PROTECTION AND CONTROL

PG-PC-E-0907

Underground Distribution Switchgear


Fault and Voltage Indicators
Underground Arresters

Product Selection Guide

PROTECTION AND CONTROL


Introduction

PROTECTION AND CONTROL


Introduction

Protection and Control Products


Electric underground distribution
systems demand high performance
in the form of improved reliability,
improved power quality, reduced
operational and maintenance costs
and flexibility of operation. These
can be accomplished by sectionalizing
feeders, installing equipment with
minimal maintenance/installation
costs, installing protection equipment,
installing automatic source transfer
equipment and/or providing ways
to monitor the system and quickly
locate a fault.
Thomas & Betts Protection and Control
products provide flexible solutions to
all of the above challenges. With a wide
array of products such as arresters, fault
indicators and switchgear, we are able
to provide the equipment that you need
to fulfill the needs of underground
distribution systems.

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PROTECTION AND CONTROL


Contents

Underground Distribution Switchgear


Product Application
Manual Sectionalizing
Automatic Sectionalizing
Underground Loop Systems
Automatic Source Transfer
Distribution Automation
Network Transformer Protection
Application Summary
Product Specifications
Ordering Information

Pg. 5-7
8
9
10-11
12
13
14-16
17
18-23
24-30

Fault and Voltage Indicators


FAULT INDICATORS
Product Application
Test Point Mounted
Underground Clamp Type
Overhead Line Mounted
Fault Indicator Accessories
VOLTAGE INDICATORS
V2
PD35 Voltage & Phasing Indicator
Ordering Information

Pg. 31-32
33-35
36-38
39-41
42
43
44
45

Underground Arresters
Product Application
Ratings
Ordering Information

Pg. 46-49
49
50-51

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Product Application

Underground Distribution Switchgear


Subsurface

riser pole

vault

Underground
Distribution Switchgear

Padmount

Elastimold Switchgear is the result of extensive field experience in underground distribution


systems combined with state-of-the-art know-how and top-notch customer support. The result?
Equipment that fits multiple application needs and contributes to improve the reliability
and operating performance of underground distribution systems up to 35kV. Elastimold
Switchgear is fully submersible and features deadfront construction for increased safety of
operation. Solid EPDM insulation and vacuum switching/interruption translate into small
footprint, no maintenance products. With a wide range of configurations suitable for feeder
sectionalizing/protection, loop sectionalizing/protection, riser pole installations and automatic
source transfer, Thomas & Betts is able to provide the right solutions to overcome your
underground distribution system performance challenges.

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PROTECTION AND CONTROL


Product Application

Underground
Distribution Switchgear

Switchgear Building Blocks


Whether it is a standard or a custom application, Thomas & Betts has the right combination
of components and expertise to fit your needs. The modularity and flexibility of Elastimold
Switchgear allows the user to combine the different individual components into products that
satisfactorily improve the reliability and performance of distribution systems. Three basic
components form the basis for Elastimold Switchgear:


Single-phase and three-phase Molded Vacuum Switches (MVS)


Single-phase and three-phase Molded Vacuum Interrupters (MVI)
Canister Fuses (MCAN)

These combined with electronic controls, motor operators and SCADA ready controls make
the building blocks of Elastimold Switchgear.

benefit/description

Feature
EPDM molded rubber construction with stainless
steel hardware and mechanism boxes

Fully sealed
Fully submersible

Vacuum switching and vacuum interruption

Maintenance-free
Small footprint
Lightweight
NO gas, NO oil, NO hassle

Deadfront construction

Insulates, shields and eliminates exposed live parts

Compact and lightweight

Fits in tight spaces


Suitable for padmount, subsurface, vault or riser pole
installations
Smaller footprint compared to other switchgear

Non-position sensitive

Can be installed almost anywhere and in any position (e.g.


hanging from ceilings, wall-mounted, mounted at an angle, riser
pole mounted)

Modular construction

Allows any combination of fused, switched and interrupter ways


on one piece of switchgear up to 35kV
The knowledge and training acquired can be applied to multiple
installations

Electronic controls for protection and automatic


source transfer applications

Flexibility of settings and operation in different locations


throughout the distribution system
Self-powered controls
Customized protection curves

Motor operators for remote/local open/close


operation of three-phase switched or
interrupter ways

Allow remote reconfiguration of loops and sectionalizing


of feeders
Allow automatic or manual source transfer
Can be used with a wide variety of RTUs and
communication devices

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Product Application
Elastimold Switchgear building blocks as described on the previous section can be combined

Underground
Distribution Switchgear

into a wide arrangement of configurations and applied to solve different system challenges in
the distribution system. Elastimold Switchgear products can be classified in three categories
according to the function they perform:
Switching and Sectionalizing Equipment
Overcurrent Protection Equipment
Automatic Source Transfer Equipment

These products can be applied in different types of installations:




Padmount
Subsurface / wet or dry vaults
Riser pole
UNDERGROUND DISTRIBUTION SWITCHGEAR APPLICATIONS
Substation 3

NC = normally closed
NO = normally opened
Automatic
Source
Transfer
Substation 1

Critical
Load

Switchgear 3

Switchgear 1

Overcurrent/
Sectionalizing
Substation 2

Sectionalizing Switchgear 2

The switching or manual sectionalizing of loads can be accomplished with the use of Molded
Vacuum Switch (MVS) modules. The simplest manual sectionalizer is a single MVS switch, which
can be installed in a vault, on a pole or inside a padmount enclosure. One of the most popular
applications of this sectionalizer is as a replacement for existing oil fuse cutouts. Two, three and
four-way units are also available in vault and padmount styles. Switches also aid in the manual
reconfiguration of distribution loops by installing them at the open point in the circuit.
Overcurrent protection is accomplished using Molded Canister Fuse (MCAN) or Molded
Vacuum Interrupter (MVI) modules. These can be used in combination with MVS modules.
The simplest product is a single MVI unit, which can be installed in a vault, on a pole or inside
a padmount enclosure. One of the most widely used applications for this configuration is as a
replacement for existing oil fuse cutouts. Two, three and four-way units are also available in any
combination of MVI, MCAN and MVS modules and in vault and padmount styles. Fuses and
interrupters are applied in underground loops to aid in the sectionalizing of the main feeder
and by providing protection to the loads along the loop. For more information on canister fuses,
please refer to the Fuses Product Selection Guide (PG-PC-H).

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PROTECTION AND CONTROL


Manual Sectionalizing

Underground
Distribution Switchgear

Load switching is required when:


1. A load needs to be isolated to perform maintenance
2. A load needs to be isolated to repair a fault
3. A loop needs to be reconfigured to feed certain load from a different substation and
isolate the faulted portion of the loop
In any case, the use of a manual sectionalizer contributes to reduce the length of time that
unfaulted or unaffected portions of the system are exposed to an outage. This results in
improved reliability of the system as the duration of outages is reduced (i.e. the SAIDI and
CAIDI reliability indices).
Switching products can be applied as replacement for existing Oil Fuse Cutouts or as Manual
Sectionalizers for loops or radial feeders. Depending on the application, these sectionalizers
may be installed in a vault or inside a padmount enclosure. Pole installations are also available.

MANUAL SECTIONALIZING IMPROVES RELIABILITY

In the example to the right, a radial feeder is


exposed to two failures in one year. Without
any manual sectionalizing, all customers are
subject to both failures and are out of power
until failures are restored. Assuming that the
duration of outage one (F1) is one hour, and
outage two (F2) is two hours, the calculation
of SAIDI shows 3 hours of interruption
duration per year.

With the use of an MVS at the midpoint of


the feeder, the restoration time is reduced.
Once the fault is located, the MVS is open
to isolate the faulted portion of the feeder.
At this point, the other half of the feeder
can be energized, reducing the outage
duration or SAIDI from 3 hours to 2.5
hours per year (16.6%).

Similar application of MVS switches in loop configurations contribute to significantly reduce


the outage duration. In these cases, single or multi-way switch configurations can be applied.

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Automatic Sectionalizing

Fault-interrupting devices are used on:


Underground
Distribution Switchgear

1. Feeders to sectionalize, so that if there is a fault only a small section of the load
is affected
2. Radial taps deriving from a main feeder or loop, so that a fault on a tap is isolated
from the main circuit
3. Network transformers to isolate the devices in case of overcurrent, excessive
pressure/temperature, etc.
While a switching device contributes to decrease the duration of outages, fault interrupters
contribute to decrease the duration AND frequency of outages (i.e. SAIDI, CAIDI, SAIFI,
CAIFI reliability indices).
AUTOMATIC SECTIONALIZING IMPROVES RELIABILITY

In the example to the right, a radial feeder is


exposed to two failures in one year. Without
any automatic sectionalizing (overcurrent
protection), all customers are subject to both
failures and are out of power until failures are
restored. Assuming that the duration of outage
one (F1) is one hour, and outage two (F2) is two
hours, the calculation of SAIDI shows 3 hours of
interruption duration per year. The calculation of
the frequency of interruptions (SAIFI) shows two
interruptions per year.

With the use of an MVI overcurrent fault-interrupting


device at the midpoint of the feeder, failure F2
only affects half of the load. Proper protection
coordination, between the MVI and the substation
breaker, allows the MVI to clear the fault before any
customers between the MVI and the breaker are
affected. Frequency and duration of interruption are
significantly reduced. SAIDI is reduced from 3 to 2
hours of interruption per year (33%), and SAIFI is
reduced from 2 to 1.5 interruptions per year (25%).

Similar improvements can be


accomplished with the use of MVIs
in loop systems. A typical example
of the use of radial protection
off the main feeder to improve
reliability is the use of single-phase
MVIs in sectionalizing cabinets.
These cabinets can be installed
with no tap protection at the
beginning of a construction project
and MVIs can be added as the loads
come online.
PG-PC-E-0907

ESP313-BJB-XXX

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PROTECTION AND CONTROL


Underground Loop Systems

Underground
Distribution Switchgear

Underground Loop Systems


In the case of underground loops, the switching devices along the loop can be used to
reconfigure the loop. Thus, regardless of the location of the fault, the switches will operate
to isolate the faulted portion of the loop and restore service to the remaining customers.
In the following example, permanent Fault A will cause the breaker to lock out and all
customers up to the open point will be subjected to an outage. The next step is to locate the
fault. After the fault is located, it is necessary to reconfigure the loop to isolate the faulted
portion. This is done by opening Switch 1 and closing Switch 2. These operations can be
done manually or via SCADA.
EXAMPLE: UNDERGROUND LOOP SYSTEM
Fault A

B1

S2
Switch 1

Breaker
Locks Out

Switchgear 1

NC = normally closed
NO = normally opened

Switch 2

Switchgear 2

B2

S4

S3

Fault A

B1

S2

OPEN

Switch 1

Breaker
Locks Out

Switchgear 1

CLOSE

Switch 2

Switchgear 2

B2

10

S4

S3

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Underground Loop Systems

Multi-Way Unit Construction

COMMON BUS
ASSEMBLY

For padmount installations, a double-sided,


drop-over, painted, mild steel enclosure is
provided. Munsell Green 7GY 3.29/1.5 is the
standard enclosure color. Other colors are
available upon request. Painted stainless steel
or fiberglass enclosures are available as options.

PADMOUNT
STYLE UNIT

VAULT
STYLE UNIT

PADMOUNT UNIT: Tap (Load) Side

Drop-in mild or stainless steel


enclosures available*

Top lifts up for ease


of operation
and fuse removal
MVI mechanism on
1 protection tap
(3 also available)

MCAN canister
fused tap

Internal electronic control


and current-sensing device
(3-Phase MVI and External
controls also available)

Parking stand

Ground rod

200 amp wells (shown)


600 amp bushings available

*Consult your local representative for fiberglass enclosure options

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

11

Underground
Distribution Switchgear

Multi-way vault and padmount units are built


using MVS, MVI and MCAN modules as required
by the application. These are mounted onto the
ES Multi-way common bus system and assembled
on a free-standing, floor-mounted frame. At this
stage, the product is ready to be used in vault
installations.

