AES SONEL

Dossier ralis entre janvier et fevrier 2013 par :



SECEL BP : 15685 Douala
T/ : 33 43 88 64 fax : 33 43 74 93
E-mail : infodla@secelgroup.com




RAPPORT DE MISE A DISPOSITION DUN EXPERT HP
POUR LAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 1 sur 77

1

SOMMAIRE
I. Cadre du travail ................................................................................................................ 2
II. DEMARCHE ........................................................................................................................... 2
III. COLLECTE DES DONNEES ......................................................................................... 3
Serveur HP PROLIANT dl320s G1, adresse IP : 10.250.90.4 .................. 3
Serveur HP PROLIANT dl360 G3, adresse IP : 10.250.90.15 ................ 12
Serveur HP PROLIANT dl360 G5, adresse IP : 10.250.10.68 ................ 16
Serveur HP PROLIANT dl380 G5, adresse IP : 10.250.90.94 ................ 27
Serveur HP PROLIANT dl380 G5, adresse IP : 10.250.90.133 ............. 41
Serveur HP PROLIANT dl580 G2, adresse IP : 10.250.90.117 ............. 54
Serveur HP PROLIANT dl580 G3, adresse IP : 10.250.90.58 ................ 57
IV. ANALYSE DES DONNEES ......................................................................................... 64
Serveur HP PROLIANT dl320s G1, adresse IP : 10.250.90.4 ................ 66
Serveur HP PROLIANT dl360 G3, adresse IP : 10.250.90.15 ................ 68
Serveur HP PROLIANT dl360 G5, adresse IP : 10.250.10.68 ................ 69
Serveur HP PROLIANT dl380 G5, adresse IP : 10.250.90.94 ................ 70
Serveur HP PROLIANT dl380 G5, adresse IP : 10.250.90.133 ............. 71
Serveur HP PROLIANT dl580 G2, adresse IP : 10.250.90.117 ............. 72
V. CONCLUSION .................................................................................................................... 75
VI. RECOMMANDATIONS ................................................................................................ 76

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 2 sur 77

2
I. Cadre du travail
La DSI de AES Sonel a enregistr la perte dune vingtaine de disque dur, sur les Serveurs du
Datacenter durant lanne 2012.
Nous avons t sollicit pour dtermin la cause profonde de ces pannes rptition et propose des
solutions pour que cela narrive plus lavenir

II. DEMARCHE
La dmarche que nous avons adopte pour mener bien ce travail est la suivante
1. Collecte des donnes sur des chantillons de serveurs (non critiques) ayant enregistr ou non
des panne (dfauts dalimentation lectrique, temprature interne, diffrentes alertes
systmes, dure de fonctionnement des disques dur, firmware des peripheriques)
Discussion avec le personnel de la DSI sur dventuels incident survenu dans le datacenter
2. Analyse des donnes collectes pour identifier les vnements de nature a favorises les
pannes des disques durs , Comparaison des donnes aux standards recommands par le
constructeur HP, Analyse des carts
3. Conclusion
4. Recommandations


RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 3 sur 77

3

III. COLLECTE DES DONNEES
Les donnes collectes sur un chantillon de serveurs installs au DATACENTER.
Nous vous prsentons ci-dessous pour chacun des serveurs de lchantillon, un extrait des donnes
collectes
a. DONNEES SERVEURS

Serveur HP PROLIANT dl320s G1, adresse IP : 10.250.90.4
HP Insight Diagnostics Version 8.1.5.2890A
Computer Name: SONL01FS02PR
Overview
System
Product Name ProLiant DL320s G1
Serial Number USE826N230
Processor Package 1 (Socket 1, Core = 2) Intel Xeon Processor @ 2.66 Ghz
Operating system environment Microsoft(R) Windows(R) Server 2003, Standard Edition, Service Pack 1 (Build 3790)
Total memory 1024 Mbytes
Board 0
DIMM 1 ( DDR ) 1024 Mbytes (667 MHz)
DIMM 2 Not Installed
DIMM 3 Not Installed
DIMM 4 Not Installed
ECC memory installed Yes
Hardware PAE enabled No
Serial presence detect (SPD) information - DIMM 1
Memory type SDRAM DDR2
DIMM Description SPS-DIMM 1GB PC2-5300
Spare Part Number 432930-001
Single-Bit Threshold Exceeded Status No DIMM errors detected
Multi-Bit Status No DIMM errors detected
Single-Bit Threshold Count 0
Multi-Bit Count 0
Storage
Array Controller, HP P400, Slot 1 HP P400
Model HP P400
Firmware 5.20
Configured logical drives 3
Total Memory Size 512 Mbytes
Installed Memory 512 Mbytes
Usable Cache RAM 464 Mbytes
Battery 1 FAILED TO RECHARGE

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 4 sur 77

4
Backplane Model HP DL320s
Backplane Revision 1.20
Serial Number P61630K9SW31RO
PCI Slot Number 1
World Wide Name 5001438002149E90
BIOS boot device order 3
Logical Volume 0, Controller Slot 1 Bus 0 32.2 Gbytes RAID 1
Status Code 0
Status Description OK
Model HP LOGICAL VOLUME
Firmware 5.20
Capacity 32.2 Gbytes
Device Path \\.\SCSI3:
Volume ID 0
Fault Tolerance RAID 1
Logical Drive Parameters
Controller Drive Count 12
Volume Drive Count 2
Drive Parameter Table
Stripe Size (physical blocks) 256
Logical Volume 1, Controller Slot 1 Bus 0 5.4 Gbytes RAID 1
Status Code 0
Status Description OK
Model HP LOGICAL VOLUME
Firmware 5.20
Capacity 5.4 Gbytes
Device Path \\.\SCSI3:
Volume ID 0
Fault Tolerance RAID 1
Logical Drive Parameters
Controller Drive Count 12
Volume Drive Count 2
Drive Parameter Table
Stripe Size (physical blocks) 256
Physical Hard Drive 1, Controller Slot 1 250.1 Gbytes - ATA GB0250EAFJF
Model ATA GB0250EAFJF
Firmware HPG6
Capacity 250.1 Gbytes
Controller Array Controller, HP P400, Slot 1
Serial Number 9SF0SDJS
Temperature Not available
Cable Configuration connector is unknown
Connector 1I
Enclosure Number 1
Enclosure Bay 1
Drive type SATA Hard Disk
Negotiated link rate 1.5 Gbps

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 5 sur 77

5
Read Errors Hard 0000004f
Read Errors Retry Recovered 00000000
Write Errors Hard 00000000
Write Errors Retry Recovered 00000000
Predictive Failure Errors 00000000
Drive Present and Operational Yes
Sectors Written 00000002ea2ffcf3
Physical Hard Drive 2, Controller Slot 1 250.1 Gbytes - ATA GB0250C8045
Model ATA GB0250C8045
Firmware HPG1
Capacity 250.1 Gbytes
Controller Array Controller, HP P400, Slot 1
Serial Number 9SF0BLNR
Temperature Not available
Cable Configuration connector is unknown
Connector 1I
Enclosure Number 1
Enclosure Bay 2
Drive type SATA Hard Disk
Negotiated link rate 1.5 Gbps
Read Errors Hard 00000000
Read Errors Retry Recovered 00000000
Write Errors Hard 00000000
Write Errors Retry Recovered 00000000
Predictive Failure Errors 00000000
Drive Present and Operational Yes
Sectors Written 00000019da331a7f
Logical Volume 2, Controller Slot 1 Bus 0 2000.2 Gbytes ADG RAID (INTERIM RECOVERY)
Status Code 3
Status Description INTERIM RECOVERY
Model HP LOGICAL VOLUME
Firmware 5.20
Capacity 2000.2 Gbytes
Device Path \\.\SCSI3:
Volume ID 3
Fault Tolerance ADG RAID
Logical Drive Parameters
Controller Drive Count 12
Volume Drive Count 10
Drive Parameter Table
Stripe Size (physical blocks) 32
Physical Hard Drive 3, Controller Slot 1 250.1 Gbytes - ATA GB0250C8045
Model ATA GB0250C8045
Firmware HPG1
Capacity 250.1 Gbytes
Controller Array Controller, HP P400, Slot 1
Serial Number 9SF0B83E

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 6 sur 77

6
Temperature Not available
Cable Configuration connector is unknown
Connector 1I
Enclosure Number 1
Enclosure Bay 3
Drive type SATA Hard Disk
Negotiated link rate 1.5 Gbps
Read Errors Hard 00000000
Read Errors Retry Recovered 00000000
Write Errors Hard 00000000
Write Errors Retry Recovered 00000000
Predictive Failure Errors 00000000
Drive Present and Operational Yes
Sectors Written 000000011284ee18
Physical Hard Drive 4, Controller Slot 1 250.1 Gbytes - ATA GB0250C8045
Model ATA GB0250C8045
Firmware HPG1
Capacity 250.1 Gbytes
Controller Array Controller, HP P400, Slot 1
Serial Number 9SF0A4SQ
Temperature Not available
Cable Configuration connector is unknown
Connector 1I
Enclosure Number 1
Enclosure Bay 4
Drive type SATA Hard Disk
Negotiated link rate 1.5 Gbps
Read Errors Hard 00000000
Read Errors Retry Recovered 00000000
Write Errors Hard 00000000
Write Errors Retry Recovered 00000000
Predictive Failure Errors 00000000
Drive Present and Operational Yes
Sectors Written 00000001155bad6f
Physical Hard Drive 5, Controller Slot 1 250.1 Gbytes - ATA GB0250C8045
Model ATA GB0250C8045
Firmware HPG1
Capacity 250.1 Gbytes
Controller Array Controller, HP P400, Slot 1
Serial Number 9SF0B8AW
Temperature Not available
Cable Configuration connector is unknown
Connector 1I
Enclosure Number 1
Enclosure Bay 6
Drive type SATA Hard Disk
Negotiated link rate 1.5 Gbps

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 7 sur 77

7
Read Errors Hard 00000000
Read Errors Retry Recovered 00000000
Write Errors Hard 00000000
Write Errors Retry Recovered 00000000
Predictive Failure Errors 00000000
Drive Present and Operational Yes
Sectors Written 00000001137d1ff7
Physical Hard Drive 6, Controller Slot 1 250.1 Gbytes - ATA GB0250EAFJF
Model ATA GB0250EAFJF
Firmware HPG6
Capacity 250.1 Gbytes
Controller Array Controller, HP P400, Slot 1
Serial Number 9SF0SEFE
Temperature Not available
Cable Configuration connector is unknown
Connector 1I
Enclosure Number 1
Enclosure Bay 7
Drive type SATA Hard Disk
Negotiated link rate 1.5 Gbps
Read Errors Hard 00000007
Read Errors Retry Recovered 00000000
Write Errors Hard 00000000
Write Errors Retry Recovered 00000000
Predictive Failure Errors 00000000
Drive Present and Operational Yes
Sectors Written 0000000743ca1d6d
Physical Hard Drive 7, Controller Slot 1 250.1 Gbytes - ATA GB0250C8045
Model ATA GB0250C8045
Firmware HPG1
Capacity 250.1 Gbytes
Controller Array Controller, HP P400, Slot 1
Serial Number 9SF0B7V5
Temperature Not available
Cable Configuration connector is unknown
Connector 1I
Enclosure Number 1
Enclosure Bay 8
Drive type SATA Hard Disk
Negotiated link rate 1.5 Gbps
Read Errors Hard 00000000
Read Errors Retry Recovered 00000000
Write Errors Hard 00000000
Write Errors Retry Recovered 00000000
Predictive Failure Errors 00000000
Drive Present and Operational Yes
Sectors Written 000000011b5521fe

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 8 sur 77

8
Physical Hard Drive 8, Controller Slot 1 250.1 Gbytes - ATA GB0250EAFJF
Model ATA GB0250EAFJF
Firmware HPG6
Capacity 250.1 Gbytes
Controller Array Controller, HP P400, Slot 1
Serial Number 9SF0S089
Temperature Not available
Cable Configuration connector is unknown
Connector 1I
Enclosure Number 1
Enclosure Bay 9
Drive type SATA Hard Disk
Negotiated link rate 1.5 Gbps
Read Errors Hard 00000000
Read Errors Retry Recovered 00000000
Write Errors Hard 00000000
Write Errors Retry Recovered 00000000
Predictive Failure Errors 00000000
Drive Present and Operational Yes
Sectors Written 00000005f543cc6b
Physical Hard Drive 9, Controller Slot 1 250.1 Gbytes - ATA GB0250C8045
Model ATA GB0250C8045
Firmware HPG1
Capacity 250.1 Gbytes
Controller Array Controller, HP P400, Slot 1
Serial Number 9SF0BB29
Temperature Not available
Cable Configuration connector is unknown
Connector 1I
Enclosure Number 1
Enclosure Bay 11
Drive type SATA Hard Disk
Negotiated link rate 1.5 Gbps
Read Errors Hard 0000003a
Read Errors Retry Recovered 00000000
Write Errors Hard 00000000
Write Errors Retry Recovered 00000000
Predictive Failure Errors 00000000
Drive Present and Operational Yes
Sectors Written 0000000112ff056d
Physical Hard Drive 10, Controller Slot 1 250.1 Gbytes - ATA GB0250C8045
Model ATA GB0250C8045
Firmware HPG1
Capacity 250.1 Gbytes
Controller Array Controller, HP P400, Slot 1
Serial Number 9SF09QZ8
Temperature Not available

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 9 sur 77

9
Cable Configuration connector is unknown
Connector 1I
Enclosure Number 1
Enclosure Bay 12
Drive type SATA Hard Disk
Negotiated link rate 1.5 Gbps
Read Errors Hard 0000014b
Read Errors Retry Recovered 00000000
Write Errors Hard 00000000
Write Errors Retry Recovered 00000000
Predictive Failure Errors 00000000
Drive Present and Operational Yes
Sectors Written 0000000112c6d5f9
FibreChannel Controller, Slot 2 ISP 2432 Fibre Channel Adapter
Model ISP 2432 Fibre Channel Adapter
Number of SCSI Channels reported by controller 1
Board ID 7040103Ch
PCI Bus 10
PCI Device Number 0
PCI Function Number 0
PCI Slot Number 2
Slot 2
BIOS boot device order 4
USB Optical Drive 1 Optiarc CDRWDVD CRX890A
Type DVD-ROM
Model Optiarc CDRWDVD CRX890A
Firmware PH52
Logical Disks
C: Logical Disk 1 ~ 32.21GB
Volume Name System
File System NTFS
Size (Byte) 32207564800
Free Space (Byte) 9740570624
E: Logical Disk 2 ~ 2000.20GB
Volume Name DATA
File System NTFS
Size (Byte) 2000198881280
Free Space (Byte) 179364253696

HP Insight Diagnostics Version 8.1.5.2890A
Computer Name: SONL01FS02PR
Severity Class Last Update Initial Update Count Description
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST 5/09/2010 5/09/2010 1 Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 10 sur 77

10
Severity Class Last Update Initial Update Count Description
11:24 11:24 system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185
Caution POST
5/09/2010
11:24
5/09/2010
11:24
1
Post Error - Message: 1610-Temperature violation detected Waiting 5 minutes for
system to cool - Error: 185


RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 11 sur 77

11

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 12 sur 77

12

Serveur HP PROLIANT dl360 G3, adresse IP : 10.250.90.15
ACU Version 8.50.5.0
Diagnostic Module Version 5.2.43.0
INFOMGR Version 5.9.25.0
Time Generated Tuesday January 08, 2013 2:57:10PM

Device Summary:
Smart Array 5i in Embedded Slot

Consolidated Error Report:
Controller: Smart Array 5i in Embedded Slot
Device: Physical Drive 1:0
Message: Physical Drive State: Predictive failure. This physical drive is predicted to fail soon.

