-----------------------------------------------------------------------------------------x100 =
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-60 2008 PdMA Corporation REV. 0-04/08
FLA = full load amp rating of asset
Vl = line voltage
100 = converts number to percentage
When voltage applied across three-phase asset leads is unbalanced, circulating currents,
called negative sequence currents, are induced. When these negative sequence currents
are present, they cause heating in the windings. EPRIs (the Electric Power Research
Institute) Handbook to Assess the Insulation Condition of Large Rotating Machines states
a 3.5% voltage imbalance can raise winding temperature 25% in the winding(s) affected
by such currents. EASA (the Electrical Apparatus Service Association) says a 1%
voltage imbalance results in a 6-7% current imbalance.
The most extreme case of resistive imbalance occurs when a asset single phases. This
single phasing quickly causes the asset to fail because the remaining two phases
compensate by increasing current by 200% to 300% of normal. Rapid heating of the
windings which are still connected destroys the insulation surrounding them.
Resistance to the flow of current in a circuit is of concern from the standpoints of safety,
energy conservation, and insulation life. High resistance points in conductors generate
heat both at the point where the resistance is located and in the three-phase assets being
supplied.
Regardless of the source, some of the effects of increased heat production in the asset
include:
Higher resistance due to heat in conductor materials adjacent to the fault
Deterioration (accelerated aging) of the surrounding and supporting insulating
materials
Imbalance in multi-phase circuits, which adversely affects equipment
performance and life
Increased power consumption in all cases
Fire or failure in extreme situations
Setting Warning Levels
The preset warning levels in MCEGold are based on both actual values and on a % change
from the baseline value.
Data Interpretation
Resistive imbalance above the setpoint indicates that a problem exists in either the power
circuit or in the stator windings. First, isolate the problem to the asset or the circuit.
Looking at individual resistance readings can help isolate the problem to a phase. Also,
look for the following characteristics which indicate faulty connections.
Aluminum cables connected to lugs marked for copper wire only
Discoloration of insulation or contacts
Damaged insulation having small cracks, bare conductors, or metal components
Mismatched cables in common circuits
Poor lug crimps on T-Leads
Oxidation of conductor metals
Presence of contaminants such as dirt
PdMA MCEGold PRODUCT SUPPORT MANUAL MCE
REV. 0-04/08 2008 PdMA Corporation 5-61
Example
The following information is from a 7,000 HP vertical reactor coolant pump asset at a
nuclear power plant. A high resistance solder joint between phases 1 and 3 produced a
resistive imbalance of 37.15%. The cost associated with the power loss was calculated to
be $58,517.84 per year. Multiple tests, shown in Table 5-11, were performed to verify the
problem.
Table 5-11: MCE Tests Used in Troubleshooting Efforts
Phase-to-Phase Inductance
What Does it Tell You?
In AC assets, phase-to-phase inductance readings can:
Indicate the condition of the stator windings
Detect phase-to-phase and coil-to-coil current leakage paths
Reveal poor or incorrect rework
These readings can also be used to detect faults in power cables. A Rotor Influence Check
(RIC) can be performed to further troubleshoot the asset to reveal faults such as:
Broken/cracked rotor bars or end rings
Porosity and lamination damage
Eccentricity problems
In DC assets, inductance changes within the field or armature can indicate current leakage
paths in the windings.
Test Date 5/31/96 5/31/96 5/31/96
Test ID: 331 332 333
Frequency 1200 1200 1200
BASELINE
Mohm Ph 1 to Gnd
Charge Time 30 30 30
Voltage 1000 1000 1000
Motor Temp 40 40 40
Measured Mohm >2000 >2000 >2000
Corrected Mohm OVR OVR OVR
pF Ph 1 to Gnd 116250 116250 116250
ohm Ph 1 to 2 0.27450 0.26800 0.27400
ohm Ph 1 to 3 0.43750 0.43700 0.44100
ohm Ph 2 to 3 0.24500 0.24300 0.24200
mH Ph 1 to 2 6.750 6.750 6.750
mH Ph 1 to 3 6.755 6.750 6.750
mH Ph 2 to 3 6.745 6.745 6.745
% Res. Imbalance 37.15 38.29 38.24
% Ind. Imbalance 0.07 0.05 0.05
$ Power Loss 58517.84 58973.83 60493.78
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-62 2008 PdMA Corporation REV. 0-04/08
Inductance changes when leakage paths develop. These paths can be either within the
winding coils, or directly to ground. Leakage paths result from mechanical, thermal,
environmental, or electrical damage to the insulation system of the windings. Additionally
phase-to-phase and turn-to-turn shorts can occur. In either case, current flow bypasses
some coils, thereby reducing inductive reactance and increasing current in other phases of
the stator. Temperature rises in the remaining conductors and in the surrounding
insulation. This accelerates the deterioration, which can cause an avalanche effect, as heat
produces more insulation failures, resulting in more leakage paths and more coils removed
from the circuit, further increasing temperature.
