Jevgeni klovski, Kuno Janson, Helar Niilo Tallinn University of Technology jevgeni@staff.ttu.ee, kuno.janson@ttu.ee, helar.niilo@ttu.ee
Abstract- This paper presents a practical way to determine leakage inductances of the windings in inverter transformer of the HFPSA (High Frequency Parallel/Series Resonance Alternating) converter individually for each winding based on the results of specially developed test and tuning procedure. I. INTRODUCTION Growing number of resonant-type power sources for DC/DC applications has put some specific requirements on inverter transformers used to match the mains voltage to load level and provide galvanic isolation for safety reasons. Often these transformers are not only to provide needed voltage matching, but to build up a part of resonant circuit with their leakage inductances [8]. Thus, it is desirable to estimate transformer leakage inductance level yet on early design stages [2], and, if possible, to design a transformer having leakage inductances to replace completely or partially inductors of resonant circuits. This can decrease not only the number of elements in unit, but also could reduce its size and weight. There are two main methods to estimate leakage inductance of the transformer: the analytical calculations, that is relatively simple and approximate method, and computer simulation (usually by FEM software), that could be relatively accurate, but time consuming way. Missing the value of the leakage inductance could not only change the resonant tank behavior, but impose some stresses on power semiconductors. Generally, it will be a good practice to test new transformer for its parameters estimated before, while leakage inductance has to be defined for each winding separately. There are some practical approaches, based on measurement and calculation, to determine individual leakages for two-winding transformers [9] and some in case of multi-winding transformer [11]. This paper describes the method developed for testing inverter transformer used to supply PSA resonant circuit and tuning this circuit at the same time.
II. TRANSFORMER IN THE PSA CONVERTER The main property of PSA resonant converters the presence of one or more inductive and capacitive branches (Fig.1), which can form parallel or series resonant circuits depending on load condition and due to the natural commutation of diodes V1 V6 in the output rectifier. More information about given circuit specialties in case of mains power supply can be found in [12, 13] and for the inverter- type power supply in [14]. W1 W2 W3 m I C U d U v I L2 I L1 L1 L2 a b c C V1 V4 V6 V2 V3 V5 T
Fig. 1. A simple PSA resonant circuit with three-winding transformer. As it seen in Fig.1 the transformer of simple PSA converter is a three-winding one having two secondary windings connected in series. Depending on load, there are up to six different circuit topologies available in resonant tank with one or two secondary windings involved. So, it is highly desirable to know the value of individual leakage inductance for each winding. For relatively high-frequencies (40-100 kHz) and high- current (100-200 A) power conversions the PSA converter is to be equipped with resonant inductors (L1 L3) up to some H and consequently, leakage inductance of the transformer must be considered as exactly as possible. In general, the properly calculated resonant circuit in PSA converter prevents overload of inverter switches and transformer at any conditions from no-load to short-circuit.
Fig. 2. Power circuit of inverter-type PSA converter.
114
III. TESTING AND TUNING PROCEDURE A. Transformer Analysis Ways Multi-winding transformers are widely used in power electronics and the leakage inductance becomes more and more crucial issue in view of increasing operation frequencies. Mostly, there is a trend of decreasing leakage inductance to reduce stresses on switches. However, there is a class of so called load-resonant converters, which can utilize leakage for resonant mode operation. So, it is desirable to know these leakages, at least approximately, before prototype is built and develop corresponding model of transformer. There are different approaches for analytical study of the leakage inductances in transformer. The leakage depends mostly on geometry and placement of the windings. When the windings are distributed non- uniformly with large insulation spacing or with significantly different winding heights the conventional formulas for the leakage inductance do not provide accurate results because of the highly non-uniform flux distribution [5]. The analytical approach is based on study of field distribution near winding and equivalent circuit drawing representing the real transformers to more or less extent. As one method the ladder model with energy (axial and radial components) storage calculation method are suggested in [5]. Another method is a full-order model (extended cantilever form) that could provide even more accurate result [4, 6]. Additionally, in the case of changing circuit topology of transformer windings the mutual leakage inductances can vary that should be also considered [7]. Testing the transformer for its equivalent parameters identification is also a common practice, where along with well-known No-Load and Short-Circuit Tests [10] the Series- Coupling Tests have been adopted [1, 3]. However, these methods are mostly to define total leakages reflected in the primary winding, while in many designs the value of individual leakage inductance for each winding is necessary. So, modeling of transformer with FEM software could be a good alternative here. B. Transformer Test and Circuit Turning One of the goals during development of converter circuit was to achieve a minimal possible increase of load current in case of transition from rated load to short-circuit condition. It was found that willing to reduce short-circuit current it is necessary to have close to zero current in secondary winding W2. Such a condition is possible if voltage drop on inductor L2 is equal to voltage across winding W2 (Fig.2.). In this case voltage between terminals A and B is about zero and there is almost no current appear in winding W2. As the circuit contains real capacitor, inductors and transformer that are non-ideal so to achieve a zero current in W2 it is needed to correct parameters of the circuit or tune circuit. In the given case changing the inductance value of L2 is used. It was easily made by changing height of the winding, The circuit shown in Fig.3 describes the tuning setup. The primary winding of transformer has a 40 kHz power supply realized by sinusoidal voltage generator. Input terminals in rectifier bridge A, B, C are short-circuited and one of the switches (S1 or S2) is opened. First step is tuning, while S2 was closed and S1 opened the voltmeter V7 shows voltage between A and B. By changing the inductance of L2 the indication of V7 was observed to have it as small as possible. In that way the resonant circuit was tuned up to desirable condition.
