LV power air circuit-breakers

and switch-disconnectors
Masterpact Merlin Gerin

52387

Catalogue

Merlin Gerin Modicon Square D Telemecanique

Sans titre-1

21/12/01, 9:26

0000 000 1996 Schneider Electric SA - All right reserved

Schneider Electric SA

5, rue Nadar
92506 Rueil-Malmaison Cedex
France
Tel: +33 (0)1 41 29 82 00
Fax:+33 (0)1 47 51 80 20

http://www.schneiderelectric.com

As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.

ce
document
a thas
imprim
This
document
been printed on ecological paper.
sur du papier cologique.

Created by:
Photos: Schneider
Printing by:

0000 000

Sans titre-1

12-96

21/12/01, 9:26

Masterpact: presentation

035928PC

Masterpact circuit breakers are used to


protect and control low-voltage distribution
systems. They may be installed in main LV
switchboards (incoming units, main and
secondary outgoers). Masterpact is a
complete range offering a large selection of
performance levels:
c ratings from 800 to 6300 A AC,
from 1000 to 8000 A DC;
c breaking capacity from 40 to 150 kA rms;
c operational voltages 690 V AC,
1000 V DC.

Many versions
c 3 or 4 poles;
c fixed or drawout versions;
c current-limiting version up to 2500 A;
c wide range of control units offering
multiple functions.
Circuit breakers designed for all
applications
c 1000 V AC version;
c DC version;
c anti-corrosion version;
c source-changeover version;
c merchant-marine and military versions.
Masterpact circuit breakers comply with all
major international standards and meet
T2 tropicalisation criteria.

front face

2
5
1
6
12
13

E28760

c "charged"

charged

c "discharged"

discharged

13 main-contact position indicator


c "OFF" (O);

10

11

c "ON" (I).

E28761

14

1 opening push-button (O)


2 closing push-button (I)
3 keylock for "connected",
"disconnected" or "test" position
4 door interlock
5 stored-energy-mechanism charging
handle
6 operations counter
7 "open" position keylock
8 racking handle storage
9 functional position indicator:
"connected", "test" and "disconnected"
10 controls on fixed chassis (accessible
with cubicle door closed)
11 padlocking facilities for "connected",
"disconnected" or "test" position
12 stored-energy-mechanism status
indicator

OFF

ON

E28791

14 fault-trip indicator/breaker reset button


LV circuit-breaker: blue figures
Enclosure: red figures

M63

M50

M40

M08 toM32
M32
M08

IG

LI

G
off

LIG

reset V

push to reset

LG

MERLIN GERIN
masterpact
I

I3

I2

I1
90%

push OFF

I
push ON

STR 58 UE

M32 H1
Ui

1000V

50/60Hz

Ue 380/440V

480/690V

Icu 100kA

85kA

Ics 100kA

85kA

Icw 75kA 1s

50%

IEC 947-2

discharged

20%

%Ir

.92
.95 60

.9

.88

0.8

0.63

90

.98 30

.85

.8

0.5

105

tr

Ir

Io

xIo

xIn
Im

Ir :

t
Ir fault

.2

.1
0
.1
2
on I t off

.2

10

xIo
12

17

22

Im :

480

off

xIn
tr

th :

Ih

600
800

500

Ih

400

Im fault
tm

fault
th

th .4

.4
.3

.3

.2
.1
.1
2
on I t off

1000 .2
320
250

i
+S

1200

Ic1 .9

.8

T+

Ic2.8

.93
.95

.7

.98

.6

.85
.9

.86
.85

test

00000

.3

6 .3

3
2
1.5

O OFF

240

15
at 1,5Ir

tm.4

120

Reduced dimensions
c AC circuit breakers:
v a single frame size from 800 to 3200 A,
v common height and depth from 800 to
6300 A;
c DC circuit breakers:
v common height and length from 1000 to
8000 A for operational voltages of up to 500
V DC,
v common height and length from 1000 to
4000 A for operational voltages greater than
500 V DC.

1
xIr

.95
1

.5
xIr

test

connected
test
disconnected

2
BTP207E-1.010-presentation

Merlin Gerin

21/12/01, 9:34

015159

3
4

6
7
8

10
9

drawout version
1
2
3
4
5
6
7
8
9
10

arc chute cover


auxiliary terminal shield
auxiliaries connection block
fixed chassis
safety shutters
arc chute
remote control voltage release
motor for electrical charging of
stored energy mechanism
control unit (AC system)
front cover

Merlin Gerin

BTP207E-1.010-presentation

21/12/01, 9:34

E29490

Masterpact: presentation

safety and reliability


c reduced, simple maintenance (main
contacts easily accessible, with wear
indication feature);
c double insulation from the front face;
c positive contact indication;
c auxiliary devices can be fitted on site
without adjustment;
c fewer parts than conventional ranges (by a
factor of 5-10);
c a trip interlock ensures that the circuit
breaker is open during connection and
disconnection;
c connection to top or bottom terminals;
c fully tropicalised as standard.
STR 58 U

stored energy operating


mechanism

50%

20%
Io
0.8

0.63

90

.9

xIo

tm

Im

tr

6 .3

.2

2
1.5

.2

.1

I
Ir :
Ir fault

14

12

19
22
Max.

4
2

Ih

xIn
Ih 1200A Max th

th :

th

600
800

500
400

Im fault
tm

fault

0
.1
on I2t off

10

xIr

Im :

tr

320
250

i
overcurrent

test

Ic2

Ic1

.9

.86

.8

.93
.95

.7

.98

.6

xIr

.4

.4

.3

.3

.2
1000 .2
.1
.1
1200
on I2t off

.85

ground

.3

.4

Masterpact circuit breakers are operated via


a stored energy mechanism for
instantaneous opening and closing.
The mechanism is charged either manually
or electrically. Closing and opening
operations can be initiated either from the
local pushbuttons on the circuit breaker front
face, or by remote control.

15
at 1.5Ir

.8

xIn

norm
min.

480

.98 30

.85

0.5

240

120
.92
.95 60

.88

%Ir
105

tr

Ir

R
.85
.9

.8

.95
.5

xIr

test

isolation renforce

sparation totale

classe II insulation
double

entre phase
chaque phase
total
separation

dclencheurs voltmtriques
accessibles
l'avant
voltage
releases
accessible from the
front

c Fixed circuit breaker


The fixed circuit breaker is derived from the
moving part of the drawout circuit breaker by
adding a fixing bracket on each side.

035929

other possibilities

c Switch version
The switch (unprotected) version is derived
directly from the standard circuit breaker, but
does not implement a control unit (or the
magnetic trip units used with the DC circuit
breakers). Available models are:
v standard: type HI and NI;
v high performance: type HF, equipped with
a protection system that instantaneously
opens the circuit breaker in the event of
closure under fault conditions.

Fixed circuit breaker

053060

c Earthing switch
A special short-circuit and earthing switch is
available on request for the M08 to M32H
drawout types, 3 or 4 poles. Please consult
us.

common auxiliaries
from 800 A to 6300 A
Auxiliaries
c accessible from the front, mounted in a
separate compartment insulated from power
circuits;
c secured by a single screw;
c adjustment-free;
c can be fitted on site.
c Source changeover system
Four solutions are available:
v mechanical interlocking for 2 or 3 circuit
breakers, adaptable to various sourcechangeover configurations;
v automatic source-changeover controller,
easy to implement on any two suitably
equipped circuit breakers (electrically
charged operating mechanism, etc.) (for 3
circuit breakers, consult us);
v complete assembly including 2 or
3 mechanically (rod assembly) interlocked
circuit breakers, adaptable to various
source-changeover configurations;
v complete assembly including
2 mechanically (rod assembly) interlocked
circuit breakers and an automatic sourcechangeover controller, adaptable to various
source-changeover configurations. Ready
for connection.

053061

053058

c 1000 V AC circuit breakers

Automatic source-changeover controller

4
BTP207E-1.015-presentation

Merlin Gerin

21/12/01, 9:35

86094

DC circuit breakers

86096

Fixed Masterpact DC circuit breaker

Masterpact DC circuit breakers are available


in fixed and drawout versions. They benefit
from the AC range technology and
advantages.
c 5 available ratings from 1000 to 8000 A;
c 2 breaking capacities, 100 kA at 500 V,
50 kA at 750 and 1000 V;
c a circuit-breaker version offering
instantaneous short-circuit protection with
an adjustable, magnetic trip unit (DINA);
c a switch (unprotected) version.
note: up to 125 V DC, the devices in the AC
range (M08 to M63) may be used only in the
switch version, in which case a three-pole,
type HI device should be used, with:
c 1 pole for the positive polarity;
c 1 pole for the negative polarity;
c 1 pole not used.

Auxiliaries
All the auxiliaries designed for the
Masterpact AC circuit breakers may be used
on the DC versions, with the exception of the
position switches, indicating the connected
(CE), disconnected (CD) and test (CT)
positions.
Auxiliary connections are made via one or
two manually disconnectable plugs that
remain accessible from the front.
Accessories
Standard Masterpact DC range equipment
includes an arc-chute cover (CC) and, on
drawout versions, safety shutters (VO).
Interphase barriers (EIP) are not available
for the DC range.

Drawout Masterpact DC circuit breaker

device identification
M 20 H1
breaking capacity;
c N1: standard;
c H1: H2: high performance;
c L1: current limiting;
c DC: direct current.
rating
c rated current / 100.
family
c Masterpact: LV power air
circuit breaker.

Merlin Gerin

BTP207E-1.015-presentation

21/12/01, 9:35

Masterpact circuit breakers are the product


of Merlin Gerins vast experience in the field
of power circuit breakers. They incorporate
all the qualities of traditional air circuit
breakers while drawing on certain of the
advantages specific to moulded-case circuit
breakers. In particular, they require no
preventive maintenance.

ease of installation
Masterpact is a complete and rationally
designed range.
c 10 ratings;
c 4 breaking-capacity levels;
c 6 control units;
c a complete range of auxiliaries and
accessories;
c numerous versions (three and four-pole
devices, fixed and drawout versions, etc.).

025179

2500 A Masterpact circuit breaker

Masterpact circuit breakers are easy to


incorporate in switchboards.
c a single frame size from 800 to 3200 A,
thus making for standardised columns;
c an upper safety clearance equal to zero
due to the arc-chute cover, on both the fixed
and drawout versions;
c built-in measurement functions in the
control units;
c auxiliaries are the same for the entire
range and may be easily implemented (only
a screwdriver is required).

Top: front connection


Bottom: rear vertical connection

Masterpact circuit breakers are easy to


connect to the main distribution system.
c all types of connections are available
(horizontal and vertical terminals, front and
mixed connections);
c connections are possible with bars of any
thickness;
c connection to the input power source is
possible on the upper or lower terminals of
the circuit breakers.
Due to their small size, Masterpact circuit
breakers can replace most existing
circuit breakers.

continuity of service
Masterpact circuit breakers are designed
with continuity of service in mind. The
result is:
c total time discrimination on the N1 and H1
circuit breakers and maximum discrimination
on H2 circuit breakers;
c factory pre-setting of Masterpact circuit
breakers which never require any periodic
maintenance;
c high electrical endurance: 10 000 cycles at
1600 A and 30 cycles at 50 kA, without
maintenance;
c preventive indications: load-shedding
indication switch, long-time threshold
overrun alarm, etc.;
c easy access to the main contacts fitted
with mechanical wear indicators. An optional
function on the STR68 control unit is the
remote indication of contact wear, thus
making possible continuous monitoring of
circuit breakers during their service life.
,

036634

Masterpact: presentation

operating safety
The insulating casing of Masterpact
circuit breakers provides for:
c user safety:
v double insulation on the front face
(class II),
v auxiliary circuits in a compartment
insulated from the power circuits;
c switchboard safety when the circuit
breaker is in the open position:
v each pole is effectively isolated in its own
housing,
v limitation of external disturbances.
Positive contact indication
The position indicator cannot indicate
open unless the poles are effectively
separated by the required distance.
The circuit breakers automatically open
during racking in and out.

reliability
c Masterpact circuit breakers comprise ten
times fewer parts than traditional devices.
They are easier to produce and more
reliable.
c the Masterpact circuit-breaker factory is
certified ISO 9002;
c the design of Masterpact circuit breakers
is modular with delayed differentiation
(highest possible number of common parts
on all models). The result is shorter delivery
times and enhanced reliability.

6
BTP207E-1.020-contents

Merlin Gerin

21/12/01, 9:38

LV power air
circuit breakers and
switch-disconnectors

Masterpact
2/ functions and
characteristics
page
generales characteristics
circuit breaker selection
switch-disconnectors
dimensions an weights
control unit selection
control unit accessories
electrical auxiliaries
mechanical accessories
source changeover systems

0
0
0
0
0
0
0
0
0

BTP207E-2.001-content

21/12/01, 9:39

Masterpact: functions and characteristics

general characteristics

E29049

conformity with standards

MERLIN GERIN
masterpact
M32 H2
Ui

1000V

50/60Hz

Ue 380/440V 480/690V
Icu 100kA

85kA

Ics 100kA

85kA

Icw 75kA 1s
IEC 947-2

Masterpact circuit breakers comply with all


the major international standards:
c International standard IEC 947-2;
c North American standards (please consult
us):
UL 489, ANSI C37-50, CSA C22-2,
NEMA AB1 et SG3;
c Japanese standards: JIS 160 and C 8372.
They also comply with the following national
standards:
c France NF C 63-120;
c Germany VDE 0660;
c United Kingdom BS 4752;
c Australia AS ;
c Italy CEI.
Masterpact circuit breakers comply with the
specifications of the marine classification
companies (Veritas, Lloyd's Register of
Shipping, Det Norske Veritas, etc.).

Standardised characteristics indicated on


the rating plate:
Ui: rated insulation voltage
Ue: rated operational voltage
Icu: ultimate breaking capacity, for various
values of the rated operational voltage Ue
Ics: service breaking capacity
Icw: short-time withstand current
: suitable for isolation

IEC 947-2
This standard replaces IEC 157-1,
applicable since 1973.
The circuit breaker selection criteria are
unchanged, but the new standard provides
the user with a better guarantee concerning
quality and performance.
Circuit breakers are subjected to tests that
are more representative of real operating
conditions.
IEC 947-2 also clarifies the notion of
breaking capacity.
c Icu : the ultimate breaking capacity, which
must be greater than or equal to the 3-phase
short-circuit current at the point of
installation of the circuit breaker, a value
unlikely to be reached under real conditions;
c Ics : the service breaking capacity,
generally expressed as a percentage of the
ultimate breaking capacity (25, 50, 75 or
100 % of Icu). It corresponds to a shortcircuit current that is more likely to be
reached under real conditions. The circuit
breaker must continue to operate normally
after having interrupted a current equal to
Ics several times;
c Icw : short-time withstand current for
circuit breakers belonging to category B
(category B refers to circuit breakers with
time discrimination and category A to those
without time discrimination).
Furthermore, IEC 947-2 takes into account
recent technological advances:
c suitability for isolation recognised for
circuit breakers having passed special
electrical and mechanical tests;
c industrial earth-fault circuit breakers
covered by an appendix;
c definition of tests designed to ensure
coordination between two circuit breakers.

tropicalisation
As standard, Masterpact circuit breakers
comply with NF C 63-100 standard level 2
conditions (95 % relative humidity at 45 C
or 80 % at 55 C, hot and humid climate
conditions). They also comply with the
following standards:
c IEC 68-2-30 damp heat;
c IEC 68-2-2 dry heat;
c IEC 68-2-11 salt spray;
c IEC 68-2-1 low temperatures during
storage.
Corrosive atmospheres: Special grease or
other surface coatings available (please
consult us).

pollution degree
Masterpact circuit breakers are certified for
operation in pollution degree IV
environments as defined by
IEC standard 947 (industrial environments).

8
BTP207E-2.020-gen. charact..

Merlin Gerin

21/12/01, 9:40

positive contact indication

All Masterpact circuit breakers are also


disconnectors (suitable for isolation) as
specified by IEC 947-2. They bear the
corresponding symbol on the front cover:

All Masterpact circuit breakers offer positive


contact indication. The toggle position
rigorously reflects the position of the main
contacts. It can indicate the "OFF" position
only if the contacts are effectively open and
a suitable distance apart.

E18569

035932RC

maximum dependability

This characteristic considerably increases


the dependability of the circuit breaker.
The conditions specified by IEC 947-2 for
this function are:
c positive contact indication;
c impulse withstand: 8 kV at sea level;
c very low leakage current, checked on new
circuit breakers and on circuit breakers
subjected to tests representative of the end
of service life.
Moreover Masterpact circuit breakers have a
double-insulation front face (i.e. a class II
device) allowing control from the outside.

installation
Masterpact circuit breakers may be installed
on horizontal metal surfaces or on rails.
They are secured by four points accessible
at the bottom of the chassis (drawout
versions) or on either side of the circuit
breaker (fixed versions). A single door
cut-out is required for the entire range and
provides access to Masterpact controls
(see the description on page 2).
.

degree of protection
E28757

IP 30-5

circuit breaker installed in a cabinet with access


to controls through a door cut-out

IP 40-5

circuit breaker installed in a cabinet behind a door with


a cut-out fitted with a sealed, transparent cover

IP 54-9

E28763

circuit breaker installed free standing

E28758

(as defined by IEC 529)

Merlin Gerin

BTP207E-2.020-gen. charact..

21/12/01, 9:40

Masterpact: functions and characteristics

035928

circuit breaker selection

Masterpact circuit breakers


number of poles

electrical characteristics as per IEC 947-2 and EN 60947-2


In

40 C

Ui
Uimp
Ue

AC 50/60 Hz

ultimate breaking capacity (1)


(kA rms)

Icu

AC 50/60 Hz

service breaking capacity


short-time withstand current
(kA rms)

Ics
Icw

(% Icu)
AC 50/60 Hz

making capacity (kA peak)

Icm

AC 50/60 Hz

electrodynamic withstand (kA peak)


utilisation category
suitability for isolation
break time
closing time
endurance (C-O cycles) x 1000

mechanical

with maintenance
no maintenance
no maintenance

rated current (A)


rating of 4th pole (A)
rated insulation voltage (V)
rated impulse withstand voltage (V)
rated operational voltage (V)

type of circuit breaker


Masterpact M16 H1

electrical

motor control (AC3-947-4) (2)

220/415 V
440 V
500/690 V
0.5 s
1s
3s
220/415 V
440 V
500/690 V

440 V - In
690 V - In
690 V

electrical characteristics as per standard Nema AB1


breaking capacity (kA)

480 V
600 V

protection (see following pages)


sensor ratings (A) (see page 12)
control unit
protection type

instantaneous
distribution
selective
universal

STR 18 M
STR 28 D
STR 38 S
STR 58 U
STR 68 U

installation and connections


connection
version

drawout
fixed

indication and measurement auxiliaries


auxiliary switches
electronic trip unit related functions

control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)

installation and connection accessories


locking by padlock or keylock/mismatch protection

(1) Defined for a power factor of 0.25 if 20 < kA rms


50 or 0.20 of kA rms > 50.
(2) Closing at 6 x Ie and opening at 0.17 x Un.
(3) For control unit STR 68 U, the minimum rating
In is 400 A.

safety shutters (VO)


interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)
Merlin Gerin

6
BTP207E-2.060-M08...16

21/12/01, 9:41

M08

M10

M12

M16

3, 4

3, 4

3, 4

3, 4

800
800
1000
8000
690

1000
1000
1000
8000
690

1250
1250
1000
8000
690

1600
1600
1000
8000
690

N1

N1

H1

H2

L1

N1

H1

H2

L1

40
65
100
130
40
65
100
130
40
65
100
110
40
65
100
110
40
65
85
65
40
65
85
65
100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 %
40
65
65
12
40
65
65
12
30
50
50
12
30
50
50
12
22
32
32
12
22
32
32
12
84
143
220
286
84
143
220
286
84
143
220
242
84
143
220
242
84
143
187
143
84
143
187
143
84
143
143
24
84
143
143
24
B
B
B
B
B
B
B
B
c
c
25 to 30 ms without intentional time delay and 9 ms for type L1
70 ms
20
20
20
20
20
20
20
20
10
10
10
10
10
10
10
10
10
10
10
3
10
10
10
2.7
10
10
10
3
10
10
10
2.7
10
10
10
10
10
10
-

H1

40
40
40
100 %
40
30
22
84
84
84
84
B
c

65
65
65
100 %
65
50
32
143
143
143
143
B

100
100
85
100 %
65
50
32
220
220
187
143
B

130
110
65
100 %
12
12
12
286
242
143
24
B

40
40
40
100 %
40
40
22
84
84
84
84
B
c

65
65
65
100 %
65
50
32
143
143
143
143
B

100
100
85
100 %
65
50
32
220
220
187
143
B

130
110
65
100 %
17
17
12
286
242
143
34
B

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

15
10
2.5
2.5
-

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

15
10
2.2
2.2
-

40
40

40
40

65
65

100
65

40
40

65
65

100
65

c
c
c

200 to 1250 (3)


c
c
c
c
c
c
c
c
c
c

c
c
c

200 to 1600 (3)


c
c
c
c
c
c
c
c
c
c

c
c
c
c
c

c
c
c

65
65

200 to 800 (3)


c
c
c
c
c
c
c
c
c
c

H2

100
65

c
c
c
c
c

L1

N1

H1

40
40

65
65

c
c
c

200 to 1000 (3)


c
c
c
c
c
c
c
c
c
c

H2

100
65

c
c
c
c
c

L1

c
c
c
c
c

front and rear connections


c
c

c
c

c
c

c
c

c
c

c
c

c
c

c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c
c
c
c
c

c
c
c
c
c
c
c

c
c
c
c
c
c
c

c
c
c
c
c
c
c
7

Merlin Gerin

BTP207E-2.060-M08...16

21/12/01, 9:41

Masterpact: functions and characteristics

036635

circuit breaker selection (cont.)

