for Factory Applied Finish
Coatings for Steel Doors and Frames (ANSI)
SDI A250.10-2004: Test Procedure and Acceptance Criteria for Prime Painted Steel Surfaces
for Steel Doors and Frames (ANSI)

Window & Door Manufacturers Association

WDMA 1.S.1-A-2004: Architectural Wood Flush Doors (ANSI)

Underwriters Laboratories Inc.

UL 10C-1998: Positive Pressure Fire Tests of Door Assemblies
UL 1784-2001: Air Leakage Tests of Door Assemblies

SECTION 08411 - ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
American Architectural Manufacturers Association

AAMA 501.1-2005: Standard Test Method for Water Penetration of Windows, Curtain Walls,
and Doors Using Dynamic Pressure
AAMA 501.2-2003: Quality Assurance and Diagnostic Water Leakage Field Check of
Installed Storefronts, Curtain Walls, and Sloped Glazing Systems
AAMA 501.4-2000 (Revised 2001): Recommended Static Test Method for Evaluating
Curtain Wall and Storefront Systems Subjected to Seismic and Wind Induced Interstory
Drifts
AAMA 501.5-2005: Test Method for Thermal Cycling of Exterior Walls
AAMA 506-2000 (Revised 2003): Voluntary Specifications for Hurricane Impact and Cycle
Testing of Fenestration Products
AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum
AAMA 701-2000: Voluntary Specifications for Pile Weatherstripping
AAMA 1503-1998: Voluntary Test Method for Thermal Transmittance and Condensation
Page 56 of 183

Resistance of Windows, Doors and Glazed Wall Sections
AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 2604-2002: Voluntary Specification, Performance Requirements and Test Procedures
for High Performance Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Superior Performing High Performance Organic Coatings on Aluminum Extrusions and
Panels

American Welding Society

AWS A5.10/A5.10M-1999: Specification for Bare Aluminum and Aluminum-Alloy Welding
Electrodes and Rods
AWS D1.2-2003: Structural Welding Code - Aluminum

ASTM International

ASTM A 36/A 36M-05: Specification for Carbon Structural Steel
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 153/A 153M-04: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 240/A 240M-05: Specification for Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 1008/A 1008M-04b: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability
ASTM A 1011/A 1011M-04a: Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon,
Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved
Formability
ASTM B 209-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 221-05: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-05: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 308/B 308M-02: Specification for Aluminum-Alloy 6061-T6 Standard Structural
Profiles
ASTM B 429-02: Specification for Aluminum-Alloy Extruded Structural Pipe and Tube
ASTM C 920-02: Specification for Elastomeric Joint Sealants
ASTM C 1184-00a: Specification for Structural Silicone Sealants
ASTM C 1401-02: Guide for Structural Sealant Glazing
ASTM D 2000-04: Classification System for Rubber Products in Automotive Applications
ASTM D 2287-96(2001): Specification for Nonrigid Vinyl Chloride Polymer and Copolymer
Molding and Extrusion Compounds
ASTM E 90-04: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss of Building Partitions and Elements
ASTM E 283-04: Test Method for Determining the Rate of Air Leakage through Exterior
Windows, Curtain Walls, and Doors under Specified Pressure Differences across the
Specimen
ASTM E 330-02: Test Method for Structural Performance of Exterior Windows, Doors,
Skylights and Curtain Walls by Uniform Static Air Pressure Difference
ASTM E 331-04: Test Method for Water Penetration of Exterior Windows, Skylights, Doors,
and Curtain Walls by Uniform Static Air Pressure Difference
ASTM E 413-04: Standard Classification for Rating Sound Insulation
Page 57 of 183

ASTM E 69903: Practice for Evaluation of Agencies Involved in Testing, Quality
Assurance, and Evaluating of Building Components
ASTM E 783-02: Test Method for Field Measurement of Air Leakage through Installed
Exterior Windows and Doors
ASTM E 1105-00: Test Method for Field Determination of Water Penetration of Installed
Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform or Cyclic Static Air
Pressure Difference
ASTM E 1332-90 (Reapproved 2003): Standard Classification for Determination of Outdoor-
Indoor Transmission Class
ASTM E 1886-05: Test Method for Performance of Exterior Windows, Curtain Walls, Doors,
and Impact Protective Systems Impacted by Missile(s) and Exposed to Cyclic Pressure
Differentials
ASTM E 1996-05: Specification for Performance of Exterior Windows, Curtain Walls, Doors
and Impact Protective Systems Impacted by Windborne Debris in Hurricanes

Builders Hardware Manufacturers Association

BHMA A156.1-2000: Butts and Hinges (ANSI)
BHMA A156.3-2001: Exit Devices (ANSI)
BHMA A156.4-2000: Door Controls - Closers (ANSI)
BHMA A156.5-2001: Auxiliary Locks & Associated Products (ANSI)
BHMA A156.6-2001: Architectural Door Trim (ANSI)
BHMA A156.8-2000: Door Controls - Overhead Stops and Holders (ANSI)
BHMA A156.16-2002: Auxiliary Hardware (ANSI)
BHMA A156.21-2001: Thresholds (ANSI)

International Code Council

ICC/ANSI A117.1-2003: Accessible and Usable Buildings and Facilities

SSPC: The Society for Protective Coatings

SSPC-Paint 12 1982: Paint Specification No. 12: Cold-Applied Asphalt Mastic (Extra Thick
Film)
SSPC-PS Guide No. 12.00 2002 (Revised 2004): Guide to Zinc-Rich Coating Systems
SSPC-SP COM 2004: Surface Preparation Specifications: Surface Preparation Commentary
for Steel and Concrete Substrates

Underwriters Laboratories Inc.

UL 305-1997: Panic Hardware

U.S. Architectural & Transportation Barriers Compliance Board

Americans with Disabilities Act (ADA) and Architectural Barriers Act (ABA) Accessibility
Guidelines for Buildings and Facilities. Adopted in 2004.

Page 58 of 183

SECTION 08460 - AUTOMATIC ENTRANCE DOORS

American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum
AAMA 701-2000: Voluntary Specifications for Pile Weatherstripping
AAMA 2603-2002: Performance Requirements and Test Procedures for Pigmented Organic
Coatings on Aluminum Extrusions and Panels
AAMA 2604-2002: High Performance Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2002: Superior Performing High Performance Organic Coatings on Aluminum
Extrusions and Panels

ASTM International

ASTM A 36/A 36M-04: Specification for Carbon Structural Steel
ASTM A 240/A 240M-02: Specification for Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 276-04: Specification for Stainless Steel Bars and Shapes
ASTM A 554-03: Specification for Welded Stainless Steel Mechanical Tubing
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 1008/A 1008M-04b: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability
ASTM A 1011/A 1011M-04a: Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon,
Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved
Formability
ASTM B 36/B 36M-01: Specification for Brass Plate, Sheet, Strip, and Rolled Bar
ASTM B 209-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 221-04a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-04: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM C 1107-02: Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM D 2000-04: Classification System for Rubber Products in Automotive Applications
ASTM D 2244-02: Test Method for Calculation of Color Tolerances and Color Differences
from Instrumentally Measured Color Coordinates
ASTM D 2287-96 (Reapproved 2001): Specification for Nonrigid Vinyl Chloride Polymer
and Copolymer Molding and Extrusion Compounds
ASTM D 4214-98: Test Methods for Evaluating the Degree of Chalking of Exterior Paint
Films
ASTM E 283-04: Test Method for Determining Rate of Air Leakage through Exterior
Windows, Curtain Walls, and Doors under Specified Pressure Differences across the
Specimen
ASTM E 1996-04: Specification for Performance of Exterior Windows, Curtain Walls, Doors
and Impact-Protective Systems Impacted by Windborne Debris in Hurricanes

Page 59 of 183

Builders Hardware Manufacturers Association

BHMA A156.1-2000: Butts and Hinges (ANSI)
BHMA A156.4-2000: Door Controls - Closers (ANSI)
BHMA A156.5-2001: Auxiliary Locks and Associated Products (ANSI)
BHMA A156.10-1999: Power Operated Pedestrian Doors (ANSI)
BHMA A156.16-2002: Auxiliary Hardware (ANSI)
BHMA A156.19-2002: Power Assist and Low Energy Power Operated Doors (ANSI)
BHMA A156.21-2001: Thresholds (ANSI)

Glass Association of North America

Glazing Manual. 2004.

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

NFPA

NFPA 70-2002: National Electrical Code

SSPC: The Society for Protective Coatings

SSPC-Paint 12 1982 (Revised 2000): Paint Specification No. 12: Cold-Applied Asphalt
Mastic (Extra Thick Film)
SSPC-PS Guide No. 12.00 1991: Guide to Zinc-Rich Coating Systems
SSPC-SP COM 2000: Surface Preparation Specifications: Surface Preparation Commentary
for Steel and Concrete Substrates

Structural Engineering Institute/American Society of Civil Engineers

SEI/ASCE 7-2002: Minimum Design Loads for Buildings and Other Structures

Underwriters Laboratories Inc.

UL 305-1997 (Revised 2004): Panic Hardware
UL 325-2002 (Revised 2003): Door, Drapery, Gate, Louver and Window Operators and
Systems

SECTION 08510 - STEEL WINDOWS

American Architectural Manufacturers Association

AAMA 502-2002: Voluntary Specification for Field Testing of Windows and Sliding Glass
Doors
AAMA 901-1996: Voluntary Specification for Rotary Operators in Window Applications
AAMA 904.1-2001: Voluntary Specification for Multi-Bar Hinges in Window Applications
AAMA 907-2005: Voluntary Specification for Corrosion Resistant Coatings on Carbon Steel
Components
AAMA 1503-1998: Voluntary Test Method for Thermal Transmittance and Condensation
Resistance of Windows, Doors and Glazed Wall Sections

Page 60 of 183

American Society of Civil Engineers/ Structural Engineering Institute

ASCE/SEI 7-2005: Minimum Design Loads for Buildings and Other Structures

ASTM International

ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel
Products
ASTM A 653/A 653M-05a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron
Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 780-01: Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized
Coatings
ASTM C 509-00: Specification for Elastomeric Cellular Preformed Gasket and Sealing
Material
ASTM C 864-05: Specification for Dense Elastomeric Compression Seal Gaskets, Setting
Blocks,
and Spacers
ASTM D 3656-04: Specification for Insect Screening and Louver Cloth Woven from Vinyl-
Coated
Glass Yarns
ASTM E 283-04: Test Method for Determining the Rate of Air Leakage through Exterior
Windows,
Curtain Walls, and Doors under Specified Pressure Differences across the Specimen
ASTM E 330-02: Test Method for Structural Performance of Exterior Windows, Curtain
Walls, and
Doors by Uniform Static Air Pressure Difference
ASTM E 331-00: Test Method for Water Penetration of Exterior Windows, Skylights, Doors,
and
Curtain Walls by Uniform Static Air Pressure Difference
ASTM E 405-04: Test Methods for Wear Testing Rotary Operators for Windows
ASTM E 1423-99: Practice for Determining the Steady State Thermal Transmittance of
Fenestration Systems
ASTM E 1886-05: Test Method for Performance of Exterior Windows, Curtain Walls, Doors,
and
Impact Protective Systems Impacted by Missile(s) and Exposed to Cyclic Pressure
Differentials
ASTM E 1996-05b: Specification for Performance of Exterior Windows, Curtain Walls,
Doors and
Impact Protective Systems Impacted by Windborne Debris in Hurricanes
ASTM E 2010-01: Test Method for Positive Pressure Fire Tests of Window Assemblies
ASTM E 2112-01: Practice for Installation of Exterior Windows, Doors and Skylights
ASTM F 588-04: Test Methods for Measuring the Forced Entry Resistance of Window
Assemblies,
Excluding Glazing Impact

National Electrical Manufacturers Association

NEMA ICS 1-2000 (Revised 2005): Industrial Control and Systems: General Requirements
NEMA ICS 2-2000 (Revised 2005): Industrial Control and Systems: Controllers, Contactors,
and
Overload Relays Rated 600 Volts
NEMA ICS 6-1993 (Revised 2001): Industrial Control and Systems Enclosures
Page 61 of 183

NEMA MG 1-2003 (Revised 2004): Motors and Generators

National Fenestration Rating Council

NFRC 100-2004: Procedure for Determining Fenestration Product U Factors
NFRC 200-2004: Procedure for Determining Fenestration Product Solar Heat Gain
Coefficients at
Normal Incidence
NFRC 500-2004: Procedure for Determining Fenestration Product Condensation Resistance
Values
NFPA

NFPA 70-2005: National Electrical Code
NFPA 80-1999: Fire Doors and Fire Windows
NFPA 257-2000: Fire Test for Windows and Glass Block Assemblies

SSPC: The Society for Protective Coatings

SSPC-SP 5/NACE No. 1 2000 (Revised 2004): Joint Surface Preparation Standard SSPC-SP
5/NACE No. 1: White Metal Blast Cleaning
SSPC-SP 8 1982 (Revised 2004): Surface Preparation Specification No. 8: Pickling
SSPC-Paint 20 2002 (Revised 2004): Paint Specification No. 20: Zinc-Rich Primers (Type I,
"Inorganic" and Type II, "Organic")

Steel Window Institute

The Architect's Guide to Steel Windows and Doors. Undated.

Underwriters Laboratories Inc.

UL 9-2000 (Revised 2005): Fire Tests of Window Assemblies (ANSI)
UL 33-2003 (Revised 2005): Heat Responsive Links for Fire-Protection Service (ANSI)

Uniform Building Code

UBC 7-4-1997: Fire Tests of Window Assemblies.

SECTION 08520 - ALUMINUM WINDOWS
American Architectural Manufacturers Association

AAMA 502-2002: Voluntary Specification for Field Testing of Windows and Sliding Glass
Doors
AAMA 505-1998: Dry Shrinkage and Composite Performance Thermal Cycling Test
Procedure
AAMA 506-2000: Voluntary Specification for Hurricane Impact and Cycle Testing of
Fenestration Products
AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum
AAMA 613-2002: Voluntary Performance Requirements and Test Procedures for Organic
Coatings on Plastic Profiles
AAMA 614-2002: Voluntary Specification, Performance Requirements and Test Procedures
for High Performance Organic Coatings on Plastic Profiles
AAMA 615-2002: Voluntary Specification, Performance Requirements and Test Procedures
Page 62 of 183

for Superior Performing Organic Coatings on Plastic Profiles
AAMA 620-2002: Voluntary Specifications for High Performance Organic Coatings on Coil
Coated Architectural Aluminum Substrates
AAMA 701/702-2000: Voluntary Specification for Pile Weatherstripping and Replaceable
Fenestration Weatherseals
AAMA 901-1996: Voluntary Specification for Rotary Operators in Window Applications
AAMA 902-1999: Voluntary Specification for Sash Balances
AAMA 904-2001: Voluntary Specification for Multi-Bar Hinges in Window Applications
AAMA 907-1996: Voluntary Specifications for Corrosion Resistant Coatings on Carbon Steel
Components
AAMA 910-1993: Voluntary "Life Cycle" Specifications and Test Methods for Architectural
Grade Windows and Sliding Glass Doors
AAMA 1503-1998: Voluntary Test Method for Thermal Transmittance and Condensation
Resistance of Windows, Doors, and Glazed Wall Sections
AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 2604-2002: Voluntary Specification, Performance Requirements and Test Procedures
for High Performance Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Superior Performing Organic Coatings on Aluminum Extrusions and Panels

American Architectural Manufacturers Association/Window & Door Manufacturers Association

AAMA/WDMA 101/I.S.2/NAFS-2002: North American Fenestration Standard Voluntary
Performance Specification for Windows, Skylights and Glass Doors (ANSI)

American Society of Civil Engineers

ASCE 7-02: Minimum Design Loads for Buildings and Other Structures

ASTM International

ASTM B 456-03: Specification for Electrodeposited Coatings of Copper Plus Nickel Plus
Chromium and Nickel Plus Chromium
ASTM B 633-98: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C 509-00: Specification for Elastomeric Cellular Preformed Gasket and Sealing
Material
ASTM C 864-99: Specification for Dense Elastomeric Compression Seal Gaskets, Setting
Blocks, and Spacers
ASTM C 1036-01: Specification for Flat Glass
ASTM D 3656-97: Specification for Insect Screening and Louver Cloth Woven from Vinyl-
Coated Glass Yarns
ASTM D 4726-02: Specification for Rigid Poly(Vinyl Chloride) (PVC) Exterior-Profile
Extrusions Used for Assembled Windows and Doors
ASTM E 90-02: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss of Building Partitions and Elements
ASTM E 405-89 (Reapproved 1996): Test Methods for Wear Testing Rotary Operators for
Windows
ASTM E 413-87 (Reapproved 1999): Classification for Rating Sound Insulation
ASTM E 1423-99: Practice for Determining the Steady State Thermal Transmittance of
Fenestration Systems
ASTM E 1886-02: Test Method for Performance of Exterior Windows, Curtain Walls, Doors,
and Storm Shutters Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials
ASTM E 1996-03: Specification for Performance of Exterior Windows, Curtain Walls, Doors
and Storm Shutters Impacted by Windborne Debris in Hurricanes
Page 63 of 183

ASTM F 588-97: Test Methods for Measuring the Forced Entry Resistance of Window
Assemblies, Excluding Glazing Impact

Federal Specification

FS RR-W-365A-1999: Wire Fabric (Insect Screening)

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

Glass Association of North America

Glazing Manual. 2004.

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

National Electrical Manufacturers Association

NEMA ICS 1-00: Industrial Control and Systems General Requirements (ANSI)
NEMA ICS 2-00: Industrial Control and Systems Controllers, Contactors, and Overload
Relays Rated 600 Volts (ANSI)
NEMA ICS 6-93: Industrial Control and Systems Enclosures
NEMA MG 1-03: Motors and Generators (ANSI)

National Fenestration Rating Council

NFRC 100-01: Procedure for Determining Fenestration Product U-Factors
NFRC 200-01: Procedure for Determining Fenestration Product Solar Heat Gain Coefficients
and Visual Transmittance at Normal Incidence

NFPA

NFPA 70-02: National Electrical Code

Screen Manufacturers Association

SMA 1004-87 (Reapproved 1998): Specifications for Aluminum Tubular Frame Screens for
Windows (ANSI)

Window & Door Manufacturers Association

WDMA T.M. 11-99: Factory Applied Pigmented Primer Coatings on Wood and Wood
Cellulosic Composites for Millwork
WDMA T.M. 12-99: Factory Applied Pigmented Coatings on Wood and Wood Cellulosic
Composites for Millwork

Page 64 of 183

SECTION 08800 - GLAZING
American Architectural Manufacturers Association

AAMA 800-2005: Voluntary Specifications and Test Methods for Sealants
AAMA GDSG-1-1987: Glass Design for Sloped Glazing
AAMA TIR-A7-1983: Sloped Glazing Guidelines

American National Standards Institute

ANSI Z97.1-2004: Safety Glazing Materials Used in Buildings - Safety Performance
Specifications and Methods of Test

American Society of Civil Engineers/Structural Engineering Institute

ASCE/SEI 7-2005: Minimum Design Loads for Buildings and Other Structures

ASTM International

ASTM C 509-00: Specification for Elastomeric Cellular Preformed Gasket and Sealing
Material
ASTM C 542-05: Specification for Lock-Strip Gaskets
ASTM C 716-00: Specification for Installing Lock-Strip Gaskets and Infill Glazing Materials
ASTM C 864-05: Specification for Dense Elastomeric Compression Seal Gaskets, Setting
Blocks, and Spacers
ASTM C 920-05: Specification for Elastomeric Joint Sealants
ASTM C 1021-01: Practice for Laboratories Engaged in the Testing of Building Sealants
ASTM C 1036-01: Specification for Flat Glass
ASTM C 1048-04: Specification for Heat-Treated Flat Glass - Kind HS, Kind FT Coated and
Uncoated Glass
ASTM C 1087-00: Test Method for Determining Compatibility of Liquid-Applied Sealants
with Accessories Used in Structural Glazing Systems
ASTM C 1115-00: Specification for Dense Elastomeric Silicone Rubber Gaskets and
Accessories
ASTM C 1172-03: Specification for Laminated Architectural Flat Glass
ASTM C 1281-03: Specification for Preformed Tape Sealants for Glazing Applications
ASTM C 1330-02: Specification for Cylindrical Sealant Backing for Use with Cold Liquid
Applied Sealants
ASTM C 1376-03: Specification for Pyrolytic and Vacuum Deposition Coatings on Flat Glass
ASTM E 1300-04: Practice for Determining Load Resistance of Glass in Buildings
ASTM E 1886-05: Test Method for Performance of Exterior Windows, Curtain Walls, Doors,
and Impact Protective Systems Impacted by Missile(s) and Exposed to Cyclic Pressure
Differentials
ASTM E 1996-06: Specification for Performance of Exterior Windows, Curtain Walls, Doors
and Impact Protective Systems Impacted by Windborne Debris in Hurricanes
ASTM E 2190-02: Specification for Insulating Glass Unit Performance and Evaluation

Code of Federal Regulations

16 CFR 1201-2006: Safety Standard for Architectural Glazing Materials
40 CFR 59, Subpart D-2005: National Volatile Organic Compound Emission Standards for
Architectural Coatings

Page 65 of 183

Glass Association of North America

Engineering Standards Manual. 2001.
Glazing Manual. 2004.
Laminated Glazing Reference Manual. 2006.

Insulating Glass Manufacturers Alliance

IGMA TB-3001-2001: Guidelines for Sloped Glazing.
SIGMA TM-3000-1990 (Revised 2004): North American Glazing Guidelines for Sealed
Insulating Glass Units for Commercial and Residential Use

International Code Council

International Building Code. 2003.

Lawrence Berkeley National Laboratory; Environmental Energy Technologies Division; Building
Technologies Department; Windows & Daylighting Group

WINDOW 5.2: A PC Program for Analyzing Window Thermal Performance (Available at
http://windows.lbl.gov/software)

National Fenestration Rating Council

NFRC 100-2004: Procedure for Determining Fenestration Product Thermal Properties
(Currently Limited to U-Factors)
NFRC 200-2004: Procedure for Determining Fenestration Product Solar Heat Gain
Coefficients at Normal Incidence
NFRC 300-2004: Procedures for Determining Solar Optical Properties of Simple Fenestration
Products

NFPA

NFPA 252-2003: Fire Tests of Door Assemblies
NFPA 257-2000: Fire Test for Window and Glass Block Assemblies
SECTION 08830 - MIRRORS
ASTM International

ASTM C 1036-06: Specification for Flat Glass
ASTM C 1048-04: Specification for Heat-Treated Flat Glass - Kind HS, Kind FT Coated and
Uncoated Glass
ASTM C 1172-03: Specification for Laminated Architectural Flat Glass
ASTM C 1503-01: Specification for Silvered Flat Glass Mirror

Code of Federal Regulations

16 CFR 1201-2006: Safety Standard for Architectural Glazing Materials

Glass Association of North America

Glazing Manual. 2004.
Mirrors, Handle with Extreme Care: Tips for the Professional on the Care and Handling of
Mirrors.2004.

Page 66 of 183

SECTION 09111 - NON-LOAD-BEARING STEEL FRAMING
ASTM International

ASTM A 641/641M-03: Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A 653/653M-07: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron
Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM C 645-08a: Specification for Nonstructural Steel Framing Members
ASTM C 754-07: Specification for Installation of Steel Framing Members to Receive Screw-
Attached Gypsum Panel Products
ASTM C 840-07: Specification for Application and Finishing of Gypsum Board
ASTM C 841-03 (Reapproved 2008): Specification for Installation of Interior Lathing and
Furring
ASTM C 844-04: Specification for Application of Gypsum Base to Receive Gypsum Veneer
Plaster
ASTM C 1063-07: Specification for Installation of Lathing and Furring to Receive Interior
and
Exterior Portland Cement-Based Plaster
ASTM D 226-06: Specification for Asphalt-Saturated Organic Felt Used in Roofing and
Waterproofing
ASTM E 90-04: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss
of Building Partitions and Elements
ASTM E 119-08a: Test Methods for Fire Tests of Building Construction and Materials
ASTM E 413-04: Classification for Rating Sound Insulation
ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM E 1190-95 (Reapproved 2007): Test Methods for Strength of Power-Actuated
Fasteners Installed in Structural Members

SECTION 09220 - PORTLAND CEMENT PLASTER
ASTM International

ASTM A 641/A 641M-03: Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A 653/A 653M-06a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM C 35-01 (Reapproved 2005): Specification for Inorganic Aggregates for Use in
Gypsum Plaster
ASTM C 91-05: Specification for Masonry Cement
ASTM C 150-05: Specification for Portland Cement
ASTM C 206-03: Specification for Finishing Hydrated Lime
ASTM C 207-06: Specification for Hydrated Lime for Masonry Purposes
ASTM C 665-06: Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame
Construction and Manufactured Housing
ASTM C 847-06: Specification for Metal Lath
ASTM C 897-05: Specification for Aggregate for Job-Mixed Portland Cement-Based Plasters
ASTM C 926-06: Specification for Application of Portland Cement-Based Plaster
ASTM C 932-06: Specification for Surface-Applied Bonding Agents for Exterior Plastering
Page 67 of 183

ASTM C 933-05: Specification for Welded Wire Lath
ASTM C 954-04: Specification for Steel Drill Screws for the Application of Gypsum Panel
Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84
mm) in Thickness
ASTM C 1002-04: Specification for Steel Self-Piercing Tapping Screws for the Application
of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
ASTM C 1032-06: Specification for Woven Wire Plaster Base
ASTM C 1063-06: Specification for Installation of Lathing and Furring to Receive Interior
and Exterior Portland Cement-Based Plaster
ASTM C 1328-05: Specification for Plastic (Stucco) Cement
ASTM E 90-04: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss of Building Partitions and Elements
ASTM E 119-05a: Test Methods for Fire Tests of Building Construction and Materials
ASTM E 413-04: Classification for Rating Sound Insulation

Code of Federal Regulations

40 CFR 59, Subpart D-2006: National Volatile Organic Compound Emission Standards for
Architectural Coatings

Federal Specification

FS UU-B-790a-1968 (Reinstated 1992): Building Paper, Vegetable Fiber: (Kraft,
Waterproofed, Water Repellant and Fire Resistant)

Underwriters Laboratories Inc.

Fire Resistance Directory. Published annually.