Fig. 3. Test and tuning circuit of converter. Second test is to control circuit parameters for rated conditions when S2 was opened and S1 closed with keeping output short-circuited. The measurement of all voltages and currents was accomplished in this case to determine values of inductances and capacitance in circuit. C. Test Results The results of measurement are given in Table I. It also contains calculated values of inductance and capacitance for reactive elements. Table II shows the values of calculated leakage inductances. The phasor diagram below (Fig. 4.) shows voltages on elements and windings at first and second steps that gives a good overview of circuit properties. So, for the first step it is seen that difference between U 2 and U 4 must be as small as possible that yields in smaller U 7 , which in its turn hints to smaller short-circuit current.
(a) (b) Fig. 4. Phasors of resonant circuit at tuning and control, a) switch S1 is OFF and S2 is ON, b) switch S1 is ON and S2 is OFF. Measurements in both steps are to provide us with data needed for determination of elements values in resonant circuit. Knowing the voltage and current in element its impedance could be found easily with Ohms law. As the test was conducted with relatively low supply voltage and current and windings have relatively large effective cross-section area (11 mm2 for W1 and 48 mm2 for W2 and W3) the own resistance of windings and inductors was neglected in the calculations. U6 U 4 U7 U2 U3 U5 U6 U2 U3 U5 115
For a tuning test inductance value of inductor L2 was changed by stretching it to achieve minimal possible U 7
value. Calculation of leakage inductance is a bit different. Based on the transformer design symmetry, there is an assumption that leakage inductances of secondary windings are equal. In the first test with disconnected W2 we can see the voltage on this winding that is equal to induced EMF (E). Knowing the turns ratio 11:1:1 of transformer, the EMF of primary winding W1 and other secondary W3 can be also derived:
2 1 2 1 E E N N =
, (1) 2 2 2 1 1 11 E E N N E = = , (2)
2 3 E E = . (3) Having the E value for each winding one can compare it with value of measured voltage. The voltage difference indicated here in Table II as U XS in our suggestion is the voltage drop on leakage inductance of the corresponding winding:
E U U xs = . (4) This way the leakage inductances for each winding were determined in both tests and shown in Table below.
D. Test Setup Description The transformer has a shell-type core made of two 0P49928EC E100 ferrites. The windings are made two concentric layers placed on center leg. The first layer is a 11- turn primary winding and second layer is a two 1-turn windings connected in series. Windings are made of Litz- wire. W1 - primary 11 turns W2 - 1 turn W3 - 1 turn
Fig. 5. Tested transformer core and windings. The measurement devices were used: Digital Scope Tektronix DPS200 and AC/DC current clamps Tektronix i30s, Hameg HZ56-2. The PeakTech DDS Function Generator 4040 as a signal source with signal amplifier build on TDA7294V was adopted here as a high-frequency power source.