Masterpact circuit breakers


number of poles

electrical characteristics as per IEC 947-2 and EN 60947-2


In

40 C

Ui
Uimp
Ue

AC 50/60 Hz

ultimate breaking capacity (1)


(kA rms)

Icu

AC 50/60 Hz

service breaking capacity


short-time withstand current
(kA rms)

Ics
Icw

(% Icu)
AC 50/60 Hz

making capacity (kA peak)

Icm

AC 50/60 Hz

electrodynamic withstand (kA peak)


utilisation category
suitability for isolation
break time
closing time
endurance (C-O cycles) x 1000

mechanical

with maintenance
no maintenance
no maintenance

rated current (A)


rating of 4th pole (A)
rated insulation voltage (V)
rated impulse withstand voltage (V)
rated operational voltage (V)

type of circuit breaker


Masterpact M50 H1

electrical

motor control (AC3-947-4) (2)

220/415 V
440 V
500/690 V
0.5 s
1s
3s
220/415 V
440 V
500/690 V

440 V - In
690 V - In
690 V

electrical characteristics as per standard Nema AB1


breaking capacity (kA)

480 V
600 V

protection (see following pages)


sensor ratings (A) (see page 12)
control unit
protection type

instantaneous
distribution
selective
universal

STR 18 M
STR 28 D
STR 38 S
STR 58 U
STR 68 U

installation and connections


connection
version

drawout
fixed

indication and measurement auxiliaries


auxiliary switches
electronic trip unit related functions

control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)

installation and connection accessories


locking by padlock or keylock/mismatch protection

(1) Defined for a power factor of 0.25 if 20 < kA rms


50 or 0.20 of kA rms > 50.
(2) Closing at 6 x Ie and opening at 0.17 x Un.
(3) For control unit STR 68 U, the minimum rating
In is 400 A.
(4) 83% if Ue i 440 V.
(5) Consult us for full rated neutral.

safety shutters (VO)


interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)
Merlin Gerin

8
BTP207E-2.070-M20...63

21/12/01, 9:42

M20

M25

M32

M40

M50

M63

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

2000
2000
1000
8000
690

2500
2500
1000
8000
690

3200
3200
1000
8000
690

4000
4000
1000
8000
690

5000
2500 (5)
1000
8000
690

6300

N1

H1

H2

H1

H2

H1

H2

H1

H2

55
75
100
130
55
75
100
130
75
55
75
100
110
55
75
100
110
75
55
75
85
65
55
75
85
65
75
100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 %
55
75
75
17
55
75
75
17
75
55
75
75
17
55
75
75
17
75
50
57
57
17
50
75
75
17
75
121
165
220
286
121
165
220
286
165
121
165
220
242
121
165
220
242
165
121
165
187
143
121
165
187
143
165
121
165
165
34
121
165
165
34
165
B
B
B
B
B
B
B
B
B
c
c
c
25 to 30 ms without intentional time delay and 9 ms for type L1
70 ms
15
15
15
15
15
15
15
15
15
10
10
10
10
10
10
10
10
10
9
9
9
2
8
8
8
1.8
4
7
7
7
2
6
6
6
1.8
2.6
7
7
7
6
6
6
2.6

100
100
85
100 %
75
75
75
220
220
187
165
B

75
75
75
100 %
75
75
75
165
165
165
165
B
c

100
100
85
100 %
75
75
75
220
220
187
165
B

100
100
85
100 %
100
100
100
220
220
187
220
B
c

150
150
85
100 % (4)
100
100
100
330
330
187
220
B

100
100
85
100 %
100
100
100
220
220
187
220
B
c

150
150
85
100 % (4)
100
100
100
330
330
187
220
B

15
10
4
2.6
2.6

80 ms
10
5
3
2.5
2.5

10
5
3
2.5
2.5

10
5
3
2.5
2.5

10
5
3
2.5
2.5

10
5
2
1.5
1.5

10
5
2
1.5
1.5

55
55

100
75

75
75

100
75

100
100

125
100

100
100

150
100

75
75

H2

100
75

200 to 2000 (3)


c
c
c
c
c
c
c
c
c
c
c
c
c
c
c

L1

N1

H1

75
75

H2

55
55

100
75

c
c
c

300 to 2500 (3)


c
c
c
c
c
c
c
c
c
c
c
c
c
c
c

L1

H1

3200
1000
8000
690

75
75

c
c
c

600 to 3200
c
c
c
c
c
c
c
c
c
c

2000 to 4000
c
c
c
c
c
c
c
c
c
c

2000 to 5000
c
c
c
c
c
c
c
c
c
c

2000 to 6300
c
c
c
c
c
c
c
c
c
c

front and rear connections


c
c

c
c

c
c

rear connections
c
c

c
c (3P only)

c
c

c
c

c
c

c
c

c
c

c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c
c
c
c
c

c
c
c
c
c
c
c

c
c
c
c
c
c
c

c
c (3P only)
c
c
c
c
c

c
c
c
c
c

c
c
c
c
c
9

Merlin Gerin

BTP207E-2.070-M20...63

21/12/01, 9:42

Masterpact: functions and characteristics

052380

circuit breaker selection (cont.)


Masterpact 1000 V AC
Masterpact 1000 V AC circuit breakers
number of poles

electrical characteristics as per IEC 947-2 and EN 60947-2


In

40 C

Ui
Uimp
Ue

AC 50/60 Hz

ultimate breaking capacity (1)


(kA rms)

Icu

AC 50/60 Hz

service breaking capacity


short-time withstand current
(kA rms)

Ics
Icw

(% Icu)
AC 50/60 Hz

making capacity (kA peak)

Icm

AC 50/60 Hz

electrodynamic withstand (kA peak)


utilisation category
suitability for isolation
break time
closing time
endurance (C-O cycles) x 1000

mechanical

with maintenance
no maintenance
no maintenance

rated current (A)


rating of 4th pole (A)
rated insulation voltage (V)
rated impulse withstand voltage (V)
rated operational voltage (V)

type of circuit breaker


Masterpact M20 H1 1000 V

electrical

motor control (AC3-947-4) (2)

220/415 V
440 V
500/690 V
1000 V
0.5 s
1s
3s
220/415 V
440 V
500/690 V
1000 V

440 V - In
690 V - In
690 V

protection (see following pages)


sensor ratings (A) (see page 12)
control unit
protection type

instantaneous
distribution
selective
universal

STR 18 M
STR 28 D
STR 38 S
STR 58 U
STR 68 U

installation and connections


connection
version

drawout
fixed

indication and measurement auxiliaries


auxiliary switches
electronic trip unit related functions

control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)

installation and connection accessories

(1) Defined for a power factor of 0.25 if 20 < kA rms


50 or 0.20 of kA rms > 50.
(2) Closing at 6 x Ie and opening at 0.17 x Un.
(3) For control unit STR 68 U, the minimum rating
In is 400 A.

locking by padlock or keylock/mismatch protection


safety shutters (VO)
interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC) (as standard on the 1000 V version)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)

Merlin Gerin

10
BTP207E-2.080-M08...32

10

21/12/01, 9:42

M08

M10

M12

M16

M20

M25

M32

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

800
800
1000
8000
1000

1000
1000
1000
8000
1000

1250
1250
1000
8000
1000

1600
1600
1000
8000
1000

2000
2000
1000
8000
1000

2500
2500
1000
8000
1000

3200
3200
1000
8000
1000

H1

H1

H1

H1

H1

H1

H1

65
65
65
65
65
65
65
65
65
65
65
65
45
45
45
45
100 %
100 %
100 %
100 %
45
45
45
45
45
45
45
45
32
32
32
32
95
95
95
95
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
143
B
B
B
B
c
c
c
c
25 to 30 ms without intentional time delay and 9 ms for type L1
70 ms
20
20
20
20
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

75
75
75
45
100 %
45
45
45
95
165
165
165
165
B
c

75
75
75
45
100 %
45
45
45
95
165
165
165
165
B
c

75
75
75
45
100 %
45
45
45
95
165
165
165
165
B
c

15
10
9
7
7

15
10
8
6
6

15
10
4
2.6
2.6

200 to 800 (3)


c
c
c
c
c

200 to 2000 (3)


c
c
c
c
c

300 to 2500 (3)


c
c
c
c
c

600 to 3200
c
c
c
c
c

rear connections only / supply by upstream terminals mandatory


c
c
c
c

c
c

c
c

c
c

c
c

c
c

c
c

c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

200 to 1000 (3)


c
c
c
c
c

200 to 1250 (3)


c
c
c
c
c

200 to 1600 (3)


c
c
c
c
c

11

Merlin Gerin

BTP207E-2.080-M08...32

11

21/12/01, 9:42

Masterpact: functions and characteristics

052384

switch-disconnectors

Masterpact switch-disconnectors
number of poles

electrical characteristics as per IEC 947-2 and EN 60947-2


rated current (A)
rating of 4th pole (A)
rated insulation voltage (V)
rated impulse withstand voltage (V)
rated operational voltage (V)

In

40 C

Ui
Uimp
Ue

AC 50/60 Hz

type of switch-disconnector
short-time withstand current
(kA rms)

Icw

AC 50/60 Hz

making capacity (kA peak)

Icm

AC 50/60 Hz

electrodynamic withstand (kA peak)


suitability for isolation
closing time
endurance (C-O cycles) x 1000

mechanical

with maintenance
no maintenance
no maintenance

Masterpact M10 NI

electrical

motor control (AC3-947-4) (1)

0.5 s
1s
3s
440 V
500/690 V

440 V - In
690 V - In
690 V

protection
STR 08 dummy unit (no protection)
STR 18I (protection against short-circuits when closing)

installation and connections


connection
version

drawout
fixed

indication and measurement auxiliaries


auxiliary switches

control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)

installation and connection accessories


locking by padlock or keylock/mismatch protection
safety shutters (VO)
interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)

(1) Closing at 6 x Ie and opening at 0.17 x Un.


Merlin Gerin

12
BTP207E-2.082-inter M08

12

21/12/01, 9:42

M08

M10

M12

M16

3, 4

3, 4

3, 4

3, 4

800
800
1000
8000
690

1000
1000
1000
8000
690

1250
1250
1000
8000
690

1600
1600
1000
8000
690

NI

HI

HF

NI

HI

HF

NI

HI

HF

NI

HI

HF

40
30
22
84
84
84
c
70 ms
20
10
10
10
10

65
50
32
105
105
143

65
50
32
143
143
143

40
30
22
84
84
84
c

65
50
32
105
105
143

65
50
32
143
143
143

40
30
22
84
84
84
c

65
50
32
105
105
143

65
50
32
143
143
143

40
30
22
84
84
84
c

65
50
32
105
105
143

65
50
32
143
143
143

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

20
10
10
10
10

front and rear connections


c
c

c
c

c
c

c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

13

Merlin Gerin

BTP207E-2.082-inter M08

13

21/12/01, 9:42

Masterpact: functions and characteristics

052388

switch-disconnectors (cont.)

Masterpact switch-disconnectors
number of poles

electrical characteristics as per IEC 947-2 and EN 60947-2


rated current (A)
rating of 4th pole (A)
rated insulation voltage (V)
rated impulse withstand voltage (V)
rated operational voltage (V)

In

40 C

Ui
Uimp
Ue

AC 50/60 Hz

type of switch-disconnector

Masterpact M50 HI

short-time withstand current


(kA rms)

Icw

AC 50/60 Hz

making capacity (kA peak)

Icm

AC 50/60 Hz

electrodynamic withstand (kA peak)


suitability for isolation
closing time
endurance (C-O cycles) x 1000

mechanical

with maintenance
no maintenance
no maintenance

electrical

motor control (AC3-947-4) (1)

0.5 s
1s
3s
440 V
500/690 V

440 V - In
690 V - In
690 V

protection
STR 08 dummy unit (no protection)
STR 18 I (protection against short-circuits when closing)

installation and connections


connection
version

drawout
fixed

indication and measurement auxiliaries


auxiliary switches

control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)

installation and connection accessories


locking by padlock or keylock/mismatch protection
safety shutters (VO)
interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)

(1) Closing at 6 x Ie and opening at 0.17 x Un.


Merlin Gerin

12
BTP207E-2.084-inter M20

12

21/12/01, 9:43

M20

M25

M32

M40

M50

M63

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

2000
2000
1000
8000
690

2500
2500
1000
8000
690

3200
3200
1000
8000
690

4000
4000
1000
8000
690

5000
2500
1000
8000
690

6300
3200
1000
8000
690

NI

HI

HF

NI

HI

HF

HI

HF

HI

HF

HI

HF

HI

HF

55
55
50
84
84
121
c
70 ms
15
10
9
7
7

75
75
57
105
105
165

75
75
57
165
165
165

55
55
50
84
84
121
c

75
75
75
105
105
165

75
75
75
165
165
165

75
75
75
105
105
165
c

75
75
75
165
165
165

75
75
75
165
165
165

100
100
100
187
187
220
c

100
100
100
220
220
220

100
100
100
187
187
220
c

100
100
100
220
220
220

15
10
9
7
7

15
10
9
7
7

15
10
8
6
6

15
10
8
6
6

15
10
8
6
6

15
10
4
2.6
2.6

15
10
4
2.6
2.6

75
75
75
105
105
165
c
80 ms
10
5
3
2.5
2.5

10
5
3
2.5
2.5

10
5
3
2.5
2.5

10
5
3
2.5
2.5

10
5
2
1.5
1.5

10
5
2
1.5
1.5

c
c

c
c

c
c

c
c

front and rear connections


c
c

c
c

c
c

rear connections
c
c

c
c (3P only)

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

c
c
c
c
c
c
c
c

c
c
c (3P only)
c
c
c
c
c

c
c

c
c

c
c
c
c
c

c
c
c
c
c

13

Merlin Gerin

BTP207E-2.084-inter M20

13

21/12/01, 9:43

Masterpact: functions and characteristics

dimensions and weights

Masterpact circuit breakers and switch-disconnectors


type
dimensions and weights
dimensions W x H x D
(mm)

drawout

3P
4P
3P
4P
3P
4P
3P
4P

fixed
maximum weight
(kg)

drawout
fixed

Masterpact circuit breakers and switch-disconnectors


type
dimensions and weights
dimensions W x H x D
(mm)

drawout

3P
4P
3P
4P
3P
4P
3P
4P

fixed
maximum weight
(kg)

drawout
fixed

Masterpact 1000 V circuit breakers


type
dimensions and weights
dimensions W x H x D
(mm)

drawout

maximum weight
(kg)

drawout

3P
4P
3P
4P

sensor selection
In (A)
Ir threshold
settings (A)
In (A)
Ir threshold
settings (A)

200
80
to 200
1250
500
to 1250

250
100
to 250
1600
640
to 1600

320
125
to 320
2000
800
to 2000

400
160
to 400
2500
1000
to 2500

500
200
to 500
3000
1200
to 3000

600
240
to 600
3200
1280
to 3200

630
250
to 630
4000
1600
to 4000

800
320
to 800
5000
2000
to 5000

1000
400
to 1000
6000
2400
to 6000

1200
480
to 1200
6300
2500
to 6300

The table above indicates:


c all the available sensor ratings In;
c the limits of the long time Ir settings.

Merlin Gerin

12
BTP207E-2.090-M08...63

12

21/12/01, 9:47

M08

M10

M12

M16

M20

M25

M32

N1/H1/H2/L1
NI/HI/HF

N1/H1/H2/L1
NI/HI/HF

N1/H1/H2/L1
NI/HI/HF

N1/H1/H2 L1
NI/HI/HF

N1/H1/H2 L1
NI/HI/HF

N1/H1/H2 L1
NI/HI/HF

H1/H2
HI/HF

435 x 439 x 367


550 x 439 x 367
422 x 356 x 290
537 x 356 x 290
65
80
43
54

435 x 439 x 367


550 x 439 x 367
422 x 356 x 290
537 x 356 x 290
65
80
43
54

435 x 439 x 367


550 x 439 x 367
422 x 356 x 290
537 x 356 x 290
65
80
43
54

435 x 439 x 367


550 x 439 x 367
422 x 356 x 290
537 x 356 x 290
69
82
85
102
46
55
58
69

435 x 439 x 367


550 x 439 x 367
422 x 356 x 290
537 x 356 x 290
82
130
102
150
55
80
69
90

435 x 439 x 367


550 x 439 x 367
422 x 356 x 290
537 x 356 x 290
82
130
102
150
55
80
69
90

435 x 439 x 367


550 x 439 x 367
422 x 356 x 290
537 x 356 x 290
130
150
80
90

M40

M50

M63

H1/H2
HI/HF

H1/H2
HI/HF

H1/H2
HI/HF

550 x 439 x 367


815 x 484 x 367
537 x 356 x 290
801 x 356 x 290
150
200
90
110

815 x 484 x 367


1045 x 484 x 367
802 x 356 x 290

1045 x 484 x 367


1045 x 484 x 367

215
230
110

245
265

M08

M10

M12

M16

M20

M25

M32

H1

H1

H1

H1

H1

H1

H1

435 x 439 x 367


550 x 439 x 367
65
80

435 x 439 x 367


550 x 439 x 367
65
80

435 x 439 x 367


550 x 439 x 367
65
80

435 x 439 x 367


550 x 439 x 367
69
85

435 x 439 x 367


550 x 439 x 367
82
102

435 x 439 x 367


550 x 439 x 367
82
102

435 x 439 x 367


550 x 439 x 367
130
150

13

Merlin Gerin

BTP207E-2.090-M08...63

13

21/12/01, 9:47

Masterpact: functions and characteristics

control unit selection

current settings (A)

Masterpact M08 to M63 circuit breakers are


equipped with microprocessor-based
electronic control units.

80

160

400

E31218

All the protection functions are powered by


the AC system and no auxiliary power
supply is required. The same is true for most
of the complementary functions.

1250

1600

2000

2500

3200

4000

5000

6300

STR 18 M
STR 28 D
STR 38 S

Each control unit of the Masterpact range


corresponds to a certain type of application
(instantaneous, distribution, selective,
universal).
All the STR control units measure the true
rms value of the current and are therefore
not affected by harmonics that may be
present on the system.

STR 58 U
STR 68 U

instantaneous protection
distribution protection
selective protection
universal protection

protection

push to reset

E31219

E30703

STR 18 M

Key:

reset button: pops out when the circuit


breaker has tripped on a fault and must
be pressed (reset) before the circuit
breaker can be closed again.

maximum protection rating.

instantaneous pick-up.

test connector.

holes for sealable cover plate screws.

STR 18 M

2
5
0

other functions
c fault indication.
I 12 14
8

19
2

22
max

4
xIn

test

Merlin Gerin

14
BTP207E-2.110-unit cont.

14

21/12/01, 9:47

protection
1

push to reset

E31220

E30704

STR 28 D

Key:

2
I1

I2

I3

3
STR 28 D

50%

20%

90

Ir
0.8

%Ir
105

11
Io
0.63

0.5

.88

.9 .92
.95

.85

.98
.8

xIn

xIo

4 5
6
2
8
1.5 xIr 10
3

c
c
c
c

Ir :

Ir

ammeter digital display.

bar graph indicating load level (% Ir).

maximum protection rating.

Im :

Ir

overcurrent indicator LED.

noted settings.

10 test connector.
11 holes for sealable cover plate screws.

other functions

Im

reset button: pops out when the circuit


breaker has tripped on a fault and must
be pressed (reset) before the circuit
breaker can be closed again.

5-6 long-time current setting as a function of:


Io x Ir x In.
7 instantaneous pick-up.

90%

fault indication;
indication of LT overrun;
ammeter;
self-monitoring (internal overheating).

Im

i
+

10

test

11

protection

E33950

E31221

STR 38 S

Key:
I2t ON

push to reset

reset button: pops out when the circuit


breaker has tripped on a fault and must
be pressed (reset) before the circuit
breaker can be closed again.

ammeter digital display.

bar graph indicating load level (% Ir).

maximum protection rating.

overcurrent indicator LED.

7
I2t OFF

2
I1

I2

I3

90%

12

3
50%

20%

16
Ir
0.8

%Ir
1

0.5

.88

.9 .92
.95

.85

.98
.8

xIn

Im

tm

4 5

2
1.5

.3

8
10

.2

xIr
t

.2

.1
0
.1
on I2t off

9
11

Im :

Ih
fault
th

14
16

max. off
xIn
th :
Ih
T
th
500 600
.4 .4
Im fault
400
tm
800 .3
.3
I
320
1000 .2
.2
.1
250 1200
.1
i
A
on I2t off
overcurrent
+

12
13

c
c
c
c
c

short-time delay.

10 noted settings.
11 instantaneous pick-up.
12 earth fault pick-up.

fault indication;
indication of LT overrun;
ammeter;
self-monitoring (internal overheating);
indication of type of fault (F).

13 earth fault delay.


14 LEDs indicating tripping on long-time,
short-time or earth fault.
15 test connector.
16 holes for sealable cover plate screws.
17 battery supplying backup power for fault
indication.
18 fault indication reset and/or battery test.

15

test

.4 .3

Ir :

Im

other functions

Ir fault
tr

Ir

1
xIo

10

11
Io
0.63

90
105

6-7 long-time current setting as a function of:


Io x Ir x In.
8 short-time pick-up.

13

STR 38 S

ground

19 re-indication of last fault.

F
test

17

19
18
15

Merlin Gerin

BTP207E-2.110-unit cont.

15

21/12/01, 9:47

Masterpact: functions and characteristics

control unit selection (cont.)

protection
E31222

E30705

STR 58 U
V

1
push to reset

reset V

I+T L+I
L+I+T
L+T
T
L off
I

Key:

t
I2t ON

8
I2t OFF

9
3
I1

I2

I3

10

90%

14

4
STR 58 U

11

15

50%

21
20%

Ir

Io
0.63

120 240
.9 .92
.95 60
480
.98 30
1
15
.8
xIn
at 1.5Ir
xIo
Max.
Im
tm
4 5
.4 .3
tr
3
.3
6
.2
2
.2
norm
8
.1
0
1.5 10
.1
on I2t off
xIr
I 12 14
Ir :
8
19
Ir fault
4
22
Im :
2 off
tr
xIn
th :
Ih 1200A Max th
T
Ih
500 600
.4 .4
fault
Im fault
400
800 .3
.3
tm
th
320
1000 .2
.2
I
.1
250 1200
.1
i
A
on I2t off
overcurrent Ic1
Ic2
R
+
.9 .93
.8 .85
test
.86
.95 .7
.9
.85
+
.98 .6
.95
ground
1
8 1
.5
xIr
xIr

90

0.8

%Ir

105

7
12
10

16

19
21
24
F

.88

.85

0.5

13

tr

test

Ir

Im

other functions
c
c
c
c
c
c

fault indication;
indication of LT overrun;
ammeter;
self-monitoring (internal overheating);
fault type indication (F);
segregated alarm switch for selected
fault type (V);
c zone selective interlocking (Z);
c load monitoring (R);
c communication (COM).

11
13
14
15
17
18
20

23

22

protection
1

reset

E31223

E33949

STR 68 U

I2t ON

Key:
1

V
N

LT setting
(Ir)

Hz

I2t OFF

Cos

LT time delay
(tr)

kW

MWh

ST pick-up
(Im)
ST time delay
(tm)

STR 68 U

earth fault
pick-up (Ih)
685812
A
KA

S
test

earth fault
time delay (th)

instantaneous
pick-up (I)

Ir

Im

max

other functions
fault

tr

tm
th
Ih

Ir

Im

11

load monitoring

10
8

%
maintenance

trip

reset button: pops out when the circuit


breaker has tripped on a fault and must
be pressed (reset) before the circuit
breaker can be closed again.
2 selection of fault type for segregated
alarm: Ir and/or Im and/or Ih
L: long-time fault (Ir)
I: short-time fault (Im/l)
T: earth fault (Ih)
3 ammeter digital display.
4 bar graph indicating load level (% Ir).
5 maximum protection rating.
6 overcurrent indicator LED.
7-8 long-time current setting as a function of:
Io x Ir x In.
9 long-time trip delay
10 short-time pick-up.
11 short-time delay.
12 adjustment of thermal memory after
tripping.
13 instantaneous pick-up.
14 earth fault pick-up.
15 earth fault delay.
16 noted settings.
17-18 load monitoring settings.
19 test connector.
20 battery supplying backup power for fault
indication.
21 holes for sealable cover plate screws.
22 fault indication reset and/or battery test.
23 re-indication of last fault.
24 LEDs indicating tripping on long-time,
short-time or earth fault.

no trip
test

MEM

c
c
c
c
c
c
c

fault indications and memorisation;


maintenance indicator;
ammeter;
integrated test;
power measurement;
load monitoring (R);
self-monitoring (internal overheating,
malfunction of the microprocessor);
c zone selective interlocking for earth
faults.

reset button: pops out when the circuit


breaker has tripped on a fault and must
be pressed (reset) before the circuit
breaker can be closed again.
2 selection of displayed value (voltage,
power, energy, power factor, frequency).
3 display of current or interrupted current
(when flashing).
4 local fault indication and indication reset.
5 selection and indication of protection
parameter to be set.
6 selection and indication of load
monitoring parameters.
7 adjustment and saving of parameter
settings.
8 holes for sealable cover plate screws.
9 test connector.
10 test.
11 maintenance indicator.

+
24 V DC

adjustments

8
Merlin Gerin

16
BTP207E-2.120-unit cont.

16

21/12/01, 9:50

options for STR control units

"earth fault" protection


(T or W)

E31225

zone selective interlocking


(Z)

A number of circuit breakers are


interconnected one after another by a pilotwire. In the event of a short-time or earth
fault, the control unit applies the set time
delay only if it receives a signal from a
downstream circuit breaker. If not, it trips
instantaneously (tripping time as 0.1 shorttime setting). In this way, the fault is cleared
rapidly by the nearest circuit breaker. The
thermal stresses in the installation are
minimised while maintaining time
discrimination throughout the entire

installation.
Opto-electronic outputs
The use of opto-transistors ensures total
isolation between the internal circuits of the
control unit and the circuits wired by the
user.