Report for Smart Array 5i in Embedded Slot
------------------------------------------

Smart Array 5i in Embedded Slot : Device Error Report

Device Severity Error
------------------ -------- ----------------------------------------------------------------------------------------
Physical Drive 1:0 Warning Physical Drive State: Predictive failure. This physical drive is predicted to fail soon.


Smart Array 5i in Embedded Slot : Identify Controller

Configured Logical Drives 1 (0x01)
Configuration Signature 0xa00005ac
RAM Firmware Revision 2.66
ROM Firmware Revision 2.66
Hardware Revision 0x01
Boot Block Revision 0.18
Drive Present Map 0x00000003
Position Device Status
-------- ------------------ -------------
0 Physical Drive 1:0 Informational
1 Physical Drive 1:1 Informational
Device Severity Error
------------------ -------- ----------------------------------------------------------------------------------------
Physical Drive 1:0 Warning Physical Drive State: Predictive failure. This physical drive is predicted to fail soon.

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 13 sur 77

13


Smart Array 5i in Embedded Slot : Storage Enclosure at Box 1 : Drive Cage on Port J1 : Physical Drive 1:0 : Physical Drive Status
SCSI Bus 0 (0x00)
SCSIID 0 (0x00)
Block Size 512 Bytes Per Block (0x0200)
Total Blocks 72.8 GB (0x087aa6c0)
Reserved Blocks 0x00000440
Drive Model COMPAQ BD07285A25
Drive Serial Number 3HZ9QTJG00007522FEZG
Drive Firmware Revision HPB8
SCSI Inquiry Bits 0x3e
Compaq Drive Stamped Stamped For Monitoring (0x01)
Last Failure Reason Hot Removed (0x14)
Device Flags 0xcd
Position Device Flag Status
-------- ----------------------------- -------------
0 Drive Present And Operational Informational
2 Wide SCSI Transfers Enabled Informational
3 Synchronous Transfers Enabled Informational
6 Ultra SCSI Transfers Enabled Informational
7 Ultra2 SCSI Transfers Enabled Informational

More Device Flags 0x2f
Position Device Flag Status
-------- -------------------------------------------------------------------------------------- -------------
0 SMART Predictive Failure Supported Informational
1 SMART Predictive Failure Errors Are Recorded In The Factory MP Data For This Drive Warning
2 SMART Predictive Failure Is Enabled Informational
3 SMART Predictive Failure Errors Are Recorded In The Since Power MP Data For This Drive Warning
4 Device Attached To Internal Connector Informational
5 Configured Data Drive Informational

SCSI Lun 0x00
Yet More Device Flags 0x95
Position Device Flag Status
-------- --------------------------------------- -------------
0 DT Clocking Mode Informational
2 DT And ST Clocking Supported Informational
4 Supports Packetized SCSI Informational
7 Drive Write Cache Setting Is Changeable Informational
Smart Array 5i in Embedded Slot : Storage Enclosure at Box 1 : Drive Cage on Port J1 : Physical Drive 1:1 : Physical Drive Status

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 14 sur 77

14

SCSI Bus 0 (0x00)
SCSIID 1 (0x01)
Block Size 512 Bytes Per Block (0x0200)
Total Blocks 72.8 GB (0x087aa6c0)
Reserved Blocks 0x00000440
Drive Model COMPAQ BF0728B26A
Drive Serial Number 3LQ0D7Z8000097281C78
Drive Firmware Revision HPB9
SCSI Inquiry Bits 0x32
Compaq Drive Stamped Not Stamped For Monitoring (0x00)
Last Failure Reason Timeout (0x07)
Device Flags 0xcd
Position Device Flag Status
-------- ----------------------------- -------------
0 Drive Present And Operational Informational
2 Wide SCSI Transfers Enabled Informational
3 Synchronous Transfers Enabled Informational
6 Ultra SCSI Transfers Enabled Informational
7 Ultra2 SCSI Transfers Enabled Informational

More Device Flags 0x25
Position Device Flag Status
-------- ------------------------------------- -------------
0 SMART Predictive Failure Supported Informational
2 SMART Predictive Failure Is Enabled Informational
4 Device Attached To Internal Connector Informational
5 Configured Data Drive Informational

SCSI Lun 0x00
Yet More Device Flags 0x95
Position Device Flag Status
-------- --------------------------------------- -------------
0 DT Clocking Mode Informational
2 DT And ST Clocking Supported Informational
4 Supports Packetized SCSI Informational
7 Drive Write Cache Setting Is Changeable Informational

HP ProLiant Integrated Management Log Viewer: SONL01SMS01PR

Description,Class,Code,Severity,Count,Update Time,Initial Time

POST Error: 1789-Drive Not Responding, Physical Drive,POST Messages,1,Caution,1,23/06/2004 00:01,23/06/2004 00:01
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,23/06/2004 00:01,23/06/2004 00:01

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 15 sur 77

15
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,23/06/2004 01:02,23/06/2004 01:02
POST Error: 1786-Drive Array Recovery Needed,POST Messages,1,Caution,1,23/02/2006 04:46,23/02/2006 04:46

POST Error: 1786-Drive Array Recovery Needed,POST Messages,1,Caution,1,20/07/2006 03:03,20/07/2006 03:03

POST Error: 1786-Drive Array Recovery Needed,POST Messages,1,Caution,1,14/01/2007 04:28,14/01/2007 04:28

POST Error: 1786-Drive Array Recovery Needed,POST Messages,1,Caution,1,24/04/2007 16:09,24/04/2007 16:09

POST Error: 1786-Drive Array Recovery Needed,POST Messages,1,Caution,1,06/09/2007 20:09,06/09/2007 20:09
POST Error: 1778-Drive Array Resuming Automatic Data Recovery Process,POST Messages,1,Caution,4,06/09/2007 20:56,06/09/2007
20:25
POST Error: 1786-Drive Array Recovery Needed,POST Messages,1,Caution,2,06/09/2007 21:58,06/09/2007 21:06
Corrected Memory Error threshold exceeded (System Memory, Memory Module 3),Main Memory,1,Caution,2,06/09/2007
21:15,06/09/2007 21:09
POST Error: 1778-Drive Array Resuming Automatic Data Recovery Process,POST Messages,1,Caution,1,06/09/2007 21:11,06/09/2007
21:11
POST Error: 1778-Drive Array Resuming Automatic Data Recovery Process,POST Messages,1,Caution,5,06/09/2007 22:29,06/09/2007
22:01
Network Adapter Link Down (Slot 0, Port 2),Network Adapter,2,Critical,11,07/01/2013 11:27,06/09/2007 22:27
Corrected Memory Error threshold exceeded (System Memory, Memory Module 3),Main Memory,1,Caution,1,06/09/2007
22:30,06/09/2007 22:30
POST Error: 1786-Drive Array Recovery Needed,POST Messages,1,Caution,1,06/09/2007 23:27,06/09/2007 23:27
Corrected Memory Error threshold exceeded (System Memory, Memory Module 3),Main Memory,1,Caution,3,06/09/2007
23:50,06/09/2007 23:27
POST Error: 1778-Drive Array Resuming Automatic Data Recovery Process,POST Messages,1,Caution,2,06/09/2007 23:49,06/09/2007
23:41
POST Error: 1786-Drive Array Recovery Needed,POST Messages,1,Caution,1,07/09/2007 16:18,07/09/2007 16:18

POST Error: 1786-Drive Array Recovery Needed,POST Messages,1,Caution,1,30/05/2008 15:39,30/05/2008 15:39

POST Error: 1786-Drive Array Recovery Needed,POST Messages,1,Caution,1,30/05/2008 16:40,30/05/2008 16:40

Drive Array Device Failure (Slot 0, Bus 1, Bay 0),Drive Array Subsystem,2,Critical,1,02/06/2008 09:42,02/06/2008 09:42
Operating System failure (BugCheck, STOP: 0x000000F4 (0x00000003, 0x8C3A9878, 0x8C3A99DC, 0x8094C6E6)),Operating
System,1,Critical,1,02/06/2008 09:42,02/06/2008 09:42
POST Error: 1779-Drive Array Controller Detects Replacement Drives,POST Messages,1,Caution,3,02/06/2008 09:57,02/06/2008 09:44
POST Error: 301-Keyboard Error,POST Messages,1,Caution,1,02/06/2008 09:56,02/06/2008 09:56

POST Error: 1789-Drive Not Responding, Physical Drive,POST Messages,1,Caution,2,02/06/2008 10:37,02/06/2008 10:33
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,02/06/2008 10:37,02/06/2008 10:37
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,02/06/2008 11:17,02/06/2008 11:17
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,10/06/2008 11:45,10/06/2008 11:45
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,10/06/2008 15:42,10/06/2008 15:42
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,29/07/2008 21:50,29/07/2008 21:50
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,14/08/2008 11:42,14/08/2008 11:42
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,21/08/2008 15:14,21/08/2008 15:14
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,11/09/2008 16:07,11/09/2008 16:07
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,2,26/09/2008 15:57,26/09/2008 15:09
POST Error: 1787-Drive Array Operating in Interim Recovery Mode,POST Messages,1,Caution,1,07/11/2008 15:06,07/11/2008 15:06
Drive Array Device Failure (Slot 0, Bus 1, Bay 1),Drive Array Subsystem,2,Critical,1,07/01/2013 11:22,07/01/2013 11:22




RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 16 sur 77

16

Serveur HP PROLIANT dl360 G5, adresse IP : 10.250.10.68
HP Insight Diagnostics Version 8.1.5.2890A
Nom de l'ordinateur: SONL01CTX01PR
Prsentation
Systme
Nom du produit ProLiant DL360 G5
Numro de srie CZJ849A20B
Package de processeurs 1 (Connecteur 1,
Cur = 4)
Intel Xeon Processeur @ 2.33 Ghz
Environnement du systme d`exploitation Microsoft(R) Windows(R) Server 2003, Enterprise Edition, Service Pack 2 (Build 3790)
Mmoire totale 2048 Mgaoctets
Carte 0
DIMM 1A ( DDR2-FBD ) 1024 Mgaoctets (667 MHz)
DIMM 2C Non install
DIMM 3A ( DDR2-FBD ) 1024 Mgaoctets (667 MHz)
DIMM 4C Non install
DIMM 5B Non install
DIMM 6D Non install
DIMM 7B Non install
DIMM 8D Non install
Mmoire ECC installe Oui
PAE matriel activ Non
Informations SPD (Serial Presence Detect) - DIMM 1
Type de mmoire DDR2 SDRAM FB-DIMM
Description DIMM
Numro de pice de rechange
Dpassement du seuil de bit unique -
tat
Aucune erreur DIMM dtecte
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 0
Nombre de bits multiples 0
Informations SPD (Serial Presence Detect) - DIMM 3
Type de mmoire DDR2 SDRAM FB-DIMM
Description DIMM
Numro de pice de rechange
Dpassement du seuil de bit unique -
tat
Aucune erreur DIMM dtecte
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 0
Nombre de bits multiples 0
Units de stockage
Disque optique 1 HL-DT-ST DVDRAM GSA-T40L at Principal/Matre
Type DVD+R
Capacit Support non install
Connecteur Principal/Matre
Contrleur RAID, HP E200i, Connecteur 0 HP E200i

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 17 sur 77

17
Modle HP E200i
Microprogramme 1.78
Units logiques configures 2
Taille totale de la mmoire 128 Mgaoctets
Mmoire installe 128 Mgaoctets
Carte mmoire RAM utilisable 96 Mgaoctets
Batterie 1 OK
Numro de srie PR8BMP5520
Numro de connecteur PCI 0
Dsignation internationale 5001438003876BD8
BIOS boot device order 1
Volume logique 0, Contrleur Connecteur 0 Bus 0 146.8 Gigaoctets RAID 0
Code d`tat 0
Description de l`tat OK
Modle HP LOGICAL VOLUME
Microprogramme 1.78
Capacit 146.8 Gigaoctets
Chemin du priphrique \\.\SCSI2:
ID du volume 0
Tolrance aux dfaillances RAID 0
Paramtres d`unit logique
Nombre d`units de contrleur 2
Nombre d`units de volume 1
Table des paramtres d`units
Taille de stripe (blocs physiques) 256
Disque dur physique 1, Contrleur Connecteur 0 146.8 Gigaoctets 10K RPM - HP DG146BB976
Modle HP DG146BB976
Microprogramme HPDC
Capacit 146.8 Gigaoctets
Contrleur Contrleur RAID, HP E200i, Connecteur 0
Vitesse de rotation 10K RPM
Numro de srie 3NM7Q39200009913LSY7
Temprature 30 Degrees Celsius
Configuration du cble
Chemin de donnes 16 bits sur un cble avec 16 ID SCSI pris
en charge
Connecteur 1I
Numro de botier 1
Baie de botier 1
Type d`unit Disque dur SAS
Vitesse de liaison ngocie 3 Gbps
Erreurs de lecture graves 00000000
Erreurs de lecture (nouvel essai russi) 00000000
Erreurs d`criture graves 00000001
Erreurs d`criture (nouvel essai russi) 00000001
Erreurs de panne prdictive 00001fa7
Unit prsente et oprationnelle Oui
Secteurs crits 000000045e10bb07

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 18 sur 77

18
Volume logique 1, Contrleur Connecteur 0 Bus 0 146.8 Gigaoctets RAID 0
Code d`tat 0
Description de l`tat OK
Modle HP LOGICAL VOLUME
Microprogramme 1.78
Capacit 146.8 Gigaoctets
Chemin du priphrique \\.\SCSI2:
ID du volume 0
Tolrance aux dfaillances RAID 0
Paramtres d`unit logique
Nombre d`units de contrleur 2
Nombre d`units de volume 1
Table des paramtres d`units
Taille de stripe (blocs physiques) 256
Disque dur physique 2, Contrleur Connecteur 0 146.8 Gigaoctets 10K RPM - HP DG146BB976
Modle HP DG146BB976
Microprogramme HPDC
Capacit 146.8 Gigaoctets
Contrleur Contrleur RAID, HP E200i, Connecteur 0
Vitesse de rotation 10K RPM
Numro de srie 3NM7PYRD00009913K65H
Temprature 29 Degrees Celsius
Configuration du cble
Chemin de donnes 16 bits sur un cble avec 16 ID SCSI pris
en charge
Connecteur 1I
Numro de botier 1
Baie de botier 2
Type d`unit Disque dur SAS
Vitesse de liaison ngocie 3 Gbps
Erreurs de lecture graves 00000000
Erreurs de lecture (nouvel essai russi) 00000000
Erreurs d`criture graves 00000000
Erreurs d`criture (nouvel essai russi) 00000000
Erreurs de panne prdictive 00000000
Unit prsente et oprationnelle Oui
Secteurs crits 0000000000197a0c
Disques logiques
C: Disque logique 1 ~ 83.89GB
Nom de volume
Systme de fichiers NTFS
Taille (octet) 83888435200
Espace libre (octet) 63354961920
E: Disque logique 2 ~ 62.89GB
Nom de volume DATA
Systme de fichiers NTFS
Taille (octet) 62886047744
Espace libre (octet) 58241765376

