ELECTRICAL INSTALLATION CERTIFICATE Certificate Reference:

Issued in accordance with British Standard BS 7671 5458


Requirements for Electrical Installations

DETAILS OF THE CLIENT


Client Address: Clas Ohlson Ltd, St James House, 13 Kensington Square, London, W8 5HD

DETAILS OF THE INSTALLATION


The Installation is:
Installation 61-64 Broad Street, Reading, Berkshire, RG1 2AJ
Address:
Extent of the This certificate relates to the refurbishment of an existing retail unit. The main distribution has been retained, adapted and
New 
re-used. All other services have been removed and installed new. The eisiting lift installation and distribution has been
installation covered retained and is subject to a seperate certificate issued by clients lift contractor.The light fitments in the retail area have been
An addition N/A
by this certificate: provided and installed by the clients specialist contractor and connect to the installed system via a plug and socket.
An alteration

DESIGN
I/We, being the person(s) responsible for the design of the electrical installation (as indicated by my/our signature(s) below)
particulars of which are described above, having exercised reasonable skill and care when carrying out the design, hereby CERTIFY
that the design work for which I/we have been responsible is, to the best of my/our knowledge and belief,
in accordance with BS 7671: 2008 amended to N/A except for the departures, detailed as follows:
Details of departures from BS 7671, as amended (Regulations 120.3, 120.4): None

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.
For the DESIGN of the installation:
Name: IVAN BERRY Position: MD Signature: Date: 16/11/2009

Where there is divided responsibility for the design


Name: N/A Position: Signature: N/A Date: N/A

CONSTRUCTION
I/We, being the person(s) responsible for the construction of the electrical installation (as indicated by my/our signature(s) below)
particulars of which are described above, having exercised reasonable skill and care when carrying out the construction, hereby
CERTIFY that the construction work for which I/we have been responsible is, to the best of
my/our knowledge and belief, in accordance with BS 7671: 2008 amended to N/A except for the
departures, if any, detailed as follows:
Details of departures from BS 7671, as amended (Regulations 120.3, 120.4): None

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.
For the CONSTRUCTION of the installation:
Name: IVAN BERRY Position: MD Signature: Date: 16/11/2009

INSPECTION AND TESTING


I/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our
signature(s) below) particulars of which are described above, having exercised reasonable skill and care when carrying out the
inspection and testing, hereby CERTIFY that the work for which I/we have been responsible is to the best of my/our
knowledge and belief, in accordance with BS 7671: 2008 amended to N/A except for the
departures, if any, detailed as follows:
Details of departures from BS 7671, as amended (Regulations 120.3, 120.4): None

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.
For the INSPECTION AND TESTING of the installation:
Name: IVAN BERRY Position: MD Signature: Date: 16/11/2009

DESIGN, CONSTRUCTION, INSPECTION AND TESTING


I/We, being the person(s) responsible for the design, construction, inspection and testing of the electrical installation (as indicated
by my/our signature(s) below) particulars of which are described above, having exercised reasonable skill and care when carrying
out the design, construction, inspection and testing, hereby CERTIFY that the said work for which I/We
have been responsible is to the best of my/our knowledge and belief, in accordance with BS 7671: 2008 amended to
N/A except for the departures, if any, detailed as follows:

Details of departures from BS 7671, as amended (Regulations 120.3, 120.4): None

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.
For the DESIGN, the CONSTRUCTION, and the INSPECTION AND TESTING of the installation:
Name: IVAN BERRY Position: MD Signature: Date: 16/11/2009

This form is based on the model shown in Appendix 6 of BS 7671:2008 Page: 1 of 21


DETAILS OF THE ELECTRICAL CONTRACTOR
DESIGN (1) Trading Title: Octopus Technical Services ltd

Address: 9 Wych Elm Road, Clayhanger, Walsall,West Midlands


Registration Number: 5993-4464

Telephone Number: 01543 361289

Post Code: WS8 7QP

DESIGN (2) Trading Title: Same as Above

Address:
Registration Number:

Telephone Number:
Post Code:

CONSTRUCTION Trading Title: Same as Above

Address:
Registration Number:

Telephone Number:

Post Code:
INSPECTION
AND TESTING Trading Title: Same as Above

Address:
Registration Number:

Telephone Number:

Post Code:

SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS


System Type(s) Number and Type of Live Conductors Nature of Supply Parameters Characteristics of Primary
Supply Overcurrent
Nominal
TN-S N/A
1-phase
ac:

1-phase
dc: N/A
voltage(s):
U: 400 V Uo: 230 V Protective Device(s)

Nominal frequency, f:
TN-C-S  (2 wire):
2-phase
N/A
(3 wire):  2 pole: N/A
Prospective fault
50 Hz BS(EN): 1361 Fuse HBC

TNC N/A
(3 wire): N/A 3 pole: N/A current, lpf: 1.1 kA Type: 2

3-phase 3-phase External earth fault


TT N/A
(3 wire):
N/A
(4 wire):
N/A Other: N/A 0.21  Rated current: 600 A
loop impedance, Ze:
Short-circuit
IT N/A Other: N/A Number of supplies: 1
capacity:
33 kA

PARTICULARS OF INSTALLATION AT THE ORIGIN


Means of Earthing Details of Installation Earth Electrode (where applicable)
Distributor's
facility:  Type: N/A Location: N/A

Installation Electrode Method of


earth electrode:
N/A
resistance, RA: N/A  measurement: N/A

Maximum Demand (Load): 550 Amps Protective measure(s) against electric shock: ADS

Main Switch or Circuit-Breaker Earthing and Protective Bonding Conductors


Type Earthing conductor
BS(EN):
60947-2 MCCB Voltage rating: 400 V Conductor Conductor Continuity
Number of
4
Rated
600 A
material:
Copper
csa:
95 mm2
check: 
poles: current, ln: Main protective bonding conductors
Supply Conductor Conductor Continuity
conductors Copper
RCD operating
N/A mA
material:
Copper
csa:
50 mm2 check: 
current: Bonding of extraneous-conductive parts
material:
Lightning
Supply
conductors 120
RCD operating
mm2 time: N/A ms
Water service:  Oil service: N/A
protection:
N/A

csa: Gas service:


 Structural Steel:
 Other services: N/A

COMMENTS ON EXISTING INSTALLATION


Note: Enter 'NONE' or, where appropriate, the page number(s) of additional page(s) of comments on the
None
existing installation.

NEXT INSPECTION
I/We, the designer(s), RECOMMEND that this installation is further inspected and tested after an
5 Years
interval of not more than:
This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 2 of 21
SCHEDULE OF ITEMS INSPECTED Prevention of mutual detrimental influence
(a) Proximity of non-electrical services and other
Methods of protection against electric shock  influences
Basic and fault protection: (b) Segregation of Band I and Band II circuits or use of
 Band II insulation
 (i) SELV N/A (ii) PELV

Double or reinforced insulation:


 (c) Segregation of safety circuits
Identification
(iii) Double or Reinforced Insulation Presence of diagrams, instructions, circuit charts and
N/A
 similar information
Basic protection:
(i) Insulation of (ii) Barriers or  Presence of danger notices and other warning notices
 live parts  enclosures Labelling of protective devices, switches and terminals
N/A (iii) Obstacles ** N/A (iv) Placing out 
of reach **
Fault protection:  Identification of conductors
Cables and Conductors
(i) Automatic disconnection of supply Selection of conductors for current carrying capacity and
 voltage drop
 Presence of earthing conductor
 Erection methods
 Presence of circuit protective conductors
Routing of cables in prescribed zones or within
 mechanical protection
 Presence of main protective bonding conductors
Cables incorporating earthed armour or sheath, or run
Presence of earthing arrangements for combined 
 protective and functional purposes
within an earthed wiring system, or otherwise adequately
protected against nails, screws and the like
Presence of adequate arrangements for alternative
 source(s), where applicable
Additional protection provided by 30mA RCD for cables in
N/A FELV  concealed walls (where required in premises not under
the supervision of skilled or instructed persons)
N/A Choice and setting of protective and monitoring devices
(for fault protection and/or overcurrent protection)
 Connection of conductors