SECTION 09250 - GYPSUM BOARD
American National Standards Institute

ANSI A108/A118/A136-2005: Installation of Ceramic Tile

ASTM International

ASTM B 221-06: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-07: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM C 423-08: Test Method for Sound Absorption and Sound Absorption Coefficients by
the Reverberation Room Method
ASTM C 475/C 475M-02 (Reapproved 2007): Specification for Joint Compound and Joint
Tape for Finishing Gypsum Board
ASTM C 665-06: Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame
Construction and Manufactured Housing
ASTM C 834-05: Specification for Latex Sealants
ASTM C 840-08: Specification for Application and Finishing of Gypsum Board
ASTM C 919-08: Use of Sealants in Acoustical Applications
ASTM C 954-07: Specification for Steel Drill Screws for the Application of Gypsum Panel
Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84
mm) in Thickness
ASTM C 1002-07: Specification for Steel Self-Piercing Tapping Screws for the Application
Page 68 of 183

of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
ASTM C 1047-05: Specification for Accessories for Gypsum Wallboard and Gypsum Veneer
Base
ASTM C 1177/C 1177M-06: Specification for Glass Mat Gypsum Substrate for Use as
Sheathing
ASTM C 1178/C 1178M-06: Specification for Glass Mat Water-Resistant Gypsum Backing
Panel
ASTM C 1278/C 1278M-07a: Specification for Fiber-Reinforced Gypsum Panel
ASTM C 1288-99 (Reapproved 2004): Specification for Discrete Non-Asbestos Fiber-
Cement Interior Substrate Sheets
ASTM C 1325-08: Specification for Non-Asbestos Fiber-Mat Reinforced Cementitious
Backer Units
ASTM C 1396/C 1396M-06a: Specification for Gypsum Board
ASTM C 1629/C 1629M-06: Classification for Abuse-Resistant Nondecorated Interior
Gypsum Panel Products and Fiber-Reinforced Cement Panels
ASTM C 1658/C 1658M-06: Specification for Glass Mat Gypsum Panels
ASTM D 3273-00 (Reapproved 2005): Test Method for Resistance to Growth of Mold on the
Surface of Interior Coatings in an Environmental Chamber
ASTM E 84-08a: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 90-04: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss of Building Partitions and Elements
ASTM E 119-08a: Test Methods for Fire Tests of Building Construction and Materials
ASTM E 413-04: Classification for Rating Sound Insulation

Code of Federal Regulations

40 CFR, Part 59, Subpart D-2007: National Volatile Organic Compound Emission Standards
for Architectural Coatings

SECTION 09310 - CERAMIC TILE
American National Standards Institute (The following 13 standards and TCA's "Handbook for
Ceramic Tile Installation" are available on a CD offered by TCA.)

ANSI A108 Series (A108.01, .02, .1A, .1B, .1C, .4, .5, .6, .8, .9, .10, .11, .12, .13, .14, .15,
.16, and.17-2005): Specifications for Installation of Ceramic Tile
ANSI A118.1-1999 (Reaffirmed 2005): Specifications for Dry-Set Portland Cement Mortar
ANSI A118.3-1999 (Reaffirmed 2005): Specifications for Chemical Resistant Water
Cleanable Tile-Setting and Grouting Epoxy and Water Cleanable Tile-Setting Epoxy
Adhesive
ANSI A118.4-1999 (Reaffirmed 2005): Specifications for Latex-Portland Cement Mortar
ANSI A118.5-1999 (Reaffirmed 2005): Specifications for Chemical Resistant Furan Mortars
and Grouts for Tile Installation
ANSI A118.6-1999 (Reaffirmed 2005): Specifications for Standard Cement Grouts for Tile
Installation
ANSI A118.7-1999 (Reaffirmed 2005): Specifications for Polymer Modified Cement Grouts
for Tile Installation
ANSI A118.9-1999 (Reaffirmed 2005): Test Methods and Specifications for Cementitious
Backer Units
ANSI A118.10-1999 (Reaffirmed 2005): Specifications for Load Bearing, Bonded,
Waterproof Membranes for Thin-Set Ceramic Tile and Dimension Stone Installations
ANSI A118.11-1999 (Reaffirmed 2005): Specification for EGP (Exterior Glue Plywood)
Latex-Portland Cement Mortar
ANSI A118.12-2005: Specifications for Crack Isolation Membranes for Thin-Set Ceramic
Page 69 of 183

Tile and Dimension Stone Installations
ANSI A136.1-1999 (Reaffirmed 2005): Organic Adhesives for Installation of Ceramic Tile
ANSI A137.1-1988: Specifications for Ceramic Tile

ASTM International

ASTM A 82/A 82M-05a: Specification for Steel Wire, Plain, for Concrete Reinforcement
ASTM A 185/A 185M-06: Specification for Steel Welded Wire Reinforcement, Plain, for
Concrete
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM C 241-90 (Reapproved 2005): Test Method for Abrasion Resistance of Stone
Subjected to Foot Traffic
ASTM C 503-05: Specification for Marble Dimension Stone
ASTM C 615-03: Specification for Granite Dimension Stone
ASTM C 629-03: Specification for Slate Dimension Stone
ASTM C 847-04: Specification for Metal Lath
ASTM C 920-05: Specification for Elastomeric Joint Sealants
ASTM C 1028-06: Test Method for Determining the Static Coefficient of Friction of Ceramic
Tile and Other Like Surfaces by the Horizontal Dynamometer Pull-Meter Method
ASTM C 1288-99 (Reapproved 2004): Specification for Discrete Non-Asbestos Fiber-
Cement Interior Substrate Sheets
ASTM C 1325-04: Specification for Non-Asbestos Fiber-Mat Reinforced Cement Substrate
Sheets
ASTM C 1353-98: Test Method Using the Taber Abraser for Abrasion Resistance of
Dimension Stone Subjected to Foot Traffic
ASTM D 87-04: Test Method for Melting Point of Petroleum Wax (Cooling Curve)
ASTM D 226-06: Specification for Asphalt-Saturated Organic Felt Used in Roofing and
Waterproofing
ASTM D 4397-02: Specification for Polyethylene Sheeting for Construction, Industrial, and
Agriculture Applications

Code of Federal Regulations

40 CFR, Part 59, Subpart D-2005: National Volatile Organic Compound Emission Standards
for Architectural Coatings
Tile Council of North America, Inc. (TCA)

Handbook for Ceramic Tile Installation. 2005. (Also available on a CD that includes ANSI
standards for tile, tile installation material, and tile installation methods.)

SECTION 09511 - ACOUSTICAL PANEL CEILINGS
American Architectural Manufacturers Association

AAMA 6111998: Voluntary Specification for Anodized Architectural Aluminum

American Society for Testing and Materials

ASTM A 641/641M98: Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A 653/A 653M99: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B 16498: Specification for Nickel-Copper Alloy Rod, Bar, and Wire
ASTM B 22196: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Page 70 of 183

Wire, Profiles, and Tubes
ASTM B 221M96: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 63398: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C 63597: Specification for the Manufacture, Performance, and Testing of Metal
Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings
ASTM C 63696: Practice for Installation of Metal Ceiling Suspension Systems for
Acoustical Tile and Lay-in Panels
ASTM C 83495: Specification for Latex Sealants
ASTM D 327394: Test Method for Resistance to Growth of Mold on the Surface of Interior
Coatings in an Environmental Chamber
ASTM E 8499: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 9099: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss of Building Partitions and Elements
ASTM E 11998: Test Methods for Fire Tests of Building Construction and Materials
ASTM E 48896: Test Method for Strength of Anchors in Concrete and Masonry Elements
ASTM E 54894: Guide for General Criteria Used for Evaluating Laboratory Competence
ASTM E 58096: Practice for Application of Ceiling Suspension Systems for Acoustical Tile
and Lay-in Panels in Areas Requiring Moderate Seismic Restraint
ASTM E 79593: Practices for Mounting Test Specimens during Sound Absorption Tests
ASTM E 119095: Test Methods for Strength of Power-Actuated Fasteners Installed in
Structural Members
ASTM E 126498: Classification for Acoustical Ceiling Products
ASTM E 151293: Test Methods for Testing Bond Performance of Adhesive-Bonded
Anchors
ASTM F 59398: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 59498: Specification for Stainless Steel Nuts

Ceilings & Interior Systems Construction Association

Ceiling Systems Handbook. 1999.
Guidelines for Seismic Restraint of Direct-Hung Suspended Ceiling AssembliesSeismic
Zones 3& 4. 1991.
Recommendations for Direct-Hung Acoustical Tile and Lay-in Panel CeilingsSeismic
Zones 02.
1991.
Code of Federal Regulations

40 CFR, Part 59, Subpart D-2001: National Volatile Organic Compound Emission Standards
for Architectural Coatings

International Conference of Building Officials

UBC Standard 2521997: Metal Suspension Systems for Acoustical Tile and for Lay-in
Panel
Ceilings

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

Underwriters Laboratories Inc.

Fire Resistance Directory. 1999.

Page 71 of 183

SECTION 09512 - ACOUSTICAL TILE CEILINGS
American Architectural Manufacturers Association

AAMA 611B1998: Voluntary Specification for Anodized Architectural Aluminum

American Society for Testing and Materials

ASTM A 641/641MB98: Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A 653/A 653MB99: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B 221B96: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221MB96: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 633B98: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C 635B97: Specification for the Manufacture, Performance, and Testing of Metal
Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings
ASTM C 636B96: Practice for Installation of Metal Ceiling Suspension Systems for
Acoustical Tile and Lay-in Panels
ASTM C 834B95: Specification for Latex Sealants
ASTM D 3273B94: Test Method for Resistance to Growth of Mold on the Surface of Interior
Coatings in an Environmental Chamber
ASTM E 84B99: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 90B99: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss of Building Partitions and Elements
ASTM E 119B98: Test Methods for Fire Tests of Building Construction and Materials
ASTM E 488B96: Test Method for Strength of Anchors in Concrete and Masonry Elements
ASTM E 548B94: Guide for General Criteria Used for Evaluating Laboratory Competence
ASTM E 580B96: Practice for Application of Ceiling Suspension Systems for Acoustical Tile
and Lay-in Panels in Areas Requiring Moderate Seismic Restraint
ASTM E 795B93: Practices for Mounting Test Specimens during Sound Absorption Tests
ASTM E 1190B95: Test Methods for Strength of Power-Actuated Fasteners Installed in
Structural Members
ASTM E 1264B98: Classification for Acoustical Ceiling Products
ASTM E 1512B93: Test Methods for Testing Bond Performance of Adhesive-Bonded
Anchors
ASTM F 593B98: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594B98: Specification for Stainless Steel Nuts

Ceilings & Interior Systems Construction Association

Ceiling Systems Handbook. 1999.
Guidelines for Seismic Restraint of Direct-Hung Suspended Ceiling Assemblies-Seismic
Zones 3 & 4. 1991.
Recommendations for Direct-Hung Acoustical Tile and Lay-in Panel Ceilings-Seismic Zones
0B2.1991.

Code of Federal Regulations

40 CFR, Part 59, Subpart D-2001: National Volatile Organic Compound Emission Standards
for Architectural Coatings

Page 72 of 183

International Conference of Building Officials

UBC Standard 25B2B1997: Metal Suspension Systems for Acoustical Tile and for Lay-in
Panel Ceilings

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

Underwriters Laboratories Inc.

Fire Resistance Directory. 1999.

SECTION 09547 - LINEAR METAL CEILINGS
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum
AAMA 2604-2002: Voluntary Specification, Performance Requirements and Test Procedures
for High Performance Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Superior Performing Organic Coatings on Aluminum Extrusions and Panels

ASTM International

ASTM A 240/A 240M-04a: Specification for Chromium and Chromium-Nickel Stainless
Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 580/A 580M-98: Specification for Stainless Steel Wire
ASTM A 591/A 591M-98: Specification for Steel Sheet, Electrolytic Zinc-Coated, for Light
Coating Weight [Mass] Applications
ASTM A 641/A 641M-03: Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A 653/A 653M-04a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 1008/A 1008M-04a: Standard Specification for Steel, Sheet, Cold-Rolled, Carbon,
Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved
Formability
ASTM B 164-03: Specification for Nickel-Copper Alloy Rod, Bar, and Wire
ASTM B 209-04: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 209M-04: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 633-98: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C 553-02: Specification for Mineral Fiber Blanket Thermal Insulation for Commercial
and Industrial Applications
ASTM C 635-00: Specification for the Manufacture, Performance, and Testing of Metal
Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings
ASTM C 636-04: Practice for Installation of Metal Ceiling Suspension Systems for
Acoustical Tile and Lay-in Panels
ASTM E 84-04: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM E 580-02: Practice for Application of Ceiling Suspension Systems for Acoustical Tile
and Lay-in Panels in Areas Requiring Moderate Seismic Restraint
ASTM E 795-00: Practices for Mounting Test Specimens during Sound Absorption Tests
Page 73 of 183

ASTM E 1190-95 (Reapproved 2000): Test Methods for Strength of Power-Actuated
Fasteners Installed in Structural Members
ASTM E 1264-98: Classification for Acoustical Ceiling Products
ASTM E 1512-01: Test Methods for Testing Bond Performance of Bonded Anchors
ASTM F 593-02: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594-02: Specification for Stainless Steel Nuts

Ceilings & Interior Systems Construction Association

Ceiling Systems Handbook. 1999.
Guidelines for Seismic Restraint of Direct-Hung Suspended Ceiling Assemblies - Seismic
Zones 3 & 4. 2004.
Recommendations for Direct-Hung Acoustical Tile and Lay-in Panel Ceilings - Seismic
Zones 0-2.2004.

International Conference of Building Officials

UBC Standard 25-2-1997: Metal Suspension Systems for Acoustical Tile and for Lay-in
Panel Ceilings

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

Structural Engineering Institute/American Society of Civil Engineers

SEI/ASCE 7-02: Minimum Design Loads for Buildings and Other Structures

SECTION 09638 - STONE FLOORING
ACI International

ACI 301-99: Specification for Structural Concrete

ACI International; American Society of Civil Engineers; and The Masonry Society

ACI 530.1/ASCE 6/TMS 602-02: Specification for Masonry Structures

American National Standards Institute

ANSI A108.4-1999: Installation of Ceramic Tile with Organic Adhesive or Water Cleanable
Tile Setting Epoxy Adhesive
ANSI A108.5-1999: Installation of Ceramic Tile with Dry-Set Portland Cement Mortar or
Latex-Portland Cement Mortar
ANSI A108.6-1999: Installation of Ceramic Tile with Chemical Resistant, Water Cleanable
Tile-Setting and Grouting Epoxy
ANSI A108.10-1999: Installation of Grout in Tilework
ANSI A118.1-1999: Specifications for Dry-Set Portland Cement Mortar
ANSI A118.3-1999: Specifications for Chemical Resistant, Water Cleanable Tile Setting and
Grouting Epoxy and Water Cleanable Tile Setting Epoxy Adhesive
ANSI A118.4-1999: Specification for Latex-Portland Cement Mortar
ANSI A118.6-1999: Specifications for Standard Cement Grouts for Tile Installation
Page 74 of 183

ANSI A118.7-1999: Specifications for Polymer Modified Cement Grouts for Tile Installation

ASTM International

ASTM A 82-02: Specification for Steel Wire, Plain, for Concrete Reinforcement
ASTM A 185-02: Specification for Steel Welded Wire Reinforcement, Plain, for Concrete
ASTM A 276-04: Specification for Stainless Steel Bars and Shapes
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM C 97-02: Test Methods for Absorption and Bulk Specific Gravity of Dimension Stone
ASTM C 99-87 (Reapproved 2000): Test Method for Modulus of Rupture of Dimension
Stone
ASTM C 114-04: Test Methods for Chemical Analysis of Hydraulic Cement
ASTM C 144-03: Specification for Aggregate for Masonry Mortar
ASTM C 150-02a: Specification for Portland Cement
ASTM C 170-90 (Reapproved 1999): Test Method for Compressive Strength of Dimension
Stone
ASTM C 207-04: Specification for Hydrated Lime for Masonry Purposes
ASTM C 241-90 (Reapproved 1997): Test Method for Abrasion Resistance of Stone
Subjected to Foot Traffic
ASTM C 270-03b: Specification for Mortar for Unit Masonry
ASTM C 503-03: Specification for Marble Dimension Stone (Exterior)
ASTM C 568-03: Specification for Limestone Dimension Stone
ASTM C 615-03: Specification for Granite Dimension Stone
ASTM C 616-03: Specification for Quartz-Based Dimension Stone
ASTM C 629-03: Specification for Slate Dimension Stone
ASTM C 880-98: Test Method for Flexural Strength of Dimension Stone
ASTM C 1353-98: Test Method for Using the Taber Abraser for Abrasion Resistance of
Dimension Stone Subjected to Foot Traffic
ASTM C 1526-03: Specification for Serpentine Dimension Stone
ASTM C 1527-03: Specification for Travertine Dimension Stone
ASTM D 226-97a: Specification for Asphalt-Saturated Organic Felt Used in Roofing and
Waterproofing
ASTM D 1752-04: Specification for Preformed Sponge Rubber and Cork Expansion Joint
Fillers for Concrete Paving and Structural Construction
ASTM D 4397-02: Specification for Polyethylene Sheeting for Construction, Industrial, and
Agricultural Applications
Code of Federal Regulations

40 CFR 59, Subpart D-2003: National Volatile Organic Compound Emission Standards for
Architectural Coatings

Indiana Limestone Institute of America, Inc.

Indiana Limestone Handbook. 21st ed. 2004.

Marble Institute of America

Dimension Stone - Design Manual. 2003.

National Building Granite Quarries Association, Inc.

Specifications for Architectural Granite. 1999.

Page 75 of 183

SECTION 09640 - WOOD FLOORING
ASTM International

ASTM D 4397-02: Specification for Polyethylene Sheeting for Construction, Industrial, and
Agricultural Applications
ASTM D 4869-05: Specification for Asphalt-Saturated Organic Felt Underlayment Used in
Steep Slope Roofing
ASTM E 492-04: Test Method for Laboratory Measurement of Impact Sound Transmission
Through Floor-Ceiling Assemblies Using the Tapping Machine
ASTM F 1869-04: Test Method for Measuring Moisture Vapor Emission Rate of Concrete
Subfloor Using Anhydrous Calcium Chloride

Code of Federal Regulations

40 CFR, Part 59, Subpart D-2006: National Volatile Organic Compound Emission Standards
for Architectural Coatings

Forest Stewardship Council

FSC STD-01-001 (Version 4-0)-2002: FSC Principles and Criteria for Forest Stewardship
(available in PDF at www.fsc.org)

Hardwood Plywood & Veneer Association

HPVA EF-2002: Engineered Wood Flooring (ANSI)

National Oak Flooring Manufacturers' Association

Installing Hardwood Flooring. 1997.

National Wood Flooring Association

Installation Guidelines: Wood Flooring. 1999.

West Coast Lumber Inspection Bureau

WCLIB No. 17-2004: Grading Rules for West Coast Lumber

SECTION 09651 - RESILIENT FLOOR TILE
ASTM International

ASTM C 109/C 109M-02: Test Method for Compressive Strength of Hydraulic Cement
Mortars
ASTM D 695-02a: Test Method for Compressive Properties of Rigid Plastics
ASTM D 2240-04: Test Method for Rubber Property Durometer Hardness
ASTM E 648-03: Test Method for Critical Radiant Flux of Floor-Covering Systems Using a
Radiant Heat Energy Source
ASTM F 510-93 (Reapproved 2004): Test Method for Resistance to Abrasion of Resilient
Floor Coverings Using an Abrader with a Grit Feed Meter
ASTM F 710-05: Practice for Preparing Concrete Floors to Receive Resilient Flooring
Page 76 of 183

ASTM F 970-00: Test Method for Static Load Limit
ASTM F 1066-04: Specification for Vinyl Composition Floor Tile
ASTM F 1303-04: Specification for Sheet Vinyl Floor Covering with Backing
ASTM F 1344-04: Specification for Rubber Floor Tile
ASTM F 1516-03: Practice for Sealing Seams of Resilient Flooring Products by the Heat
Weld Method (When Recommended)
ASTM F 1700-04: Specification for Solid Vinyl Floor Tile
ASTM F 1859-04: Specification for Rubber Sheet Floor Covering without Backing
ASTM F 1860-04: Specification for Rubber Sheet Flooring with Backing
ASTM F 1869-04: Test Method for Measuring Moisture Vapor Emission Rate of Concrete
Subfloor Using Anhydrous Calcium Chloride
ASTM F 1913-04: Specification for Vinyl Sheet Floor Covering without Backing
ASTM F 2170-02: Test Method for Determining Relative Humidity in Concrete Floor Slabs
Using in situ Probes

Code of Federal Regulations

40 CFR 59, Subpart D-2003: National Volatile Organic Compound Emission Standards for
Architectural Coatings
NFPA

NFPA 253-2000: Method of Test for Critical Radiant Flux of Floor Covering Systems Using
a Radiant Heat Energy Source

SECTION 09680 - CARPET
The American Association of Textile Chemists and Colorists

AATCC 16-2004: Colorfastness to Light
AATCC 24-2004: Insects, Resistance of Textiles to
AATCC 134-2006: Electrostatic Propensity of Carpets
AATCC 165-1999: Colorfastness to Crocking: Carpets - AATCC Crockmeter Method
AATCC 174-2007: Antimicrobial Activity Assessment of Carpets

American National Standards Institute/NSF International

ANSI/NSF 140-2005: Sustainable Carpet Assessment Standard

ASTM International

ASTM C 423-08: Test Method for Sound Absorption and Sound Absorption Coefficients by
the Reverberation Room Method
ASTM D 1335-05: Test Method for Tuft Bind of Pile Yarn Floor Coverings
ASTM D 2646-05: Test Methods for Backing Fabric Characteristics of Pile Yarn Floor
Coverings
ASTM D 3574-05: Test Methods for Flexible Cellular Materials - Slab, Bonded, and Molded
Urethane Foams
ASTM D 3676-01: Specification for Rubber Cellular Cushion Used for Carpet or Rug
Underlay
ASTM D 3936-05: Test Method for Resistance to Delamination of the Secondary Backing of
Page 77 of 183

Pile Yarn Floor Covering
ASTM D 6859-05: Test Method for Pile Thickness of Finished Level Pile Yarn Floor
Coverings
ASTM D 7330-07: Test Method for Assessment of Surface Appearance Change in Pile Floor
Coverings Using Standard Reference Scales
ASTM F 710-08: Practice for Preparing Concrete Floors to Receive Resilient Flooring

California Department of Health Services

Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using
Small-Scale Environmental Chambers. 2004.

The Carpet and Rug Institute

CRI 104-2002: Standard for Installation Specification of Commercial Carpet
Green Label (testing program). Undated.
Green Label Plus (testing program). Undated.

Code of Federal Regulations

40 CFR 59, Subpart D-2007: National Volatile Organic Compound Emission Standards for
Architectural Coatings

NFPA

NFPA 253-2006: Method of Test for Critical Radiant Flux of Floor Covering Systems Using
a Radiant Heat Energy Source

SECTION 09720 - WALL COVERINGS
The American Association of Textile Chemists and Colorists

AATCC 8-2005: Colorfastness to Crocking: AATCC Crockmeter Method
AATCC 16-2004: Colorfastness to Light

ASTM International

ASTM E 84-05: Test Method for Surface Burning Characteristics of Building Materials
ASTM F 793-05: Classification of Wall Covering by Durability Characteristic
ASTM F 1141-93 (Reapproved 2004): Specification for Wallcovering

Chemical Fabrics & Film Association, Inc.

CFFA-W-101-D-2002: Quality Standard for Vinyl Coated Fabric Wallcovering

Code of Federal Regulations

40 CFR 59, Subchapter C, Subpart D-2005: National Volatile Organic Compound Emission
Standards for Architectural Coatings

Federal Specification

FS CCC-W-408D-1994: Wall Covering, Vinyl Coated

Page 78 of 183

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

International Code Council

International Building Code. 2003.

International Conference of Building Officials

UBC Standard 8-2-1997: Test Method for Evaluating Room Fire Growth Contribution of
Textile Wall Covering

NFPA

NFPA 265-2002: Standard Methods of Fire Tests for Evaluating Room Fire Growth
Contribution of Textile Wall Coverings
NFPA 286-2006: Standard Methods of Fire Tests for Evaluating Room Fire Growth
Contribution of Wall and Ceiling Interior Finish

SECTION 09751 - INTERIOR STONE FACING
American National Standards Institute

ANSI A108.10-1999: Installation of Grout in Tilework
ANSI A118.3-1999: Specifications for Chemical Resistant, Water Cleanable Tile Setting and
Grouting Epoxy and Water Cleanable Tile Setting Epoxy Adhesive
ANSI A118.6-1999: Specifications for Standard Cement Grouts for Tile Installation
ANSI A118.7-1999: Specification for Polymer Modified Cement Grouts for Tile Installation
ANSI A136.1-1999: Specifications for Organic Adhesives for Installation of Ceramic Tile

American Society of Civil Engineers

ASCE 7-02: Minimum Design Loads for Buildings and Other Structures

ASTM International

ASTM A 240/A 240M-04a: Specification for Chromium and Chromium-Nickel Stainless
Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 276-04: Specification for Stainless Steel Bars and Shapes
ASTM A 653/A 653M-03: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B 221-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles and Tubes
ASTM B 221M-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM C 59/C 59M-00: Specification for Gypsum Casting Plaster and Gypsum Molding
Plaster
ASTM C 97-02: Test Methods for Absorption and Bulk Specific Gravity of Dimension Stone
ASTM C 114-03: Test Methods for Chemical Analysis of Hydraulic Cement
ASTM C 144-03: Specification for Aggregate for Masonry Mortar
Page 79 of 183

ASTM C 150-02: Specification for Portland Cement
ASTM C 170-90 (Reapproved 1999): Test Method for Compressive Strength of Dimension
Stone
ASTM C 207-91 (Reapproved 1997): Specification for Hydrated Lime for Masonry Purposes
ASTM C 270-03b: Specification for Mortar for Unit Masonry
ASTM C 503-03: Specification for Marble Dimension Stone (Exterior)
ASTM C 568-03: Specification for Limestone Dimension Stone
ASTM C 615-03: Specification for Granite Dimension Stone
ASTM C 616-03: Specification for Quartz-Based Dimension Stone
ASTM C 629-03: Specification for Slate Dimension Stone
ASTM C 880-98: Test Method for Flexural Strength of Dimension Stone
ASTM C 1242-04: Guide for Selection, Design, and Installation of Dimension Stone
Anchoring Systems
ASTM C 1526-02: Specification for Serpentine Dimension Stone
ASTM C 1527-02: Specification for Travertine Dimension Stone
ASTM F 593-02: Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
ASTM F 594-02: Specification for Stainless Steel Nuts
ASTM F 738M-02: Specification for Stainless Steel Metric Bolts, Screws, and Studs
ASTM F 836M-02: Specification for Style 1 Stainless Steel Metric Nuts

Code of Federal Regulations

40 CFR 59, Subpart D-2003: National Volatile Organic Compound Emission Standards for
Architectural Coatings

Indiana Limestone Institute of America, Inc.

Indiana Limestone Handbook. 21st ed. 2003.

Marble Institute of America

Dimension Stone - Design Manual. 2003.

National Building Granite Quarries Association, Inc.

Specifications for Architectural Granite. 1999.