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 19 sur 77

19

HP Insight Diagnostics Version 8.1.5.2890A
Nom de l'ordinateur: SONL01CTX01PR
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Repaired Power Supply 8/04/2008 1:58 0/00/00 0:00 2
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Repaired Power Supply 8/04/2008 1:58 0/00/00 0:00 2
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/03/2008 0:00 8/03/2008 0:00 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 8/03/2008 0:00 8/03/2008 0:00 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 8/03/2008 0:01 8/03/2008 0:01 1 Post Error - Message: 1785-Drive Array not Configured - Error: 85
Caution Power Supply 8/03/2008 0:02 8/03/2008 0:02 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/03/2008 0:02 8/03/2008 0:02 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 8/03/2008 0:02 8/03/2008 0:02 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 8/03/2008 0:02 8/03/2008 0:02 1
Post Error - Message: 1794-Drive Array - Array Accelerator Battery
Charge Low - Error: 94
Caution POST 8/04/2008 1:55 8/04/2008 1:55 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 8/04/2008 1:55 8/04/2008 1:55 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 8/04/2008 1:55 8/04/2008 1:55 1
Post Error - Message: 1794-Drive Array - Array Accelerator Battery
Charge Low - Error: 94
Repaired Power Supply 8/04/2008 1:58 8/04/2008 1:58 1
Not Redundant - Chassis Name: - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Failed
Network
Adapter
1/09/2009 13:58 1/07/2009 10:24 7
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 2
Failed
Network
Adapter
1/07/2009 10:45 1/07/2009 10:24 3
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Failed
Network
Adapter
1/07/2009 11:47 1/07/2009 11:31 2
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Repaired
Network
Adapter
1/08/2009 12:21 1/08/2009 11:47 1
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Repaired
Machine
Environment
3/18/2009 0:11 3/18/2009 0:11 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/18/2009 0:11 3/18/2009 0:11 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
3/18/2009 0:12 3/18/2009 0:11 6 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
3/18/2009 0:11 3/18/2009 0:11 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/18/2009 0:11 3/18/2009 0:11 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/18/2009 0:11 3/18/2009 0:11 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/18/2009 0:11 3/18/2009 0:11 1 Auto Shutdown - Cause: Overheat

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 20 sur 77

20
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Repaired
Machine
Environment
3/18/2009 0:12 3/18/2009 0:11 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/18/2009 0:12 3/18/2009 0:11 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/18/2009 0:12 3/18/2009 0:12 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/18/2009 0:12 3/18/2009 0:12 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/18/2009 0:12 3/18/2009 0:12 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/18/2009 0:12 3/18/2009 0:12 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
3/18/2009 0:12 3/18/2009 0:12 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
3/18/2009 0:12 3/18/2009 0:12 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/18/2009 1:48 3/18/2009 0:15 1
Overheat - Chassis Name: - Temp: 41 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 3/18/2009 0:14 3/18/2009 0:14 1
Post Error - Message: 1610-Temperature violation detected Waiting
5 minutes for system to cool - Error: 185
Repaired
Network
Adapter
3/26/2009 21:05 3/26/2009 20:55 1
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Repaired
Machine
Environment
3/29/2009 9:56 3/29/2009 9:56 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:56 3/29/2009 9:56 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
3/29/2009 9:56 3/29/2009 9:56 2 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
3/29/2009 9:56 3/29/2009 9:56 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:56 3/29/2009 9:56 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 10:40 3/29/2009 9:56 2
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
3/29/2009 9:56 3/29/2009 9:56 1 Auto Shutdown - Cause: Overheat
Caution POST 3/29/2009 9:58 3/29/2009 9:58 1
Post Error - Message: 1610-Temperature violation detected Waiting
5 minutes for system to cool - Error: 185
Repaired
Network
Adapter
5/02/2009 11:21 5/02/2009 11:17 1
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Repaired
Machine
Environment
5/26/2009 2:15 5/26/2009 2:15 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:15 5/26/2009 2:15 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
5/26/2009 2:17 5/26/2009 2:15 9 Auto Shutdown - Cause: Temp Abort
Repaired Machine 5/26/2009 2:15 5/26/2009 2:15 1 Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 21 sur 77

21
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Environment Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:15 5/26/2009 2:15 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:16 5/26/2009 2:16 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:16 5/26/2009 2:16 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:16 5/26/2009 2:16 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:16 5/26/2009 2:16 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:16 5/26/2009 2:16 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:16 5/26/2009 2:16 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:16 5/26/2009 2:16 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:16 5/26/2009 2:16 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:17 5/26/2009 2:17 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:17 5/26/2009 2:17 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:17 5/26/2009 2:17 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:17 5/26/2009 2:17 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:17 5/26/2009 2:17 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:17 5/26/2009 2:17 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:34 5/26/2009 2:17 2
Overheat - Chassis Name: - Temp: 41 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
5/26/2009 2:17 5/26/2009 2:17 1 Auto Shutdown - Cause: Overheat
Caution POST 5/26/2009 2:19 5/26/2009 2:19 1
Post Error - Message: 1610-Temperature violation detected Waiting
5 minutes for system to cool - Error: 185
Repaired
Network
Adapter
6/25/2009 19:39 6/25/2009 19:35 1
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Repaired
Network
Adapter
7/11/2009 17:36 7/11/2009 17:32 1
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Repaired
Network
Adapter
8/20/2009 8:48 8/20/2009 8:46 1
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Failed ASR 10/29/2009 10:38
10/29/2009
10:38
1 Reset
Repaired
Machine
Environment
11/05/2009 19:36
11/05/2009
19:36
1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 22 sur 77

22
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
slots - Chassis Port: 0
Repaired
Operating
System
11/05/2009 19:36
11/05/2009
19:36
1 Auto Shutdown - Cause: Overheat
Info
Operating
System
11/05/2009 19:37
11/05/2009
19:36
2 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
11/05/2009 19:37
11/05/2009
19:37
1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
11/05/2009 19:37
11/05/2009
19:37
1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
11/05/2009 20:15
11/05/2009
19:37
2
Overheat - Chassis Name: - Temp: 41 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
11/05/2009 19:37
11/05/2009
19:37
1 Auto Shutdown - Cause: Overheat
Caution POST 11/05/2009 19:38
11/05/2009
19:38
1
Post Error - Message: 1610-Temperature violation detected Waiting
5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
1/09/2010 15:35 1/09/2010 15:35 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
1/09/2010 15:35 1/09/2010 15:35 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
1/09/2010 15:35 1/09/2010 15:35 2 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
1/09/2010 15:35 1/09/2010 15:35 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
1/09/2010 15:35 1/09/2010 15:35 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
1/09/2010 16:45 1/09/2010 15:35 2
Overheat - Chassis Name: - Temp: 41 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
1/09/2010 15:35 1/09/2010 15:35 1 Auto Shutdown - Cause: Overheat
Caution POST 1/09/2010 15:37 1/09/2010 15:37 1
Post Error - Message: 1610-Temperature violation detected Waiting
5 minutes for system to cool - Error: 185
Repaired
Network
Adapter
2/14/2010 12:56 2/14/2010 12:54 1
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Failed
Operating
System
5/06/2010 12:49 5/06/2010 12:49 1
System Crash - Message: BugCheck, STOP: 0x0000008E
(0xC0000005, 0x80929979, 0xB52F4BDC, 0x00000000)
Caution
Machine
Environment
5/09/2010 10:00 5/09/2010 10:00 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
5/09/2010 10:00 5/09/2010 10:00 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/09/2010 11:41 5/09/2010 10:02 1
Overheat - Chassis Name: - Temp: 41 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 5/09/2010 10:01 5/09/2010 10:01 1
Post Error - Message: 1610-Temperature violation detected Waiting
5 minutes for system to cool - Error: 185
Failed
Operating
System
8/01/2010 4:09 8/01/2010 4:09 1
System Crash - Message: BugCheck, STOP: 0x00000024
(0x0019033D, 0xB65B6328, 0xB65B6024, 0xF7174024)
Caution Power Supply 0/00/00 0:00 0/00/00 0:00 5
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/15/2010 0:31 8/15/2010 0:31 1 Post Error - Message: 1615-Power Supply Failure or Power Supply

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 23 sur 77

23
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Unplugged in Bay 2 - Error: 208
Caution POST 8/15/2010 0:31 8/15/2010 0:31 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 8/16/2010 8:34 8/16/2010 8:34 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 8/16/2010 8:34 8/16/2010 8:34 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 8/16/2010 8:34 8/16/2010 8:34 1
Post Error - Message: 1792-Drive Array Reports Valid Data Found
in Array Accelerator - Error: 92
Caution POST 8/16/2010 9:19 8/16/2010 9:19 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 8/16/2010 9:19 8/16/2010 9:19 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 8/20/2010 9:56 8/20/2010 9:56 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/20/2010 9:54 8/20/2010 9:54 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 8/20/2010 9:54 8/20/2010 9:54 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Repaired
Network
Adapter
9/01/2010 14:42 9/01/2010 14:16 1
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Caution Power Supply 1/27/2011 16:26 1/27/2011 16:26 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 1/27/2011 16:22 1/27/2011 16:22 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 1/27/2011 16:22 1/27/2011 16:22 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 1/31/2011 13:24 1/31/2011 13:24 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 1/31/2011 13:20 1/31/2011 13:20 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 1/31/2011 13:20 1/31/2011 13:20 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Failed
Operating
System
1/31/2011 22:12 1/31/2011 22:12 1
System Crash - Message: BugCheck, STOP: 0x000000D0
(0x00000008, 0xD0000002, 0x00000000, 0x80899707)
Caution Power Supply 1/31/2011 22:13 1/31/2011 22:13 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 1/31/2011 22:09 1/31/2011 22:09 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 1/31/2011 22:09 1/31/2011 22:09 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 2/01/2011 7:33 2/01/2011 7:33 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 2/01/2011 7:29 2/01/2011 7:29 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 2/01/2011 7:29 2/01/2011 7:29 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 3/31/2011 13:05 3/31/2011 13:05 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 3/31/2011 13:01 3/31/2011 13:01 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 3/31/2011 13:01 3/31/2011 13:01 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 4/02/2011 15:51 4/02/2011 15:51 1 Post Error - Message: 1615-Power Supply Failure or Power Supply

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 24 sur 77

24
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Unplugged in Bay 2 - Error: 208
Caution POST 4/02/2011 15:51 4/02/2011 15:51 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 6/07/2011 15:50 6/07/2011 15:50 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 6/07/2011 15:50 6/07/2011 15:50 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 6/07/2011 15:50 6/07/2011 15:50 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 7/20/2011 10:21 7/20/2011 10:21 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 7/20/2011 10:21 7/20/2011 10:21 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 7/20/2011 10:21 7/20/2011 10:21 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 8/23/2011 12:13 8/23/2011 12:13 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 8/23/2011 12:13 8/23/2011 12:13 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 8/26/2011 10:30 8/26/2011 10:30 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/26/2011 10:30 8/26/2011 10:30 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 8/26/2011 10:30 8/26/2011 10:30 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 9/20/2011 14:35 9/20/2011 14:35 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 9/20/2011 14:35 9/20/2011 14:35 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 9/20/2011 14:35 9/20/2011 14:35 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 9/28/2011 13:58 9/28/2011 13:18 2
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 9/28/2011 13:19 9/28/2011 13:19 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 9/28/2011 13:19 9/28/2011 13:19 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 9/28/2011 13:58 9/28/2011 13:58 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 9/28/2011 13:58 9/28/2011 13:58 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 9/28/2011 14:23 9/28/2011 14:02 2
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 9/28/2011 14:02 9/28/2011 14:02 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 9/28/2011 14:02 9/28/2011 14:02 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 9/28/2011 14:23 9/28/2011 14:23 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 9/28/2011 14:23 9/28/2011 14:23 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 11/03/2011 9:33 11/03/2011 9:33 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 11/03/2011 9:33 11/03/2011 9:33 1 Post Error - Message: 1615-Power Supply Failure or Power Supply

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 25 sur 77

25
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Unplugged in Bay 2 - Error: 208
Caution POST 11/03/2011 9:33 11/03/2011 9:33 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Repaired
Network
Adapter
11/04/2011 17:32
11/04/2011
17:30
1
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Repaired
Network
Adapter
12/11/2011 18:22
12/11/2011
12:36
4
Link Down - Chassis Name: - Slot: 0 - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 1
Caution Power Supply 12/15/2011 9:27 12/15/2011 9:27 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 12/15/2011 9:26 12/15/2011 9:26 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 12/15/2011 9:26 12/15/2011 9:26 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution Power Supply 6/11/2012 13:05 6/11/2012 13:05 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 6/11/2012 13:05 6/11/2012 13:05 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 6/11/2012 13:05 6/11/2012 13:05 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 6/11/2012 13:05 6/11/2012 13:05 1
Post Error - Message: 1720-S.M.A.R.T. Hard Drive Detects
Imminent Failure - Error: 200
Caution Power Supply 8/14/2012 12:50 8/14/2012 12:50 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/14/2012 12:50 8/14/2012 12:50 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 8/14/2012 12:50 8/14/2012 12:50 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 8/14/2012 12:50 8/14/2012 12:50 1
Post Error - Message: 1720-S.M.A.R.T. Hard Drive Detects
Imminent Failure - Error: 200
Caution Power Supply 8/16/2012 8:15 8/16/2012 8:15 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/16/2012 8:15 8/16/2012 8:15 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 8/16/2012 8:15 8/16/2012 8:15 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 8/16/2012 8:15 8/16/2012 8:15 1
Post Error - Message: 1720-S.M.A.R.T. Hard Drive Detects
Imminent Failure - Error: 200
Caution Power Supply 9/12/2012 9:56 9/12/2012 9:56 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 9/12/2012 9:55 9/12/2012 9:55 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 9/12/2012 9:55 9/12/2012 9:55 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 9/12/2012 9:55 9/12/2012 9:55 1
Post Error - Message: 1720-S.M.A.R.T. Hard Drive Detects
Imminent Failure - Error: 200
Caution Power Supply 1/03/2013 8:48 1/03/2013 8:48 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 1/03/2013 8:47 1/03/2013 8:47 1
Post Error - Message: 1615-Power Supply Failure or Power Supply
Unplugged in Bay 2 - Error: 208
Caution POST 1/03/2013 8:47 1/03/2013 8:47 1
Post Error - Message: Power Supply Solution Not Fully Redundant -
Error: 186
Caution POST 1/03/2013 8:47 1/03/2013 8:47 1
Post Error - Message: 1720-S.M.A.R.T. Hard Drive Detects
Imminent Failure - Error: 200
Info Maintenance 1/08/2013 12:20 1/08/2013 12:20 1 Note - Text: Remarque sur Insight Diagnostics: Disque dur physique

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 26 sur 77

26
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
1, Contrleur Connecteur 0-Diagnostic: chec

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 27 sur 77

27

Serveur HP PROLIANT dl380 G5, adresse IP : 10.250.90.94
HP Insight Diagnostics Version 8.1.5.2890A
Nom de l'ordinateur: SONL01CTX02PR
Prsentation
Systme
Nom du produit ProLiant DL380 G5
Numro de srie CZC8476HW1
Package de processeurs 1 (Connecteur 1,
Cur = 4)
Intel Xeon Processeur @ 2.50 Ghz
Package de processeurs 2 (Connecteur 2,
Cur = 4)
Intel Xeon Processeur @ 2.50 Ghz
Environnement du systme d`exploitation Microsoft(R) Windows(R) Server 2003, Enterprise Edition, Service Pack 2 (Build 3790)
Mmoire totale 8192 Mgaoctets
Carte 0
DIMM 1A ( DDR2-FBD ) 2048 Mgaoctets (667 MHz)
DIMM 2C Non install
DIMM 3A ( DDR2-FBD ) 2048 Mgaoctets (667 MHz)
DIMM 4C Non install
DIMM 5B ( DDR2-FBD ) 2048 Mgaoctets (667 MHz)
DIMM 6D Non install
DIMM 7B ( DDR2-FBD ) 2048 Mgaoctets (667 MHz)
DIMM 8D Non install
Mmoire ECC installe Oui
PAE matriel activ Non
Informations SPD (Serial Presence Detect) - DIMM 1
Type de mmoire DDR2 SDRAM FB-DIMM
Description DIMM
Numro de pice de rechange
Dpassement du seuil de bit unique -
tat
Aucune erreur DIMM dtecte
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 0
Nombre de bits multiples 0
Informations SPD (Serial Presence Detect) - DIMM 3
Type de mmoire DDR2 SDRAM FB-DIMM
Description DIMM
Numro de pice de rechange
Dpassement du seuil de bit unique -
tat
Aucune erreur DIMM dtecte
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 0
Nombre de bits multiples 0
Informations SPD (Serial Presence Detect) - DIMM 5
Type de mmoire DDR2 SDRAM FB-DIMM
Description DIMM
Numro de pice de rechange