(ii) Non-conducting location ** Presence of fire barriers, suitable seals and protection
 against thermal effects
N/A Absence of protective conductors General
Presence and correct location of appropriate devices for
(iii) Earth-free local equipotential bonding **  isolation and switching
Adequacy of access to switchgear and other equipment
N/A Presence of earth-free local equipotential bonding 
(iv) Electrical Separation Particular protective measures for special installations
 and locations
 Provided for one item of current-using equipment

Connection of single-pole devices for protection or
switching in line conductors only
Provided for more than one item of current-using
N/A
equipment **
Additional protection:
 Correct connection of accessories and equipment

 Presence of residual current device(s)  Presence of undervoltage protective devices


Selection of equipment and protective measures
 Presence of supplementary bonding conductors  appropriate to external influences

** For use in controlled supervised/conditions only  Selection of appropriate functional switching devices

SCHEDULE OF ITEMS TESTED Protection against direct contact by barrier or enclosure


 provided during erection
 External earth fault loop impedance, Ze
 Insulation of non-conducting floors or walls
N/A Installation earth electrode resistance, RA
 Polarity

 Continuity of protective conductors


 Earth fault loop impedance, Zs

 Continuity of ring final circuit conductors


 Verification of phase sequence

 Insulation resistance between live conductors


N/A Operation of residual current device(s)
Insulation resistance between live conductors and earth
  Functional testing of assemblies

 Protection by separation of circuits


 Verification of voltage drop

SCHEDULE OF ADDITIONAL RECORDS (See attached schedule)


Note: Additional page(s) must be identified by the Electrical Installation Cert serial and page number(s).
All boxes must be completed. 'tick' indicates that an inspection or test was carried out and that the result was satisfactory. 'X' indicates than an
inspection or test was carried out and the result is not satisfactory. 'N/A' indicates that an inspection or test was not applicable to the particular
installation. 'LIM' indicates that, exceptionally, a limitation agreed with the person ordering the work prevented the inspection or test being carried out.

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 3 of 21
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
TO BE COMPLETED IN EVERY CASE
DIRECTLY TO THE ORIGIN OF THE INSTALLATION
Location of distribution board: Supply to distribution No of Nominal
MCCB Panel distribution board 3 400 V
First Floor Mains Room board is from: phases: Voltage:
Overcurrent protective device for the Associated RCD
n/a
distribution circuit: (if any) BS(EN):
Distribution board designation:
Type RCD No
D.B. 3
BS(EN):
60947-2 MCCB Rating: 100 A
of poles:
n/a RCD ln: n/a mA

CIRCUIT DETAILS
Circuit

permitted by BS7671

permitted by BS7671
Overcurrent protective

Max disconnect time


conductors: RCD
devices
csa

Reference Method

Maximum Zs
Circuit number

Type of wiring

points served
Circuit designation

Operating
Capacity
Type No
Number of
and phase

current
Live cpc BS(EN)

Rating
mm2 mm2 s A kA mA 
1 L1 office lights A C 35 1.5 1.0 5 3871 2 16 10 N/A 2.05

1 L2 secure store office sockets A C 4 2.5 1.5 0.4 60898 C 20 10 N/A 1.15

1 L3 Access control spurs offices sockets A C 6 2.5 1.5 0.4 60898 C 20 10 N/A 1.15

2 L1 Toilet and staff room lights A C 16 1.5 1.0 5 3871 2 10 10 N/A 3.29

2 L2 Cash/team leader sockets A C 6 2.5 1.5 0.4 60898 C 20 10 N/A 1.15

2 L3 Manager sockets A C 4 2.5 1.5 0.4 60898 C 20 10 N/A 1.15

3 L1 Stairwell - Lights L/H side A C 10 1.5 1.0 5 3871 2 10 10 N/A 3.29

3 L2 Remote store C B 4 4 4 5 3871 C 10 10 N/A 2.30

3 L3 Kitchen water heater A C 1 2.5 1.5 5 3871 2 16 10 N/A 2.05

4 L1 Stock room lights L/H side D B 30 1.5 1.5 5 3871 2 10 10 N/A 3.29

4 L2 Kitchen Sockets A C 8 2.5 2.5 0.4 3871 2 20 10 N/A 1.64

4 L3 Dedicated computer sockets A C 4 2.5 1.5 0.4 60898 C 20 10 N/A 1.15

5 L1 Stock room lights R/H side D B 28 1.5 1.5 5 3871 2 10 10 N/A 3.29

5 L2 Dedicated computer sockets A C 4 2.5 1.5 0.4 60898 C 16 10 N/A 1.44

5 L3 Dedicated computer sockets A C 4 2.5 1.5 0.4 60898 C 20 10 N/A 1.15

6 L1 Stock room lights middle D B 30 1.5 1.5 5 3871 2 10 10 N/A 3.29

6 L2 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

6 L3 Disabled w/c h/dryer A C 1 2.5 1.5 5 3871 2 10 10 N/A 3.29

7 L1 Goods lift lobby lights D B 12 1.5 1.5 5 3871 2 10 10 N/A 3.29

7 L2 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

7 L3 Ladies h/dryer A C 1 2.5 1.5 5 3871 2 16 10 N/A 2.05

8 L1 Mains Cupboard Lift motor Lights A C 2 1.5 1.0 5 3871 2 10 10 N/A 3.29

8 L2 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

8 L3 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

CODES FOR TYPE OF WIRING


A: PVC/PVC cables D: PVC cables in metallic trunking G: XLPE/SWA cables
B: PVC cables in metallic conduit E: PVC cables in non-metallic trunking H: Mineral-insulated cables
C: PVC cables in non-metallic conduit F: PVC/SWA cables O - Other:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 4 of 21
CHARACTERISTICS AT THIS D.B. DETAILS OF TEST INSTRUMENTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT Test Instruments (serial numbers) used:
CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION Earth fault loop
N/A RCD: N/A
 Confirmation of supply polarity impedance:
Insulation
Zs: 0.28  Operating times At ln: n/a ms Resistance: N/A Other: N/A
of associated RCD
lpf: 0.90 kA (if any) At 5ln: n/a ms Continuity: N/A Other: N/A

TEST RESULTS
Insulation resistance RCD Operating
Circuit impedances ohms Maximum
(record lower or lowest value) times
measured
All circuits earth fault
Ring final circuits only
Circuit number

(one column to be Polarity loop


(measured end to end)
completed) Line/ Line/ Line/ Neutral/ impedance
and phase

Line Neutral Earth Earth At ln At 5 ln


Zs
r1 rn r2 R1+R2 R2
(Line) (Neutral) (cpc) M M M M   ms ms
1 L1 N/A N/A N/A 0.98 N/A N/A > 200 > 200 > 200
 1.03 N/A N/A