PROTECTION AND CONTROL


Automatic Source Transfer

Underground
Distribution Switchgear

Automatic Source Transfer


The main application of source transfer packages is to transfer a load from one power source
to another. In some cases, when the load is not critical, this is done manually using a switching
device (see switching section). In the case of critical loads such as hospitals, financial institutions,
manufacturing facilities and any other load that would have computerized equipment, a fast
transfer is required between the main (preferred) source and the backup (alternate) source.
It is important for the automatic source transfer not to affect the operation of the load because
any interruption of the business process translates into costly lost production and setup time.
The preferred and backup sources are normally utility feeders, but in some cases the backup
source may be a generator.
Elastimold Switchgear offers automatic transfer (AT) packages capable of performing a full
transfer in less than two seconds. The system monitors the voltage on the preferred source and
initiates a transfer when the voltage is below the acceptable level for the customer. At this point,
the preferred source is disconnected and the alternate source connected. AT packages include:
Two three-phase MVS Switches with motor operators (one for the preferred source
and one for the alternate source).
Six voltage sensors (one for each phase of the MVS switches). These sensors monitor
voltage on every phase and feed their output to the AT control.




AT control which receives the output from the voltage sensors and determines if there
is a loss of voltage. If there is a loss of voltage, the AT control sends an OPEN signal to
the preferred source MVS, and a CLOSE signal to the alternate source MVS. When the
voltage is restored, the system transfers back to its normal state, either automatically or
at a set time.

One or two protected taps These can be MCAN or MVI modules, which protect the critical
load against overcurrent. Solid taps are also available.
PADMOUNT AUTOMATIC SOURCE TRANSFER*
MVS Switches
with Motor Operators

AT Control

Voltage
Sensor

*Automatic Source Transfer packages are also available for subsurface/vault installations.

12

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Distribution Automation

Distribution Automation

AUTOMATED UNITS
Underground
Distribution Switchgear

Elastimold distribution automation products are


designed for interoperability and rapid automation
implementation. These products can provide
Supervisory Control and Data Acquisition System
(SCADA) interface and enable feeder automation
with or without communications. Elastimold
distribution automation products will help to
strengthen existing distribution systems and
provide a strong foundation for building a
fully implemented scheme in the future.
Here are some of the benefits of distribution
automation implementation:

Early detection and correction of
abnormal line conditions

Reduced frequency and duration of outages

Remote control and automatic restoration

Floor Mounted
Vault Installation

Riser Pole
Installation


Improved dispatcher decision-making
and field manpower savings

Automation packages can be added-on
or upgraded as the system requirements
change
Elastimold Modular Switchgear offers the
ability to add automation to existing or new
installations. DC or AC motor operators can be
added to switches or interrupters in vault, riser
pole or padmount installations. The motors are
submersible and the same automation package
can be used in all applications.
The motors can either be operated from a short
distance using a handheld device, as it is the case
in some vault installations, or they can be outfitted
with fully automated controls containing:

Battery

Power supply

Customer-selected RTU

Padmount
Installation


Customer-selected
communications protocol

Customer-selected
communications device

Wall Mounted Vault Installation

NOTE: Consult your local representative on specific Distribution Automation Packages and configurations available.
PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

13

PROTECTION AND CONTROL


Network Transformer Protection

Underground
Distribution Switchgear

Network Transformer Protection


The reliability of conventional radial or looped
underground distribution circuits is measured
in terms of the number and/or frequency of
interruptions. These measurements cannot be
directly applied to a network system. A typical
network system has built-in redundancy. During
most events the continuity of power supply to
the end user is not affected by fault conditions
on the high side of the network transformers.
So, from the point of view of customer interruptions network systems are reliable.
However, transformer failures have been known
to result in catastrophic fires, explosions and
even loss of lives. The failure or overload of
multiple transformers within a network may
ultimately result in the interruption of
service to the end user.

LOSS OF REDUNDANCY

Loss of redundancy is a method that highlights the increased vulnerability of

the system every time a network transformer is lost. Loss of redundancy indices are
calculated as follows:

S (No. Hours a Transformer is Disconnected


Duration of Loss of Redundancy (hours/yr) =

Frequency of Loss of Redundancy (times/yr) =

* No. of Transformers in the Circuit)


No. of Transformers in the Circuit
Total No. Transformer De-energizations
No. of Transformers in the Circuit

Where the number of transformers in the circuit is the number of transformers energized
by the same feeder.

14

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Network Transformer Protection
The Loss of Redundancy indices are calculated in the following example.
Underground
Distribution Switchgear

EXAMPLE 1: NO HIGH-SIDE TRANSFORMER PROTECTION

One substation breaker and one exclusive feeder out to the network
Five transformers are energized by the same feeder
Assume one permanent fault on one transformer in one year
Assume the faulted transformer is de-energized for 6 hours
Because there is only one
breaker for five transformers,
a failure in one transformer
translates in the interruption
of power to 5 transformers for
6 hours.

Duration of Loss of Redundancy (hours/yr) =

(6 * 5)
5
5
5

Frequency of Loss of Redundancy (times/yr) =

= 6 hours/year
= 1 time/year

Loss of redundancy can occur as a consequence of:





Transformer fire
Transformer overheating
Transformer pressure build-up
Overcurrent condition

While the substation breaker may detect most overcurrent faults, faults caused by excessive
pressure/heat or fires cannot be detected by the breaker. One method that allows the automatic
isolation of a network transformer from the primary side, regardless of the type of failure, is
the installation of an MVI fault interrupter on the high side of the transformer. This MVI can
isolate based on overcurrent conditions but also can be wired to isolate the transformer in case
of fire, excessive pressure / heat, emergency signal, etc.
Benefits of such a setup to the network system and the end users include:






Minimization of fire damage


Reduction or elimination of transformer damage
due to pressure or temperature build-up
Longer transformer life

The following example calculates the loss of redundancy of the same system used in Example 1,
but adding protection to the primary side of the transformers.
EXAMPLE 2: HIGH-SIDE TRANSFORMER PROTECTION

One substation breaker and one exclusive feeder out to the network
Five transformers are energized by the same feeder
Each transformer is equipped with a fault interrupter installed on the high-side
Assume one permanent fault on one transformer in one year
Assume the transformer is de-energized for 6 hours
A failure in one transformer
Duration of Loss of Redundancy (hours/yr) =
translates in the interruption
of power to only 1 transformer
Frequency of Loss of Redundancy (times/yr) =
for 6 hours.

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

(6 * 1)
5
1
5

= 1.2 hours/year
= 0.2 times/year

15

PROTECTION AND CONTROL

Underground
Distribution Switchgear

Network Transformer Protection


Once an MVI is installed, remote operation from the entrance of the vault or via SCADA
is possible with the addition of a motor operator and control. Installation of panic/
emergency push buttons at the entrance of the vault is also possible; pressing this
emergency switch will instantaneously trip open one or all of the interrupters in a vault
and isolate the transformers.
TRANSFORMER NETWORK WITH PROTECTION ON THE HIGH SIDE OF THE TRANSFORMER
Local /
Remote
Operation

Local /
Remote
Operation
Trip

MVI

EPDM
Molded
Vacuum
Interrupters

MVI

Trip

Transformers
Secondary
Relay
Outputs

Secondary
Relay
Outputs
Network
Protector

Network
Protector

Network
Protector
Fuse

Network
Protector
Fuse
Network
Service Bus

Elastimold SWITCHGEAR NETWORK PACKAGE (NMVI3)


/2" 13 mm Mounting Bolts (4)

1
Ground 6 /4"
159
mm
Lug

18 1/2"
470 mm
Mounting

42 9/64"
1,070 mm

14"
356 mm
Mounting

5 1/2"
140 mm

120 VAC
Power
Supply

19"
483 mm
Mounting

5 1/2"
140 mm

DOOR IN OPEN
POSITION

Programmable Control &


Current Transformer

MVI

16

Contact Position Indicator

Motor

Network Control

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Application Summary

Product selection
Application

Function
Switching
Sectionalizing

Overcurrent
Protection

PG-PC-E-0907

Nominal Continuous Interrupting


Voltage Current
Current

Product

Page
24

Fuse Cutout Replacement

Subsurface/Vault

MVS

Manual Underground Feeder


or Loop Sectionalizing

Subsurface/Vault
Padmount

Riser Pole

Pole

ESV
ESD/PMVS/
ESP
RMVI

Network Transformer Protection

Network Transformer Vault

Fuse Cutout Replacement

Subsurface/Vault

Automatic Underground Feeder or


Loop Sectionalizing
Underground Feeder or Loop Protection

Source
Transfer

Installation

Automatic Source Transfer

26
24

NMVI

24

MVI

24

Subsurface/Vault
Padmount

ESV
PMVI/ESD/
ESP

26

Subsurface/Vault
Padmount

ATV/ATS
ATD/ATP

26

15kV
25kV
35kV

600/200A
600/200A
600/200A 12.5/16/20kA

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

17

Underground
Distribution Switchgear

From the following table, select the function and application specific to your system needs.
The last column will indicate the product to be used for the specific selection. With this
information, go to the appropriate section and finalize the construction of the catalog number
that you would need to order.

PROTECTION AND CONTROL


Product Specifications
MVS Molded Vacuum Switches are spring
Underground
Distribution Switchgear

energy, load switching devices capable of


making, carrying and interrupting load
currents through 600 amperes on 5-38kV
distribution systems. The MVS combines
vacuum switching with high dielectric strength
EPDM rubber insulation, providing compact,
lightweight submersible switching. Units
include molded-in elbow connection interfaces,
spring energy mechanism and are available in
both single and three-phase models. Units are
manually operated with a hotstick and motor
operator. SCADA and Auto-Transfer Control
options are available.
Single-Phase Switches
ApproxIMATE Weight 30 lbs.
12 1/2"
318 mm

6 15/64"
176 mm

4 1/16"
103 mm
5 1/2"
140 mm

6 7/16"
164 mm

THREE-Phase Switches
ApproxIMATE Weight 135 lbs.