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 28 sur 77

28
Dpassement du seuil de bit unique -
tat
Aucune erreur DIMM dtecte
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 0
Nombre de bits multiples 0
Informations SPD (Serial Presence Detect) - DIMM 7
Type de mmoire DDR2 SDRAM FB-DIMM
Description DIMM
Numro de pice de rechange
Dpassement du seuil de bit unique -
tat
Aucune erreur DIMM dtecte
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 0
Nombre de bits multiples 0
Units de stockage
Disque optique 1 TEAC DV-W28E-RW at Principal/Matre
Type DVD+R
Capacit Support non install
Connecteur Principal/Matre
Contrleur RAID, HP P400, Connecteur 3 HP P400
Modle HP P400
Microprogramme 5.20
Units logiques configures 2
Taille totale de la mmoire 512 Mgaoctets
Mmoire installe 512 Mgaoctets
Carte mmoire RAM utilisable 464 Mgaoctets
Batterie 1 OK
Numro de srie PAFGL0M9VWI0BF
Numro de connecteur PCI 3
Dsignation internationale 5001438002833028
BIOS boot device order 1
Volume logique 0, Contrleur Connecteur 3 Bus 0 146.8 Gigaoctets RAID 0
Code d`tat 0
Description de l`tat OK
Modle HP LOGICAL VOLUME
Microprogramme 5.20
Capacit 146.8 Gigaoctets
Chemin du priphrique \\.\SCSI2:
ID du volume 0
Tolrance aux dfaillances RAID 0
Paramtres d`unit logique
Nombre d`units de contrleur 2
Nombre d`units de volume 1
Table des paramtres d`units
Taille de stripe (blocs physiques) 256
Disque dur physique 1, Contrleur Connecteur 3 146.8 Gigaoctets 10K RPM - HP DG146BB976
Modle HP DG146BB976
Microprogramme HPDC

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 29 sur 77

29
Capacit 146.8 Gigaoctets
Contrleur Contrleur RAID, HP P400, Connecteur 3
Vitesse de rotation 10K RPM
Numro de srie 3NM7P5DR00009912YB5R
Temprature 31 Degrees Celsius
Configuration du cble
Chemin de donnes 16 bits sur un cble avec 16 ID SCSI pris
en charge
Connecteur 2I
Numro de botier 1
Baie de botier 1
Type d`unit Disque dur SAS
Vitesse de liaison ngocie 3 Gbps
Erreurs de lecture graves 00000000
Erreurs de lecture (nouvel essai russi) 00000000
Erreurs d`criture graves 00000000
Erreurs d`criture (nouvel essai russi) 00000000
Erreurs de panne prdictive 00000000
Unit prsente et oprationnelle Oui
Secteurs crits 00000007ff608dc7
Volume logique 1, Contrleur Connecteur 3 Bus 0 146.8 Gigaoctets RAID 0
Code d`tat 0
Description de l`tat OK
Modle HP LOGICAL VOLUME
Microprogramme 5.20
Capacit 146.8 Gigaoctets
Chemin du priphrique \\.\SCSI2:
ID du volume 0
Tolrance aux dfaillances RAID 0
Paramtres d`unit logique
Nombre d`units de contrleur 2
Nombre d`units de volume 1
Table des paramtres d`units
Taille de stripe (blocs physiques) 256
Disque dur physique 2, Contrleur Connecteur 3 146.8 Gigaoctets 10K RPM - HP DG146BB976
Modle HP DG146BB976
Microprogramme HPDC
Capacit 146.8 Gigaoctets
Contrleur Contrleur RAID, HP P400, Connecteur 3
Vitesse de rotation 10K RPM
Numro de srie 3NM7Q3CF00009910VQAW
Temprature 31 Degrees Celsius
Configuration du cble
Chemin de donnes 16 bits sur un cble avec 16 ID SCSI pris
en charge
Connecteur 2I
Numro de botier 1
Baie de botier 2
Type d`unit Disque dur SAS
Vitesse de liaison ngocie 3 Gbps

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 30 sur 77

30
Erreurs de lecture graves 00000000
Erreurs de lecture (nouvel essai russi) 00000000
Erreurs d`criture graves 00000000
Erreurs d`criture (nouvel essai russi) 00000000
Erreurs de panne prdictive 00000000
Unit prsente et oprationnelle Oui
Secteurs crits 0000000000193ed1
Disques logiques
C: Disque logique 1 ~ 94.38GB
Nom de volume
Systme de fichiers NTFS
Taille (octet) 94375014400
Espace libre (octet) 33106718720
E: Disque logique 2 ~ 52.40GB
Nom de volume DATA
Systme de fichiers NTFS
Taille (octet) 52399468544
Espace libre (octet) 48265805824

HP Insight Diagnostics Version 8.1.5.2890A
Nom de l'ordinateur: SONL01CTX02PR
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
Caution Power Supply 0/00/00 0:00 0/00/00 0:00 8
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution Power Supply 0/00/00 0:00 0/00/00 0:00 8
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/03/2008 0:00 8/03/2008 0:00 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Repaired Power Supply 8/04/2008 2:37 0/00/00 0:00 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/04/2008 2:37 8/04/2008 2:37 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 1 - Error: 208
Repaired Power Supply 8/04/2008 2:37 8/04/2008 2:37 1
Not Redundant - Chassis Name: - Chassis Id: 0 - Chassis Type:
Main system or external slots - Chassis Port: 0
Caution POST 8/10/2008 23:38 8/10/2008 23:38 1
Post Error - Message: 1792-Drive Array Reports Valid Data
Found in Array Accelerator - Error: 92
Failed
Network
Adapter
8/12/2008 1:07 8/11/2008 0:02 4
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Failed
Network
Adapter
8/11/2008 0:07 8/11/2008 0:07 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Failed
Network
Adapter
8/11/2008 1:07 8/11/2008 1:07 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Network
Adapter
8/12/2008 1:35 8/12/2008 1:07 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Network
Adapter
1/14/2009 14:58 1/14/2009 14:40 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Machine
Environment
3/17/2009 23:44 3/17/2009 23:44 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired Operating 3/17/2009 23:44 3/17/2009 23:44 1 Auto Shutdown - Cause: Overheat

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 31 sur 77

31
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
System
Info
Operating
System
3/17/2009 23:44 3/17/2009 23:44 5 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
3/17/2009 23:44 3/17/2009 23:44 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/17/2009 23:44 3/17/2009 23:44 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/17/2009 23:44 3/17/2009 23:44 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/17/2009 23:44 3/17/2009 23:44 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/17/2009 23:44 3/17/2009 23:44 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/17/2009 23:44 3/17/2009 23:44 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/17/2009 23:44 3/17/2009 23:44 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/17/2009 23:44 3/17/2009 23:44 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
3/17/2009 23:44 3/17/2009 23:44 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
3/17/2009 23:44 3/17/2009 23:44 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
3/17/2009 23:47 3/17/2009 23:47 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 3/17/2009 23:47 3/17/2009 23:47 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
3/18/2009 1:55 3/18/2009 1:42 1
Overheat - Chassis Name: - Temp: 44 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 3/18/2009 1:42 3/18/2009 1:42 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
3/18/2009 1:55 3/18/2009 1:55 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/18/2009 1:55 3/18/2009 1:55 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
3/18/2009 1:55 3/18/2009 1:55 1 Auto Shutdown - Cause: Temp Abort
Repaired
Network
Adapter
3/26/2009 21:05 3/26/2009 20:53 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Machine
Environment
3/29/2009 8:47 3/29/2009 8:47 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 8:47 3/29/2009 8:47 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
3/29/2009 8:47 3/29/2009 8:47 2 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
3/29/2009 8:47 3/29/2009 8:47 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 32 sur 77

32
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 8:47 3/29/2009 8:47 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
3/29/2009 8:47 3/29/2009 8:47 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
3/29/2009 8:47 3/29/2009 8:47 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
3/29/2009 8:50 3/29/2009 8:50 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 3/29/2009 8:49 3/29/2009 8:49 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
3/29/2009 11:13 3/29/2009 10:26 5
Overheat - Chassis Name: - Temp: 44 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 3/29/2009 10:25 3/29/2009 10:25 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Caution POST 3/29/2009 10:31 3/29/2009 10:31 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Caution POST 3/29/2009 10:33 3/29/2009 10:33 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Caution POST 3/29/2009 10:34 3/29/2009 10:34 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
3/29/2009 11:13 3/29/2009 11:13 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 11:13 3/29/2009 11:13 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
3/29/2009 11:15 3/29/2009 11:13 5 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
3/29/2009 11:13 3/29/2009 11:13 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 11:13 3/29/2009 11:13 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 11:13 3/29/2009 11:13 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 11:13 3/29/2009 11:13 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 11:14 3/29/2009 11:13 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 11:14 3/29/2009 11:13 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 11:15 3/29/2009 11:15 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 11:15 3/29/2009 11:15 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:29 3/29/2009 13:29 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:29 3/29/2009 13:29 1 Auto Shutdown - Cause: Overheat

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 33 sur 77

33
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
Info
Operating
System
3/29/2009 13:43 3/29/2009 13:29 13 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
3/29/2009 13:29 3/29/2009 13:29 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:29 3/29/2009 13:29 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:31 3/29/2009 13:31 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:31 3/29/2009 13:31 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:31 3/29/2009 13:31 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:31 3/29/2009 13:31 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:32 3/29/2009 13:31 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:32 3/29/2009 13:31 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:33 3/29/2009 13:33 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:33 3/29/2009 13:33 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:33 3/29/2009 13:33 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:33 3/29/2009 13:33 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:33 3/29/2009 13:33 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:33 3/29/2009 13:33 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:34 3/29/2009 13:33 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:34 3/29/2009 13:33 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:42 3/29/2009 13:42 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:42 3/29/2009 13:42 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:43 3/29/2009 13:42 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:43 3/29/2009 13:42 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 13:43 3/29/2009 13:43 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired Operating 3/29/2009 13:43 3/29/2009 13:43 1 Auto Shutdown - Cause: Overheat

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 34 sur 77

34
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
System
Repaired
Machine
Environment
3/29/2009 13:43 3/29/2009 13:43 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 13:43 3/29/2009 13:43 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 14:26 3/29/2009 13:43 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 14:26 3/29/2009 13:43 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
3/29/2009 14:26 3/29/2009 14:26 1 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
4/13/2009 20:26 4/13/2009 20:26 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
4/13/2009 20:26 4/13/2009 20:26 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
4/13/2009 20:26 4/13/2009 20:26 2 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
4/13/2009 20:26 4/13/2009 20:26 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
4/13/2009 20:26 4/13/2009 20:26 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
4/13/2009 20:31 4/13/2009 20:26 2
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
4/13/2009 20:26 4/13/2009 20:26 1 Auto Shutdown - Cause: Overheat
Caution POST 4/13/2009 20:28 4/13/2009 20:28 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Network
Adapter
5/02/2009 11:20 5/02/2009 11:18 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Machine
Environment
5/26/2009 1:46 5/26/2009 1:46 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 1:46 5/26/2009 1:46 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
5/26/2009 1:47 5/26/2009 1:46 3 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
5/26/2009 1:47 5/26/2009 1:47 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 1:47 5/26/2009 1:47 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 1:47 5/26/2009 1:47 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 1:47 5/26/2009 1:47 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
5/26/2009 1:47 5/26/2009 1:47 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
5/26/2009 1:47 5/26/2009 1:47 1 Auto Shutdown - Cause: Overheat

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 35 sur 77

35
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
Repaired
Machine
Environment
5/26/2009 2:39 5/26/2009 1:49 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 5/26/2009 1:48 5/26/2009 1:48 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
5/26/2009 2:39 5/26/2009 2:39 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:39 5/26/2009 2:39 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
5/26/2009 2:39 5/26/2009 2:39 1 Auto Shutdown - Cause: Temp Abort
Repaired
Network
Adapter
6/25/2009 19:37 6/25/2009 19:35 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Caution
Machine
Environment
6/27/2009 12:11 6/27/2009 12:11 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
6/27/2009 12:11 6/27/2009 12:11 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
6/27/2009 12:25 6/27/2009 12:13 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 6/27/2009 12:12 6/27/2009 12:12 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Network
Adapter
7/11/2009 17:35 7/11/2009 17:33 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Machine
Environment
10/14/2009 23:54 10/14/2009 23:54 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
10/14/2009 23:54 10/14/2009 23:54 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
10/14/2009 23:54 10/14/2009 23:54 1 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
10/15/2009 0:18 10/14/2009 23:54 2
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
10/14/2009 23:54 10/14/2009 23:54 1 Auto Shutdown - Cause: Overheat
Caution POST 10/14/2009 23:55 10/14/2009 23:55 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
11/05/2009 19:13 11/05/2009 19:13 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
11/05/2009 19:13 11/05/2009 19:13 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
11/05/2009 19:13 11/05/2009 19:13 1 Auto Shutdown - Cause: Temp Abort
Caution
Machine
Environment
11/05/2009 19:16 11/05/2009 19:13 2
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
11/05/2009 19:13 11/05/2009 19:13 1 Auto Shutdown - Cause: Overheat
Caution POST 11/05/2009 19:15 11/05/2009 19:15 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Caution
Machine
Environment
11/05/2009 19:55 11/05/2009 19:55 1
Overheat - Chassis Name: - Temp: 44 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 36 sur 77

36
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
slots - Chassis Port: 0
Repaired
Machine
Environment
11/05/2009 20:13 11/05/2009 20:00 1
Overheat - Chassis Name: - Temp: 44 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 11/05/2009 20:00 11/05/2009 20:00 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
1/09/2010 15:10 1/09/2010 15:10 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
1/09/2010 15:10 1/09/2010 15:10 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
1/09/2010 15:12 1/09/2010 15:10 4 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
1/09/2010 15:11 1/09/2010 15:10 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
1/09/2010 15:11 1/09/2010 15:10 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
1/09/2010 15:12 1/09/2010 15:12 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
1/09/2010 15:12 1/09/2010 15:12 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
1/09/2010 15:12 1/09/2010 15:12 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
1/09/2010 15:12 1/09/2010 15:12 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
1/09/2010 15:12 1/09/2010 15:12 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
1/09/2010 15:12 1/09/2010 15:12 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
1/09/2010 16:40 1/09/2010 15:14 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 1/09/2010 15:14 1/09/2010 15:14 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
4/28/2010 16:06 4/28/2010 16:06 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
4/28/2010 16:06 4/28/2010 16:06 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
4/28/2010 16:14 4/28/2010 16:06 3 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
4/28/2010 16:14 4/28/2010 16:06 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
4/28/2010 16:14 4/28/2010 16:06 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
4/28/2010 16:14 4/28/2010 16:14 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
4/28/2010 16:14 4/28/2010 16:14 1 Auto Shutdown - Cause: Overheat
Repaired Machine 5/09/2010 9:42 5/09/2010 9:42 1 Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 37 sur 77