SECTION 09841 - ACOUSTICAL WALL PANELS
American Wood-Preservers' Association

AWPA C20-99: Structural Lumber - Fire-Retardant Treatment by Pressure Processes

ASTM International

ASTM C 423-02: Test Method for Sound Absorption and Sound Absorption Coefficients by
the
Reverberation Room Method
ASTM C 612-00a: Specification for Mineral Fiber Block and Board Thermal Insulation
ASTM E 84-01: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 795-00: Practices for Mounting Test Specimens during Sound Absorption Tests

Page 80 of 183

Code of Federal Regulations

40 CFR, Part 59, Subpart D-2001: National Volatile Organic Compound Emission Standards
for
Architectural Coatings

International Conference of Building Officials

UBC Standard 8-1-1997: Test Method for Surface-Burning Characteristics of Building
Materials

SECTION 09851 - SOUND-ABSORBING CEILING UNITS
American National Standards Institute

ANSI A208.1-1999: Particleboard
ANSI A208.2-2002: Medium Density Fiberboard (MDF) for Interior Applications

ASTM International

ASTM C 423-08: Test Method for Sound Absorption and Sound Absorption Coefficients by
the Reverberation Room Method
ASTM C 553-02: Specification for Mineral Fiber Blanket Thermal Insulation for Commercial
and Industrial Applications
ASTM C 612-04: Specification for Mineral Fiber Block and Board Thermal Insulation
ASTM C 665-06: Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame
Construction and Manufactured Housing
ASTM D 3201-08: Test Method for Hygroscopic Properties of Fire-Retardant Wood and
Wood-Based Products
ASTM E 84-08a: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 795-05: Practices for Mounting Test Specimens during Sound Absorption Tests
ASTM E 1477-98a (Reapproved 2003): Test Method for Luminous Reflectance Factor of
Acoustical Materials by Use of Integrating-Sphere Reflectometers

California Department of Health Services

Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using
Small-Scale Environmental Chambers. 2004.
Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

NFPA

NFPA 265-2007: Standard Methods of Fire Tests for Evaluating Room Fire Growth
Contribution of Textile Coverings on Full Height Panels and Walls
NFPA 286-2006: Standard Methods of Fire Tests for Evaluating Contribution of Wall and
Ceiling Interior Finish to Room Fire Growth

Page 81 of 183

SECTION 09852 - SOUND-ABSORBING WALL UNITS
ASTM International

ASTM C 423-08: Test Method for Sound Absorption and Sound Absorption Coefficients by
the Reverberation Room Method
ASTM C 612-04: Specification for Mineral Fiber Block and Board Thermal Insulation
ASTM D 3201-08: Test Method for Hygroscopic Properties of Fire-Retardant Wood and
Wood-Based Products
ASTM E 84-08a: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 795-05: Practices for Mounting Test Specimens during Sound Absorption Tests

California Department of Health Services

Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using
Small-Scale Environmental Chambers. 2004.

Code of Federal Regulations

40 CFR 59, Subpart D-2007: National Volatile Organic Compound Emission Standards for
Architectural Coatings

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

NFPA

NFPA 265-2007: Standard Methods of Fire Tests for Evaluating Room Fire Growth
Contribution of Textile Coverings on Full Height Panels and Walls
NFPA 286-2006: Standard Methods of Fire Tests for Evaluating Contribution of Wall and
Ceiling Interior Finish to Room Fire Growth

SECTION 09911 - EXTERIOR PAINTING
Code of Federal Regulations

40 CFR, Part 59, Subpart D-2001: National Volatile Organic Compound Emission Standards
for Architectural Coatings

Master Painters Institute

MPI Approved Products List. January 2004.
MPI Architectural Painting Specification Manual. 2004.

SECTION 09912 - INTERIOR PAINTING
Code of Federal Regulations

40 CFR, Part 59, Subpart D-2001: National Volatile Organic Compound Emission Standards
for Architectural Coatings

Page 82 of 183

Master Painters Institute

MPI Approved Products List. January 2004.
MPI Architectural Painting Specification Manual. 2004.

SECTION 09960 - HIGH-PERFORMANCE COATINGS
Code of Federal Regulations

40 CFR, Part 59, Subpart D-2001: National Volatile Organic Compound Emission Standards
for Architectural Coatings

Master Painters Institute

MPI Approved Products List, July 31, 2003
MPI Architectural Painting Specification Manual, 2002.

SSPC: The Society for Protective Coatings

SSPC-SP 5/NACE No. 1 2000: Joint Surface Preparation Standard SSPC-SP 5/NACE No. 1:
White Metal Blast Cleaning
SSPC-SP 6/NACE No. 3 2000: Joint Surface Preparation Standard SSPC-SP 6/NACE No. 3:
Commercial Blast Cleaning
SSPC-SP 7/NACE No. 4 2000: Joint Surface Preparation Standard SSPC-SP 7/NACE No. 4:
Brush-Off Blast Cleaning
SSPC-SP 10/NACE No. 2 2000: Joint Surface Preparation Standard SSPC-SP 10/NACE No.
2: Near-White Blast Cleaning

SECTION 09963 - ELASTOMERIC COATINGS
ASTM International

ASTM D 1653-03: Test Method for Water Vapor Transmission of Organic Coating Films

Master Painters Institute

MPI #38-2006: Detailed Performance Standard - Exterior Non-Flat Waterborne, Pigmented
Elastomeric Coating
MPI #113-2006: Detailed Performance Standard - Exterior Flat Waterborne, Pigmented
Elastomeric Coating
MPI Approved Products List. July 2006.
MPI Architectural Painting Specification Manual. 2004.

SECTION 10101 - VISUAL DISPLAY SURFACES
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum
AAMA 2603-2002: Voluntary Specifications, Performance Requirements and Test
Procedures for Pigmented Organic Coatings on Aluminum Extrusions and Panels

Page 83 of 183

ASTM International

ASTM A 424-00: Specification for Steel, Sheet, for Porcelain Enameling
ASTM A 463/A 463M-05: Specification for Steel Sheet, Aluminum-Coated, by the Hot-Dip
Process
ASTM B 221-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-05: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM C 208-95 (Reapproved 2001): Specification for Cellulosic Fiber Insulating Board
ASTM E 84-05: Test Method for Surface Burning Characteristics of Building Materials

Code of Federal Regulations

40 CFR 59, Subpart D-2005: National Volatile Organic Compound Emission Standards for
Architectural Coatings

Composite Panel Association/Composite Wood Council

ANSI A135.4-2004: Basic Hardwood
ANSI A208.1-1999: Particleboard

Federal Specification

FS CCC-W-408D 1994: Wall Covering, Vinyl-Coated

Laminating Materials Association

LMA SAT-1-1998: Voluntary Product Standard and Typical Physical Properties of Saturated
Paper Overlays

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

National Electrical Manufacturers Association

NEMA ICS 6-1993 (Reaffirmed 2001): Industrial Control and Systems Enclosures
NEMA LD 3-2005: High-Pressure Decorative Laminates (ANSI)
NEMA MG 1-2003: Motors and Generators (ANSI)

NFPA

NFPA 70-2005: National Electrical Code

SECTION 10155 - TOILET COMPARTMENTS
American National Standards Institute

ANSI A208.1-1999: Particleboard

Page 84 of 183

ASTM International

ASTM A 653/A 653M-05a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron
Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet,
Strip, Plate, and Flat Bar
ASTM A 743/A 743M-06: Specification for Castings, Iron-Chromium, Iron-Chromium-
Nickel,
Corrosion Resistant, for General Application
ASTM A 879/A 879M-04: Specification for Steel Sheet, Zinc Coated by the Electrolytic
Process for
Applications Requiring Designation of the Coating Mass on Each Surface
ASTM B 26/B 26M-05: Specification for Aluminum-Alloy Sand Castings
ASTM B 86-05: Specification for Zinc and Zinc-Aluminum (ZA) Alloy Foundry and Die
Castings
ASTM B 221-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire,
Profiles, and Tubes
ASTM B 221M-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire,
Profiles, and Tubes [Metric]
ASTM B 455-05: Specification for Copper-Zinc-Lead Alloy (Leaded-Brass) Extruded Shapes
ASTM B 584-06: Specification for Copper Alloy Sand Castings for General Applications
ASTM E 84-05: Test Method for Surface Burning Characteristics of Building Materials

General Services Administration

CID-A-A-60003-1997: Partitions, Toilet, Complete

International Code Council/American National Standards Institute

ICC/ANSI A117.1-2003: Accessible and Usable Buildings and Facilities

National Electrical Manufacturers Association

NEMA LD 3-2005: High-Pressure Decorative Laminates (ANSI)

U.S. Architectural & Transportation Barriers Compliance Board

Americans with Disabilities Act (ADA) and Architectural Barriers Act (ABA) Accessibility
Guidelines for Buildings and Facilities. Adopted in 2004.

SECTION 10200 - LOUVERS AND VENTS
Air Movement and Control Association International, Inc.

AMCA 500-L-1999: Test Methods for Louvers, Dampers
AMCA 501-2003: Application Manual for Air Louvers

American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum
AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
Page 85 of 183

for Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 2604-2002: Voluntary Specification, Performance Requirements and Test Procedures
for High Performing Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Superior Performing Organic Coatings on Aluminum Extrusions and Panels

American Welding Society

AWS D1.2/D1.2M-2003: Structural Welding Code - Aluminum
AWS D1.3-1998: Structural Welding Code - Sheet Steel
AWS D1.6-1999: Structural Welding Code - Stainless Steel

ASTM International

ASTM A 240/A 240M-04a: Specification for Chromium and Chromium-Nickel Stainless
Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 653/A 653M-04a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 780-01: Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized Coatings
ASTM B 26/B 26M-03: Specification for Aluminum-Alloy Sand Castings
ASTM B 209-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 221-04a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles and Tubes
ASTM B 221M-04: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles and Tubes [Metric]
ASTM D 1187-97 (Reapproved 2002): Specification for Asphalt-Base Emulsions for Use as
Protective Coatings for Metal
ASTM E 90-04: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss of Building Partitions and Elements
ASTM E 413-04: Classification for Rating Sound Insulation
ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM E 966-04: Guide for Field Measurements of Airborne Sound Insulation of Building
Facades and Facade Elements
ASTM E 1332-90 (Reapproved 2003): Classification for Determination of Outdoor-Indoor
Transmission Class

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

Sheet Metal and Air Conditioning Contractors' National Association

Architectural Sheet Metal Manual. 2003.

Structural Engineering Institute/American Society of Civil Engineers

SEI/ASCE 7-2002: Minimum Design Loads for Buildings and Other Structures

Page 86 of 183

SECTION 10265 - IMPACT-RESISTANT WALL PROTECTION
American National Standards Institute

ANSI A208.1-1999: Particleboard

ASTM International

ASTM A 240/A 240M-06b: Specification for Chromium and Chromium-Nickel Stainless
Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM B 36/B 36M-06: Specification for Brass Plate, Sheet, Strip, and Rolled Bar
ASTM B 221-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 249/B 249M-06: Specification for General Requirements for Wrought Copper and
Copper-Alloy Rod, Bar, Shapes and Forgings
ASTM D 256-06: Test Methods for Determining the Izod Pendulum Impact Resistance of
Plastics
ASTM D 543-05: Practices for Evaluating the Resistance of Plastics to Chemical Reagents
ASTM D 635-06: Test Method for Rate of Burning and/or Extent and Time of Burning of
Plastics in a Horizontal Position
ASTM D 1308-02: Test Method for Effect of Household Chemicals on Clear and Pigmented
Organic Finishes
ASTM D 1784-03: Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds and
Chlorinated Poly(Vinyl Chloride) (CPVC) Compounds
ASTM D 6098-97 (Reapproved 2003): Specification for Extruded and Compression Molded
Shapes Made from Polycarbonate (PC)
ASTM E 84-06: Test Method for Surface Burning Characteristics of Building Materials

Builders Hardware Manufacturers Association

BHMA A156.6-2005: Architectural Door Trim (ANSI)

Code of Federal Regulations

40 CFR 59, Subpart D-2006: National Volatile Organic Compound Emission Standards for
Architectural Coatings

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fscus.org)

International Code Council/American National Standards Institute

ICC/ANSI A117.1-2003: Standard on Accessible and Usable Buildings and Facilities

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

Page 87 of 183

NFPA

NFPA 255-2006: Method of Test of Surface Burning Characteristics of Building Materials

Underwriters Laboratories Inc.

UL 723-2003: Safety Test for Surface Burning Characteristics of Building Materials
UL 2079-2004: Tests for Fire Resistance of Building Joint Systems

U.S. Architectural & Transportation Barriers Compliance Board

Americans with Disabilities Act (ADA) and Architectural Barriers Act (ABA) Accessibility
Guidelines for Buildings and Facilities. Adopted in 2004.

SECTION 10270 - ACCESS FLOORING
American Association of Textile Chemists and Colorists (The)

AATCC-134-01: Electrostatic Propensity of Carpets

American Society of Civil Engineers

ASCE 7-02: Minimum Design Loads for Buildings and Other Structures

ASTM International

ASTM B 85-02: Specification for Aluminum-Alloy Die Castings
ASTM B 633-98: Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM D 5116-97: Guide for Small-Scale Environmental Chamber Determinations of
Organic Emissions from Indoor Materials/Products
ASTM E 84-03: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM E 595-93 (Reapproved 2003): Test Method for Total Mass Loss and Collected
Volatile Condensable Materials from Outgassing in a Vacuum Environment
ASTM E 648-03: Test Method for Critical Radiant Flux of Floor-Covering Systems Using a
Radiant Heat Energy Source
ASTM F 150-98: Test Method for Electrical Resistance of Conductive Resilient Flooring
ASTM F 1700-99: Specification for Solid Vinyl Tile
ASTM F 1861-02: Specification for Resilient Wall Base

Ceilings & Interior Systems Construction Association

CISCA A/F-92: Recommended Test Procedures for Access Floors

Code of Federal Regulations

40 CFR 59, Subpart D-02: National Volatile Organic Compound Emission Standards for
Architectural Coatings

ESD Association

ESD STM 7.1-2001: Resistive Characterization of Materials - Floor Materials (ANSI)
Page 88 of 183

Federal Specification

FED-STD-101C/4046.1-80: Electrostatic Properties of Materials

National Electrical Manufacturers Association

NEMA LD 3-00: High Pressure Decorative Laminates
NEMA WD 6-02: Wiring Devices - Dimensional Requirements

NFPA

NFPA 75-03: Protection of Information Technology Equipment
NFPA 99-02: Health Care Facilities

Underwriters Laboratories Inc.

UL 94-96: Tests for Flammability of Plastic Materials for Parts in Devices and Appliances
UL 779-95: Electrically Conductive Floorings

SECTION 10350 - FLAGPOLES
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum
AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
for
Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 2604-2005: Voluntary Specification, Performance Requirements and Test Procedures
for
High Performance Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2005: Voluntary Specification, Performance Requirements and Test Procedures
for
Superior Performing Organic Coatings on Aluminum Extrusions and Panels

ASTM International

ASTM A 53/A 53M-04a: Specification for Pipe, Steel, Black and Hot-Dipped, Zinc Coated,
Welded and Seamless
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel
Products
ASTM A 269-04: Specification for Seamless and Welded Austenitic Stainless Steel Tubing
for
General Service
ASTM A 312/A 312M-05: Specification for Seamless, Welded, and Heavily Cold Austenitic
Stainless Steel Pipes
ASTM A 513-00: Specification for Electric-Resistance-Welded Carbon and Alloy Steel
Mechanical
Tubing
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet,
Page 89 of 183

Strip, Plate, and Flat Bar
ASTM B 43-98 (Reappoved 2004): Specification for Seamless Red Brass Pipe, Standard
Sizes
ASTM B 135-02: Specification for Seamless Brass Tube
ASTM B 135M-00: Specification for Seamless Brass Tube [Metric]
ASTM B 241/B 241M-02: Specification for Aluminum and Aluminum-Alloy Seamless Pipe
and
Seamless Extruded Tube
ASTM C 33-03: Specification for Concrete Aggregates
ASTM C 1107-05: Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM D 1187-97 (Reapproved 2002): Specification for Asphalt-Base Emulsions for Use as
Protective Coatings for Metal

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.
NAAMM FP 1001-1997: Guide Specifications for Design of Metal Flagpoles

SSPC: The Society for Protective Coatings

SSPC-SP 5/NACE No. 1 2000 (Revised 2004): Surface Preparation Specification SSPCSP
5/NACE No. 1: White Metal Blast Cleaning
SSPC-SP 8 1982 (Revised 2004): Surface Preparation Specification No. 8: Pickling

Structural Engineering Institute/American Society of Civil Engineers

SEI/ASCE 7-2002: Minimum Design Loads for Buildings and Other Structures

SECTION 10410 - DIRECTORIES
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum
AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
for
Pigmented Organic Coatings on Aluminum Extrusions and Panels

American Society of Civil Engineers/Structural Engineering Institute

ASCE/SEI 7-2005: Minimum Design Loads for Buildings and Other Structures

ASTM International

ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet,
Strip, Plate, and Flat Bar
ASTM B 36/B 36M-06: Specification for Brass Plate, Sheet, Strip, and Rolled Bar
ASTM B 209-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 221-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes

Page 90 of 183

ASTM B 221M-05a: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire,
Profiles, and Tubes [Metric]
ASTM C 1036-01: Specification for Flat Glass
ASTM C 1048-04: Specification for Heat-Treated Flat Glass - Kind HS, Kind FT Coated and
Uncoated Glass
ASTM D 1003-00: Test Method for Haze and Luminous Transmittance of Transparent
Plastics
ASTM D 4802-02: Specification for Poly(Methyl Methacrylate) Acrylic Plastic Sheet
ASTM E 84-05: Test Method for Surface Burning Characteristics of Building Materials

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

NFPA

NFPA 70-2005: National Electrical Code

SECTION 10431 - SIGNS
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specifications for Anodized Architectural Aluminum
AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Pigmented Organic Coatings on Aluminum Extrusions and Panels

ASTM International

ASTM A 240/A 240M-04a: Specification for Chromium and Chromium-Nickel Stainless
Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 529/A 529M-04: Specification for High Strength Carbon-Manganese Steel of
Structural Quality
ASTM A 572/A 572M-04: Specification for High-Strength Low-Alloy Columbium-
Vanadium Structural Steel
ASTM A 591/A 591M-98: Specification for Steel Sheet, Electrolytic Zinc-Coated, for Light
Coating Weight [Mass] Applications
ASTM A 653/A 653M-04a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 1008/A 1008M-04b: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low Alloy and High-Strength Low-Alloy with Improved Formability
ASTM B 26/B 26M-03: Specification for Aluminum Alloy Sand Casting
ASTM B 36/B 36M-01: Specification for Brass Plate, Sheet, Strip, and Rolled Bar
ASTM B 152/B 152M-00: Specification for Copper Sheet, Strip, Plate, and Rolled Bar
ASTM B 209-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 221-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Shapes, and Tubes
ASTM B 221M-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Shapes, and Tubes [Metric]
ASTM B 584-00: Specification for Copper Alloy Sand Castings for General Applications
Page 91 of 183

ASTM D 256-04: Test Methods for Determining the Izod Pendulum Impact Resistance of
Plastics
ASTM D 638-03: Test Method for Tensile Properties of Plastics
ASTM D 648-04: Test Method for Deflection Temperature of Plastics Under Flexural Load in
Edgewise Position
ASTM D 790-03: Test Method for Flexural Properties for Unreinforced and Reinforced
Plastics and Electrical Insulating Materials
ASTM D 1044-99: Test Method for Resistance of Transparent Plastics to Surface Abrasion
ASTM D 4802-02: Specification for Poly(Methyl Methacrylate) Acrylic Plastic Sheet

International Code Council/American National Standards Institute

ICC/ANSI A117.1-98: Accessible and Usable Buildings and Facilities

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

NFPA

NFPA 70-02: National Electrical Code

SSPC: The Society for Protective Coatings

SSPC-SP 5/NACE No. 1 2000: Joint Surface Preparation Standard SSPC-SP 5/NACE No. 1:
White Metal Blast Cleaning
SSPC-SP 8 1982 (Revised 2000): Surface Preparation Specification No. 8: Pickling

Underwriters Laboratories Inc.

UL 924-01: Emergency Lighting and Power Equipment

U.S. Architectural & Transportation Barriers Compliance Board

Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities;
Architectural Barriers Act (ABA) Accessibility Guidelines. Adopted in 2004.

SECTION 10436 - POST AND PANEL SIGNS
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specifications for Anodized Architectural Aluminum
AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
for
Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 2604-2002: Voluntary Specification, Performance Requirements and Test Procedures
for
High Performance Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2002: Voluntary Specification, Performance Requirements and Test Procedures
for
Superior Performing Organic Coatings on Aluminum Extrusions and Panels

Page 92 of 183

ASTM International

ASTM A 36/A 36M-04: Specification for Carbon Structural Steel
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel
Products
ASTM A 240/A 240M-04a: Specification for Chromium and Chromium-Nickel Stainless
Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A 307-04: Specification for Carbon Steel Bolts and Studs, 60,000 psi Tensile Strength
ASTM A 325-04: Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi
Minimum
Tensile Strength
ASTM A 325M-X04: Specification for Structural Bolts, Steel, Heat Treated 830 MPa
Minimum
Tensile Strength [Metric]
ASTM A 500-03a: Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural
Tubing in Rounds and Shapes
ASTM A 529/A 529M-04: Specification for High Strength Carbon-Manganese Steel of
Structural
Quality
ASTM A 572/A 572M-04: Specification for High-Strength, Low-Alloy Columbium-
Vanadium
Structural Steel
ASTM A 591/A 591M-98: Specification for Steel Sheet, Electrolytic Zinc-Coated, for Light
Coating Weight [Mass] Applications
ASTM A 653/A 653M-04a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron
Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet,
Strip, Plate, and Flat Bar
ASTM A 780-01: Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized Coatings
ASTM A 1008/A 1008M-04b: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability
ASTM B 152/B 152M-00: Specification for Copper Sheet, Strip, Plate, and Rolled Bar
ASTM B 209-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B 209M-04: Specification for Aluminum and Aluminum-Alloy Sheet and Plate
[Metric]
ASTM B 221-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire,
Shapes, and Tubes
ASTM B 221M-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire,
Shapes, and Tubes [Metric]
ASTM D 256-04: Test Methods for Determining the Izod Pendulum Impact Resistance of
Plastics
ASTM D 638-03: Test Method for Tensile Properties of Plastics
ASTM D 648-04: Test Method for Deflection Temperature of Plastics Under Flexural Load in
Edgewise Position
ASTM D 790-03: Test Method for Flexural Properties for Unreinforced and Reinforced
Plastics
Page 93 of 183

and Electrical Insulating Materials
ASTM D 1044-99: Test Method for Resistance of Transparent Plastics to Surface Abrasion
ASTM D 4802-02: Specification for Poly(Methyl Methacrylate) Acrylic Plastic Sheet

International Code Council/American National Standards Institute

ICC/ANSI A117.1-98: Accessible and Usable Buildings and Facilities

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

NFPA

NFPA-70-02: National Electrical Code

SSPC: The Society for Protective Coatings

SSPC-Paint 20 2002: Paint Specification No. 20: Zinc-Rich Primers (Type I, Inorganic, and
Type
II, Organic)
SSPC-SP 5/NAC No. 1 2000: Joint Surface Preparation Standard SSPC-SP 5/NAC No. 1:
White
Metal Blast Cleaning
SSPC-SP 8 1982 (Revised 2000): Surface Preparation Specification No. 8: Pickling

Structural Engineering Institute/American Society of Civil Engineers

SEI/ASCE 7-02: Minimum Design Loads for Buildings and Other Structures

U.S. Architectural & Transportation Barriers Compliance Board

Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities;
Architectural Barriers Act (ABA) Accessibility Guidelines. Adopted in 2004.

SECTION 10505 - METAL LOCKERS
American National Standards Institute

ANSI A208.1-1999: Particleboard

ASTM International

ASTM A 500-03a: Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural
Tubing in Rounds and Shapes
ASTM A 653/A 653M-05: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron
Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet,
Strip, Plate, and Flat Bar

Page 94 of 183

ASTM A 1008/A 1008M-05: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-
Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution-
Hardened, and
Bake Hardenable
ASTM B 221-05: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire,
Profiles, and Tubes
ASTM B 221M-05: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire,
Profiles, and Tubes [Metric]
ASTM F 1267-01: Specification for Metal, Expanded, Steel

International Code Council/American National Standards Institute

ICC/ANSI A117.1-2003: Accessible and Usable Buildings and Facilities

National Electrical Manufacturers Association

NEMA LD 3-2005: High Pressure Decorative Laminates

U.S. Architectural & Transportation Barriers Compliance Board

Americans with Disabilities Act (ADA) and Architectural Barriers Act (ABA) Accessibility
Guidelines for Buildings and Facilities. Adopted in 2004.

SECTION 10616 - SITE-ASSEMBLED DEMOUNTABLE PARTITIONS
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specification for Anodized Architectural Aluminum

American Society of Civil Engineers

ASCE 7-98: Minimum Design Loads for Buildings and Other Structures

ASTM International

ASTM C 36/C 36M-01: Specification for Gypsum Wallboard
ASTM E 72-02: Test Methods of Conducting Strength Tests of Panels for Building
Construction
ASTM E 84-03: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 90-02: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss of Building Partitions and Elements
ASTM E 119-00a: Test Methods for Fire Tests of Building Construction and Materials
ASTM E 413-87 (Reapproved 1999): Classification for Rating Sound Insulation

BIFMA International

BIFMA X 5.6-03: Panel Systems - Tests (ANSI)

Chemical Fabrics & Film Association, Inc.

CFFA-W-101-A-02: Quality Standard for Vinyl Coated Fabric Wallcovering
Page 95 of 183

NFPA

NFPA 70-02: National Electrical Code
NFPA 80-99: Fire Doors and Fire Windows
NFPA 252-03: Fire Tests of Door Assemblies

Underwriters Laboratories Inc.

UL 10B-97 (Rev. 01): Fire Tests of Door Assemblies
UL 10C-98: Positive Pressure Fire Tests of Door Assemblies
Fire Resistance Directory. 2003.

SECTION 10655 - ACCORDION FOLDING PARTITIONS
American Society of Civil Engineers/Structural Engineering Institute

ASCE/SEI 7-2005: Minimum Design Loads for Buildings and Other Structures

ASTM International

ASTM C 423-07a: Test Method for Sound Absorption and Sound Absorption Coefficients by
the
Reverberation Room Method
ASTM E 84-08: Test Method for Surface Burning Characteristics of Building Materials
ASTM E 90-04: Test Method for Laboratory Measurement of Airborne Sound Transmission
Loss
of Building Partitions and Elements
ASTM E 336-07: Test Method for Measurement of Airborne Sound Attenuation Between
Rooms
in Buildings
ASTM E 413-04: Classification for Rating Sound Insulation
ASTM E 557-00 (Reapproved 2006): Guide for the Installation of Operable Partitions

California Department of Health Services

Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using
Small-
Scale Environmental Chambers. 2004.

Chemical Fabrics & Film Association, Inc.