/8" / 16 mm Dia. x 7/8" / 22 mm (4) Mounting Holes

Open

43

8 5/32"
207 mm

Closed

13 7/16"
341 mm

26"
660 mm
14"
356 mm

8 15/16"
227 mm

5 1/2"
140 mm

23 25/32"
604 mm
12 1/2"
318 mm

5 1/2"
140 mm
5 1/2"
140 mm

6 15/64"
176 mm
/8" / 16 mm Dia. x 7/8" / 22 mm (4) Mounting Holes

Open

43

19"
483 mm

6 1/16"
154 mm
10 5/32"
258 mm

Closed

13 7/16"
341 mm

8 1/32"
204 mm
6 /64"
173 mm
51

25 27/32"
656 mm

9 1/2"
241 mm

19"
483 mm

1 35/64" / 39 mm

Available with 600 amp one-piece bushings


or 200 amp wells on either/both terminals

18

18 1/2"
470 mm

21"
533 mm

Available with 600 amp one-piece bushings


or 200 amp wells on either/both terminals

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Product Specifications

RATINGS

MVS loadbreak switches have been


designed and tested per applicable
portions of IEEE, ANSI, NEMA and
other industry standards including:

Maximum Design Voltage

27kV

38kV

50/60 Hz

50/60 Hz

50/60 Hz

BIL Impulse Withstand

95kV

125kV

150kV

One Minute AC Withstand

35kV

60kV

70kV

IEEE C37.74 Standard for Subsurface,


Vault and Padmounted Load
Interrupting Switches

Five Minute DC Withstand

53kV

78kV

103kV

Load Interrupting & Loop Switching

600 A

600 A

600 A

Transformer Magnetizing Interrupting

21 A

21 A

21 A

IEEE 386 Standard for Separable


Connectors and Bushing Interfaces

Capacitor or Cable Charging


Interrupting

40 A

40 A

40 A

Asymmetrical Momentary and


3 Operation Fault Close

20,000 A

20,000 A

20,000 A

Symmetrical One Second Rating

12,500 A

12,500 A

12,500 A

Continuous Current

600 A

600 A

600 A

8 Hour Overload Current

900 A

900 A

900 A

IEC 265 International Standards for


Load Interrupting Switches
ANSI C57.12.28 Standard for
Padmount Enclosures

Frequency

15.5kV

APPLICATION INFORMATION
Construction: Submersible, corrosion resistant, fully shielded
Ambient Temperature Range: -30 to +40 degrees Celsius

Cable connection
bushings

43
Open
position

Closed
position

Operating
handle

Spring operating
mechanism contained
within 304 stainless steel
housing

Insulated
drive rod
assembly

Vacuum interrupter
contact system

Molded EPDM rubber


insulation and shielding

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

19

Underground
Distribution Switchgear

CERTIFIEDTESTS & PERFORMANCE

PROTECTION AND CONTROL


Product Specifications

Underground
Distribution Switchgear

MVI Molded Vacuum Fault Interrupters


are devices capable of making, carrying and
automatically interrupting currents through
12,500 amperes symmetrical on 5-38kV
distribution systems. The MVI combines
vacuum interrupters, programmable
electronic self-powered controls and high
dielectric strength EPDM rubber insulation
to provide compact, lightweight, submersible,
overcurrent protection. Units include moldedin elbow connection interfaces, trip-free
mechanism and are available in single-phase
and three-phase models.
Units are self-powered and include currentsensing and electronic control. The control is
field programmable with a wide range of TimeCurrent Characteristic (TCC) curves and trip
settings. The TCC curves provide predictable
tripping for ease of coordination with upstream
and/or downstream protective devices. The
control monitors the circuit condition and when
the programmed parameters are exceeded,
a signal is sent to the tripping mechanism.
Motor operators and controls are available
and allow reconfiguration of radial feeders
or loops, manually or via SCADA.
FRONT VIEW THREE-PHASE

FRONT VIEW SINGLE-PHASE


29 /8"
740 mm
1

30 5/8"
778 mm

Ground
Lug

12 1/2"
318 mm
5 1/2"
140 mm

200 AMP WELLS


8 61/64"
227 mm

14 3/32"
358 mm
Mounting

32 7/8"
835 mm

5 1/2"
18 1/2"
140
mm
470 mm
Mounting
5 1/2"
140 mm

19"
483 mm
Mounting

Well Interface
accepts Standard
Bushing Inserts
5 27/32"
148 mm

600 AMP T ELBOW INTERFACE


Programmable Control &
Current Transformer
600 amp
10 57/64"
Bushing
277 mm
Interfaces

600 AMP BUSHINGS


Conforms to ANSI std. 386

6 /4"
156 mm
1

8 61/64"
227 mm

9 /2"
241 mm
2 57/64"
73 mm
600 Series
Elbow Interfaces

Closed/
Tripped

Open/
Reset

Locking
Features

8 15/16"
227 mm

20

17 45/64"
450 mm

Alternate Handle Position


Handle maybe repositioned in 60 Incements

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Product Specifications
CERTIFIEDTESTS & PERFORMANCE

RATINGS
Voltage Class

ANSI C37.60 Standard for Fault


Interrupters

Five Minute DC Withstand

53kV

Load Interrupting & Loop Switching

600 A


IEEE
C37.74 Standard for
Subsurface, Vault and Padmount
Load Interrupting Switches

Transformer Magnetizing Interrupting

21 A

21 A

IEEE 386 Standard for Separable


Connectors and Bushing
Interfaces
IEC 265 International Standards
for Load Interrupting Switches
ANSI C57.12.28 Standard for
Padmounted Enclosures

Maximum Design Voltage


Frequency

15.5kV

15.5kV

27kV

35kV

17kV

15.5kV

29kV

38kV

50/60Hz

50/60Hz 50/60Hz

50/60Hz

BIL Impulse Withstand

95kV

95kV

125kV

150kV

One Minute AC Withstand

35kV

35kV

60kV

70kV

53kV

78kV

103kV

600 A

600 A

600 A

21 A

21 A

Capacitor or Cable Charging Interrupting


Symmetrical/Asymmetrical Momentary
and Fault Close
Symmetrical One Second Rating
Continuous Current
Symmetrical/Asymmetrical
Interrupting Capability
Current Sensor Ratio

40 A

40 A

40 A

40 A

12.5/20 kA
or 16/32 kA

20/
25.6 kA

12.5/
20 kA

12.5/
20 kA

600 A

600 A

600 A

600 A

12.5/20 kA
or 16/32 kA

20/
25.6 kA

12.5/
20 kA

12.5/
20 kA

1000:1

1000:1

1000:1

1000:1

APPLICATION INFORMATION
Meets ANSI C37.60 requirement
Construction: Submersible, corrosion resistant, fully shielded
Ambient Temperature Range: -30 to +40 degrees Celsius

Operating handle
Control module (1)
Sensing module (3)

Positive
contact
position

Spring
operating
mechanism
with tripping

PG-PC-E-0907

Insulated drive
rod assembly

Molded EPDM
rubber insulation
and shielding

Cable connection
bushings

Vacuum fault
interrupter
contact system

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

21

Underground
Distribution Switchgear

MVI Molded Vacuum Fault


Interrupters have been designed
and tested per applicable portions
of IEEE, ANSI, NEMA and other
industry standards including:

PROTECTION AND CONTROL


Product Specifications

Underground
Distribution Switchgear

Molded Vacuum Interrupters are provided with self-powered electronic control packages,
requiring no batteries or external power. Field-selectable Fuse or Relay Curves and Trip
Settings are available. The controls monitor current through the interrupter and, if an
overcurrent condition is detected, send a signal to the vacuum interrupters to trip open and
interrupt the fault. Depending on the application, four electronic control options are available
for the MVI:
INTERNAL CONTROL

This control is integral to the unit (no separate


control box). It is accessible via computer
connection to view or modify settings. This control
is used on ganged three-phase or single-phase MVI
interrupters. Phase and Ground trip, as well as
Inrush restraint, are available. The E-Set software
allows the user to connect to the internal control
either in the shop or the field to program or change
settings. MVI-STP programming connector is
required to connect between the PC and the MVI.
With a computer connected to the MVI control
the user can view real-time currents, the number
of overcurrent protection operations, current
magnitude of the last trip and the phase/ground
fault targets. This is the standard control option.

Note: E-set can be downloaded from


www.elastimoldswitchgear.com

EXTERNAL CONTROL WITH SINGLE / THREE-PHASE TRIP SELECTION (Style 10)

This control is mounted externally to the mechanism and


provides the ability to select TCCs by setting dip switches
on the front panel. Each phase can be assigned
a different minimum trip setting by means of manual
rotary switches. This control is used on one, two or
three single-phase MVI mechanisms.

EXTERNAL CONTROL WITH PHASE AND GROUND TRIP (Style 20)

This control is mounted externally to the mechanism


and provides the ability to select phase minimum
trip (one for all three phases), time delay for phase
tripping, ground trip as a percent of phase minimum
trip, and ground trip delay by means of manual rotary
switches. This control may be used on ganged threephase or three single-phase MVI mechanisms.

22

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Product Specifications
EXTERNAL CONTROL WITH THREE-PHASE TRIP ONLY (Style 30)
Underground
Distribution Switchgear

This control is mounted externally to the mechanism and


provides the ability to select phase minimum trip (one for
all three phases) by means of a manual rotary switch.
It also has an RS232 port for connection to a PC to
view the last trip data. This control is used on ganged
three-phase or three single-phase MVI mechanisms.

EXTERNAL CONTROL WITH SELECTABLE SINGLE / THREE-PHASE TRIP FUNCTION (80 Control)

This control is mounted externally to the mechanism of


the interrupter and provides the ability to select between
single-phase trip and three-phase trip. The 80 Control can
be used with one three-phase interrupter or with three
single-phase interrupters. For three-phase applications, the
ground trip function can be blocked from the front panel.
Manual Trip and Reset Target buttons are also located on
the front panel. This control uses the E-Set software, which
allows programming via computer using the MVI-STP
adapter. E-Set features custom TCC curves and provides
access to the last fault event information, as well as
real-time-current per phase.
CURVES

Relay Curves (minimum trip 30-600 amp) Fuse Curves (minimum trip 10-200 amp)

Curve #

01

02

03

04

05

06

07

08

09

10

11

12

13

14

16

17
18-23
24-27
28-31

PG-PC-E-0907

Curve Reference #
MVI-TCC-01
MVI-TCC-02
MVI-TCC-03
MVI-TCC-04
MVI-TCC-05
MVI-TCC-06
MVI-TCC-07
MVI-TCC-08
MVI-TCC-09
MVI-TCC-10
MVI-TCC-11
MVI-TCC-12
MVI-TCC-13
MVI-TCC-14
MVI-TCC-16
MVI-TCC-17
MVI-TCC-18 to 23
MVI-TCC-24 to 27
MVI-TCC-28 to 31

Curve Type
E Slow
E Standard
Oil Fuse Cutout
K
Kearney QA
Cooper EF
Cooper NX-C
CO-11-1
CO-11-2
T
CO-9-1
CO-9-2
Cooper 280ARX
F
Kearney KS
GE Relay
CO-8-1 to CO-8-6
CO-9-3 to CO-9-6
CO-11-3 to CO-11-6

Curve #
54
55
56
57
58
59
60

Curve Reference #
MVI-TCC-54
MVI-TCC-55
MVI-TCC-56
MVI-TCC-57
MVI-TCC-58
MVI-TCC-59
MVI-TCC-60

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

Curve Type
E Slow
E Standard
Oil Fuse Cutout
K
Kearney QA
Cooper NX-C
T

23

PROTECTION AND CONTROL


Ordering Information

Underground
Distribution Switchgear

ORDERING INFORMATION for MOLDED VACUUM SWITCHES AND INTERRUPTERS

The following graph shows how to construct


the catalog number for Molded Vacuum
Switches and Interrupters. Catalog numbers
are shown on Tables 1-2.