37
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
Environment Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/09/2010 9:42 5/09/2010 9:42 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
5/09/2010 9:42 5/09/2010 9:42 1 Auto Shutdown - Cause: Temp Abort
Caution
Machine
Environment
5/09/2010 9:43 5/09/2010 9:43 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
5/09/2010 9:43 5/09/2010 9:43 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
5/09/2010 9:45 5/09/2010 9:45 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 5/09/2010 9:43 5/09/2010 9:43 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Caution
Machine
Environment
5/09/2010 10:42 5/09/2010 10:24 2
Overheat - Chassis Name: - Temp: 44 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 5/09/2010 10:22 5/09/2010 10:22 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Caution POST 5/09/2010 10:41 5/09/2010 10:41 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
5/09/2010 12:24 5/09/2010 11:06 2
Overheat - Chassis Name: - Temp: 44 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 5/09/2010 11:04 5/09/2010 11:04 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Caution POST 5/09/2010 11:21 5/09/2010 11:21 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
5/09/2010 12:24 5/09/2010 12:24 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/09/2010 12:24 5/09/2010 12:24 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
5/09/2010 12:25 5/09/2010 12:24 2 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
5/09/2010 12:25 5/09/2010 12:25 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
5/09/2010 12:25 5/09/2010 12:25 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
7/04/2010 13:02 7/04/2010 13:00 2
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Failed
Operating
System
7/04/2010 13:00 7/04/2010 13:00 1 Auto Shutdown - Cause: Overheat
Caution POST 7/04/2010 12:59 7/04/2010 12:59 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Caution
Machine
Environment
7/04/2010 13:40 7/04/2010 13:40 1
Overheat - Chassis Name: - Temp: 44 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Machine
Environment
7/04/2010 14:46 7/04/2010 14:10 1
Overheat - Chassis Name: - Temp: 44 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Caution POST 7/04/2010 14:08 7/04/2010 14:08 1 Post Error - Message: 1610-Temperature violation detected

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 38 sur 77

38
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
7/04/2010 14:53 7/04/2010 14:53 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 14:53 7/04/2010 14:53 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
7/04/2010 14:53 7/04/2010 14:53 2 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
7/04/2010 14:53 7/04/2010 14:53 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 14:53 7/04/2010 14:53 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
7/04/2010 15:32 7/04/2010 14:53 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 15:32 7/04/2010 14:53 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
7/04/2010 15:32 7/04/2010 15:32 2 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
7/04/2010 15:32 7/04/2010 15:32 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type: Ambient -
Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main system or external
slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 15:32 7/04/2010 15:32 1 Auto Shutdown - Cause: Overheat
Caution POST 8/15/2010 0:31 8/15/2010 0:31 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 8/16/2010 8:34 8/16/2010 8:34 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 8/16/2010 9:19 8/16/2010 9:19 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Repaired
Network
Adapter
9/01/2010 14:41 9/01/2010 14:17 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Caution Power Supply 1/31/2011 12:33 1/31/2011 12:33 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 1/31/2011 12:30 1/31/2011 12:30 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 2/01/2011 7:36 2/01/2011 7:36 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 2/01/2011 7:34 2/01/2011 7:34 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 4/02/2011 15:48 4/02/2011 15:48 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 4/06/2011 19:21 4/06/2011 19:21 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 4/06/2011 19:18 4/06/2011 19:18 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 4/09/2011 5:04 4/09/2011 5:04 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 4/09/2011 5:01 4/09/2011 5:01 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 5/04/2011 14:52 5/04/2011 14:27 2
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 5/04/2011 14:25 5/04/2011 14:25 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 39 sur 77

39
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
Caution POST 5/04/2011 14:52 5/04/2011 14:52 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 5/04/2011 15:59 5/04/2011 15:01 6
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 5/04/2011 15:00 5/04/2011 15:00 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 5/04/2011 15:14 5/04/2011 15:14 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 5/04/2011 15:38 5/04/2011 15:38 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 5/04/2011 15:49 5/04/2011 15:49 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 5/04/2011 15:56 5/04/2011 15:56 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 5/04/2011 16:00 5/04/2011 16:00 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 5/04/2011 16:01 5/04/2011 16:01 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 5/04/2011 16:01 5/04/2011 16:01 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 8/23/2011 12:13 8/23/2011 12:13 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 8/26/2011 21:57 8/26/2011 21:57 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/26/2011 21:57 8/26/2011 21:57 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 8/31/2011 10:36 8/31/2011 10:36 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/31/2011 10:36 8/31/2011 10:36 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 9/20/2011 14:51 9/20/2011 14:35 4
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 9/20/2011 14:35 9/20/2011 14:35 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 9/20/2011 14:41 9/20/2011 14:41 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 9/20/2011 14:45 9/20/2011 14:45 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 9/20/2011 14:51 9/20/2011 14:51 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 11/04/2011 8:25 11/04/2011 8:25 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 11/04/2011 8:26 11/04/2011 8:26 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
11/04/2011 17:29 11/04/2011 17:29 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Failed
Network
Adapter
12/11/2011 12:37 12/11/2011 12:37 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Network
Adapter
12/11/2011 18:23 12/11/2011 13:25 3
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Caution Power Supply 1/10/2012 12:07 1/10/2012 12:07 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 1/10/2012 12:07 1/10/2012 12:07 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 40 sur 77

40
Gravit Classe Dernire mise jour
Premire mise
jour
Comptage Description
Caution POST 4/02/2012 8:51 4/02/2012 8:51 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 6/11/2012 13:05 6/11/2012 13:05 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 6/11/2012 13:05 6/11/2012 13:05 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 9/12/2012 9:55 9/12/2012 9:55 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 9/12/2012 9:55 9/12/2012 9:55 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution Power Supply 12/07/2012 9:30 12/07/2012 9:30 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 12/07/2012 9:30 12/07/2012 9:30 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Info Maintenance 1/08/2013 12:35 1/08/2013 12:35 1
Note - Text: Remarque sur Insight Diagnostics: Disque dur
physique 1, Contrleur Connecteur 3-Diagnostic: chec

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 41 sur 77

41

Serveur HP PROLIANT dl380 G5, adresse IP : 10.250.90.133
HP Insight Diagnostics Version 8.1.5.2890A
Nom de l'ordinateur: SONL01CTX09PR
Prsentation
Systme
Nom du produit ProLiant DL380 G5
Numro de srie CZC8476HTH
Package de processeurs 1 (Connecteur 1,
Cur = 4)
Intel Xeon Processeur @ 2.50 Ghz
Package de processeurs 2 (Connecteur 2,
Cur = 4)
Intel Xeon Processeur @ 2.50 Ghz
Environnement du systme d`exploitation Microsoft(R) Windows(R) Server 2003, Enterprise Edition, Service Pack 2 (Build 3790)
Mmoire totale 8192 Mgaoctets
Carte 0
DIMM 1A ( DDR2-FBD ) 2048 Mgaoctets (667 MHz)
DIMM 2C Non install
DIMM 3A ( DDR2-FBD ) 2048 Mgaoctets (667 MHz)
DIMM 4C Non install
DIMM 5B ( DDR2-FBD ) 2048 Mgaoctets (667 MHz)
DIMM 6D Non install
DIMM 7B ( DDR2-FBD ) 2048 Mgaoctets (667 MHz)
DIMM 8D Non install
Mmoire ECC installe Oui
PAE matriel activ Non
Informations SPD (Serial Presence Detect) - DIMM 1
Type de mmoire DDR2 SDRAM FB-DIMM
Description DIMM
Numro de pice de rechange
Dpassement du seuil de bit unique -
tat
Aucune erreur DIMM dtecte
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 0
Nombre de bits multiples 0
Informations SPD (Serial Presence Detect) - DIMM 3
Type de mmoire DDR2 SDRAM FB-DIMM
Description DIMM
Numro de pice de rechange
Dpassement du seuil de bit unique -
tat
Aucune erreur DIMM dtecte
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 0
Nombre de bits multiples 0
Informations SPD (Serial Presence Detect) - DIMM 5
Type de mmoire DDR2 SDRAM FB-DIMM
Description DIMM
Numro de pice de rechange

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 42 sur 77

42
Dpassement du seuil de bit unique -
tat
Aucune erreur DIMM dtecte
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 0
Nombre de bits multiples 0
Informations SPD (Serial Presence Detect) - DIMM 7
Type de mmoire DDR2 SDRAM FB-DIMM
Description DIMM
Numro de pice de rechange
Dpassement du seuil de bit unique -
tat
Aucune erreur DIMM dtecte
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 0
Nombre de bits multiples 0
Units de stockage
Disque optique 1 TEAC DV-W28E-RW at Principal/Matre
Type DVD+R
Capacit Support non install
Connecteur Principal/Matre
Contrleur RAID, HP P400, Connecteur 3 HP P400
Modle HP P400
Microprogramme 5.20
Units logiques configures 2
Taille totale de la mmoire 512 Mgaoctets
Mmoire installe 512 Mgaoctets
Carte mmoire RAM utilisable 464 Mgaoctets
Batterie 1 OK
Numro de srie PAFGL0M9VWK0J7
Numro de connecteur PCI 3
Dsignation internationale 5001438002865728
BIOS boot device order 1
Volume logique 0, Contrleur Connecteur 3 Bus 0 146.8 Gigaoctets RAID 0
Code d`tat 0
Description de l`tat OK
Modle HP LOGICAL VOLUME
Microprogramme 5.20
Capacit 146.8 Gigaoctets
Chemin du priphrique \\.\SCSI2:
ID du volume 0
Tolrance aux dfaillances RAID 0
Paramtres d`unit logique
Nombre d`units de contrleur 2
Nombre d`units de volume 1
Table des paramtres d`units
Taille de stripe (blocs physiques) 256
Disque dur physique 1, Contrleur Connecteur 3 146.8 Gigaoctets 10K RPM - HP DG146BB976
Modle HP DG146BB976
Microprogramme HPDC

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 43 sur 77

43
Capacit 146.8 Gigaoctets
Contrleur Contrleur RAID, HP P400, Connecteur 3
Vitesse de rotation 10K RPM
Numro de srie 3NM7QKTV00009913LHP9
Temprature 31 Degrees Celsius
Configuration du cble
Chemin de donnes 16 bits sur un cble avec 16 ID SCSI pris
en charge
Connecteur 2I
Numro de botier 1
Baie de botier 1
Type d`unit Disque dur SAS
Vitesse de liaison ngocie 3 Gbps
Erreurs de lecture graves 00000000
Erreurs de lecture (nouvel essai russi) 00000000
Erreurs d`criture graves 00000000
Erreurs d`criture (nouvel essai russi) 00000000
Erreurs de panne prdictive 00000000
Unit prsente et oprationnelle Oui
Secteurs crits 00000007f34719cb
Volume logique 1, Contrleur Connecteur 3 Bus 0 146.8 Gigaoctets RAID 0
Code d`tat 0
Description de l`tat OK
Modle HP LOGICAL VOLUME
Microprogramme 5.20
Capacit 146.8 Gigaoctets
Chemin du priphrique \\.\SCSI2:
ID du volume 0
Tolrance aux dfaillances RAID 0
Paramtres d`unit logique
Nombre d`units de contrleur 2
Nombre d`units de volume 1
Table des paramtres d`units
Taille de stripe (blocs physiques) 256
Disque dur physique 2, Contrleur Connecteur 3 146.8 Gigaoctets 10K RPM - HP DG146BB976
Modle HP DG146BB976
Microprogramme HPDC
Capacit 146.8 Gigaoctets
Contrleur Contrleur RAID, HP P400, Connecteur 3
Vitesse de rotation 10K RPM
Numro de srie 3NM7NQ1E00009912VFXG
Temprature 29 Degrees Celsius
Configuration du cble
Chemin de donnes 16 bits sur un cble avec 16 ID SCSI pris
en charge
Connecteur 2I
Numro de botier 1
Baie de botier 2
Type d`unit Disque dur SAS
Vitesse de liaison ngocie 3 Gbps

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 44 sur 77

44
Erreurs de lecture graves 00000000
Erreurs de lecture (nouvel essai russi) 00000000
Erreurs d`criture graves 00000000
Erreurs d`criture (nouvel essai russi) 00000000
Erreurs de panne prdictive 00000000
Unit prsente et oprationnelle Oui
Secteurs crits 000000000019211b
Disques logiques
C: Disque logique 1 ~ 94.38GB
Nom de volume
Systme de fichiers NTFS
Taille (octet) 94375014400
Espace libre (octet) 24400699392
E: Disque logique 2 ~ 52.40GB
Nom de volume DATA
Systme de fichiers NTFS
Taille (octet) 52399468544
Espace libre (octet) 50102566912

HP Insight Diagnostics Version 8.1.5.2890A
Nom de l'ordinateur: SONL01CTX09PR
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Caution Power Supply 0/00/00 0:00 0/00/00 0:00 5
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution Power Supply 0/00/00 0:00 0/00/00 0:00 5
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/03/2008 0:00 8/03/2008 0:00 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Caution POST 8/03/2008 0:01 8/03/2008 0:01 1
Post Error - Message: 1785-Drive Array not Configured - Error:
85
Caution POST 8/07/2008 19:48 8/07/2008 19:48 1
Post Error - Message: 1794-Drive Array - Array Accelerator
Battery Charge Low - Error: 94
Failed
Network
Adapter
12/08/2011 17:54 1/07/2009 15:00 28
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Failed
Network
Adapter
1/07/2009 15:15 1/07/2009 15:00 3
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Network
Adapter
1/08/2009 12:16 1/08/2009 12:06 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Caution
Machine
Environment
3/17/2009 23:59 3/17/2009 23:59 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Failed
Operating
System
3/17/2009 23:59 3/17/2009 23:59 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
3/18/2009 0:02 3/18/2009 0:02 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Caution POST 3/18/2009 0:02 3/18/2009 0:02 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
3/18/2009 1:47 3/18/2009 1:15 5
Overheat - Chassis Name: - Temp: 44 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 45 sur 77

45
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
system or external slots - Chassis Port: 0
Caution POST 3/18/2009 1:15 3/18/2009 1:15 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Caution POST 3/18/2009 1:16 3/18/2009 1:16 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Caution POST 3/18/2009 1:39 3/18/2009 1:39 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Failed
Network
Adapter
3/18/2009 1:57 3/18/2009 1:57 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution POST 3/21/2009 23:13 3/21/2009 23:13 1
Post Error - Message: 1792-Drive Array Reports Valid Data
Found in Array Accelerator - Error: 92
Caution POST 3/21/2009 23:13 3/21/2009 23:13 1
Post Error - Message: 1794-Drive Array - Array Accelerator
Battery Charge Low - Error: 94
Failed
Network
Adapter
3/21/2009 23:15 3/21/2009 23:15 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Repaired
Network
Adapter
3/26/2009 21:06 3/26/2009 20:56 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Machine
Environment
3/29/2009 9:28 3/29/2009 9:28 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:28 3/29/2009 9:28 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
3/29/2009 9:36 3/29/2009 9:28 12 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
3/29/2009 9:29 3/29/2009 9:29 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:29 3/29/2009 9:29 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 9:30 3/29/2009 9:29 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:30 3/29/2009 9:29 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 9:33 3/29/2009 9:33 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:33 3/29/2009 9:33 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 9:33 3/29/2009 9:33 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:33 3/29/2009 9:33 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 9:33 3/29/2009 9:33 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:33 3/29/2009 9:33 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 9:33 3/29/2009 9:33 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:33 3/29/2009 9:33 1 Auto Shutdown - Cause: Overheat
Repaired Machine 3/29/2009 9:33 3/29/2009 9:33 1 Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 46 sur 77