1 L2 N/A N/A N/A 0.83 N/A N/A > 200 > 200 > 200
 0.99 N/A N/A

1 L3 N/A N/A N/A 0.98 N/A N/A > 200 > 200 > 200
 1.09 N/A N/A

2 L1 N/A N/A N/A 1.69 N/A N/A > 200 > 200 > 200
 1.80 N/A N/A

2 L2 N/A N/A N/A 0.84 N/A N/A > 200 > 200 > 200
 0.93 N/A N/A

2 L3 N/A N/A N/A 0.80 N/A N/A > 200 > 200 > 200
 0.92 N/A N/A

3 L1 N/A N/A N/A 1.00 N/A N/A > 200 > 200 > 200
 1.13 N/A N/A

3 L2 N/A N/A N/A 0.72 N/A N/A > 200 > 200 > 200
 1.00 N/A N/A

3 L3 N/A N/A N/A 0.38 N/A N/A > 200 > 200 > 200
 0.47 N/A N/A

4 L1 N/A N/A N/A 2.16 N/A N/A > 200 > 200 > 200
 3.16 N/A N/A

4 L2 N/A N/A N/A 0.90 N/A N/A > 200 > 200 > 200
 1.05 N/A N/A

4 L3 N/A N/A N/A 0.81 N/A N/A > 200 > 200 > 200
 0.96 N/A N/A

5 L1 N/A N/A N/A 1.16 N/A N/A > 200 > 200 > 200
 1.48 N/A N/A

5 L2 N/A N/A N/A 1.40 N/A N/A > 200 > 200 > 200
 1.42 N/A N/A

5 L3 N/A N/A N/A 0.93 N/A N/A > 200 > 200 > 200
 1.02 N/A N/A

6 L1 N/A N/A N/A 1.21 N/A N/A > 200 > 200 > 200
 1.36 N/A N/A

6 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

6 L3 N/A N/A N/A 0.66 N/A N/A > 200 > 200 > 200 N/A 0.78 N/A N/A

7 L1 N/A N/A N/A 1.53 N/A N/A > 200 > 200 > 200 N/A 1.63 N/A N/A

7 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

7 L3 N/A N/A N/A 0.63 N/A N/A > 200 > 200 > 200 N/A 0.69 N/A N/A

8 L1 N/A N/A N/A 0.50 N/A N/A > 200 > 200 > 200 N/A 0.57 N/A N/A

8 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

8 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

TESTED BY
Name
(CAPITALS): ANDREW RUSSELL Position: Engineer

Date of
Signature: 16/11/2009
testing:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 5 of 21
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
TO BE COMPLETED IN EVERY CASE
DIRECTLY TO THE ORIGIN OF THE INSTALLATION
Location of distribution board: Supply to distribution No of Nominal
MCCB Panel distribution board 3 400 V
First floor mains room board is from: phases: Voltage:
Overcurrent protective device for the Associated RCD
N/A
distribution circuit: (if any) BS(EN):
Distribution board designation:
Type RCD No
D.B. 3A
BS(EN):
60947-2 MCCB Rating: 100 A
of poles:
N/A RCD ln: N/A mA

CIRCUIT DETAILS
Circuit

permitted by BS7671

permitted by BS7671
Overcurrent protective

Max disconnect time


conductors: RCD
devices
csa

Reference Method

Maximum Zs
Circuit number

Type of wiring

points served
Circuit designation

Operating
Capacity
Type No
Number of
and phase

current
Live cpc BS(EN)

Rating
mm2 mm2 s A kA mA 
9 L1 Rear corridor lights A C 12 1.5 1.0 5 3871 2 10 10 N/A 3.29

9 L2 Ladies water heater A C 1 2.5 1.5 5 3871 2 16 10 N/A 2.05

9 L3 Male h/dryer A C 1 2.5 1.5 5 60898 C 10 10 N/A 2.30

10 L1 Staff room dado sockets A C 2 2.5 1.5 0.4 60898 C 20 10 N/A 1.15

10 L2 UPS Supply G C 1 16 16 5 3871 2 32 10 N/A 1.03

10 L3 Security spur-mains room A C 1 2.5 1.5 5 3871 2 10 10 N/A 3.29

11 L1 Store room general power A C 2 2.5 1.5 0.4 60898 C 20 10 N/A 1.15

11 L2 Mens water heater A C 1 2.5 1.5 5 1361 2 10 33 N/A N/A

11 L3 Spare

12 L1 Spare

12 L2 Spare

12 L3 Spare

13 L1 Spare

13 L2 Spare

13 L3 Spare

14 L1 Spare

14 L2 Spare

14 L3 Spare

15 L1 Spare

15 L2 Spare

15 L3 Spare

16 L1 Spare

16 L2 Spare

16 L3 Spare

CODES FOR TYPE OF WIRING


A: PVC/PVC cables D: PVC cables in metallic trunking G: XLPE/SWA cables
B: PVC cables in metallic conduit E: PVC cables in non-metallic trunking H: Mineral-insulated cables
C: PVC cables in non-metallic conduit F: PVC/SWA cables O - Other:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 6 of 21
CHARACTERISTICS AT THIS D.B. DETAILS OF TEST INSTRUMENTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT Test Instruments (serial numbers) used:
CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION Earth fault loop
N/A RCD: N/A
 Confirmation of supply polarity impedance:
Insulation
Zs: 0.28  Operating times At ln: n/a ms Resistance: N/A Other: N/A
of associated RCD
lpf: 0.90 kA (if any) At 5ln: n/a ms Continuity: N/A Other: N/A

TEST RESULTS
Insulation resistance RCD Operating
Circuit impedances ohms Maximum
(record lower or lowest value) times
measured
All circuits earth fault
Ring final circuits only
Circuit number

(one column to be Polarity loop


(measured end to end)
completed) Line/ Line/ Line/ Neutral/ impedance
and phase

Line Neutral Earth Earth At ln At 5 ln


Zs
r1 rn r2 R1+R2 R2
(Line) (Neutral) (cpc) M M M M   ms ms
9 L1 N/A N/A N/A 1.68 N/A N/A > 200 > 200 > 200
 1.77 N/A N/A

9 L2 N/A N/A N/A 1.72 N/A N/A > 200 > 200 > 200
 0.72 N/A N/A

9 L3 N/A N/A N/A 0.69 N/A N/A > 200 > 200 > 200
 0.67 N/A N/A

10 L1 N/A N/A N/A 0.90 N/A N/A > 200 > 200 > 200
 0.95 N/A N/A

10 L2 N/A N/A N/A 0.34 N/A N/A > 200 > 200 > 200
 0.35 N/A N/A

10 L3 N/A N/A N/A 0.26 N/A N/A > 200 > 200 > 200
 0.32 N/A N/A

11 L1 N/A N/A N/A 0.41 N/A N/A > 200 > 200 > 200
 0.45 N/A N/A

11 L2 N/A N/A N/A 0.69 N/A N/A > 200 > 200 > 200
 0.67 N/A N/A

11 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

12 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

12 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

12 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

13 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

13 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

13 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

14 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

14 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

14 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

15 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

15 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

15 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

16 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

16 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

16 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

TESTED BY
Name
(CAPITALS): ANDREW RUSSELL Position: Engineer

Date of
Signature: 16/11/2009
testing:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 7 of 21
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
TO BE COMPLETED IN EVERY CASE
DIRECTLY TO THE ORIGIN OF THE INSTALLATION
Location of distribution board: Supply to distribution No of Nominal
MCCB Panel distribution board 3 400 V
Mains room - first floor board is from: phases: Voltage:
Overcurrent protective device for the Associated RCD
N/A
distribution circuit: (if any) BS(EN):
Distribution board designation:
Type RCD No
D.B. A/C
BS(EN):
60947-2 MCCB Rating: 250 A
of poles:
N/A RCD ln: N/A mA

CIRCUIT DETAILS
Circuit

permitted by BS7671

permitted by BS7671
Overcurrent protective

Max disconnect time


conductors: RCD
devices
csa

Reference Method

Maximum Zs
Circuit number

Type of wiring

points served
Circuit designation

Operating
Capacity
Type No
Number of
and phase

current
Live cpc BS(EN)