As there are fewer winding turns in a given phase actively creating the magnetic field
upon which the asset is functioning, the windings in the other phases compensate to meet
the requirements of the load on the asset. These windings in turn draw more current than is
normally supplied by a balanced asset.
Why is This Important?
A large inductive imbalance causes torque-induced vibration at two-times line frequency
(2F
L
). This vibration can be linked to mechanical degradation. Also, inductive imbalance
can contribute to other problems, among which are:
Bearing damage
Coupling damage
Loosened rotor bars
Insulation failure at winding end turns or at exit of stator slots
Setting Warning Levels
The preset warning levels in MCEGold are based on both actual values and on a change
from the baseline value.
Data Interpretation
Many factors affect inductance readings, including asset winding coils, the stator iron, the
rotor, and the number of rotor bars. The power circuit has little or no effect on the
inductance readings unless there are power factor or surge capacitors in the circuit.
Power correction and surge capacitors are used in some circuits and will affect phase-to-
phase inductance readings. Whenever possible, phase-to-phase inductance tests should be
performed with the capacitors in the circuit as well as disconnected, to indicate the health
of the capacitors. This allows for trending the condition of the capacitors as well as the
phase-to-phase inductance of the asset.
If both inductive and resistive imbalance are high, look for a leakage path in a coil or an
open coil. If resistive imbalance is low, the fault may be in the rotor.
A rotor bar/cage anomaly may not produce a large inductive imbalance on one single test.
If inductive imbalance has increased or is high, perform a RIC to further define the
problem. Excessive vibration can also be an indicator of inductive imbalance. If you
notice high vibration readings, perform a RIC to collaborate the data.
Example
A new asset with a cast aluminum rotor was load-tested prior to installation. The asset
failed to reach rated HP. A RIC was conducted and indicated the presence of broken rotor
bars.
PdMA MCEGold PRODUCT SUPPORT MANUAL MCE
REV. 0-04/08 2008 PdMA Corporation 5-63
When the rotor bars were cast, high resistance connections were formed. Operating the
asset during the load-test produced excessive heat at those points. The melted paint on the
rotor identified the high resistance connections beneath them.
Test Lead Check
The MCE verifies the resistance of the test leads before and after each test. This ensures
test lead continuity and proper connection prior to running the test. If any test lead
resistance exceeds a predetermined value, the MCE stops the test. That lead must then be
reconnected and retested successfully to continue. This ensures maximum accuracy and
repeatability of the collected data.
Resistive Imbalance
Resistive imbalance is calculated from the three individual phase-to-phase resistance
readings taken during the standard test. It is displayed as a percentage and will be put into
a caution or alarm state if it exceeds a specific limit. This limit can be changed in the
MCEGold software. Because this value is calculated from three phase-to-phase readings,
there is no resistive imbalance value for DC assets.
In AC assets, resistive imbalance is an indication of one or more high-resistance
connections in the circuit or shorted turns. Assuming the original test was performed at the
MCC, isolate the problem to the asset or to the power circuit by retesting the asset at the
connection box. If the resistive imbalance remains, the problem is in the asset. If the
resistive imbalance goes away, the problem is in the cables or power circuit. Look at the
individual resistance readings to determine the faulty phase.
Inductive Imbalance
Inductive imbalance is calculated from the three individual phase-to-phase inductance
readings taken during the standard test. It is displayed as a percentage and will be put into
a caution or alarm state if it exceeds a specific limit. This limit can be changed in the
MCEGold software. Due to the fact that this value is calculated from three phase-to-phase
readings, there is no inductive imbalance value for DC assets.
In AC assets, this calculated value can indicate the condition of the stator and rotor/stator
relationship. Turn-to-turn or phase-to-phase shorts in the stator causes a high inductive
imbalance. Rotor/stator eccentricity causes a varying value of inductive imbalance, as
seen on subsequent standard tests. To isolate a problem to the rotor or the stator, perform a
Rotor Influence Check.
Power factor capacitors, line reactors, and other power correction devices can impact
inductance values. Separation of these devices from the circuit may be required when
troubleshooting the asset.
Average Inductance
Average inductance is calculated from the three individual phase-to-phase inductance
readings taken during the standard test. Due to the fact that this value is calculated from
three phase-to-phase readings, there is no inductance imbalance value for DC assets. In
AC assets, this calculated value can indicate the condition of the rotor and rotor/stator
relationship. Rotor defects will cause an increase in the average inductance. To isolate a
problem to the rotor or the stator, perform a Rotor Influence Check.
