DATA SHEET
#NPR050
Description
The Bladder Tank Proportioning System is a balanced
pressure proportioning system, requiring no external power
other than an adequate water supply. A bladder tank, with
an appropriate proportioner(s), injects foam concentrate
into the water supply of a fire protection system and
automatically proportions over a wide range of flows and
pressures.
The Bladder Tank Proportioning System employs water
to pressurize the bladder and force foam concentrate to
the ratio controller. The water supply simultaneously feeds
the ratio controller and the bladder tank. As water flows
through the ratio controller the level of pressure reduction
increases, thereby affecting a corresponding pressure
drop across the foam concentrate metering orifice. The
corresponding pressure drop results in foam concentrate
flow that is proportionate to the water flow through the ratio
controller. As both the water and foam concentrate flow into
a common reduced pressure area, it is necessary only to
maintain identical water and foam concentrate pressures
at the respective inlets of the ratio controller.
During operation, the water outside the bladder gradually
displaces the foam concentrate inside causing the bladder
to collapse until the supply is exhausted. The bladder tank
may then be isolated and the system allowed to discharge
water only. Since the bladder tank is pressurized, the
bladder should not be refilled during operation.
Features
Compatible with all foam concentrates
Requires less floor space than horizontal tanks
Bottom foam concentrate discharge keeps feed piping
full, eliminating air pockets and preventing corrosion
Permanently welded lifting lugs
Applications
Pre-Piped
Technical Specifications
www.Kidde-Fire.com
Technical Information
Materials of Construction:
Tank: Carbon steel, ASME code
Bladder: Thermoplastic vulcanized rubber
Options
Fill kit
Automatic concentrate valve
RATIO CONTROLLER
"A"
CONTRACTOR
P.O.C. SEE TABLE 4
FOR RC
CONNECTION
SIZE AND TYPE
CONTRACTOR
P.O.C. SEE TABLE 4
FOR RC
CONNECTION
SIZE AND TYPE
7-3/4
"B"
8-3/4
LIFTING
LUG
FILL FUNNEL
TO BE SCREWED
INTO VALVE #5
SEE NOTE #9
INSTALLATION
INSTRUCTION
LABEL
CHECK
VALVE
WATER
FEED
"H"
"J"
CAUTION LABEL
"G"
U.L. AND
F.M. LABELS
"C"
CONC. LEVEL
CHECK LABEL
1A
11-7/8
8
6
2" RC ASSEMBLY
"F"
90
TYP.
"E"
HOLE
(TYP. 4)
Valve
No.
1
"D"
BOLT
CIRCLE
1A
DETAIL A - A
9
9
SIGHT GLASS
(OPTIONAL)
7
DETAIL B - B
45
TYP.
1-3/4
5-1/8
"K"
OPERATING
INSTRUCTIONS
8
SIGHT GLASS
(OPTIONAL)
Normal Position
Description
Concentrate Shutoff
Auto. Concentrate Shutoff (Optional)
Manual System
Auto. System
Closed
Open
---
Closed
Open
Open
Closed
Closed
Concentrate Vent/Fill
Closed
Closed
Water Drain/Fill
Closed
Closed
Concentrate Drain/Fill
Closed
Closed
Closed
Closed
Open
Open
DETAIL C - C
NPR050
25 (95)
36 (136)
50 (189)
100 (379)
150 (568)
200 (757)
300 (1136)
400 (1514)
500 (1892)
600 (2271)
700 (2649)
750 (2839)
800 (3028)
900 (3407)
1000 (3785)
1100 (4164)
1200 (4542)
1300 (4921)
1400 (5300)
1500 (5678)
1600 (6057)
1700 (6435)
1800 (6814)
1900 (7192)
2000 (7571)
2100 (7949)
2200 (8328)
2300 (8706)
2400 (9085)
20 (508)
24 (610)
24 (610)
24 (610)
30 (762)
30 (762)
36 (914)
48 (1219)
48 (1219)
48 (1219)
48 (1219)
48 (1219)
60 (1524)
60 (1524)
60 (1524)
60 (1524)
60 (1524)
60 (1524)