Rating
mm2 mm2 s A kA mA 
1 L1 AHU #1 G E 1 10 43 5 60898 C 50 10 N/A 0.46

1 L2 AHU #1 G E 1 10 43 5 60898 C 50 10 N/A 0.46

1 L3 AHU #1 G E 1 10 43 5 60898 C 50 10 N/A 0.46

2 L1 AHU #2 G E 1 10 43 5 60898 C 50 10 N/A 0.46

2 L2 AHU #2 G E 1 10 43 5 60898 C 50 10 N/A 0.46

2 L3 AHU #2 G E 1 10 43 5 60898 C 50 10 N/A 0.46

3 L1 A/C #1 G E 1 4 23 5 60898 C 32 10 N/A 0.72

3 L2 A/C #1 G E 1 4 23 5 60898 C 32 10 N/A 0.72

3 L3 A/C #1 G E 1 4 23 5 60898 C 32 10 N/A 0.72

4 L1 A/C #2 G E 1 4 23 5 60898 C 32 10 N/A 0.72

4 L2 A/C #2 G E 1 4 23 5 60898 C 32 10 N/A 0.72

4 L3 A/C #2 G E 1 4 23 5 60898 C 32 10 N/A 0.72

5 L1 A/C #3 G E 1 4 23 5 60898 C 32 10 N/A 0.72

5 L2 A/C #3 G E 1 4 23 5 60898 C 32 10 N/A 0.72

5 L3 A/C #3 G E 1 4 23 5 60898 C 32 10 N/A 0.72

6 L1 A/C #6 G E 1 4 23 5 60898 C 32 10 N/A 0.72

6 L2 A/C #6 G E 1 4 23 5 60898 C 32 10 N/A 0.72

6 L3 A/C #6 G E 1 4 23 5 60898 C 32 10 N/A 0.72

7 L1 A/C #4 G E 1 4 23 5 60898 C 32 10 N/A 0.72

7 L2 A/C #4 G E 1 4 23 5 60898 C 32 10 N/A 0.72

7 L3 A/C #4 G E 1 4 23 5 60898 C 32 10 N/A 0.72

8 L1 A/C #5 G E 1 4 23 5 60898 C 25 10 N/A 0.92

8 L2 A/C #5 G E 1 4 23 5 60898 C 25 10 N/A 0.92

8 L3 A/C #5 G E 1 4 23 5 60898 C 25 10 N/A 0.92

CODES FOR TYPE OF WIRING


A: PVC/PVC cables D: PVC cables in metallic trunking G: XLPE/SWA cables
B: PVC cables in metallic conduit E: PVC cables in non-metallic trunking H: Mineral-insulated cables
C: PVC cables in non-metallic conduit F: PVC/SWA cables O - Other:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 8 of 21
CHARACTERISTICS AT THIS D.B. DETAILS OF TEST INSTRUMENTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT Test Instruments (serial numbers) used:
CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION Earth fault loop
N/A RCD: N/A
 Confirmation of supply polarity impedance:
Insulation
Zs: 0.29  Operating times At ln: n/a ms Resistance: N/A Other: N/A
of associated RCD
lpf: 1.1 kA (if any) At 5ln: n/a ms Continuity: N/A Other: N/A

TEST RESULTS
Insulation resistance RCD Operating
Circuit impedances ohms Maximum
(record lower or lowest value) times
measured
All circuits earth fault
Ring final circuits only
Circuit number

(one column to be Polarity loop


(measured end to end)
completed) Line/ Line/ Line/ Neutral/ impedance
and phase

Line Neutral Earth Earth At ln At 5 ln


Zs
r1 rn r2 R1+R2 R2
(Line) (Neutral) (cpc) M M M M   ms ms
1 L1 N/A N/A N/A 0.36 N/A N/A > 200 > 200 > 200
 0.37 N/A N/A

1 L2 N/A N/A N/A 0.35 N/A N/A > 200 > 200 > 200
 0.40 N/A N/A

1 L3 N/A N/A N/A 0.37 N/A N/A > 200 > 200 > 200
 0.38 N/A N/A

2 L1 N/A N/A N/A 0.25 N/A N/A > 200 > 200 > 200
 0.39 N/A N/A

2 L2 N/A N/A N/A 0.34 N/A N/A > 200 > 200 > 200
 0.36 N/A N/A

2 L3 N/A N/A N/A 0.38 N/A N/A > 200 > 200 > 200
 0.39 N/A N/A

3 L1 N/A N/A N/A 0.65 N/A N/A > 200 > 200 > 200
 0.69 N/A N/A

3 L2 N/A N/A N/A 0.66 N/A N/A > 200 > 200 > 200
 0.70 N/A N/A

3 L3 N/A N/A N/A 0.69 N/A N/A > 200 > 200 > 200
 0.69 N/A N/A

4 L1 N/A N/A N/A 0.63 N/A N/A > 200 > 200 > 200
 0.64 N/A N/A

4 L2 N/A N/A N/A 0.67 N/A N/A > 200 > 200 > 200
 0.65 N/A N/A

4 L3 N/A N/A N/A 0.64 N/A N/A > 200 > 200 > 200
 0.65 N/A N/A

5 L1 N/A N/A N/A 0.65 N/A N/A > 200 > 200 > 200
 0.66 N/A N/A

5 L2 N/A N/A N/A 0.67 N/A N/A > 200 > 200 > 200
 0.68 N/A N/A

5 L3 N/A N/A N/A 0.63 N/A N/A > 200 > 200 > 200
 0.65 N/A N/A

6 L1 N/A N/A N/A 0.50 N/A N/A > 200 > 200 > 200
 0.53 N/A N/A

6 L2 N/A N/A N/A 0.49 N/A N/A > 200 > 200 > 200
 0.57 N/A N/A

6 L3 N/A N/A N/A 0.55 N/A N/A > 200 > 200 > 200
 0.58 N/A N/A

7 L1 N/A N/A N/A 0.59 N/A N/A > 200 > 200 > 200
 0.59 N/A N/A

7 L2 N/A N/A N/A 0.60 N/A N/A > 200 > 200 > 200
 0.60 N/A N/A

7 L3 N/A N/A N/A 0.59 N/A N/A > 200 > 200 > 200
 0.60 N/A N/A

8 L1 N/A N/A N/A 0.53 N/A N/A > 200 > 200 > 200
 0.54 N/A N/A

8 L2 N/A N/A N/A 0.52 N/A N/A > 200 > 200 > 200
 0.54 N/A N/A

8 L3 N/A N/A N/A 0.39 N/A N/A > 200 > 200 > 200
 0.54 N/A N/A

TESTED BY
Name
(CAPITALS): ANDREW RUSSELL Position: Engineer

Date of
Signature: 16/11/2009
testing:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 9 of 21
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
TO BE COMPLETED IN EVERY CASE
DIRECTLY TO THE ORIGIN OF THE INSTALLATION
Location of distribution board: Supply to distribution No of Nominal
MCCB Panel distribution board 3 400 V
Mains room - first floor board is from: phases: Voltage:
Overcurrent protective device for the Associated RCD
N/A
distribution circuit: (if any) BS(EN):
Distribution board designation:
Type RCD No
D.B. A/C A
BS(EN):
60947-2 MCCB Rating: 250 A
of poles:
N/A RCD ln: N/A mA

CIRCUIT DETAILS
Circuit

permitted by BS7671

permitted by BS7671
Overcurrent protective

Max disconnect time


conductors: RCD
devices
csa

Reference Method

Maximum Zs
Circuit number

Type of wiring

points served
Circuit designation

Operating
Capacity
Type No
Number of
and phase

current
Live cpc BS(EN)

Rating
mm2 mm2 s A kA mA 
9 L1 A/C #11 G E 1 4 23 5 60898 C 20 10 N/A 1.15

9 L2 A/C #11 G E 1 4 23 5 60898 C 20 10 N/A 1.15

9 L3 A/C #11 G E 1 4 23 5 60898 C 20 10 N/A 1.15

10 L1 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

10 L2 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

10 L3 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

11 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

11 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

11 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

12 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

12 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

12 L3 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

13 L1 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

13 L2 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

13 L3 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

14 L1 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

14 L2 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

14 L3 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

15 L1 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

15 L2 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

15 L3 Spare N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

16 L1 Thermoscreen G E 1 16 49 5 60898 C 32 10 N/A 0.72

16 L2 Thermoscreen G E 1 16 49 5 60898 C 32 10 N/A 0.72

16 L3 Thermoscreen G E 1 16 49 5 60898 C 32 10 N/A 0.72

CODES FOR TYPE OF WIRING


A: PVC/PVC cables D: PVC cables in metallic trunking G: XLPE/SWA cables
B: PVC cables in metallic conduit E: PVC cables in non-metallic trunking H: Mineral-insulated cables
C: PVC cables in non-metallic conduit F: PVC/SWA cables O - Other:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 10 of 21
CHARACTERISTICS AT THIS D.B. DETAILS OF TEST INSTRUMENTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT Test Instruments (serial numbers) used:
CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION Earth fault loop
N/A RCD: N/A
 Confirmation of supply polarity impedance:
Insulation
Zs: 0.29  Operating times At ln: n/a ms Resistance: N/A Other: N/A
of associated RCD
lpf: 1.1 kA (if any) At 5ln: n/a ms Continuity: N/A Other: N/A