This earth fault protection is designed to


protect the installation against the risks of
fire due to high earth faults (not to be
confused with schemes designed for the
protection of persons against electrical
shock).
Two types of earth protection are available
for Masterpact:
c residual current type (T): the control unit
calculates the vector sum of the phase and
neutral (if distributed) currents;
c source ground return type (W): the control
unit acts directly on the signal received from
an external current transformer installed on
the source earthing circuit.

I2t ON

I2t OFF

Ih
Th

load monitoring (R)

E26037

earth fault curves for the STR 58

Remote indication of threshold overrun for


load-shedding or load-reconnection
purposes.

Ic2
Ic1

load monitoring curves for the STR 58

communication: STR 58 U
transmission: STR 68 U

Transmission of the control unit settings,


circuit breaker position and current, voltage
and power measurements.

Other information that can be transmitted


includes the value of the interrupted current,
the state of the thermal memory and the
maintenance indications

indication and
measurement

c ammeter (I): a digital display


continuously indicates the current of the
phase with the greatest load (Imax). By
pressing a scroll button, it is also possible to
display successively the readings of I1, I2,
I3, Ineutral and Ih.
In addition, three bargraphs provide an
immediate visual indication of the load on
each of the three phases.

c indication of type of fault (F);


c segregated alarm switch for selected
fault type (V), wired in parallel with the
opening button (MX), it disables circuit
breaker closing for the selected type of fault.

17

Merlin Gerin

BTP207E-2.120-unit cont.

17

21/12/01, 9:50

Masterpact: functions and characteristics

048449

control unit selection (cont.)


STR 18 M to STR 58 U
control unit
type of circuit breaker

basic protection
long time protection LT
current setting (Ir) as a function of Io and Ir
settings tripping between 1.05 and 1.20 x Ir
time delay (tr)
accuracy: + 0 - 20 %

short-time protection ST
pick-up (Im) adjustable by Im setting
time delay (tm)

Io = In x ...
Ir = Io x ...
tr at 1.5 Ir (s)
tr at 6 Ir (s)
tr at 7.2 Ir (s)
Im = Ir x ...
tm setting with I2t OFF
tm setting with I2t ON
max. overcurrent time before tripping (ms)
max. break time (ms)

instantaneous protection I
pick-up setting
setting range
accuracy
OFF switch on front face

STR 58 U

basic functions
fault indication
for tripping on a fault
for LT setting overrun

self-monitoring

indicator button on front face


fault trip alarm contact (SDE)
LED (lights up at 0.9 Ir and flashes at 1.05 Ir)
LT overrun alarm contact (optional)
self-powered
internal overheating

optional functions

(1) Plus the uncertainty of the built-in transformers:


3 %.
(2) Max = In x ...
630 A
800 - 1000 A
1200 - 1600 A
2000 A
2500 A
3000 - 3200 A
4000 - 6300 A

N1/H1
22
22
22
17
12
10
8

H2
28
28
24
20
14
12
10

L1
14
10
8
6
6

(3) Continuous display for the phase with the


greatest load.
(4) 0.2 x In to 1200 A without external power
supply or 0.1 x In with external power supply.
(5) Accuracy with respect to the long time LT
protection.

ammeter (I)
display between 0.2 and 1.20 In
current readings with an accuracy of 1.5 % (1) (3)
bargraph indication of current levels with a resolution of 10 %
self-powered
earth fault protection: residual current (T) or source ground return (W) type on request
pick-up adjustable by Ih setting
Ih = In x ...
time delay (th)
th setting with I2t ON and I2t OFF
max. overcurrent time before tripping (ms)
max. break time (ms)
indication of type of fault (F) (LT - CT/Inst. - Earth) by LEDs on front face
power supply
with battery module
with external power supply by AD module
segregated alarm switch for selected fault type (V) (LT - CT/Inst. - Earth)
output via relay contact
power supply by AD module
zone selective interlocking (Z)
by opto-electronic contact on ST and earth (T/W) fault
load monitoring (R)
adjustment of load limit thresholds by Ic1 and Ic2 settings Ic1 = Ir x ... / Ic2 = Ir x ...
time delay tr1 at 1.5 Ic1
time delay tr2 at 1.5 Ic2
output via opto-electronic contact 0.1 A / 240 V
time delay for load reconnection
communication (COM)
2 outputs for data transmission to Dialpact module
transmitted values
all control unit settings
alarms: Ir warning, fault type, self-monitoring
load monitoring thresholds
current values I1, I2, I3, IN
power supply by AD module

(6) Resettable maximum ammeter.


Merlin Gerin

18
BTP207E-2.130-STR1858

18

21/12/01, 9:51

STR 18 M

STR 28 D

STR 38 S

STR 58 U

N1, H1, H2

N1, H1, H2

N1, H1, H2, L1

N1, H1, H2, L1

c
0.5 to 1 (4 settings)
0.8 to 1 (8 settings)
fixed
120
7.5
5.2

c
0.5 to 1 (4 settings)
0.8 to 1 (8 settings)
fixed
120
7.5
5.2
c
1.5 to 10 15 %
0
0.1
0.2
0.3
0.1
0.2
0.3
0
80
140
230
80
140
230
350
c
I = In x ...
fixed at high set (Max) (2)
20 %
on types N1 and H1

c
0.5 to 1 (4 settings)
0.8 to 1 (8 settings)
adjustable
15
30
60
120
0.94 1.88 3.75 7.50
0.65 1.30 2.60 5.20
c
1.5 to 10 15 %
0
0.1 0.2 0.3
0.1 0.2 0.3
0
80
140 230
80
140 230 350
c
I = In x ...
2 x In to Max (2)
15 %
on types N1 and H1

0.4
350
500

240
15
10

480
30
21

0.4
350
500

c
Im = In x ...
2 x In to Max (2)
15 %
on types N1 and H1

c
Im = Ir x ...
1.5 to 10 x Ir
15 %

c
c

c
c
c
c
c
c

c
c
c
c
c
c

c
c
c
c
c
c

c
I1, I2, I3, IN, Imax (6)
I1, I2, I3
c

c
I1, I2, I3, IN, Ih, Imax (6)
I1, I2, I3
c
c
0.1 at 1 (max 1200 A) (4) 15 %
0.1
0.2
0.3
0.4
60
140
230
350
140
230
350
500
c
c
c

c
I1, I2, I3, IN, Ih, Imax (6)
I1, I2, I3
c
c
0.1 at 1 (max 1200 A) (4) 15 %
0.1 0.2 0.3 0.4
60
140 230 350
140 230 350 500
c
c
c
c
c
c
0.8 to 1 (8 settings) 1 % (5)
0.5 x tr
0.25 x tr
c
fixed at 10 s
c
c
c
c
c
c
19

Merlin Gerin

BTP207E-2.130-STR1858

19

21/12/01, 9:51

Masterpact: functions and characteristics

036630

control unit selection (cont.)


STR 68 U
presentation
The STR 68 U control unit offers
measurement, supervision and energy
management functions.
Microprocessor technology, liquid crystal
display and function keys ensure high
accuracy and easy adjustment.
The standard STR 68 U control unit provides
the following:
c universal protection;
c ammeter function;
c indication of fault type;
c values of interrupted currents;
c maintenance indicator;
c integrated test.
The following options can be added:
c power measurement module (P);
c "earth fault" protection module;
c control and indication modules (M) with or
without transmission to a supervisor.
Certain M modules can provide load
monitoring or zone selective interlocking for
earth fault protection.

protection

The STR 68 control unit provides:


c overload protection, with long time
protection LT including:
v adjustable time delay and thermal
memory possibility;
c short-circuit protection:
v delayed, with short time function ST, for
which the I2t curve can be disabled by the
user,
v instantaneous, with the INST function that
can be disabled by the user;

basic functions

c ammeter;
c maintenance indicator;
c fault indications and values of the
interrupted currents;
c self-monitoring: in the event of
overheating of the control unit or a
malfunction of the microprocessor, an alarm
signal is transmitted. Unless the "service
continuity" option was ordered, the circuit
breaker will trip ;
c test.

c "earth" protection with time


discrimination or zone selective interlocking.
The protection is of the residual current type
(or source ground return type on request).

Merlin Gerin

20
BTP207E-2.140-unit cont.

20

21/12/01, 9:51

optional functions

c power measurement (P);


c indication and control (M)
Thirty-one different modules offer various
combinations of functions including:
v load monitoring,
v trip indication,
v self-monitoring,
v zone selective interlocking for "earth fault"
protection,
v transmission of data to a supervisor
(modules M17 to M31 only).
Each STR 68 U control unit can be equipped
with only one M module.
For the function offered by each M module,
(see page xxx).

c "earth fault" protection (T)


Of the residual current type (or source
ground return type on request), it is possible
to obtain zone selective interlocking by
combining the T option with the appropriate
M option.

21

Merlin Gerin

BTP207E-2.140-unit cont.

21

21/12/01, 9:51

Masterpact: functions and characteristics

control unit selection (cont.)


STR 68 U
control unit

STR 68 U

type of circuit breaker

N1. H1. H2. L1

basic protection
long time protection LT
current setting (Ir) adjustable in 2 % steps
tripping
time delay (tr)
accuracy: + 0 - 20 %

thermal memory (30 mn)


short time protection ST
pick-up (Im) adjustable in 4 % steps
time delay (tr)

Ir = In x ...

tr at 1.5 Ir (s)
tr at 6 Ir (s)
tr at 7.2 Ir (s)

Im = Ir x ...
tm setting with I2t OFF
tm setting with I2t ON
max. overcurrent time before tripping (ms)
max. break time (ms)

thermal memory (10 mn)


instantaneous protection I
fixed pick-up I (kA)
pick-up (I) adjustable in 8 % steps
accuracy
OFF switch on front face

c
0.4 to 1 (mini 160 A)
between 1.05 and 1.20 x Ir
adjustable
15
30
60
120 240 480
0.94 1.88 3.75 7.50 15
30
0.65 1.30 2.60 5.20 10
21
standard + OFF position
c
0.4 to 15 10 %
0.1 0.2 0.3 0.4
0.1 0.2 0.3 0.4
60
140 230 350
140 230 350 500
standard
c
M08 to M16 : 65. M20 to M63: 75.
from In to fixed pick-up (mini at 1.6 kA)
15 %
on types N1 and H1

basic functions
fault indication
for tripping on a fault
for Ir setting overrun
indication of fault type
and value of interrupted current
self-monitoring
maintenance indicator
displays degree of wear of main contacts
ammeter
current readings with an accuracy of 3 %
self-powered
integrated test

button on front face


fault trip alarm contact (SDE)
LED on front face
self powered
LEDs on front face
display on ammeter
power supply
internal overheating and microprocessor errors

c
c
c
c
c
c
110 V - 220 V - 380 V AC 50/60 Hz
c
c
between 0 and 655
c
I1. I2. I3. Imax (1)
c
c

(1) Current of the phase carrying the highest load.


Merlin Gerin

22
BTP207E-2.160-STR68U

22

21/12/01, 9:52

optional functions
earth fault protection: residual current (T) or source ground return (W) type on request
pick-up (Ih) adjustable in 2 % steps
Ih = In x ...
time delay (th)
th setting
max. overcurrent time before tripping (ms)
max. break time (ms)
thermal memory (10 mn)
power measurement (P) (see opposite page for details)
output characteristics
integrated power supply
voltage measurements
U12. U23. U31
V1N. V2N. V3N
frequency measurement: f
power factor measurement: cos
instantaneous active power measurement: P
instantaneous active energy measurement: EP
indication and control (M): 31 modules (1 per control unit) providing the following combinations:
load monitoring
option 1: 2 load limit pick-ups Ic1 and Ic2 Ic1 = In x ...
delay tr1 =
Ic2 = In x ...
delay tr2 =
option 2: 1 load limit pick-up Ic1
Ic1 = In x ...
1 load reconnection pick-up Ic2 delay tr1 =
Ic2 = In x ...
delay tr2 =
zone selective interlocking
trip indications
for type of fault
for self-monitoring (1)
transmission
characteristics
type
protocol
speed
max. number of addresses
values transmitted:
type of fault
circuit breaker status
self-monitoring
settings
circuit breaker status
values transmitted:
ammeter
power system status
voltmeter
power factor, frequency
instantaneous active power and energy: P. EP
instantaneous reactive power and energy: Q. EQ
power supply

c (zone selective interlocking with option M)


0.2 to 1 (maxi 1200 A. mini 160 A ) 15 %
0.1
0.2
0.3
0.4
60
140
230
350
140
230
350
500
c
c
opto-decoupled 0.2 A - 24 V DC
c
160 to 690 1 %
90 to 400 V 1 %
45 to 65 Hz 0.5 %
- 1 to + 1 2.5 %
- 9000 to 9000 kW 5 %
0 to 9999 MWh 5 %
c
2 possible options
0.2 to 1 In 2 % steps
0.5 x tr 5 %
0.2 to 1 In 2 % steps
0.25 x tr 5 %
0.2 to 1 In 2 % steps
0.5 x tr 5 %
0.2 to 1 In 2 % steps
60 s fixed 5 %
for earth fault protection
long-time, short-time, earth
alarm
RS 485
JBus
9600 bauds
255
tripping on Im, Ir, Ih
alarm
all pick-ups and delays
open or closed
currents I1, I2, I3 max
voltages U12, U23, U31
voltages V1N, V2N, V3N
cos , f
- 9000 to 9000 kW. 0 to 9999 MWh 5 %
- 9000 to 9000 kVar. 0 to 9999 MVahr 5 %
24, 48, 125 V DC or 100, 240 V AC

(1) Depending on the equipment, the "self-monitoring" alarm signal may or may not trip the circuit breaker, see "service continuity" option on the order form.

23

Merlin Gerin

BTP207E-2.160-STR68U

23

21/12/01, 9:52

Masterpact: functions and characteristics

control unit selection


STR 68 U (cont.)
option m selection

The following table indicates the functions of


the different versions, designated m01 to
m31.
For terminal wiring see page xxxx.

Option M can be incorporated in control unit


STR68U to provide the following functions:
c RS485 data transmission at 9600 bauds to
JBUS protocol;
c remote signal via opto-electronic output;
c zone selective interlocking for earth fault
protection.

without data transmission


option
remoting
load monitoring and control
pick-up Ic1 indication
load shedding
pick-up Ic2 indication
load shedding
load reconnection
fault indications
Ir
Im/I
Ih
self-monitoring
zone selective interlocking
on the earth fault protection

m01

m02

m03

m04

m05

m06

m07

m08

c
c
c
c

c
c
c

c
c

c
c
c
c

c
c

c
c

c
c

c
c

c
c

c
c

m09

m10

m11

c
c
c
c

c
c
c

c
c

m12

m13

m14

m15

c
c

c
c

c
c
c
c

c
c
c
c

c
c
c
c

c
c
c

c
c

c
c
c

m16

c
c
c

c
c

c
c
c

c
c (1)
c
c

with data transmission


option
data transmission
all parameters (see page xxxx)
remoting
load monitoring and control
pick-up Ic1 indication
load shedding
pick-up Ic2 indication
load shedding
load reconnection
fault indications
Ir
Im/I
Ih
self-monitoring
zone selective interlocking
on the earth fault protection

m17

m18

m19

m20

m21

m22

m23

m24

m25

m26

m27

m28

m29

m30

m31

c
c
c
c
c

c
c

c
c

c
c

c
c
c

c
c

c
c

(1) Two separate outputs for Im and I.


Merlin Gerin

24
BTP207E-2.170-STR68U

24

21/12/01, 9:52

Basic functions: long time LT,


short time ST, instantaneous INST

Earth fault protection (option T)

Factory adjustments
The STR68U control unit is factory adjusted
as follows:
LT

E26042

E26039

operating zones

I2t ON

ST

I2t ON

1
I2t OFF

INST
T

I2t OFF

setting Ir
time delay tr
pick-up Im
time delay tm
pick-up I
earth fault pick-up Ih
time delay th
load monitor
Ic1
Ic2

In
480 s
4 In
0,2 s
maxi
0,2 In
0,1 s
In
In

T1

T2

4
5
0

Ir

Im

earth fault protection settings


T1 : earth fault pick-up Ih
T2 : earth fault time delay th

overcurrent settings
1 : LT setting Ir (long time)
2 : LT time delay tr (long time)
3 : ST pick-up Im ( short time)
4 : ST time delay tm ( short time)
5 : INST pick-up I (instantaneous)

load monitoring and control


(option M)
Operation with 2 load limit pick-ups

Operation with 1 load limit and 1 load


reconnection pick-up

E26038

E26037

Ic2

Ic2

Ic1

Ic1

load monitoring and control settings


Ic1 pick-up (load limit)
Ic2 pick-up (load limit)

load monitoring and control settings


Ic1 pick-up (load limit)
Ic2 pick-up (load reconnection)

Merlin Gerin

BTP207E-2.170-STR68U

25

25

21/12/01, 9:52

Masterpact: functions and characteristics

control unit accessories

048327

battery module (PIL)


Complementary to the local indication of the
faults (F option for STR 38 and STR 58 trip
units), the battery module avoids the need
for any external power supply to save front
face indications.

048321

interface module ET44


Compulsory with the data transmission
option on the STR 68 trip unit, the ET44
interface module allows:
c setting of the transmission speed;
c definition of the address of the breaker
(which will not be affected by any drawout
breaker manipulation);

025172

relay module (MR6)


For relaying of information from outputs of
modules m01 to m32 of control unit STR 68
via output changeover contacts
10 A/220 V AC or 3 A/24 V DC.

025173

power supply module (AD)


These modules can be used to power
control unit complementary functions which
cannot be self-powered by the built-in
current transformers:
c STR 38 and STR 58: fault type indication
(F);
c STR 58: segregated alarm switch (V);
c STR 58: communication option (COM);
c STR 28, STR 38, STR 58: ammeter (I) for
load less than 20% of In.
c STR 68: indication and saving of

025171

battery module (BAT)


Providing a complement to the AD module,
the battery module provides backup power
for display indications and maintenance
indicator data in the event of a power failure.
Float connected between the power supply
and the control unit, it ensures a backup
time of approximately:

047035

mini test kit (BU)


This self-contained portable unit is used to
check STR 18 M to STR 58 U control units
operations and breaker tripping.
Power supply: five 9 V alkaline batteries (not
supplied).

052172

portable test kit for STR 18


to STR 58
The portable test kit is used:
c for control unit STR 68, to power, check
and carry out adjustments and tests on the
breaker/control unit assembly (control unit
without auxiliary power supply connected);

This module is equipped with a button for reactivation, of fault indications that have been
de-activated by the battery power-saving
feature. A test button is used to check the
battery status.

c the direct remote control of the breaker,


thanks to two outputs directly controlled
through the data transmission.
Installation: on vertical plate or symmetrical
rail.
Power supply: 24 V DC with galvanic
isolation, or AD type power module.
Installation : on vertical plate or symmetrical
rail.
Power supply module (AD) is required.

measurements, alarms, maintenance


indicator;
c MR6 module.
Moreover, these modules protect the trip unit
from transient overvoltages thanks to
galvanic isolation.
Available voltages:
c AC 50/60 Hz: 110 V, 220 V or 380 V
(20 %; +15 %) (consumption 10 VA);
c DC : 24/30 V, 48/60 V, 125 V (20 %)
(consumption 10 W).
Installation: on vertical plate or symmetrical
rail.
c 12 h with STR 38 and STR 58 control
units;
c 1.5 h with STR 68 control unit.
Installation: on vertical plate or symmetrical
rail. (ambient temperature from: 0 C to
+50 C).

This test kit is common to the Masterpact,


Compact NS, C, CM ranges.

c for other control units, to check the


operation of the trip unit by measuring the
actual trip time:
v long-time protection,
v short-time protection,
v instantaneous protection,
v earth-fault protection.
Power supply: 110, 220 V AC 50/60 Hz.
This test kit is common to the Masterpact,
Compact NS, C, CM ranges.

Merlin Gerin

26
BTP207E-2.180-unit cont

26

21/12/01, 9:56

Masterpact: functions and characteristics

auxiliary power supplies

The protection functions and most of the


options available for the STR control units
are self-powered. An auxiliary power supply
is nevertheless required for certain uses.

self-powered

auxiliary power supply


direct
AD + BAT
connection
modules

terminals

battery

no (1)

yes (2)

F1/F2

no

no (1)
no (1)

yes
yes

F1/F2
F1/F2

yes
no

no (1)

yes

F1/F2

no

STR 28 / 58
protection : LT, ST, INST
option I
if I u 20% In
if I < 20% In
or single phase load
option F
option FV
option ALR
option R
option T/W
if Ih u 0.2 x In
if Ih < 0.2 x In

yes
yes
no
no
no
yes
yes
yes
no (3)

STR 68
protection : LT, ST, INST, T, W

yes

other functions : see drawings page 71


(1) Not recommended: possible with a 24 V DC source, class 2, 5 Watt, ripple factor < 10%.
(2) Display will in this case be "". Auxiliary supply allows to save maximeter information.
(3) Ih pick-ups for which protection is not self-powered are printed in red on the trip unit front face.

27

Merlin Gerin

BTP207E-2.180-unit cont

27

21/12/01, 9:56

Masterpact: functions and characteristics

013282

auxiliaries

electrical operating
mechanism
Added to the manual charging mechanism,
a motor charges and automatically
recharges the stored-energy spring upon
breaker closing making possible fast
O-C-O cycles.
Opening and closing operations are
instantaneous.
The manual mechanism remains available
for emergency use.
characteristics
power supply 50/60 Hz (V)
consumption (VA)
DC (V)
consumption (W)
motor start-up surge
charging time

The electrical operating mechanism


includes:
c the gear motor(MCH);
c a closing release (XF);
c a shunt release (MX) or an undervoltage
release (MN) for opening;
c "springs charged" limit switch changeover
contact (CH).
The addition of the electrical operating
mechanism does not alter circuit breaker
dimensions.

geared motor MCH


100/127 - 200/240 - 250/277 - 380 - 415 - 440 - 480
180
24/30 - 48/60 - 100/125 - 200/250
180
2 to 3 In for 0.1 s
3 to 4 s

14
BTP207E-2.202-circuit-breaker

Merlin Gerin

14

21/12/01, 9:58

035932

operation counter
(CDM)
With gear-motor option only. The operation
counter is read from the front and gives the
total number of breaker operating cycles.

15

Merlin Gerin

BTP207E-2.202-circuit-breaker

15

21/12/01, 9:58

Masterpact: functions and characteristics

016813

auxiliaries (cont.)

releases
Two types of voltage releases can be used
for remote opening of Masterpact circuit
breakers.
Undervoltage releases
c instantaneous (MN)
This release instantaneously opens the
breaker when its supply voltage drops below
a value between 35 % and 70 % of its rated
voltage.
If the release is not energised, the breaker
cannot be closed (either manually of
electrically). Any attempt to close will have
no effect on the main contacts.
Closing is possible when the release voltage
reaches 85 % of its rated value.
c time delayed (MNR)
To prevent the breaker tripping in the event
of transient voltage dips, this release has a
built-in time delay.
A special version, available on request,
allows instantaneous tripping (from a
mushroom-head emergency off button) by
the wiring of an external contact.

closing release (XF)


This device releases the breaker closing
mechanism when the spring is charged.
Energisation can be maintained, as the
closing release provides an antipumping
function.

characteristics
breaker response time
at Un
operating thresholds
opening
closing
power supply
AC 50/60 Hz (V)

036051

consumption (VA)
DC (V) (2)
consumption (W)

Shunt release (MX)


This release instantaneously opens the
breaker when energised. The supply can be
maintained or automatically disconnected. In
the latter case, the user can series connect
an internal auxiliary contact (OF).