60 (1524)
60 (1524)
72 (1829)
72 (1829)
72 (1829)
72 (1829)
72 (1829)
72 (1829)
72 (1829)
72 (1829)
72 (1829)
22 (559)
24 (610)
24 (610)
24 (610)
27 (686)
27 (686)
30 (762)
36 (914)
36 (914)
36 (914)
37-1/2 (953)
37-1/2 (953)
43-1/2 (1105)
43-1/2 (1105)
43-1/2 (1105)
43-1/2 (1105)
43-1/2 (1105)
43-1/2 (1105)
43-1/2 (1105)
43-1/2 (1105)
49-1/2 (1257)
49-1/2 (1257)
49-1/2 (1257)
49-1/2 (1257)
49-1/2 (1257)
49-1/2 (1257)
49-1/2 (1257)
49-1/2 (1257)
49-1/2 (1257)
46 (1168)
46 (1168)
46 (1168)
85 (2159)
82 (1561)
100 (2540)
103 (2616)
83 (2108)
97 (2464)
112 (2845)
126 (3200)
134 (3404)
102 (2591)
110 (2794)
120 (3048)
130 (3302)
140 (3556)
150 (3810)
158 (4013)
167 (4242)
134 (3404)
140 (3556)
147 (3734)
153 (3886)
160 (4064)
166 (4216)
173 (4394)
179 (4547)
186 (4724)
22-3/4 (578)
22-3/4 (578)
22-3/4 (578)
22-3/4 (578)
27-3/4 (705)
27-3/4 (705)
32-3/4 (832)
41-1/2 (1054)
41-1/2 (1054)
41-1/2 (1054)
41-1/2 (1054)
41-1/2 (1054)
51-1/2 (1308)
51-1/2 (1308)
51-1/2 (1308)
51-1/2 (1308)
51-1/2 (1308)
51-1/2 (1308)
51-1/2 (1308)
51-1/2 (1308)
57-1/2 (1461)
57-1/2 (1461)
57-1/2 (1461)
57-1/2 (1461)
57-1/2 (1461)
57-1/2 (1461)
57-1/2 (1461)
57-1/2 (1461)
57-1/2 (1461)
9/16 (14)
9/16 (14)
9/16 (14)
9/16 (14)
9/16 (14)
9/16 (14)
9/16 (14)
11/16 (17)
11/16 (17)
11/16 (17)
11/16 (17)
11/16 (17)
11/16 (17)
11/16 (17)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
13/16 (21)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
8 (203)
49 (1245)
50 (1270)
58 (1473)
87 (2210)
86 (2184)
104 (2642)
108 (2743)
91 (2311)
105 (2667)
120 (3048)
134 (3404)
142 (3607)
113 (2870)
122 (3099)
132 (3353)
141 (3581)
150 (3810)
160 (4064)
169 (4293)
178 (4521)
144 (3658)
150 (3810)
157 (3988)
163 (4140)
170 (4318)
176 (4470)
183 (4648)
189 (4801)
196 (4978)
Notes:
1. All dimensions are approximate and may vary slightly.
2. Weights listed apply to empty tanks.
3. All tank and valve openings will be plugged for
shipping.
4. Optional sight glass assembly includes:
Polycarbonate sight glass tube, 1" (38) O.D. open
to atmosphere (vented cap)
Ball shutoff valve
Split pipe clamp w/ threaded rod
5. Fill funnel and optional sight glass tube will be packed
and shipped separately.
6. Optional sight glass level check cannot be performed with
alcohol type AFFF concentrates. Refer to the operating
and maintenance manual for further instructions.
7. Contents label will be supplied to customer by NF and
applied by customer to area provided on caution label.
8. When designing a building to house bladder tanks,
provisions must be to allow for the removal of the
internal piping and bladder. These items are the full
height of tank.
9. Concentrate vent valve #5 will also be used to top off the
concentrate level. A fill funnel will be provided with each
tank for this purpose.
10. For non-standard or special tanks, refer to the tanks
specific outline assembly drawing for details.
TABLE 3 - RC DIMENSIONS
H
3" RC
4" RC
6" RC
8" RC
19
25
27
31
4
4-1/4
5-1/4
7
4-1/2
7
9-11/16
10
NPR050
Assembly w/ Spool
Standard
Flow
Range
gpm (lpm)
Special
Flow Range
with AR-AFFF
Foam Conc.
gpm (lpm)
30-180
60-180
(114-681)
(227-681)
70-450
170-450
(265-1703)
(644-1703)
150-1200
320-1200
(568-4542)
(1211-4542)
300-2500
700-2500
(1136-9463)
(2650-9463)
850-5000
1400-5000
(3218-18925) (5300-18925)
Water &
Conc.