CFFA-W-101-D-2002: Quality Standard for Vinyl Coated Fabric Wallcovering

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at
www.fsc.org)
Page 96 of 183

National Electrical Manufacturers Association

NEMA ICS 1-2000 (Reaffirmed 2005): Industrial Control and Systems: General
Requirements
NEMA ICS 2-2000 (Reaffirmed 2005): Industrial Control and Systems: Controllers,
Contactors,
and Overload Relays Rated 600 Volts
NEMA ICS 6-1993 (Reaffirmed 2006): Industrial Controls and Systems: Enclosures
NEMA LD 3-2005: High-Pressure Decorative Laminates (ANSI)
NEMA MG 1-2006 (Revision No. 1, 2007): Motors and Generators

NFPA

NFPA 70-2008: National Electrical Code
NFPA 80-2007: Fire Doors and Fire Windows (ANSI)
NFPA 265-2007: Standard Methods of Fire Tests for Evaluating Room Fire Growth
Contribution
of Textile Coverings on Full Height Panels and Walls
NFPA 286-2006: Standard Methods of Fire Tests for Evaluating Contribution of Wall and
Ceiling
Interior Finish to Room Fire Growth

Underwriters Laboratories Inc.

UL 10B-2004: Fire Tests of Door Assemblies

SECTION 10671 - METAL STORAGE SHELVING
American National Standards Institute

ANSI A135.4-2004: Basic Hardboard
ANSI A208.1-1999: Particleboard

American Society of Civil Engineers/Structural Engineering Institute

ASCE/SEI 7-2005: Minimum Design Loads for Buildings and Other Structures

American Welding Society

AWS D1.3-1990: Structural Welding Code - Sheet Steel

ASTM International

ASTM A 513-00: Specification for Electric-Resistance-Welded Carbon and Alloy Steel
Mechanical Tubing
ASTM A 554-03: Specification for Welded Stainless Steel Mechanical Tubing
ASTM A 580/A 580M-06: Specification for Stainless Steel Wire
ASTM A 653/A 653M-05a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 780-01: Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized Coatings
ASTM A 899-91 (Reapproved 2002): Specification for Steel Wire, Epoxy-Coated
ASTM A 1008/A 1008M-05b: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability,
Page 97 of 183

Solution Hardened, and Bake Hardenable
ASTM A 1011/A 1011M-05a: Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon,
Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved
Formability

Material Handling Industry of America

MH 28.1-1997: For the Design, Testing, Utilization and Application of Industrial Grade Steel
Shelving - Specifications (ANSI)
MH 28.2-2003: Design and Testing of Boltless Metal-Wood Shelving (ANSI)

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

SSPC: The Society for Protective Coatings

SSPC-Paint 20 2002 (Revised 2004): Paint Specification No. 20: Zinc-Rich Coating, Type
IInorganic and Type II- Organic
SSPC-SP 5/NACE No. 1 2000 (Revised 2004): Joint Surface Preparation Specification
SSPCBSP 5/NACE No. 1: White Metal Blast Cleaning
SSPC-SP 8 1982 (Revised 2000): Surface Preparation Specification No. 8: Pickling

SECTION 10705 - EXTERIOR SUN CONTROL DEVICES
American Architectural Manufacturers Association

AAMA 2603-2002: Voluntary Specification, Performance Requirements and Test Procedures
for
Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605-2002: Voluntary Specification, Performance Requirements and Test Procedures
for
Superior Performing High Performance Organic Coatings on Aluminum Extrusions and
Panels

American Welding Society

AWS D1.2/D1.2M-2003: Structural Welding Code - Aluminum
AWS D1.6-1999: Structural Welding Code - Stainless Steel

ASTM International

ASTM A269 - 08 Standard Specification for Seamless and Welded Austenitic Stainless Steel
Tubing for General Service
ASTM A 307-04: Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile
Strength
ASTM A449 - 07b Standard Specification for Hex Cap Screws, Bolts and Studs, Steel, Heat
Treated, 120/105/90 ksi Minimum Tensile Strength, General Use
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM B211 - 03 Standard Specification for Aluminum and Aluminum-Alloy Bar, Rod, and
Wire

Page 98 of 183

SECTION 10801 - TOILET AND BATH ACCESSORIES
ASTM International

ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A 653/A 653M-06a: Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-
Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A 666-03: Specification for Annealed or Cold-Worked Austenitic Stainless Steel
Sheet, Strip, Plate, and Flat Bar
ASTM A 1008/A 1008M-07: Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,
High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution
Hardened, and Bake Hardenable
ASTM B 16/B 16M-05: Specification for Free-Cutting Brass Rod, Bar and Shapes for Use in
Screw Machines
ASTM B 19-05: Specification for Cartridge Brass Sheet, Strip, Plate, Bar, and Disks
ASTM B 30-06a: Specification for Copper Alloys in Ingot Form
ASTM B 456-03: Specification for Electrodeposited Coatings of Copper Plus Nickel Plus
Chromium and Nickel Plus Chromium
ASTM C 1503-01: Specification for Silvered Flat Glass Mirror
ASTM F 446-85 (Reapproved 2004): Consumer Safety Specification for Grab Bars and
Accessories Installed in the Bathing Area

NFPA

NFPA 70-2008: National Electrical Code

SECTION 11160 - LOADING DOCK EQUIPMENT
American National Standards Institute

ANSI Z535.1-2002: Safety Color Code

American Welding Society

AWS D1.1/D.1.1M-2004: Structural Welding Code - Steel
AWS D1.3-1998: Structural Welding Code - Sheet Steel

American Wood-Preservers' Association

AWPA C2-2002: Lumber, Timber, Bridge Ties and Mine Ties - Preservative Treatment by
Pressure Process

ASTM International

ASTM A 36/A 36M-05: Specification for Carbon Structural Steel
ASTM A 123/A 123M-02: Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
ASTM A 153/A 153M-05: Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Page 99 of 183

Hardware
ASTM A 500-03a: Specification for Cold-Formed Welded and Seamless Carbon Steel
Structural Tubing in Rounds and Shapes
ASTM A 572/A 572M-04: Specification for High-Strength Low-Alloy Columbium-
Vanadium Structural Steel
ASTM A 786/A 786M-00b: Specification for Hot-Rolled Carbon, Low-Alloy, High-Strength
Low-Alloy, and Alloy Steel Floor Plates
ASTM D 2000-05: Standard Classification System for Rubber Products in Automotive
Applications
ASTM D 2240-05: Test Method for Rubber Property-Durometer Hardness
ASTM D 2261-96 (Reapproved 2002): Test Method for Tearing Strength of Fabrics by the
Tongue (Single Rip) Procedure (Constant-Rate-of-Extension Tensile Testing Machine)
ASTM F 2329-05: Specification for Zinc Coating, Hot-Dip, Requirements for Applications to
Carbon and Alloy Steel Bolts, Screws, Washers, Nuts and Special Threaded Fasteners

Federal Standards

FED-STD-191A-5100.1-1989: Strength and Elongation, Breaking of Woven Cloth; Grab
Method
FED-STD-191A-5306-1978: Abrasion Resistance of Cloth; Rotary Platform, Double-Head
(Taber) Method
FED-STD-191A-5874-1978: Temperature, Low; Effect on Coated Cloth

Material Handling Industry of America

MH 29.1-2003: Safety Requirements for Industrial Scissors Lifts (ANSI)
MH 30.1-1993 (Revised 2000): Safety, Performance and Testing of Dock Leveling Devices
(ANSI)
MH 30.3-2005: Vehicle Restraining Devices: Safety, Performance and Testing (ANSI)

National Electrical Manufacturers Association

NEMA ICS 6-1993 (Reaffirmed 2001): Industrial Control and Systems: Enclosures

NFPA

NFPA 70-2005: National Electrical Code

U.S. Department of Commerce, National Institute of Standards and Technology

DOC PS 20-1999: American Softwood Lumber Standard

SECTION 11172 - WASTE COMPACTORS
ANSI Z245.1 - Safety Requirements for Refuse Collection and Compaction
Equipment.
NEMA MG1 - Motors and Generators
NSWMA (National Solid Wastes Management Association) - Commercial / Industrial
Compactors Ratings

Page 100 of 183

SECTION 11400 FOOD SERVICE EQUIPMENT
UL Underwriters Laboratory.

ASTM
ASTM A 36: Specification for Carbon Structural Steel
ASTM A 153: Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware.
ASTM A 123: Specification for Zinc (Hot Dip Galvanized) Coatings on Iron and Steel
Products.
ASTM A 385: Practice for Providing High Quality Zinc Coatings (Hot-Dip).
AWS D1.1: Structural Welding Code.
ASTM A 446: Specification for Steel Sheet, Zinc-Coated (Galvanized) by the Hot-Dip
Process, Structural (Physical) Quality.
ASTM A 666: Specification for Austenitic Stainless Steel Sheet, Strip, Plate and Flat Bar.
ASTM C 1036: Specification for Flat Glass.
ASTM C 1048: Specification for Heat-Treated Flat Glass - Kind HS, Kind FT Coated and
Uncoated Glass.
NEMA LD3: Specification for High Pressure Decorative Laminates.
NFPA National Fire Protection Association: Appliances.
NFPA 96: Removal of Smoke and Grease Laden Vapors from Commercial Cooking
Equipment.
NSF National Sanitation Foundation: Appliances.
Exhaust Hoods: Conform to NFPA 96
Sheet Steel: ASTM A 653, 380 g/sq m galvanized coating.
Stainless Steel: ASTM A 666, Type 304 316 commercial grade, No. 4 finish.
Glass: ASTM C 1036 ASTM C 1048; 5.5 mm flat laminated heat strengthened tempered
type; exposed edges ground, cut or drilled to receive hardware.
Plastic Laminate: NEMA LD3; 1.27 mm thick; acid-resistant, color as selected.
Laminate Backing Sheets: NEMA LD3 Type BK20, 0.5 mm thick, unfinished, plastic
laminate.
Structural Shapes: All angles, band channels, etc., used for framing shall conform to ASTM
A 36.
Hot dip galvanization shall conform to ASTM A 386.

SECTION 11455 - RESIDENTIAL APPLIANCES AND PANTRY EQUIPMENT

New kitchen and laundry equipment specified herein shall be new factory shipped models.
Floor and showroom models are prohibited.

Items shall be furnished with applicable UL listing and electrical features adapted to local
electric power.

Manufacturer: As selected by Engineer.

Model: As accepted by Engineer.

Page 101 of 183

SECTION 12000 - FURNITURE
NFPA
NFPA 260: Standard Methods of Tests and Classification System for Cigarette Ignition
Resistance of Components of Upholstered Furniture.
ASTM C 150
ASTM A 446
ASTM A 36
ASTM A 525
ASTM D 668
ASTM E 84
BS 4875
BS 5651
BS 3120
BS 191-93

SECTION 12356 - RESIDENTIAL CASEWORK
American National Standards Institute

ANSI A135.4-2004: Basic Hardboard
ANSI A208.1-1999: Particleboard
ANSI A208.2-2002: Medium Density Fiberboard (MDF)

Builders Hardware Manufacturers Association

BHMA A156.9-2001: American National Standard for Cabinet Hardware (ANSI)

California Department of Health Services

Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using
Small-Scale Environmental Chambers. 2004.

Forest Stewardship Council

FSC STD-01-001-2004: FSC Principles and Criteria for Forest Stewardship (available in PDF
at www.fsc.org)

Page 102 of 183

Hardwood Plywood & Veneer Association

HPVA HP-1-2000: American National Standard for Hardwood and Decorative Plywood
(ANSI)

Kitchen Cabinet Manufacturers Association

KCMA A161.1-2000: Performance & Construction Standard for Kitchen and Vanity Cabinets
KCMA A161.2-1998: Performance Standard for Fabricated High Pressure Decorative
Laminate Countertops

National Electrical Manufacturers Association

NEMA LD 3-2005: High Pressure Decorative Laminates

National Institute of Standards and Technology, Department of Commerce

DOC PS 1-1995: U.S. Product Standard for Construction and Industrial Plywood

SECTION 12484 - FLOOR MATS AND FRAMES
American Architectural Manufacturers Association

AAMA 611-1998: Voluntary Specifications for Anodized Architectural Aluminum

ASTM International

ASTM B 221-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes
ASTM B 221M-02: Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, Profiles, and Tubes [Metric]
ASTM B 455-01: Specification for Copper-Zinc-Lead Alloy (Leaded-Brass) Extruded Shapes

International Code Council

ICC A117.1-98: Accessible and Usable Buildings and Facilities (ANSI)

National Association of Architectural Metal Manufacturers

Metal Finishes Manual for Architectural and Metal Products. 1988.

U.S. Architectural & Transportation Barriers Compliance Board

Americans with Disabilities Act (ADA), Accessibility Guidelines for Buildings and Facilities
(ADAAG). Adopted in 1991; continual revisions.

SECTION 12497 - DRAPERIES AND TRACKS
NFPA

NFPA 70-2008: National Electrical Code
NFPA 701-2004: Methods of Fire Tests for Flame Propagation of Textiles and Films

Page 103 of 183

Window Covering Manufacturers Association

WCMA A 100.1-2007: Safety of Corded Window Covering Products (ANSI)

SECTION 13080 - SOUND AND VIBRATION CONTROL

American Architectural Manufacturers Association

AAMA 2605-2002: Voluntary Specification, Performance Requirements and Test Procedures
for Superior Performing High Performance Organic Coatings on Aluminum Extrusions and
Panels

ASTM International

ASTM A591/A591M: Standard Specification for Steel Sheet, Electrolytic Zinc-Coated, for
Light Coating Weight [Mass] Applications
ASTM B633 - 07 Standard Specification for Electrodeposited Coatings of Zinc on Iron and
Steel
ASTM C553 - 08 Standard Specification for Mineral Fiber Blanket Thermal Insulation for
Commercial and Industrial Applications
ASTM C834 - 05 Standard Specification for Latex Sealants
ASTM E90 - 04 Standard Test Method for Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions and Elements
ASTM E488 - 96(2003) Standard Test Methods for Strength of Anchors in Concrete and
Masonry Elements
ASTM E1190 - 95(2007) Standard Test Methods for Strength of Power-Actuated Fasteners
Installed in Structural Members.

SECTION 12520 MODULAR OFFICE FURNITURE
ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building
Materials
ANSI/HFES 100-2007, Human Factors Engineering of Computer Workstations.
ANSI/BIFMA - American National Standard For Office Furnishings.
ANSI A208.1 - Particleboard Standard.
ANSI/BIFMA X5.5 - American National Standard For Office Furnishings-Desk Products
NEMA LD 3 - High Pressure Decorative Laminates.
ADA: Accessibility Guidelines for Buildings and Facilities.
California Technical Bulletin 117 - Requirements, Test Procedure and Apparatus for Testing
the Flame Retardance of Resilient Filling Materials Used in Upholstered Furniture
US Green Building Council.

SECTION 13038 COLD STORAGE ROOM
APA - American Plywood Association
ASTM A264 - Stainless Chromium-Nickel-Steel Clad Plate, Sheet, and Strip.
ASTM A446 - Steel Sheet, Zinc-Coated (Galvanized by the Hot Dip Process, Physical
(Structural) Quality.
ASTM A792 - Steel Sheet, Aluminum-Zinc Alloy-Coated by the Hot Dip Process.
Page 104 of 183

ASTM B209 - Aluminum-Alloy, Sheet and Plate.
ASTM E283 - Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors.
NSF - National Sanitation Foundation.

SECTION 12800 INTERIOR PLANTS AND PLANTERS

AAN - American Association of Nurserymen:
Botanical Listing, Tagging and Sizes
AJCHN - American Joint Committee on Horticultural Nomenclature:
Latest Edition of Standardized Plant Names
ANSI - American National Standards Institute:
ANSI Z60.1 American Standard for Nursery Stock
ASTM - American Society for Testing and Materials:
ASTM C 136 Sieve or Screen Analysis of Fine and Coarse Aggregates
AOAC - Association of Official Analytical Chemists:
Official Methods of Analysis
Royal Horticultural Society:
Dictionary of Gardening
ALCA - Associated Landscape Contractors of America:
Guide to Specifications for Interior Landscaping

SECTION 13152 SWIMMING POOL ACCESSORIES

AAU American Athletic Association
NFSHA National Federation of State High School Associations
Furnish and install equipment meeting the requirements of American Athletic Association
(AAU); National Federation of State High School Associations (NFSHA); and pertinent electrical
codes, plumbing codes, and health codes.

SECTION 13640 - TOP RUNNING DOUBLE GIRDER (BRIDGE CRANE)

Crane Manufacturers Association of America (CMAA)
Specification No. 70 for Top Running & Under Running Single Girder Electric Overhead
Traveling Cranes.
American National Standard (ANSI)
ANSI B-30.16 Overhead Hoists
Occupational Safety and Health Administration (OSHA)
Par. 1910.179 Overhead & Gantry Cranes
Hoist Manufacturers Institute (HMI)
National Electric Code (NEC)
NEC (Latest Edition Article 610 Cranes and Hoists)
American Institute of Steel Construction (AISC)
Specification for the Design, Fabrication, and Erection of Structural Steel for Buildings
American Society for Testing and Materials (ASTM)
A36/A36M - Specification for Carbon Structural Steel
American Welding Society (AWS)
D1.1 - Structural Welding Code Steel
D14.1 - Overhead Cranes
Page 105 of 183

4. STRUCTURE
Page 106 of 183

4. Structural
4.1 Codes and Standards

The design and construction of the structural works shall be based on the latest edition of the
following Saudi and International standards:
4.2 Reinforced Concrete Design

Design :
Saudi Building Code SBC 304
American Concrete Institute ACI 318
Detailing:
Saudi Building Code SBC 304
American Concrete Institute ACI 315
Testing:
Saudi Building Code SBC 302
American Society of Testing and Materials (ASTM)
4.3 Structural Steel Design

Saudi Building Code SBC 306
AISC "Specification for Structural Steel Buildings" including "Commentary" and
Supplements thereto as issued, ANSI/AISC.
American Institute of Steel Construction - Steel Construction Manual.
AISC "Seismic Provisions for Structural Steel Buildings." ANSI/AISC 341-05 Including
Supplement No. 1 ANSI/AISC 341s1-05
ASTM A 6 (ASTM A 6M) "Specification for General Requirements for Rolled Steel
Plates, Shapes, Sheet Piling, and Bars for Structural Use".
Research Council on Structural Connections' (RCSC) "Specification for Structural Joints
Using ASTM A 325 or A 490 Bolts.
American Welding Society (AWS) D1.1 / D 1.1 M: "Structural Welding Code - Steel"
AISC "Specifications for Architecturally Exposed Structural Steel"
AISC Code of Standard Practice for Steel Buildings and Bridges.
Cold Formed Steel Design Manual- American Iron and Steel Institute AISI.
Structural Welding Code American Welding Society ANSI AWS D1.1.
Uniform Building Code UBC, 1997
Minimum Design Loads for Buildings and other Structures ASCE- 7-05
Steel Structure Painting Manual steel Structures Painting Council SSPC
4.4 Pre-stressed Concrete Design

Saudi Building Code SBC 304
American Concrete Institute ACI 318
Portland Cement Association (PCA)
PCI pre-cast /pre-stressed concrete institute for design and detailing.
Page 107 of 183

4.5 Masonry Design

Saudi Building Code SBC 305
National Concrete Masonry Association (NCMA)
4.6 Other Standards

(SASO) Saudi Arabian Standards Organization
British Standards (BS).
Concrete Reinforcing Steel Institute (CRSI).
Portland Cement Association (PCA).
American Association of State Highway and transportation Officials (AASHTO).
4.7 Design Criteria

The structural design concept must be based on functional, economical and efficient systems.
The systems adopted are to be chosen to fulfill the specific architectural requirement, in
addition to any other requirements related to utilities and services.

The most critical load combinations shall govern the design of structural members including
combinations of lateral and secondary loads.
4.8 Loads Assessment

Live loads:
Saudi Building Code SBC 301
Uniform Building Code (UBC) 1997 edition
ANSI / ASCE 7-05 "Minimum Design Loads for Buildings and other
Structures"
Seismic loads:
Saudi Building Code SBC 301
UBC 1997 Edition, with seismic zone and soil classification according to site
location and to Saudi standards.
Wind loads:
Saudi Building Code SBC 301
UBC 1997 Edition, with Basic Wind Speed and exposure as site location and
Saudi standards.
Dynamic Loads: dynamic effect caused by vibrating loads shall be assessed by
established analytical methods or design data from suppliers and subsequently
incorporated in the design
Temperature Variations: +/-30 degrees C. (to be checked with the site location and Saudi
standards)
Truck loads shall be as per AASHTO, SASO and MOT
Importance factors for essential and other buildings shall be used in the design as per
UBC.
Page 108 of 183

4.9 Load Combinations

Combinations of loads applied to structure shall follow those listed in
Saudi Building Code SBC 301, SBC 304, SBC 305 and SBC 306.
UBC 1997.
4.10 Vertical Deflection and Lateral Sway

Limits for vertical deflection and lateral sway of any structure or structural member shall be
based on the requirements of SBC 301, SBC 304, SBC 305,SBC 306, ACI 318, UBC 1997
and ASCE 7-05.
4.11 Computer Programs

Where structural computer analyses are used, they should be carried out using well-known
computer programs. Moreover, the Consultant shall submit the original copy of the computer
programs software with manuals that are used in the design, and verification evidence of all
computer programs used.

4.12 Structural Materials
Reinforced Concrete:
The classes of concrete should be clearly identified for different structural members
considering design requirements and availability of concrete technology and materials.
Types of cement and grades of reinforcing steel will be selected accordingly.

The following data is for guidance only, and is subject to change based on the detailed
design requirements:

Page 109 of 183

Table 1.1: Concrete 28 days cylinder strength & properties:
Concrete
Class
Cylinder
Strength
N/mm
2
Maximum
Slump
mm
Maximum
Water/Cement
Ratio
Location
A 40/50
100 0.4
Precast Concrete.
B 30/35 100 0.4
All reinforced concrete elements
except the slabs on grade.
C 20/24 100 0.45
Slabs on grade and Structural
Plain Concrete
D 20 100 0.5
Plain or Blinding concrete.
Reinforcement: Deformed high tensile steel bars according to ASTM A 615M,
Grade 60.
Pre-stressing steel: 7-wire stress-relieved low-relaxation super-strand conforming to
BS5896 or ASTM A416-85 grade 270.
Cement: Ordinary Portland cement shall conform to ASTM C150 Type I for
superstructure. However, for substructure, the type of cement shall be based on the
chemical analysis of soil (as per the durability requirements shown in chapter 4 of the
ACI 318 code).and/or recommended by Geotechnical Report.

Page 110 of 183

4.13 Structural Steel

The following is for guidance only, and is subject to change based on the detailed design
requirements:

Structural Steel Shapes, Plates and Bars:

ASTM A572 Grade 50 having a minimum yield stress of 345 N/mm2 [50 ksi] or approved
equal.

Structural Steel Hollow Sections:

Cold formed steel Hollow Square and rectangular sections are to be ASTM A500, Grade
B, having a minimum yield stress of 345 MPa or equal.

Cold rolled steel Z and C sections:
To be ASTM A653M grade HSLAS, type A, Grade 50 (340) and ASTM A924/A924M,
having a minimum yield stress 345 MPa, or equal, and shall be galvanized in accordance
with ASTM A525 to give a life to first maintenance with coating class of G-90.

Headed Stud-Type Shear Connectors:
AWS D1.1, type B, minimum yield strength 345 N/mm2 [50 ksi] at 0.2% offset, made
from steel to ASTM A108, with mechanical properties to ASTM A370.

High-Strength Threaded Fasteners:
Quenched and tempered alloy steel bolts, nuts and washers, complying with ASTM A 490,
or A325.

Page 111 of 183

Metal-Arc Welding Electrodes:
E70XX series of the Specification for Mild Steel Covered Arc-Welding Electrodes, AWS
A5.1, or the Specification for Low-Alloy Steel Covered Arc-Welding Electrodes, AWS
A5.5.

Bare Electrodes and Granular Flux used in the submerged-arc process:
F7 X-EXXX AWS flux classifications of the Specification for Base Mild Steel Electrodes
and Fluxes for Submerged Arc Welding, AWS A5.17, or A5.23.

4.14 Structural systems

Foundation System

The selection of foundations type shall follow the geotechnical recommendations to
provide the most adequate system to sustain the loads from the superstructures. Special
consideration should be given to water ingress and durability of foundation systems.

Building Structural Systems

The design should be based on the most efficient structural system. Provision of
expansion joints to alleviate thermal stresses should be clearly indicated for both floors
and roof structures. Relationship between expansion joints in floors and those in roofs
should be thoroughly studied.

Durability Provisions

Structures within the scope of this project will be subject to different environmental
conditions; ranging from severe to moderate conditions. For foundations, underground
tanks, elevated tanks and the like, the severity of the environmental conditions is
governed by their assigned function, their closeness to the water front, and their
foundation level with respect to the natural ground level and ground water table. The
design shall provide all the necessary measures to ensure durability of different structural
elements to withstand relevant environmental conditions.

Page 112 of 183

4.15 Fire Protection

Provisions to achieve the projects fire endurance criteria should be clearly stated for reinforced,
concrete, pre-stressed concrete and structural steel elements.

Page 113 of 183

5. GEOTECHNICAL

Page 114 of 183

5.1 Codes and Standards

The design and construction of the geotechnical works shall be based on the latest edition of
the following standards:
- Saudi Building code
- MOT
- ASTM
- BS (British Standard)
- AASHTO
- ISRIC
- EN
- DIN
- CDP,MOI
5.2 Geotechnical Detailed Design Requirements:

- Adequate geotechnical investigation for each structure to the Owner Representatives
satisfaction that would enable the complete and adequate characterization of the geotechnical
conditions and define the engineering properties for all subsurface layers at the locations of
each structure as well as any adjacent location that may affect the structure.
- Adequate Soil improvement system at locations were problematic zones are encountered (If
needed).
- Calculations for safe bearing capacity satisfying stability and serviceability requirements
according to international codes and norms for each building.
- Detailed procedure for cavity detection and methodology for grouting (If needed).
- Design and calculations for slope stability and shoring works (where required) according to
relevant internationals codes and standards that satisfy the safety and stability for site
buildings and neighbouring structures and utilities.
- Design for temporary dewatering works (where required) to allow construction of foundation
works in dry condition.
- Pavement design according to international codes and norms.
- Protection measures for foundations against the soil/rock chemical aggressiveness as
determined by adequate chemical analyses for soils, rocks and groundwater to the Owner
Representatives satisfaction.
- For site adaptation, contractor should take into consideration to make a feasibility study of
execution of project buildings in different levels according to site topography and surrounding
roads levels to decrease the quantities of earth works (Excavation and backfilling).
- Contractor shall make all the necessary procedure to get rid of the storm and rain water outside
the site according to the site conditions.
- Any other Document needed for the proper design and execution of the project.