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-64 2008 PdMA Corporation REV. 0-04/08
Polarization Index Test
What Does it Tell You?
The Polarization Index (PI) and Dielectric Absorption (DA) ratios indicate the condition
of the insulation system of the asset and power circuit. Both of these tests use ratios of
measurements of insulation resistance taken at two different times. The PI is the ratio of
the reading taken at 10 minutes and divided by the reading taken at 1 minute. The DA is
the ratio of the reading taken at 60 seconds divided by the reading taken at 30 seconds.
There are three different currents that flow through an insulator when a voltage potential is
applied. Since the RTG test measures the voltage and current to calculate insulation
resistance, all of these currents must be taken into account.
First, the capacitive current starts out high and drops to nearly zero after the
insulation has been charged to full test voltage. This is normally negligible after
the first few seconds of the test.
Second, the absorption current also starts out high and drops off. The majority
of this current dissipates after one minute, but continues to decay for up to 5 to 10
minutes.
Finally, the conduction or leakage current is a small, mostly steady current
which becomes a factor after the absorption current drops to a negligible value.
This current should remain steady for the remainder of the test.
The relationship between all these currents is shown in Figure 5-59.
Figure 5-59: Current Relationships
As the asset accumulates dirt and as the insulation ages and cracks, the PI and DA ratios
decrease. Dirt accumulates based on the operation and environment of the asset. The
insulation cracks as a function of heat and aging of the asset.
Because of the effects of each of these varying currents, the resistance to ground measured
by any insulation tester varies with the amount of time the voltage is applied to the
insulation. In order to trend or compare insulation RTG values, the charge time for all tests
PdMA MCEGold PRODUCT SUPPORT MANUAL MCE
REV. 0-04/08 2008 PdMA Corporation 5-65
MUST be the same. If the charge time is not the same, the trend or comparison may not be
valid.
Finally, the charging developed by these three different currents does not dissipate
immediately when the voltage is removed at the end of the test. The insulation system
must be allowed to discharge sufficiently between resistance to ground tests in order to
obtain accurate results. A rule of thumb states that insulation takes four times the amount
of charge time to discharge.
Why Is This Important?
Resistance-to-ground readings involve three different current components: capacitive,
absorption, and leakage. The PI test allows the charging and absorption currents to decay
so that only actual leakage current is measured. As a voltage is continuously applied,
healthy insulation slowly polarizes and the absorption current diminishes. This causes a
steady rise in resistance until the majority of the current is from the small amount leaking
to ground. In poor insulation, leakage current is high enough to overshadow the lowering
absorption current and provide little increase in the resistance over time.
Setting Warning Levels
In Managing Motors, Richard Nailen, P.E., offers the following guidelines for interpreting
PI and DA ratios. If the PI ratio is less than 2 or the DA ratio is less than 1.5, look for
insulation degradation.
Unacceptable Acceptable
PI 1 to 1.5 2 to 4
DA 1.25 >1.50
IEEE recommends the following values for PI. Machines rated at 10,000 kVA and less
should have values at least as large as the acceptable values listed below before operation
or hi-pot testing.
PI
Class A 1.5
Class B, F, H 2.0
Data Interpretation
Because the PI and DA values are ratios, temperature correction is unnecessary. PI and
DA can be used for both on-the-spot, one-time checks and for trending over time.
Individual readings can be compared to the recommended setpoints.
A good PI Profile (PIP) shows a sharp rise followed by a steady, but slowly increasing
trend. A downward trend suggests deteriorating conditions. A flat or ragged trace
indicates short-term current transients. Such traces indicate insulation breakdown,
possibly due to contamination or moisture in the power circuit or asset. Observing the
readings over time permits scheduling of cleaning or reconditioning before failure occurs.
If the PI or DA ratio is low, isolate the problem to the circuit or the asset. Assuming the
first test was made at the MCC, run another test from the MCC with the T leads
disconnected.
If the low value is gone, the problem is in the power circuit. If the low value still exists,
test the asset at the asset connection box with the leads to the MCC disconnected. If the
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-66 2008 PdMA Corporation REV. 0-04/08
low value is gone, the problem is in the cables between the asset and the MCC. If the low
value still exists, the problem is in the asset.
Examine the cables in the asset connection box. They could require cleaning, drying, or
replacement. Also, check for water in the conduit.
If the PI or DA ratio is < 1.0, look for a ground fault. Clear this fault before starting the
asset.