46
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Environment Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:33 3/29/2009 9:33 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 9:34 3/29/2009 9:34 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:34 3/29/2009 9:34 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 9:35 3/29/2009 9:34 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:35 3/29/2009 9:34 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 9:35 3/29/2009 9:35 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:35 3/29/2009 9:35 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 9:36 3/29/2009 9:36 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
3/29/2009 9:36 3/29/2009 9:36 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
3/29/2009 10:39 3/29/2009 9:38 2
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Failed
Operating
System
3/29/2009 9:38 3/29/2009 9:38 1 Auto Shutdown - Cause: Overheat
Caution POST 3/29/2009 9:40 3/29/2009 9:40 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Failed
Network
Adapter
3/29/2009 10:52 3/29/2009 10:52 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Repaired
Network
Adapter
5/02/2009 11:21 5/02/2009 11:17 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Machine
Environment
5/26/2009 2:17 5/26/2009 2:17 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:17 5/26/2009 2:17 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
5/26/2009 2:30 5/26/2009 2:17 9 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
5/26/2009 2:18 5/26/2009 2:17 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:18 5/26/2009 2:17 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:18 5/26/2009 2:18 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:18 5/26/2009 2:18 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:18 5/26/2009 2:18 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired Operating 5/26/2009 2:18 5/26/2009 2:18 1 Auto Shutdown - Cause: Overheat

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 47 sur 77

47
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
System
Repaired
Machine
Environment
5/26/2009 2:18 5/26/2009 2:18 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:18 5/26/2009 2:18 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:18 5/26/2009 2:18 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:18 5/26/2009 2:18 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:18 5/26/2009 2:18 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:18 5/26/2009 2:18 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:18 5/26/2009 2:18 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:18 5/26/2009 2:18 1 Auto Shutdown - Cause: Overheat
Caution
Machine
Environment
5/26/2009 2:18 5/26/2009 2:18 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/26/2009 2:30 5/26/2009 2:18 2 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/26/2009 2:22 5/26/2009 2:20 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Caution POST 5/26/2009 2:21 5/26/2009 2:21 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
5/26/2009 2:30 5/26/2009 2:22 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Failed
Network
Adapter
5/26/2009 2:36 5/26/2009 2:36 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Repaired
Network
Adapter
6/25/2009 19:39 6/25/2009 19:35 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Network
Adapter
7/11/2009 17:36 7/11/2009 17:32 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Network
Adapter
8/20/2009 8:49 8/20/2009 8:47 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Machine
Environment
11/05/2009 20:08 11/05/2009 19:33 2
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Failed
Operating
System
11/05/2009 19:33 11/05/2009 19:33 1 Auto Shutdown - Cause: Overheat
Caution POST 11/05/2009 19:35 11/05/2009 19:35 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Failed
Network
Adapter
11/05/2009 20:21 11/05/2009 20:21 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution POST 11/29/2009 14:34 11/29/2009 14:34 1
Post Error - Message: 1792-Drive Array Reports Valid Data
Found in Array Accelerator - Error: 92
Failed
Network
Adapter
11/29/2009 14:36 11/29/2009 14:36 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 48 sur 77

48
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Repaired
Machine
Environment
1/09/2010 16:27 1/09/2010 16:27 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
1/09/2010 16:27 1/09/2010 16:27 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
1/09/2010 16:27 1/09/2010 16:27 2 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
1/09/2010 16:27 1/09/2010 16:27 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
1/09/2010 16:27 1/09/2010 16:27 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
1/09/2010 16:35 1/09/2010 16:27 2
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Failed
Operating
System
1/09/2010 16:27 1/09/2010 16:27 1 Auto Shutdown - Cause: Overheat
Caution POST 1/09/2010 16:29 1/09/2010 16:29 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Failed
Network
Adapter
1/09/2010 16:42 1/09/2010 16:42 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Repaired
Machine
Environment
5/09/2010 10:12 5/09/2010 10:12 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/09/2010 10:12 5/09/2010 10:12 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
5/09/2010 10:59 5/09/2010 10:12 5 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
5/09/2010 10:12 5/09/2010 10:12 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/09/2010 10:12 5/09/2010 10:12 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/09/2010 10:13 5/09/2010 10:12 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/09/2010 10:13 5/09/2010 10:12 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/09/2010 10:13 5/09/2010 10:13 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/09/2010 10:13 5/09/2010 10:13 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/09/2010 10:59 5/09/2010 10:13 2
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
5/09/2010 10:59 5/09/2010 10:13 2 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
5/09/2010 10:45 5/09/2010 10:15 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Caution POST 5/09/2010 10:15 5/09/2010 10:15 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
5/09/2010 11:22 5/09/2010 10:59 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 49 sur 77

49
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Repaired
Operating
System
5/09/2010 11:22 5/09/2010 10:59 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
5/09/2010 11:22 5/09/2010 11:22 1 Auto Shutdown - Cause: Temp Abort
Failed
Network
Adapter
5/09/2010 11:41 5/09/2010 11:41 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution
Machine
Environment
7/04/2010 13:32 7/04/2010 13:32 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Failed
Operating
System
7/04/2010 13:32 7/04/2010 13:32 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
7/04/2010 14:02 7/04/2010 13:35 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Caution POST 7/04/2010 13:33 7/04/2010 13:33 1
Post Error - Message: 1610-Temperature violation detected
Waiting 5 minutes for system to cool - Error: 185
Repaired
Machine
Environment
7/04/2010 14:03 7/04/2010 14:03 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 14:03 7/04/2010 14:03 1 Auto Shutdown - Cause: Overheat
Info
Operating
System
7/04/2010 14:11 7/04/2010 14:03 9 Auto Shutdown - Cause: Temp Abort
Repaired
Machine
Environment
7/04/2010 14:04 7/04/2010 14:04 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 14:04 7/04/2010 14:04 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
7/04/2010 14:04 7/04/2010 14:04 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 14:04 7/04/2010 14:04 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
7/04/2010 14:04 7/04/2010 14:04 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 14:04 7/04/2010 14:04 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
7/04/2010 14:05 7/04/2010 14:05 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 14:05 7/04/2010 14:05 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
7/04/2010 14:05 7/04/2010 14:05 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 14:05 7/04/2010 14:05 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
7/04/2010 14:05 7/04/2010 14:05 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 14:05 7/04/2010 14:05 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
7/04/2010 14:11 7/04/2010 14:11 1
Overheat - Chassis Name: - Temp: 40 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 50 sur 77

50
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Repaired
Operating
System
7/04/2010 14:11 7/04/2010 14:11 1 Auto Shutdown - Cause: Overheat
Repaired
Machine
Environment
7/04/2010 14:11 7/04/2010 14:11 1
Overheat - Chassis Name: - Temp: 39 - Fan Zone Type:
Ambient - Zone Id: 2 - Chassis Id: 0 - Chassis Type: Main
system or external slots - Chassis Port: 0
Repaired
Operating
System
7/04/2010 14:11 7/04/2010 14:11 1 Auto Shutdown - Cause: Overheat
Failed
Network
Adapter
7/04/2010 14:36 7/04/2010 14:36 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution POST 8/15/2010 0:33 8/15/2010 0:33 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
8/15/2010 0:36 8/15/2010 0:36 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution POST 8/16/2010 8:35 8/16/2010 8:35 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
8/16/2010 8:38 8/16/2010 8:38 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution POST 8/16/2010 9:21 8/16/2010 9:21 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
8/16/2010 9:24 8/16/2010 9:24 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Repaired
Network
Adapter
9/01/2010 14:41 9/01/2010 14:17 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Caution Power Supply 10/20/2010 10:25 10/20/2010 10:25 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 10/20/2010 10:24 10/20/2010 10:24 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
10/20/2010 10:27 10/20/2010 10:27 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 3/31/2011 13:13 3/31/2011 13:13 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 3/31/2011 13:12 3/31/2011 13:12 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
3/31/2011 13:15 3/31/2011 13:15 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 4/02/2011 5:24 4/02/2011 5:24 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 4/02/2011 5:23 4/02/2011 5:23 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
4/02/2011 5:26 4/02/2011 5:26 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution POST 4/02/2011 15:50 4/02/2011 15:50 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
4/02/2011 15:53 4/02/2011 15:53 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 4/09/2011 5:04 4/09/2011 5:04 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 4/09/2011 5:03 4/09/2011 5:03 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
4/09/2011 5:05 4/09/2011 5:05 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 5/27/2011 16:11 5/27/2011 16:11 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 5/27/2011 16:12 5/27/2011 16:12 1 Post Error - Message: 1615-Power Supply Failure or Power

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 51 sur 77

51
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
5/27/2011 16:14 5/27/2011 16:14 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 6/10/2011 0:02 6/10/2011 0:02 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 6/10/2011 0:02 6/10/2011 0:02 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
6/10/2011 0:05 6/10/2011 0:05 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 6/21/2011 15:54 6/21/2011 15:54 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 6/21/2011 15:54 6/21/2011 15:54 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
6/21/2011 15:57 6/21/2011 15:57 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 8/26/2011 21:47 8/26/2011 21:47 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/26/2011 21:47 8/26/2011 21:47 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
8/26/2011 21:50 8/26/2011 21:50 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 9/20/2011 14:35 9/20/2011 14:35 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 9/20/2011 14:35 9/20/2011 14:35 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
9/20/2011 14:39 9/20/2011 14:39 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 11/04/2011 8:25 11/04/2011 8:25 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 11/04/2011 8:25 11/04/2011 8:25 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
11/04/2011 8:28 11/04/2011 8:28 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Repaired
Network
Adapter
11/04/2011 17:32 11/04/2011 17:28 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Repaired
Network
Adapter
12/11/2011 18:24 12/11/2011 12:36 4
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 1 - Chassis Name:
Caution Power Supply 3/13/2012 10:11 3/13/2012 10:11 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 3/13/2012 10:12 3/13/2012 10:12 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
3/13/2012 10:15 3/13/2012 10:15 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 6/11/2012 13:05 6/11/2012 13:05 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 6/11/2012 13:05 6/11/2012 13:05 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
6/11/2012 13:08 6/11/2012 13:08 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 6/26/2012 13:57 6/26/2012 13:57 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 6/26/2012 13:57 6/26/2012 13:57 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed Network 6/26/2012 14:01 6/26/2012 14:01 1 Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 52 sur 77

52
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Adapter or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 7/16/2012 10:24 7/16/2012 10:24 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 7/16/2012 10:24 7/16/2012 10:24 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
7/16/2012 10:28 7/16/2012 10:28 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 7/25/2012 9:45 7/25/2012 9:45 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 7/25/2012 9:45 7/25/2012 9:45 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
7/25/2012 9:49 7/25/2012 9:49 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 7/30/2012 8:40 7/30/2012 8:40 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 7/30/2012 8:40 7/30/2012 8:40 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
7/30/2012 8:44 7/30/2012 8:44 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 8/14/2012 12:28 8/14/2012 12:28 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 8/14/2012 12:28 8/14/2012 12:28 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
8/14/2012 12:32 8/14/2012 12:32 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 9/12/2012 9:55 9/12/2012 9:55 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 9/12/2012 9:56 9/12/2012 9:56 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
9/12/2012 9:59 9/12/2012 9:59 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 10/31/2012 10:57 10/31/2012 10:57 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 10/31/2012 10:57 10/31/2012 10:57 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
10/31/2012 11:01 10/31/2012 11:01 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 11/05/2012 8:35 11/05/2012 8:35 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 11/05/2012 8:35 11/05/2012 8:35 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
11/05/2012 8:38 11/05/2012 8:38 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 11/30/2012 14:15 11/30/2012 14:15 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 11/30/2012 14:15 11/30/2012 14:15 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
11/30/2012 14:18 11/30/2012 14:18 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 12/07/2012 8:40 12/07/2012 8:40 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 12/07/2012 8:40 12/07/2012 8:40 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed Network 12/07/2012 8:44 12/07/2012 8:44 1 Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 53 sur 77

53
Gravit Classe
Dernire mise
jour
Premire mise
jour
Comptage Description
Adapter or external slots - Chassis Port: 2 - Chassis Name:
Caution Power Supply 12/07/2012 14:30 12/07/2012 14:30 1
Failure - Chassis Name: - Error: General Failure - Chassis Id: 0 -
Chassis Type: Main system or external slots - Chassis Port: 0
Caution POST 12/07/2012 14:31 12/07/2012 14:31 1
Post Error - Message: 1615-Power Supply Failure or Power
Supply Unplugged in Bay 2 - Error: 208
Failed
Network
Adapter
12/07/2012 14:34 12/07/2012 14:34 1
Link Down - Slot: 0 - Chassis Id: 0 - Chassis Type: Main system
or external slots - Chassis Port: 2 - Chassis Name:
Info Maintenance 1/08/2013 12:30 1/08/2013 12:30 1
Note - Text: Remarque sur Insight Diagnostics: Disque dur
physique 1, Contrleur Connecteur 3-Diagnostic: chec

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 54 sur 77

54

Serveur HP PROLIANT dl580 G2, adresse IP : 10.250.90.117
HP Insight Diagnostics Version 8.3.0.3320A
Computer Name: SONL01AV01PR
System
Product Name ProLiant DL580 G2
Serial Number A22APBFOUQSS
Processor Package 1 (Socket 1, Core = 1) Intel Xeon Processor @ 2.00 Ghz
Processor Package 2 (Socket 2, Core = 1) Intel Xeon Processor @ 2.00 Ghz
Operating system environment Microsoft(R) Windows(R) Server 2003, Enterprise Edition, Service Pack 2 (Build 3790)
Total memory - 4096 Mbytes
Board 1
Card 1 Status Online
DIMM 1 (DDR) 512 Mbytes
DIMM 2 (DDR) 512 Mbytes
DIMM 3 (DDR) 512 Mbytes
DIMM 4 (DDR) 512 Mbytes
DIMM 5 (DDR) 512 Mbytes
DIMM 6 (DDR) 512 Mbytes
DIMM 7 (DDR) 512 Mbytes
DIMM 8 (DDR) 512 Mbytes
Board 2
Card 2 Status Empty
DIMM 1 Not Installed
DIMM 2 Not Installed
DIMM 3 Not Installed
DIMM 4 Not Installed
DIMM 5 Not Installed
DIMM 6 Not Installed
DIMM 7 Not Installed
DIMM 8 Not Installed
ECC memory installed Yes
Hardware PAE enabled No
Serial presence detect (SPD) information - DIMM 1, Card 1
Memory type Unknown
Memory DRAM type Unknown
DIMM Description
Spare Part Number
Single-Bit Threshold Exceeded Status No DIMM errors detected
Multi-Bit Status No DIMM errors detected
Single-Bit Threshold Count 0
Multi-Bit Count 0
Serial presence detect (SPD) information - DIMM 2, Card 1
Memory type Unknown
Memory DRAM type Unknown
DIMM Description