EXAMPLE: The catalog number for Molded


Vacuum Interrupter on a three-phase,
27kV system, with 600 amp terminal
and parking stands between bushings
is: MVI3-21-27-66-PS

X MV X X - 21 - XX - X X X - SUFFIX
LOAD INTERFACE

SWITCH TYPE

R

N
Blank

Riser Pole
Network
Subsurface

2
6

200 Amp Bushing Well


600 Amp Bushing

INTERFACE
E
600 Amp T Body
R Top Interface Rotated 180 Degrees
AB Air Bushings (for Riser Pole Units)

DEVICE

S
I

Switch
Interrupter

LOAD INTERFACE

PHASES

1
3

Single-phase
Three-phase

2
6

200 Amp Bushing Well


600 Amp Bushing

Voltage class


15
27
38

15.0kV
27.0kV
38.0kV

SUFFIX (CONTROLS AND ACCESSORIES)


20
30
80
110
310
320
330
380
MO120A
MO12D
PS
MPS
PS6
BT
P

External 20 Control with Phase and Ground Trip (to be used on ganged 3-phase MVI mechanism)
External 30 Control with 3-phase Trip Only (to be used on ganged 3-phase MVI mechanism)
External 80 Control with Selectable Single/3-phase Trip Function (to be used on ganged 3-phase MVI mechanism)
External 10 Control with Single Trip Selection (to be used on one 1-phase MVI mechanism)
External 10 Control with Single/3-phase Trip Selection (to be used on three 1-phase MVI mechanisms)
External 20 Control with Phase and Ground Trip (to be used on three 1-phase MVI mechanisms)
External 30 Control with 3-phase Trip Only (to be used on three 1-phase MVI mechanisms)
External 80 Control with Selectable Single/3-phase Trip Function (to be used on three 1-phase MVI mechanisms)
120 VAC Motor Operator and Controller for MVS3 or MV13 Units
12-24 VDC Motor Operator and Controller for MVS3 or MVI3 Units
Parking Stand for MVS or MVI (between bushings for single or 3-phase units)
Parking Stand for MVS3, MVI3 or RMVI3 on Mechanism Cover
Double Parking Stand for MVS3, MVI3 or RMVI3 (between bushings and on mechanism cover)
Bail Tab Plate Installed for 3-phase Units Only
Customer Settings to be Programmed at the Factory

NOTE: Leave suffix blank for internal (self-contained) control

TABLE 1 ordering information for molded vacuum switches


Diagram

Width

Description

Catalog Number

Height

Depth

Weight

Single-Phase Vacuum Switches


MVS1-21-15-XX
MVS1-21-15-6EX
MVS1-21-27-XX
MVS1-21-27-6EX
MVS1-21-38-XX
* Height includes handle

24

15kV 2-way 1-phase Switch


15kV 2-way 1-phase Switch - Elbow Interface
25kV 2-way 1-phase Switch
25kV 2-way 1-phase Switch - Elbow Interface
35kV 2-way 1-phase Switch

6"
6"
6"
6"
6"

152mm
152mm
152mm
152mm
152mm

24"
26"
24"
26"
24"

610mm
660mm
610mm
660mm
610mm

14"
15"
14"
15"
14"

356mm
381mm
356mm
381mm
356mm

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

30lb
30lb
30lb
30lb
30lb

14kg
14kg
14kg
14kg
14kg

PG-PC-E-0907

PROTECTION AND CONTROL


Ordering Information
TABLE 1 ordering information for molded vacuum switches (continued)
Diagram

Width

Description

Catalog Number

Height

Depth

Weight

*
**

MVS3-21-15-XX

15kV 2-way 3-phase Switch

21"

533mm 26"

660mm

19" 483mm 135lb 61kg

MVS3-21-27-XX

25kV 2-way 3-phase Switch

21"

533mm 26"

660mm

19" 483mm 135lb 61kg

MVS3-21-38-XX

35kV 2-way 3-phase Switch

21"

533mm 26"

660mm

19" 483mm 135lb 61kg

* Height includes handle


** Three-Phase Vacuum Switches are motor ready

TABLE 2 ordering information for molded vacuum interrupTers


Diagram

Catalog Number

Width

Description

Depth

Height

Weight

RISER POLE (Three-Phase Installations Only)


RMVI3-21-15-6ABX-YY

15kV 2-way 3-phase - Interrupter with Air Bushings on Top Terminals

30"

762mm 45" 1,143mm 25" 635mm 150lb 68kg

RMVI3-21-27-6ABX-YY

25kV 2-way 3-phase - Interrupter with Air Bushings on Top Terminals

30"

762mm 45" 1,143mm 25" 635mm 150lb 68kg

RMVI3-21-38-6ABX-YY

38kV 2-way 3-phase - Interrupter with Air Bushings on Top Terminals

30"

762mm 45" 1,143mm 25" 635mm 150lb 68kg

RMVI1-21-15-6ABX-3YY

15kV 2-way 3-phase - Interrupter with Air Bushings on Top Terminals


1-phase Trip Selectable

30"

762mm 45" 1,143mm 25" 635mm 150lb 68kg

RMVI1-21-27-6ABX-3YY

27kV 2-way 3-phase - Interrupter with Air Bushings on Top Terminals


1-phase Trip Selectable

30"

762mm 45" 1,143mm 25" 635mm 150lb 68kg

RMVI1-21-38-6ABX-3YY

38kV 2-way 3-phase - Interrupter with Air Bushings on Top Terminals


1-phase Trip Selectable

30"

762mm 45" 1,143mm 25" 635mm 150lb 68kg

SUBSURFACE
Single-Phase Vacuum Interrupter
MVI1-21-15-XX

15kV 2-way 1-phase Interrupter

6"

152mm 31"

787mm

9"

229mm

45lb

20kg

MVI1-21-15-6EX

15kV 2-way 1-phase Interrupter - Elbow Interface

6"

152mm 31"

787mm

11" 279mm

45lb

20kg

MVI1-21-27-XX

27kV 2-way 1-phase Interrupter

6"

152mm 31"

787mm

9"

229mm

45lb

20kg

MVI1-21-27-6EX

27kV 2-way 1-phase Interrupter - Elbow Interface

6"

152mm 31"

787mm

11" 279mm

45lb

20kg

MVI1-21-38-XX

38kV 2-way 1-phase Interrupter

6"

152mm 31"

787mm

9"

229mm

45lb

20kg

MVI1-21-38-6EX

38kV 2-way 1-phase Interrupter - Elbow Interface

6"

152mm 31"

787mm

11" 279mm

45lb

20kg

20"

508mm 31"

787mm

9"

229mm 145lb 66kg

Three-Phase Vacuum Interrupter


MVI1-21-15-XX-3YY
15kV 2-way 3-phase Interrupter - 1-phase Trip Selectable - Ext. Control
MVI1-21-27-XX-3YY

27kV 2-way 3-phase Interrupter - 1-phase Trip Selectable - Ext. Control

20"

508mm 31"

787mm

9"

229mm 145lb 66kg

MVI1-21-38-XX-3YY

38kV 2-way 3-phase Interrupter - 1-phase Trip Selectable - Ext. Control

20"

508mm 31"

787mm

9"

229mm 145lb 66kg

MVI3-21-15-XX-YY

15kV 2-way 3-phase Interrupter

20"

508mm 33"

838mm

10" 254mm 145lb 66kg

MVI3-21-27-XX-YY

27kV 2-way 3-phase Interrupter

20"

508mm 33"

838mm

10" 254mm 145lb 66kg

MVI3-21-38-XX-YY

38kV 2-way 3-phase Interrupter

20"

508mm 33"

838mm

10" 254mm 145lb 66kg

ACCESSORIES (order separately)


Catalog Number
MVI-STP-USB

Description
Adapter for Connection Between MVI Units with Internal Control, and a Computer for Programming/Viewing Settings

MV1PMB

Pole Mounting Bracket for 1-phase Units Only

MV3PMB

Pole Mounting Bracket for 3-phase Units Only

MV3HPMB

Horizontal Pole Mounting Bracket for 3-phase Units Only

MV13PMB

Pole Mounting Bracket for Three 1-phase Units Only

35AL-11

Connector Bare Wire Type 3/4" - 16 Rod for Riser Pole Units. Qty. of 1 Needed per Phase

35AL-12

Connector 2-Hole Spade Type 3/4" - 16 Rod for Riser Pole Units. Qty. of 1 Needed per Phase

MVI-TESTER

Tester for Electric Control Style 80

NOTES:
Weights and dimensions are approximate.
X = 6 for 600 amp or 2 for 200 amp or 6E for 600 amp T interface.
Y = 10, 20, 30, 80 for different electronic controls.
Leave blank for internal (self-contained) control.

PG-PC-E-0907

Accessories should be added as suffix to the main catalog number


unless otherwise noted.
Other configurations are available. Please consult your local
representative on configurations not shown here.
Three-phase Vacuum Interrupters are motor ready.

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

25

Underground
Distribution Switchgear

Three-Phase Vacuum Switches

PROTECTION AND CONTROL


Ordering Information
ORDERING INFORMATION for multi-way switchgear or transfer package
Underground
Distribution Switchgear

The following graph shows how to construct


the catalog number for Multi-Way Switchgear
or transfer packages. Catalog numbers are
shown on Tables 3-5 for the most common
configurations:

EXAMPLE: The catalog number for an


auto-transfer package for padmount
installation on a three-phase, 27kV system,
with two MVI protected taps, 600 amp
terminals and standard mild steel enclosure
is: ATD324-AAPP-6666

XX X X X X - XXXX - XXXX X X
Ways

enclosure material

Switch type

Blank

AT

Auto Transfer

ES

Multi-Way Switch

Mild Steel
Stainless Steel

Cabinet Depth Padmount


Blank

Type



V
S
D
P

Vault
Sub Surface
Double Side Padmount
Single Side Padmount

interface by way

Single-phase

Three-phase

Voltage class

1
2
3

15.5kV
27.0kV
38.0kV

# Ways


2
3
4

2 Way
3 Way
4 Way

EXAMPLE: ATD324-AAPP-6666

Way 1

Way 2

NOTES:
Custom padmount enclosure dimensions
P
P
are available
Parking stands are standard on padmount units
Consult your local representative on multi-way
configurations that include 38kV MVIs
Way 3 Way 4
Three-phase MVS and MVI are motor ready
Auto transfer ways 1 & 2 are always A
* The Multi-Way Switchgear needs to be de-energized for fuse replacement

26

2
6

200 Amp Bushing Well


600 Amp Bushing

COMPONENTS BY WAY

PHASES

54 Inches

3-phase Switch Motor Operator Auto Transfer

Solid Tap/Direct Bus Connection (600 or 200A)

3-phase MVI Fault Interrupter 20 Control

3-phase MVI Fault Interrupter 30 Control

E*

MCAN 4B CL Fuse Canister 8.3kV Fuses

F*

MCAN 5B CL Fuse Canister 15.5kV Fuses

G*

MCAN 6B CL Fuse Canister 23.0kV Fuses

1-phase Fault Interrupter

1-phase Fault Interrupter, 10 Control

1-phase Fault Interrupter, 80 Control

1-phase Fault Interrupter, 20 Control

1-phase Fault Interrupter, 30 Control

3-phase MVI Fault Interrupter, 80 Control

3-phase MVI Fault Interrupter

3-phase MVS Switch with UAD Control

3-phase MVI Fault Interrupter Motor Operator 12-24 Vdc

1-phase MVS Switch

3-phase MVS Switch

3-phase MVS with 12-24 Vdc Motor

3-phase MVS with 120 Vac Motor

3-phase MVI Fault Interrupter Motor Operator 120 Vac

3-phase MVI Fault Interrupter with UAD Control

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Ordering Information
DOUBLE SIDE PADMOUNT ESd3X4-IIPP-6622-S

SINGLE SIDE PADMOUNT ESP313-BJB-626


84"
2,134 mm

42"
1,067 mm

Subsurface ESS3X2-TT-66

Underground
Distribution Switchgear

54"
1,372 mm

54"
1,372 mm

vault ESV3X4-TTTT-2222
MVs3 switch

33 /8"
841 mm
1

35 3/8"
899 mm
19"
483 mm

5 1/2"
140 mm

48"
1,219 mm
Stainless steel bottom rails

TABLE 3 ordering information for SWITCHING AND SECTIONALIZING SWITCHGEAR


Diagram

Catalog Number

Description

ESV313-TTT-XXX

15kV 3-way 3-phase Switch

48"

1,219mm

36"

914mm

22"

559mm

750lb

340kg

ESV323-TTT-XXX

27kV 3-way 3-phase Switch

48"

1,219mm

36"

914mm

22"

559mm

750lb

340kg

ESV333-TTT-XXX

38kV 3-way 3-phase Switch

48"

1,219mm

36"

914mm

22"

559mm

750lb

340kg

ESV314-TTTT-XXXX

15kV 4-way 3-phase Switch

48"

1,219mm

36"

914mm

22"

559mm

880lb

399kg

ESV324-TTTT-XXXX

27kV 4-way 3-phase Switch

48"