TEST RESULTS
Insulation resistance RCD Operating
Circuit impedances ohms Maximum
(record lower or lowest value) times
measured
All circuits earth fault
Ring final circuits only
Circuit number

(one column to be Polarity loop


(measured end to end)
completed) Line/ Line/ Line/ Neutral/ impedance
and phase

Line Neutral Earth Earth At ln At 5 ln


Zs
r1 rn r2 R1+R2 R2
(Line) (Neutral) (cpc) M M M M   ms ms
9 L1 N/A N/A N/A 0.58 N/A N/A > 200 > 200 > 200
 0.59 N/A N/A

9 L2 N/A N/A N/A 0.52 N/A N/A > 200 > 200 > 200
 0.58 N/A N/A

9 L3 N/A N/A N/A 0.56 N/A N/A > 200 > 200 > 200
 0.59 N/A N/A

10 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

10 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

10 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

11 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

11 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

11 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

12 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

12 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

12 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

13 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

13 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

13 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

14 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

14 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

14 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

15 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

15 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

15 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

16 L1 N/A N/A N/A 0.70 N/A N/A > 200 > 200 > 200
 0.72 N/A N/A

16 L2 N/A N/A N/A 0.69 N/A N/A > 200 > 200 > 200
 0.72 N/A N/A

16 L3 N/A N/A N/A 0.69 N/A N/A > 200 > 200 > 200
 0.72 N/A N/A

TESTED BY
Name
(CAPITALS): ANDREW RUSSELL Position: Engineer

Date of
Signature: 16/11/2009
testing:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 11 of 21
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
TO BE COMPLETED IN EVERY CASE
DIRECTLY TO THE ORIGIN OF THE INSTALLATION
Location of distribution board: Supply to distribution No of Nominal
MCCB Panel distribution board 3 400 V
Mains room - first floor board is from: phases: Voltage:
Overcurrent protective device for the Associated RCD
N/A
distribution circuit: (if any) BS(EN):
Distribution board designation:
Type RCD No
D.B. A/C B
BS(EN):
60947-2 MCCB Rating: 250 A
of poles:
N/A RCD ln: N/A mA

CIRCUIT DETAILS
Circuit

permitted by BS7671

permitted by BS7671
Overcurrent protective

Max disconnect time


conductors: RCD
devices
csa

Reference Method

Maximum Zs
Circuit number

Type of wiring

points served
Circuit designation

Operating
Capacity
Type No
Number of
and phase

current
Live cpc BS(EN)

Rating
mm2 mm2 s A kA mA 
17 L1 A/C #7 G E 1 4 4 5 60947-2 C 20 10 N/A 1.15

17 L2 A/C #9 G E 1 4 4 5 60947-2 C 20 10 N/A 1.15

17 L3 A/C #13 G E 1 4 4 5 60947-2 C 20 10 N/A 1.15

18 L1 A/C #12 G E 1 4 4 5 60947-2 C 20 10 N/A 1.15

18 L2 A/C #8 G E 1 4 4 5 60947-2 C 20 10 N/A 1.15

18 L3 A/C #10 G E 1 4 4 5 60947-2 C 20 10 N/A 1.15

N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

CODES FOR TYPE OF WIRING


A: PVC/PVC cables D: PVC cables in metallic trunking G: XLPE/SWA cables
B: PVC cables in metallic conduit E: PVC cables in non-metallic trunking H: Mineral-insulated cables
C: PVC cables in non-metallic conduit F: PVC/SWA cables O - Other:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 12 of 21
CHARACTERISTICS AT THIS D.B. DETAILS OF TEST INSTRUMENTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT Test Instruments (serial numbers) used:
CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION Earth fault loop
N/A RCD: N/A
 Confirmation of supply polarity impedance:
Insulation
Zs: 0.29  Operating times At ln: n/a ms Resistance: N/A Other: N/A
of associated RCD
lpf: 1.1 kA (if any) At 5ln: n/a ms Continuity: N/A Other: N/A

TEST RESULTS
Insulation resistance RCD Operating
Circuit impedances ohms Maximum
(record lower or lowest value) times
measured
All circuits earth fault
Ring final circuits only
Circuit number

(one column to be Polarity loop


(measured end to end)
completed) Line/ Line/ Line/ Neutral/ impedance
and phase

Line Neutral Earth Earth At ln At 5 ln


Zs
r1 rn r2 R1+R2 R2
(Line) (Neutral) (cpc) M M M M   ms ms
17 L1 N/A N/A N/A 0.54 N/A N/A > 200 > 200 > 200
 0.66 N/A N/A

17 L2 N/A N/A N/A 0.44 N/A N/A > 200 > 200 > 200
 0.46 N/A N/A

17 L3 N/A N/A N/A 0.40 N/A N/A > 200 > 200 > 200
 0.42 N/A N/A

18 L1 N/A N/A N/A 0.34 N/A N/A > 200 > 200 > 200
 0.34 N/A N/A

18 L2 N/A N/A N/A 0.45 N/A N/A > 200 > 200 > 200
 0.45 N/A N/A

18 L3 N/A N/A N/A 0.37 N/A N/A > 200 > 200 > 200
 0.41 N/A N/A

TESTED BY
Name
(CAPITALS): ANDREW RUSSELL Position: Engineer

Date of
Signature: 16/11/2009
testing:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 13 of 21
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
TO BE COMPLETED IN EVERY CASE
DIRECTLY TO THE ORIGIN OF THE INSTALLATION
Location of distribution board: Supply to distribution No of Nominal
DB3-10L2 3 400 V
Server Room board is from: phases: Voltage:
Overcurrent protective device for the Associated RCD
N/A
distribution circuit: (if any) BS(EN):
Distribution board designation:
Type RCD No
D.B. UPS
BS(EN):
60898 MCB - Type C Rating: 32 A of poles: N/A RCD ln: N/A mA

CIRCUIT DETAILS
Circuit

permitted by BS7671

permitted by BS7671
Overcurrent protective

Max disconnect time


conductors: RCD
devices
csa

Reference Method

Maximum Zs
Circuit number

Type of wiring

points served
Circuit designation

Operating
Capacity
Type No
Number of
and phase

current
Live cpc BS(EN)

Rating
mm2 mm2 s A kA mA 
1 UPS Group #1 A B 2 2.5 1.5 0.4 60898 C 16 10 N/A 1.44