Some exceptions to be aware of include:
Moisture or contamination on the windings decreases the PI
The PI can be lowered by certain semiconducting materials which are used for
corona elimination on the end windings of some high-potential AC machines
Performing PI testing in ambient temperatures less than the dew point may
significantly impact the PI values
Examples
The following pictures show the response of the insulation in both a good (Figure 5-60)
and a bad (Figure 5-61) asset, with a constant voltage applied for a 10 minute period. The
increase in the RTG value is due to the decrease in current through the insulation.
Figure 5-60: Asset with a Good PI
PdMA MCEGold PRODUCT SUPPORT MANUAL MCE
REV. 0-04/08 2008 PdMA Corporation 5-67
Figure 5-61: Asset With a Bad PI
The unstable RTG readings in the bad PI are a result of low level discharges occurring in
faults in the insulation.
ROTOR INFLUENCE CHECK (RIC)
What Does It Tell You?
The Rotor Influence Check (RIC) is a graphical representation of the rotor/stator
relationship. By analyzing variations in the magnetic flux while rotating the rotor,
eccentricity and rotor defects are identified. The RIC can also be used to confirm stator
faults. Figure 5-62 shows a RIC graph for a motor with no defects.
Figure 5-62: RIC from a Good Asset
A motor acts similar to an electromagnet. The rotor acts like the core and the stator acts
like the windings of the electromagnet. A RIC shows how the rotors residual magnetism
influences the stator inductance in different positions. As the magnetic field of the rotor
interacts with more of the coils in each stator winding, the inductance of that winding
changes. This influence causes repeatable patterns of change in the graph of the stator
inductance, shown above as sinusoidal waveforms.
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-68 2008 PdMA Corporation REV. 0-04/08
Why Is This Important?
Broken rotor bars can cause extreme heat and vibration, which can result in winding
failure, bearing failure, and loss of torque in a motor. Eccentricity, a non-uniformity of the
air gap between the rotor and stator, can cause excessive vibration, which can result in
winding and bearing failure.
Rotor Position And Aliasing
Each RIC consists of a series of inductance measurements taken at predetermined
positions of the rotor. The amount by which the rotor is moved for each measurement and
the total rotation of the rotor for the test are determined by the number of poles in the
asset. The increment and total rotation are calculated to show the RIC pattern for one
complete pole group. If additional readings are taken beyond the total and at the same
increments, the pattern should repeat itself. Table 5-12 shows the recommended
increments and total rotation to cover one pole face for a asset with a given number of
poles.
Table 5-12: RIC Degree Increments vs. Number of Poles
The number of increments and total rotation are automatically calculated by MCEGold,
based on the entered nameplate data. You may reduce the increment and perform more
tests to cover the recommended total rotation. Increasing the increments and performing
fewer measurements than the default values is not recommended because doing this
results in aliasing. Because not enough points are taken to reveal a true picture of the
curve, aliasing produces an inaccurate and incomplete graph.
The following example shows how to determine the number of poles a asset has, the
number of total degrees to turn the rotor, and the increments by which to turn it. Start with
the basic equation:
In the formula:
F = line frequency (60 Hertz in the US)
N = synchronous asset speed
P = number of poles in the asset
120 = 120 degrees of electrical spacing between poles
For a asset whose synchronous speed is 1800 rpm, use a variation of this equation to find
the number of poles:
P = 120F/N
P = (120)x(60)/1800
P = 4 poles
Poles Increment Total
2 10.0 180
4 5.0 90
6 3.3 60
8+ 2.5 45
F
NP
120
-------- - =
PdMA MCEGold PRODUCT SUPPORT MANUAL MCE
REV. 0-04/08 2008 PdMA Corporation 5-69
Next, determine the number of degrees per pole face. To find this, divide 360 by the
number of poles.
360/4 = 90 degrees per pole face.
Next, determine the increments, in degrees, by which to position the rotor to generate an
accurate RIC pattern. To find this, divide the number of degrees per pole face by 18.
90/18 = 5 degrees.
Thus, the following would apply for a asset whose synchronous speed is 1800 rpm:
4 poles
90 degrees per pole face
5 degree increments per rotation to develop an accurate RIC
The increments were chosen since the RIC pattern typically repeats itself by the same
number of poles in the asset through a complete 360 rotation of the rotor. Using these
increments is recommended to increase consistency and reduce aliasing. Also, use the
same increments and total rotation each time you perform a RIC. This ensures that the RIC
is started and run the same way for each test. Doing this enables you to reliably compare
the data and graph to subsequent tests for trending.
When the RIC is started, the MCE measures the resistance of each phase winding. At each
increment the inductance of each winding pair is measured and recorded. Between
measurements you are prompted to move the rotor to the next position.