1,219mm

36"

914mm

22"

559mm

880lb

399kg

ESV334-TTTT-XXXX

38kV 4-way 3-phase Switch

48"

1,219mm

36"

914mm

22"

559mm

880lb

399kg

PMVS1-21-15-XX

15kV 2-way 1-phase Switch

36"

914mm

30"

762mm

30"

762mm

310lb

141kg

PMVS1-21-27-XX

27kV 2-way 1-phase Switch

36"

914mm

30"

762mm

30"

762mm

310lb

141kg

PMVS1-21-38-XX

38kV 2-way 1-phase Switch

36"

914mm

30"

762mm

30"

762mm

310lb

141kg

ESD312-T-XX

15kV 2-way 3-phase Switch

36"

914mm

48"

1,219mm

42" 1,067mm

680lb

308kg

ESD322-T-XX

27kV 2-way 3-phase Switch

36"

914mm

48"

1,219mm

42" 1,067mm

680lb

308kg

Width

Depth

Height

Weight

VAULT

PADMOUNT

ESD332-T-XX

38kV 2-way 3-phase Switch

36"

914mm

48"

1,219mm

42" 1,067mm

680lb

308kg

ESD313-TTT-XXX

15kV 3-way 3-phase Switch

54"

1,317mm

48"

1,219mm

54" 1,317mm 1250lb

567kg

ESD323-TTT-XXX

27kV 3-way 3-phase Switch

54"

1,317mm

48"

1,219mm

54" 1,317mm 1250lb

567kg

ESD333-TTT-XXX

38kV 3-way 3-phase Switch

54"

1,317mm

48"

1,219mm

54" 1,317mm 1250lb

567kg

ESD314-TTTT-XXXX

15kV 4-way 3-phase Switch

54"

1,317mm

48"

1,219mm

54" 1,317mm 1380lb

626kg

ESD324-TTTT-XXXX

27kV 4-way 3-phase Switch

54"

1,317mm

48"

1,219mm

54" 1,317mm 1380lb

626kg

ESD334-TTTT-XXXX

38kV 4-way 3-phase Switch

54"

1,317mm

48"

1,219mm

54" 1,317mm 1380lb

626kg

NOTE:
Other configurations are available. Consult your local representative on configurations not shown here.
PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

27

PROTECTION AND CONTROL


Ordering Information
TABLE 4 ordering information for Overcurrent protection switchgear
Underground
Distribution Switchgear

Diagram Catalog Number

Width

Description

Depth

Height

Weight

VAULT
ESV312-E-XX

8.3kV 2-way 3-phase - One Fused Tap with Canister Fuses

21"

533mm

24"

610mm

11"

279mm

63lb

29kg

ESV322-F-XX

15kV 2-way 3-phase - One Fused Tap with Canister Fuses

21"

533mm

29"

737mm

11"

279mm

69lb

31kg

ESV332-G-XX

23kV 2-way 3-phase - One Fused Tap with Canister Fuses

21"

533mm

32"

813mm

11"

279mm

72lb

33kg

ESV312-TE-XX

8.3kV 2-way 3-phase - One Source Switch, One Fused Tap

24"

610mm

36"

914mm

22"

559mm

350lb

159kg

ESV322-TF-XX

15kV 2-way 3-phase - One Source Switch, One Fused Tap

24"

610mm

36"

914mm

22"

559mm

350lb

159kg

ESV332-TG-XX

23kV 2-way 3-phase - One Source Switch, One Fused Tap

24"

610mm

39"

991mm

22"

559mm

350lb

159kg

ESV313-TEE-XXX

8.3kV 3-way 3-phase - One Source Switch, Two Fused Taps

36"

914mm

48"

1,219mm 22"

559mm

560lb

254kg

ESV323-TFF-XXX

15kV 3-way 3-phase - One Source Switch, Two Fused Taps

36"

914mm

48"

1,219mm 22"

559mm

560lb

254kg

ESV333-TGG-XXX

23kV 3-way 3-phase - One Source Switch, Two Fused Taps

39"

991mm

48"

1,219mm 22"

559mm

560lb

254kg

ESV313-TTE-XXX

8.3kV 3-way 3-phase - Two Source Switches, One Fused Tap

36"

914mm

48"

1,219mm 22"

559mm

560lb

254kg

ESV323-TTF-XXX

15kV 3-way 3-phase - Two Source Switches, One Fused Tap

36"

914mm

48"

1,219mm 22"

559mm

560lb

254kg

ESV333-TTG-XXX

23kV 3-way 3-phase - Two Source Switches, One Fused Tap

39"

991mm

48"

1,219mm 22"

559mm

560lb

254kg

ESV313-TPP-XXX

15kV 3-way 3-phase - One Source Switch, Two Vacuum Interrupter Taps

40"

1,016mm

48"

1,219mm 22"

559mm

660lb

299kg

ESV323-TPP-XXX

27kV 3-way 3-phase - One Source Switch, Two Vacuum Interrupter Taps

40"

1,016mm

48"

1,219mm 22"

559mm

660lb

299kg

ESV313-TTP-XXX

15kV 3-way 3-phase - Two Source Switches, One Vacuum Interrupter Tap

40"

1,016mm

48"

1,219mm 22"

559mm

660lb

299kg

ESV323-TTP-XXX

27kV 3-way 3-phase - Two Source Switches, One Vacuum Interrupter Tap

40"

1,016mm

48"

1,219mm 22"

559mm

660lb

299kg

ESV314-TEEE-XXXX

8.3kV 4-way 3-phase - One Source Switch, Three Fused Taps

36"

914mm

48"

1,219mm 22"

559mm

670lb

304kg

ESV324-TFFF-XXXX

15kV 4-way 3-phase - One Source Switch, Three Fused Taps

36"

914mm

48"

1,219mm 22"

559mm

670lb

304kg

ESV334-TGGG-XXXX

23kV 4-way 3-phase - One Source Switch, Three Fused Taps

36"

914mm

48"

1,219mm 22"

559mm

670lb

304kg

ESV314-TTEE-XXXX

8.3kV 4-way 3-phase - Two Source Switches, Two Fused Taps

36"

914mm

48"

1,219mm 22"

559mm

740lb

336kg

ESV324-TTFF-XXXX

15kV 4-way 3-phase - Two Source Switches, Two Fused Taps

36"

914mm

48"

1,219mm 22"

559mm

740lb

336kg

ESV334-TTGG-XXXX

23kV 4-way 3-phase - Two Source Switches, Two Fused Taps

39"

991mm

48"

1,219mm 22"

559mm

740lb

336kg

ESV314-TTTE-XXXX

8.3kV 4-way 3-phase - Three Source Switches, One Fused Tap

36"

914mm

48"

1,219mm 22"

559mm

810lb

367kg

ESV324-TTTF-XXXX

15kV 4-way 3-phase - Three Source Switches, One Fused Tap

39"

991mm

48"

1,219mm 22"

559mm

810lb

367kg

ESV334-TTTG-XXXX

23kV 4-way 3-phase - Three Source Switches, One Fused Tap

39"

991mm

48"

1,219mm 22"

559mm

810lb

367kg

ESV314-TPPP-XXXX

15kV 4-way 3-phase - One Source Switch, Three Vacuum Interrupter Taps

40"

1,016mm

48"

1,219mm 22"

559mm

880lb

399kg

ESV324-TPPP-XXXX

27kV 4-way 3-phase - One Source Switch, Three Vacuum Interrupter Taps

40"

1,016mm

48"

1,219mm 22"

559mm

880lb

399kg

ESV314-TTPP-XXXX

15kV 4-way 3-phase - Two Source Switches, Two Vacuum Interrupter Taps

40"

1,016mm

48"

1,219mm 22"

559mm

880lb

399kg

ESV324-TTPP-XXXX

27kV 4-way 3-phase - Two Source Switches, Two Vacuum Interrupter Taps

40"

1,016mm

48"

1,219mm 22"

559mm

880lb

399kg

ESV314-TTTP-XXXX

15kV 4-way 3-phase - Three Source Switches, One Vacuum Interrupter Tap

40"

1,016mm

48"

1,219mm 22"

559mm

880lb

399kg

ESV324-TTTP-XXXX

27kV 4-way 3-phase - Three Source Switches, One Vacuum Interrupter Tap

40"

1,016mm

48"

1,219mm 22"

559mm

880lb

399kg

PMVI1-21-15-XX

15kV 2-way 1-phase Interrupter

36"

914mm

30"

762mm

30"

762mm

310lb

141kg

PMVI1-21-27-XX

27kV 2-way 1-phase Interrupter

36"

914mm

30"

762mm

30"

762mm

310lb

141kg

PMVI1-21-38-XX

38kV 2-way 1-phase Interrupter

36"

914mm

30"

762mm

30"

762mm

310lb

141kg

PMVI1-21-15-XX-3YY

15kV 2-way 3-phase Interrupter - 1-phase Trip Selectable - Ext. Control

48"

1,219mm

42"

1,067mm 30"

762mm

680lb

308kg

PMVI1-21-27-XX-3YY

27kV 2-way 3-phase Interrupter - 1-phase Trip Selectable - Ext. Control

48"

1,219mm

42"

1,067mm 30"

762mm

680lb

308kg

PMVI1-21-38-XX-3YY

38kV 2-way 3-phase Interrupter - 1-phase Trip Selectable - Ext. Control

48"

1,219mm

42"

1,067mm 30"

762mm

680lb

308kg

ESD312-E-XX

8.3kV 2-way 3-phase - One Fused Tap

36"

914mm

48"

1,219mm 42"

1,067mm

610lb

277kg

ESD322-F-XX

15kV 2-way 3-phase - One Fused Tap

36"

914mm

48"

1,219mm 42"

1,067mm

610lb

277kg

ESD332-G-XX

23kV 2-way 3-phase - One Fused Tap

36"

914mm

48"

1,219mm 42"

1,067mm

610lb

277kg

PADMOUNT

28

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Ordering Information
TABLE 4 ordering information for Overcurrent protection switchgear (continued)
Diagram Catalog Number

Width

Description

Height

Depth

Weight

ESD312-P-XX

15kV 2-way 3-phase - One Vacuum Interrupter Tap

36"

914mm

48" 1,219mm 42"

1,067mm

680lb

308kg

ESD322-P-XX

27kV 2-way 3-phase - One Vacuum Interrupter Tap

36"

914mm

48" 1,219mm 42"

1,067mm

680lb

308kg

ESD332-P-XX

38kV 2-way 3-phase - One Vacuum Interrupter Tap

36"

914mm

48" 1,219mm 42"

1,067mm

680lb

308kg

ESD312-TE-XX

8.3kV 2-way 3-phase - One Source Switch, One Fused Tap

36"

914mm

48" 1,219mm 42"

1,067mm

750lb

340kg

ESD322-TF-XX

15kV 2-way 3-phase - One Source Switch, One Fused Tap

36"

914mm

48" 1,219mm 42"

1,067mm

750lb

340kg

ESD332-TG-XX

23kV 2-way 3-phase - One Source Switch, One Fused Tap

36"

914mm

48" 1,219mm 42"

1,067mm

750lb

340kg

ESD313-TEE-XXX

8.3kV 3-way 3-phase - One Source Switch, Two Fused Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1050lb 476kg

ESD323-TFF-XXX

15kV 3-way 3-phase - One Source Switch, Two Fused Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1050lb 476kg

ESD333-TGG-XXX

23kV 3-way 3-phase - One Source Switch, Two Fused Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1050lb 476kg

ESD313-TTE-XXX

8.3kV 3-way 3-phase - Two Source Switches, One Fused Tap

54" 1,372mm 48" 1,219mm 54"

1,372mm

1050lb 476kg

ESD323-TTF-XXX

15kV 3-way 3-phase - Two Source Switches, One Fused Tap

54" 1,372mm 48" 1,219mm 54"

