0 penilaian0% menganggap dokumen ini bermanfaat (0 suara)
32 tayangan4 halaman
The SEL-787 relay tripped due to incorrect CT compensation settings, causing a differential current above the 0.3 pu threshold. Specifically, W1CTC was set to 6 instead of the correct value of 7 for the wye-connected 4.16 kV winding. With the proper setting of W1CTC = 7, the calculated differential current would have been 0 pu, below the trip threshold. The document recommends updating W1CTC to the proper value of 7 to prevent future incorrect trips.
The SEL-787 relay tripped due to incorrect CT compensation settings, causing a differential current above the 0.3 pu threshold. Specifically, W1CTC was set to 6 instead of the correct value of 7 for the wye-connected 4.16 kV winding. With the proper setting of W1CTC = 7, the calculated differential current would have been 0 pu, below the trip threshold. The document recommends updating W1CTC to the proper value of 7 to prevent future incorrect trips.
The SEL-787 relay tripped due to incorrect CT compensation settings, causing a differential current above the 0.3 pu threshold. Specifically, W1CTC was set to 6 instead of the correct value of 7 for the wye-connected 4.16 kV winding. With the proper setting of W1CTC = 7, the calculated differential current would have been 0 pu, below the trip threshold. The document recommends updating W1CTC to the proper value of 7 to prevent future incorrect trips.
Petrochemical Transformer: SEL-787 Page 1 of 4 20120718
Event Analysis Introduction Session
Petrochemical Transformer: SEL-787 Transformer Differential Current Trip Introduction Basic transformer protection includes a transformer differential relay. Because power transformers have different voltage levels at the primary and secondary sides, the currents at each side are different for the same power level. This means that current transformer (CT) ratios must be different at the primary side and the secondary side of the transformer. This current difference must be accounted for in the settings of the current differential relay. The transformer may also have a delta-connected primary winding and a wye-connected secondary winding. This means that the CTs must be connected such that the phase shift of the delta-to-wye transformation is compensated for before the current differential relay can compare the difference between the primary- and secondary-side currents. In modern microprocessor-based current differential relays, this phase and magnitude compensation can be done internally in the relay through programmable settings. These settings must be correct for the current differential to operate correctly. These settings should be verified during commissioning of the transformer. Date and Time of Trip Event Date: May 24, 2012 (Thursday) Time: 12:32:18.163 Targets: 87 (differential current) Event: differential trip Currents at Time of Trip IAW1 = 942 A at 0 degrees (4.16 kV, A-phase current) IBW1 = 945 A at 240 degrees (4.16 kV, B-phase current) ICW1 = 947 A at 120 degrees (4.16 kV, C-phase current) IAW2 = 285 A at 30 degrees (13.8 kV, A-phase current) IBW2 = 284 A at 270 degrees (13.8 kV, B-phase current) ICW2 = 285 A at 150 degrees (13.8 kV, C-phase current) Settings That Caused Trip W1CT := WYE (4.16 kV CTs connected in wye) W2CT := WYE (13.8 kV CTs connected in wye) CTR1 := 400 (4.16 kV CT ratio is 2000/5 or 400/1) CTR2 := 120 (13.8 kV CT ratio is 600/5 or 120/1) MVA := 10.5 (transformer power rating is 10.5 MVA) ICOM := Y (internal CT compensation to be used)
Petrochemical Transformer: SEL-787 Page 2 of 4 20120718 W1CTC := 6 (180-degree compensation used on a 4.16 kV winding) W2CTC := 0 (no internal compensation used on a 13.8 kV winding) VWDG1 := 4.16 (Winding 1 is at 4.16 kV) VWDG2 := 13.80 (Winding 2 is at 13.8 kV) E87 := Y (enable transformer differential element) TAP1 := 3.64 (4.16 kV current tap = 10.5 MVA 1000/(4.16 kV 1.73 400) = 3.64) TAP2 := 3.67 (13.8 kV current tap = 10.5 MVA 1000/(13.8 kV 1.73 120) = 3.67) O87P := 0.30 (minimum differential trip is at 0.3 pu of tap) SLP1 := 25 (differential restraint Slope 1 is at 25 percent) TRXFMR := 87R OR (restrained differential set to trip the transformer) OUT103 := TRIPXFMR OR (output 103 set to trip the transformer breaker) Summary of Trip The SEL-787 tripped on the current differential element when the differential current went above the 0.3 pu of tap threshold and above the 25 percent restraint slope threshold. Cause of Trip The differential current can be calculated using the current values shown below: IAW1 pu = IAW1/(CTR1 TAP1) = 942/(400 3.64) = 0.65 pu at 0 degrees IBW1 pu = IBW1/(CTR1 TAP1) = 945/(400 3.64) = 0.65 pu at 240 degrees ICW1 pu = ICW1/(CTR1 TAP1) = 947/(400 3.64) = 0.65 pu at 120 degrees IAW2 pu = IAW2/(CTR2 TAP2) = 285/(120 3.67) = 0.65 pu at 30 degrees Using the Winding 1 CT compensation of 6: I1W1C1 = (2 (IAW1) + IBW1 + ICW1)/3 I1W1C1 = (2 (0.65 at 0) + 0.65 at 240 + 0.65 at 120)/3 = 0.65 pu at 180 degrees Using the Winding 2 CT compensation of 0: I1W2C1 = IAW2 = 0.65 pu at 30 degrees IOP1 = I1W1C1 + I1W2C1 = 0.65 at 180 + 0.65 at 30 = 0.34 pu differential current IRT1 = 0.65 + 0.65 = 1.3 pu SLOPE = IOP1 100/(IRT1) = 0.34 100/1.3 = 26 percent The differential current is above the minimum value of 0.3 pu and above the slope of 25 percent due to the incorrect CT compensation values being used.
Petrochemical Transformer: SEL-787 Page 3 of 4 20120718 Graphs and Pictures The graph below shows the currents recorded by the SEL-787.
The plot below shows the magnitudes and angles of the currents at the time of the trip.
Conclusions The relay tripped because of incorrect CT current connection compensation settings of W1CTC = 6 and W2CTC = 0. Recommendations Winding 2 is a delta-wound, 13.8 kV winding, so W2CTC = 0 is a correct setting. The delta winding actually removes the zero-sequence currents for a ground fault on the 4.16 kV side. Winding 1 is a wye- connected, 4.16 kV winding. Given the polarity that the CTs have, W1CTC should be set to 7, as shown in the following calculations.
Petrochemical Transformer: SEL-787 Page 4 of 4 20120718 Using the Winding 1 CT compensation of 7: I1W1C1 = (IAW1 + IBW1)/1.73 I1W1C1 = ((0.65 at 0) + 0.65 at 240)/1.73 = 0.65 pu at 150 degrees Using the Winding 2 CT compensation of 0: I1W2C1 = IAW2 = 0.65 pu at 30 degrees IOP1 = I1W1C1 + I1W2C1 = 0.65 at 150 + 0.65 at 30 = 0.0 pu differential current IRT1 = 0.65 + 0.65 = 1.3 pu SLOPE = IOP1 100/(IRT1) = 0 100/1.3 = 0 percent So W1CTC should equal 7.