Data Interpretation
Aliasing
Aliasing occurs when too few measurements are taken too far apart to show the true shape
of the curve. The following figures show RICs which exhibit aliasing.
Figure 5-63 shows two waveforms of a good rotor in a 6-pole asset. The waveform with
the connected circles was generated with measurements taken at the recommended
interval of 3.3. The waveform with the dashed lines was generated with measurements
taken at 15 intervals. The waveform from measurements taken at 15 intervals shows a
lack of definition.
Figure 5-63: Aliasing
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-70 2008 PdMA Corporation REV. 0-04/08
Figure 5-64 shows two waveforms taken on a asset which has known rotor faults. The
presence of the fault is hidden when the measurements are taken at 15 increments
(dashed waveform). When they were made at the recommended 3.3 increments (circles),
the presence of the rotor fault is indicated by the flattened peaks. Note that the dashed
waveforms shown in Figure 5-63 and 5-64 appear identical masking the true rotor
conditions..
Figure 5-64: Aliasing
Good Asset
Figure 5-65 shows a RIC test for a typical AC induction asset with a good rotor. The three
graphs resemble sine waves which are 120 out of phase with each other. The sinusoidal
pattern is smooth and repeatable. The amplitude of the sine waves varies from asset to
asset, due to factors specific to each asset, such as winding configuration, air gap, core
steel quality, and rotor construction and design.
Figure 5-65: RIC from Good Asset
In some assets, the amplitude changes of the graphs are very small and may appear erratic.
This erratic appearance may be due to measurement resolution steps, and not due to actual
changes in inductance. This condition may indicate a low influence rotor with no rotor
defects. One such low influence rotor is shown in the RIC graph in Figure 5-66.
PdMA MCEGold PRODUCT SUPPORT MANUAL MCE
REV. 0-04/08 2008 PdMA Corporation 5-71
.
Figure 5-66: RIC from Asset with Low Influence Rotor
Eccentricity
Eccentricity is defined as the condition of the air gap between the rotor and stator, all the
way around 360 of the asset. This gap should be the same width all the way around. If the
rotor is bowed, the bearing clearances improperly set, or the end bell not aligned properly,
the air gap will not be equal. An unequal air gap produces a phase-to-phase inductance
graph that is markedly higher at one end of the graph than at the other. This is shown in
Figure 5-67.
Figure 5-67: RIC from Asset with Eccentricity
If an eccentricity problem is suspected, continue performing the RIC to include at least
two pole faces beyond the default increment setting. An exception to be aware of is when
sleeve bearings are used in the asset. Due to their oil film, they can falsely indicate
eccentricity problems since the rotor settles when the asset is not running.
Broken Rotor Bars
A rotor with broken bars produces graphs with anomalies in their wave shapes, such as
flattened and staggered peaks.
0.686
0.688
0.690
0.692
0.694
0.696
0.698
0
1
0
2
0
3
0
4
0
5
0
6
0
mH Ph 1-2
mH Ph 1-3
mH Ph 2-3
12.500
13.000
13.500
14.000
14.500
15.000
0
1
5
3
0
4
5
6
0
7
5
9
0
1
0
5
1
2
0
1
3
5
1
5
0
1
6
5
1
8
0
1
9
5
2
1
0
mHPh1-2
mHPh1-3
mHPh2-3
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-72 2008 PdMA Corporation REV. 0-04/08
Figure 5-68 shows a motor with ten broken rotor bars. These were found following a RIC.
The flattening of the peaks in the phase-to-phase inductance graphs results from the
influence of the broken bars. The irregularities in these traces are repeatable in each phase.
Figure 5-68: RIC from Motor with Broken Rotor Bars
Figure 5-69 shows a motor with cracked welded joints at the shorting rings. The cracked
welded joints were found in 14 out of 122 rotor bars after a RIC was taken. The erratic
pattern of flattened and staggered peaks points to the presence of the broken bars.
Figure 5-69: RIC from Motor with Broken Rotor Bars
Figure 5-70 shows the RIC test of a 480 volt 60 HP AC induction motor with broken rotor
bars and a slight air gap problem. Note the flattened peaks in each phase-to-phase graph.
Figure 5-70: RIC from Motor with Broken Rotor Bars
PdMA MCEGold PRODUCT SUPPORT MANUAL MCE
REV. 0-04/08 2008 PdMA Corporation 5-73
Figure 5-71 shows the staggered peaks in a RIC for a 480 volt 5 HP motor. A rotor
anomaly was determined to be the cause for these peaks. This was the result of a
maintenance supervisor drilling a hole in one rotor bar as a demonstration.