1,372mm

1050lb 476kg

ESD333-TTG-XXX

23kV 3-way 3-phase - Two Source Switches, One Fused Tap

54" 1,372mm 48" 1,219mm 54"

1,372mm

1050lb 476kg

ESD313-TPP-XXX

15kV 3-way 3-phase - One Source Switch, Two Vacuum Interrupter Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1160lb 526kg

ESD323-TPP-XXX

27kV 3-way 3-phase - One Source Switch, Two Vacuum Interrupter Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1160lb 526kg

ESD333-TPP-XXX

38kV 3-way 3-phase - One Source Switch, Two Vacuum Interrupter Taps

72" 1,829mm 54" 1,372mm 72"

1,829mm

1500lb 680kg

ESD313-TTP-XXX

15kV 3-way 3-phase - Two Source Switches, One Vacuum Interrupter Tap

54" 1,372mm 48" 1,219mm 54"

1,372mm

1160lb 526kg

ESD323-TTP-XXX

27kV 3-way 3-phase - Two Source Switches, One Vacuum Interrupter Tap

54" 1,372mm 48" 1,219mm 54"

1,372mm

1160lb 526kg

ESD333-TTP-XXX

38kV 3-way 3-phase - Two Source Switches, One Vacuum Interrupter Tap

72" 1,829mm 54" 1,372mm 72"

1,829mm

1500lb 680kg

ESD314-TEEE-XXXX

8.3kV 4-way 3-phase - One Source Switch, Three Fused Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1170lb 531kg

ESD324-TFFF-XXXX

15kV 4-way 3-phase - One Source Switch, Three Fused Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1170lb 531kg

ESD334-TGGG-XXXX

23kV 4-way 3-phase - One Source Switch, Three Fused Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1170lb 531kg

ESD314-TTEE-XXXX

8.3kV 4-way 3-phase - Two Source Switches, Two Fused Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1240lb 562kg

ESD324-TTFF-XXXX

15kV 4-way 3-phase - Two Source Switches, Two Fused Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1240lb 562kg

ESD334-TTGG-XXXX

23kV 4-way 3-phase - Two Source Switches, Two Fused Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1240lb 562kg

ESD314-TTTE-XXXX

8.3kV 4-way 3-phase - Three Source Switches, One Fused Tap

54" 1,372mm 48" 1,219mm 54"

1,372mm

1310lb 594kg

ESD324-TTTF-XXXX

15kV 4-way 3-phase - Three Source Switches, One Fused Tap

54" 1,372mm 48" 1,219mm 54"

1,372mm

1310lb 594kg

ESD334-TTTG-XXXX

23kV 4-way 3-phase - Three Source Switches, One Fused Tap

54" 1,372mm 48" 1,219mm 54"

1,372mm

1310lb 594kg

ESD314-TPPP-XXXX

15kV 4-way 3-phase - One Source Switch, Three Vacuum Interrupter Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1380lb 626kg

ESD324-TPPP-XXXX

27kV 4-way 3-phase - One Source Switch, Three Vacuum Interrupter Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1380lb 626kg

ESD334-TPPP-XXXX

38kV 4-way 3-phase - One Source Switch, Three Vacuum Interrupter Taps

72" 1,829mm 54" 1,372mm 72"

1,829mm

1500lb 680kg

ESD314-TTPP-XXXX

15kV 4-way 3-phase - Two Source Switches,


Two Vacuum Interrupter Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1380lb 626kg

ESD324-TTPP-XXXX

27kV 4-way 3-phase - Two Source Switches, Two Vacuum Interrupter Taps

54" 1,372mm 48" 1,219mm 54"

1,372mm

1380lb 626kg

ESD334-TTPP-XXXX

38kV 4-way 3-phase - Two Source Switches, Two Vacuum Interrupter Taps

72" 1,829mm 54" 1,372mm 72"

1,829mm

1500lb 680kg

ESD314-TTTP-XXXX

15kV 4-way 3-phase - Three Source Switches,


One Vacuum Interrupter Tap

54" 1,372mm 48" 1,219mm 54"

1,372mm

1380lb 626kg

ESD324-TTTP-XXXX

27kV 4-way 3-phase - Three Source Switches,


One Vacuum Interrupter Tap

54" 1,372mm 48" 1,219mm 54"

1,372mm

1380lb 626kg

ESD334-TTTP-XXXX

38kV 4-way 3-phase - Three Source Switches,


One Vacuum Interrupter Tap

72" 1,829mm 54" 1,372mm 72"

1,829mm

1500lb 680kg

NOTE: Consult your local representative on 38kV Multi-Way configurations.

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

29

Underground
Distribution Switchgear

PADMOUNT (continued)

PROTECTION AND CONTROL


Ordering Information
TABLE 5 ordering information for automatic source transfer Packages
Underground
Distribution Switchgear

Diagram Catalog Number

Width

Description

Depth

Height

Weight

SUBSURFACE (2-MVS3 interconnected with multi-point junctions. For wall/floor mounting.)

**

**

ATS312-AA-XX

15kV 2-way 3-phase - Two Source Switches,


Customer Connected Tap

21"

533mm

19"

483mm

26"

660mm

60lb

27kg

ATS322-AA-XX

25kV 2-way 3-phase - Two Source Switches,


Customer Connected Tap

21"

533mm

19"

483mm

26"

660mm

60lb

27kg

ATS313-AAB-XXX

15kV 3-way 3-phase - Two Source Switches, One Solid Tap

22"

559mm

79"

2,007mm

21"

533mm

300lb

136kg

ATS323-AAB-XXX

25kV 3-way 3-phase - Two Source Switches, One Solid Tap

22"

559mm

79"

2,007mm

21"

533mm

300lb

136kg

ATS314-AABB-XXXX

15kV 4-way 3-phase - Two Source Switches, Two Solid Taps

22"

559mm

79"

2,007mm

21"

533mm

300lb

136kg

ATS324-AABB-XXXX

25kV 4-way 3-phase - Two Source Switches, Two Solid Taps

22"

559mm

79"

2,007mm

21"

533mm

300lb

136kg

ATS313-AAP-XXX

15kV 3-way 3-phase - Two Source Switches,


One Vacuum Interrupter Tap

22"

559mm

79"

2,007mm

21"

533mm

450lb

204kg

ATS323-AAP-XXX

25kV 3-way 3-phase - Two Source Switches,


One Vacuum Interrupter Tap

22"

559mm

79"

2,007mm

21"

533mm

450lb

204kg

ATS314-AAPP-XXXX

15kV 4-way 3-phase - Two Source Switches,


Two Vacuum Interrupter Taps

22"

559mm

79"

2,007mm

21"

533mm

600lb

272kg

ATS324-AAPP-XXXX

25kV 4-way 3-phase - Two Source Switches,


Two Vacuum Interrupter Taps

22"

559mm

79"

2,007mm

21"

533mm

600lb

272kg

VAULT (All ways mounted onto a common bus and supported by a free-standing frame. For floor mounting.)
ATV313-AAB-XXX

15kV 3-way 3-phase - Two Source Switches, One Solid Tap

48" 1,219mm 36"

914mm

22"

559mm

620lb

281kg

ATV323-AAB-XXX

25kV 3-way 3-phase - Two Source Switches, One Solid Tap

48" 1,219mm 36"

914mm

22"

559mm

620lb

281kg

ATV313-AAP-XXX

15kV 3-way 3-phase - Two Source Switches,


One Vacuum Interrupter Tap

48" 1,219mm 36"

914mm

22"

559mm

750lb

340kg

ATV323-AAP-XXX

25kV 3-way 3-phase - Two Source Switches,


One Vacuum Interrupter Tap

48" 1,219mm 36"

914mm

22"

559mm

750lb

340kg

ATV314-AAPP-XXXX

15kV 4-way 3-phase - Two Source Switches,


Two Vacuum Interrupter Taps

48" 1,219mm 36"

914mm

22"

559mm

880lb

399kg

ATV324-AAPP-XXXX

25kV 4-way 3-phase - Two Source Switches,


Two Vacuum Interrupter Taps

48" 1,219mm 36"

914mm

22"

559mm

880lb

399kg

ATD313-AAP-XXX

15kV 3-way 3-phase - Two Source Switches,


One Vacuum Interrupter Tap

54" 1,317mm 48"

1,220mm

54" 1,317mm 1160lb 526kg

ATD323-AAP-XXX

25kV 3-way 3-phase - Two Source Switches,


One Vacuum Interrupter Tap

54" 1,317mm 48"

1,220mm

54" 1,317mm 1160lb 526kg

ATD314-AAPP-XXXX

15kV 4-way 3-phase - Two Source Switches,


Two Vacuum Interrupter Taps

54" 1,317mm 48"

1,220mm

54" 1,317mm 1380lb 626kg

ATD324-AAPP-XXXX

25kV 4-way 3-phase - Two Source Switches,


Two Vacuum Interrupter Taps

54" 1,317mm 48"

1,220mm

54" 1,317mm 1380lb 626kg

PADMOUNT

NOTES:
X=6 for 600 amp or 2 for 200 amp
Other configurations are available. Please consult your local representative on configurations not shown here.
* Dimensions for one switch
** Dimensions for 2-MVS3 interconnected with Multi-Point Junctions. MVIs are mounted elsewhere in the vault.

30

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Product Application

Fault Indicators
Thomas & Betts Elastimold Fault Indicators aid
in the location and isolation of the faulted cable
or equipment in overhead and underground
distribution systems through 35kV (L-G). This
product guide details the different types of
faulted circuit indicators, voltage indicators and
phase indicators. With a complete line of elbow
test point mount and cable mount indicators,
you will find the best product to meet your
systems performance needs.
CABLE
FAULT

OPEN
POINT

T1
T
1

T2
T
2

T3
T
3

TT4
4

T5
T
5

T6
T
6

TT7
7

UNDERGROUND LOOP CIRCUIT WITH ELBOW CONNECTED TRANSFORMERS T1 THRU T7


FAULTED CIRCUIT

UNFAULTED CIRCUIT

INDICATOR SHOWING
FAULTED CIRCUIT DISPLAY

INDICATOR SHOWING
NORMAL CIRCUIT DISPLAY

Fault Indicators reduce outage duration


by quickly pinpointing the location of the
fault. As shown in the circuit diagram,
the fault is located between the last tripped
indicator and the first untripped indicator.
Once identified, this section is switched
to become the new open point, allowing
full service restoration to the rest of the
customers during repairs.

False tripping occurs when the indicator trips due


to high currents that are feeding the fault from
a down line location (e.g. from capacitor banks).
TPMVOL or OLMVOL indicators will not false trip.
After the fault occurs, the indicator located beyond
the fault has no voltage running through it, which
prevents any operation of the indicator even if the
backfed current is above the trip setting.
False resetting occurs when an indicator that has
tripped due to a single-phase fault detects voltage
from the unfaulted phases (e.g. delta-connected
load). This voltage could be enough to reset the
indicator. TPMVOL and OLMVOL indicators will
not false reset. These indicators reset based on
time, so even if backfed voltage is available, the
indicators will not reset.

benefit/description

Feature
AccQTrip Off the Trip logic circuitry

Prevents false tripping due to transient current surges or system overloading.

AccQClamp self-adjusting mounting provision

No need for customer to specify cable O.D. when ordering cable mount FCIs. The
AccQClamp maintains 10% trip accuracy over the entire clamping range (.4"-2.2"),
and is composed of U.V. stable polycarbonate, stainless steel reinforced materials.

Voltage reset fault indicators


Eliminate false resetting and false tripping. Ideal for use on lightly loaded circuits
where sufficient current may not be available to reliably energize a current reset type
fault indicator. Automatic reset upon restoration of system voltage and/or time reset
after four hours.