Note: anti-pumping function:


After the breaker has been opened, either by
fault trip or by manual or electrical operation,
anti-pumping is provided by requiring
cancellation of the initial closing command
before reclosure of the breaker is possible.
The closing release is supplied on request
with the manual operating mechanism

undervoltage and shunt releases


MN
MNR
MX
90 ms 5
0.5 s-0.9 s
50 ms 10
1.5 s-3 s

from 0.35 to 0.7 Un


0.85 Un

closing release
XF
70 ms + 10, 15
i 3 200 A
80 ms 10 > 3 200 A

0.7 to 1.1 Un
0.85 to 1.1 Un

100 - 110/127 - 200 - 220/250 - 277 - 380/415 - 440/480 500/525(1)


20
24 - 30 - 48 - 60 - 100/110 - 125 - 200/220 - 250
15

Release combinations
Each Masterpact circuit breaker can be
equipped with:
1 MX + 1 MN + 1 XF, or
2 MX + 1 XF

(1) 500/525 V AC not available for MNR.


(2) MNR: DC, 125 V only.

16
BTP207E-2.204-auxiliaries

Merlin Gerin

16

21/12/01, 10:08

016814

"spring charged"
contact (CH)

auxiliary switches

018242

Double break changeover switches "OF"

Additional changeover switches ("OFSUP" block)

In addition to the main contact position


indication on the front, 3 auxiliary switch
blocks are available to indicate the open and
closed breaker positions.
c standard: 4 contacts (O) (2 normally
open 2 normally closed);
c optional: 4 directly-operated double
break changeover switches (OF) which
operate only when the minimum isolating
distance between the main contacts is
reached;
c optional: 24 additional changeover
switches (OFSUP block). These
microswitches can be parallel connected in
pairs to increase the rated current and
breaking capacity (in drawout version only).

In addition to the local mechanical indicator


and the "ready to close" contact, the gearmotor limit switch changeover contact can
indicate that the operating mechanism is
ready (spring charged). This contact is
supplied as standard with the gear motor.

fault-trip indication (SDE)


As standard and independent from the
differentiated fault indications on the control
unit, any fault-trip is indicated by:
c 1 fault-trip indicator/reset button;
c 1 changeover contact (SDE).
The reset button must always be pressed
after a fault-trip to enable breaker closing.
Optional: automatic reset, allowing remote
breaker closing without local resetting (the
SDE contact operates up to the reset).

"ready to close" contact


(PF)

016524

Optional:
This contact simultaneously indicates the
following:
c the breaker is open;
c the stored-energy mechanism is charged;
c the mechanism is correctly reset;
c the breaker opening pushbutton is not
locked;
c no opening order is present.
This contact can be series connected to the
closing release (XF) to disable the antipumping function.

connected/disconnected
position carriage switches
Changeover switches to indicate "connected"
position "CE"

In addition to the local "connected/test/


disconnected" position indicator, two series
of optional carriage switches are available
for the fixed chassis (of drawout circuit
breaker).
c a block of 4 changeover switches to
indicate "connected" position (CE);
c a block of 2 changeover switches to
indicate "disconnected" position (CD). The
disconnected position is indicated only when
the minimum isolating distance between
main and auxiliary circuits has been
reached.
By series connection of these contacts the
test position can be indicated.
c 1 changeover switch to indicate "test"
position (CT).

contact characteristics
auxiliary contacts
quantity

current rating (A)


breaking capacity
AC 50/60 Hz (A rms.)
pf u 0.3

DC (A)
L/R i 0.01 s

type
O
changeover
NO
2 NO
NC
2 NC
10
110 V
240 V
10
380 V
6
480 V
6
600 V
3
48 V
3
125 V
0.5
250 V
0.25
500 V

OF
4

OFSUP SDE PF
24
1
1

CE
4

CD
2

CT
1

CH
1

10
15
10
10
10
6
5
3
3
0.5

10

10

10

10

10

10

10

10
6
6
3
3
0.5
0.25

10
5

10
5

10
6
6
3
3
0.5
0.25

10
6
6
3
3
0.5
0.25

10
6
6
3
3
0.5
0.25

17

Merlin Gerin

BTP207E-2.204-auxiliaries

10
6
6
3
3
3
3
0.3 0,3 0.5
0.15 0.15 0.25

17

21/12/01, 10:08

Masterpact: functions and characteristics

013280

accessories

safety shutters (VO)

shutter lock (VVC)

Optional: mounted on the fixed portion of


drawout breakers, the safety shutters
automatically block access to the
disconnection contacts when the breaker is
in the disconnected or test position (degree
of protection IP 20).

Optional: mounted on the fixed portion of


drawout breakers, a mobile and lockable
slide (padlocks not supplied) is used to:
c lock the shutters in the closed position;,
c hold the shutters in the open position.
A support is provided at the back of the
frame to hold the slide when not in use. A
second slide is supplied:
c on request for Masterpact i 3200 A ;
c in standard for Masterpact 4000 A
to 6300 A.

arc chute cover (CC)

terminal shield (CB)

Optional: attached to the fixed portion of


drawout circuit breakers or on the fixed
circuit breaker, this cover eliminates the
safety clearance requirement above the
breaker (this option is incompatible with front
connection on top).

Optional: attached to the fixed portion of


drawout circuit breakers, this cover prevents
access to the electrical auxiliary connection
terminals.

interphase barrier
(EIP)

partitioning fixture (AC)

035928

Fixed portion of drawout circuit breakers with safety shutters

016818

Fixed portion of drawout circuit breakers with arc chute and


terminal shield

Optional: attached to the fixed portion of


drawout breakers (except when equipped
with front connections), this fixture provides
IP30 partitioning between the breaker
compartment (accessible from the front) and
the connection zone (located in the rear). It
simplifies partition cut-outs.
Example of partition cut-out for
Masterpact M08 to M32.
445 (3
445
(3pole)
ples)

560
pole)
etand
560
(4(4
ples)

28518

Optional: attached to the fixed portion of


drawout breaker (Masterpact i M40 3P), the
insulated partitions for vertical installation
between connection pads to:
c reinforce insulation at connection points in
insulated busbar installation;
c prevent arc propagation to the breaker in
the event of a line side fault on the main
busbars.

360

datum
rfrence
a

plan
de fixation
chassis
chssis
fixing
60

a: partitioning fixture (AC)


b: interphase barrier (EIP)

18
BTP207E-2.206-accessories

Merlin Gerin

18

21/12/01, 10:09

016819
016814

door frame (CDP)

transparent cover (CCP)

Optional: fixed to the cublicle door, this


frame provides an equipment seal function
(degree of protection IP 405).
Suitable for fixed and drawout patterns.

Optional: hinge-mounted and equipped with


a screw-closure, this cover is designed for
the door frame (CDP). It provides a degree
of protection of IP549.
Suitable for fixed and drawout patterns.

auxiliaries connection

"Connected/disconnect/test" position
contacts
Installed on the fixed chassis, these contacts
are directly connected by 6.35 mm
connectors.

Fixed version
Connection by one or two plugs,
disconnectable and accessible from the front
(screwless tunnel terminals for flex cable up
to 2.5 mm2).
Drawout version
c standard: connection to a terminal block
in the front of the fixed frame (screwless
tunnel terminals for flex cable up to
2.5 mm2).
The breaker auxiliary circuits are connected
by connection blocks that operate
automatically to isolate the auxiliaries when
the breaker is in "disconnected" position.
On request, an additional 5-way terminal
block (BS) is available to provide five
common points.
c optional: by one or two plugs,
disconnectable and accessible from the
front, installed on the mobile part of the
assembly.

015561

Auxiliaries for fixed version

Auxiliaries for drawout version

035940

breaker mismatch
protection
Optional: for drawout version only, this
systems allows only correctly matched
breakers (rating, type wiring, etc.) to be
inserted in a given fixed frame.
Two matching parts (1 for the fixed chassis
and 1 for the mobile assembly) can be used
to create 20 different user selected
combinations.

Earth connection
The earth connection terminal (drawout
pattern) is on the left hand side of the
chassis. It is marked with the symbol t

19

Merlin Gerin

BTP207E-2.206-accessories

19

21/12/01, 10:09

Masterpact: functions and characteristics

035932

accessories (cont.)

pushbutton locking device


Optional: this padlockable device (padlocks
not supplied) prevents direct operation of the
circuit breaker by covering the "on" and "off"
pushbuttons. This locking device can also be
used for lead sealing.

"off" position locking


device
Optional: a Profalux key lock locks the
breaker in "off" position by holding the
pushbutton in its depressed position.

pushbutton locking device


by padlocks (not supplied)

VBP

"off " position locking device (1)

035931

1 Profalux key lock


2 Profalux key locks, identical profiles
adaptation fixture for 1 Profalux key lock, lock not supplied
On request
1 Ronis key lock
2 Ronis key locks, identical profiles
adaptation for 1 Castell key lock, lock not supplied
adaptation for 1 Kirk key lock, lock not supplied

"disconnected",
"connected" and "test"
position locking (1)
Mounted on the frame and accessible with
the cubicle door locked, this system is
available in two versions:
c "disconnected" position locking;
v as standard by 1 padlocking device (1 to 3
padlocks not supplied),
v optional: by a locking device with 1 or 2
Profalux key locks;
c "disconnected", "connected" and "test"
position locking (optional);
v by 1 padlocking device, with 1 to 3
padlocks not supplied (VEC),
v by 1 locking device, with 1 or 2 Profalux
key locks (VSPEC),
padlocks
"disconnected"
standard
"disconnected"
standard
"disconnected"
standard
"disconnected,
connected"
"disconnected,
connected"
"disconnected,
connected"

1 keylock

VSPA1
VSPA2
VSPRAC
VSRA1
VSRA2
VSCA
VSKA

Remarks
c the keylocks are of the captive key type,
i.e. key free when locked;
c Profalux and Ronis keylocks can be used
together;
c a second Profalux or Ronis lock, identical
to the one mounted on the chassis, can be
supplied separately.

2 keylocks

"disconnected"
optional
"disconnected" "disconnected"
optional
optional

"disconnected,
connected"
"disconnected, "disconnected,
connected"
connected"

(1) keylock types


Profalux B24 D4Z
Ronis
1351 B
Kirk
CN22-12
Castell
SK7113/1
Trayvou L1P1E

20
BTP207E-2.208-accessories

Merlin Gerin

20

21/12/01, 10:09

"disconnected" position locking


by padlocks (not supplied)
1 Profalux key lock
2 Profalux key locks, identical profiles
2 Profalux key locks, different profiles
adaptation fixture for Profalux key lock (lock not supplied)

as standard
VSPC1
VSPC2
2 VSPC1
VSPRCC

On request
1 Ronis key lock
2 Ronis key locks, identical profiles
2 Ronis key locks, different profiles
adaptation fixture for Castell key lock (lock not supplied)
adaptation fixture for Kirk key lock (lock not supplied)
adaptation fixture for Trayvou key lock (lock not supplied)

VSRC1
VSRC2
2 VSRC1
VSCC
VSKC
VSTC

"disconnected", "connected" and "test" position locking


by padlocks (not supplied)
1 Profalux key lock
2 Profalux key lock, different profiles

VEC
VSEPC
2 VSEPC

On request
1 Ronis key lock
2 Ronis key locks, differents profiles
adaptation fixture for Castell key lock (lock not supplied)
adaptation fixture for Kirk key lock (lock not supplied)

VSERC
2 VSERC
VSECC
VSEKC

016817

door interlock
Optional: mounted on the chassis, this lock
prevents the cubicle door from being opened
when the breaker is in the "connected"
position. If the breaker is put into the
"connected" position with the door open, the
latter can be closed without disconnecting
the breaker.

withdrawal/spring charged
interlock
Optional: this lock prevents withdrawal of
the breaker from the chassis when the
springs are charged.
Incompatible with MN or MNR release.

racking interlock

Optional: this lock prevents insertion of the


breaker racking handle when the cubicle
door is open. It can be defeated by pressing
on the unlocking mechanism.

door interlock
right-hand side
left-hand side
racking interlock
withdrawal/spring charged interlock

a: racking interlock
b: door latch

VPECD
VPECG
VPOC
VEAA

21

Merlin Gerin

BTP207E-2.208-accessories

21

21/12/01, 10:09

Masterpact: functions and characteristics

automatic source-changeover systems

053060

025186

Masterpact source-changeover systems can


be used to implement various configurations
involving several incoming feeders. The two
or three Masterpact circuit breakers or
switch-disconnectors used are mechanically
interlocked to prevent certain combinations
of operations.
All types of Masterpact devices may be fitted
(fixed and drawout versions, three-pole and
four-pole, different ratings).
The devices may be arranged:
c vertically, i.e. stack-mounted and
interconnected by a set of rods;
c horizontally (two only), i.e. side-by-side
and interconnected by a set of cables.
An electrical interlock must be used when
the source changeover is part of an
automatic system.

053061

053058

Masterpact automatic source-changeover system

Controller

automatic source-changeover system with 2 devices


without controller

In this case, the automatic control system to


initiate changeovers between the Normal
and Replacement sources under
predefined conditions must be provided by
the customer.
Note that we can provide diagrams for the
design of various automatic control systems
for different sources.

E33079

A Masterpact automatic sourcechangeover system with 2 devices is


made up of:
1 - circuit breaker QN connected to the
"Normal" source;
2 - circuit breaker QR connected to the
"Replacement" source;
3 - mechanical interlocking system by rods
or cables;

automatic control of the system can be


provided by adding:
4 - electrical interlocking unit IVE;
5 - auxiliaries control plate ACP;
6 - controller BA or UA.

E33078

3
2

Each Masterpact circuit breaker is


equipped with:
c a motor mechanism;
c a shunt release (MX);
c a ready to close contact (PF);
c a block of 4 changeover switches (OF);
c an additional terminal block (BS) and a
block of 4 connected position switches
(CE) for source-changeover systems made
up of drawout breakers.

with controller
E33082

In this case, conditional changeovers


between the Normal and Replacement
sources are initiated by a Merlin Gerin
controller.
IN
GER

MERLIN

N
R
N

UN =

UN =

UR

0,5s

UN
ON /
ON /
OFF

OFF

0,5s

/O

/O

fault

fault
stop

test

manu

R
N

4
6
GERIN
MERLIN
multi

0 . OFF

P25M

GERIN
MERLIN
multi

0 . OFF

660V
2-1
AC3-IEC29

P25M
660V
2-1
AC3-IEC29

Test

B US

Test

MERLIN

IN
GER

N
R

UN =

UN =

generat

or

UR

UN
ON /
ON /
OFF

OFF

I
/O

/O
fault

fault
auto
stop

manu

test
STOP

R
N

5
Merlin Gerin

36
BTP207E-2.220-invers source

36

21/12/01, 10:10

automatic source-changeover system with 3 devices


without controller

In this case, the automatic control system to


initiate changeovers between the Normal
and Replacement sources under
predefined conditions must be provided by
the customer.
Note that we can provide diagrams for the
design of various automatic control systems
for different sources.

E33080

A Masterpact automatic sourcechangeover system with 3 devices is


made up of:
1 - 2 circuit breakers QN1 and QN2
connected to the "Normal" source;
2 - circuit breaker QR connected to the
"Replacement" source;
3 - mechanical interlocking system by rods;

for such applications (consult us)


automatic control of the system can be
provided by adding:
4 - 2 electrical interlocking unit IVE;
5 - auxiliaries control plate ACP;
6 - controller BA or UA.

Each Masterpact circuit breaker is


equipped with:
c a motor mechanism;
c a shunt release (MX);
c a "ready to close" contact (PF);
c a block of 4 changeover switches (OF);
c an additional terminal block (BS) and a
block of 4 "connected" position switches
(CE) for source-changeover systems made
up of drawout breakers.

3
2

E33383

with controller (consult us)

GERIN
MERLIN
multi

0 . OFF

P25M

GERIN
MERLIN
multi

0 . OFF

660V
2-1
AC3-IEC29

P25M
660V
2-1
AC3-IEC29

MERLIN

IN
GER

Test

UN =

UN =

UR

0,5s

Test

UN
ON /
I
ON /
OFF

OFF

0,5s

/O

/O

fault

fault
stop

test

manu

R
N

B US

5
MERLIN

IN
GER

N
R

UN =

UN =

UR

UN
ON /
ON /
OFF

OFF

I
/O

/O
fault

fault
auto
stop

manu

test
STOP

gen

erator

R
N

In this case, conditional changeovers


between the "Normal" and "Replacement"
sources are initiated by a Merlin Gerin
controller.

37

Merlin Gerin

BTP207E-2.220-invers source

37

21/12/01, 10:10

Masterpact: functions and characteristics

automatic source-changeover systems (cont.)


mechanical interlock selection
025184

mechanical interlocking by
connecting rods for 2 or 3
stack-mounted breakers
This involves:
c 2 or 3 Masterpact circuit breakers and/or
switch-disconnectors;
c an adaptation fixture on the right side of
each breaker;
c 1 or 2 sets of connecting rods with no-slip
adjustments;
The various parts are mounted by the user.
The changeover system with interlocking by
connecting rods is also available in a version
which is factory mounted on a steel frame.
Maximum distance between fixing
planes: 900 mm.

025186

mechanical interlocking by
cables for 2 side-by-side
breakers
This involves:
c 2 Masterpact circuit breakers and/or
switch-disconnectors;
c an adaptation fixture on the right side of
each breaker;
c a set of cables with no-slip adjustments;
The various parts are mounted by the user.
Distance between fixing planes:
c maximum: 2 000 mm;
c minimum: breaker height with arc chute
cover (see pages ????).

device combinations

assembly and installation

All combinations are possible: fixed and


drawout versions, three-pole and four-pole,
different ratings, circuit breakers or switchdisconnectors.
All control units can be used on the circuit
breakers.

The various parts of the Masterpact


automatic source-changeover system are
mounted and connected by the user. No
circuit breaker modifications are required.
The wiring diagrams are shown on pages
??? to ???.
The Masterpact automatic sourcechangeover system may also be supplied
factory-wired and mounted on a metal
frame.

Merlin Gerin

38
BTP207E-2.230-invers source

38

21/12/01, 10:11

Masterpact: functions and characteristics

automatic source-changeover systems (cont.)


automatic control: typical configurations
c a motor mechanism (MCH);
c a shunt release (MX);
c a "ready to close" contact (PF);
c a block of 4 changeover switches (OF);
c an additional terminal block (BS) and a
block of 4 "connected" position switches
(CE) for changeover systems including
drawout breakers.

Necessary auxiliaries and accessories


To implement the configurations below, each
Masterpact circuit breaker must be equipped
with:

Option with "lockout after fault"


With this option, the circuit breaker must be
reset manually after a fault trip.

power circuit

possible combinations

configuration type

cat. No.

interlocking with 2 breakers

Q1
0
0
1

Q2
0
1
0

electrical interlocking
automatic control
with generator set
with permanent "Replacement"
source

685363

Q1
0
1
0
1
0

Q2
0
0
0
1
1

Q3
0
0
1
0
0

automatic control with permanent


"Replacement" source
with lockout after fault
685366
without lockout after fault
688183
automatic control with generator set
with lockout after fault
689642
without lockout after fault
689644

Q1
0
1
0
0

Q2
0
0
1
0

Q3
0
0
0
1

electrical interlocking
with lockout after fault
without lockout after fault

688188
688187

Q1
0
1
0
0
1
0
1

Q2
0
0
1
0
1
1
0

Q3
0
0
0
1
0
1
1

electrical interlocking
with lockout after fault
without lockout after fault
automatic control

688189
688190
689651

E30736

The electrical interlocking system and


automatic control system for multiple
sources must be wired by the user. It must
be used in conjunction with the mechanical
interlocking system.
Typical wiring configurations are available
on request. See examples below. For other
configurations, consult us.

Q1

Q2

E30737

interlocking with 3 breakers


2 "Normal" sources + 1 "Replacement"
source

Q1

Q2

Q3

E30738

interlocking with 3 breakers


3 sources, only one breaker closed

Q1

Q2

Q3

E30739

interlocking with 3 breakers


2 sources + 1 coupling

Q1

Q2

Q3

39

Merlin Gerin

BTP207E-2.230-invers source

688784
688942

39

21/12/01, 10:11

Masterpact: functions and characteristics

automatic source-changeover systems (cont.)


controller option selection
Used together with the auxiliaries control
plate ACP, controllers BA and UA initiate the
automatic changeover operations according
to the status of the "Normal" and
"Replacement" sources.
c mounted on the front of the switchboard.
The distance between the controller and the
auxiliaries control plate must not exceed
2 metres. The interconnection wiring must
be done by the customer.

E32704

E32705

Installation
Two possibilities:
c mounted directly on the auxiliaries control
plate ACP.

MERLI
multi

0 . OFF

N GERIN

MERLI
multi

N GERIN

660V
292-1
AC3-IEC

0 . OFF

N GERIN

MERLI
multi

0 . OFF

N GERIN

0 . OFF

660V
292-1
AC3-IEC

P25M
660V
292-1
AC3-IEC

660V
292-1
AC3-IEC

Test

Test

Test

Test

B US

multi

P25M

P25M

MERLI
P25M

RIN
IN GE
MERL

N
R

B US

RIN
IN GE
MERL

N
R

UN =

/O

ON /

OFF

/O

OFF

/O

OFF

/O

UN =

fault

auto
stop

OFF

ON /

ON /

fault

UR

UN

ON /

UN =

UR

UN

manu
UN =

test

STO

genera

tor

R
N

fault

fault
auto
stop

manu

test
tor

P
STO

genera

R
N

customer
connection

terminal block and electrical interlocking unit: IVE


E32703

The terminal block and electrical interlocking


unit IVE is used to connect the operating
mechanism.
Control voltage:
c 48 to 415 V, 50/60 Hz - 440 V 60 Hz.
The IVE control voltage must be the same
as the motor mechanism voltage.

auxiliaries control plate: ACP


053060

The auxiliaries control plate ACP includes:


c two P25M circuit breakers supplying and
protecting the automatic control circuits for
the "Normal" and "Replacement" sources.
These circuit breakers have an infinite
breaking capacity;
c two relay contactors for the BA or UA
controller;
c the terminal block for connection to the
controller.

Power supply:
Power is supplied by the "Normal" and
"Replacement" sources. The control
voltage for the auxiliaries control plate must
be the same as for the IVE unit and the
motor mechanisms.
Control voltages
c 220 to 240 V 50/60 Hz;
c 380 to 415 V 50/60 Hz - 440 V 60 Hz.
Installation:
The auxiliaries control plate ACP must be
wired to the IVE unit by the customer.

Merlin Gerin

40
BTP207E-2.240-invers source

40

21/12/01, 10:12

053058

controller

Controller UA

controller

BA

compatible circuit breakers

All Masterpact circuit breakers

UA

4-position switch
automatic operation
forced operation on "Normal" source
forced operation on "Replacement" source
stop (both "Normal" and "Replacement" sources off)

c
c
c
c

c
c
c
c

c
c
c

automatic operation
monitoring of the "Normal" source and automatic changeover
generator set control
load shedding and reconnection of non-priority circuits
changeover to the "Replacement" source if one of the phases of the
"Normal" phase is absent

test
by opening the P25M circuit breaker supplying the controller
by pressing the test button on the front of the controller

c
c

indications
circuit breaker status indication on the front of the controller: on, off,
fault trip, automatic mode indicating contact
automatic mode indicating contract

c
c

c
c

c
c

other functions
selection of type of "Normal" source (single-phase or three-phase)
voluntary transfer to "Replacement" source (e.g. energy management commands)
during peak-tariff periods (energy management commands), forced operation
on "Normal" if "Replacement" source not operational
supplementary control contact (not carried out by the controller). Transfer to
"Replacement" source only if contact closed. (ex: UR frequency control)
setting of maximum startup time for the replacement source

c
c

c
c

power supply
control voltages (1)

220 to 240 V 50/60 Hz


380 to 415 V 50/60 Hz - 440 V 60 Hz

options
c

communication option

(1) The same voltage must be used for the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, then
the Normal and Replacement sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used.