TABLE I MEASUREMENT RESULTS AND CALCULATED VALUES OF ELEMENTS Test U1,V I1,A U2,V U3,V U4,V (L2) U5,V (L3) U6,V (C) U7,V I2,A U8,V I n i t i a l Measured 4,94 0,48 0,4 0,91 0,97 0,48 2,56 0,69 5,57 1,47 Calculated, Ohm - - - - 0,17 0,086 0,46 - - - Calculated, H / F - - - - 0,69 0,34 8,70 - - - T u n e d
Measured 6,55 0,39 0,53 0,97 0,52 0,37 2,1 0,07 4,5 - Calculated, Ohm - - - - 0,12 0,082 0,47 - - Calculated, H / F - - - - 0,46 0,33 8,50 - - S e r i e s
c i r c u i t
( S 1 - o n ,
S 2 - o f f )
Measured 2,9 0,5 0,47 0,47 - 0,28 1,3 - 2,77 - Calculated, Ohm - - - - - 0,10 0,47 - - - Calculated, H / F - - - - - 0,40 8,50 - - - TABLE II DETERMINATION OF INDIVIDUAL LEAKAGE INDUCTANCES FROM TEST RESULTS Test w1 w2 w3 O n l y
W 3
U E UXS U E UXS U E UXS Voltage and EMF (V) 6,55 5.83 0.72 0,53 0,53 - 0,97 0,53 0,44 Current (A) 0,39 - 4,5 Lea- kage reactance () 1,85 - 0,097 inductance (H) 7,3 - 0,39 W 2
IV. ANALYSIS The currents and voltages measured during test on transformer windings and reactive elements make possible to calculate and verify values of corresponding elements. For example it could be seen that value of capacitance C lays in the range of specified parameters, as calculated capacitance yields in 8.5 8.7 F, while installed capacitors has 9 F 10%. In the case of tuned resonant circuit it was determined that L2=460 nH and L3=330 nH. The leakage inductance of secondary windings is determined by voltage measured on transformer terminals, defined EMF and current measured in windings. Based on this data, the calculated value of one-turn secondary winding yields to about 400 nH in both test
V. CONCLUSIONS In this paper, the simple method for tuning resonant circuit and determining individual leakage inductances is presented. Complicated calculations are avoided and only a simple measurement procedure is needed that has a twofold effect: firstly, the PSA resonant circuit could be tuned for optimal operation and, secondly, the individual leakage inductances can be defined for steady state operation. This could be helpful in further tests and analysis of resonant circuit.
ACKNOWLEDGMENTS This paper was supported by European Social Funds Doctoral Studies and Internationalisation Programme DoRa. Authors thank Estonian Archimedes Foundation (Inter- disciplinary project Optimal energy conversion and control in Smart and Microgrids within the framework of Doctoral School of Energy and Geotechnology-II) for support of this study.
REFERENCES [1] J. G. Hayes, D. Cashman, M. G. Egan, T. ODonnell, N. Wang, Comparison of Test Methods for Characterization of High-Leakage Two-Winding Transformers, IEEE Transactions on Industry Applications vol. 45, no.5, sept/oct 2009. [2] R. Doebbelin, M. Benecke and A. Lindemann, Calculation of leakage Inductance of Core-Type Transformers for Power Electronic Circuits, in Proceedings of 13th International Power Electronics and Motion Control Conference (EPE-PEMC 2008). [3] J. G. Hayes, N. ODonovan and M. G. Egan., The Extended T Model of the Multiwinding transformer, in Proceedings of 35th Annual IEEE Power Electronics Specialists Conference (2004). [4] R. W. Ericksom, D. Maksimovic, A Multiple-Winding Magnetics Model Having Directly Measurable Parameters IEEE 1998 . [5] J. Wang, A. F. Witulski, J. L. Vollin, T.K. Phelps and G.J. Cardwell, Derivation, Calculation and Measurement of Parameters for a Multi- Winding Transformer Electrical Model IEEE Xplore 1999 [Online]. Available: http://ieeexplore.ieee.org/xpl/freeabs_all.jsp?arnumber=749513. [6] K. Changtong. R. W. Erickson and D. Maksimovic A Comparison of the Ladder and Full-Order Magnetic Models IEEE [2] 2001 [Online]. Available: http://ieeexplore.ieee.org/xpl/freeabs_all.jsp?arnumber=954425. [7] W. Jia-ju, H. Sugimoto and W. Sheng-yu Determination and Relativity of the leakage Inductance of Push-pull Transformers, IEEE. [8] A. Jeyalakshmi, M. Prabhakar Effect of Leakage Inductance on the Performance of Parallel Resonant Converter SPEEDAM 2006 International Symposium on Power Electronics, Electrical Drives, Automation and Motion (doc 16). [9] K.I.Hwu and Y.H.Chen Estimation of Individual Leakage Inductances of a Transformer Based on Measurements 2008 IEEE. Available: http://ieeexplore.ieee.org/xpl/freeabs_all.jsp?arnumb er=4608452. [10] . , LCR- !. 8, 2003, pp.58-61. [11] F. de Leon, J. A. Martinez Dual Three-Winding Transformer Equivalent Circuit Matching Leakage Measurements 2008 IEEE Transactions on Power Delivery vol. 24 no 1, jan. 2009. [12] K. Janson, J. Jrvik, AC-DC converter with parametric reactive power compensation Industrial Electronics, IEEE Transactions, Jun 1999, Volume 46, Issue:3, pp: 554 - 562 . [13] K. Janson, and J. Jrvik, Load adapting mains frequency resonant converters for supplying electrical arc-a new way in power electronics Power Electronics Specialists Conference, 1998. PESC 98 Record. 29th Annual IEEE, pp. 2090 - 2096 vol.2. [14] K. Janson, J. Jrvik, J. Shklovski, T. Vinnal, Inverter Mode in Converter with Alternating Parallel and Series Resonance. In: Proc. of the 11th International Conference on Power Electronics and Motion Control (EPE-PEMC 2004): CD-ROM, A2216.