High/low trip setting selection

Coordinates FCIs with current-limiting fuses. No minimum load current requirements


and no load surveys needed.

Inrush restraint circuitry

Coordinates FCIs with circuit breaker or auto-recloser operation, avoiding


misindication due to inrush currents.

Internal adjacent phase shielding

Prevents electro-magnetic interference from adjacent phase conductors.

1 ms trip response time

Coordinates FCIs with current-limiting fuses and other protective devices.

No false trips due to back feed

Voltage operated time reset indicators will not trip or reset due to current backfeed

Quality manufacturing processes

Manufactured using state-of-the-art surface mount technology and premium quality


electronic components for the highest degree of performance and reliability. All fault
indicators meet or exceed ANSI/IEEE Standard 495-1986.

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

31

Fault Indicators

BLOWN FUSE
AT RISER POLE

Backfeed Prevention Using Fault Indicators


One concern, especially on three-phase
installations of fault indicators, is causing a false
trip or a false reset operation on the indicator due
to current flowing through the cable into the fault.
This current can be in the opposite direction to
the fault current and cause a false trip or reset
on indicators.

PROTECTION AND CONTROL


Product Application

Faulted Circuit Operation


t1 Fault Indicator is connected to the
system and powers up. At 5kV, this takes
3 minutes in the case of the test point
mounted unit and 6 minutes in the case
of the overhead type unit. At higher
voltages the power up time is shorter.

Fault Indicators

t2 Fault current is detected. Fault


Indicator is Armed after 1ms. Fault
Indicator display shows Normal.
t3 Breaker/recloser locks out and
voltage drops.
t4 Voltage is lost. A 30-second time
window allows for the protective device
to clear the fault and reclose. Indicator
changes state.

Inrush Restraint Operation


t1 Fault Indicator is connected to the
system and powers up. At 5kV, this takes
3 minutes in the case of the test point
mounted unit and 6 minutes in the case
of the overhead type unit. At higher
voltages the power up time is shorter.
t1 - t2 Upline recloser / breaker operation
due to fault on another phase. After
100ms (t2) the Fault Indicator is disabled
because there is no fault current
detected.
t3 Recloser closes back. Voltage is back
to normal. Unfaulted phases see Inrush.
No change in the Fault Indicator display.

Overloading Operation
t1 Fault Indicator is connected to the
system and powers up. At 5kV, this takes
3 minutes in the case of the test point
mounted unit and 6 minutes in the case
of the overhead type unit. At higher
voltages the power up time is shorter.

faulted circuit operation


(1 ms Trip Response)

(30 second window)

System
Voltage

Primary
Current

Fault
Indicator
Status

Fault
Indicator
Display
Status

Inrush restraint operation

System
Voltage

Primary
Current

Fault
Indicator
Status
Fault
Indicator
Display
Status

overloading operation

System
Voltage

Primary
Current

t2 Device downline from Fault Indicator


switches creating an overload. Fault
Indicator is Armed after 1ms. Fault
Indicator display shows Normal.

Fault
Indicator
Status

t3 Overload condition over. Fault


Indicator does not change state.

Fault
Indicator
Display
Status

t4 After 30 seconds Fault Indicator goes


back to initialized state.

32

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Test Point Mounted

Test Point Mounted

TPM Series Standard Features


AccQTrip Logic Circuitry In voltage reset
units prevents false indications due to inrush
currents, cold load pickup and overloading.

TPMVF
Model

High/Low Trip Setting Selection No minimum


load current requirement and no load surveys
needed.
Internal Magnetic Shielding Prevents adjacent
phase effects.

Fault Indicators

Trip Response .001 Seconds Coordinates


with current-limiting fuses, as well as other
protection devices.
Magnetically Latched Flag Indication Flag
indication will not change state due to shock
or vibration.
Lightweight, Compact and Sealed

Test Point Mounted Fault Indicators provide


a clear, visual means for locating faulted cables
and equipment on underground distribution
systems. Indicators are self-powered and
consist of a solid state current sensor connected
to a faulted circuit display. Designs incorporate
advanced circuit logic, monitoring system
protection operation and preventing indicator
tripping unless an overcurrent condition is
followed by a loss of system voltage. Trip and
reset operations are automatic and the same
indicator may be used for 5kV thru 35kV
applications.
Units are designed to mount directly to 200
& 600 amp elbows, splices and other cable
accessory components equipped with IEEE
386 Standard capacitive test points. Indicators
include a universal mounting provision
allowing installation on test point products
as manufactured by Elastimold and others.

TPMVL/TPMVOL
Model

Basic Operation
A faulted circuit produces an associated
magnetic field which closes a reed switch in
the indicator resulting in a tripped display.
Trip response occurs in .001 seconds allowing
the fault indicator to properly coordinate
with all types of circuit protection schemes
including current-limiting fuses.
To eliminate confusing false trips, voltage
reset indicators are equipped with inrush,
backfeed, overload and cold load pickup
restraint circuitry as standard. Current
sensors are constructed with internal
shielding to prevent inadvertent tripping
when located in close proximity to
adjacent phases, such as junction
mounted applications.

Designs feature compact, shielded and sealed,


corrosion-resistant construction. The indicator
is enclosed in a rugged, impact-resistant Lexan
housing and includes an EPDM molded rubber,
test point mounting boot. A built-in pulling eye
allows for easy hotstick installation and removal
of the indicator from the test point.

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

33

PROTECTION AND CONTROL


Test Point Mounted

Test Point Mounted


Specifications for TPM Voltage Reset,
Flag Display: Model TPMVf4

Fault Indicators

Specifications for TPM Voltage operated,


Time reset, led Display: Model TPMVol4
Nominal Voltage

4.16-60kV (L-L)

Nominal Voltage

4.16-60kV (L-L)

Nominal Trip Ratings

Low, 400 Amp; High, 800 Amp

Nominal Trip Ratings

Low, 400 Amp; High, 800 Amp

Trip Response Time

1mS

Trip Response Time

1mS

Fault-Clearing Time1

.001 30 Seconds Subsequent to Arming

Fault Clearing Time1

.001 30 Seconds Subsequent to Arming

Maximum Surge Level

25kA 10 Cycles 60 Hz

Maximum Surge Level

25kA 10 Cycles 60 Hz

Effect of Adjacent Phase

Internal Shielding Prevents Adjacent Phase Effects

Effect of Adjacent Phase

Inrush/Backfeed Restraint

100mS (Disable Delay)

Internal Shielding Prevents Adjacent


Phase Effects

Load Current Requirements

None

Inrush Restraint Response

100mS (Disable Delay)

Power Up Requirement

3 Minutes @ 5kV

Load Current Requirements

None

Display Type

Flashing Super Bright LED

Display Type

Mechanical Flag

Flash Rate

30 Flashes per Minute

Minimum Reset Voltage

5kV (Beginning Initializing Sequence)

LED Display Time

4 Hour Standard

Voltage Reset Time

3 Minutes @ 5kV

Reset Time

4 Hour-Standard (longer times available upon request)

Power Source

Volt Test Point Powered

Power Source3

3.6 Volt Lithium Thyonil Chloride Battery

Temperature Range

-40C to +85C

Battery Capacity

2.4 Ah

Housing Material

Mounting Boot EPDM Conductive Rubber Housing


Body UV Stabilized Polycarbonate Polymer

Battery Operating Life

1200 Flash Hours Minimum

Weight

258 Grams

Battery Storage Life

15-20 Years

Temperature Range

-40C to +85C

Housing Material

Mounting Boot EPDM Conductive Rubber


Housing Body UV Stabilized Polycarbonate Polymer

Weight

258 Grams

Specifications for TPM Voltage Reset,


led Display: Model TPMVL4

Specifications for TPM TIME Reset,


led Display: Model TPMTL2, 4

Nominal Voltage

4.16-60kV (L-L)

Nominal Voltage

4.16-60kV (L-L)

Nominal Trip Ratings

Low, 400 Amp; High, 800 Amp

Nominal Trip Ratings

Low, 400 Amp; High, 800 Amp

Trip Response Time

1mS

Trip Response Time

1mS

Fault-Clearing Time1

.001 30 Seconds Subsequent to Arming

Maximum Surge Level

25kA 10 Cycles 60 Hz

Maximum Surge Level

25kA 10 Cycles 60 Hz

Effect of Adjacent Phase

Internal Shielding Prevents Adjacent Phase Effects

Effect of Adjacent Phase

Internal Shielding Prevents Adjacent Phase Effects

Power Up Requirement

None

Inrush Restraint Response

100mS (Disable Delay)

Display Type

Flashing Super Bright LED

Load Current Requirements

None

Flash Rate

30 Flashes per Minute

Power Up Requirement

3 Minutes @ 5kV

Reset Time

Display Type

Flashing Super Bright LED

Power Source

3.6 Volt Lithium Thyonil Chloride Battery

Flash Rate

30 Flashes per Minute

Battery Capacity

2.4 Ah

LED Display Time

4 Hour Standard

Battery Operating Life

1200 Flash Hours Minimum

Voltage Reset Time

3 Minutes @ 5kV

Battery Storage Life

15-20 Years

Power Source3

3.6 Volt Lithium Thyonil Chloride Battery

Temperature Range

-40C to +85C

Battery Capacity

2.4 Ah

Housing Material

Battery Operating Life

1200 Flash Hours Minimum

Mounting Boot EPDM Conductive Rubber


Housing Body UV Stabilized Polycarbonate Polymer

Battery Storage Life

15-20 Years

Weight

258 Grams

Temperature Range

-40C to +85C

Housing Material

Mounting Boot EPDM Conductive Rubber


Housing Body UV Stabilized Polycarbonate Polymer

Weight

258 Grams

NOTES:
1) Prevents false trips due to short time interruptions without loss of voltage.
2) Inrush restraint is standard on voltage reset models. It is not available
on time reset models.
3) Battery powers LED and it is active only when LED is ON. Lithium
Thyonil Chloride batteries provide accurate indication throughout the
entire temperature range.
4) Certified per ANSI/IEEE Standard 495-1986.

34

4 Hour Standard
3

Test Point
Provision
for Hotstick
Installation
and Removal

Test Point
Mounting Provision

Faulted Circuit
Display

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Test Point Mounted
trip point vs. cable diameter

conductor current

current in k amps

time/current curve for TPMVF, vl,VOL,tl

Time in Seconds

cable diameter

Fault Indicators

dimensions
3 7/8"
98 mm

2 1/4"
57 mm
1 1/8" 29 mm
1 /8" 35 mm
3

3 1/4"
83 mm

ORDERING INFORMATION

Catalog prefix
Catalog
Number

Description

Reset Operation

TPMTL

Time Reset with LED Display

Indicator auto-resets to normal after a four hour time


duration. Indicator may also be manually reset using an
FTT test tool.

TPMVF

Voltage Reset with Flag Display

Indicator auto-resets to normal after system voltage restoration. Reset requires 5kV minimum voltage to operate.
Reset operation time is proportional to system voltage.

TPMVL

Voltage Reset with LED Display

Example: at 15kV, reset occurs 30 seconds after system


voltage restoration.

TPMVOL

Voltage Operated, Time Reset,


LED display

Indicator auto-resets after a four hour time period.


Longer time resets are available upon request.

Catalog Suffix
Catalog
Number

PG-PC-E-0907

LT

All fused taps use LOW trip rating.


For 200 amp. URD applications, use LOW trip rating.

HT

For 600 amp. URD applications, use HIGH trip rating.

NOTE: For overhead bulk feeder applications, use HIGH or LOW trip ratings (whichever is greater than the minimum

Description

pickup setting of the related protection device).

AccQTrip and AccQClamp are trademarks of Quality Indications, Inc.