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 55 sur 77

55
Spare Part Number
Single-Bit Threshold Exceeded Status No DIMM errors detected
Multi-Bit Status No DIMM errors detected
Single-Bit Threshold Count 0
Multi-Bit Count 0
Serial presence detect (SPD) information - DIMM 3, Card 1
Memory type Unknown
Memory DRAM type Unknown
DIMM Description
Spare Part Number
Single-Bit Threshold Exceeded Status No DIMM errors detected
Multi-Bit Status No DIMM errors detected
Single-Bit Threshold Count 0
Multi-Bit Count 0
Serial presence detect (SPD) information - DIMM 4, Card 1
Memory type Unknown
Memory DRAM type Unknown
DIMM Description
Spare Part Number
Single-Bit Threshold Exceeded Status No DIMM errors detected
Multi-Bit Status No DIMM errors detected
Single-Bit Threshold Count 0
Multi-Bit Count 0
Serial presence detect (SPD) information - DIMM 5, Card 1
Memory type Unknown
Memory DRAM type Unknown
DIMM Description
Spare Part Number
Single-Bit Threshold Exceeded Status No DIMM errors detected
Multi-Bit Status No DIMM errors detected
Single-Bit Threshold Count 0
Multi-Bit Count 0
Serial presence detect (SPD) information - DIMM 6, Card 1
Memory type Unknown
Memory DRAM type Unknown
DIMM Description
Spare Part Number
Single-Bit Threshold Exceeded Status No DIMM errors detected
Multi-Bit Status No DIMM errors detected
Single-Bit Threshold Count 0
Multi-Bit Count 0
Serial presence detect (SPD) information - DIMM 7, Card 1
Memory type Unknown
Memory DRAM type Unknown
DIMM Description
Spare Part Number
Single-Bit Threshold Exceeded Status No DIMM errors detected

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 56 sur 77

56
Multi-Bit Status No DIMM errors detected
Single-Bit Threshold Count 0
Multi-Bit Count 0
Serial presence detect (SPD) information - DIMM 8, Card 1
Memory type Unknown
Memory DRAM type Unknown
DIMM Description
Spare Part Number
Single-Bit Threshold Exceeded Status No DIMM errors detected
Multi-Bit Status No DIMM errors detected
Single-Bit Threshold Count 0
Multi-Bit Count 0
Storage
Diskette Drive 1 HighDensity 1.44
Optical Drive 1 COMPAQ CRN-8245B at Primary/Master
Physical Hard Drive 3, Controller Slot 0 72.8 Gbytes 10K RPM - COMPAQ BD07286224
Physical Hard Drive 4, Controller Slot 0 72.8 Gbytes 10K RPM - COMPAQ BD07289BB8
Physical Hard Drive 1, Controller Slot 0 300.0 Gbytes 10K RPM - COMPAQ BD3008A4C6
Physical Hard Drive 2, Controller Slot 0 300.0 Gbytes 10K RPM - COMPAQ BD3008A4C6

HP Insight Diagnostics Version 8.3.0.3320A
Computer Name: SONL01AV01PR

- Denotes passed tests

- Denotes tests that passed with warnings

- Denotes failed tests
Device, Test Number of Times Diagnosed Failed Count Passed with warnings Count Diagnosis Time

Logical Volume 0, Controller Slot 0 Bus 0 1 0 1 0:00:02

Errors and Warnings for Physical Hard Drive 3, Serial Number: UPD6P3701BHC0329, Controller Serial Number: Unavailable
1/8/2013 12:11:28 PM
Warning: Drive does not support a DST log on this configuration
Warning: Failed to write to Application Client Log

Errors and Warnings for Physical Hard Drive 4, Serial Number: DAL1P63073MP0610, Controller Serial Number: Unavailable
1/8/2013 12:11:28 PM
Warning: Drive does not support a DST log on this configuration
Warning: Failed to write to Application Client Log

Logical Volume 1, Controller Slot 0 Bus 0 1 0 1 0:00:03

Errors and Warnings for Physical Hard Drive 1, Serial Number: 3KR462SW000097524MA6, Controller Serial Number: Unavailable
1/8/2013 12:11:32 PM
Warning: Failed to write to Application Client Log

Errors and Warnings for Physical Hard Drive 2, Serial Number: 3KR4GPNP0000981100TJ, Controller Serial Number: Unavailable
1/8/2013 12:11:32 PM
Warning: Failed to write to Application Client Log

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 57 sur 77

57

Serveur HP PROLIANT dl580 G3, adresse IP : 10.250.90.58
HP Insight Diagnostics Version 8.1.5.2890A
Nom de l'ordinateur: SONL01DBSQL01PR
Prsentation
Systme
Nom du produit ProLiant DL580 G3
Numro de srie GB86132Y8J
Package de processeurs 1 (Connecteur 1,
Cur = 1)
Intel Xeon Processeur @ 3.00 Ghz
Package de processeurs 2 (Connecteur 2,
Cur = 1)
Intel Xeon Processeur @ 3.00 Ghz
Environnement du systme d`exploitation Microsoft(R) Windows(R) Server 2003, Enterprise Edition, Service Pack 2 (Build 3790)
Mmoire totale 4096 Mgaoctets
Carte 1
Statut de carte 1 En ligne
DIMM 1 (DDR) 1024 Mgaoctets
DIMM 2 (DDR) 1024 Mgaoctets
DIMM 3 (DDR) 1024 Mgaoctets
DIMM 4 (DDR) 1024 Mgaoctets
Carte 2
Statut de carte 2 Vide
DIMM 1 Non install
DIMM 2 Non install
DIMM 3 Non install
DIMM 4 Non install
Carte 3
Statut de carte 3 Vide
DIMM 1 Non install
DIMM 2 Non install
DIMM 3 Non install
DIMM 4 Non install
Carte 4
Statut de carte 4 Vide
DIMM 1 Non install
DIMM 2 Non install
DIMM 3 Non install
DIMM 4 Non install
Mmoire ECC installe Oui
PAE matriel activ Non
Informations SPD (Serial Presence Detect) - DIMM 1, Card 1
Type de mmoire SDRAM DDR2
Description DIMM SPS-MEM DIMM, 1GB, PC2-3200, 128Mx4
Numro de pice de rechange 359242-001
Dpassement du seuil de bit unique -
tat
Seuil d`erreurs corrigeables dpass
tat des bits multiples Aucune erreur DIMM dtecte

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 58 sur 77

58
Seuil de bit unique 4
Nombre de bits multiples 0
Informations SPD (Serial Presence Detect) - DIMM 2, Card 1
Type de mmoire SDRAM DDR2
Description DIMM SPS-MEM DIMM, 1GB, PC2-3200, 128Mx4
Numro de pice de rechange 359242-001
Dpassement du seuil de bit unique -
tat
Seuil d`erreurs corrigeables dpass
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 16
Nombre de bits multiples 0
Informations SPD (Serial Presence Detect) - DIMM 3, Card 1
Type de mmoire SDRAM DDR2
Description DIMM SPS-MEM DIMM, 1GB, PC2-3200, 128Mx4
Numro de pice de rechange 359242-001
Dpassement du seuil de bit unique -
tat
Seuil d`erreurs corrigeables dpass
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 1
Nombre de bits multiples 0
Informations SPD (Serial Presence Detect) - DIMM 4, Card 1
Type de mmoire SDRAM DDR2
Description DIMM SPS-MEM DIMM, 1GB, PC2-3200, 128Mx4
Numro de pice de rechange 359242-001
Dpassement du seuil de bit unique -
tat
Seuil d`erreurs corrigeables dpass
tat des bits multiples Aucune erreur DIMM dtecte
Seuil de bit unique 3
Nombre de bits multiples 0
Units de stockage
Contrleur RAID, HP SA6i, Connecteur 0 HP SA6i
Modle HP SA6i
Microprogramme 2.58
Units logiques configures 2
Taille totale de la mmoire 64 Mgaoctets
Carte mmoire RAM utilisable 32 Mgaoctets
Modle du fond de panier COMPAQ PROLIANT 6L2I
Rvision du fond de panier 0.20
Numro de srie
Numro de connecteur PCI 0
BIOS boot device order 1
Volume logique 0, Contrleur Connecteur 0 Bus 0 72.8 Gigaoctets RAID 0
Code d`tat 0
Description de l`tat OK
Modle HP LOGICAL VOLUME
Microprogramme 2.58
Capacit 72.8 Gigaoctets
Chemin du priphrique \\.\SCSI3:

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 59 sur 77

59
ID du volume 0
Tolrance aux dfaillances RAID 0
Paramtres d`unit logique
Nombre d`units de contrleur 4
Nombre d`units de volume 1
Table des paramtres d`units
Taille de stripe (blocs physiques) 256
Disque dur physique 1, Contrleur Connecteur 0 72.8 Gigaoctets 10K RPM - COMPAQ BD07289BB8
Modle COMPAQ BD07289BB8
Microprogramme HPB1
Capacit 72.8 Gigaoctets
Contrleur Contrleur RAID, HP SA6i, Connecteur 0
Bus 1
Unit 0
Lun 0
Vitesse de rotation 10K RPM
Numro de srie DAL1P63078D40610
Temprature 29 Degrees Celsius
Configuration du cble
Chemin de donnes 16 bits sur un cble avec 16 ID SCSI
pris en charge
Connecteur J1
Numro de botier 0
Baie de botier 0
Type d`unit Disque dur SCSI
Vitesse relle du bus Ultra-320 (320 MHz)
Erreurs de lecture graves 00000000
Erreurs de lecture (nouvel essai russi) 00000001
Erreurs d`criture graves 00000002
Erreurs d`criture (nouvel essai russi) 00000001
Erreurs de panne prdictive 00000000
Unit prsente et oprationnelle Oui
Secteurs crits 00000008d9d59104
Volume logique 1, Contrleur Connecteur 0 Bus 0 218.5 Gigaoctets RAID 0
Code d`tat 0
Description de l`tat OK
Modle HP LOGICAL VOLUME
Microprogramme 2.58
Capacit 218.5 Gigaoctets
Chemin du priphrique \\.\SCSI3:
ID du volume 0
Tolrance aux dfaillances RAID 0
Paramtres d`unit logique
Nombre d`units de contrleur 4
Nombre d`units de volume 3
Table des paramtres d`units
Taille de stripe (blocs physiques) 256
Disque dur physique 2, Contrleur Connecteur 0 72.8 Gigaoctets 10K RPM - COMPAQ BD07289BB8

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 60 sur 77

60
Modle COMPAQ BD07289BB8
Microprogramme HPB1
Capacit 72.8 Gigaoctets
Contrleur Contrleur RAID, HP SA6i, Connecteur 0
Bus 1
Unit 1
Lun 0
Vitesse de rotation 10K RPM
Numro de srie DAL1P63084R50613
Temprature 29 Degrees Celsius
Configuration du cble
Chemin de donnes 16 bits sur un cble avec 16 ID SCSI
pris en charge
Connecteur J1
Numro de botier 0
Baie de botier 1
Type d`unit Disque dur SCSI
Vitesse relle du bus Ultra-320 (320 MHz)
Erreurs de lecture graves 00000000
Erreurs de lecture (nouvel essai russi) 00000000
Erreurs d`criture graves 00000002
Erreurs d`criture (nouvel essai russi) 00000000
Erreurs de panne prdictive 00000000
Unit prsente et oprationnelle Oui
Secteurs crits 0000001191c8c3b0
Contrleur Fibre Channel, Connecteur 6 ISP 2312 Fibre Channel Adapter
Modle ISP 2312 Fibre Channel Adapter
Nombre de canaux SCSI signals par le contrleur 1
ID de la carte 01001077h
Bus PCI 22
Numro de priphrique PCI 1
Numro de fonction PCI 0
Numro de connecteur PCI 6
Connecteur 6
BIOS boot device order 3
Disques logiques
C: Disque logique 1 ~ 72.83GB
Nom de volume
Systme de fichiers NTFS
Taille (octet) 72825303040
Espace libre (octet) 28600688640
E: Disque logique 2 ~ 218.50GB
Nom de volume VM
Systme de fichiers NTFS
Taille (octet) 218496839680
Espace libre (octet) 117429497856


RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 61 sur 77

61
HP Insight Diagnostics Version 8.1.5.2890A
Nom de l'ordinateur: SONL01DBSQL01PR
Gravit Classe
Dernire mise
jour
Premire mise
jour
Compt
age
Description
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired Machine 8/03/2010 5:55 8/03/2010 5:55 1 Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 62 sur 77

62
Gravit Classe
Dernire mise
jour
Premire mise
jour
Compt
age
Description
Environment Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 63 sur 77

63
Gravit Classe
Dernire mise
jour
Premire mise
jour
Compt
age
Description
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage
Repaired
Machine
Environment
8/03/2010 5:55 8/03/2010 5:55 1
Overheat - Chassis Name: SGM05143JD - Temp: 255 - Fan Zone Type:
Storage - Zone Id: 255 - Chassis Id: 6 - Chassis Port: 255 - Chassis Type:
External storage


RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 64 sur 77

64
b. DONNEES ENVIRONNEMENTALE

ID BAIE
TEMP
baie 43 baie 42 baie 41 baie 45 baie 46 baie 48 baie 49 baie 50 baie 52 baie 53 baie 55
T front UP 30 C 27 C 28 C 23 C 23 C 26 C 28 C 28 C 27 C 25 C 28 C
T front middle 27 C 32 C 27 C 23 C 23 C 24 C 23 C 25 C 24 C 24 C 25 C
T front down 27 C 26 C 23 C 23 C 22 C 23 C 24 C 24 C 23 C 23 C 24 C
T rear UP 29 C 29 C 29 C 22 C 22 C 28 C 30 C 26 C 27 C 25 C 28 C
T rear middle 29 C 29 C 28 C 22 C 24 C 29 C 27 C 30 C 25 C 26 C 27 C
T rear down 33 C 25 C 26 C 23 C 22 C 25 C 28 C 34 C 23 C 26 C 27 C
voltage 1 226,5 V 226,5 V 227,2 V 226,5 V 227,5 V 226,5 V 226,1 V 227,4 V 226,3 V 225,4 V
voltage 2 226,6 V 226,4 V 227,3 V 226 V 227,6 V 225,8 V 225,7 V 227,2 V 226,3 V 225,6 V
voltage 3 226,7 V 226 V 227,3 V 226,6 V 227,6 V 226,5 V 226,1 V 227,3 V 226,5 V 225,9 V
ground-neutre 1,4 V 1,5 V 1,4 V 1,6 V 1,5 V 1,5 V 1,6 V 1,5 V 1,6 V 1,5 V
equipements
installs
10 dl380g5
02 citrix
netscaler mpx
01 dl380g6 02 dl580g5 02 dl580g2 04 dl360g5 04 ibm x3550 02 dl580g4 03 dl160g5 05 dl580g3 06 dl580g5
03 dl380g6 02 dl580g5
02 netapp
ds4243
02 dl160g5 02 dl320g2 03 dl360g5 02 dl580g5 01 ultirum 460 01 dl380g6 01 dl160g6
02 dl360g5 01 dl580g7
01 quantum
dx5000
04 dl160g5 02 dl360g3 01 dl360g5
01 hp nas
e7000
02 dl740 01 dl380g7
02 dl160g6 02 dl785g6
01 quantum
scalar i500
01 ibm x366 01 dl320s 01dl160g2 01 msa 60 01msl6000 01MSA1000
01 boitier citrix 01 dl380g6 02 dl360g3 02 dl580g2
05 cisco
mcs7800
01 unitrend
dpu


RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 65 sur 77

65
03 dl320g3 03 dl740
01 quantum
dx5000

02 ml370g2
01 hp nas
e7000

01 quantum
scalar i500

01 dl380g4
T ambiante 22C


RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 66 sur 77

66
IV. ANALYSE DES DONNEES
Serveur HP PROLIANT dl320s G1, adresse IP : 10.250.90.4
DESIGNATION S/N T systme T SEUIL IP ADDRESS ALIMENTATION version BIOS NVELLE VERSION
HP PROLIANT DL320S USE826N230 CPU 34C 10.250.90.4 REDONDANTE HOTPLUG W04 W04
CPU 28C
CPU 28C
AMBIANT 27C 35C