Page 115 of 183

6. MECHANICAL

Page 116 of 183

6.1 HVAC
--)-- :-
Q;-- ',=-; -,'~--' ')- -----' -';--' _-- -=-;---' ;--'~--' J'--' _--=-- J;'---' ;-- ---' ;,; ~'--=--- '-;
,'---' _ -=- Q' J;'---' _-- - -;-' J';V'; '---' _ ----; -----' -'=-' _ -,--- -';- _ -- -,'~--'
--=--' -',= --- -;;--' ;--'~--' -';- --; -;- -- ---'; -;)--'; -----' -=-- ~'-' ;--'~--' =',- _
_-'---' ~''-; --'~-' -='---' ;,=-'; -;,-'; -,',=-' ~'=,- -; _ -;--' J';'; ;,=- --- -',=; -
--)-' ~'-'~=-' ;----; -- _-- -'-- -,-' ~----' ---'; -;)--'; -----' J'-' --' -,-' - ) ~'-; ---
--- _----'; '-~-' ~'-; -'--- -;)--'; -----' ( ~'-'~=-' '- Q;-- Q' _-- --- '-; -------' ~'==--' ;----;
-';->- '-; ASHRAE, SMACNA&NFPA--- ,'--='; --,--'; --,;--' --' -~-; - --;,- ;-- Q' _-- -~--';
-----' ~'-=; (DUCTED TYPE) -;,-' _ ;-=- --;- ) --;; ----' -;,-' ~'- -'-V' _ -;, --;,- --;
--,--' -;,-' ~'- -'-V' _ _'=- -- - -;, -', ( --,---' -,'---'; -'~-'; -'-,)--' ~----' -- -
'- _-- _- .
GENERAL INSTRUCTION:
Contractor scope of work includes (but not limited to) preparation, submitting all detailed calculations
and all related drawings (taking into account to modify all routings, sizes, equipments capacities and
selection according to modified architectural and ID drawings, actual site location and buildings
orientations) to the engineer to get the approval then supplying, installation, operation, testing,
balancing, commissioning, maintenance and Warranty for all systems and components as per
ASHRAE, SMACNA and NFPA.

GENERAL
1- The cooling load calculations must be reconsidered based on actual site Location, project
orientation and the modified Architectural Sketches, and then the HVAC equipments should be
resized and reselected accordingly.
2- Cooling Load calculations should be submitted for approval under HAP 4.3 or later.
3- Contractor shall check, modify, rectify and update all HVAC works as per modified architectural
and ID Sketches for all buildings.
4- Humidity control will be provided for data base and data storage.
5- Humidifier to be provided on A/C ducted units at areas with low relative humidity.
6- De-Humidifier to be provided on A/C ducted units at areas with high relative humidity.
7- Cupper tubes cupper fins condensing units shall be provided at coastal locations with high relative
humidity.
8- Cooling load calculation should be submitted for detention areas (tanks) based on 36 persons per
tank then the related HVAC unit should be enlarged and reselected accordingly.
9- The air quantity to solitary detention areas to be increased to minimum 35 L/S, the effect of the
increased air quantity to be considered while selecting the related A/C units.
10- The contractor shall allow for an additional stand-by A/C unit (From the same type) for each unit
serving detention areas, as described in BOQ noting that the price in BOQ shall include all
additional associated ductwork, Back draft dampers, motorized dampers, cables, control,
additional isolators and concrete foundations and all needed.
11- Data center will be served via Precision Air Handlers best known as Computer Room Air
Conditioning (CRAC) units.
12- Each low current room, control room and server room to be served by suitable two mini-split
units (One duty and one standby connected to emergency power).
Page 117 of 183

13- Ventilation to be provided as per ASHRAE.
14- Elevator room to be served by suitable mini-split unit or window unit.
15- All HVAC equipments to be selected at 2c higher than outdoor design DBT.
16- Duct work to be coordinated with drop beams before site works begins.
17- Condensate drain for each A/C unit shall provided to nearest drain point and the price shall upload
on A/C unite price.
18- The contractor fully responsible to study and provide HVAC system for each area for all
buildings even not shown on attached sketches.
19- The cooling systems shall use R407 or approved equal.
20- The preparation of calculations and related drawings approach will provide maximum services
availability and flexibility with minimum initial investment and optimum safety and energy
efficiency.
21- The works shall use best quality material and be executed to the highest standards of
workmanship.
22- The following specifications represent the minimum requirements for such works.
23- The Scope of works described herein includes, but is not necessarily limited to the content of this
document.
24- All the attached sketches used as guidance only.

2. HVAC WORKS
2.01 SECTION INCLUDES (BUT NOT LIMITED TO):
Chillers, Air Handling Units, Fan Coils, Computer Room Air Conditioning (CRAC) units, Packaged
Air Conditioning Units (PACU), DX type Split Units comprising indoor Fan-Coil Unit (FCU) and
outdoor Air-Cooled Condensing Unit (ACCU), VAV, Humidifier, De- Humidifier, Chilled water
pipes, Refrigerant pipes, Insulation, Sound attenuators, Ducting and related accessories, Air outlets,
Noise Control, Exhaust/Ventilation Fans, Vibration isolators, HVAC Testing, Adjusting, Balancing,
Control, BMS, All related electrical and civil works and all needed.

2.02 REFERENCES
Latest Issues of the listed Codes and Standards
A. SASO Saudi Arabian Standards Organization.
B. ARI 210 Unitary Air Conditioning Equipment.
C. ARI 270 Sound Rating of Outdoor Unitary Equipment.
D. ARI 360 Commercial Industrial Air Conditioning Equipment.
E. American Society of Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE).
F. Sheet Metal and Air Conditioning Contractors National Association (SMACNA)
G. IEC 328-ANSI Safety Requirements for the Electrical Equipment Room
Air Conditioners.
Page 118 of 183

H. NEC Article 44 Air Conditioning and Refrigerating Equipment.
I. National Fire Protection Association (NFPA).
J. ISO R 859 Testing and Rating Room Air Conditioners.
K. UL 465 Central Cooling Air Conditioners.
L. UL 484 Room Air Conditioners.
M. UL 586 Test Performance of High Efficiency Air Filters.
N. Gulf Life Safety Code.
O. Uniform Building Code (UBC).

2.03 SUBMITTALS
A. Comply with General Requirements for Submittals.
B. Drawings and Documentation:
1. Submittal Schedule
2. Shop Drawings - Layouts, Details, System Schematics
3. Equipment Schedules

C. Products:
1. Submit full manufacturer's data for every item including installation data to enable coordination
requirements to be assessed.
2. As required by the Engineer, for each item: submit a catalog cut or sample; provide manufacturer's
factory performance type or individual test certificate; or arrange for witnessing of factory testing by
the Engineer.

2.04 QUALITY ASSURANCE
C. Obtain applicable test certificates for works testing of sample equipment in this
Section as selected by the Engineer to demonstrate adequate quality, performance and compliance
with relevant codes.

Page 119 of 183

2.05 OPERATION AND MAINTENANCE DATA

Comply with any requirements elsewhere in Specification for Operation and Maintenance material in
higher quantities and/or alternate formats.

2.07 DESIGN CRITERIA
A. Introduction:

Air conditioning for the projects shall be provided keeping in mind the comfort conditions,
temperature control for different spaces, proper ventilation and ease of operation and maintenance.
The site conditions shall be determined according to the land plot location in KSA.

B. Climatic Conditions
Location : Different Regions of KSA
Latitude : According to the site survey.
Longitude : According to the site survey.

Outdoor Design Conditions
Summer:
Dry Bulb As per actual site location.
Mean Coincident Wet Bulb As per actual site location.

Winter:
Dry Bulb As per actual site location.

C. Indoor Design Conditions
To reach comfort conditions and proper environment, it is necessary to maintain and control
temperature and humidity within different areas to acceptable levels.
As such, the indoor design temperature conditions which will be followed in the design of the project
are as follows:
Page 120 of 183

Table.1 Indoor Design Conditions
ROOM / AREA Db %RH
Room of the Field Communication with Batteries
Connected to the Tower (Wireless)
20 40
Data Storage and Data Base Room & UPS Room 20 40
M.D.F Room 23 50
Field Security Control System Room 23 50
Vertical Aviation System Room 23 50
Electronic Violations Detection System Room 23 50
Equipment Inspection Room 23 40
Offices 23 50
Employees Rest Rooms 23 50
Technical Support Director 23 50
Control 23 50
Secretary 23 50
Lounge 23 50
Cafeteria & Services 23 50
Operations Room Director 23 50
Director Rest House 23 50
Meetings Room 23 50
Field Security Room Director 23 50
Administration 23 50
Office of HRH Prince of the Region 20 50
Call Takers 20 50
Rest House 23 50
Archive 23 50
Main Joint Operation Rooms 20 50
Page 121 of 183

Table.1 Indoor Design Conditions
ROOM / AREA Db %RH
Dormitories Sleeping Rooms 23 50
Toilets / Restrooms Ventilation with indirect cooling
Emergency Generator Ventilation Only
Storage Areas 23
Kitchen Ventilation & Cooling to 28 C
Battery Room 22 C
Notes on indoor design conditions:
Indirect cooling shall be achieved by air transfer from any adjacent air-conditioned area to the space
by creating negative pressure via exhaust system.

Tolerances:
Temperature 1 deg. C
Relative humidity 5 %
D. Sound Levels (The Background Noise Level inside the Buildings)
The values of the background level will be represented by the Noise Criteria curves, noted NC. All
the mechanical equipment, including plumbing, ventilation, elevators and air conditioning, should be
designed and installed to meet with the noise criteria levels:

Page 122 of 183

Table.2 Accepted Noise Criteria

-maximum outdoor air borne sound level: It should be less or equal 50 dB from the faade of the
closest building for the inlet and outlet ventilation
-Noise Measurement:
Measurement tolerance should be according to ISC 16032:2004
E. Occupancy Rates
Occupancy within the buildings shall follow the recommendations of ANSI/ASHRAE Standards
62.1-2007, based on each occupancy category and default values for occupant density or on seating
furniture layout as shown on architectural drawings.

2.8 VENTILATION AND FILTERATION
A. For all buildings a good Ventilation and air filtration will be provided to maintain acceptable
indoor air quality and achieve comfort for people inside the buildings according to ASHARE 62
Slandered (Latest addition).
Outdoor air rates will be basically provided in accordance with the recommendations of ANSI /
ASHRAE 62.1-2007 Standards.
B. Air Balance should be made for every building and it should be little pressurized.
C. The fresh air is introduced to the building through one of the next two ways
- 100% fresh air package unit or Central split or AHU with pre-filters and final filters. The Pre-filter
will be of the aluminum cleanable type.
- Direct infiltration to the Air conditioned space by one of the following:
a- installing Ex. Fan the Infiltration shall pass through Louver grill completed with washable Filter.
General Office NC 35
Private Office NC 30
Meeting room NC 30
Prayer Room NC 30
Cafeteria NC 35
Call talkers NC 30
Joint Operation NC 35
Operation Room NC 30
Corridor NC 35
Page 123 of 183

b- Using Fresh air supply fan with Fresh air intake louvers and Sand trap louvers.
D. Provide ventilation system for pump room.
E. Toilets and Pantries: All toilets and pantries will be mechanically ventilated through exhaust fans.
Make-up air will be provided from adjacent spaces by means of pressurization.
F. Kitchens: In addition to the provision of air conditioning for the kitchens, vitiated air generated
from cooking or heating work shall be extracted by means of exhaust hood through fans located on
roof of the building in accordance with NFPA 96. Exhaust ducts shall be welded black steel.
In case of hood flow rate over than 2000 l/s, Ecology Units for air purification system should be
provided to filtrate the exhaust air from grease and smoke.
Make-up air will be provided from the surplus air of adjacent spaces through door grills if the exhaust
air flow is relatively small. Otherwise, supply fans will force make up air inside the space using short
circuit double skin kitchen exhaust hoods.
G. The fresh air requirements for different space functions are tabulated here below:
Table.3 Outdoor Air ventilation rates

ROOM / AREA
People Outdoor Air Rate
L/s/Person
Area Outdoor Air
Rate
L/s/m2
Room of the Field Communication 2.5 0.3
M.D.F Room 2.5 0.3
Field Security Control System Room 2.5 0.3
Vertical Aviation System Room 2.5 0.3
V-SAT Room 2.5 0.3
N.M.S Room 2.5 0.3
Electronic Violations Detection System Room 2.5 0.3
Equipment Inspection Room 2.5 0.3
Rest Rooms 2.5 0.3
Control Room 2.5 0.3
Lounge 3.5 0.3
Kitchen & Services A minimum of 15 ACH Exhaust with makeup air
Page 124 of 183

ROOM / AREA
People Outdoor Air Rate
L/s/Person
Area Outdoor Air
Rate
L/s/m2
Offices 2.5 0.3
Meeting Room 2.5 0.3
Archive 2.5 0.3
Main Operation Rooms 2.5 0.3
Dormitories Sleeping Room 2.5 0.3
Toilets / Restrooms
A minimum of 12 ACH Exhaust with makeup air
(For Common).
A minimum of 8 ACH Exhaust with makeup air
(For Private).
Storage Areas - 0.6
Battery Room A minimum of 6 ACH Exhaust with make-up air
All toilets, kitchen areas and other spaces will be ventilated using fans and ductwork collecting
exhausts in a vertical approach up to roof levels.

2.9 EXECUTION
A. Ductwork:
Rectangular ducts shall be factory-fabricated using a proprietary
Flange joint system, such as Duct Mate, Mez-Flange or similar. Slip-jointed ductwork may be
permitted for ducts 150mm or below on the longer side. Circular ducts shall be factory-fabricated
spiral wound type assembled with prefabricated connectors and fittings of a proprietary push-in
jointing system incorporating elastomeric sealing gaskets. All ductwork connections to air-
conditioning units and fans shall be by means of a fire-resistant flexible connector
B. Insulation:
Inside buildings the thermal insulation on ductwork etc. shall generally be at least 25 mm thick where
its declared value of thermal conductivity at the relevant temperature is equal to or less than 0.04
W/m,C or at least 38mm thick where the declared value of thermal conductivity is between 0.04 and
0.06 W/m,C. In the open air, in plant rooms and in large unconditioned open areas of buildings, the
thermal insulation shall be at least 50 mm thick where the thermal conductivity is less than or equal to
0.04 W/m o C or at least 63 mm thick where the thermal conductivity is between 0.04 and 0.06 W/m o
C.
Page 125 of 183

C. Refrigerant Pipe work:
Refrigerant pipe work connecting FCU and ACCU of DX Split A/C units, if not supplied pre-charged
by the unit manufacturer, shall not be more than 20m long or as Recommended by the manufacturer.

D. Noise and Vibration Control:
All possible steps shall be taken to reduce the noise and vibration from the mechanical equipment:
primarily by careful design and selection of pumps, valves, motors, fans, ducts, elbows, dampers,
grilles, louvers and other related equipment; and by the use of anti-vibration mountings and sound
insulation where specified or necessary to achieve specified Noise Criteria levels.

E. Equipment Installation:
1. Power Supply: Each item of electrically-powered HVAC equipment of whichever type shall be
complete with a local disconnect switch.
2. Mounting:
a. HVAC equipment such as PACUs, ACCUs and fans incorporating motors or refrigerant
compressors shall be mounted using enclosed spring type vibration isolators on a concrete base a
minimum of 100 mm above the surrounding roof or floor finish and 150mm larger all around than the
rectangle enclosing the unit.
b. FCUs and in-line fans shall be mounted using hangers incorporating spring type vibration isolators

2.10 INSPECTION AND TESTING:
A. HVAC units and associated equipments and components shall be inspected and tested in
accordance with the standards (NEBB or AABC) of the approved independent Testing, Adjusting and
Balancing Agency.

2.11 HVAC-AIR OUTLETS AND INLETS
GENERAL DESCRIPTION:
The finale selection of type and shape for air outlet as per Architectural and ID Ceiling drawings.
1. General:
a) Furnish all labor materials, tools, equipment and services for Air Outlets and Inlets, in accordance
with provisions of Contract Documents.
b) Completely coordinate with work of other trades.
c) Although such work is not specifically indicated, furnish and install all supplementary or
miscellaneous items, appurtenances and devices incidental to or necessary for a sound, secure and
complete installation.
d) See Division 1, for General Requirements.
Page 126 of 183

e) Work Included (in the absence of ID):
1. Ceiling Diffusers. (For offices and all areas with tiles ceiling type)
2. Linear Slot Diffusers, supply. (For areas with gypsum ceiling type)
3. Linear Slot Diffusers, Return. (For areas with gypsum ceiling type)
4. Exhaust, Return and Transfer Grille
5. Door Transfer, Grille.
6. Supply Air Grilles.
3. QUALITY ASSURANCE
-Air flow tests and sound level measurements shall be made in accordance with Codes and ASHRAE
Standards.
- Manufacturer shall certify catalogued performance and ensure correct application of air outlet types.

JOB CONDITIONS
- Review requirements of air outlets and inlets as to size, finish and type of mounting prior to
submitting shop drawings and Schedules of outlets and inlets.
- Positions indicated are for guidance only. Check locations of outlets and inlets and make necessary
adjustments in position to conform with Architectural features, symmetry and lighting arrangement.
4. PRODUCTS
GENERAL
Base air outlet application on space noise level to match ASHRAE recommendations.
4.1 CEILING DIFFUSERS
- Provide square ceiling diffusers with louvered face and horizontal air pattern.
- Diffuser shall have central bolt fixing and sub-frame.
- Fabrication: Aluminum with factory baked enamel finish.
- Provide units with one, two, three or four way discharge as necessary.
- Supply Air Diffusers shall be provided with hand-operated opposed blade control damper, key
operated from face of unit.
- Color and finish subject to the Client approval.
4.2 LINEAR SLOT DIFFUSER, SUPPLY
- Fabricate linear slot diffusers from heavy extruded aluminum factory baked enamel finish.
- Diffuser length, number of slots, throws and air volume as indicated on the drawings. Width of
slots shall be 20 mm. Number of slots shall be according to drawings.
- Provide air distribution pattern controller painted matt black in all supply sections. Pattern
controllers shall be face adjustable through full 180. For multi slot diffusers, each slot shall be
individually adjustable.
- Provide diffusers with integral air straightened and hit- and-miss volume control damper,
operable from face.
Page 127 of 183

- Plenums shall be acoustically lined till neck for connection of flexible duct.
- Provide end caps as required.
- Color and finish subject to the Client approval.
- Provide joining strips to neatly join and align sections to give continuous appearance without
overlapping.

4.3 LINEAR SLOT DIFFUSER, RETURN
As supply linear slots diffusers but without plenum and damper.
4.4 WALL SUPPLY REGISTERS
- Registers shall have streamlined and individually adjustable aerofoil blades.
- Fabricate of heavy aluminum extrusions, with factory backed enamel finish.
- Front blades shall be horizontal, and rear blades shall be vertical
- Provide supply registers with integral, gang-operated opposed blade dampers with removable key
operator, operable from face.
- Color and finish subject to the Client approval.
4.5 EXHAUST, RETURN AND TRANSFER GRILLES
- Fabricate grilles of honeycomb pattern core.
- Provide 30 mm margin with concealed fixing and sub-frame.
- Fabricate of aluminum, or stainless steel (if required).
- Provide exhaust grilles with integral, gang-operated opposed blade dampers with removable key
operator, operable from face.
- Color and finish subject to the Client approval.
4.6 DOOR TRANSFER, GRILLE
- Fabricate of V-shaped louvers of heavy aluminum, 25 mm deep on 12 mm centers.
- Provide heavy aluminum frame with auxiliary frame to give finished appearance of both sides of
door.
- Color and finish subject to the Client approval.
5. EXECUTION
INSTALLATION
4.6.1.1 Install in accordance with manufacturers instructions.
4.6.1.2 Check location of outlets and inlets and make necessary adjustments in position to conform
with architectural features, symmetry, and lighting arrangement.
4.6.1.3 Install diffusers to ductwork with air tight connection.
4.6.1.4 Provide balancing dampers on duct take-off to supply and exhaust diffusers, grilles and
registers, despite whether dampers are specified as part of the air outlet assembly.
4.6.1.5 Paint ductwork visible behind air outlets and inlets matte black.
- Smoke Management/Evacuation System

Page 128 of 183

- The building will be provided with Roof Top Smoke Exhaust Fans operating by the BMS system
in case of fire detection. Make up air will be provided from the ground floor level by means of
operable windows which will have its operation interlocked with the Smoke Exhaust Fans
operation.
- Staircase Pressurization System
- Emergency exit staircases will be kept positively pressurized by means of pressurization fans to
ensure the staircases are constantly smoke free in case of fire. Operation of the system will be
triggered via the BMS. Relief dampers will be installed to regulate the maximum pressure limit
accepted to enable doors opening. Smoke system to be as per Saudi Code and Local Authorities
recommendations.
- Building Management System (BMS)
- A building management facility, with a central monitoring(control if mentioned in other
documents) system shall be provided to monitor the mechanical, electrical, security, fire
protection and the building environmental systems. The system shall be connected the BMS in
the educational building
- Individual systems should remain in operation upon failure of the Central Building Management
System.
- The system shall have enough capacity to monitor the environmental data and the functions of all
air conditioning and ventilation systems.

END OF SECTION

Page 129 of 183

6.2 FIRE FIGHTING
GENERAL

The Contractor scope of work includes preparation, submitting all detailed calculations and all related
drawings (taking into account to modify all routings, sizes, equipments capacities and selection
according to modified architectural drawings, actual site location) to the engineer to get the approval
then supplying, installation, operation, testing, balancing, commissioning, maintenance and Warranty
for all systems and components as per NFPA.
The Fire Fighting Systems in this project shall include (but not limited to) all the
Following:
A. The Preparation of calculation (as mentioned above) of Fire Fighting Systems for the project
shall be made strictly in accordance with the requirements of NFPA Codes, requirements of
Local Civil Defense and International Standards and the criteria stated herein, as well as
complying with applicable local codes.
B. The Preparation of calculation (as mentioned above) approach will provide maximum
services availability and flexibility with minimum initial investment and optimum safety.
C. The works shall use best quality material and be executed to the highest standards of
workmanship.
D. The following specifications represent the minimum requirements for such works.
E. The Scope of works described herein includes, but is not necessarily limited to the
content of this document.
F. The MTR shall be read in conjunction with project specifications.
G. The Contractor is fully responsible to review , check and calculate all the
fire system data Pumps , Pipes , etc and provide all the required modification to the fire
system to suite with international standard and NFPA.
H. The Contractor is fully responsible to connect all the fire pipes for all the buildings
with fire network on site.
I. All the buildings included in the project shall be served by one set fire pumps
(located at pump room in site work).
J. Test line with water flow meter and indicated valve to be provided for fire
fighting pump set at pump discharge between non-return valve and OS&Y
gate valve and to be return to fire fighting water tank.
K. Relief valve for fire pump to be provided and its discharge connected to sump
pit.
Page 130 of 183

L. Side wall sprinklers serving tanks solitary rooms should be vandal proof (protected from
possible damage by prisoners ]^_`a bcdefc ( ).
M. The Contractor is fully responsible to follow and implement all the Last
edition of (Civil Defense & NFPA, IBC &Life Safety) instructions and
recommendation.
N. Contractor shall rectify all the fire fighting works as per modified ARCH
Sketches.
SECTION INCLUDES
A. Facility Fire Suppression System described in this section includes fire suppression
system service piping and related components as follows:
Related Sections:
1. Fire Suppression external network. Stand Pipes and Accessories.
2. Electric Drive, Centrifugal Fire Pumps & Jokey Pump.
3. Electric & Diesel Drive, Centrifugal Fire Pumps & Jokey Pump.
4. Fire Water Network & Fire Hydrants
5. Special Systems.
6. If the system require fire hose cabinet and sprinkler system , combined system shall
be used.

B. Underground fire fighting water storage tank (shall be separate tank for bghijki lme^nai ) ]oe^nai (
and at least 60 minutes or as per civil defense requirements, fire fighting pump set (Two
electrical or One electrical duty & One diesel stand by)-shall be One electrical duty & One
diesel stand by for ]oe^nai bghijki lme^nai ( ) ,Automatic FM200 Clean Agent Total Flooding
system for Electrical & pump rooms in external site and for Low current , Archive , Server ,
Control rooms inside building if using of water is not allowable ,Automatic CO2 Total
Flooding system for generator and transformer rooms in external site, portable fire
extinguishers (PFE-1/dry powder ABC & PFE-2/CO2) will be used.

REFERENCES
A. SASO : Saudi Arabian Standards Organization.
: Local Codes and Ordinances, Civil Defense & Authorities having
Jurisdiction.
B. NFPA 10 : Standard for Portable Fire Extinguishers
C. NFPA 11 : Standard for Low-, Medium-, and High-Expansion Foam
D. NFPA 12 : Standard on Carbon Dioxide Extinguishing Systems
Page 131 of 183

E. NFPA 13 : Standards for the Installation of Sprinkler Systems.
F. NFPA 13 E : Recommended Practice for Fire Department Operations in
Properties Protected by Sprinkler and Standpipe Systems
E. NFPA 14 : Standard for the Installation of Standpipes and Hose Systems
F. NFPA 20 : Standard for the Installation of Stationary Pumps for Fire
Protection
G. NFPA 22 : Standard for Water Tanks for Private Fire Protection
H. NFPA 24 : Standard for the Installation of Private Fire Service Mains and
Their Appurtenances
I. NFPA 70 : National Electrical Code
J. NFPA 72 : National Fire Alarm Code
K. NFPA 75 : Standard for the Protection of Information Technology Equipment
L. NFPA 76 : Standard for the Fire Protection of Telecommunications Facilities
M. NFPA 2001 : Standard on Clean Agent Fire Extinguishing Systems

SUBMITTALS
A. Comply with General Requirements for Submittals.
B. Drawings and Documentation:
1. Submittal Schedule
2. Shop Drawings - Layouts, Installation Details, System Schematics Diagrams.
3. Hydraulic calculations for each fixed fire fighting system of whatever type
4. Equipment Schedules

C. Products:
1. Submit full manufacturer's data for every item including installation data to enable
coordination requirements to be assessed.
2. As required by the Engineer, for each item: submit a catalog cut or sample; provide
manufacturer's factory performance type or individual test certificate; or arrange for
witnessing of factory testing by the Engineer.
Page 132 of 183

QUALITY ASSURANCE
Obtain applicable test certificates for works testing of all fire fighting works such as pumps,
valves,etc to demonstrate adequate quality, performance and compliance with relevant
codes.

A. FIRE SUPPRESSION EXTERNAL NETWORK
1. Regulatory Requirements:
1.1 Comply with standards of authorities having jurisdiction for fire suppression
water service piping, including materials, hose threads, installation, and
testing.
1.2 Comply with NFPA 24 for materials, installations, tests, flushing, valves,
hydrants and service piping.
1.3 Applicable NFPA Codes.
2. UL Listed and FM Approved Gate Valves
2.1 175 psig (1200 kPa), UL Listed and FM Approved, Iron, OS&Y, Gate
Valves (unless high pressure is required due to project requirements).
2.2 UL Listed and FM Approved, OS&Y Bronze, Gate Valves and Pressure
Reducing Valve (if required).
3. Fire Hydrants
3.1 Description: Post Type(if required), with one NPS 4-1/2 (DN 115) and two
NPS 2-1/2 (DN 65) outlets; and with 5-1/4-inch (133-mm) main valve, drain
valve and NPS 6 (DN 150) mechanical-joint inlet. Including interior coating
according to AWWA C550. Hydrant shall have cast-iron body and
compression-type valve opening against pressure and closing with pressure.
3.2 Standard: AWWA C502.