Figure 5-71: RIC from Motor with Broken Rotor Bars
One-Up/Two-Down and Two-Up/One-Down
Phase-to-phase or turn-to-turn stator winding shorts can result in either a one-up/two-
down or two-up/one-down RIC pattern. This is shown in the graphs in Figure 5-72.
Figure 5-72: RIC from Motor with Phase-to-Phase or Turn-to-Turn Shorts
To assist in the analysis, compare the RIC with the phase-to-phase resistance readings on
the standard test. If the same phases are affected resistively and inductively, this further
confirms a winding defect. If resistance readings do not confirm this condition, evaluate
the asset for eccentricity/air gap problems.
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-74 2008 PdMA Corporation REV. 0-04/08
DC Bar-to-Bar Test
What Does It Tell You?
Testing the resistance between commutator bars gives an indication of the comparative
value of resistance that exists between all like electrical circuits in an armature.
Why Is This Important?
The commutator consists of insulated segments assembled into a cylinder and held
together by insulated rings. Electric current is transferred to the armature windings by
brushes made mainly of carbon and graphite. Brush wear creates carbon dust, a
conductive contaminant, which penetrates into crevices, cracks and openings of the
armature. Copper particles add to the contaminant accumulation when the wrong brushes
are installed or the brushes are improperly installed, or when maintenance is inadequate. If
the insulating material on the commutator bars or their risers has cracked, these
contaminants can short entire windings.
Also, high resistance connections can develop at the risers causing open or high-resistance
armature coils. Equalizing connections can break and cause an imbalance due to the loss
of equalization.
Data Interpretation
The resistance readings between bars are in the microhm range for medium to large
machines. Most DC assets of this size have armatures constructed with equalizing jumpers
or compensating shorting connections. The effect of these connections on the Bar-to-Bar
test results shows as a regular pattern of change from bar to bar. Good bars have 1 or 2
different values. If a bar differs greatly from either of these 2 values then look for faults.
Armatures with 50% compensation have every other bar equalized; with 33%
compensation have every 3rd bar equalized; with 25% compensation have every 4th bar
equalized.
MCE ANALYSIS
AC Induction Assets
Rotor Influence Check (RIC)
Normal - smooth three-phase sinusoidal waveforms
Rotor Defect - repeatable erratic inductance throughout the peaks of the
waveforms
Eccentricity - inconsistent variations in the amplitude of the waveforms. Static
eccentricity sometimes causes a consistent separation in the three sine waves,
coupled with a low inductive imbalance.
One method of analyzing a RIC is done by following four steps, outlined by the acronym
SAME.
S - look at the scale; verify correct resolution
A - check the alignment of the peaks; check for eccentricity
M - check the max-to-min values of the peaks; all three waveforms should be the
same; check for stator problems
E - evaluate the characteristics of the waveforms
PdMA MCEGold PRODUCT SUPPORT MANUAL MCE
REV. 0-04/08 2008 PdMA Corporation 5-75
Standard Test
In the Fault Zone Report, check for Caution and Alarm indications. Click the
value highlighted in yellow or red to see the recommended actions.
Low Resistance-to-Ground - RTG in Caution or Alarm indicates a possible
breakdown in the insulation system.
High Capacitance-to-Ground - CTG in Caution or Alarm indicates an increase in
the contamination on the surface of the insulation.
High Resistive Imbalance - Resistive Imbalance in Caution or Alarm indicates
high resistance connection in the switchgear, disconnect, or asset connection box.
Refer to the individual phase-to-phase resistance readings to assist in locating the
fault.
High Inductive Imbalance - Inductive Imbalance in Caution or Alarm indicates a
winding defect (turn-to-turn or phase-to-phase) or severe eccentricity. Refer to
the individual phase-to-phase inductance readings to assist in locating the fault. If
a RIC has not been performed, perform a RIC to obtain additional information.
Polarization Index/Dielectric Absorption
Low PI or DA ratio - PI or DA in Caution or Alarm indicates changing or
excessive surface contamination.
Breakdown of insulation system.
At this point, a Condition Code may be assigned and Notes completed to explain the
following:
Asset condition/status; basis for the asset condition assigned.
Anomalies that had to be overcome during the performance of the test.
If multiple tests were performed during troubleshooting, explain where test leads
were connected for each test.
AC Synchronous Assets
Stator
Rotor Influence Check (RIC)
Normal - smooth three-phase sinusoidal waveforms
Rotor Defect - appears like a normal sine wave but has a larger than normal
inductive imbalance
Eccentricity - inconsistent variations in the amplitude of the waveforms. Static
eccentricity can sometimes cause a consistent separation in the three sine waves.
One method of analyzing a RIC is done by following four steps, outlined by the acronym
SAME.