DESIGNATION P/N S/N DUREE FONCTIONNEMENT TEMP DISQUE
VERSION
FW
FW A
JOUR STATUS
HP SMART ARRAY P400

P61630K9SW31RO 5.20 7.22 BATTERY TO BE REPLACED
HP SATA 250G 7.2K GB0250EAFJF 9SF0SDJS 24265 N/A HPG6 HPGC
HP SATA 250G 7.2K GB0250C8045 9SF0BLNR 35858 N/A HPG1 HPG8
HP SATA 250G 7.2K GB0250C8045 9SF0B83E 35858 N/A HPG1 HPG8
HP SATA 250G 7.2K GB0250C8045 9SF0A4SQ 35858 N/A HPG1 HPG8
HP SATA 250G 7.2K GB0250C8045 9SF0BFAE 35545 N/A HPG1 HPG8 FAILED

RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 67 sur 77

67
HP SATA 250G 7.2K GB0250C8045 9SF0B8AW 35545 N/A HPG1 HPG8
HP SATA 250G 7.2K GB0250EAFJF 9SF0SEFE 35858 N/A HPG6 HPGC
HP SATA 250G 7.2K GB0250C8045 9SF0B7V5 24718 N/A HPG1 HPG8
HP SATA 250G 7.2K GB0250EAFJF 9SF0S089 35857 N/A HPG6 HPGC
HP SATA 250G 7.2K GB0250C8045 9SF0BMDL 35073 N/A HPG1 HPG8 FAILED
HP SATA 250G 7.2K GB0250C8045 9SF0BB29 24582 N/A HPG1 HPG8
HP SATA 250G 7.2K GB0250C8045 9SF09QZ8 35073 N/A HPG1 HPG8

Ce serveur presente des caractristiques de fonctionnement normales.
La temperature ambiante de 27c est comprises dans la plage de temperature admise (10C 35C)
Le controleur HP SMART ARRAY P400, presente un defaut de la batterie cache qui doit etre remplace. Le firmware du controleur nest
pas a jour.
12 disques durs SATA de 250G sont presents dans le serveur.
Parmi les 12 disques installs, 09 disques fonctionnent depuis plus de 35000h (soit env 4 ANS) et 03 disques fonctionnent depuis plus
de 24 000h (soit env 2ans et 8 mois)
02 de ces disques sont defectueux et doivent etre remplac
La totalite des disques nont pas de firmware jour
Une alerte de temperature lev t dtect sur le serveur en septembre 2010

RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 68 sur 77

68
Serveur HP PROLIANT dl360 G3, adresse IP : 10.250.90.15
DESIGNATION S/N T systme T SEUIL IP ADDRESS ALIMENTATION version BIOS NVELLE VERSION
HP PROLIANT DL360G3 10.250.90.15 N/A


DESIGNATION P/N S/N DUREE FONCTIONNEMENT TEMP DISQUE
VERSION
FW
FW A
JOUR STATUS
HP SMART ARRAY 5i M00TLGP53B 2.66 2.72
HP SCSI 72GB 10K BD07285A25 3HZ9QTJG00007522FEZG HPB8 HPB8 PREDICTIVE FAILURE
HP SCSI 72GB 15K BF0728B26A 3LQ0D7Z8000097281C78 HPB9 HPB9

Nous navons pas pu obtenir les donnees de temprerature sur ce serveur cause des restrictions daccs.
La temperature ambiante de 27c est comprises dans la plage de temperature admise (10C 35C)
Le controleur HP SMART ARRAY 5i, na pas un firmware a jour.
2 disques durs SCSI de 72G sont presents dans le serveur, parmi lesquels, 01 doit etre remplac


RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 69 sur 77

69
Serveur HP PROLIANT dl360 G5, adresse IP : 10.250.10.68
DESIGNATION S/N T systme T SEUIL IP ADDRESS ALIMENTATION version BIOS NVELLE VERSION
HP PROLIANT DL360G5 CZJ849A20B IO BOARD 43C 70C 10.250.90.68 ALIM 1 REDONDANTE HOTPLUG P58 P58
CPU 30C 127C ALIM 2 HS
CPU 30C 127C
POWER 28C 77C
AMBIANT 19C 39C

DESIGNATION P/N S/N DUREE FONCTIONNEMENT TEMP DISQUE
VERSION
FW
FW A
JOUR STATUS
Smart Array E200i PR8BMP5520 1.78 1.86
HP SAS 146Go 10K HP DG146BB976 3NM7Q39200009913LSY7 35073 30C HPDC HPDC PREDICTIVE FAILURE
HP SAS 146Go 10K HP DG146BB976 3NM7PYRD00009913K65H 35073 29C HPDC HPDC OK

La temperature ambiante de 19c est comprises dans la plage de temperature admise (10C 39C)
Le controleur HP SMART ARRAY E200i est jour.
02 disques durs sas de 146Go avec des firmware a jour sont install dans le serveur, et 01 disque dur est a remplac
Les 02 disques fonctionnent depuis plus de 35000h (soit env 4 ANS)
Le serveur a connu beaucoup darret brusque li la surchauffe entre 2009 et 2010, et signale jusqu ce jour un defaut dalimentation
redondante.

RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 70 sur 77

70
Serveur HP PROLIANT dl380 G5, adresse IP : 10.250.90.94
DESIGNATION S/N T systme T SEUIL IP ADDRESS ALIMENTATION version BIOS NVELLE VERSION
HP PROLIANT DL380G5 CZC8476HW1 IO BOARD 39C 70C 10.250.90.94 ALIM 1 REDONDANTE HOTPLUG P56 P56
CPU 30C 127C ALIM 2 HS
CPU 30C 127C
POWER 42C 77C
AMBIANT 19C 39C

DESIGNATION P/N S/N
DUREE
FONCTIONNEMENT TEMP DISQUE
VERSION
FW
FW A
JOUR STATUS
HP SA P400 PAFGL0M9VWI0BF 5.2 7.22
HP SAS 146Go 10K HP DG146BB976 3NM7Q3CF00009910VQAW 35210 31c HPDC HPDC
HP SAS 146Go 10K HP DG146BB976 3NM7P5DR00009912YB5R 35210 31c HPDC HPDC

Ce serveur presente des caractristiques de fonctionnement normales.
La temperature ambiante de 19c est comprises dans la plage de temperature admise (10C 39C)
Le firmware du controleur HP SMART ARRAY P400 nest pas jour.
02 disques durs sas de 146Go avec des firmware a jour sont install dans le serveur,Les 02 disques fonctionnent depuis plus de 35000h
(soit env 4 ANS)
Le serveur a connu beaucoup darrets brusque li la surchauffe entre 2009 et 2010, et signale jusqu ce jour un defaut dalimentation
redondante.

RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 71 sur 77

71
Serveur HP PROLIANT dl380 G5, adresse IP : 10.250.90.133
DESIGNATION S/N T systme T SEUIL IP ADDRESS ALIMENTATION version BIOS NVELLE VERSION
HP PROLIANT DL380G5 CZC8476HTH IO BOARD 37C 70C 10.250.90.133 ALIM 1 REDONDANTE HOTPLUG P56 P56
CPU 30C 127C ALIM 2 HS
CPU 30C 127C
POWER 42C 77C
AMBIANT 18C 39C

DESIGNATION P/N S/N DUREE FONCTIONNEMENT TEMP DISQUE
VERSION
FW
FW A
JOUR STATUS
HP SA P400 PAFGL0M9VWK0J7 5.2 7.22
HP SAS 146Go 10K HP DG146BB976 3NM7NQ1E00009912VFXG 35055 31C HPDC HPDC
HP SAS 146Go 10K HP DG146BB976 3NM7QKTV00009913LHP9 35074 29C HPDC HPDC

Ce serveur presente des caractristiques de fonctionnement normales.
La temperature ambiante de 19c est comprises dans la plage de temperature admise (10C 39C)
Le firmware du controleur HP SMART ARRAY P400 nest pas jour.
02 disques durs sas de 146Go avec des firmware jour sont install dans le serveur
Les 02 disques fonctionnent depuis plus de 35000h (soit env 4 ANS)
Le serveur a connu beaucoup darret brusque li la surchauffe entre 2009 et 2010, et signale jusqu ce jour un defaut dalimentation
redondante.

RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 72 sur 77

72

Serveur HP PROLIANT dl580 G2, adresse IP : 10.250.90.117
DESIGNATION S/N T systme T SEUIL IP ADDRESS ALIMENTATION version BIOS NVELLE VERSION
HP PROLIANT DL580G2 A22APBFOUQSS IO BOARD 26C 51C 10.250.90.117 ALIM 1 REDONDANTE HOTPLUG P27 P27
CPU 33C 68C ALIM 2 HS
CPU 32C 68C
MEMORY 29C 52C

DESIGNATION P/N S/N DUREE FONCTIONNEMENT TEMP DISQUE
VERSION
FW
FW A
JOUR STATUS
HP SA 5i 2.58 2.72
HP SCSI 300Go 10K BD3008A4C6 3KR462SW000097524MA6 HPB4 HPB4
HP SCSI 300Go 10K BD3008A4C6 3KR4GPNP0000981100TJ HPB4 HPB4
HP SCSI 72Go 10K BD07286224 UPD6P3701BHC0329 HPB6 HPB6
HP SCSI 72Go 10K BD07289BB8 DAL1P63073MP0610 55268 HPB1 HPB1

Ce serveur presente des caractristiques de fonctionnement normales.
La temperature ambiante de 26c est comprises dans la plage de temperature admise (10C 39C)
Le firmware du controleur HP SMART ARRAY 5i nest pas jour.
02 disques durs SCSI de 300Go et 02 disques durs SCSI de 72Go avec des firmware jour sont installs dans le serveur
01 des disques fonctionne depuis plus de 55000h (soit plus de 06 ANS)
Le serveur de possede pas dalimentation redondante

RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 73 sur 77

73

Serveur HP PROLIANT dl580 G3, adresse IP : 10.250.90.58
DESIGNATION S/N T systme T SEUIL IP ADDRESS ALIMENTATION version BIOS NVELLE VERSION
HP PROLIANT DL580G3 GB86132Y8J IO BOARD 27C 60C 10.250.90.58 ALIM 1 REDONDANTE HOTPLUG P38 P38
CPU 46C 80C ALIM 2 HS
CPU 47C 80C
BOARD 31C 60C
AMBIANT 20C 40C

DESIGNATION P/N S/N DUREE FONCTIONNEMENT TEMP DISQUE
VERSION
FW
FW A
JOUR STATUS
HP SA 6i 2.58 2.72 OK
HP SCSI 72Go 10K BD07289BB8 DAL1P63078D40610 57487 HPB1 HPB1 OK
HP SCSI 72Go 10K BD07289BB8 DAL1P63084R50613 57487 HPB1 HPB1 OK
HP SCSI 72Go 10K BD07289BB8 DAL1P630882M0613 57401 HPB1 HPB1 OK
HP SCSI 72Go 10K BD07289BB8 DAL1P63089JU0613 57487 HPB1 HPB1 OK

Ce serveur presente des caractristiques de fonctionnement normales.
La temperature ambiante de 20c est comprises dans la plage de temperature admise (10C 39C)
Le firmware du controleur HP SMART ARRAY 5i nest pas jour.
04 disques durs SCSI de 72Go avec des firmware jour sont installs dans le serveur
01 des disques fonctionne depuis plus de 57000h (soit plus de 06 ANS et demi)
Le serveur de possede pas dalimentation redondante
Le serveur a connu des probleme de temperature en mars 2010

RAPPORT DAUDIT SUR LA CAUSE DE PANNES RECURRENTES DE
DISQUES DURS SUR LES SERVEUR DU DATACENTER

Douala le 07 fevrier 2013 MISE A DISPOSITION DUN EXPERT HP Page 74 sur 77

74
DONNEES ENVIRONNEMENTALES DU DATACENTER
Les mesures de temperature prises au datacenter, nont pas revele danomalie particuliere.
Certes, certaines baies (notamment la baie 43 et la baie 50) pnt des relev de temperature proche de la limite fixe 35C par le constructeur.

Les mesures de tension prise dans chacune des baies se sont averes elles aussi normale.

ANALYSE PHYSIQUE DUN ECHANTILLON DE DISQUES DEFECTUEUX
Nous avons obtenu de AES SONEL la possibilit danlyser dans nos laboratoires, 6 disques durs defectueux parmi lesquels
03 disques dur de type SAS SFF
03 disque dur de type SATA LFF


Nous avons constateraucune trace de choc physique ou de choc electrique.
Cependant nous avons constater que certains disque dur signals comme defectueux, fonctionnaient normalement sur nos serveurs.

RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 75 sur 77



75
V. CONCLUSION

Au terme de notre analyse, sommes arrivs aux conclusions suivantes :
Aucun facteurs environnnemental de nature a cre les pannes sur les disques durs na t relev. .
Lenvironnement actuel du DATACENTER (temprature, nergie electrique) respecte les standards du
contructeur HP
La majorit des serveurs ont par le pass (entre 2009 et 2010) connu des problemes de surchauffe
qui ont occasionn a plusieurs reprises les arrets brusque des serveurs. Ces temperature atteignait
gnralement 40C, soit 5C au dessus du seuil de temperature support par les disques. Ces incident
ont pu fragiliser les disques durs, et meme les composants internes des serveurs
Beaucoup des serveurs, controlleur de stockage et disques dur nont pas de firmware a jour. Cet etat
peut altrer le fonctionnement optimal du systme et conduire le systme a effectuer des faux
diagnostic dtat des disques.
Le serveur de stockage HP 320S, utilise des disques durs SATA, qui ne sont pas destins des
utilisations intensives en entreprise. Cela peut se verifier par le nombre important drreurs de
lecture journaliss sur ces disques.
Il nous a t difficile dobtenir lhistorique de tous les incidents survenu sur chaque serveur du
DATACENTER, ceci peut due la confidentialit de ces information, et meme les journaux systme
ne nous ont pas aid parceque lespace a eux allou ne permet pas de tracer des evenement vieux de
plus de 6 mois, ce qui nous a empecher de comprendre par exemple pourquoi sur le serveur de
stockage DL320s, le disque dur le plus recent tourne dessus depuis 2 ans et demi, alors quil nous a
t rapporte des remplacement rcent de disques sur ce serveur.
Les outils de management sytmes HP ne sont pas systmatiquement installs et configur sur les
serveurs, encore moins lagent HP version control repository manager qui permet dobtenir
automatiquement les mises jour de software et firmware des composants installs dans les
serveurs.
Il est impossibe dobtenir des donnes sur lenvironnement du DATA CENTER pour une priode vieille
de 5 jours ou plus, ceci du une limitation du systme de monitoring du DATACENTER.
Les composants hardwares internes aux serveurs ne sont pas monitor en permanence, ce qui ne
permet dobtenir un historique de toutes les alertes survenu sur les lments dun serveur sur une
priode donne.


RAPPORT DAUDIT SUR LA CAUSE DE PANNES
RECURRENTES DE DISQUES DURS SUR LES
SERVEUR DU DATACENTER

Douala le 07 fevrier 2013
MISE A DISPOSITION DUN EXPERT HP Page 76 sur 77



76

VI. RECOMMANDATIONS
Suite nos analyses, nous recommandons a AES les action suivantes :

1) Mettre jours tous les drivers, softwares, firmwares des serveurs installs dans le
datacenter.
2) Installer et configurer un serveur HP INSIGHT MANAGEMENT, pour le monitoring,
le diagnostic et lemission dalertes en cas de danomalies detect sur les serveurs
3) Tenir un cahier de maintenance qui permettra de retracer chaque incident survenu dans
le datacenter
4) Meetre en place un serveur de LOG pour le monitoring et larchivage des donnes
denvironnement dans le datacenter
5) Configurer le HP repository agent pour la mise a jour automatique des softwares et
firmwares des serveurs et de leur composants
6) Remplacer les disques dur SATA du serveur PROLIANT DL320S par des disques dur
SAS, plus robustes et plus performant.