Merlin Gerin

BTP207E-2.240-invers source

41
41

21/12/01, 10:12

Masterpact: functions and characteristics

automatic source-changeover systems


controller option selection (cont.)

E30184

controller BA

Controller BA can be used with Masterpact


circuit breakers to implement a straightforward automatic source-changeover
system (switching from one source to
another depending on the presence of
voltage UN on the "Normal" source).

MERLIN GERIN
compact / masterpact

BA automatism
220/240 V 50/60 Hz

UN

UR

ON/I

ON/I

OFF/O

OFF/O

fault

fault

UN = 0

2 4
t1
1
8 s
15
0.5
0.1 30

0.5s

0.5s

t2
s

stop
manu

reset

15 30
8
60
120
4
0.1 240

UN = I

auto

Electrical characteristics
Power is supplied from the auxiliaries control
plate ACP. The same voltage must be used
to supply the ACP plate, the IVE unit and the
circuit breaker motor mechanisms. If this
voltage is the same as the source voltage,
the "Normal" and "Replacement" sources
can be used directly for the power supply.
If not, a BC type or equivalent isolation
transformer must be used.

Control voltages
c 220 to 240 V 50/60 Hz;
c 380 to 415 V 50/60 Hz - 440 V 60 Hz.

Operation
c a four-position switch can be used to
select:
v automatic operation;
v forced operation on source N;
v forced operation on source R;
v stop (both "Normal" and "Replacement"
sources off);
c adjustment of time delays in front:
v t1 from 0.1 to 30 seconds;
v t2 from 0.1 to 240 seconds;
c circuit breaker status indication on the
front of the controller: on, off, fault trip;

c integrated terminal block for connection of


the following signals:
v inputs:
order for voluntary transfer to source R
(e.g. energy management commands),
supplementary control contact: (not
carried out by the controller). Transfer to
"Replacement" source only if contact closed
(ex: UR frequency control),
v outputs:
indication of operation in automatic mode.
Connection to the terminal block: see p.XXX.
c controller BA can be tested by opening
the P25M circuit breaker on the N circuit,
thus simulating a failure of UN.
See detailed transfer steps on page XXX.

Front face of controller BA

Time delay settings:


QN: Masterpact circuit breaker with motor
mechanism on Normal source,
QR: Masterpact circuit breaker with motor
mechanism on Replacement source,
t1: time delay before QN opens when the voltage
UN of the Normal source disappears,
t2: time delay before QR opens when the voltage
UN of the Normal source is restored.

Merlin Gerin

42
BTP207E-2.250-BA

42

21/12/01, 10:12

c 4-position switch in "auto" position


(automatic operation)

QN et QR open

off

N
I

operat. on
source N

R
O

4-position switch N et UN prsente

UN fail (duration > t1) or voluntary


switching order received
UR present and supplementary
control contact NR closed

"auto"

reset

c 4-position switch in "N " position


(forced operation on "Normal" source)
E30187

E27107

E21108

c 4-position switch in "stop" position

duration a 1 s

QR opens

QN opens

t > 0,5 s

end of reset
t > 0,5 s

QN closes

QR closes

QN ferm

"stop"
operat. on
source N

QR closed

N
O

operat. on
source R

R
I

N
I

R
O

action on 4-position switch

UN present for t > t2 or voluntary


switching order stopped

c 4-position switch in "R" position


(forced operation on "Replacement" source)
E32708

QR opens

t > 0,5 s

4-position switch in "R" position


UR present and supplementary control
contact NR closed
QN closes
QN opens

QN closed
t > 0,5 s

QR closes

QR closed

operat. on
source R

N
O

R
I

action on 4-position switch

Merlin Gerin

BTP207E-2.250-BA

43
43

21/12/01, 10:12

Masterpact: functions and characteristics

automatic source-changeover systems


controller option selection (cont.)
controller UA

E30183

053059

Controller UA can be used with Masterpact


circuit breakers to implement a sourcechangeover system offering the following
automatic functions:
c switching from one source to another
depending on the presence of voltage UN
on the "Normal" source;
c control of an engine generating set;
c shedding and reconnection of non-priority
circuits;
c switching to the "Replacement" source in
the event of a failure on one of the phases of
the "Normal" source.
Electrical characteristics
Power is supplied from the auxiliaries control
plate ACP. The same voltage must be used
to supply the ACP plate, the IVE unit and the
circuit breaker motor mechanisms. If this
voltage is the same as the source voltage,
the "Normal" and "Replacement" sources
can be used directly for the power supply. If
not, a BC type or equivalent isolation
transformer must be used.

Control voltages
c 220 to 240 V 50/60 Hz;
c 380 to 415 V 50/60 Hz - 440 V 60 Hz.

Operation
c a four-position switch can be used to
select:
v automatic operation;
v forced operation on source N;
v forced operation on source R;
v stop (circuit breakers open and manual
operation);
c adjustment of time delays in front:
v t1 from 0.1 to 30 seconds;
v t2 from 0.1 to 240 seconds;
v t3 from 0.5 to 30 seconds;
v t4 from 0.5 to 30 seconds;
v t5 from 60 to 600 seconds;
c circuit breaker status indication on the
front of the controller: on, off, fault trip;
c test button on the front of the controller
to check the transfer from the Normal
source to the "Replacement" source and the
return to the "Normal" source;

c integrated terminal block for connection of


the following signals:
v inputs:
order for voluntary transfer to source R
(e.g. energy management commands),
supplementary control contact: (not
carried out by the controller). Transfer to
"Replacement" source only if contact closed
(ex: UR frequency control),
v outputs:
control of engine generator set,
load shedding of non-priority circuits,
indication of operation in automatic mode;
c 3 switches provide the following functions:
v selection of the type of "Normal" source,
i.e. single-phase or three-phase;
v enable or disable voluntary energy
management transfer if the "Replacement"
source is not operational;
v selection of the maximum tolerated
starting time for the engine generator set
("Replacement" source): 120 s or 180 s.

Batibus option for controller UA


A communication function can be used to
check the following from a remote location:
c status of the circuit breakers (open,
closed or fault trip);
c voltage presence on the Normal and
Replacement sources;
c presence of an order forcing operation on
the Replacement source (e.g. for energy
management purposes);
c values of settings and configurations,
c status of the non-priority circuits (whether
subject to load shedding or not).

In automatic mode, this communications


option also offers the possibility of remote
forced operation on the Replacement
source.

MERLIN GERIN
compact / masterpact

UA automatism
220/240 V 50/60 Hz

UN
ON/I

ON/I

OFF/O

OFF/O

fault

fault

stop
manu

reset

auto
test

UR

UN = 0

t4
s

5 10
2
15
20
1
0.5 30

t2
s

15 30
8
60
120
4
0.1 240

240 300
160
360
480
120
60 600

2 4
t1
1
8 s
15
0.5
0.1 30
5 10 t3
2
15 s
20
1
0.5 30

UN = I

t5
s

R
STOP

generator

Front face of controller UA

Time delay settings:


QN: Masterpact circuit breaker with motor
mechanism on Normal source,
QR: Masterpact circuit breaker with motor
mechanism on Replacement source,
t1: time delay before QN opens when the voltage
UN of the Normal source disappears,
t2: time delay before QR opens when the voltage
UN of the Normal source is restored,
t3: time delay before QR closes once QN has
opened and the load has been shed,
t4: time delay before QN closes once QR has
opened and the load has been reconnected,
t5: time delay for confirmation of presence of UN
before stopping the generator set.

44
BTP207E-2.260-UA

Merlin Gerin

44

21/12/01, 10:12

E30185

E27107

QN and QR open

stop

"auto"

reset

c 4-position switch in "N" position


(forced operation on "Normal" source)
E30187

c 4-position switch in "auto" position


(automatic operation)

c 4-position switch in "stop" position

N
I

operat. on
source N

R
genset off
O

4-position switch in "N" and UN


present

UN fails (duration > t1) or voluntary


switching order received
duration a 1 s

end of reset

QR opens and load


shedding

genset startup

t > t4

UR present for t < 120 s or 180 s


and supplementary control contact
NR closed

QN closes

QN opens and load


shedding

QN closed

"stop"

operat. on
source N

t > t3

QR closes

N
I

R
genset off
O

action on 4-position switch

QR closed

R
genset on
I

UN present for t > t2 or voluntary


switching order stopped

c 4-position switch in "R" position


(forced operation on "Replacement" source)
E30186

N
O

operat. on
source R

4-position switch in "R" and UN


present

QR opens and load


reconnection
genset startup
t > t4

UR present for t < 120 s or 180 s


and supplementary control contact NR
closed
QN closes
QN opens and load
shedding

QN closed
t > t3
genset remains on
QR closes
UN present for t > t5 and no
voluntary switching order received
QR closed
genset off
operat. on
source R

N
O

R
genset on
I

UR absent
action on 4-position switch

45

Merlin Gerin

BTP207E-2.260-UA

45

21/12/01, 10:12

Merlin Gerin

40
BTP207E-3.001-sommaire

40

21/12/01, 10:13

LV power air circuit


breakers and
switch-disconnectors

Masterpact
3/ installation
and connection
page
installation
general
safety clearance
fixed circuit breakers M08 to M32
drawout circuit breakers M08 to M32
fixed circuit breaker M40
drawout circuit breaker M40
fixed circuit breaker M50
drawout circuit breaker M50
drawout circuit breaker M63
manual source changeover systems
manual and automatic source
changeover systems
connection
fixed and drawout circuit breakers
M08N/M10N/M12N
fixed and drawout circuit breakers
M08H,L/M10H,L/M12H,L/M16N,H,L
fixed and drawout circuit breakers
M20N,H/M25N,H
fixed and drawout circuit breakers
M20L/M25L/M32H
fixed and drawout circuit breaker M40
fixed and drawout circuit breaker
M08 to M16
fixed and drawout circuit breaker
M50 to M63
wiring diagrams:
c STR 18 M / 28 D / 38 S / 58 U
c STR 28 D / 38 S / 58 U avec options
c STR 68 U avec options m01 m31
c automatic source changeover
c manual source changeover

0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0

41

BTP207E-3.001-sommaire

41

21/12/01, 10:13

Masterpact: installation and connection

general

installation

Masterpact circuit breakers must be installed


in the vertical position on a base plate or on
rails.

drawout circuit breaker


(M08 to M63)

The drawout version makes it possible to:


c rapidly remove and/or replace the circuit
breaker without having to deal with
connections;
c install stand-by outgoers in a switchboard
that will receive the necessary circuit
breakers later in time

E31256

E31254

"Connected" position

26

"Test" position
ample clearance between contacts

E31255

Installation on a metal base plate

018241

Installation on rails

45

"Disconnected" position
easy withdrawal, short travel

E31257

E29026

E28811

fixed circuit breaker (M08 to M50)

305

"Withdrawn" position
compact dimensions

Merlin Gerin

42
BTP207E-3.200-gnralit

42

21/12/01, 10:14

Masterpact: installation and connection

safety clearance

Certain distances must be maintained


between a circuit breaker and other
elements such as panels, bars and other
circuit breakers. Taken together, these
distances form the safety clearance for the
circuit breaker. The diagrams and the table
below indicate the required distances when
installing Masterpact circuit breakers.

These distances are the results of tests


carried out in accordance with standard
IEC 947-2 and are in part determined by the
ultimate breaking capacities.

100

C
A

E31230

100

E31233

E31232

fixed circuit breaker

A
B

Masterpact M08 to M50


type of connection

to insulated barrier
A
B
C
front connection without cover (1) 360
30
0
rear connection without cover 150
30
20
rear connection with cover
0
0
20

to metal parts
A
B
360
70
250
70
0
0

D (2)
0
0
0

95
95

D (2)
0
0

to live bars
A
B
1085
420
1085
420
145
105

495
125

D (2)
0
0
0

100

C
E31231

E31229

drawout circuit breaker

213

Masterpact M08 to M63


type of connection

to insulated barrier
A
B
front connection without cover (1) 300
15
rear connection without cover 150
15
rear connection with cover
0
0

(1) Shield necessary.


(2) D is the clearance required for connection of
auxiliaries.
D = 0 for fixed circuit breakers (required clearance
included in the height of the connection plugs).
D = 0 for drawout circuit breakers as well.

C
0
45
45

to metal parts
A
B
300
50
150
50
0
0

45
45

445
75

Note: For the fixed circuit breakers, a clearance of


130 mm is required on top for removal of the arc
chutes.

43

Merlin Gerin

BTP207E-3.200-gnralit

to live bars
A
B
1000
400
1000
400
60
85

43

21/12/01, 10:14

Masterpact: connection

general

Conductor materials
The terminals of Masterpact circuit breakers
can be used to connect bare copper, tinned
copper or tinned aluminium conductors
without any special surface treatment.

016807

016806

Four types of connection are possible:


c rear horizontal;
c rear vertical;
c front;
c mixed.
The terminals are sized to allow circuit
breaker connection with bars up to 20 mm
thick (except for the M40, M50 and M63).

Rear vertical connection

016808

025179

Front connection

electrodynamic forces

Rear horizontal connection

Mixed connection.
Upper terminals: front connection.
Bottom terminals: vertical connection.

c the first bar spacers must be located at


less than a certain distance from the circuit
breaker connection point;

c this maximum distance must be


respected to withstand the electrodynamic
forces that are applied between the bars
during a short-circuit.

Maximum distance between circuit breaker connection point and the


first bar spacers for various short-circuit currents
Isc (kA)
distance (mm)

30
350

50
300

65
250

80
150

150
150

Merlin Gerin

44
BTP207E-3.210-gnralit

100
150

44

21/12/01, 10:16

Note:
The indicated values come from tests and
theoretical calculations made for the
parameters given below. These tables are
intended to serve as a general guide for
connection design and not to replace
experience acquired for a certain type of
connection or the need for subsequent tests.

parameters used in
establishing the tables

c maximum admissible bar


temperature: 100 C;
c temperature in the switchboard around
the circuit breaker and its connections: Ta;
c copper busbars.

drawout circuit breakers

E31258

connection selection table

drawout circuit breakers, edgewise bars


maximum
current

Ta = 40 C

800
1000
1250
1400
1600
1800
2000
2200
2500
2800
3000
3200
3600
4000
4700
5000
5100
5700
6300

M08
M10
M12
M16
M16
M20
M20
M25
M25
M32
M32
M32
M40
M40
M50
M50
M63
M63
M63

Masterpact

Ta = 50 C
number of bars
5 thick bars 10 thick bars
2b.50 x 5
1b.50 x 10
2b.50 x 5
1b.50 x 10
2b.63 x 5
1b.63 x 10
2b.63 x 5
1b.63 x 10
2b.80 x 5
1b.80 x 10
2b.80 x 5
1b.80 x 10
2b.100 x 5
2b.63 x 10
2b.100 x 5
2b.63 x 10
4b.80 x 5
2b.80 x 10
4b.100 x 5
2b.100 x 10
5b.100 x 5
3b.80 x 10
6b.100 x 5
3b.100 x 10
4b.100 x 10
4b.100 x 10
5b.100 x 10
5b.100 x 10
5b.100 x 10
6b.100 x 10
6b.100 x 10

Masterpact
M08
M10
M12
M16
M16
M20
M20
M25
M25
M32
M32
M40
M40
M50
M50
M50
M63
M63

Ta = 60C
number of bars
5 thick bars 10 thick bars
2b.50 x 5
1b.50 x 10
2b.50 x 5
1b.50 x 10
2b.63 x 5
1b.63 x 10
2b.63 x 5
1b.63 x 10
2b.80 x 5
1b.80 x 10
2b.80 x 5
2b.50 x 10
2b.100 x 5
2b.63 x 10
2b.100 x 5
2b.63 x 10
4b.80 x 5
2b.80 x 10
4b.100 x 5
2b.100 x 10
6b.100 x 5
3b.100 x 10
3b.100 x 10
4b.100 x 10
4b.100 x 10
5b.100 x 10
5b.100 x 10
6b.100 x 10
6b.100 x 10

Masterpact
M08
M10
M12
M16
M20
M20
M25
M25
M32
M32
M40
M40
M50
M50
M50
M63
M63

Merlin Gerin

BTP207E-3.210-gnralit

number of bars
5 thick bars 10 thick bars
2b.50 x 5
1b.50 x 10
2b.63 x 5
1b.63 x 10
3b.50 x 5
2b.50 x 10
3b.50 x 5
2b.50 x 10
3b.63 x 5
2b.50 x 10
3b.80 x 5
2b.63 x 10
3b.100 x 5
2b.80 x 10
3b.100 x 5
2b.80 x 10
4b.100 x 5
3b.80 x 10
4b.100 x 5
3b.80 x 10
3b.100 x 10
4b.100 x 10
4b.100 x 10
5b.100 x 10
5b.100 x 10
6b.100 x 10
6b.100 x 10

45
45

21/12/01, 10:16

Masterpact: installation

fixed circuit breakers M08 to M32

dimensions
E30742

553

E30749

necessary space for removing


the arc chutes
(with or without arc chute cover)

E30748

3 or 4 poles

438
493
378

90 130

45

311
(*)
(*)

30 mini
60 maxi

150

400

11

68

11

422 (3p)

290

515

11

11

537 (4p)

(*) Datum

mounting
on a base plate

mounting detail
14

E30775

E30766

E30765

on rails

11

150

150

30 mini
60 maxi

A
B

30 mini
60 maxi

3 poles
150
400

2 11 x 6

4 poles
150
515

cut-outs
holes for escutcheon

E30764

E30763

cut-outs de porte

152,5

270
14,5
148,5

(*)
71,5

69

27
37,5

80 mini

80
mini

325

11 5

180

180

17,5

(*)

(*) Datum
Merlin Gerin

48
BTP207E-3.230-M0832

48

21/12/01, 10:17

Masterpact: installation

drawout circuit breaker M08 to M32

E30746

3 or 4 poles

"disconnected" position

E30747

dimensions
E30741

45

a
439

800
mini

(*)

60

101

175

55

325

55

128

435 (3p)

85

367

55

425

70

550 (4p)

(*)

(*) Datum

mounting

mounting detail

E30768

E30767

E30775

on rails

on a base plate

14

11

101

175

101

cut-outs

E30761

front panel cut-out

A
B

175

3 poles
175
325

2 11 x 6

4 poles
175
425

holes for escutcheon

E30760

ACB's side

152,5

270

148,5

71,5

47

55

100
mini
ACB's basis

100
mini

325

Merlin Gerin

BTP207E-3.230-M0832

19

69

18,5

11 5

180

180

17,5

49

49

21/12/01, 10:17

Masterpact: installation

fixed circuit breaker M40

dimensions
E31226

E30752

necessary space for removing


the arc chutes
(with or without arc chute cover)
90

45

819

E30753

3 or 4 poles

553
759
493

130

311
(*)
(*)

30 mini
60 maxi

150
290

11

515

11

68

537 (3p)

11

780
11

802 (4p)
(*) Datum

mounting
on a base plate

mounting detail
E30775

E30772

E30771

on rails

14

11

150

50 maxi

150

50 maxi

A
B

30 mini
60 maxi

30 mini
60 maxi

3 poles
150
515

2 11 x 6

4 poles
150
780

cut-outs
holes for escutcheon

E30764

E30763

front panel cut-out

152,5

270
14,5
148,5

(*)
71,5

69

27
37,5

80 mini

80
mini

325

11 5

180

180

17,5

(*)

(*) Datum
Merlin Gerin

50
BTP207E-3.240-M40

50

21/12/01, 10:17

Masterpact: installation

drawout circuit breaker M40

E30743

E30750

3 or 4 poles

"disconnected" position

E30751

dimensions

45

a
439
484

(*)

800
mini

128

(1)

60

101

55

425

70

85

175

550 (3p)

367

60

55

350

350

815 (4p)

(*)

(*) Datum
(1) 4-pole version only.

mounting

on a base plate

mounting detail

E30777

E30773

E30774

on rails

40

40

30

350

150

350

101

101

175

(1) 4-pole version only.

cut-outs

front panel cut-out

2 11 x 6 (3p)
6 11 x 22 (4p)

175

holes for escutcheon

ACB's side

E30760

E30762

175

(1)

(1)

152,5

270

47

19

45 (1)

55

100
mini

325

ACB's basis

(1) 4-pole version only.

69

18,5

11 5

180

180

17,5

51

Merlin Gerin

BTP207E-3.240-M40

148,5

71,5

51

21/12/01, 10:17

Masterpact: installation

fixed circuit breaker M40

dimensions
E31226

E30752

necessary space for removing


the arc chutes
(with or without arc chute cover)
90

45

819

E30753

3 or 4 poles

553
759
493

130

311
(*)
(*)

30 mini
60 maxi

150
290

11

515

11

68

537 (3p)

11

780
11

802 (4p)
(*) Datum

mounting
on a base plate

mounting detail
E30775

E30772

E30771

on rails

14

11

150

50 maxi

150

50 maxi

A
B

30 mini
60 maxi

30 mini
60 maxi

3 poles
150
515

2 11 x 6

4 poles
150
780

cut-outs
holes for escutcheon

E30764

E30763

front panel cut-out

152,5

270
14,5
148,5

(*)
71,5

69

27
37,5

80 mini

80
mini

325

11 5

180

180

17,5

(*)

(*) Datum
Merlin Gerin

50
BTP207E-3.240-M40

50

21/12/01, 10:17

Masterpact: installation

drawout circuit breaker M40

E30743

E30750

3 or 4 poles

"disconnected" position

E30751

dimensions

45

a
439
484

(*)

800
mini

128

(1)

60

101

55

425

70

85

175

550 (3p)

367

60

55

350

350

815 (4p)

(*)

(*) Datum
(1) 4-pole version only.

mounting

on a base plate

mounting detail

E30777

E30773

E30774

on rails

40

40

30

350

150

350

101

101

175

(1) 4-pole version only.

cut-outs

front panel cut-out

2 11 x 6 (3p)
6 11 x 22 (4p)

175

holes for escutcheon

ACB's side

E30760

E30762

175

(1)

(1)

152,5

270

47

19

45 (1)

55

100
mini

325

ACB's basis

(1) 4-pole version only.

69

18,5

11 5

180

180

17,5

51

Merlin Gerin

BTP207E-3.240-M40

148,5

71,5

51

21/12/01, 10:17

Masterpact: installation

fixed circuit breaker M50

dimensions

90

45

E30757

E30756

necessary space for removing


the arc chutes
(with or without arc chute cover)

E31227

3 poles

819
759

130

311

(*)
(*)
30 mini
60 maxi

150

780

11

68

11

802

290

(*) Datum

mounting
on a base plate

mounting detail
E30775

E30772

E30771

on rails

14

11

150

50 maxi

150

50 maxi

A
B

30 mini
60 maxi

30 mini
60 maxi

2 11 x 6

3 poles
150
780

cut-outs
holes for escutcheon

E30764

E30763

front panel cut-out

152,5
270

14,5
148,5

(*)

71,5

69

27
37,5

80 mini

80
mini

325

11 5

180

180

17,5

(*)

(*) Datum
Merlin Gerin

52
BTP207E-3.250-M50

52

21/12/01, 10:18

Masterpact: installation

drawout circuit breaker M50

E30744

3 or 4 poles

"disconnected" position

E30755

E30754

dimensions

45

45

a
484

800
mini

(*)

128
60

101

175

60

85

55

350

350

815 (3p)

367

40

475

55

475

1045 (4p)

(*)

(*) Datum

mounting

on a base plate

mounting detail

E31228

E30770

E30769

on rails

40

40

30

350

150

350

175

101

101

175

cut-outs

175

holes for escutcheon

front panel cut-out

E30762

6 11 x 22 (3p)
6 11 x 33 (4p)

E30760

ACB's side

152,5

270

47

19

45 (1)

55

100
mini

325

ACB's basis

(1) 4-pole version only.