S - look at the scale; verify correct resolution
A - check the alignment of the peaks; check for eccentricity
M - check the max-to-min values of the peaks; all three waveforms should be the
same; check for stator problems
E - evaluate the characteristics of the waveforms
Standard Test
In the Fault Zone Report, check for Caution and Alarm indications. Click the
value highlighted in yellow or red to see the recommended actions.
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-76 2008 PdMA Corporation REV. 0-04/08
Low Resistance-to-Ground - RTG in Caution or Alarm indicates a possible
breakdown in the insulation system.
High Capacitance-to-Ground - CTG in Caution or Alarm indicates an increase in
the contamination on the surface of the insulation.
High Resistive Imbalance - Resistive Imbalance in Caution or Alarm indicates
high resistance connection in the switchgear, disconnect, or asset connection box.
Refer to the individual phase-to-phase resistance readings to assist in locating the
fault.
High Inductive Imbalance - Inductive Imbalance in Caution or Alarm indicates a
winding defect (turn-to-turn or phase-to-phase), circuit defect (cable short or
power factor correction capacitor failure), or severe eccentricity. Refer to the
individual phase-to-phase inductance readings to assist in locating the fault. If a
RIC has not been performed, perform a RIC to obtain additional information on
the rotor condition.
Polarization Index/Dielectric Absorption
Low PI or DA ratio- PI or DA ratio in Caution or Alarm indicates changing or
excessive surface contamination.
Step Voltage
If the plot of the curve of current versus voltage deviates from near linear,
impending breakdown is suggested.
Field Circuit
Synchronous Test
In the Fault Zone Report, check for Caution and Alarm indications. Click the
value highlighted in yellow or red to see the recommended actions.
Low Resistance-to-Ground - RTG in Caution or Alarm indicates a breakdown in
the insulation system.
High Capacitance-to-Ground - CTG in Caution or Alarm indicates an increase in
the contamination on the surface of the insulation.
High/Low Resistance - Resistance in Caution or Alarm indicates a high or low
resistance of the field windings.
NOTE: The Caution and Alarm limits are set based on nameplate field voltage
and current values at normal operating temperature of the asset. Testing on a cold
asset may indicate values outside the Caution and Alarm settings.
Low Inductance - Low Inductance in Caution or Alarm indicates turn-to-turn
faults in the field coils.
Polarization Index/Dielectric Absorption
Low PI or DA ratio - PI or DA ratio in Caution or Alarm indicates changing or
excessive surface contamination.
At this point, a Condition Code may be assigned and Notes completed to explain the
following:
Asset condition/status; basis for the asset condition assigned.
Anomalies that had to be overcome during the performance of the test.
If multiple tests were performed during troubleshooting, explain where test leads
were connected for each test.
PdMA MCEGold PRODUCT SUPPORT MANUAL MCE
REV. 0-04/08 2008 PdMA Corporation 5-77
Step Voltage
If the plot of the curve of current versus voltage deviates from near linear,
impending breakdown is suggested.
AC Wound Rotor Assets
Stator
Rotor Influence Check (RIC)
Normal - smooth three-phase sinusoidal waveforms
Rotor Defect - appears like a normal sine wave but has a larger than normal
inductive imbalance
Eccentricity - inconsistent variations in the amplitude of the waveforms. Static
eccentricity can sometimes cause a consistent separation in the three sine waves,
coupled with a low inductive imbalance.
One method of analyzing a RIC is done by following four steps, outlined by the acronym
SAME.
S - look at the scale; verify correct resolution
A - check the alignment of the peaks; check for eccentricity
M - check the max-to-min values of the peaks; all three waveforms should be the
same; check for stator problems
E - evaluate the characteristics of the waveforms
Standard Test
In the Fault Zone Report, check for Caution and Alarm indications. Click the
value highlighted in yellow or red to see the recommended actions.
Low Resistance-to-Ground - RTG in Caution or Alarm indicates a breakdown in
the insulation system.
High Capacitance-to-Ground - CTG in Caution or Alarm indicates an increase in
the contamination on the surface of the insulation.
High Resistive Imbalance - Resistive Imbalance in Caution or Alarm indicates
high resistance connection in the switchgear, disconnect, or asset connection box.
Refer to the individual phase-to-phase resistance readings to assist in locating the
fault.
High Inductive Imbalance - Inductive Imbalance in Caution or Alarm indicates a
winding defect (turn-to-turn or phase-to-phase) or severe eccentricity. Refer to
the individual phase-to-phase inductance readings to assist in locating the fault. If
a RIC has not been performed, perform a RIC to obtain additional information.
Polarization Index/Dielectric Absorption
Low PI or DA ratio - PI or DA ratio in Caution or Alarm indicates changing or
excessive surface contamination.