2 UPS Group #2 A B 2 2.5 1.5 0.4 60898 C 16 10 N/A 1.44

3 UPS Group #3 A B 2 2.5 1.5 0.4 60898 C 16 10 N/A 1.44

4 UPS Group #4 G E 1 4 4 0.4 60898 C 16 10 N/A 1.44

5 UPS Group #5 G E 1 4 4 0.4 60898 C 16 10 N/A 1.44

6 UPS Group #6 G E 1 4 4 0.4 60898 C 16 10 N/A 1.44

7 UPS Group #7 G E 1 4 4 0.4 60898 C 16 10 N/A 1.44

8 UPS Group #8 G E 1 4 4 0.4 60898 C 16 10 N/A 1.44

9 UPS Group #9 G E 1 4 4 0.4 60898 C 16 10 N/A 1.44

10 UPS Group #10 G E 1 4 4 0.4 60898 C 16 10 N/A 1.44

11 UPS Group #11 G E 1 4 4 0.4 60898 C 16 10 N/A 1.44

12 UPS Group #12 G E 1 4 4 0.4 60898 C 16 10 N/A 1.44

13 Spare

14 Spare

15 Spare

16 Spare

17 Spare

18 Spare

19 Spare

20 Spare

21 Spare

22 Spare

CODES FOR TYPE OF WIRING


A: PVC/PVC cables D: PVC cables in metallic trunking G: XLPE/SWA cables
B: PVC cables in metallic conduit E: PVC cables in non-metallic trunking H: Mineral-insulated cables
C: PVC cables in non-metallic conduit F: PVC/SWA cables O - Other:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 14 of 21
CHARACTERISTICS AT THIS D.B. DETAILS OF TEST INSTRUMENTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT Test Instruments (serial numbers) used:
CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION Earth fault loop
N/A RCD: N/A
 Confirmation of supply polarity impedance:
Insulation
Zs: 0.36  Operating times At ln: n/a ms Resistance: N/A Other: N/A
of associated RCD
lpf: 0.67 kA (if any) At 5ln: n/a ms Continuity: N/A Other: N/A

TEST RESULTS
Insulation resistance RCD Operating
Circuit impedances ohms Maximum
(record lower or lowest value) times
measured
All circuits earth fault
Ring final circuits only
Circuit number

(one column to be Polarity loop


(measured end to end)
completed) Line/ Line/ Line/ Neutral/ impedance
and phase

Line Neutral Earth Earth At ln At 5 ln


Zs
r1 rn r2 R1+R2 R2
(Line) (Neutral) (cpc) M M M M   ms ms
1 N/A N/A N/A 0.28 N/A N/A > 200 > 200 > 200
 0.31 N/A N/A

2 N/A N/A N/A 0.21 N/A N/A > 200 > 200 > 200
 0.30 N/A N/A

3 N/A N/A N/A 0.30 N/A N/A > 200 > 200 > 200
 0.32 N/A N/A

4 N/A N/A N/A 0.99 N/A N/A > 200 > 200 > 200
 0.96 N/A N/A

5 N/A N/A N/A 0.76 N/A N/A > 200 > 200 > 200
 0.82 N/A N/A

6 N/A N/A N/A 0.70 N/A N/A > 200 > 200 > 200
 0.71 N/A N/A

7 N/A N/A N/A 0.93 N/A N/A > 200 > 200 > 200
 0.94 N/A N/A

8 N/A N/A N/A 0.84 N/A N/A > 200 > 200 > 200
 0.93 N/A N/A

9 N/A N/A N/A 0.87 N/A N/A > 200 > 200 > 200
 0.87 N/A N/A

10 N/A N/A N/A 0.78 N/A N/A > 200 > 200 > 200
 0.82 N/A N/A

11 N/A N/A N/A 0.93 N/A N/A > 200 > 200 > 200
 0.96 N/A N/A

12 N/A N/A N/A 0.84 N/A N/A > 200 > 200 > 200
 0.88 N/A N/A

13 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

14 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

15 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

16 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

17 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

18 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

19 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

20 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

21 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

22 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

TESTED BY
Name
(CAPITALS): ANDREW RUSSELL Position: Engineer

Date of
Signature: 16/11/2009
testing:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 15 of 21
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
TO BE COMPLETED IN EVERY CASE
DIRECTLY TO THE ORIGIN OF THE INSTALLATION
Location of distribution board: Supply to distribution No of Nominal
MCCB Panel distribution board 3 400 V
Ground floor electrical cupboard board is from: phases: Voltage:
Overcurrent protective device for the Associated RCD
N/A
distribution circuit: (if any) BS(EN):
Distribution board designation:
Type RCD No
DB1
BS(EN):
60947-2 MCCB Rating: 100 A
of poles:
N/A RCD ln: N/A mA

CIRCUIT DETAILS
Circuit

permitted by BS7671

permitted by BS7671
Overcurrent protective

Max disconnect time


conductors: RCD
devices
csa

Reference Method

Maximum Zs
Circuit number

Type of wiring

points served
Circuit designation

Operating
Capacity
Type No
Number of
and phase

current
Live cpc BS(EN)

Rating
mm2 mm2 s A kA mA 
1 L1 General power above tego D B 10 4 4 0.4 60898 C 16 10 N/A 1.44

1 L2 General power above tego D B 10 4 4 0.4 60898 C 16 10 N/A 1.44

1 L3 General power above tego D B 10 4 4 0.4 60898 C 16 10 N/A 1.44

2 L1 General power above tego D B 10 4 4 0.4 60898 C 16 10 N/A 1.44

2 L2 Auto door supply D B 1 4 4 5 60898 C 16 10 N/A 1.44

2 L3 Display power A E 2 2.5 1.5 0.4 60898 C 16 10 N/A 1.44

3 L1 General power above tego D B 8 4 4 0.4 60898 C 16 10 N/A 1.44

3 L2 A/C pump cct D B 3 4 4 5 60898 C 16 10 N/A 1.44

3 L3 A/C pump cct D B 3 4 4 5 60898 C 16 10 N/A 1.44

4 L1 A/C pump cct D B 1 4 4 5 60898 C 16 10 N/A 1.44

4 L2 Tagging system socket A B 1 2.5 1.5 0.4 60898 C 10 10 N/A 2.30

4 L3 Fire Alarm H C 1 2.5 1.5 5 60898 C 10 10 N/A 2.30

5 L1 A/C shut down relays H C 1 1.5 1.5 5 60898 C 10 10 N/A 2.30

5 L2 Shelf lighting G F 4 4 4 5 60898 C 20 10 N/A 1.15

5 L3 Shelf lighting G F 4 4 4 5 60898 C 16 10 N/A 1.44

6 L1 Shelf lighting G F 4 4 4 5 60898 C 20 10 N/A 1.15

6 L2 Security spur-below A B 1 2.5 1.5 5 60898 C 16 10 N/A 1.44

6 L3 Clocking in machine A C 1 2.5 1.5 5 60898 C 20 10 N/A 1.15

7 L1 CCTV room dedicated computer A B 4 2.5 1.5 0.4 60898 C 20 10 N/A 1.15

7 L2 CCTV room power A B 4 2.5 1.5 0.4 60898 C 20 10 N/A 1.15

7 L3 Tills power 4 G B 3 4 4 0.4 60898 C 20 10 N/A 1.15

8 L1 Tills power 3 G B 3 4 4 0.4 60898 C 20 10 N/A 1.15

8 L2 Tills power 2 G B 3 4 4 0.4 60898 C 20 10 N/A 1.15

8 L3 Tills power 1 G B 3 4 4 0.4 60898 C 20 10 N/A 1.15

CODES FOR TYPE OF WIRING


A: PVC/PVC cables D: PVC cables in metallic trunking G: XLPE/SWA cables
B: PVC cables in metallic conduit E: PVC cables in non-metallic trunking H: Mineral-insulated cables
C: PVC cables in non-metallic conduit F: PVC/SWA cables O - Other:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 16 of 21
CHARACTERISTICS AT THIS D.B. DETAILS OF TEST INSTRUMENTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT Test Instruments (serial numbers) used:
CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION Earth fault loop
N/A RCD: N/A
 Confirmation of supply polarity impedance:
Insulation
Zs: 0.38  Operating times At ln: n/a ms Resistance: N/A Other: N/A
of associated RCD
lpf: 0.63 kA (if any) At 5ln: n/a ms Continuity: N/A Other: N/A

TEST RESULTS
Insulation resistance RCD Operating
Circuit impedances ohms Maximum
(record lower or lowest value) times
measured
All circuits earth fault
Ring final circuits only
Circuit number