Line
Sizes
in. (mm)
1 (25)
1-1/4 (32)
1-1/2 (38)
2 (51)
2-1/2 (64)
Ratio Controller
Connections
in. (mm)
Inlet
Outlet
2 (51)
NPT (F)
3 (76)
FF flg.
4 (102)
FF flg.
6 (152)
FF flg.
8 (203)
FF flg.
2 (51)
NPT (F)
3 (76)
FF flg.
4 (102)
FF flg.
6 (152)
FF flg.
8 (203)
FF flg.
3
Ordering Information
Capacity
gal.
liters
Part Number
w/o sight gauge
Part Number
w/ sight gauge
25
36
50
100
150
200
300
400
500
600
700
750
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
95
136
189
379
568
757
1136
1514
1892
2271
2649
2839
3028
3407
3785
4164
4542
4921
5300
5678
6057
6435
6814
7192
7571
7949
8328
8706
9085
1218-2133-6
1218-2133-7
1218-2128-0
1218-2128-1
1218-2128-2
1218-2128-3
1218-2128-4
1218-2128-5
1218-2128-6
1218-2128-7
1218-2128-8
1218-2133-8
1218-2128-9
1218-2129-0
1218-2129-1
1218-2129-2
1218-2129-3
1218-2129-4
1218-2129-5
1218-2129-6
1218-2129-7
1218-2129-8
1218-2129-9
1218-2133-0
1218-2133-1
1218-2133-2
1218-2133-3
1218-2133-4
1218-2133-5
1218-2132-6
1218-2132-7
1218-2130-0
1218-2130-1
1218-2130-2
1218-2130-3
1218-2130-4
1218-2130-5
1218-2130-6
1218-2130-7
1218-2130-8
1218-2132-8
1218-2130-9
1218-2131-0
1218-2131-1
1218-2131-2
1218-2131-3
1218-2131-4
1218-2131-5
1218-2131-6
1218-2131-7
1218-2131-8
1218-2131-9
1218-2132-0
1218-2132-1
1218-2132-2
1218-2132-3
1218-2132-4
1218-2132-5
Empty Weight
Approx. Shipping
lb
kg
ft3
m3
150
220
307
465
620
757
1101
1504
1560
1669
1799
1900
2004
2334
2730
3823
3221
3340
3459
3510
3600
3725
3850
3975
4100
4225
4350
4475
4600
68
100
139
211
281
343
499
682
708
757
816
862
909
1059
1238
1734
1461
1515
1569
1592
1633
1690
1746
1803
1860
1916
1973
2030
2087
20
25
28.3
41.7
66.5
85.6
118.8
157
162.6
203.1
217.1
231.1
245.1
285.3
322.1
353.3
384.5
399
413.1
441.6
475
500
525
550
575
600
625
650
675
0.57
1.71
0.8
1.18
1.88
2.42
3.36
4.45
4.6
5.75
6.15
6.54
6.94
8.08
9.12
10
10.89
11.29
11.7
12.51
13.45
14.16
14.87
15.57
16.28
16.99
17.7
18.41
19.11
Proportioner
Size
Tank Size
(gal.)
Part
Number
lb
kg
2"
2"
3"
3"
4"
4"
6"
6"
8"
8"
50 to 400
500 to 1500
50 to 400
500 to 1500
50 to 400
500 to 1500
50 to 400
500 to 1500
50 to 400
500 to 1500
5000-4100-0
5000-4110-0
5000-4120-0
5000-4130-0
5000-4140-0
5000-4150-0
5000-4160-0
5000-4170-0
5000-4180-0
5000-4190-0
49
49
110
110
147
147
210
210
323
323
22.23
22.23
49.9
49.9
66.68
66.68
95.26
95.26
146.52
146.52
This information is only a general guideline, and each installation may require modifications to meet the applications or requirements of that situation. The
company reserves the right to change any portion of this information without notice. Terms and conditions of sale apply and are available on request.
02/12 (Rev. K) Printed in U.S.A. (NPR050.INDD)