B. FIRE SUPPRESSION STANDPIPE & ACCESSORIES
1. This section includes fire suppression standpipes and hose system. Quality
assurance NFPA 14 Installation of Standpipe and Hose Systems and NFPA 70
National Electrical Code.
2. Hose Connections: Reel-Type Hose Station:
3. Where required by another section of the NFPA Code 5000 and NFPA 1, Uniform
Fire Code, fire hydrants shall be installed in accordance with NFPA 24, Standard for
the Installation of Private Fire Service Mains and Their Appurtenances.
4. Fire Department Connections
5. Fire water storage tank will be provided based on NFPA 22 requirements.

Page 133 of 183

D. ELECTRICAL & Diesel - DRIVE, FIRE PUMPS
1. Minimum Working Pressure rating: 175 psig (1200 kPa.).Quality assurance: NFPA
20 Installation of Stationary Pumps and NFPA 70 National Electrical Code
2. End Suction Fire Pumps Standard.
3. Fire Pump Accessories and Specialties (refer to general specification).
4. Flow meter System: UL Listed and FM Approved (refer to general specification).
5. Water Meter: (refer to general specification).

E. PRESSURE MAINTENANCE PUMPS
1. Minimum Working Pressure rating: 175 psig (1200 kPa.) minimum unless higher
pressure rating is indicated.
2. Manufactured Units: Multistage, Pressure Maintenance Pumps.

EXECUTION

A. GENERAL

1. Contractor shall submit Life Safety and Fire Protection Strategy Report fully based on
applicable section of NFPA Codes and Local Civil Defense requirements for review
and approval of ENGINEER.
2. Contractor shall provide all the provisions Equipments & Installations required by the
Codes in accordance with the approval Life Safety & Fire Protection Strategy report.
3. The equipment and plant shall be seated and secured strictly in accordance with the
manufacturers instructions.
4. Adequate supervision shall be provided to maintain high quality workmanship. The
work shall present a neat, mechanical appearance when completed.
5. Piping for CO2 and FM200 fixed fire fighting systems shall generally be of seamless
black steel Shc.80 with screwed connections and shall comply with the requirements
of NFPA 12 or NFPA 2001 respectively.
6. Piping for sprinkler and standpipe inside building shall be seamless black steel Shc.40
and the type of drainage pipe used for fire network drain is galvanized pipe Shc.40.
7. Piping required for fire pump connection inside pump room shall be seamless black
steel Shc.80 except test line is galvanized pipe Shc.80.
Page 134 of 183

8. Piping required for fire work under ground outside building shall be UPVC Class 5.

B. NOISE AND VIBRATION
1. All piping, equipment and system shall be installed with the utmost precautions to
prevent noise and vibration transmission.
2. Equipment such as pumps that would tend to cause noise or vibration shall be isolated
with suitable vibration isolators to reduce noise or vibration transmission to buildings
and /or other equipment. Piping connected to this equipment shall also be isolated by
means of flexible couplings and suspended by spring hangers for a minimum distance
of 5 meters from the equipment or to the Pump Room boundary.

INSPECTION AND TESTING
Inspection and testing of the fire fighting systems and associated storage tanks installation
shall be performed strictly in accordance with applicable codes of NFPA and to the
satisfaction of the Authority Having Jurisdiction.

FIRE FIGHTING SYSTEM EXECUTION, OPERATION & MAINTAINANE

Reference Standards: Fire Protection system and equipment shall be designed, installed, and
maintained in operating condition in accordance with the requirements of the NFPA
Standards..

Page 135 of 183

6.3 PLUMBING WORKS
GENERAL

The Contractor scope of work includes preparation, submitting all detailed calculations and all related
drawings (taking into account to modify all routings, sizes, equipments capacities and selection
according to modified architectural drawings, actual site location) to the engineer to get the approval
then supplying, installation, operation, testing, balancing, commissioning, maintenance and Warranty
for all systems and components as per NPC , UPC.

The Plumbing Systems in project shall include (but not limited to) all the
following:
1.1. Potable Cold/Hot water supply system.
1.2. Drainage and sewer system
1.3. Irrigation System
1.4. Rainfall drainage system
1.5. Flushing system.
1.6.Compressed Air.
1.7.LPG system.
1.8. Other facilities such as fountains, etc.(If required).

The project requirements; however, a special attention and priority shall be given to the
following issues:
- The Preparation of calculation as mentioned above, shop drawings, supply , installation ,
testing and commissioning shall ensure economic objectives.
- The Preparation of calculation as mentioned above, supply , installation , testing and
commissioning shall be environmentally friendly.
Page 136 of 183

- The Preparation of calculation as mentioned above, supply , installation , testing and
commissioning shall ensure the requirements of life and properly safety.
The contractor shall prepare and submit for approval all the required calculation and shop
drawings including all the installation details and site network proposal before starting of
installation work.
Contractor shall rectify all the plumbing works as per modified ARCH Sketches.

NOTE
(All the attached modified site and building sketches used as guidance only).

SELECTION OF MATERIALS
The selected materials shall ensure the following requirements:
- Using of National products that have proved quality and reliability.
- Using of materials which can be efficiently handled by almost the available
workmanship.
- Using of materials which are applied in common practice, and high quality projects.
- Maintenance flexibility shall be given considerable attention.

QUALITY ASSURANCE CODES:
- ASHRAE: American Society For Heating, Refrigeration and Air Conditioning Engineers
- ASTM: American Society For Testing and Materials.
- ASME: American Society For Mechanical Engineers.
- NPC: National Plumbing Code.
- NFPA: National Fire Protection Association.
- ANSI: American National Standard Institute.
- AWWA: American Water Works Association SASO: Saudi Arabian Standard
Organization
- SCDB: Saudi Civil Defense Bureau
- UL: Underwriters Laboratories:
- ARI: American Refrigeration Institute
Page 137 of 183

- UPC: Uniform Plumbing Code
- UMC: Uniform Mechanical Code
CONNECTION WITH GENERAL SITE UTILITIES
- The contractor shall connect all buildings utilities with the network at general site.
VALVES , AIR VENTS, THERMOMETER, GAUGES etc.
These Performance Specifications do not generally detail such items. The Contractor is
expected to provide all necessary even minor equipment items, fittings and accessories in
accordance with Codes, Standards and the General Specifications.

DOMESTIC WATER (DW) SUPPLY SYSTEM
A. SUPPLY AND DISTRIBUTION
a) The DW (potable water & non potable water ) supply system shall be based on the use of
City water, with provision for acceptance of additional supplies from tankers , R.O
with Wells (if required) in addition to use the STP or WTP discharge only for non
potable water.
b) The City water shall be metered by means of an in-line propeller type meter approved by
the Water and Sewerage Department (WSD).
c) The meter shall have provision for sending water consumption data to the BMS in the form
of volume unit pulses or digital information .
d) Due to the present intermittent City supply, the complex shall include DW main storage of
capacity at least equal to 7 days demand and located (along with main pump room).
Tanks shall be constructed of reinforced concrete.
e) DW demand shall be based on SPC/IPC tables, considering the building functional
zones and their respective populations.
f) The DW( potable water & non potable water ) storage tanks as showing in guidance
proposal sketches ).
g) Provision shall be made for the chlorination of tinkered water to 0.1 ppm (mg/l)
h) All piping up to Storage Tanks shall be UPVC Class 5.
j) System Configuration and Operating Pressure:
The DW distribution system shall be pressurized to suitable pressure by the use of
booster pump sets (a minimum residual head of 0.5 bars shall be achieved at the
hydraulically most remote fixture of each network).
B. BOOSTER PUMPS
1. The system shall be maintained under constant pressure with varying flow by a booster
pump set with automatic pressure control system. The pump set shall be comprised of
Page 138 of 183

probably three( at least ) vertical in-line or end suction centrifugal pumps, each with a
variable frequency drive (VFD), operates two Duty (Lead/Lag) and one Standby. The pumps
shall be directly driven by TEFC motors with Class F insulation operating at 1750 rpm
nominal speed.
2. For more information refer to general specification.

C. PIPE WORK SYSTEM ( FOR POTABLE & NON POTABLE WATER )
1. All pipe work and fittings unless otherwise indicated shall be suitable for a test pressure up
to 16 bar with a water temperature of 35C.
2. External pipe work shall be UPVC class 5 pipe with the manufacturers' approved solvent
weld class 5 fittings. Pipes to be directly buried in soil at a minimum depth of 700mm
in pedestrian and landscaped areas and 1200mm elsewhere.
- Piping crossing paved areas shall pass through a sleeve of Class 5 UPVC pipe at least
100mm larger than the main pipe with access points at each end to permit its eventual
replacement. For piping crossing roadways carrying truck traffic the sleeve shall be of
ductile iron pipe.
- The interface connection between external and internal pipe work shall:
a. be at a point approximately 1500mm outside the building perimeter
b. be made by the Contractor responsible for the external pipe work
c. be within an approved concrete chamber or manufactured Cast Iron or ABS box
large enough to accommodate the building isolation valve, a water meter with bypass
or spool piece for future provision, connections and union or flanges for water meter
maintenance
3. Pipe work within buildings below the ground slab shall be as specified above for external
pipe work in paved areas (UPVC class-5) and potable water &non potable water
distribution pipe work within buildings shall be UPVC Class-5.
4. Pipe work fittings and connection method(s) shall be designed for use with the selected pipe
material(s) and the appropriate threaded or flanged fittings shall be available for
connection to sanitary fixtures and other equipment.
5. Backflow prevention devices and air gaps shall be provided as necessary to comply with
Code requirements. Potable water shall be supplied to Bidets, Ablution Hoses and any
other hose connections via a vacuum breaker. Potable water supplies to Plant Rooms
or Mechanical equipment shall be via a backflow preventer. Potable water supplies to
fixtures of biologically hazardous spaces shall be via reduced pressure zone (RPZ)
backflow preventer.
6. Exposed domestic water systems pipes to be protected against sun light.
Page 139 of 183

7. A shutoff valve will be provided for each Laboratory, wet area and where required for
proper control of the system.
8. Where valves are located in concealed spaces, access panels of suitable size will be
furnished.
9. Unless flanges are indicated, a union will be installed on one side of all screwed valves or
valve combinations, equipment connections, and elsewhere as indicated or required
for ease of installation and servicing.
10. Angle stop valves on cold and hot water supplies will be provided for each individual
fixture such as lavatory, water closet, kitchen sink, etc.
11. Chilled domestic water system(ALL SYSTEM COMPONENTS) for detention areas to be
prepared , calculated and executed as per modified ARCH drawings.

D. FLUSH WATER SYSTEM
a) As per attached guidance drawing the Flush Water will be generated from the
Following:
1- Sewage Treatment Plant (STP) or
2- Water Treatment Plant (WTP) or
3- Truck filling of City Main Raw Water.
The contractor shall take the necessary approval from client before starting in case of
Sewage Treatment Plant STP or WTP.
The Water Treatment Plant (WTP) or (STP) shall be used as a complete functional
System installed and commissioned by a specialist supplier.
The capacity of (STP) or (WTP) plant shall be calculated based on:
The building Water consumption / person ( l/d)
Admin. 75
Workshop & store 20
Mosque 40
Restaurant 30 (with toilets), 10 (without toilets)
Barracks 190
b) For more information refer to general specification.
FLUSH WATER SYSTEM COVERAGE
1) The FW system shall provide flushing water to all WCs within the project. WCs shall be
fitted with low volume tanks and dual-flush systems. WCs with flush valves
calculated to provide a dual flush with water consumption no greater than that of the
corresponding flush tank.
Page 140 of 183

2) The FW supply pumps shall provide sufficient pressure for the operation of a flush valve
WC as in at the hydraulically most remote location within the building.
3) Distribution: FW shall be pumped up the building in the same manner as DW.
4) Contractor to use raw water as flush water source in all toilets and WC,s in all
Buildings which indicated in the drawings and/or B.O.Q taking into account to
Prepare and submit for approval all calculations and related drawings then provide,
Install, operate, testing and warranty of all works and modifying all related
Mechanical, electrical, civil, architectural and all other works.

D. HOT WATER SUPPLY
This shall be provided thru (individual / central) Electric Water Heaters as per
drawings and sketches with suitable capacities to be installed at all toilet and wet
areas, ,. etc.

MATERIALS
CPVC Sch. 80 pipes shall be used for Hot Water Supply System and UPVC Class -5
for Cold Water Supply System.
E. EXTERNAL DRAINAGE SYSTEMS
SOIL , WASTE AND RAINWATER DRAINAGE
GENERAL
a) External drainage shall be connected to One-pipe or Two pipe drainage network including
external manholes (SMH and WMH) for One-pipe or only SMH for Two-pipe
drainage (waste & soil) pipes , Gully Trap to be connected at the end of waste pipe
before connecting to SMH , System to be installed according to Code requirements
and good practice.
b) According to the circumstances of each site, drainage pipes flows from individual
buildings shall be collected and flow by gravity (using falls):
1) To one or more connection points (manholes) as mentioned above of a sewerage network
2) In case of Laboratory the drain pipe shall drain to neutralization tank before connected to
normal drain
3) Collection of soil pipe or both soil and waste pipes drained to Holding Tank(H.T).
4)In case of using Water treatment Plant (WTP), only waste pipe enter to water treatment
plant wherever soil pipes collected to H.T and In the case of using Sewage Treatment
Plant (STP), both waste and soil pipes will enter to sewage treatment plant.
5) The discharge of STP or WTP will use in irrigation and also in Flushing system(if required)
6) Future connection to be provided to the last manhole before Holding Tank.
Page 141 of 183

7) Lift Station to be provided to drainage system if required.
NOTE
In Case Of Not Use Sewage or Water Treatment Plant or City Drainage Network
Over flow from holding tank to be connected to percolating pit subject to geotechnical
report of soil permeability (Holding Tank Capacity to be 7 days).
In cases where the sites are located within an area where percolating pit cannot be
implemented due to soil report or local authoritys restrictions, the holding tank size shall be
doubled (Holding Tank Capacity to be 14 days).
.
G. EXECUTION
a) All external drainage pipes shall be UPVC Class 5.
b) Inspection chambers shall be constructed of reinforced cast in place concrete or be
prefabricated plastic moldings embedded in concrete as approved by the Engineer.
c) Wet wells and lift stations shall be constructed of reinforced cast in place concrete and
located in non-traffic areas. Covers for pump maintenance and cleaning access shall
be fabricated from heavy duty steel-reinforced plastic, hinged with gas spring
assistance for opening and positively latched when open.
d) All concrete shall be given two coats of approved bituminous or coal tar epoxy protective
paint. Whenever a sewer enters a manhole at an elevation 450 mm or more above the
manhole floor, a drop type manhole will be used.
e) All sewer lines will be designed to provide a minimum velocity of 0.70 m/sec at peak flow
condition.

RAIN WATER DRAINAGE
a) Rain Water (RW) collected by roof drains shall be piped to discharge freely with splash
blocks to plant areas and roads at ground floor level.
b) Roof drain with drainage pipe up to 30 cm above ground floor shall be used.
c) Rain Water shall be based on a rainfall rate of 140 mm per hour.

H. IRRIGATION SYSTEM
GENERAL
Underground water reservoir for irrigation, pump set, irrigation water piping of
UPVC Class-5 for main lines, polyethylene distribution piping for mini-bubblers,
solenoid valves, drippers, bubblers, quick couplers, valves, etc. and a controller for
automatic operation according to the programmed timing of watering the plants all
the year round.
The source of irrigation water shall be :
Page 142 of 183

From Truck filling or Municipality or STP or WTP.
- The capacity of the irrigation underground reservoir shall be estimated to
Be sufficient for 7 days.

FUEL OIL SYSTEM
A. Work shall included the preparation of calculation , drawings, providing of
labor, materials, equipment and services necessary for a complete and safe installation
of complete fuel oil system .
B. Fuel oil system with piping, valves, fittings, fuel storage tank (Bulk), day
tank, collecting pans, fuel transfer pumps, controls and alarm actuators.
C. Provide systems in accordance with the diesel generator Manufacturer's
recommendations.
D. Fabrication and installation of any portion of Emergency Diesel Generator
Systems shall be in compliance with diesel generator Manufacturer, National Fire
Protection Association and all authorities having jurisdiction.
E. Comply with provisions of NFPA 31 - Standard for the Installation of Oil
Burning Equipment, for oil piping materials and components, oil piping installations,
and inspection, and testing of fuel oil piping systems.
F. UL Compliance: Provide fuel oil piping components and storage tanks which
are listed and labeled by UL.

PIPING MATERIALS
A. Piping for fuel oil system shall be black steel pipe, seamless, conforming to
ASTM A 53, Schedule 40, with beveled ends.
B. All black steel piping shall have a painted finish as per the requirements of
specification - Painting color shall be as selected by the Engineer.
C. Fill line and test well terminals shall be cast iron body, cadmium plated body
with brass cap and lock.

FUEL OIL STORAGE TANK (BULK)
Fuel Oil Storage Tank shall be factory fabricated glass fiber reinforced polyester (GFRP)
underground fuel oil storage tank (one week) .Tank shall be horizontal cylindrical with
spherical heads and designed for operation at atmospheric pressure. Tank suitable for
diesel fuel shall be constructed, tested and installed in accordance with NFPA
recommendations and comply with all regulations of authorities having jurisdiction.
Page 143 of 183

Tank shall meet the design loading conditions when buried in ground due to external
hydrostatic pressure, internal loads due to 5 psi test pressure in annular space and
primary tank, storage of fuel oil, and designed to support accessory equipment such as
ladders, drop tubes, etc.
Tank shall be vented to atmosphere.
Accessories: Tank Manufacturer shall provide GFRP anchor straps, One carbon steel
ladder extending to bottom of tank with bolts, nuts, lugs , UL certification plate shall be
affixed to the tank , The tank Manufacturer's statement that this conforms with 6NYC2R
Part 614 New York State Department of Environmental Conservation must be
permanently displayed,etc

DAY TANK
Refer to Electrical specification (POWER GENERATING SYSTEM).
DIESEL FUEL-OIL TRANSFER PUMP
Pumps shall be single-stage positive displacement rotary type with motors. Pump and
motor shall be mounted on cast-iron base (full length of motor and pump) with a
raised lip. Pumps shall conform to UL 343, and be UL listed. Pressure relief valve
shall be provided and operation shall give an alarm signal.

CONTROLS, ALARMS AND OIL TANK GAUGES
A. For oil tank provide level controls and alarm actuators including level
indicator, Level control to operate fuel oil transfer pump on and off.
B. For collecting pan provide pump cut-off and alarm including diesel fuel - oil
transfer pump cut-off.

FIELD QUALITY CONTROL
A. Test oil piping in accordance with NFPA 31. Remake leaking joints and
connections using new materials.
B. Tank shall be pressure tested in conformance with local ordinances and
Manufacturer's written instructions. Pumps, level controls and alarms shall be
operational tested. Replace damaged or malfunctioning controls and equipment.
Assist in performing operational test of entire emergency power system.
COMPRESSED AIR
Page 144 of 183

Air (refer to general specification) to be used for workshops as indicated in plumbing
Guidance sketches.

LPG GAS
This technical specification establishes the type and quality of materials and the standard of
workmanship to be used in the prepare calculation, supply, installation and testing of the bulk storage
and distribution of LPG (Liquid Petroleum Gas) to serve food service equipment & Laboratories.
- The storage and handling facilities shall be provided in accordance with the specifications of the
LPG suppliers and shall comply with the requirements of NFPA 58 (last edition).
- Gas pipe or tubing and fittings shall be clear and free from cutting burrs and defects in
Structure or threading, and shall be thoroughly brushed, and chip and scale blown.
- Defects in pipe or tubing or fittings shall not be repaired. When defective pipe, tubing, or fittings are
located in a system, the defective material shall be replaced.
- For more information refer to general specification.
- LPG system to be enough for one month consumption.
- Storage systems (tanks or cylinders) to be as per sits conditions, supervision and client requirements.

CHILLED DOMESTIC WATER SYSTEM:
Contractor to provide complete chilled domestic water system which include but not
limited to the following components:
Instantaneous water chiller.
Cartridge filter.
UV filters.
Membrane tank.
Booster pumps.
Break tank with suitable capacity.
Seamless black steel sch. 40 with 50 mm thickness fiberglass insulation.
Drinking bubblers (2 for tank and 1 for solitary (single)).
All vales, gages, accessories and all needed.

Page 145 of 183

Chilled domestic water schematic diagram 1
Page 146 of 183

7. ELECTRICAL

Page 147 of 183

I. ELECTRICAL (POWER & LIGHTING SYSTEMS):

Introduction

This part of the report is intended to set out the minimum technical requirements required for
the final calculations, final detailed drawings and installations of the electrical systems.

The detail drawings, documents, calculations and installations of the electrical works will be
carried out by the Contractor. The requirements and responsibilities of the contractor as well
as the deliverables required shall be the same as that outlined in this MTR, illustrative
electrical sketches and electrical specifications related to the project.

Scope of Work

The scope of electrical power, telecommunication & low-current installations in the project
will include but not necessarily limited to the following:-
- MV switchgear.
- Distribution transformers.
- Standby diesel generators complete with automatic transfer switches.
- Low voltage switchgear comprising main distribution boards (MDB), sub-main
distribution boards (SMDB), distribution boards. (DBs) distribution panel boards
(DPs), and branch circuits panel boards (LPs, PPs).
- Uninterruptable Power Supply (UPS) systems.
- Medium voltage feeders network.
- Low voltage cables, raceways and all accessories.
- Miscellaneous wiring devices and disconnecting switches.
- Indoor, roads, parking, facade and outdoor lighting installations.
- Earthing system.
- Lightning system.
- Elevators.

Page 148 of 183

1 TECHNICAL CONDITIONS
1.1 Regulations and Standards
The electrical systems will be designed and constructed in accordance with the latest version
of Saudi Building Code (SBC) and Saudi Arabian Standard Organization (SASO) Codes and
Standards; however, items/systems not covered in SASO Standards shall conform to the latest
version of the following:

Standards/Regulations issued by Saudi Electric Company (SEC), Ministry of Public
Building and Works, Civil Aviation Authority, etc., as applicable.
(IEE) Seventeenth edition of IEE wiring Regulations. (BS 7671: 2008).
(IEC) International Electro-Technical Committee codes/standards.
(NFPA) National Fire Protection Association.
(NEC) National Electrical Code - U.S.A.
(CIBSE) British Code of Interior Lighting issued by the Chartered Institution of
Building Services.
Illuminating Engineering Society (IES) Code.
British standard for Earthing (BS 7430)
British Standards for Protection of Structures against lightning (BSEN 62305).
ISO Standards.

The entire electrical installations, the associated equipment and materials shall fully comply
with the above and shall be designed and specified for a continuous and trouble-free operation
at the ambient conditions of the relevant site.

The contractor must take into account any Saudi regulations that are legally mandatory.

1.2 Climatic Conditions

All electrical equipment, accessories and fittings employed in electrical installation will be
specified, designed and rated for continuous and free operation at the climatic conditions of
relevant site.

The contractor must use a de-rating factor for ambient temperature, when sizing cables and
selecting equipment.
Page 149 of 183

1.3 Specific conditions

The contractor shall be responsible for coordinating and negotiating with the authorities with
regard to the services that may belong to them or within their control. Any costs,
contributions or permits required by any national authority to enable full completion of the
works shall be covered by the contractor and included in his price.

The contractor shall check and advise the owner representative/engineer on all room sizes that
are particular to the electrical services equipment.

The contractor shall undertake to maintain at his sole expense, the apparatus and installation
against all defects, reasonable wear and tear expected for a period of not less than twelve
months from the date of hand over of the installation.

2 ELECTRICAL POWER SYSTEMS

2.1 Power Supply Characteristic

All electrical equipment, accessories and fittings will be of the best material and
manufactured to operate continuously in the electricity supply having the following
characteristics:

Medium Voltage (MV) : 13.8 kV, 60 Hz, 3 phases, 3 wires.
Low Voltage (LV) : 400/230 V, 3 phase, 4 wire & ground, solidly
Earthed neutral.
Fault Level : L 500 MVA at 13.8 kV side of transformer
(transformer input)

The power supply characteristics listed above have to be confirmed with local electric
authority at site.
Page 150 of 183

2.2 Incoming Power Supply

Utility power supply shall be obtained from the network of the Local Electricity Authority at
13.8 kV.

An advance coordination meeting shall be arranged between the Contractor and the Local
Electricity Authority (SEC) to check the availability of the utility supply and how to achieve
the required reliability of that source. Site specifics shall be discussed and agreed upon with
SEC, taking into consideration the particular conditions of the site. The contractor shall fully
conform to SEC technical and space requirements and obtain SEC approval where applicable.

2.3 Electrical Substation(s) / Electric Utility Building(s)

Project shall be catered electrically through substation(s) distributed in the site in the way that
guarantees the most liable feeding of loads.

Electrical feeding of all external works (street/fence lighting, external security systems,
parking areas, watching towers, main/secondary gates, guards rooms, stadiums, septic tanks
pumps, ranges, future expansions etc) to be distributed on the substation(s) according to the
location and loads values.
All mechanical loads located in the site or on buildings to be fed with power after final
selection of mechanical equipment.
Water tank building is to be totally submitted electrically- in details by the Contractor (with
feeding all the mechanical loads) and after his final mechanical, structural and architectural
submission.
Helipad area when found- is to be totally submitted -electrically- in details by the Contractor
(regarding lighting, power, grounding, control) to match the international standards (codes)
and the end user requirements.

All gates security systems (Road blockers, car barriers, electrical gates, scanners) to be fed
with the required power after full coordination with the Architectural Engineers.

In case of voltage drop problem raised during the final calculation stage due to far away
loads from substations-; Contractor is to provide the most effective solutions to reduce the
Page 151 of 183

voltage drop and to save cables as much as possible.

Electric utility building / Substation(s) will consist of transformer(s), stand by generator(s),
automatic transfer switch(es) and Main Distribution Board(s) . Final number and size of
transformers and generators in substation(s) shall be determined by the Contractor after his
final load calculations.

The scope will deem to include but not necessary be limited to concrete bases, foundations,
supporting structures, cable trenches and all necessary builder works in connection

The Contractor will allow for all related installations to make the electric utility building fully
operational, as intended taking into consideration that the transformer room will have a
concrete ceiling (not open to above). The Contractor shall also endeavor to achieve a high
degree of standardization.

2.3.1 Medium Voltage Switchgear (Main)

The incoming Medium Voltage MV 13.8 kV supply cables from Saudi Electric Company
SEC shall enter site and shall be terminated in the MV switchgear - located in SEC room -.
The Contractor will include for all necessary fault protection and adequate discrimination
throughout the medium voltage level. The contractor will also enquire with SEC the
maximum fault level of the incoming supply and select the suitable equipment.

The MV Switchgear will be indoor type, metal clad switchgear, with withdrawable Vacuum
or SF6 type circuit breakers. Outgoing circuit breakers which feed the MV switchgear shall be
fully equipped with control power supply and all required mechanical interlocks and alarms,
multifunction digital-metering, instrument transformers, terminal blocks, protection and
control devices.