Merlin Gerin

BTP207E-3.250-M50

148,5

71,5

69

18,5

11 5

180

180

17,5

53

53

21/12/01, 10:18

Masterpact: installation

drawout circuit breaker M63

E30745

3 poles or 4 poles

"disconnected" position

E30759

E30758

dimensions

45

45

a
484

800
mini

(*)

128
60

101

175

40

85

55

475

475

1045

367

(*)

(*) Datum

mounting
on a plate

mounting detail

E30778

E30770

E30769

on rails

40

40

30

475

150

475

175

101

101

175

cut-outs

175

holes for escutcheon

front panel cut-out

side of c.b.

E30760

E30762

6 11 x 33

152,5

270

47

148,5

71,5

19

55

325

45 (1)

18,5

100
mini

11 5

base of c.b.

(1) 4-pole version only.

180

180

17,5

Merlin Gerin

54

BTP207E-3.260-M63+inv sour

69

54

21/12/01, 10:18

Masterpact: installation

source-changeover system

Interlocking by connecting rods for 2 stack-mounted breakers


drawout pattern, 3 or 4 poles
E30780

E30779

fixed pattern, 3 or 4 poles

50
50
5
52

40

30

14

30

125

125

900
max.

900
max.
900
max.

175

153

105

(*)

163

30 base of c.b.
180
30 mini
60 maxi

45
65
166

base of c.b.
for ratings :
M08 to M40 (3p)

base of c.b.
for ratings :
M40 (4p) to M63

(*)

82
(*)

44
(*)

Interlocking by connecting rods for 3 stack-mounted breakers


fixed pattern, 3 or 4 poles
E30782

E30781

drawout pattern, 3 or 4 poles

50
5

40

52

180

60

14

60

14

60

180
900
max.

900
max.

50

50
5

40

52

180

60

180
900
max.

900
max.

153

175

900
max.

105

(*)

163

45
65
166

base of c.b.
for ratings :
M08 to M40 (3p)

base of c.b.
for ratings :
M40 (4p) to M63

100

(*)

30 base of c.b.
180
30 mini
60 maxi

62
(*)

(*) Datum
Merlin Gerin

BTP207E-3.260-M63+inv sour

55
55

21/12/01, 10:18

Masterpact: installation

source-changeover system

Interlocking by cables for 2 side-by-side breakers


E30783

fixed or drawout patterns, 3 or 4 poles


2m maxi

200 mini
r= 120 mini

r= 120 mini

automatic source-changeover system

10

11 1 2 1 3 1 4 1 5 1 6

E33352

H48

E30784

E33353

electrical interlocking IVE

mounted on a frame

H47
H43

H49
R

controller
P58

L33

P62

L34
L35

M32(4p)
M40(3p)
M32(3p)

E33354

E33355

auxiliaries control plate ACP and controller UA/BA

2100

P60

1940
H51

1640

H50

H52

940

P61
P59
P63

L36
L37

panel cut-out for controller UA/BA

56

56

56

E33364

E33363

150
56

600

750
C34

C34

Dimensions (mm)
type
C34 H43
140
120

H47
151

H48
137

H49
160

H50
200

H51
255

H52
22

L33
6

L34
48

L35
84

L36
138

L37
150

P58
61,5

P59
170

P61
90

P62 P63
150(min) 187
Merlin Gerin

56
BTP207E-3.270-inv sour+M08N

P60
95

56

21/12/01, 10:19

Masterpact: connection

fixed and drawout circuit breakers


M08N/M10N/M12N
fixed circuit breaker
front connection

rear connection

front connection
E30786

E30785

horizontal terminals vertical terminals

115

115

85
45

12,5

front connectors screen

115
25

10

N
(1)

10

25

112

horizontal terminals

15

17

115

E30787

12,5
107

115

85

115
45

23

17,5

(*)

rear connection

132

53

175 (**)

2 12

50

335

25

10

(*)
12,5

221

2 12

10
233

(*)
12,5

vertical terminals
E30788

278

115

115

85

115

10

2 12

(*) Datum.

(*)

(**) Hole for securing front connection support bracket.


(1) On request, neutral on the right.

drawout circuit breaker


front connection

rear connection

front connection

E30789

E30790

horizontal terminals vertical terminals

115

115

115

47,5
80
25 25

front connectors screen

12,5

15

N
(1)

3 12

10

(*)
45

rear connection
112

25

92

10

horizontal terminals

112

74,5

115

E30791

306

115

25
12,5

273
300,5

12,5

47,5
45

25

30
175

115

10

15
12,5

2 12

10

(*)

306

vertical terminals
E30792

(*)

115

115

47,5

2 12

(*) Datum.

(*)

(1) On request, neutral on the right.


Merlin Gerin

BTP207E-3.270-inv sour+M08N

115

57

57

21/12/01, 10:19

Masterpact: connection

fixed and drawout circuit breaker


M50 to M63
fixed circuit breaker M50
rear connection 3 poles
vertical terminals

E30819

horizontal terminals

100

30
200

112

53
(*)

25

25
25
25 52

15

246

55
306

12,5
15

drawout circuit breaker M50


rear connection 3 or 4 poles
vertical terminals

E30810

horizontal terminals

100
30
112
25 157
25
25

92
137

79,5
12,5
43

25
15

345

363

15

(*)

drawout circuit breaker M63


rear connection 3 or 4 poles
vertical terminals

E30820

horizontal terminals

100
30
112
25 157
25
25

92
137

79,5
12,5
25

43

15

345

363

15

(*)
(*) Datum.
Merlin Gerin

64
BTP207E-3.310-raccord M50-M63

64

21/12/01, 10:22

fixed circuit breaker M50


rear connection 3 poles
vertical terminals
248

E30826

E30827

horizontal terminals

248

248

213

248

226

142,5
35

142,5

12

213

10

10

25 25 25

20

13

145

20
12

175

145
(*)

(*)

drawout circuit breaker M50


rear connection 3 poles
vertical terminals

E30828

E30829

horizontal terminals

252,5

252,5

252,5

252,5
10

12

220
12,5

100
72,5

100

10

25 25 25 45 25 25 25

12
145

(*)

(*)

rear connection 4 poles

297,5

vertical terminals

245

245

100

100
12,5

12,5

245

245

100

35
10

220

25 25 25

297,5

E30831

E30830

horizontal terminals

72,5

10

10

12

10

25 25 25 45 25 25 25

12

(1)
70

(*)

(1)

145
(*)

drawout circuit breaker M63


rear connection 3 poles
vertical terminals
E30823

horizontal terminals

E30822

350

350

350

350

117,5
92,5

117,5

10

12

260

10

25 25 25 85 25 25 25

12

(*)

185

(*)

rear connection 4 poles


vertical terminals

E30824

E30825

horizontal terminals

206
100

287

287

260

260

206

287

12

10

10

25 25 25 85 25 25 25

12
(*)

(1)
(*) Datum.

(1)
70

185
(*)

(1) On request, neutral on the right.


Merlin Gerin

BTP207E-3.310-raccord M50-M63

117,5
92,5

260

25 25 25

287

35

117,5

65
65

21/12/01, 10:22

Masterpact: connection

fixed and drawout circuit breaker


M40
fixed circuit breaker
rear connection 3 or 4 poles
vertical terminals

E30809

horizontal terminals

100

30
112
252
53
(*)

25

25
25
25

15

243

55
306

12,5
15

(*) Datum.

drawout circuit breaker


rear connection 3 or 4 poles
vertical terminals

E30810

horizontal terminals

100
30
112
25 157
25
25

92
137

79,5(4p)
12,5
175

34,5(3p)
15

345

363

15

(*)

(*) Datum.
Merlin Gerin

62
BTP207E-3.300-raccord M40

62

21/12/01, 10:22

fixed circuit breaker


rear connection 3 poles

180
100

vertical terminals
165

E30812

E30811

horizontal terminals
85

130

25 25 25

172,5

85
35

80

100

25 25 25

172,5
145

10

10

12,5

12,5

12
(*)

12

80
(*)

rear connection 4 poles

230
100

vertical terminals

216

165

100

85

130

25 25 25

208,5

172,5

85
35

80

100

25 25 25

230

E30814

E30813

horizontal terminals

80

145

10

10

12,5

12,5
12

12

(1)

(*)

80

(1)

(*)

(*) Datum.
(1) On request, neutral on the right.

drawout circuit breaker


rear connection 3 poles

E30815

155

vertical terminals
155

100
12,5

E30816

horizontal terminals
65

172,5

35

155

25 25 25

47,5

172,5
10

10

25 25 25 40

12
(*)

12

70
(*)

rear connection 4 poles


vertical terminals

230
155

191
155

155
100

65

230

E30818

E30817

horizontal terminals

208,5

25 25 25

47,5
35

155

10

10

25 25 25 40

12,5

12
12

(1)

172,5

(*)

70

(1)

(*)

(*) Datum.
(1) On request, neutral on the right.
Merlin Gerin

BTP207E-3.300-raccord M40

63
63

21/12/01, 10:22

Masterpact: connection

fixed circuit breakers


M20L/M25L/M32H
fixed circuit breaker
front connection

rear connection

front connection
115

E30901

E30802

horizontal terminals vertical terminals

115

85

115
80
25 25

15

front connectors screen

15

N
(1)

3 12

100
335

rear connection

112

horizontal terminals

25 162

87

18

12,5

15
18

(*)
221

30

E30803

25
25

53

175 (**)

(*)

30

115

140

115

72,5
85,5
25 25

11,5

15

15

3 12

(*)

236
268
E30804

vertical terminals
115

140

140

60
25

4 12

(*)

(*) Datum.
(**) Hole for securing front connection support bracket.
(1) On request, neutral on the right.
Merlin Gerin

60
BTP207E-3.290-raccorde

60

21/12/01, 10:20

Masterpact: connection

drawout circuit breakers


M20L/M25L/M32H
drawout circuit breaker
front connection

rear connection

front connection
115

E30805

E30806

horizontal terminals vertical terminals

125

125

37,5
100
25 25 25

front connectors sceen

12,5

15

N
(1)

30

4 12

(*)

100

rear connection

363
112

115

E30807

92

horizontal terminals
25 157
25
25

125

37,5
100

34,5
37

125
25 25 25

15

329
344

12,5

12,5
4 12

30

(*)

15
344

15

vertical terminals
E30808

(*)

115

152,5

152,5

10
25

4 12

(*)

(*) Datum.
(1) On request, neutral on the right.
Merlin Gerin

BTP207E-3.290-raccorde

61
61

21/12/01, 10:20

Masterpact: connection

fixed and drawout circuit breakers


M08H,L/M10H,L/M12H,L/M16N,H,L
fixed circuit breaker
rear connection

front connection

E30793

horizontal terminals vertical terminals


front connectors screen

115

E30901

front connection

115

85

115
80

12,5

25 25

15

N
(1)

10

112

107

15

horizontal terminals

17

17,5

115

E30832

15

(*)

rear connection

132
25
25

53

175 (**)

3 12

80

335

115

115

85
80

25 25

15

(*)
12,5

221
10
233

12,5

(*)

115

85

vertical terminals
115

E30794

278

3 12

115

10

3 12

(*) Datum.

(*)

(**) Hole for securing front connection support bracket.


(1) On request, neutral on the right.

drawout circuit breaker


rear connection

front connection

E30795

horizontal terminals vertical terminals

115

E30790

front connection

115

115

47,5
80
25 25

front connectors screen

12,5

15

N
(1)

3 12

10

(*)
80

rear connection

306

112

92
15

horizontal terminals
E30796

25 112
25

115

115

115

25 25

30
175

25
12,5

273
300,5

12,5

47,5
80

57

15

15
12,5

3 12

10

(*)
306

vertical terminals
E30797

(*)

115

115

47,5

10

3 12

(*) Datum.

(*)

(1) On request, neutral on the right.

Merlin Gerin

58
BTP207E-3.280-raccorde

115

58

21/12/01, 10:19

Masterpact: connection

fixed and drawout circuit breakers


M20N,H/M25N,H
fixed circuit breaker
rear connection

front connection

E30798

horizontal terminals vertical terminals

E30901

front connection

115

115

80
25 25

12,5

front connectors screen

85

115

15

N
(1)
20

335

25
25

152

horizontal terminals
115

E30832

53

115

115

15

18

85
80

15 3

107

(*)

rear connection

112

175 (**)

3 12

80

25 25

17,5

15

12,5

(*)
12,5

221

3 12

16

(*)

233
283
E30799

vertical terminals
115

115

85

115
20

3 12

(*) Datum.

(*)

(**) Hole for securing front connection support bracket.


(1) On request, neutral on the right.

drawout circuit breaker


rear connection

front connection

E30800

horizontal terminals vertical terminals

115

E30790

front connection

115

115

47,5
80
25 25

front connectors screen

12,5

15

N
(1)

3 12
(*)

20

80

rear connection

306

112

92
15

horizontal terminals
115

E30796

25 112
25

115

115

25 25

30
175

25
12,5

273
300,5

12,5

47,5
80

62

15

15
12,5

3 12

20

(*)
306

vertical terminals
E30801

(*)

115

115

47,5

16

3 12

(*) Datum.

(*)

(1) On request, neutral on the right.


Merlin Gerin

BTP207E-3.280-raccorde

115

59
59

21/12/01, 10:19

Masterpact: connection

E30721

wiring diagrams
STR 18 M / 28 D / 38 S / 58 U
CHASSIS AUXILIARIES
CN 1

- CN

BREAKER AUXILIARIES

CONTROL UNIT

+
Fu

AT

fault

disconnected

connected

closed

ready
to
close

BPO

BPF

open

springs
charged
314 312 324 322 334 332 344 342 352 354 362 364 372 374

82

84

212 222

234 244

12

14

24

22

32

34

44

42

D4

C12

C2

A4 252 254 262 B4

CE
or

MN
or
MNR

M
MX

XF
MX

OF
F

O
CH

SDE

processing
unit

CD

311

321

331

341

351

361

PF

CT

371

81

211 221

231 241

11

21

31

41

D1

C11

C1

A1

251

B1

Fu

- CN

AT:
BPO:
BPF:
CE:

emergency off
"open" pushbutton
"close" pushbutton
"connected" position contact
(10 A/240 V AC)
M:
spring charging motor
(180 VA/240 V AC)
XF:
closing release
(20 VA/240 V AC)
MX: shunt release (20 VA/240 V AC)
MN: undervoltage release
(20 VA/240 V AC)
MNR: time delayed undervoltage release
(20 VA/240 AC)
OF: auxiliary changeover contacts
(10 A/240 V AC)
O:
2 auxiliary NO contacts
(10 A/240 V AC)
F:
2 auxiliary NC contacts
(10 A/240 V AC)
SDE: fault trip indication contact
(10 A/240 V AC)
CH: charging motor limit switch contact
PF:
"ready to close" contact
(10 A/240 V AC) (closing possible if
breaker is open, not locked and
operating mechanism charged)
CD: "disconnected" position contact
(10 A/240 V AC)
CT:
test posiiton contact
(10 A/240 V AC)

c diagram shown with circuits deenergised,


breaker open and in "connected" position,
springs charged and relays in released
position;
c accessories such as pushbuttons, lamps
and fuses are not supplied with the circuit
breaker.

Wiring of the MNR (modified diagram).


Instantaneous tripping with MNR when
contact 254-262 opens.
E30718

CN2

D4

254

MNR
D1

Note: the wiring of the external contact


replaces the spring charged indication and
the contact PF.

Merlin Gerin

66
BTP207E-3.320-raccord

262

66

21/12/01, 10:23

Masterpact: connection

E30720

wiring diagrams
STR 28 D / 38 S / 58 U with options
CHASSIS AUXILIARIES
CN 1

- CN

BREAKER AUXILIARIES

CONTROL UNIT

+
Fu

N
P1

S1

P2

S2

AT

(4)

(4)
LR
alarm

disconnected

connected

372

374

362
364

354

342

352

344

332

322

324

334

312

314

(2)
Z11 Z12

LR2

BPF

closed

fault

ready
to
close

BPO

open
springs
charged

Ic1 Ic2
V2

T2 T1

R1 R2

e+ e

82

(5)
84 212 222

234 244

12

14

22

24

32

34

42

44

D4

C12 C2

A4 252 254 262 B4

CE
or
MN
or
MNR

M
MX

XF
MX

OF
F
F

V
CH

SDE
ammeter

ALR

PF

processing
unit

CD

311

321

331

341

351

361

CT

371

Z21

Z22
(3)

LR1

F2 F1

V1

81 211 221

231 241

11

21

41

31

D1

C11 C1

A1

251

B1

power supply
(1)

Fu

AT:
BPO:
BPF:
LR:
CR:
T:
CE:

emergency off
"open" pushbutton
"close" pushbutton
long time trip (LT) indicating lamp
short time trip (ST) indicating lamp
earth fault trip indicating lamp
"connected" position contact
(10 A/240 V AC)
M:
spring charging motor
(180 VA/240 V AC)
R:
load monitoring and control
XF:
closing release (20 VA/240 V AC)
T:
earth fault protection (EZ and SZ:
input and output for zone selective
interlocking)
MX: shunt release (20 VA/240 V AC)
MN: undervoltage release
(20 VA/240 V AC)
MNR: time delayed undervoltage release
(20 VA/240 V AC)
OF: auxiliary changeover contacts
(10 A/240 V AC)
O:
2 auxiliary NC contacts
(10 A/240 V AC)
F:
2 auxiliary NC contacts
(10 A/240 V AC)
SDE: fault trip indication contact
(10 A/240 V AC)
CH: charging motor limit switch contact
F:
fault trip local indicator
FV:
segregated fault trip indication contact
(5 A/240 V AC)
PF:
"ready to close" contact
(10 A/240 V AC) (closing possible if
breaker is open, not locked and
operating mechanism charged)

CD:
CT:
C:

"disconnected" position contact


(10 A/240 V AC)
test position contact (10 A/240 V AC)
communication.

c Ic1: load shedding command according to


Ic1 setting
Ic2: load shedding command according to
Ic2 setting;
c diagram shown with circuits deenergised,
breaker open and in "connected" position,
springs charged and relays in released
position;
c accessories such as pushbuttons, lamps
and fuses are not supplied with the circuit
breaker.

Wiring of the MNR (modified diagram).


Instantaneous tripping with MNR when
contact 254-262 opens.
E30718

- CN

D4

D1

Note: the wiring of the external contact


replaces the spring charged indication and
the contact PF.

V contact wiring:
for breaker locking, depending on the
selected fault.
CN1/CN +
BPO
C2

V
V
(1) Power supply terminals for I or T or F options
(AD module with BAT battery module for backup
power).
(2) Zone selective interlocking with line side
breaker.
(3) Zone selective interlocking with load side
breaker (remove jumper).
(4) DC power supply. R contacts reset request
wiring of an external contact.
(5) With Z and/or C options, terminal 84 is not
available.

CN2/CN

MX
C1

Selective locking needs:


c external power supply (F1, F2);
c an additional terminal (BS).

Merlin Gerin

BTP207E-3.320-raccord

262

254

MNR

E30719

CN2

67
67

21/12/01, 10:23

Masterpact: connection

E30722

wiring diagrams
STR 68 U
with options m01 to m31
CHASSIS AUXILIARIES
CN 1

- CN

BREAKER AUXILIARIES

CONTROL UNIT

+
Fu

N
P1

S1

P2

S2

AT

(5)

disconnected

connected

closed

ready
to
close

BPO

BPF

open

374

372

362
364

352
354

332

342

334

344

322

324

312

314

springs
charged
T21

T2 T1(3)

T22

234 244

82 212 222

12

14

22

24

32

34

42

44

D4

C12

A4 252 254 262 B4

C2

CE
or
MN
or
MNR

M
MX

XF
MX

OF
F

O
CH

SDE
EZ(4)
M01
to
M16

processing
unit

CD

311

321

331

341

351

361

PF

CT

371

F1 F2
F12 F11 512 522 532 542 552 562
+
power supply (2)

81

211 221

231 241

11

21

31

41

D1

C11

C1

A1

251

B1

E56

E55

E54

E53

E52

E51

MR6

411
412
414
421
422
424
431
432
434
441
442
444
451
452
454
461
462
464

power supply
(1)

E2

Fu

AT:
BPO:
BPF:
CE:
M:
XF:
MX:
MN:
MNR:
OF:
O:
F:
SDE:
CH:
M01:
to
M16

PF:

MR6:

- CN

emergency off
"open" pushbutton
"close" pushbutton
"connected" position contact
(10 A/240 V AC)
spring charging motor
(180 VA/240 V AC)
closing release (20 VA/240 V AC)
shunt release (20 VA/240 V AC)
undervoltage release
(20 VA/240 V AC)
time delayed undervoltage release
(20 VA/240 V AC)
auxiliary changeover contacts
(10 A/240 V AC)
2 auxiliary NO contacts
(10 A/240 V AC)
2 auxiliary NC contacts
(10 A/240 V AC)
fault trip indication contact
(10 A/240 V AC)
charging motor limit switch contact
indication option equipped with
6 opto-decoupled
outputs to contacts (0.2 A/24 V DC),
for programming as per table on
page C54 (EZ: input for earth fault
protection zone selective interlocking)
"ready to close" contact
(10 A/240 V AC) (closing possible if
breaker is open, not locked and
operating mechanism charged)
relay module with 6 changeover
contacts (3 A, 24 V DC)

CD:
CT:

Wiring of the MNR (modified diagram).


Instantaneous tripping with MNR when
contact 254-262 opens.

"disconnected" position contact


(10 A/240 V AC)
test position contact
(10 A/240 V AC).

c diagram shown with circuits deenergised,


breaker open and in "connected" position,
springs charged and relays in released
position;
c accessories such as pushbuttons, lamps
and fuses are not supplied with the circuit
breaker.

E30718

CN2

D4

254

MNR
D1

Note: the wiring of the external contact


replaces the spring charged indication and
the contact PF.

(1) Power supply for control unit and modules.


(2) Power supply for option M and module MR6 by
module AD.
(3) Terminals T1 and T2 must be imperatively
short-circuited when the external CT is not
connected.
(4) The zone selective interlocking output is
provided by one output of module m01 to m32..
(5) Zone selective interlocking with load side
breaker: remove the jumper.
Merlin Gerin

68
BTP207E-3.330-raccord

262

68

21/12/01, 10:24

relay outputs

basic version
m01
other versions
m02
m03
m04
m05
m06
m07
m08
m09
m10
m11
m12
m13
m14
m15
m16

transmission
m17
reception outputs m18
m19
m20
m21
m22
m23
m24
m25
m26
m27
m28
m29
m30
m31

terminal number
512

522

LT

ST/Inst.