Step Voltage
If the plot of the curve of current versus voltage deviates from near linear,
impending breakdown is suggested.
Rotor
Standard Test
In the Fault Zone Report, check for Caution and Alarm indications. Click the
value highlighted in yellow or red for recommended actions.
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-78 2008 PdMA Corporation REV. 0-04/08
Low Resistance-to-Ground - RTG in Caution or Alarm indicates a breakdown in
the insulation system.
High Capacitance-to-Ground - CTG in Caution or Alarm indicates an increase in
the contamination on the surface of the insulation.
High Resistive Imbalance - Resistive Imbalance in Caution or Alarm indicates
high resistance connection on the slip ring or winding connections. Refer to the
individual phase-to-phase resistance readings to assist in locating the fault.
High Inductive Imbalance - Inductive Imbalance in Caution or Alarm indicates a
winding defect (turn-to-turn or phase-to-phase). Refer to the individual phase-to-
phase inductance readings to assist in locating the fault.
Polarization Index/Dielectric Absorption
Low PI or DA ratio - PI or DA ratio in Caution or Alarm indicates changing or
excessive surface contamination.
Step Voltage
If the plot of the curve of current versus voltage deviates from near linear,
impending breakdown is suggested.
Resistor Bank
Resistor Bank
In the Fault Zone Report, check for Caution and Alarm indications. Click the
value highlighted in yellow or red to see the recommended actions.
Low Resistance-to-Ground - RTG in Caution or Alarm indicates a breakdown in
the insulation system.
High Capacitance-to-Ground - CTG in Caution or Alarm indicates an increase in
the contamination on the surface of the insulation.
High Resistive Imbalance - Resistive Imbalance in Caution or Alarm indicates
high resistance connection between the resistors or a faulty resistor. Refer to the
individual phase-to-phase resistance readings to assist in locating the fault.
Polarization Index/Dielectric Absorption
Low PI or DA ratio - PI or DA ratio in Caution or Alarm indicates changing or
excessive surface contamination.
At this point, a Condition Code may be assigned and Notes completed to explain the
following:
Asset condition/status; basis for the asset condition assigned.
Anomalies that had to be overcome during the performance of the test.
If multiple tests were performed during troubleshooting, explain where test leads
were connected for each test.
Step Voltage
If the plot of the curve of current versus voltage deviates from near linear,
impending breakdown is suggested.
PdMA MCEGold PRODUCT SUPPORT MANUAL MCE
REV. 0-04/08 2008 PdMA Corporation 5-79
DC Assets
Armature Circuit
Standard Test
In the Fault Zone Report, check for Caution and Alarm indications. Click the
value highlighted in yellow or red to see the recommended actions.
Low Resistance-to-Ground - RTG in Caution or Alarm indicates a possible
breakdown in the insulation system.
High Capacitance-to-Ground - CTG in Caution or Alarm indicates an increase in
the contamination on the surface of the insulation.
High/Low Resistance - values in Caution or Alarm indicate high resistance
connection in the switchgear, disconnect, or asset connection box. This can also
indicate improper brush wear/seating or a poor commutator film.
High/Low Inductance - values in Caution or Alarm indicate a winding defect
(turn-to-turn or coil-to-coil).
Polarization Index/Dielectric Absorption
Low PI or DA ratio - PI or DA ratio in Caution or Alarm indicates changing or
excessive surface contamination.
Bar-to-Bar
High/Low Resistance - values significantly above or below the average
resistance reading indicate an open or a short in the armature winding or
commutator segments.
Field Circuit
Standard Test
In the Fault Zone Report, check for Caution and Alarm indications. Click the
value highlighted in yellow or red to see the recommended actions.
Low Resistance-to-Ground - RTG in Caution or Alarm indicates a possible
breakdown in the insulation system.
High Capacitance-to-Ground - CTG in Caution or Alarm indicates an increase in
the contamination on the surface of the insulation.
High/Low Resistance - values in Caution or Alarm indicate a high resistance
connection in the switchgear, disconnect, or asset connection box.
High/Low Inductance - values in Caution or Alarm indicate a winding defect
(turn-to-turn or coil-to-coil).
Polarization Index/Dielectric Absorption
Low PI or DA Ratio - PI or DA Ratio in Caution or Alarm indicates changing or
excessive surface contamination.
At this point, a Condition Code may be assigned and Notes completed to explain the
following:
Asset condition/status; basis for the asset condition assigned.
Anomalies that had to be overcome during the performance of the test.
If multiple tests were performed during troubleshooting, explain where test leads
were connected for each test.
MCE PdMA MCEGold PRODUCT SUPPORT MANUAL
5-80 2008 PdMA Corporation REV. 0-04/08