2.3.2 Medium voltage network, Distribution Transformers and Ring Main Units (RMU)

MV cables from MV switchgear to the RMU of the transformers will be single or multi-core
8.7/15 kV (17.5kV) annealed copper, XLPE insulated, flame retardant PVC overheated to
IEC 60502. The cables shall have adequate current carrying and short circuit withstands
capacity.
M.V cables -when running inside the site- shall be direct buried armoured cables or
Page 152 of 183

nonarmoured type running in UPVC conduits. Concrete duct bank to be used when crossing
roads only.

Transformer(s) shall be; 13.8kV/400V Oil type or Dry type (according to SEC and project
status), 3-phase 4-wire, Dyn11, 2-copper winding, insulation class F.

Final number and size of transformer(s) required for the project shall be specified by the
Contractor according to his final summation of the total actual loads.

2.3.3 Stand by Generators

Stand-by diesel engine-generator(s) shall be provided in Electric utility building /
substation(s) to supply power to the following emergency, critical, essential and life safety
loads and systems in the event of normal power supply failure:
All emergency & essential electrical loads.
life safety systems (fire fighting pumps, etc)
Security and access control systems and the like.
Data systems and the like.
Critical mechanical systems (sewage/sump pumps, domestic water pumps, etc.).
100% of the external security and helipad lighting.
20% of the external (fence and street) lighting.
Electric loads (control and monitoring equipment) for the helipad area.
Allowance of 20% as spare capacity to cover all contingencies.

The generator(s) will be 400V, 3-phase, 4-wire, 1800 rpm; 60 Hz, 0.8 power factor turbo-
charged after cooled, class G3 to ISO 8528, with electronic governor; and complete with
associated auxiliaries, acoustic treatment and ventilation attenuators to minimize noise level,
residential type exhaust system; start up system, cooling system and daily fuel storage and
transfer systems.

Contractor will determine the final size of generator(s) required based on his final calculations
and final selection of equipment. The generator shall be loaded up to 80 % maximum of its
rating capacity and the maximum voltage dip permitted for each step is 15 %.

Bulk storage fuel tank will be sized for four days full load operation of the generator set(s).
Contractor will advise the engineer at the earliest the size of the diesel storage tank required.

Automatic transfer switch(es) shall be 4-pole, single switch-double-throw and provided with
Page 153 of 183

bypass isolation switches to allow for a safe and convenient means of manually bypassing and
isolation for the automatic transfer switch, regardless of the condition or position of the
switch.

Upon total failure of SECs power supply, the generator(s) will be started automatically (via
automatic transfer switches) and accelerated to rated frequency and voltage (and then
synchronized for parallel operation- if more than one generator is determined-). The power
interruption to the loads connected to the emergency power supply will be limited to no more
than 30 seconds.

2.3.4 Main Low Voltage switchgear

The connection between Transformer (s) LV terminals and the generator (s) to ATS and LV
switchgears shall be XLPE insulated copper cables.

LV main distribution boards (MDB's) will be metal enclosed, free standing type, with
separation class form 4b, housing incomings, outgoings ,couplers and bus-ties circuit
breakers, bottom or top entry for incoming and outgoing cables, IP 42, 600/1000V, to
IEC60439.

Copper busbars are to be used; the busbar rating is the same rating of the main circuit breaker
frame size, and to have a symmetrical short circuit withstand current equal to the nearest
highest standard rating to the maximum expected short circuit current at its location. The
neutral bar is to be sized as the phase busbar. The earthing bar is to be half size the phase
busbar.

Main incoming, tie and couplers breakers of MDB's will be motorized (where applicable &
required) air circuit breakers (ACB) when sized equal to or more than 1000 Amp.
Withdrawable type for more than 1250 Amp, individually mounted and fitted with electronic
solid state trip units (LSIG type) having an adjustable setting for long time current pickup and
delay, short time current pickup & delay, instantaneous current pickup and earth fault current
pickup and delay, with short circuit rating to IEC 60947-2 (service rating).ACBs installed in
MDBs as incomers, couplers or tie- breakers shall be specified 4-Pole type.

The outgoings of MDBs will be Molded Case Circuit Breakers (MCCBs) for 800 Amp. Or
less, motorized where applicable & required, with electronic solid state trip units (LSI type)
with time / current adjustments as applicable, however and for ratings 1000 A and above
ACBs shall be specified as outgoing breakers.

A digital multifunctional display unit (MFDU) shall be provided on the main incoming
section of the MDBs and connected to the controlling and monitoring system (when found).
Unit shall be microprocessor based and providing complete electrical metering (KW, KVA,
KVAR, power factor, frequency, current per phase, single and composite phase voltage, etc.).
In addition to the above MFDU, 3 analog voltmeters and 3 analog ammeters shall be
provided.
Surge arresters shall be provided on each MDB main incoming.
Minimum 10% spare capacity shall be provided at each MDB. The number of spare
compartments shall be calculated based on the active / operational breakers. Spare
compartments mean compartments equipped, for future, with circuit breakers.
Page 154 of 183

Compartments shall be rated for dissipating the heat developed without forced ventilation
measures. Compartments shall be ventilated, where required, by approved method complying
with Standards.

MDBs shall be located in dedicated rooms. Clearances requested by the Codes shall be
provided in the front, rear and on the sides of the boards to permit safe operation, inspection,
testing and maintenance.

Contractor will include within the main distribution boards power factor correction units to
achieve the power factor value accepted by the local power authority (SEC) .Automatic
regulation will be employed to avoid over compensation .The effect of harmonics and
resonance shall be taken into consideration while designing the system .

2.4 UPS Systems

UPS systems will be provided to maintain power supply to the critical and essential loads in
the event of power failure.

UPS units shall be on line type completed with all necessaries.

UPS systems shall be provided in the suitable locations to serve the essential/critical loads.
Output isolating transformer (other than the inverter transformer) is to be installed at the end
of each UPS unit for galvanic isolation.

By pass for UPS system shall be fed from the same source.

2.5 LV Distribution Network

2.5.1 Distribution & Final Branch Panel Boards and Feeder Pillars:

Main Distribution Boards will supply power to distribution panel boards, UPSs, large
mechanical equipments (chillers, pumps, etc.), motor control centers, power factor equipment
and other electrically operated equipment.
Distribution panel boards shall be allocated to feed specific zones/load floors and will be
located inside electrical rooms and will supply power to all final branch circuit panel boards
and other electrically operated equipments (elevators, etc).

Distribution panel boards DP shall be metal enclosed, factory designed and assembled,
IP42, for indoor installation and,IP55, for outdoor and wet installation free standing or wall
mounted, with group mounted molded case circuit breakers on the outgoing circuits and
molded case switch on the incoming feeder, to IEC 60439.

Page 155 of 183

Final branch circuit panel boards shall be located inside electrical rooms/closets and will feed
final branch circuits for lighting and convenience power outlets.

Final branch circuit Panel boards shall be metal enclosed ,factory designed and assembled
type IP 42, wall mounted, surface or flush with hinged lockable doors to IEC 60439. Final
branch circuit Panel boards shall be in general of the three phase type with triple pole T.P.
molded case switch having shunt trip unit on the main incoming and with miniature outgoing
circuit breakers.

Copper busbars are to be used for distribution and final branch panel boards. The busbar
rating has to be equal to at least the standard upstream frame size and to carry 125% of the
max. short circuit level at the point of applications for 1 second. The neutral bar is to be sized
as the phase busbar. The earthing bar is to be half size the phase busbar.

Feeder pillar is to be factory-built assemblies designed, manufactured and tested in
compliance with IEC 60439, IP 65 enclosure complete with all equipment and fitting required
including but not limited to incoming and outgoing molded case circuit breakers, contactors,
photocell, and electronic timer and all necessary measurement ,control and protective devices.
The feeder pillar cupper busbars are to be fully insulated, rated 1.25 the main incoming
molded case circuit breaker frame size at 50 degrees C and to carry 125% of the max. short
circuit level at the point of installation.

Circuits breakers shall be in accordance with IEC 60947-2, sequence II (service rating) for
main distribution boards and distribution panel boards. Final branch circuit panel boards will
have miniature circuit breakers at the output to IEC 60898.

The breaking capacity of circuit breakers shall be fully rated and selected in accordance with
the nearest highest standard rating to the maximum expected short circuit current at the
breaker location.

Earth leakage protection device is to be provided as per the requirement of the NEC/IEE in
proper areas such as: Kitchen countertop surfaces, wet areas, outdoor, garages and etc

The Contractor/manufacturer shall allow for tripping discrimination between circuit breakers
to minimize inconvenience and nuisance tripping.

The Contractor/manufacturer shall allow for a minimum of 15 % spare capacity /ways for
distribution boards and final branch panels.

2.5.2 Motor Starters and Motor Control Centers:

Motor control centre(s) and panel board(s) shall be provided at mechanical rooms for the
supply and control of mechanical motors.

Page 156 of 183

Motor Control Centers shall be of dead front type with fixed cubicles, type Form 3b. Each
motor shall have its own individual starter cubicle. An under/over voltage relay, phase failure
relay and phase reversal relay shall be provided on the main incoming supply to shut down all
motors when the preset values are exceeded.

Direct on line starting shall be accepted for ratings below 10 H.P. Reduced voltage start of an
approved type shall apply for motors rated 10 H.P. and above. Reduced voltage start of the
open transition type shall not be acceptable.

Motors (particularly large motors) shall be designed to start sequentially to avoid
unacceptable starting surge and consequent voltage dip.

The motor control centers shall be provided with facilities for connections with monitoring
and controlling systems.

The Contractor/manufacturer shall allow for a minimum of 15 % spare capacity /ways for
motor control center and panel.
2.5.3 Distribution, Sub distribution Cables and Wires

The LV distribution and sub distribution cables shall be rated 600/1000 V, XLPE insulated
copper conductor, flame retardant, PVC sheathed and with minimum temperature rating of 85
deg. C.

The outdoor LV cables shall be direct buried armoured cables or nonarmoured type running
in conduits. Concrete duct bank to be used when crossing roads only or as indicated on
drawings.

The cable distribution network shall be provided to ensure that the voltage drop from the
transformer and up to the farthest end of a branch circuit is not to exceed 5 percent.

Fire resistant cables multi-core, 600/1000V, low smoke zero halogen (LS0H) to IEC 60331,
BS 6387 category CWZ and IEC 60332-1, shall be used for feeders of fire pumps, fire alarm
voice evacuation, mechanical equipment for fire control and smoke management systems.
The final sub-circuit cables/wires for lighting and small power shall be rated 450/750 V, PVC
insulated, copper conductor, flame retardant, with minimum temperature rating of 85 deg. C.
drawn in conduit or trunking as applicable.

All circuits of both lighting and power applications will be loaded to not more than 75-80% of
the actual net rated capacity of the protection circuit breakers.

Page 157 of 183

2.5.4 Conduits, Wire ways and Related Accessories for All Systems (Electrical, Low Current
Systems:

For Outdoor Network:
PVC ducts for lighting, power and low current /telecom Cable Installations are to be non
sparking type, suitable for direct burial in ground, minimum tensile strength 500 kg/cm2,
impact strength 5 kg/cm2, supplied in standard 6 m lengths, with one end of each length
tapered.
Minimum Wall Thickness of the ducts are to be 3.2 mm for 100-mm ducts; 4.7 mm for 150-
mm ducts. All conduits filling ratios do not exceed 40%. All necessary manholes and
handholes required for duct bank installations are to be provided in every bend /every
building entrance, manholes should be spaced not farther than 150m apart for straight runs.

For Indoor Network:
Cable trays, trunking shall be hot dip galvanized steel and shall be electrically and
mechanically continuous.
Rigid heavy gauge steel conduits (hot dip galvanized) shall be used for all exposed
installations composing lighting, power, low current, communication and signal system
wiring, for wet areas, laundry, kitchen, mechanical equipment rooms, electrical equipment
rooms, workshops, storage areas and any other location / area where there is a possibility of
mechanical damage or any possibility of high humidity.

Light gauge steel conduits (EMT) to UL 797 & ANSI C 80.3 shall be used for all exposed and
above false installations in areas other than the areas listed for heavy gauge steel conduits,
toilets with anti-humidity ceiling and for all installations if false ceiling is used as an air
plenum.

Rigid heavy gauge PVC conduits to BS 4607 and BS 6099 shall be used for lighting, power,
low current, communication and signal system wiring, where embedded in the slabs, walls or
screed.

The Contractor shall follow the space factors in trunking and conduits as required per the
approved standards.
Page 158 of 183

2.6 Lighting Installation
Indoor lighting installations shall be designed in accordance with CIBSE requirements.
Lighting fixtures will be selected to provide comfort light distribution and minimize glare
effects.

Generally fluorescent fixtures will be used throughout the building, except in main operation
room Fluorescent /metal halide fixtures may be used as appropriate and applicable .Also in
some specific areas decorative incandescent/ halogen lights may be used to highlight
architectural features. Lighting levels in the various areas will be according to code
recommendations as a minimum.

Fluorescent fixtures shall utilize energy efficient T8 or T5 with minimum colour-rendering
index (CRI) of 82 and 3500K colour temperature .Ballasts for Fluorescent fixtures shall be
high-frequency solid state, high power factor, class A with auto resetting built-in thermal
protection and maximum total harmonic distortion (THD) of 10%.

Luminaries shall be the standard products of reputable manufacturers and shall be the best of
their respective kind. The protection class IP of all luminaries shall be specified according to
the location where they will be installed.

Lighting scheme and lamp selection shall be based on achieving recommended illumination
levels, proper color rendering and temperature for each task. Glare shall be kept to minimum
as per CIBSE recommendations through the correct selection and positioning of luminaries.
The following are the minimum requirements for illumination levels at the various areas:
Area Lux Level
Meeting Rooms 500 lux
Administration/Offices 500 lux
Corridors & Stairs 100-150 lux
Entrance/ Lobbies / waiting areas 200-300 lux
Prayer areas 200 lux
Store /Service/Support room 100-150 lux
Page 159 of 183

Electric /Mech.room 200-300 lux
Servers/Telecommunication/security control rooms 500 lux
Toilet & lockers 100-150 lux
Kitchen & pantries 300 lux
Bed room 100 Lux
Rest room 150 lux
Open Outdoor Parking Areas 20 lux
Covered/Structure Parking Areas 50 lux
Lighting control means shall be provided through local lighting switches in different offices
and rooms. However in large/public spaces such as lobbies, corridors, toilets, stairs, etc; the
lighting control shall be provided through BMS and /or push buttons.

Escape signage (Exit and directional signs) shall be provided along all escape routes, at
change of direction and above all escape doors.
Escape routes and Life safety lighting will be selected to secure average lighting level not less
than an average of 10.8 lux at any point and not less than 1.1 lux measured along the path of
egress at floor level.

Outdoor (i.e. Road, Parking Area, Fence, range and Helipad) lighting shall be provided with
an adequate Lighting levels recommended by the approved codes/ standards in an energy
efficient manner. Outdoor lighting will be controlled via photocell/ timer, contactors, push
buttons (external lighting control panels).

Training ranges areas when found and when required to be used for night purposes- shall be
illuminated by galvanized high mast - IP65- with metal halide luminaries for better
efficiency, longer lifetime, energy saving and reduction of the number of luminaries complete
with all related lighting panels and controls.

Landscape and faade lighting shall be provided and coordinated to satisfy the Architecture
site requirements.

Fluorescent and High Intensity Discharge luminaries shall be power-factor compensated.
Page 160 of 183

2.7 Wiring Devices and Small Power System:

Lighting switches will be in general, grid type rated at 10A and will be quick make, quick
break, and rocker type with suitable earthing terminal.

Socket outlets, fused connection units and isolators shall be provided to serve various fixed
and portable equipment and general appliances throughout the facilities. Duplex socket
outlets will be provided where there is likelihood that numerous equipments require plug-in
points.

Equipment that requires fixed connection or heavy electric power outlets shall be supplied by
means of flexible cord, from suitable non fused disconnect switches mounted adjacent to the
equipment for maintenance purpose.

Single phase socket outlets for general convenience use will be two wires, with grounding,
rated 16 A, 250 V a.c.

Industrial type 16A, 32 A single phase and three phase socket outlets shall be provided
through out technical areas such as workshops, generator, pump room and the like.

Switches and Socket outlets located in wet/outdoor areas will be housed in waterproof
enclosure suitable for the location and fed with power through earth leakage relays.

All switches, socket outlets and any other wiring devices are to be located at easily accessible
places.
Convenience outlets shall be selected to comply with the area where installed. Decorative
accessories will be provided to match the interior design scheme, where required.

Receptacles connected to the UPS power system shall be properly color coded/ designated.

Page 161 of 183

2.8 Earthing System

The earthing system shall be provided to meet all relevant requirements of SEC Standards.
The earthing system (associated with LV system) will be TN-S type as per BS7671:2008 (IEE
Regulations, 17th Edition) and in full compliance with BS7430:1998.

The earth source will be provided at transformer substation/emergency generator and will
consist of multi-earth electrodes, earth conductors and busbars for earthing of neutrals and
enclosures of electrical equipment. Transformer neutrals will be connected to the main earth
source.
All earth electrodes will be interconnected in a loop using directly buried underground bare
copper conductor. Resistance to earth of the each earth electrode system shall not exceed 5
Ohm.

An earth bar will be provided at the main distribution boards cubicles and will be linked to the
neutral bar using two links. Protective earth conductors will be run separately from the earth
bar of the main distribution boards to the distribution panel boards earth bars.

A complete system of separate protective conductors will be provided in all installations for
earthing of lighting fixtures, socket outlets and other metal parts of switches, motors and the
like.

All non-current carrying metal parts of equipment, pumps and water pipes will be bonded to
the earthing system

Separate earthing systems will be provided for MV equipment switchgear.

A separate earthing system (clean earth) will be provided for telecommunication, electronic
and data systems. The associated earthing resistance will not exceed 0.5 Ohms, when
measured independent of other systems.

The calculation and installation of earthing system will be such as to keep step voltage and
touch voltage within safe limit.

Page 162 of 183

The earthing system shall include earthing associated with the external lighting and shall form
a part of external light installations.

The metallic conduits, cable trays and cable armor shall not be used as a sole protective
conductor for any section of installations.
All earthing materials will be made of copper.

As for weapons & immunity warehouses; separate earthing systems (clean earth) with their
own electrostatic discharge devices to be provided.

2.9 Lightning protection system

Based on the risk assessment calculations for the buildings (to be submitted for review and
approval); complete lightning protective system shall be provided in accordance with NFPA
780 &/ or the British Standards BS 62305 "Code of Practice for the Protection of Structures
against Lightning and shall also comply with SEC requirements, if any.

The roof termination network will be composed of bare annealed copper roof conductors
forming a mesh with dimensions as called for in the regulations and connected to the down
conductors .The building's steel reinforcing bars may be used as down conductors by bonding
them to the roof and earthing conductors at approved intervals according to BS requirements.

The earth source will be bonded underground to the main earthing system. The earth source
will consist of multi-earth pits interconnected with bare copper and will ensure an earth
resistance less than 5 ohms.

2.10 Elevators

The elevators will comply with the requirements of EN81: Safety Rules for Construction and
installation of lifts and all its applicable related derivatives. Lifts of adequate capacity and
speed shall be provided as per design assessment to serve the building.

Tie-in (link) to the fire alarm system shall be provided to park the lifts on ground floor upon
receipt of a fire signal.
Page 163 of 183

Lifts shall be equipped with key operated buttons as deemed necessary to guarantee security
of personnel.

The Contractor shall allow for free fall test on selected sample at each site and shall replace
worn out components resulting from this test.
Finishes of Passenger lifts will be as per coordination with the Arch/ID.

Page 164 of 183

II. ELECTRICAL (LOW CURRENT SYSTEMS):

Introduction

This part of the report is intended to set out the scope of works outline specifications and
minimum technical requirements required to prepare the drawing and installations of the low
current systems in the 1KP Projects.

The detail drawings and installations of the low current systems works will be carried out by
the Contractor. The requirements and responsibilities of the contractor as well as the
deliverables required shall be the same as that outlined in the General requirements.

Scope of Work

The scope of telecommunication & low-current installations in the 1KP projects will include
but not necessarily limited to the following:-
- Public Address System.
- Fire Alarm System.
- Integrated Security System.
- IP CCTV System.
- IP Access Control System.
- Microwave Intrusion Detection System.
- Under-Vehicle Inspection System.
- Buried Electromagnetic Cable Sensor.
- Security Devices.
- MATV System.
- Structured Cabling Networks.
- IP Telephony System.
- Traditional Telephone system .(for administrations projects only)( ]oe^nai )
- Audio/Visual and Video Conference System.
- Data network active equipment.

Page 165 of 183

1 LOW CURRENT/TELECOM SYSTEMS
1.1 FIRE ALARM SYSTEM
Introduction
An addressable fire alarm system shall be provided to achieve automatic fire of fire in all
areas via automatic fire alarm devices as well as manual fire reporting via distributed manual
pull stations.

System Description
The system consists basically of the following components:

Main Fire Alarm Control Panel (MFACP)
The MFACP shall be surface mounted and located in the main Building in the
project in specified area.
The MFACP shall contain power supplies, data bus conductors, battery charger
and all necessary function modules and components, including the following:
Microprocessor based, Central Processing Unit (CPU) to process all system
data and generate all system automatic alarm functions.
Fire alarm loops cards to covered all buildings in the project.
Alphanumeric, backlit, Liquid Crystal Display (LCD).
System ALARM LED indicator with alarm condition acknowledge button.
System supervisory condition LED indicator with supervisory condition
acknowledge button.
System trouble condition LED indicator with trouble condition acknowledge
button.
System alarm silence button.
System reset button.
Emergency voice dialer for fire brigade interconnection.
The MFACP shall be provided with battery backup capability. The batteries shall
provide 12-hours of normal standby operation and 5 minutes of normal alarm
operation at the end of the 12-hour standby period.
The MFACP shall:
Interface with Public Address System control relays, each control relay module
represent one Public Address zone that will be interfaced with the correspondent
fire alarm zone as per the approved fire alarm zones.
In case of fire alarm reporting from any device within one of the fire alarm zones,
the MFACP shall initiate the corresponding zone relay module which in turn,
shall initiate a pre-recorded evacuation message via public address speakers.
Interface with BMS System via control relays. The interface shall be on the zone
level (one control relay per each fire alarm zone). Through this interface, the
BMS system shall control the HVAC equipment and electrical panels.
The interface between the fire alarm system and BMS System may be via
software protocol (if exist).
Interface with elevators, if applicable.
Interface with Fire fighting system via monitor modules to monitor the fire pump,
tamper switches and water flow switches.
Interface with security system (Access control).
Page 166 of 183

Interface between the Main fire alarm panel and each Fire alarm panel in each
building as mentioned in Main riser diagram.

Graphic Display Unit (GDU)
The graphic fire command center shall provide easily recognizable site plan and
floor plan information to simplify the fire alarm system operation and in order to
direct the operator to the immediate area of interest.
The system shall consist of Desktop computer, 17 inch color LCD monitor and
the needed software.
The system shall have the following features:
A graphical annunciation and control for all fire alarm devices/ points of the Fire
Alarm System.
Importing of drawing files.
Extensive historical logging.
Multiple operator level with password control.
System Printer
Desktop type printer shall be provided in the main control room and it shall print
the following:
A permanent hardcopy record of all pertinent details of system activity.
Record all alarm, supervisory and trouble conditions.

- Fire Alarm Control Panel (FACP) (number shall be according to the drawings and
covered all buildings in the project )
FACPs shall be used and located in the open area 24 hour (Security room,
hall,) . The connection between the fire alarm control panels and the MFACP
shall be peer to peer connection via fiber optic cables or the manufactured
recommended.
The FACP shall contain power supplies system, data bus conductors, battery
charger.
All necessary function modules and components shall include the following:
a. Solid state, microprocessor based, Central Processing Unit (CPU) to process
all system data and generate all system automatic alarm functions.
b. Fire alarm loop cards.
c. Alphanumeric, backlit, Liquid Crystal Display (LCD).
d. System ALARM LED indicator.
e. System supervisory condition LED indicator.
f. System trouble condition LED indicator.

The FACP shall be provided with battery backup capability. The batteries shall
provide 12-hours of normal standby operation and 5 minutes of normal alarm
operation at the end of the 12-hour standby period.
All fire alarm control panels shall send all alarm, supervisory and trouble actions
to the main fire alarm control panel in order to achieve centralized monitoring
and control of the fire alarm system

Page 167 of 183

Fire Alarm Repeater Panel (FARP)
Fire alarm repeater panel shall be of modular design and containing all
components of the system including solid-state electronic components, audible
and visual unit, relays and interface components, batteries and charger and other
components required for operation of system.
Addressable Smoke Detector
An addressable photoelectric smoke detector type shall be provided. The
Photoelectric detector sensor shall provide an analogue measurement that is
digitally communicated to the fire alarm control panel. At the panel, the data is
analyzed and the average value is determined and stored. The alarm or abnormal
condition is determined by comparing the sensors present value against its
average value and time.

The addressable smoke detector shall have the following features:
Automatic time programmable sensitivity to allow setting up sensitivity level for
different times during the day.
Automatic environmental compensation via the fire alarm control panel.
Sensor alarm and trouble led indication.
The addressable smoke detector shall be supplied as a complete set with its base.
All detectors shall be supplied with a standard base type except 7% of all devices
which shall be supplied with fault isolator base according to the No. of devices
and No. of loops.

Addressable Duct Smoke Detector
An addressable duct smoke detector type shall be provided. The duct smoke detector
shall incorporate sampling tubes and housing designed for this application.
The addressable duct smoke detector shall be connected to the fire alarm system loop, but
it shall be provided as a complete set with control relay for connection with BMS system
as well.

Addressable Heat Detector
An addressable Fixed Temperature/Rate of Rise Heat detector type shall be provided. The
heat detector sensor shall provide an analogue measurement that is digitally transmitted to
the fire alarm control panel. At the panel, the received data shall be calculated to
determine and store the average value. The alarm or abnormal condition is determined by
comparing the sensors presented value against its average value and time.
The addressable heat detector shall have the following features:
Automatic environmental compensation via the fire alarm control panel.
Sensor alarm and trouble led indication.
The addressable heat detector shall be supplied as a complete set with its base. All
detectors shall be supplied with a standard base type except 7% of devices which shall be
supplied with fault isolator base.
Heat detector, fixed temperature type at range from 80C to 90C shall be provided for
installation in diesel generator rooms.
Page 168 of 183

Addressable Manual Station
Addressable manual fire alarm station shall be provided. The manual station shall be of a
single action push type.
When the manual station operated, the pull level latches into the alarm position remains
extended out of the housings to provide a visible indication until the station is reset.

Addressable Control Module
Addressable Control Modules: Shall be individually addressable control relay and shall
consist of printed circuit board with discrete circuitry for controlling one individually
addressable control relay. The control shall respond to control signals from the Fire
Alarm Control Panel.
These control relays shall be used for interface with the BMS, lifter and Public Address
systems.