LT
LT
LT
limit 2
LT
LT
LT
LT
LT
limit 2
LT
limit 1
limit 1
Z
LT
512
ST/Inst.
ST/Inst.
T
T
T
Z
Z
Z
T
ST/Inst.
ST/Inst.
limit 2
shed 2
reconn. 2
shed 1

ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST/Inst.
ST
522
LT
AS
ST/Inst.
AS
Z
AS
limit 1
shed 1
shed 1
limit 1
shed 1
limit 1
shed 1
shed 1
AS

Protection:
LT
long time trip indication
ST/Inst. short time or instantaneous trip
indication
T
earth fault trip indication
Z
zone selective interlocking output
Load monitoring and control:
limit 1
indication of Ic1 setting overrun
limit 2
indication of Ic2 setting overrun
shed 1 load shedding command
according to Ic1 setting (limit 1)
shed 2 load shedding command
according to Ic2 setting
reconn. 2 load reconnection command
according to Ic2 setting (limit 2)

532

542

552

562

shed 1
shed 1
shed 1
shed 1
shed 1
shed 1
limit 1
shed 1
shed 1
shed 1
shed 1
shed 1
shed 1
shed 1
T
5

shed 2
reconn. 1
shed 2
shed 2
reconn. 2
shed 2
Z
shed 2
shed 2
shed 2
reconn. 2
shed 2
shed 2
reconn. 2

AS
limit 1
limit 1
limit 1
limit 1
limit 1
T
T
T
T
T
T
T
T
T
Inst.
1

limit 2
limit 2
AS
AS
AS
limit 1
AS
AS
Z
limit 1
Z
AS
Z
AS
AS
6

data transmission

e+
output

e
output

s+
input

s
input

connection modification for


data transmission: options m17 to m31
E30723

module

T2

T1

T21

datatransmission

M17
to
M31

processing
unit

T22

e+

r+

self-monitoring:
AS
indication of control unit fault or
overtemperature.
F1

F2

F12 F11

532 542 552 562

512 522

power supply
(2)

(3)
0V

4
5
8
9

ET 44 interface (1)
(3) S1 (4)
S2 (4)

24V

(1) Communication interface for RS485 - 9600 baud


network.
(2) Power supply for m option and ET44 interface
(AD module).
(3) Provided connectors.
(4) Remote controlled relay output (10 A, 220 V AC).
(5) JBUS, RS485, 9600 baud network.

Sub D9
connector
(5)

(3)

Merlin Gerin

BTP207E-3.330-raccord

RD
TD
RD+
TD+

69
69

21/12/01, 10:24

Masterpact: connection

wiring diagrams
STR 68 U
with options m01 to m31 (cont.)

T2

T1

T21

E30725

E30724

power supply connection


T22

module P

1 3

2 1 3

r
S1
S2
r+ 4
e 3
ET 44
e+ 2
1

2
4
5
8
9

RD
TD Sub D 9
RD+ connector
(6)
TD+

H1

H2

H1

H2

H4

BAT
H4

processing
unit

H3

H3

(4)

M17
to
M31

e+er+ r

Sub D 9
connector
(1)

Sub D 15
connector
module P

F1 F2

F12

F11 512 522


(7) (7) (7)

N L1 L2 L3
CN1 CN2 H1 H2 H3 H4

(5)
+

power supply
(2)

power supply for control


units and complementary
functions

(3)

All the protection functions of the control unit


are powered by current sensors built into the
circuit breaker.
However power must be supplied:
c to terminals F1 and F2 for the indication
and display functions:
v if the device has a low 3-phase load (less
than 20% of the rated current) or a singlephase load,
v if display and indications are required
when the circuit breaker is off;
c to terminals F11 and F12 for the M
modules.

(1) Provided cable: length 1.5 m (connected to


chassis).
(2) Available supply sources:
24-48 V DC, 125 V DC, 100-240 V AC.
(3) Backup power for trip unit information with BAT
module (remove jumpers).
(4) Provided cable.
(5) Voltage connection (load side shown, line side
also available). 3 or 4 poles available.
(6) JBUS, RS 485-9600 baud network.
(7) MR6 module wiring.

To ensure proper isolation of the circuits,


two separate power supplies are required.
They can be implemented as follows:
c for terminals F1 and F2:
v by direct supply of AC current (specify the
required voltage when ordering: 100, 220,
380 V 50/60 Hz),
v or by an AD module, with or without BAT
(1 AD for each STR68),
v or by direct supply of 24 V DC current (5
W, Class 2 insulation, < 10% ripple);
c for terminals F11 and F12:
v by another AD module (1 AD for each
STR68, in addition to the modules supplying
terminals F1 and F2),
v or by direct supply of 24 V DC current,
isolated from the circuit supplying terminals
F1 and F2 (5 W, Class 2 insulation, < 10%
ripple).

Merlin Gerin

70
BTP207E-3.340-raccord

70

21/12/01, 10:24

control unit STR 68 without power module


E30728

E30727

AC supply without indicators maintained after tripping

control
unit
F1

M01 to M16
option

F2

F11

module
MR6

control
unit

F12

F1

M17 to M31
option

F2

F11

module
ET 44

F12

0V

24V

module
AD

module
AD

110 - 220 - 380 V 50/60 Hz

110 - 220 - 380 V 50/60 Hz

AC supply with indicators maintained after tripping

E30729

E30730

DC supply with or without indicators maintained after tripping

control
unit
F1

M01 to M16
option

F2

F11

module
MR6

F12

control
unit
F1

F2

M17 to M31
option
F11

F12

module
BAT

module
BAT

module
BAT

module
AD

module
AD

0V

24V

+
module
BAT

module
AD

110 - 220 - 380 V 50/60 Hz


24/30 - 48/60 - 110/125 V CC

module
ET44

+
module
AD

110 - 220 - 380 V 50/60 Hz


24/30 - 48/60 - 110/125 V CC

STR 68 control unit with power module


E30732

E30731

AC or DC supply with or without indicators maintained after tripping

control
unit
F1

module
BAT

F2

M17 to M31
option
F11

F12

module
P
Cn1+

control
unit

module
MR6
F1

module
BAT

F2

M01 to M16
option
F11

module
MR6

F12

module
P
Cn1+

Cn2-

Cn2-

100/240 V 50/60 Hz
24/28 - 125 V CC

100/240 V 50/60 Hz
24/28 - 125 V CC

Note: the battery module (BAT) provides


back up power to the indicators on the trip
unit front face to maintain indications after
tripping. It can be omitted if the auxiliary
supply is reliable.
Merlin Gerin

BTP207E-3.340-raccord

71
71

21/12/01, 10:24

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)


electrical interlocking - 2 sources + 1 coupling
and lockout after fault (688189)
possible states
source 1
0 1
source 2
0 1
coupling
0 0

E33097

Version represented:
c 2 sources + 1 coupling;
c 2 circuit breakers closed;
c electrical interlocking with lockout after a
fault (SDE wiring): inoperative with
automatic reset option.

"SOURCE 1" BREAKER AUXILIARIES

S1

1
0
1

0
1
1

1
0
0

0
1
0

0
0
1

"SOURCE 2" BREAKER AUXILIARIES

"COUPLING" BREAKER AUXILIARIES

S2

CN1
CN2

D
to A

t1

COUPLING
t2

t3

t4

R1

B4

262

254

252

A4

C2

34

32

84

24

22

82

322

14

12

CE

312
324

B4

262

254

252

A4

C2

34

32

84

24

22

82

322

14

314

CE

XF

12

CE

312
324

B4

262

254

252

A4

C2

34

32

84

24

22

82

322

14

314

CE

R3
12

312
324

314

R2

M
MX
Q1

OF

OF

CE

XF

CE

OF
MX
SDE

QC

OF

OF

XF

OF

CH

MX
SDE

PF

OF

Q2

OF

CH

OF
SDE

PF

Q1:
QC:
Q2:
D:
t1:

Masterpact on source 1
Masterpact used for coupling
Masterpact on source 2
P25M circuit breaker (2 x 10 A)
coupling signal: source 1 failure
(minimum time delay 250 ms)
t2:
coupling signal: source 2 failure
(minimum time delay 250 ms)
t3:
uncoupling signal: source 1
restored (minimum time delay 250
ms)
t4:
uncoupling signal: source 2
restored (minimum time delay 250
ms)
R1,R2,R3: external relays for interlocking of
SDE auxiliary switches.

M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:

motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

B1

A1

C1

31

81

21

251

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
Note: All indicating signals by O, F, OF,
SDE, PF and CH auxiliary switches should
be protected by fuses that discriminate with
respect to the protection devices on the
automatic control circuits to avoid disturbing
the operation of the source-changeover
system.
The relays are not supplied with the circuit
breakers.

Merlin Gerin

88
BTP207E-3.430-raccord

11

321

311

B1

251

A1

C1

31

81

21

11

321

311

B1

251

A1

C1

31

81

21

11

321

311

CH
PF

88

21/12/01, 10:27

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)


electrical interlocking - 2 sources + 1 coupling
and wihtout lockout after fault (688190)
possible states
source 1
0 1
source 2
0 1
coupling
0 0

E33098

Version represented:
c 2 sources + 1 coupling;
c 2 circuit breakers closed;
c electrical interlocking without lockout after
a fault.

"SOURCE 1" BREAKER AUXILIARIES

S1

1
0
1

0
1
1

1
0
0

0
1
0

0
0
1

"SOURCE 2" BREAKER AUXILIARIES

"COUPLING" BREAKER AUXILIARIES

S2

CN1
CN2

D
to A

t1

COUPLING
t2

t3

B4

262

254

252

A4

C2

34

32

24

22

14

322

CE

XF

12

312
324

314

B4

262

254

252

A4

C2

34

32

24

22

14

322

12

CE

312
324

314

B4

262

254

252

A4

C2

34

32

24

22

14

322

12

312
324

314

t4

M
MX
Q1

OF

OF

CE

XF

OF

M
XF

MX
QC

OF

OF

OF
MX

CH
PF

Q2

OF

OF

OF

CH
PF
CH

Q1:
QC:
Q2:
D:
t1:
t2:
t3:

t4:

Masterpact on source 1
Masterpact used for coupling
Masterpact on source 2
P25M circuit breaker (2 x 10 A)
coupling signal: source 1 failure
(minimum time delay 250 ms)
coupling signal: source 2 failure
(minimum time delay 250 ms)
uncoupling signal: source 1
restored (minimum time delay 250
ms)
uncoupling signal: source 2
restored (minimum time delay 250
ms)

M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:

motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

251

A1

C1

31

21

11

B1
A

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
Note: All indicating signals by O, F, OF,
SDE, PF and CH auxiliary switches should
be protected by fuses that discriminate with
respect to the protection devices on the
automatic control circuits to avoid disturbing
the operation of the source-changeover
system.

Merlin Gerin

BTP207E-3.430-raccord

321

311

B1

251

A1

C1

31

21

11

321

311

B1

251

A1

C1

31

21

11

321

311

PF

89
89

21/12/01, 10:27

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)


electrical interlocking - 3 sources / 1 circuit breaker closed and
lockout after fault (688188)

E33095

Version represented:
c 3 sources, 1 circuit breaker closed;
c electrical interlocking with lockout after a
fault (SDE wiring).

possible states
source 1
0
source 2
0
source 3
0

"SOURCE 2" BREAKER AUXILIARIES

"SOURCE 1" BREAKER AUXILIARIES

S1

S2

1
0
0

0
1
0

0
0
1

"SOURCE 3" BREAKER AUXILIARIES

S3

CN1
CN2

D
to A

t1

t2

t3

R1

B4

262

254

252

A4

C2

34

32

84

82

22
24

14

322

12

CE

312
324

B4

262

254

252

A4

C2

34

32

24

84

82

22

322

14

314

CE

XF

12

CE

312
324

B4

262

254

252

A4

C2

34

32

24

84

82

22

322

14

314

CE

R3
12

312
324

314

R2

M
MX
Q1

OF

OF

CE

XF

CE

OF
MX
SDE

Q2

OF

OF

XF

OF

CH

MX
SDE

PF

OF

Q3

OF

OF

CH

SDE

PF

B1

251

A1

C1

31

81

21

11

321

311

B1

251

A1

C1

31

81

21

11

321

311

B1

251

A1

C1

31

81

21

11

321

311

CH
PF

Q1:
Q2:
Q3:
D:
t1:

Masterpact on source 1
Masterpact on source 2
Masterpact on source 3
P25M circuit breaker (2 x 10 A)
signal for transfer to source 1
(minimum time delay 250 ms)
t2:
signal for transfer to source 2
(minimum time delay 250 ms)
t3:
signal for transfer to source 3
(minimum time delay 250 ms)
R1,R2,R3: external relays for interlocking of
SDE auxiliary switches.

M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:

motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication
switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
Note: All indicating signals by O, F, OF,
SDE, PF and CH auxiliary switches should
be protected by fuses that discriminate with
respect to the protection devices on the
automatic control circuits to avoid disturbing
the operation of the source-changeover
system.
The relays are not supplied with the circuit
breakers.

Merlin Gerin

86
BTP207E-3.420-raccord

86

21/12/01, 10:27

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)


electrical interlocking - 3 sources / 1 circuit breaker closed and
without lockout after fault (688187)

E33096

Version represented:
c 3 sources, 1 circuit breaker closed;
c electrical interlocking without lockout after
a fault.

possible states
source 1
0
source 2
0
source 3
0

"SOURCE 2" BREAKER AUXILIARIES

"SOURCE 1" BREAKER AUXILIARIES

S1

S2

1
0
0

0
1
0

0
0
1

"SOURCE 3" BREAKER AUXILIARIES

S3

CN1
CN2

to A

t1

t2

B4

262

254

252

A4

C2

34

24

32

22

14

322

12

CE

XF

312
324

314

B4

262

254

252

A4

C2

24

34

22

32

14

322

CE

12

312
324

314

B4

262

254

252

A4

C2

24

34

22

32

14

322

12

312
324

314

t3

M
Q1

OF

OF

CE

XF

MX

OF
MX
OF

Q2

OF

XF
M

OF
MX

CH
Q3

PF

OF

OF

OF

CH
PF

B1

251

A1

31

C1

21

11

321

311

B1

A1

251

C1

31

21

11

321

311

B1

A1

251

C1

31

21

11

321

311

CH
PF

Q1:
Q2:
Q3:
D:
t1:
t2:
t3:

Masterpact on source 1
Masterpact on source 2
Masterpact on source 3
P25M circuit breaker (2 x 10 A)
signal for transfer to source 1
(minimum time delay 250 ms)
signal for transfer to source 2
(minimum time delay 250 ms)
signal for transfer to source 3
(minimum time delay 250 ms)

M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:

motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
Note: All indicating signals by O, F, OF,
SDE, PF and CH auxiliary switches should
be protected by fuses that discriminate with
respect to the protection devices on the
automatic control circuits to avoid disturbing
the operation of the source-changeover
system.

Merlin Gerin

BTP207E-3.420-raccord

87
87

21/12/01, 10:27

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)


3 circuit breakers - automatic control with generator set and
lockout after fault (689642)

E33093

Version represented:
c 2 sources + generator set;
c electrical interlocking with lockout after
a fault: inoperative with automatic reset
option;
c with auxiliary source;
c with MN undervoltage release;
c with choice of sources.

possible states
"Normal 1"
0
"Normal 2"
0
"Replacement"
0

"NORMAL 1" BREAKER AUXILIARIES

1
1
0

0
0
1

1
0
0

0
1
0

"REPLACEMENT" BREAKER AUXILIARIES

"NORMAL 2" BREAKER AUXILIARIES

N1 N2 R

auxiliary
source

genset startup signal


G

undervoltage relay

to B

U=0

genset fault
contact

OFF
R

N
AUTO
CMa

Fu

Fu

N1
RTn2

N1-2

Fu
N2

RTn3
RX3

Fu

RTn1

RX2

RX1
R1

OF

OF

B4

262

254

252

A4

D4

24

22

14

12

312

314

CE

84

CE

82

CE

XF
QN1

322

324

B4

262

254

252

A4

D4

24

22

14

12

312

314

322

324

CE

84

CE

82

CE

332

334

B4

262

254

252

A4

D4

24

22

14

12

312

84

82

314

322

324

332

334

R2

MN

XF

SDE

CE

CE

MN
OF

QN2

XF

OF

MN

SDE

CH

OF

QR

PF

OF

SDE

CH
PF

CH

B1

251

A1

D1

21

11

81

311

321

B1

251

A1

D1

21

11

81

311

321

331

B1

251

A1

D1

21

11

81

311

321

331

PF

QN1: Masterpact on Normal1 source


QN2: Masterpact on Normal2 source
QR:
Masterpact on Replacement
source
D:
P25M circuit breaker (2 x 10 A)
C:
operation selection switch
Cma: source selection switch
FU:
fuses
Rtn1: voltage relay with 0.1 to 30 s time
delay
Rtn2: voltage relay with 10 to 180 s time
delay
Rtn3: voltage relay
RX1: relay with 0.25 s time delay
RX2: relay with 0.25 s time delay
RX3: relay
R1/R2: external relays for interlocking of
SDE auxiliary switches (equipped
with 2 contacts O).

M:
XF:
MN:
CE:
OF:
SDE:
CH:
PF:

motor mechanism
closing release
undervoltage release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication
switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
Note: All indicating signals by O, F, OF,
SDE, PF and CH auxiliary switches should
be protected by fuses that discriminate with
respect to the protection devices on the
automatic control circuits to avoid disturbing
the operation of the source-changeover
system.
The two relays and selection switches are
not supplied with the circuit breakers.

Merlin Gerin

84
BTP207E-3.410-raccord

84

21/12/01, 10:26

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)


3 circuit breakers - automatic control with generator set and
without lockout after fault (689644)

E33094

Version represented:
c 2 sources + generator set;
c electrical interlocking with lockout after a
fault: inoperative with automatic reset
option;
c with auxiliary source;
c with MN undervoltage release;
c with choice of sources.

possible states
"Normal 1"
0
"Normal 2"
0
"replacement"
0

"NORMAL 2" BREAKER AUXILIARIES

"NORMAL 1" BREAKER AUXILIARIES

1
1
0

0
0
1

1
0
0

0
1
0

"REPLACEMENT" BREAKER AUXILIARIES

N1 N2 R

auxiliary
source

genset startup signal


G

undervoltage relay

to B

U=0

genset fault
contact

OFF
R

N
AUTO
CMa

Fu

Fu

N1
RTn2

N1-2

Fu
N2

RTn3
RX3

Fu

RTn1

RX2

RX1
R1

OF

OF

B4

262

254

252

A4

D4

24

22

14

12

312

84

314

CE

82

CE

XF
QN1

322

324

B4

262

254

252

A4

D4

24

22

14

12

84

312

314

CE

82

CE

322

324

B4

262

254

252

A4

D4

24

22

14

12

84

312

314

82

322

324

R2

MN

XF

SDE

CE

CE

MN
QN2

OF

XF

OF

MN

SDE

CH

QR

PF

OF

OF

SDE

CH
PF

CH

B1

251

A1

D1

21

11

81

311

321

B1

251

A1

D1

21

11

81

311

321

B1

251

A1

D1

21

11

81

311

321

PF

QN1: Masterpact on Normal1 source


QN2: Masterpact on Normal2 source
QR:
Masterpact on Replacement
source
D:
P25M circuit breaker (2 x 10 A)
C:
operation selection switch
Cma: source selection switch
FU:
fuses
Rtn1: voltage relay with 0.1 to 30 s time
delay
Rtn2: voltage relay with 10 to 180 s time
delay
Rtn3: voltage relay
RX1: relay with 0.25 s time delay
RX2: relay with 0.25 s time delay
RX3: relay

M:
XF:
MN:
CE:
OF:
SDE:
CH:
PF:

motor mechanism
closing release
undervoltage release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication
switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
Note: All indicating signals by O, F, OF,
SDE, PF and CH auxiliary switches should
be protected by fuses that discriminate with
respect to the protection devices on the
automatic control circuits to avoid disturbing
the operation of the source-changeover
system.
The relays and selection switches are not
supplied with the circuit breakers.

Merlin Gerin

BTP207E-3.410-raccord

85
85

21/12/01, 10:26

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)


3 circuit breakers - automatic control with permanent "Replacement"
source and lockout after fault (685366)

E33091

Version represented:
c 2 Normal sources + 1 Replacement
source;
c electrical interlocking with lockout after a
fault (SDE wiring): inoperative with
automatic reset option.

possible states
"Normal 1"
0
"Normal 2"
0
"Replacement"
0

N1

N2

0
0
1

1
0
0

0
1
0

"REPLACEMENT" BREAKER AUXILIARIES

"NORMAL 2" BREAKER AUXILIARIES

"NORMAL 1" BREAKER AUXILIARIES

1
1
0

R
CN1
CN2

D
to A

t1
t2

R1 (1)

QN1

OF

M
OF

B4

262

254

XF

MX
QN2

252

CE

XF

OF
SDE

A4

C2

24

22

84

82

312

CE
M

14

XF

MX

12

314

B4

262

254

252

A4

C2

24

22

84

82

312

14

CE

12

314

B4

262

254

252

A4

C2

24

22

84

82

312

14

12

314

R2 (1)

OF
MX

CH
SDE

PF

QR

OF

CH

OF
SDE

PF
CH

B1

251

A1

C1

21

81

11

311

B1

251

A1

C1

21

81

11

311

B1

251

A1

C1

21

81

11

311

PF

QN1: Masterpact on Normal1 source


QN2: Masterpact on Normal2 source
QR: Masterpact on Replacement
source
D:
P25M circuit breaker (2 x 10 A)
t1:
signal for transfer to Normal1 and
Normal2 sources (minimum time
delay 250 ms)
t1:
signal for transfer to Replacement
source (minimum time delay 250 ms)
R1/R2:external relays for interlocking of
SDE auxiliary switches (equipped
with 2 contacts O).

M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:

motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
Note: All indicating signals by O, F, OF,
SDE, PF and CH auxiliary switches should
be protected by fuses that discriminate with
respect to the protection devices on the
automatic control circuits to avoid disturbing
the operation of the source-changeover
system.
(1) The two relays are not supplied with the
circuit breakers.

Merlin Gerin

82
BTP207E-3.400-raccord

82

21/12/01, 10:26

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)


3 circuit breakers - automatic control with permanent
"Replacement" source and without lockout after fault (688183)

E33092

Version represented:
c 2 Normal sources + 1 Replacement
source;
c electrical interlocking without lockout after
a fault.

possible states
"Normal 1"
0
"Normal 2"
0
"Replacement"
0

"NORMAL 2" BREAKER AUXILIARIES

"NORMAL 1" BREAKER AUXILIARIES

N1

N2

1
1
0

0
0
1

1
0
0

0
1
0

"REPLACEMENT" BREAKER AUXILIARIES

CN1
CN2

D
to A

t1

B4

262

254

252

A4

C2

24

22

14

312

CE

XF

12

314

B4

262

254

252

A4

C2

24

22

14

312

CE

12

314

B4

262

254

252

A4

C2

24

22

14

312

12

314

t2

M
QN1

OF

CE

XF

MX
OF

M
XF

MX
QN2

OF

OF

M
MX

CH

QR

PF

OF

OF

CH
PF
CH

B1

251

A1

C1

21

11

311

B1

251

A1

C1

21

11

311

B1

251

A1

C1

21

11

311

PF

QN1: Masterpact on Normal1 source


QN2: Masterpact on Normal2 source
QR: Masterpact on Replacement source
D:
P25M circuit breaker (2 x 10 A)
t1: signal for transfer to Normal1 and
Normal2 sources (minimum time
delay 250 ms)
t2: signal for transfer to Replacement
source (minimum time delay 250 ms)

M: motor mechanism
XF: closing release
MX: shunt release
CE: connected position switch
OF: auxiliary changeover switch
SDE: overcurrent fault-trip indication switch
CH: springs charged switch
PF: ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
Note: All indicating signals by O, F, OF,
SDE, PF and CH auxiliary switches should
be protected by fuses that discriminate with
respect to the protection devices on the
automatic control circuits to avoid disturbing
the operation of the source-changeover
system.

Merlin Gerin

BTP207E-3.400-raccord

83
83

21/12/01, 10:26

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)


2 circuit breakers - automatic control with generator set (688784)
c with auxiliary source;
c with MN undervoltage release.