(one column to be Polarity loop


(measured end to end)
completed) Line/ Line/ Line/ Neutral/ impedance
and phase

Line Neutral Earth Earth At ln At 5 ln


Zs
r1 rn r2 R1+R2 R2
(Line) (Neutral) (cpc) M M M M   ms ms
1 L1 N/A N/A N/A 1.02 N/A N/A > 200 > 200 > 200
 1.06 N/A N/A

1 L2 N/A N/A N/A 0.99 N/A N/A > 200 > 200 > 200
 0.99 N/A N/A

1 L3 N/A N/A N/A 0.51 N/A N/A > 200 > 200 > 200
 0.59 N/A N/A

2 L1 N/A N/A N/A 0.89 N/A N/A > 200 > 200 > 200
 1.09 N/A N/A

2 L2 N/A N/A N/A 0.70 N/A N/A > 200 > 200 > 200
 0.70 N/A N/A

2 L3 N/A N/A N/A 0.14 N/A N/A > 200 > 200 > 200
 0.51 N/A N/A

3 L1 N/A N/A N/A 0.53 N/A N/A > 200 > 200 > 200
 0.61 N/A N/A

3 L2 N/A N/A N/A 0.90 N/A N/A > 200 > 200 > 200
 0.92 N/A N/A

3 L3 N/A N/A N/A 0.86 N/A N/A > 200 > 200 > 200
 0.99 N/A N/A

4 L1 N/A N/A N/A 0.98 N/A N/A > 200 > 200 > 200
 0.97 N/A N/A

4 L2 N/A N/A N/A 1.83 N/A N/A > 200 > 200 > 200
 1.87 N/A N/A

4 L3 N/A N/A N/A 1.65 N/A N/A > 200 > 200 > 200
 1.68 N/A N/A

5 L1 N/A N/A N/A 0.53 N/A N/A > 200 > 200 > 200
 0.53 N/A N/A

5 L2 1.10 0.85 0.50 0.86 N/A N/A > 200 > 200 > 200
 0.62 N/A N/A

5 L3 1.03 0.90 0.42 1.35 N/A N/A > 200 > 200 > 200
 0.74 N/A N/A

6 L1 0.30 0.36 0.32 0.40 N/A N/A > 200 > 200 > 200
 0.47 N/A N/A

6 L2 N/A N/A N/A 0.32 N/A N/A > 200 > 200 > 200
 0.39 N/A N/A

6 L3 N/A N/A N/A 0.38 N/A N/A > 200 > 200 > 200
 0.38 N/A N/A

7 L1 N/A N/A N/A 0.49 N/A N/A > 200 > 200 > 200
 0.46 N/A N/A

7 L2 N/A N/A N/A 0.37 N/A N/A > 200 > 200 > 200
 0.45 N/A N/A

7 L3 N/A N/A N/A 0.92 N/A N/A > 200 > 200 > 200
 1.01 N/A N/A

8 L1 N/A N/A N/A 0.96 N/A N/A > 200 > 200 > 200
 0.99 N/A N/A

8 L2 N/A N/A N/A 0.73 N/A N/A > 200 > 200 > 200
 0.96 N/A N/A

8 L3 N/A N/A N/A 1.03 N/A N/A > 200 > 200 > 200
 1.04 N/A N/A

TESTED BY
Name
(CAPITALS): ANDREW RUSSELL Position: Engineer

Date of
Signature: 17/11/2009
testing:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 17 of 21
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
TO BE COMPLETED IN EVERY CASE
DIRECTLY TO THE ORIGIN OF THE INSTALLATION
Location of distribution board: Supply to distribution No of Nominal
MCCB Panel distribution board 3 400 V
Ground floor electrical cupboard board is from: phases: Voltage:
Overcurrent protective device for the Associated RCD
N/A
distribution circuit: (if any) BS(EN):
Distribution board designation:
Type RCD No
DB2
BS(EN):
60947-2 MCCB Rating: 100 A
of poles:
N/A RCD ln: N/A mA

CIRCUIT DETAILS
Circuit

permitted by BS7671

permitted by BS7671
Overcurrent protective

Max disconnect time


conductors: RCD
devices
csa

Reference Method

Maximum Zs
Circuit number

Type of wiring

points served
Circuit designation

Operating
Capacity
Type No
Number of
and phase

current
Live cpc BS(EN)

Rating
mm2 mm2 s A kA mA 
1 L1 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 16 10 N/A 1.44

1 L2 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 20 10 N/A 1.15

1 L3 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 20 10 N/A 1.15

2 L1 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 16 10 N/A 1.44

2 L2 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 20 10 N/A 1.15

2 L3 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 16 10 N/A 1.44

3 L1 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 20 10 N/A 1.15

3 L2 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 20 10 N/A 1.15

3 L3 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 16 10 N/A 1.44

4 L1 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 20 10 N/A 1.15

4 L2 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 16 10 N/A 1.44

4 L3 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 16 10 N/A 1.44

5 L1 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 16 10 N/A 1.44

5 L2 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 16 10 N/A 1.44

5 L3 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 16 10 N/A 1.44

6 L1 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 20 10 N/A 1.15

6 L2 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 20 10 N/A 1.15

6 L3 Retail Lights - via marshalling box D B 4 4 4 5 60898 C 16 10 N/A 1.44

7 L1 Lift lobby/CCTV/external Lts A C 14 1.5 1.0 5 60898 C 16 10 N/A 1.44

7 L2 Window bay power D B 2 4 4 0.4 60898 C 16 10 N/A 1.44

7 L3 Sign/window bay lights D B 1 4 4 5 60898 C 16 10 N/A 1.44

8 L1 Music system socket G B 1 4 4 0.4 3871 2 10 10 N/A 3.29

8 L2 Shelf lighting G E 3 4 4 5 60898 C 20 10 N/A 1.15

8 L3 Contactor control circuit D B 20 1.5 1.5 5 60898 C 10 10 N/A 2.30

CODES FOR TYPE OF WIRING


A: PVC/PVC cables D: PVC cables in metallic trunking G: XLPE/SWA cables
B: PVC cables in metallic conduit E: PVC cables in non-metallic trunking H: Mineral-insulated cables
C: PVC cables in non-metallic conduit F: PVC/SWA cables O - Other:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 18 of 21
CHARACTERISTICS AT THIS D.B. DETAILS OF TEST INSTRUMENTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT Test Instruments (serial numbers) used:
CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION Earth fault loop
N/A RCD: N/A
 Confirmation of supply polarity impedance:
Insulation
Zs: 0.21  Operating times At ln: n/a ms Resistance: N/A Other: N/A
of associated RCD
lpf: 1.1 kA (if any) At 5ln: n/a ms Continuity: N/A Other: N/A

TEST RESULTS
Insulation resistance RCD Operating
Circuit impedances ohms Maximum
(record lower or lowest value) times
measured
All circuits earth fault
Ring final circuits only
Circuit number

(one column to be Polarity loop


(measured end to end)
completed) Line/ Line/ Line/ Neutral/ impedance
and phase

Line Neutral Earth Earth At ln At 5 ln


Zs
r1 rn r2 R1+R2 R2
(Line) (Neutral) (cpc) M M M M   ms ms
1 L1 N/A N/A N/A 0.21 N/A N/A > 200 > 200 > 200
 0.44 N/A N/A