Multi-Sensor Detector
DESIGN: two wire operation, processes and analyses information from each
sensor (photo/heat) separately using dynamic filters, with high quality solid state
electronic components, completely shielded, protected against false alarms from
EMI and RFI, and obtaining operating power from supervisory current in
detection loop.

DETECTOR is to be analogue addressable and is to have the circuitry for two-
way communication with the FACP. Each time the detector is polled, it is to
communicate its individual address, and an analogue/digitally encoded value
corresponding to its sensitivity and status with microcomputer processing in the
control unit. Detector is to be automatically addressed by its location in the
signaling loop.

Addressable Monitor Module
Addressable Monitor Modules: Shall be individually addressable alarm
initiating/supervisory circuit board and shall consist of printed circuit board with discrete
circuitry for monitoring normally open, dry contacts. The monitor shall respond to
polling signals from the Fire Alarm Control Panel and shall report alarm
initiating/supervisory circuit status changes to it.
These monitor modules shall be used for interface with the fire fighting pump, tamper
switches and water flow switches.

Alarm Bell with strobe light
6 inch size fire alarm bell including strobe light unit shall be used. The alarm bell and
strobe light unit shall operate on 12 or 24 Volt DC supplied directly from the fire alarm
control panel.
The alarm bells and strobe light units shall be provided in all buildings.
Page 169 of 183

System Distribution Criteria
The fire alarm system shall cover all areas with smoke detectors except the kitchens, the
buffets and the tea rooms which shall be covered by heat detectors.
Smoke detectors shall be installed above suspended ceiling in all areas which contains
combustible materials.
The manual pull stations shall be provided in all buildings.
Generator rooms shall be covered with heat detectors and smoke detectors transformer
rooms power panel rooms.

System Control
The monitoring, control and operation of the fire alarm control system shall be controlled
from the main control room through the following equipment:
Main Fire Alarm Control Panel (MFACP).
Graphic Display unit.
Printer

System Power
In addition to the power backup batteries used in the fire alarm systems capable to keep the system
running for 12h in standby mode and 5 minutes alarm mode (MFACP, FACPs, Graphic Display Unit
and printer), all also should be fed from the Uninterrupted Power Supply (UPS) for 15 minutes.

Fire alarm Cabling
Fire alarm cables shall be low smoke, zero halogens, LSOH fire resistant type to IEC
331,332 part 1 and 3, 754 and 1034.

Fire alarm system block diagram
Refer to the main fire alarm system riser diagrams in the projects and update the riser
according to the modified arch. Drawings in plans in addendum 1.

1.2 Public Address System
Introduction
A Public Address System shall be provided with the following features:
Broadcasting audio materials from CD player, DVD and AM/FM Radio Tuner
Achieve paging from paging microphones to a certain zone, group of zones or All-Call
paging via paging microphones.
Interface with the fire alarm system to be used for voice evacuation announcements inside
and outside buildings.
Indoor type loudspeakers (mounted in fire-resistant dome) shall be distributed in all areas
inside buildings while outdoor type speakers shall cover all outside areas.
The cable shall be recommended by supplier.
Page 170 of 183

System Description
The public address system shall consist of the following components:
Paging Microphone
More paging microphones shall be used; one microphone shall be located in the main
control room.
Each paging microphone can be used to page a certain zone, group of zones or ALL
CALL paging facility.
The paging microphone shall be a desktop type and shall comprise a microphone, double-
signal chime tone, paging button for each zone and ALL CALL paging button.
Rack Cabinet
A standard "19 inch" rack cabinet(s) shall be provided to house the public address system
central equipment. The rack cabinet(s) of the system shall be located in the main
equipments room in the main Building.

The centralized public address equipment shall be installed within the rack in a logical
(signal path) sequence. Notwithstanding this requirement, equipment requiring routing
operation (e.g. switch and monitor panels) shall be located at a convenient working
height.
The rack cabinet shall be equipped with power strip unit and blower.
CD player and DVD
No. 1 rack-mounted CD player shall be provided with the following specifications:
CD player with capacity of 1 CD and 1 DVD .
Continuous repeat of a pre-programmed track selection.
Visible display of track number and of total playing time on the inserted CD and DVD .

AM/FM Radio Tuner
A rack-mounted AM/FM radio tuner shall be provided. The unit shall have high
sensitivity reception performance and clear sound.
The unit shall be equipped with display, tuning and search buttons and preset memory
buttons.
The AM / FM antenna shall be provided with the radio tuner.
Audio Switching Matrix
The Audio Switching Matrix shall be provided to assign any audio input source to any
designated audio output(s) with the required priorities between inputs. The audio
switching matrix shall be a rack-mounted type.
The Audio Switching Matrix shall have a number of audio inputs for the sound sources,
emergency message unit and paging microphones.
The Audio Switching Matrix shall have a number of audio outputs that feeds the
loudspeaker zones.
The Audio Switching Matrix shall have a contact closure control inputs to interface with
the fire alarm system.
Page 171 of 183

Power Amplifiers
A rack-mounted power amplifier with 100V matching transformer shall be provided to
feed the speaker lines. Each public address zone shall be served by a dedicated power
amplifier.
The power amplifier shall include the following:
Power "ON/OFF" indicator.
Gain control.
The capacity of the power amplifiers shall be calculated based on ceiling speakers
operated at 6 watt and according to the type of Speaker mentioned in the drawings and
Main riser diagram.
A standby power amplifier shall be provided within the rack cabinet to replace the main
power amplifier incase of any failure.
Speaker Lines Surveillance Unit
A rack-mounted surveillance unit shall be used to monitor the status of the loudspeaker
lines.
The surveillance unit shall automatically detect the following fault conditions:
Loudspeaker line short circuit.
Loudspeaker line open circuit.

Monitor Panel
A monitor panel shall be provided to monitor the output of each amplifier. An amplifier
selector switch, integral loudspeaker and calibrated loudspeaker gain control shall be
provided.
Visual monitoring with a visual meter shall be provided on the monitor panel.
Ceiling Speaker
Cone ceiling speaker type complete with grille shall be used.
The ceiling speaker shall be 6W RMS and complete with 100V matching transformer.
The ceiling speaker shall be complete with rear fire dome.
Outdoor Speaker
Wall mounted and weather proof complete with 100V matching transformer.
Rated power 30 watt.
Sensitivity 101 dB (1w/1m).
Other speaker mentioned in the drawing.

Speaker cables
All speaker cables shall be twisted pair plenum rated type, minimum size of 2.5 sq. mm with no more
than 0.5 dB insertion loss per circuit.
System Control
The operation and control of the public address system shall be as following:
The broadcasting of audio signals from the available sources like CD player or AM/ FM
Radio Tuner.
Automatic broadcasting of pre-recorded evacuation message in case of fire alarm
reporting.
Page 172 of 183

Achieve Paging from the Paging microphones located in the main control room, in the
operations room building gate control room and in the entrance of operations room
building.
The following input signals shall be provided with automatic priority (lowest number =
highest priority):
Paging Microphone located in the main control room.
Emergency Message Unit.
Background music from CD player, DVD or AM/FM Radio Tuner.

Public address system block diagram

Refer to the P.A risers drawing in the projects, scope of work and modified drawing in
addendum 1.

1.3 Security System
Security system drawings
Refer to the buildings drawings and scope of work

1.3.1 Integrated Security system
The scope shall include interfacing the security systems and devices, i.e. the
CCTV Systems, Access Control System, Intrusions Detection System, Road
Blockers, fire alarm system , fire fighting systems, and under vehicle inspection
system, etc. together in one platform software for monitoring the status and alerts
of each system.
The system shall have all required hardware and software to make a complete
compatibility, share information and control all security systems and monitor life
safety systems.

1.3.2 IP CCTV System
Introduction
A number of IP based CCTV cameras shall be placed within the Buildings and on the facility
fences to video surveillance of all areas in/around the facility projects. The video recording
of all cameras shall be saved in order to keep a record of all events. Camera monitoring and
control are to be via Main equipment in main Building.
System Provision
The IP CCTV System shall be provided in all project buildings as mentioned in the drawings
and Main Gate, entrances building, Fences and outdoor area in the site, .

Page 173 of 183

System Description
System utilizes different types of IP color cameras, operator workstations, video servers,
image recording equipment and application software. All cameras are utilizing a TCP/IP
interface where UTP cables are to be connected to the camera through an RJ 45 connector.
Camera UTP cables are then connected to the nearest Low Current room where it shall be
connected to the facility data network and some cameras connect to the LAN network with
Fiber optic cable 2 core if the distance more than 90m from the nearest Low current room. the
IP CCTV Camera in Fence connected to the Watch tower with Cat6 cable also the watch
tower connected to the LAN with single mode fiber optic 4 cores as shown in the drawings
.All operator workstations are connected to the data network via UTP cable which is in turn
connected to the nearest data switch where it gets connected to facility data network. Camera
video servers are connected via UTP to nearest data switch to the Central Control Room in
main building. Each video server can handle up to 1000 fps. The Video storage equipments
shall be connected to the LAN via Ethernet interface. The LAN shall be connected to the
nearest data switch that connected to the Central Control Room with an adequate storage
capacity for minimum of 30 days period of time continuous for all cameras with live picture
of 30 frame/sec minimum and high resolution.
Operator workstations are located at main control room or some anther location in the main
building also in some anther building as mentioned in the drawing buildings , riser diagram or
in BOQ where viewing of cameras in single and multi screen formats is available as well as
initiation of image recording as per the request of the operator. They shall be able to monitor,
record, playback and control all cameras existing in the project.
System Distribution Criteria
Cameras are distributed as follows:

PTZ cameras to monitor corridors, entrances, lobbies, sitting areas, gates and lift
lobbies.
Fixed indoor high security cameras within computer equipment room and data
storage room.
Fixed day/night outdoor cameras are utilized to monitor the facility fence from
the inside part and the outside part as well.
Some system need to PTZ camera and fixed camera as indicative in the drawing
and BOQ.
Integrations
Cameras located on the fence surrounding are integrated with the perimeter intruder detection
system in order to be able to call cameras automatically in case of intruder alarm detection.
All cameras are integrated within the security management system under which all security
systems are integrated.
System Control
Cameras shall be monitored and controlled via operator workstations from the central control
room located in Admin building, and Maine gate building some building having a sub control
room and connected to the main control room in the Admin building. Central control room
shall be able to monitor and control all existing cameras within the entire facility. Gate
control room shall only monitor gate cameras as well as cameras located at road blockers and
car barriers. Camera control includes camera viewing, camera PTZ control, camera recording
and play back of recorded images.
Page 174 of 183

System Power
The IP CCTV system shall be fed from UPS for 15 minutes for both the Cameras and control
equipment.
1.3.3 Access Control System
Introduction
A number of IP Access Control Panels panel with related proximity card readers, locks and
magnetic door position switches shall be placed within the buildings. Biometric
authentication (fingerprint) shall be used at computer equipment room, data storage room and
intermediate distribution frame rooms and all rooms indicated in the drawing buildings. A
system server and operator workstations shall be located at Central Control Room for door
transaction monitoring and control. All system transactions (who, when and where) shall be
logged to an event printer as well as being recorded on hard desk located in the main Control
Room for report generations. Main and operations rooms building gate doors, road blockers
and car barriers are monitored and controlled through the Access Control System.
System Provision
The IP Access Control System shall be provided in some projects and anther projects contain
the normal Access control system. See the Document of each project the BOQ , scope of
work, riser diagram ) taken into consideration the modified drawing in addendum No.1.
System Description
System utilizes distributed panel architecture; access control panels are distributed within the
buildings in order to be able to control access to secured areas. Each access control panel is
equipped with a number of proximity card readers with integrated keypad, magnetic door
locks and magnetic door position sensors in order to control access to highly secured areas
related to doors under control of this particular control panel. All rooms such as stores, server
rooms, low current rooms, control room etc. shall be equipped with an emergency break
glass unit in order to mechanically release the door in case of emergency. A system setup and
configuration is to be done via system software by system administrator. Cardkeys are to be
issued at a central location for all authorized personnel with related access levels
corresponding to his duties and areas he is authorized to enter, this keycard can be time, date
and access level limited. An authorized person can gain access introducing his keycard to the
proximity readers as well as entering a Personal Identification Number (PIN) related to his
keycard in order to be allowed through that particular door. All access control panels shall be
programmed via main Control Room for purpose of security, also door control and
monitoring shall be done via Central Control room. All system transactions such as door
open, close, forced open, valid card, invalid card etc. with time and date stamp are reported to
main control room where it shall be printed on an event printer and saved on a hard desk for
report generation. Access control panels are equipped with an Ethernet interface board which
leads to more system flexibility in terms of system expansion since all communications
between panels and system server is via operations room building data network.
System Distribution Criteria
Access control system shall control and monitor the following locations:
Areas enclosing valuable items like stores and low current rooms.
Main control room
Computer equipment room/data storage room
Page 175 of 183

Electrical/Mechanical rooms (provision only)
Road blockers
Car barriers
Main gate.
Branch Gate.
Some area mentioned in the drawing buildings.

System Integrations
Access control system shall be integrated within the security management system. Access
control system is to be interfaced with CCTV system in order to call cameras .on particular
monitors in case of any access control event. Moreover the access control system is interfaced
with the fire alarm system in order to automatically release specific doors in case of
confirmed fire alarm status, interface criteria is to be advised by building management.

System Control
Authorized personnel shall gain access to restricted areas based on their access levels via
proximity cards and PIN. All doors can be Locked, Secured and Unlocked via Central Control
Room through operator workstation units located inside it. If door is locked, no one even
authorized personnel can open this particular door, if secured, only authorized personnel can
gain access through that door, if unlocked, anyone can gain access through this door during
the unlock period of time. Road blockers and car barriers can be raised and lowered via Push
Buttons located at the main gate control room.

1.3.4 Microwave Intrusion Detection System
It includes the following features:
a) Detection Capability
Beam Diameter: 0.6m to 12.2m depending upon link length, antenna
pattern element and Sensitivity setting.

b) Reliability
Equipment False Alarm Rate: 1/year/unit based upon signal-to-noise
ratio at maximum sensitivity setting.
Probability of Detection: 0.9 minimum on 35kg human upright or on
hands and knees.
c) Transmittal Signal
Radiated Power: 10 mille watts peak, 5 mille watts average, square
wave modulated.
Carrier Frequency: X-band (USA 10.525 GHz 25MH).
Modulation Frequencies: Four field-selectable modulation
frequencies.
Page 176 of 183

Above specifications for USA are in accordance with F.C.C.
regulations. Equipment available to meet regulations of other
countries.

1.3.5 Buried Electromagnetic Cable Sensor
a) The system shall be able to function as a standalone system and as an
integral component of a centralized security control system.
b) The detection field shall be formed by radio-frequency (RF) signals carried
by sensor cables that are buried along the perimeter.
c) The RF signals shall form an invisible electromagnetic detection field
around the sensor cables that can detect the presence of an intruder passing
through the field.
d) The system shall detect moving intruders that have a significant
electromagnetic field (e.g. humans, vehicles, and other large conductive
objects) while rejecting other environmental stimuli such as birds, small
animals, weather elements.
e) A sensor module shall contain the electronics required to:
1) Transmit and receive the RF signal without the use of an external
antenna.
2) Monitor the detection fields of No. of zones according to the system
and produce an alarm when an intruder enters the zones.
f) Field power modules shall be available for standalone systems and
networked systems.
g) As part of a network configuration, the primary operator interface shall be a
personal computer (PC) based central controller. The central controller
shall monitor the performance of the entire buried coaxial cable outdoor
intrusion detection system and any auxiliary sensors. The central controller
shall have the capability of acknowledging, processing and reporting
alarms. A customized color site map that is displayed on the PC monitor
shall be an available option for the system to monitor sensor locations.
h) Transmission and reception shall be accomplished without the use of
antennae. The RF signal shall be monitored and analyzed by the sensor
module for any changes in the detection field properties that would indicate
the presence of an intruder.
i) Alarms generated by internal electronic processes (cables excluded) shall
not exceed one (1) per zone per month. System generated alarms are
averaged based on the total number of zones in the system.
j) When the system is calibrated in accordance with the manufacturers'
recommendations, the detection field shall be continuous and uniform over
the protected site perimeter.
k) When system sensitivity is calibrated according to manufacturers'
recommendations, the detection field shall not detect a valid target that is a
minimum of 6.5 ft. (2 m) from the nearest sensor cable.

Page 177 of 183

1.4 MATV System
Introduction
System Provisions
The MATV system shall be applied in the project and can be serve at least 30 channel TV
Satellite from three satellite at least Nile sat, Arab sat and Hot bird sat or (as mentioned in
each project) ,one head end located in the main building in the project and connect all other
buildings with Head end by coaxial cable and Amplifier and Tap off as per mentioned in riser
diagram buildings and scope of work.
System Description
MATV Head-End
- The Head-end contains equipment for:
Receivers Set Tap Box (STB).
Combiners.
Tap off
Modulator.
Software management
- End-to-End Solution shall provide key pieces, such as:
System Components
- The MATV system shall be consists of:
Dish Farm
Off-Air broadcast Receivers
Coaxial cable
Splitter Amplifier
Tap off.
Distributions amplifier
Splitter.
TV RF outlet.

Dish Farm
Dish Farm consists of three satellite Dishes 1.8 m diameter. Aligned to Arab sat, Nile sat and
Hot bird sat, Each dish has a quad LNB installed and the LNB outputs connect to the
receivers head-ends using coaxial cables. Dishes shall be connected to head end station (RF)
via coaxial cables (4 cables for every LNB).

Head End

The head end equipment shall receive the TV channel (RF) from the receiving dishes in
digital form.

Page 178 of 183

The head end equipment shall receive, demodulate, modulate channels and combine
Channels.
Off-Air Receivers
The Off-Air Receiver subsystem shall be responsible for converting the RF signal, received
from the satellite LNB, to receivers.
Set-top Boxes
Set top box shall be installed in the head End and combine the out in the coaxial cable to
send the other building
System Distribution Criteria
- A Dish Farm that includes (3) satellite dishes which shall be aligned to Arabsat, Niles
at and Hot bird.
- The head-end shall provide 30 Free-To-Air TV channel services.
- Head-End equipment shall be installed as shown in the drawings.
System Requirements
- The MATV system shall be based on the coaxial Network distribution. The solution
is not dependent on specific companys network hardware in order to deliver analog
and digital Television. However, there are some network requirements, the solution
must be carefully designed, tested, and staged to ensure the infrastructure can sustain
the traffic necessary to deliver video.

1.5 Structured cabling system
Introduction
- There are structured cabling networks:
Network: Data/IP telephony and security systems as mentioned in the building
drawings and in Main riser diagrams in the project Also, the contractor shall prepare
the Structure cabling system drawings in some projects according to the scope of
work in addendum No.1 and BOQ.
- Structured cabling shall be comprised of copper and fiber technology, and shall
follow the star topology concept that is implemented in the networking criteria.
- Future proof multi mode fiber optic backbone shall be accommodated to support the
current and future requirements and single mode fiber optic cable. Also, a Copper
CAT 6 cable solution shall be available to support bandwidths up to 250MHZ latest
technology requirements.
Compliances
The Infrastructure Cabling System complies with TIA/EIA 568B standards and Saudi
Telecom Company.
Page 179 of 183

System Description
Each structured cabling network shall consist of the following:
- Main communication cabinets including fiber optic and copper patch panels.
- Horizontal communication cabinets including fiber optic and copper patch panels.
- Backbone fiber and copper cables.
- Horizontal copper cables.
- Work area outlet RJ 45.

Structured cabling network shall have the following transmission performance:
Frequency (MHz) 1 4 10 16 20 31.25 62.5 100 160 200 250
Insertion Loss (dB) 2.1 3.8 6.0 7.6 8.5 9.6 10.8 15.5 25.8 29.0 33.0
NEXT (dB) 74.3 65.3 59.3 56.2 54.8 51.9 47.4 44.3 41.2 39.8 38.3
PSNEXT (dB) 72.3 63.3 57.3 54.2 52.8 49.9 45.4 42.3 39.2 37.8 36.3
ACR (dB) 72.2 61.4 53.3 48.6 46.2 41.1 31.9 24.4 15.5 10.6 5.3
PSACR (dB) 70.2 59.4 51.3 46.6 44.2 39.1 29.9 22.4 13.5 8.6 3.3
ACR-F (dB) 67.8 55.8 47.8 43.7 41.8 37.9 31.9 27.8 23.7 21.8 19.8
PS ACR-F (dB) 64.8 52.8 44.8 40.7 38.8 34.9 28.9 24.8 20.7 18.8 16.8
Return Loss (dB) 20.0 23.0 25.0 25.0 25.0 23.6 21.5 20.1 18.7 18.0 17.3
Propagation Delay (ns) 570 552 545 543 542 540 539 538 537 537 536
Note: some projects contain the Traditional Telephone system and the Telephone network
contain the copper telephone cable, MDF, IDF see the scope of work in addendum No.1 and
BOQ.

1.6 IP Telephony System

Introduction
IP telephony is the utilization of data network infrastructure (LAN) to transport
telecommunication transactions including, telephone calls, faxes and messages.
IP Telephony depends on existing data network infrastructure, yet facilitates higher
redundancy and availability, ease of installation, administration, and maintenance, enormous
application capabilities and significantly cost saving and lower total cost of network
ownership and positive return on investment.
Some projects contain the traditional telephone system, PABX and MDF, IDF. The contractor
shall follow up the scope of work of each project in addendum no.1 and BOQ.

Page 180 of 183

1.6.1 System Provisions
The IP Telephony System shall be applicable on all facilities buildings in the projects see the
BOQ.

1.6.2 System Description
The IP Telephony system shall have the following features and facilities:
- IP extensions, referred to as Directory Number (DN)
- Music on Hold service
- Background Music
- Call Conferencing service
- Operator Console
- PSTN Digital trunks connectivity
- Flexible DID services
- Corporate Directory
- Call Waiting Notification
- Voice Mail Box
- Auto Attendant
- Scheduled Access Restriction
- Automatic Line Selection
- Call Party Name Display

In addition to the above, shall have the following advance features:
- Call Features: hold, conferencing, and transfer, forward, redial, and speed dial, Do Not
Disturb (DND), etc.
- Enhanced telephone set features: Ring tone and volume control, call log for received, dialed
and missed calls, hands-free, Microphone mute, etc.
- Flexible Call Restrictions
Note that Saudi Telecom Company (STC) business interface, application, and installation up
to site perimeter are the contractor responsibility. Connecting and installing the interfaces of
those trunks with the IPT system shall be contractor responsibility also, including the
interface equipment. The owner shall pay the total cost required from STC.
Page 181 of 183

1.6.3 System Components of IP Telephony
The system shall be based on the IP telephony model and shall include the following
components:
- Control and signaling equipment
- Basic IP phone set shall be equipped for all telephony ports
- Executive and office-type IP phone
- Voice Gateway based on E1s digital technology
- Voice mail system
- Attendant console
- Analogue terminal adaptor for faxes connectivity
- Voice digital recording

1.6.4 IP Telephone sets
Three types of telephone sets shall be used for this scope:
- Basic telephone set with limited features (Entry level).
- Senior level telephone sets
- VIP and Manager telephone set shall with touch screen facility.

1.6.5 Voice Gateway
The site shall be equipped with dual voice gateway in order to provide voice connectivity
through digital E1s interface trunks interface to the STC for off-campus telephone calls.

1.6.6 Voice mail
The Voice mail service shall be provided for 100% of the total users of telephone sets.

1.6.7 Attendant Console
The project shall be equipped with one attend console system, which supports all traditional
features.
Analogue Terminal Adaptor
Analog terminal adaptor (ATA) shall provide analogue type connectivity through IP multi
services network. The ATA shall support Fax application. The distribution of the ATA units
shall be finalized during the detailed design revision.
Page 182 of 183

Solution Capacity
The System Capacity shall be according to the no. of users and design requirement.
System Control
The services shall be controlled through a software program that shall facilitate the required
administration, day-to-day operation and add-on, maintenance, and alarming.
1.6.8 Traditional Telephone system.
Some of project contain the traditional telephone system Technology, the stem shall cover all
future mentioned above in the IP telephone system, the contractor shall follow up the scope
of work in addendum no.1, BOQ and specification to cover the system.

1.7 IP Data Networks
1.7.1 Introduction
The model that we are considering is the three layers or two layer architecture models to
simplify network design, implementation and management for the project buildings.
Some projects contain two Data network the contractor shall follow up the scope of work and
BOQ of each project.
1.7.2 System Provisions
The network IP Data Network System shall be provided to the main Building and all
buildings in the projects as per mentioned in the drawing and BOQ buildings.
1.7.3 System Description
This network should secure different departments application. It is consider the main
solution for connecting the secure active ports.
1.7.3.1 System components
This network shall be based on the hierarchy of three layers: Access layer, distribution layer
(if exist ) and Core layer. The Edge switches are Layer1 fixed configuration switches, the
distribution layer are Layer-2 and the core switches are third layer.

The number of active ports in each IT closet shall be based on the design drawing and as
approved prepare drawings by contractor. The Edge switch that shall be used is a fixed
configuration switches 24 10/100 ports or 48 10/100 port with 2 Gigabyte uplink to the
backbone switches, as per port distribution requirements. The backbone switches shall be
high performance modular switches that support a variety of modules, like Ethernet Gigabit.
The Secure IP data network provides Ethernet connectivity and switching for all connected
ports. Core, distribution and Access switches shall maintain QoS performance for all
provided services based on type of service and class of service. Different security techniques
can be used to guarantee network security, such as VLAN and Access Control Lists. The
secure IP data network operation can be monitored, managed, and reported via the LAN
centralized management system.
Page 183 of 183

This network shall be used to connect the IP telephony system and internet connectivity ports.
The IP data network shall be considered the main network for connecting the IP telephony
sets/ Internet PCs. This requires a complete available, manageable, and secure solution.
The Edge switches shall offer Power over Ethernet (PoE) that deliver DC power to IP
telephone sets. The modular Backbone switches shall support a variety of network modules,
like Ethernet Gigabit.
The IP data network shall provide Ethernet connectivity and switching for all connected ports.
The Core , distribution and Access switches shall maintain QoS performance for all provided
services based on type of service and class of service.
Also, this network is responsible to serve IP Low current systems (CCTV, access control,
BMS, etc.).
1.8 Audio/Visual and video conference systems
Audio Visual system and training Aids shall be designed for Auditoriums, Lecture halls,
Training workshops, Class rooms, meeting rooms and conference rooms as mentioned in the
drawing project building and BOQ , The system shall be intelligent control system to
distribute Audio/ Visual sources to display units .
The equipment shall be consists of Audio/ visual sources , DVD players , VCRs, Double
auto revere cassettes , Video Projector with automatic lift, Motorized large screens, Mixer
Preamplifiers , Computer Interface, speaker ..
For the Education building, each class room shall have the A/V system which can operate
standalone from the class and can operate from centralized location for all class rooms in the
same time.

Anda mungkin juga menyukai