Version represented:
c with generator set;
c with lockout after a fault (SDE wiring):
v inoperative with automatic reset option,
v if lockout after a fault is not required, the
SDE must be shorted on both breakers;

possible states
"Normal"
0
"Replacement"
0

E33089

"NORMAL" BREAKER AUXILIARIES

1
0

0
1

"REPLACEMENT" BREAKER AUXILIARIES

R
genset startup signal
auxiliary
source

unvoltage relay
U=0

to B
genset fault
contact

C
OFF
STANDBY

N
AUTO

Fu
RTn2

RX3
RTn1

Fu

RX1

CE

XF

B4

262

254

252

A4

D1

24

22

14

12

84

312

82

CE

322
314

B4

262

254

252

A4

D1

24

22

14

12

312

84

324

CE

82

322
314

324

RX2

CE

M
XF

MN
QN

OF

OF

M
MN

SDE

QR

OF

CH

OF

SDE

PF
CH

B1

251

A1

D4

21

11

81

311

321

B1

251

A1

D4

21

11

81

311

321

PF

QN:
QR:
D:
C:
FU:
Rtn1:
Rtn2:
RX1:
RX2:
RX3:

Masterpact on Normal source


Masterpact on Replacement
source
P25M circuit breaker (2 x 10 A)
4-position switch
fuses
voltage relay with 0.1 to 30 s time
delay
voltage relay with 10 to 180 s time
delay
relay with 0.25 s time delay
relay with 0.25 s time delay
relay

M:
XF:
MN:
CE:
OF:
SDE:
CH:
PF:

motor mechanism
closing release
undervoltage release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
Note: All indicating signals by O, F and OF
auxiliary switches should be protected by
fuses that discriminate with respect to the
protection devices on the automatic control
circuits to avoid disturbing the operation of
the source-changeover system.

Merlin Gerin

80
BTP207E-3.390-raccord

80

21/12/01, 10:26

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)

2 circuit breakers - automatic control with permanent


"Replacement" source (688942)

E33090

Version represented:
c with permanent Replacement source;
c with lockout after a fault (SDE wiring):
v inoperative with automatic reset option,
v if lockout after a fault is not required, the
SDE must be shorted;

c with auxiliary source;


c with MN undervoltage release.

"NORMAL" BREAKER AUXILIARIES

possible states
"Normal"
0
"Replacement"
0

1
0

0
1

"REPLACEMENT" BREAKER AUXILIARIES

R
auxiliary
source
D

to B

C
N
STANDBY AUTO

OFF

Fu
RTn2
RTn1

Fu
Fu

RTn3
RX1

Fu

CE

XF

B4

262

254

252

A4

D1

24

22

14

12

84

312

82

CE

322
314

B4

262

254

252

A4

24

D1

22

14

12

312

84

324

CE

82

322
314

324

RX2

CE

M
XF

MN
QN

OF

OF

M
MN

SDE

OF

QR
CH

OF

SDE

PF
CH

B1

251

A1

D4

21

11

81

311

321

B1

251

A1

D4

21

11

81

311

321

PF

QN:
QR:

Masterpact on Normal source


Masterpact on Replacement
source
D:
P25M circuit breaker (2 x 10 A)
C:
4-position switch
FU: fuses
Rtn1: voltage relay with 0.1 to 30 s time delay
Rtn2: voltage relay with 10 to 180 s time
delay
Rtn3: voltage relay
RX1: relay with 0.25 s time delay
RX2: relay with 0.25 s time delay

CE:
M:
XF:
MN:
OF:
SDE:
CH:
PF:

connected position switch


motor mechanism
closing release
undervoltage release
auxiliary changeover switch
overcurrent fault-trip indication switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

c diagram shown with circuits deenergised, breakers open and in


connected position, springs charged and
relays in released position.
Note: All indicating signals by O, F and OF
auxiliary switches should be protected by
fuses that discriminate with respect to the
protection devices on the automatic control
circuits to avoid disturbing the operation of
the source-changeover system.

Merlin Gerin

BTP207E-3.390-raccord

81
81

21/12/01, 10:26

Masterpact: connection

automatic source-changeover systems


controller option (cont.)

E27121

BA operation

I
O
I
UR
O
I
KR
O

UN or KT

I
O
I
QR
O

QN

T1
0,130 s

500 ms

250 ms

T2
0,1240 s

500 ms

250 ms

UA operation

E30189

UN or KT

I
O

UR
KR

I
O
I
O

KG

I
O

SH I
O
QN I
O
QR I
O
T1
0,1...30s

120-180s

Inputs
UN : normal-source voltage
UR : replacement-source voltage
KT : forced operation on replacementsource control signal
KR : additional check before transfer.

T3
0,5...30s

If UR is not in I state when the transfer order


(KT or UN) is given, transfer is not carried
out.
If KR is not in I state when the transfer order
(KT or UN) is given, transfer takes place
only once KR has changed to I state.

T2
10...240s

T4
0,5...30s

T5
60...600s

Legend
c O position: circuit open
c I position: circuit closed
: no effect O or I.
c

Outputs
KG : engine-generator set control signal
SH : load-shedding control signal
QN : normal-source Masterpact
QR : replacement-source Masterpact.

Merlin Gerin

78
BTP207E-3.380-raccord

78

21/12/01, 10:25

Masterpact: connection

wiring diagrams for automatic source-changeover systems


2 circuit breakers - electrical interlocking (685363)

E33088

Version represented: With lockout after a


fault.
If lockout after a fault is not required, contact
PF of the Normal breaker must be
connected directly in series with auxiliary
switch OF of the Replacement breaker
and vice versa, without passing through the
switch SDE.

The indication circuits, represented on the


diagram by broken lines, are optional.
Accessories such as voltage relays,
indicating lights and fuses are not supplied
with the circuit breaker.

"NORMAL" BREAKER AUXILIARIES

possible states
"Normal"
0
"Replacement"
0

CONTROL PRINCIPLE

1
0

"REPLACEMENT" BREAKER AUXILIARIES

CN1

control
voltage

CN2

F1 (1)

0
1

F2 (1)
D
to B
to A

to C

fault

RTs

closed

fault

closed

RTn
open

open

B4

262

254

252

A4

C2

24

22

14

(2)

12

84

82

314
CE

312

B4

262

254

252

A4

C2

24

22

14

(2)

F4 (1)

12

84

82

314

312

F3 (1)

CE

XF
M

XF

MX
QN

OF

OF

M
MX

SDE

QR

OF

CH

OF

SDE

PF
CH

B1

251

A1

C1

21

11

81

311

B1

251

A1

C1

21

11

81

311

PF

B
A

QN: Masterpact on Normal source


QR: Masterpact on Replacement source
D: P25M circuit breaker (2 x 10 A)
F1, F2, F3, F4: protective fuses 2 A
Rts: Replacement source voltage relay
(minimum time delay 250 ms)
Rtn: Normal source voltage relay
(minimum time delay 250 ms)

M: motor mechanism
XF: closing release
MX: shunt release
CE: connected position switch
OF: auxiliary changeover switch
SDE:overcurrent fault-trip indication switch
CH: springs charged switch
PF: ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
(1) The fuses clear faults occurring on the
indication circuits without disturbing the
operation of the source-changeover system.
(2) Terminal 84 does not exist on control
units STR58 with options Z and/or C or
STR68UM/UTM; in this case there is
discrimination between the indications.

Merlin Gerin

BTP207E-3.380-raccord

79
79

21/12/01, 10:25

Masterpact: connection

automatic source-changeover systems


controller option
source-changeover system with 2 circuit breakers
E33081

"NORMAL" BREAKER AUXILIARIES

1
0

0
1

"REPLACEMENT" BREAKER AUXILIARIES

(1)

(1)

WH

VT

BK

RD

GN

possible states
"Normal"
0
"Replacement"
0

IVE

XF

WH
B4

262

254

252

A4

C2

VT

BK
84

82

GN

RD
14

CE

312

314

(3)

12

B4

262

254

252

A4

C2

84

82

312

14

12

314

(3)

CE

MX
OF

XF
SDE
OF
SDE

CH

251

A1

C1

81

11

311
GY

YE

(2)
BN

BN

(3)

QN: Masterpact on Normal source


QR: Masterpact on Replacement source
IVE: electrical interlocking and terminal
block unit
M: motor mechanism
XF: closing release
MX: shunt release
CE: connected position switch

CH

B1

A1

251

C1

(2)
YE

(3)

81

311

11

PF

B1

PF

MX

QR

GY

QN

OF: auxiliary changeover switch


SDE: overcurrent fault-trip indication switch
CH: springs charged switch
PF: ready to close contact (closing
possible if device is open, unlocked and
operating mechanism charged).

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
This diagram doesn't operate with
"automatic reset" option.
(1) provided ready to connect wiring.
(2) Don't wire for option "without lockout after fault".
(3) Don't wire in fixed position.

Merlin Gerin

72
BTP207E-3.350-raccord

72

21/12/01, 10:25

E33075

controller UA

Q1

E33076

load shedding and genset


management
5

UA

genset
startup

Q2

23 22 27 26 28 30 29 31

ACP

24

load
shedding

10

load
shedding

25

load reconnection

genset
startup
genset shutdown

24

E33077

BatiBUS option
25

23 22

controller status
indication

BatiBUS
loop

BatiBUS
loop

0V

24V

17 18 20

BA/UA

24V 0V

21

supplementary
control contact
NR

voluntary transfer
command (e.j. for
energy management)

11 12

13 14 15 16 10

UA

11 12 13 14 15 16

IVE
R
1

Q1 : circuit breaker supplying and protecting


the automatic control circuits for the
"Normal" source
Q2 : circuit breaker supplying and protecting
the automatic control circuits for the
"Replacement" source
IVE : electrical interlocking and terminal
block unit
ACP : auxiliaries control plate
BA/UA : controller

10

c diagram shown with circuits de-energised,


all devices open and relays in the released
position.

Tests on "Normal" and "Replacement"


voltages
BA:
c single-phase check for UN and UR:
v tested across terminals 1 and 5 of circuit
breakers Q1 and Q2.
UA:
c three-phase check for UN:
v tested across terminals 1, 3 and 5 of
circuit breaker Q1,
v selection switch A of controller set to 1;
c single-phase check for UN :
v tested across terminals 1 and 5 of circuit
breaker Q1,
v selection switch A of controller set to 0.

Merlin Gerin

BTP207E-3.350-raccord

73
73

21/12/01, 10:25

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)


automatic control - 2 sources + 1 coupling
and lockout after fault (689651)
possible states
source 1
0 1
source 2
0 0
coupling
0 0

E33099

Version represented:
c 2 sources + 1 coupling;
c 2 circuit breakers closed;
c electrical interlocking with lockout after a
fault: inoperative with automatic reset
option.

"SOURCE 1" BREAKER AUXILIARIES

S1

0
1
0

0
0
1

1
1
0

0
1
1

1
0
1

"SOURCE 2" BREAKER AUXILIARIES

"COUPLING" BREAKER AUXILIARIES

S2

CMa
permanent
OFF
auto

Fu
RTn1
RTn2

Fu
Fu

CMb
RTn3

COUPLER

N1+C
N1+N2
N2+C

RTn4

Fu

RX1
Fu
RX2
Fu

B4

262

254

252

A4

C2

24

22

14

12

84

312

82

CE

322
314

B4

262

254

252

A4

C2

24

22

14

12

312

84

324

CE

XF

82

CE

322
314

324

B4

262

254

252

A4

C2

24

22

14

12

84

82

322
314
CE

312

324

RX3

M
OF

CE

XF

MX
OF

CE

M
XF

MX
SDE

OF

OF

M
MX

CH

SDE

PF

OF
CH

OF

SDE

PF
CH

Q1:
QC:
Q2:
Cma:
FU:
Rtn1:
Rtn2:
Rtn3:
Rtn4:
Cmb:
RX1:
RX2:
RX3:

Masterpact on source 1
Masterpact used for coupling
Masterpact on source 2
3-position switch
fuses
voltage relay with 10 to 180 s time
delay
voltage relay with 0.1 to 30 s time
delay
voltage relay with 10 to 180 s time
delay
voltage relay with 0.1 to 30 s time
delay
coupling selection switch
relay with 0.25 s time delay
relay with 0.25 s time delay
relay with 0.25 s time delay

M:
XF:
MX:
CE:
OF:
SDE:
CH:
PF:

motor mechanism
closing release
shunt release
connected position switch
auxiliary changeover switch
overcurrent fault-trip indication
switch
springs charged switch
ready to close contact (closing
possible if device is open, unlocked
and operating mechanism charged).

B1

251

A1

C1

21

11

c diagram shown with circuits de-energised,


breakers open and in connected position,
springs charged and relays in released
position.
Note: All indicating signals by O, F, OF,
SDE, PF and CH auxiliary switches should
be protected by fuses that discriminate with
respect to the protection devices on the
automatic control circuits to avoid disturbing
the operation of the source-changeover
system.
The relays are not supplied with the circuit
breakers.

Merlin Gerin

90
BTP207E-3.440-raccord

81

311

321

B1

251

A1

C1

21

11

81

311

321

B1

251

A1

C1

21

11

81

311

321

PF

90

21/12/01, 10:28

LV power air
circuit breakers
and switch-disconnectors

Masterpact
4/ complementary technical
information
page
tripping curves
effect of ambient temperature

0
0

77
BTP207E-4.001-sommaire

77

21/12/01, 10:29

Masterpact: complementary technical information

tripping curves (cont.)

E30715

STR 68 U: load monitoring with 2 load limits


10000
5000

Ir = 0,41 x In

2000

Ic1 = 0,21 x In
1000

Ic2 = 0,21 x In
500

tr = 15480s
200

tr1 = tr / 2
100

tr2 = tr / 4
50

20
10
5

t(s)

2
1
.5

.2
.1
.05

.02
.01
.005

.002
.001
.05 .06

.08

.1

.2

.3

.4

.5 .6

.8

8 10

20

30

x In
In: CT rating
Ir: LT protection current setting (delay: tr)

Ic1: one load-shedding pick-up (delay: tr1)


Ic2: another load-shedding pick-up (delay: tr2)

Merlin Gerin

86
BTP207E-4.100-courbe dcl

86

21/12/01, 10:32

E30717

STR 68: load monitoring with 1 load-shedding and 1 load-reconnection pick-up


10000
5000

Ir = 0,41 x In

2000

Ic1 = 0,21 x In

1000

Ic2 = 0,21 x In

500

tr = 15480s
200

tr1 = tr / 2
100
50

20

tr2 = 60s
10
5

t(s)

2
1
.5

.2
.1
.05

.02
.01
.005

.002
.001
.05.06

.08 .1

.2

.3

.4

.5 .6

.8

5 6

10

20

30

x In
Ic1: load-shedding pick-up (delay: tr1)
Ic2: load-reconnection pick-up 2 (delay: tr2)

Merlin Gerin

BTP207E-4.100-courbe dcl

87
87

21/12/01, 10:32

Masterpact: complementary technical information

tripping curves (cont.)

E30714

STR 68 U
10000
5000

Ir = 0,4 1 x In

2000

tr = 15480s
1000
500

200
100
50

20
10
5

t(s)

I2t ON

Im = 0,4 15 x In

1
.5

.2
.1

I2t OFF

0,4

0,4

0,3

0,3

0,2

0,2

0,1

0,1

.05

I (*)

.02
.01
.005

.002
.001
.5 .6

.8 1

10

30

20

40 50 60

80 100

x In

200

300

kA

(*)I
In (A)

800

1000

type H2 : I =
type H1 : I =
type L1 : I =

1,6 kA ... 65 kA
In ou 1,6 kA ... 50 kA
1,6 kA ... 11 kA

1250

1600

2000

2500

3200

5000

6000

In ... 75 kA
In ... 15 kA
Merlin Gerin

84
BTP207E-4.090-courbe dcl

4000

84

21/12/01, 10:31

STR 68 U: earth fault protection


E30716

10000
5000

2000

Ih = 0,21 x In
Max. 1200A

1000
500

200
100
50

20
10
5

t(s)

2
1
.5

0,4
0,3

.2

0,2

.1

0,1

.05

.02
.01
.005

.002
.001
.05 .06

.08 .1

.2

.3

.4

.5 .6

.8

5 6

10

20

30

x In
In: CT rating
Ir: LT protection current setting (delay: tr)
Im: ST protection pick-up (delay: tm)
INST: instantaneous protection pick-up

Ih: earth fault protection pick-up (delay: th)


(0, 0.1, : time delay settings)

Merlin Gerin

BTP207E-4.090-courbe dcl

85
85

21/12/01, 10:31

Masterpact: complementary technical information

tripping curves (cont.)

STR 38 S/STR 58 U: earth fault protection


E30713

10000
5000

2000

Ih = 0,11 x In
Max 1200A

1000
500

200
100
50

20
10
5

t(s)

I2t ON

2
1
.5

0,4
0,3

.2

0,2
I2t OFF

.1

0,1

.05

.02
.01
.005

.002
.001
.05 .06

.08 .1

.2

.3

.4

.5 .6

.8

10

20

30

x In
In: CT rating
Ih: earth fault protection pick-up (delay: th)

Merlin Gerin

82
BTP207E-4.080-courbe dcl

82

21/12/01, 10:31

E30710

STR 38 S/STR 58 U: load monitoring


10000
5000

Ir = 0,41 x In

2000

Ic1 = 0,81 x Ir

1000

Ic2 = 0,51 x Ir

500

tr1 = tr / 2
200

tr2 = tr / 4
100
50

20
10
5

t(s)

2
1
.5

.2
.1
.05

.02
.01
.005

.002
.001
.05 .06

.08 .1

.2

.3

.4

.5 .6

.8

5 6

10

20

30

x In
Ir: LT protection current setting (delay: tr)
Ic1: load-shedding pick-up 1 (delay: tr1)
Ic2: load-shedding pick-up 2 (delay: tr2)

Merlin Gerin

BTP207E-4.080-courbe dcl

83
83

21/12/01, 10:31

Masterpact: complementary technical information

tripping curves (cont.)

E30711

STR 38 S
10000
5000

Ir = 0,4 1 x In

2000
1000
500

200
100
50

20
10
5

t(s)

Inst (*)

I2t ON

Im = 1,5 10 x Ir
1
.5

0,4

.2

I2t OFF

.1

0,3

0,3

0,2

0,2

0,1

0,1

.05

.02

0
.01
.005

.002
.001

.5 .6

.8

5 6

10

20

5 6

8 10

20

30

x In

x Ir
(*)Inst
In (A)

630

800/1000

1200/1600

2000

2500

3000/3200

4000/5000/6300

I = In x ... (N-H)

28

28

24

20

14

12

10

I = In x ... (L)

14

10

Merlin Gerin

80
BTP207E-4.070-courbe dcl

80

21/12/01, 10:30

E30712

STR 58 U
10000
5000

Ir = 0,4 1 x In

2000

tr = 15480s
1000
500

200
100
50

20
10
5

t(s)

Im = 1,5 10 x Ir
I2t ON

2
1
.5

0,4
0,3

.2
2

I t OFF

.1

0,3

0,2

0,2

0,1

0,1

.05

0
I = 2 x InMax (*)

.02
.01
.005

.002
.001
.5 .6

.8

5 6

10

20

5 6

10

20

30

x In

x Ir
(*)Max
In (A)

630

800/1000

1200/1600

2000

2500

3000/3200

4000/5000/6300

Max = In x ... (N-H)

28

28

24

20

14

12

10

Max = In x ... (L)

14

10

Merlin Gerin

BTP207E-4.070-courbe dcl

81
81

21/12/01, 10:30

Masterpact: complementary technical information

tripping curves

E30708

STR 18 M
10000
5000

2000
1000
500

200
100
50

20

I = 2 x In Max (*)
10
5

t(s)

2
1
.5

.2
.1
.05

.02
.01
.005

.002
.001
.5 .6

.8

8 10

20

30

40 50 60

80 100

200

300

x In
(*)Max
In (A)

630

800/1000

1200/1600

2000

2500

3000/3200

4000/5000/6300

Max = In x ...

28

28

24

20

14

12

10

Merlin Gerin

78
BTP207E-4.060-courbe dcl

78

21/12/01, 10:30

E30709

STR 28 D
10000
5000

Ir = 0,4 1 x In

2000
1000
500

200
100
50

20
10
5

t(s)

Im = 1,5 10 x Ir

Inst (*)

1
.5

.2
.1
.05

.02
.01
.005

.002
.001

.5 .6

.8

5 6

10

20

x Ir

5 6

10

20

30

x In

Inst (*): fixed pick-up at 10 In


Merlin Gerin

BTP207E-4.060-courbe dcl

79
79

21/12/01, 10:30

Masterpact: complementary technical information

effect of ambient temperature

ambient temperature

The electrical and mechanical


characteristics are specified for an ambient
temperature between 5 and +60 C.
Masterpact circuit breakers operate from
10 and +70 C.
First closing minimum temperature: 30 C.
In addition, Masterpact circuit breakers
comply with IEC standards 68.2.1 and
68.2.2: exceptional storage temperature
from: 50 to +100 C.
The table below indicates the maximum
current rating, for each connection type, as a
function of the ambient temperature around
the circuit breaker and the busbars.

Current rating (A) as a function ambient temperature (C)


Masterpact
version
drawout

M08N/H/L M10N/H/L M12N


connection T C
front or rear 40
800
1 000
1 250
horizontal 45
800
1 000
1 250
50
800
1 000
1 250
55
800
1 000
1 250
60
800
1 000
1 200
rear vertical 40
800
1 000
1 250
45
800
1 000
1 250
50
800
1 000
1 250
55
800
1 000
1 250
60
800
1 000
1 250
fixed
front or rear 40
800
1 000
1 250
horizontal 45
800
1 000
1 250
50
800
1 000
1 250
55
800
1 000
1 250
60
800
1 000
1 250
rear vertical 40
800
1 000
1 250
45
800
1 000
1 250
50
800
1 000
1 250
55
800
1 000
1 250
60
800
1 000
1 250
Power dissipation and resistance between inputs/outputs
power(1)
drawout
160
250
360
dissipated (W) fixed
66
103
150
input/output(2) drawout
53
53
53
resistance () fixed
33
33
33

M12H

M12L

M16N/H M16L

M20N/H M20L

M25N/H M25L

M32H

M40H

M50H

M63H

1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250

1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250
1 250

1 600
1 600
1 600
1 600
1 550
1 600
1 600
1 600
1 600
1 550
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600

1 600
1 600
1 600
1 600
1 500
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600
1 600

2 000
2 000
2 000
2 000
1 900
2 000
2 000
2 000
2 000
1 900
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000

2 000
2 000
2 000
2 000
1 900
2 000
2 000
2 000
2 000
1 900
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000
2 000

2 500
2 500
2 430
2 350
2 250
2 500
2 500
2 500
2 500
2 400
2 500
2 500
2 500
2 500
2 500
2 500
2 500
2 500
2 500
2 500

2 500
2 350
2 250
2 150
2 000
2 500
2 500
2 500
2 350
2 200
2 500
2 500
2 500
2 500
2 300
2 500
2 500
2 500
2 500
2 500

3 150
3 080
3 000
2 900
2 800
3 200
3 200
3 100
3 000
2 900
3 200
3 200
3 200
3 200
3 100
3 200
3 200
3 200
3 200
3 100

3 800
3 650
3 500
3 300
3 100
4 000
3 800
3 600
3 400
3 200
4 000
4 000
4 000
3 900
3 800
4 000
4 000
4 000
4 000
3 900

5 000
4 750
4 500
4 250
4 000
5 000
5 000
5 000
5 000
4 700
5 000
5 000
5 000
5 000
5 000
5 000
5 000
5 000
5 000
5 000

6 000
5 700
5 400
5 100
4 800
6 300
6 000
5 700
5 400
5 100

230
100
32
16

360
150
50
36

390
170
32
16

460
220
31
12

365
180
18
9

500
250
23
10

520
260
17
8

780
390
23
10

803
500
15
10

1 250
780
15
10

1 150
700
9
8

1 200

(1) Values measured at In, 50/60 Hz for a 3-pole or 4-pole breaker.


(2) Values measured per pole.

Merlin Gerin

88
BTP207E-4.110-dclassement

88

21/12/01, 10:32

Merlin Gerin

BTP207E-4.110-dclassement

89
89

21/12/01, 10:32