1 L2 0.29 0.17 0.23 0.19 N/A N/A > 200 > 200 > 200
 0.41 N/A N/A

1 L3 0.18 0.26 0.24 0.17 N/A N/A > 200 > 200 > 200
 0.36 N/A N/A

2 L1 N/A N/A N/A 0.40 N/A N/A > 200 > 200 > 200
 0.61 N/A N/A

2 L2 0.54 0.48 0.47 0.31 N/A N/A > 200 > 200 > 200
 0.40 N/A N/A

2 L3 N/A N/A N/A 0.42 N/A N/A > 200 > 200 > 200
 0.67 N/A N/A

3 L1 0.65 0.62 0.59 0.36 N/A N/A > 200 > 200 > 200
 0.57 N/A N/A

3 L2 0.47 0.45 0.51 0.23 N/A N/A > 200 > 200 > 200
 0.44 N/A N/A

3 L3 N/A N/A N/A 0.43 N/A N/A > 200 > 200 > 200
 0.63 N/A N/A

4 L1 0.88 0.82 0.78 0.25 N/A N/A > 200 > 200 > 200
 0.47 N/A N/A

4 L2 N/A N/A N/A 0.39 N/A N/A > 200 > 200 > 200
 0.60 N/A N/A

4 L3 N/A N/A N/A 0.35 N/A N/A > 200 > 200 > 200
 0.58 N/A N/A

5 L1 N/A N/A N/A 0.29 N/A N/A > 200 > 200 > 200
 0.57 N/A N/A

5 L2 N/A N/A N/A 0.30 N/A N/A > 200 > 200 > 200
 0.54 N/A N/A

5 L3 N/A N/A N/A 0.31 N/A N/A > 200 > 200 > 200
 0.55 N/A N/A

6 L1 N/A N/A N/A 0.37 N/A N/A > 200 > 200 > 200
 0.58 N/A N/A

6 L2 0.51 0.49 0.52 0.25 N/A N/A > 200 > 200 > 200
 0.48 N/A N/A

6 L3 0.78 0.81 0.77 0.23 N/A N/A > 200 > 200 > 200
 0.52 N/A N/A

7 L1 N/A N/A N/A 0.92 N/A N/A > 200 > 200 > 200
 1.13 N/A N/A

7 L2 N/A N/A N/A 0.88 N/A N/A > 200 > 200 > 200
 1.02 N/A N/A

7 L3 N/A N/A N/A 1.01 N/A N/A > 200 > 200 > 200
 1.24 N/A N/A

8 L1 N/A N/A N/A 0.79 N/A N/A > 200 > 200 > 200
 0.95 N/A N/A

8 L2 0.40 0.39 0.38 0.22 N/A N/A > 200 > 200 > 200
 0.52 N/A N/A

8 L3 N/A N/A N/A 0.17 N/A N/A > 200 > 200 > 200
 0.32 N/A N/A

TESTED BY
Name
(CAPITALS): ANDREW RUSSELL Position: Engineer

Date of
Signature: 16/11/2009
testing:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 19 of 21
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED
TO BE COMPLETED IN EVERY CASE
DIRECTLY TO THE ORIGIN OF THE INSTALLATION
Location of distribution board: Supply to distribution No of Nominal
MCCB Panel distribution board 3 400 V
Lift Motor Room board is from: phases: Voltage:
Overcurrent protective device for the Associated RCD
N/A
distribution circuit: (if any) BS(EN):
Distribution board designation:
Type RCD No
Lift DB
BS(EN):
60947-2 MCCB Rating: 100 A
of poles:
N/A RCD ln: N/A mA

CIRCUIT DETAILS
Circuit

permitted by BS7671

permitted by BS7671
Overcurrent protective

Max disconnect time


conductors: RCD
devices
csa

Reference Method

Maximum Zs
Circuit number

Type of wiring

points served
Circuit designation

Operating
Capacity
Type No
Number of
and phase

current
Live cpc BS(EN)

Rating
mm2 mm2 s A kA mA 
1 L1 Lift 1 D B 1 10 10 5 3871 D 32 10 N/A 0.36

1 L2 Lift 1 D B 1 10 10 5 3871 D 32 10 N/A 0.36

1 L3 Lift 1 D B 1 10 10 5 3871 D 32 10 N/A 0.36

2 L1 Lift 2 D B 1 10 10 5 3871 D 32 10 N/A 0.36

2 L2 Lift 2 D B 1 10 10 5 3871 D 32 10 N/A 0.36

2 L3 Lift 2 D B 1 10 10 5 3871 D 32 10 N/A 0.36

3 L1 Responsibility of lift company N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

3 L2 Responsibility of lift company N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

3 L3 Responsibility of lift company N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

4 L1 Responsibility of lift company N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

4 L2 Responsibility of lift company N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

4 L3 Responsibility of lift company N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

CODES FOR TYPE OF WIRING


A: PVC/PVC cables D: PVC cables in metallic trunking G: XLPE/SWA cables
B: PVC cables in metallic conduit E: PVC cables in non-metallic trunking H: Mineral-insulated cables
C: PVC cables in non-metallic conduit F: PVC/SWA cables O - Other:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 20 of 21
CHARACTERISTICS AT THIS D.B. DETAILS OF TEST INSTRUMENTS
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT Test Instruments (serial numbers) used:
CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION Earth fault loop
N/A RCD: N/A
 Confirmation of supply polarity impedance:
Insulation
Zs: 0.27  Operating times At ln: n/a ms Resistance: N/A Other: N/A
of associated RCD
lpf: 0.88 kA (if any) At 5ln: n/a ms Continuity: N/A Other: N/A

TEST RESULTS
Insulation resistance RCD Operating
Circuit impedances ohms Maximum
(record lower or lowest value) times
measured
All circuits earth fault
Ring final circuits only
Circuit number

(one column to be Polarity loop


(measured end to end)
completed) Line/ Line/ Line/ Neutral/ impedance
and phase

Line Neutral Earth Earth At ln At 5 ln


Zs
r1 rn r2 R1+R2 R2
(Line) (Neutral) (cpc) M M M M   ms ms
1 L1 N/A N/A N/A 0.01 N/A >200 > 200 > 200 > 200
 0.26 N/A N/A

1 L2 N/A N/A N/A 0.01 N/A >200 > 200 > 200 > 200
 0.27 N/A N/A

1 L3 N/A N/A N/A 0.01 N/A >200 > 200 > 200 > 200
 0.26 N/A N/A

2 L1 N/A N/A N/A 0.03 N/A >200 > 200 > 200 > 200
 0.30 N/A N/A

2 L2 N/A N/A N/A 0.03 N/A >200 > 200 > 200 > 200
 0.26 N/A N/A

2 L3 N/A N/A N/A 0.03 N/A >200 > 200 > 200 > 200
 0.29 N/A N/A

3 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

3 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

3 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

4 L1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

4 L2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

4 L3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

TESTED BY
Name
(CAPITALS): ANDREW RUSSELL Position: Engineer

Date of
Signature: 16/11/2009
testing:

This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 5458 Page: 21 of 21
ELECTRICAL INSTALLATION CERTIFICATE

GUIDANCE FOR RECIPIENT (to be appended to the Certificate)

This safety Certificate has been issued to confirm that the electrical installation work to which it
relates has been designed, constructed and inspected and tested in accordance with British Standard
7671 (as amended) (The IEE Wiring Regulations).

You should have received an original Certificate and the contractor should have retained a duplicate
Certificate. If you were the person ordering the work, but not the user of the installation, you should
pass this Certificate, or a full copy of it including the schedules, immediately to the user.

The 'original' Certificate should be retained in a safe place and be shown to any person inspecting or
undertaking further work on the electrical installation in the future. If you later vacate the property,
this Certificate will demonstrate to the new owner that the electrical installation complied with the
requirements of British Standard 7671 at the time the certificate was issued. The Construction
(Design and Management) Regulations require that for a project covered by those regulations, a copy
of this Certificate, together with schedules is included in the project health and safety documentation.

For safety reasons, the electrical installation will need to be inspected at appropriate intervals by a
competent person. The maximum time interval recommended before the next inspection it stated on
Page 1 under 'Next Inspection'.

This Certificate is intended to be issued only for a new electrical installation or new new work
associated with an alteration or addition to an existing installation. It should not have been issued for
the inspection of an existing electrical installation. A 'Periodic Inspection Report' should be issued for
such a periodic inspection.

This Certificate is only valid if a Schedule of Inspections and Schedule of Test Results are appended.

Anda mungkin juga menyukai