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

35

PROTECTION AND CONTROL


Underground Clamp Type

Underground Clamp Type

UCM Series Standard Features


AccQClamp Mounting Provision Universal
one-size-fits-all design automatically adjusts.
High/Low Trip Setting Selection No minimum
load current requirement and no load surveys
needed.

Fault Indicators

Trip Response .001 Seconds Coordinates


with current-limiting fuses, as well as other
protection devices.
Internal Magnetic Shielding Prevents adjacent
phase effects.

UCMTL
Model

URD Cable Mounted Fault Indicators aid in


locating faulted cables and equipment on
underground distribution systems. Indicators
are self-powered and consist of a solid state
current sensor connected to faulted circuit
display.
Units are designed for direct installation to an
underground power cable using a spring loaded,
over center toggle clamp mounting provision.
The clamp accommodates cables ranging
from .4 to 2.2 inches in diameter and includes
retainer pads to prevent slip and twist. The
clamp positions the cable conductor at a
constant distance from the current sensor,
maintaining indicator trip accuracy over the
entire range of cable sizes.
Designs feature compact, shielded and sealed,
corrosion resistant construction. The indicator
is enclosed in a durable, impact resistant
Lexan housing and includes a built-in pulling
eye for easy hotstick installation and removal
from the cable.

Basic Operation
A faulted circuit produces an associated
magnetic field which closes a reed switch in
the indicator resulting in a tripped display.
Trip response occurs in .001 seconds allowing
the fault indicator to properly coordinate with
all types of circuit protection schemes including
current-limiting fuses.
URD cable mounted fault indicators are
constructed with an internally shielded current
sensor that prevents inadvertent tripping when
located in close proximity to adjacent phases,
such as junction mounted applications.

36

Spring Loaded
Mounting Clamps

Provision for Hotstick


Installation and Removal

Faulted Circuit Display

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Underground Clamp Type
Specifications for UCM TIME Reset,
led Display: Model UCMTL2
4.16-60kV (L-L)

Nominal Trip Ratings

Low, 400 Amp; High, 800 Amp

Trip Response Time

1mS

Maximum Surge Level

25kA 10 Cycles 60 Hz

Effect of Adjacent Phase

Internal Shielding Prevents Adjacent Phase Effects

Display Type

Flashing Super Bright LED

Flash Rate

30 Flashes per Minute

Reset Time

4 Hour - Standard

Power Source1

3.6 Volt Lithium Thyonil Chloride Battery

Battery Capacity

2.4 Ah

Battery Operating Life

1200 Flash Hours Minimum

Battery Storage Life

15-20 Years

Temperature Range

-40C to +85C

Housing Material

Mounting Boot EPDM Conductive Rubber


Housing Body UV Stabilized Polycarbonate Polymer

Weight

258 Grams

Fault Indicators

Nominal Voltage

NOTES:
1) Battery powers LED and it is active only when LED is ON.
Lithium Thyonil Chloride batteries provide accurate indication
throughout the entire temperature range.
2) Certified per ANSI/IEEE Standard 495-1986.

TYPICAL INSTALLATION
As shown below, proper installation of URD cable mounted fault
indicators requires routing cable neutral wires to prevent the ground
return from affecting trip accuracy. Similar procedures should be
followed for tape, wire, LC or other types of shielded cable constructions.
Install Fault Indicator in Area Shown

Fig. 1

* Recommended

Fig. 2

Fig. 3

Fig. 4
INCORRECT

Do not install indicator directly over the concentric neutral to avoid


misindication (Fig. 4).

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

37

PROTECTION AND CONTROL


Underground Clamp Type

Underground Clamp Type


trip point vs. cable diameter

current in k amps

conductor current

time/current curve for UCMTL

Fault Indicators

Time in Seconds

cable diameter

dimensions
4 1/4"
108 mm
open
2 1/4"
57 mm

3 7/8"
98 mm
1 1/8" 29 mm
1 3/8" 35 mm

2 3/8"
60 mm
open

4 1/4"
108 mm

5 5/8"
143 mm
open

ORDERING INFORMATION

Catalog prefix
Catalog
Number

Description

Reset Operation

UCMTL

Time Reset with LED Display

Indicator auto-resets to normal after a four hour time


duration. Indicator may also be manually reset using
an FTT test tool.

Catalog Suffix
Catalog
Number

38

LT

All fused taps use LOW trip rating.


For 200 amp circuits. URD applications, use LOW trip rating.

HT

For 600 amp circuits. URD applications, use HIGH trip rating.

NOTE: For overhead bulk feeder applications, use HIGH or LOW trip ratings (whichever is greater than the minimum

Description

pickup setting of the related protection device).

AccQTrip and AccQClamp are trademarks of Quality Indications, Inc.

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Overhead Line Mounted

OLM Standard Features


AccQTrip Logic Circuitry In voltage reset
units prevents false indications due to inrush
currents, cold load pickup and overloading.

OLMVF
Model

AccQClamp Mounting Provision Universal


one-size-fits-all design automatically adjusts.
High/Low Trip Setting Selection No minimum
load current requirement and no load surveys
needed.
Fault Indicators

Trip Response .001 Seconds Coordinates


with current-limiting fuses, as well as other
protection devices.
Internal Magnetic Shielding Prevents adjacent
phase effects.
Magnetically Latched Flag Indication Flag
Indication will not change states due to
shock or vibration.
Lightweight, Compact and Sealed

OLMVL
OLMVOL
Model

Overhead Line Fault Indicators aid in


locating faulted circuits and equipment on
overhead distribution systems. Indicators
are self-powered and consist of a solid state
current sensor connected to a faulted circuit
display. Designs incorporate advanced circuit
logic, monitoring system protection operation
and prevent indicator tripping unless an
overcurrent condition is followed by a loss of
system voltage. Trip and reset operations are
automatic and the same indicator may be used
for 5kV thru 35kV line-to-ground applications.
Units are designed for direct installation to
the overhead line using a spring loaded, over
center, toggle clamp mounting provision. The
clamp accommodates conductors ranging
from .4 to 2.2 inches in diameter and includes
retainer pads to prevent slip and twist. The
clamp positions the conductor at a constant
distance from the current sensor, maintaining
indicator trip accuracy over the entire range
of conductors. Designs are compact, sealed
and corrosion resistant.

PG-PC-E-0907

OLMtL-Lt
Model

Basic Operation
A faulted circuit produces an associated
magnetic field which closes a reed switch
in the indicator resulting in a tripped
display. Trip response occurs in .001
seconds allowing the fault indicator to
properly coordinate with all types of circuit
protection schemes including currentlimiting fuses.
To eliminate confusing false trips, indicators
are equipped with inrush, overload and cold
load pick up restraint circuitry as standard.
Current sensors are constructed with
internal shielding to prevent inadvertent
tripping when located in close proximity
to adjacent phases.

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

39

PROTECTION AND CONTROL


Overhead Line Mounted

Fault Indicators

Specifications for OLM Voltage operated,


Time reset, led Display: Model OLMVOL4

Specifications for OLM Voltage Reset,


Flag Display: Model OLMVF4

Nominal Voltage

4.16-60kV (L-L)

Nominal Voltage

4.16-60kV (L-L)

Nominal Trip Ratings

Low, 400 Amp; High, 800 Amp

Nominal Trip Ratings

Low, 400 Amp; High, 800 Amp

Trip Response Time

1mS

Trip Response Time

1mS

Fault Clearing Time1

.001 30 Seconds Subsequent to Arming

Fault-Clearing Time1

.001 30 Seconds Subsequent to Arming

Maximum Surge Level

25kA 10 Cycles 60 Hz

Maximum Surge Level

25kA 10 Cycles 60 Hz

Effect of Adjacent Phase

Internal Shielding Prevents Adjacent Phase Effects

Effect of Adjacent Phase

Inrush/Backfeed Restraint

100mS (Disable Delay)

Internal Shielding Prevents Adjacent


Phase Effects

Load Current Requirements

None

Inrush Restraint Response

100mS (Disable Delay)

Power Up Requirement

6 Minutes @ 5kV

Load Current Requirements

None

Display Type

Flashing Super Bright LED

Display Type

Mechanical Flag

Flash Rate

30 Flashes per Minute

Minimum Reset Voltage

5kV (Beginning Initializing Sequence)

LED Display Time

4 Hour Standard

Voltage Reset Time

6 Minutes @ 5kV

Reset Time

4 Hour-Standard (longer times available upon request)

Power Source

Volt Test Point Powered

Power Source3

3.6 Volt Lithium Thyonil Chloride Battery

Temperature Range

-40C to +85C

Battery Capacity

2.4 Ah

Housing Material

Mounting Boot EPDM Conductive Rubber Housing


Body UV Stabilized Polycarbonate Polymer

Battery Operating Life

1200 Flash Hours Minimum

Weight

258 Grams

Battery Storage Life

15-20 Years

Temperature Range

-40C to +85C

Housing Material

Mounting Boot EPDM Conductive Rubber


Housing Body UV Stabilized Polycarbonate Polymer

Weight

258 Grams

Specifications for OLM Voltage Reset,


led Display: Model OLMVL4

Specifications for OLM TIMe Reset,


led Display: Model OLMTL2, 4

Nominal Voltage

4.16-60kV (L-L)

Nominal Voltage

4.16-60kV (L-L)

Nominal Trip Ratings

Low, 400 Amp; High, 800 Amp

Nominal Trip Ratings

Low, 400 Amp; High, 800 Amp

Trip Response Time

1mS

Trip Response Time

1mS

Fault Clearing Time

.001 30 Seconds Subsequent to Arming

Maximum Surge Level

25kA 10 Cycles 60 Hz

Maximum Surge Level

25kA 10 Cycles 60 Hz

Effect of Adjacent Phase

Internal Shielding Prevents Adjacent Phase Effects

Effect of Adjacent Phase

Internal Shielding Prevents Adjacent Phase Effects

Power Up Requirement

None

Inrush Restraint Response

100mS (Disable Delay)

Display Type

Flashing Super Bright LED

Load Current Requirements

None

Flash Rate

30 Flashes per Minute

Power Up Requirement

6 Minutes @ 5kV

Reset Time

4 Hour Standard

Display Type

Flashing Super Bright LED

Power Source3

3.6 Volt Lithium Thyonil Chloride Battery

Flash Rate

30 Flashes per Minute

Battery Capacity

2.4 Ah

LED Display Time

4 Hour Standard

Battery Operating Life

1200 Flash Hours Minimum

Voltage Reset Time

6 Minutes @ 5kV

Battery Storage Life

15-20 Years

Power Source3

3.6 Volt Lithium Thyonil Chloride Battery

Temperature Range

-40C to +85C

Battery Capacity

2.4 Ah

Housing Material

Battery Operating Life

1200 Flash Hours Minimum

Mounting Boot EPDM Conductive Rubber


Housing Body UV Stabilized Polycarbonate Polymer

Battery Storage Life

15-20 Years

Weight

258 Grams

Temperature Range

-40C to +85C

Housing Material

Mounting Boot EPDM Conductive Rubber


Housing Body UV Stabilized Polycarbonate Polymer

Weight

258 Grams

NOTES:
1) Prevents false trips due to short time interruptions without loss of voltage.
2) Inrush restraint is standard on voltage reset models. It is not available
on time reset models.
3) Battery powers LED and it is active only when LED is ON. Lithium
Thyonil Chloride batteries provide accurate indication throughout the
entire temperature range.
4) Certified per ANSI/IEEE Standard 495-1986.

40

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Overhead Line Mounted
trip point vs. cable diameter

conductor current

current in k amps

time/current curve for OLMVF,VL,VOL,TL

cable diameter

Time in Seconds

Fault Indicators

dimensions
4 1/4"
108 mm
open
2 1/4"
57 mm

3 7/8"
98 mm
1 1/8" 29 mm
1 3/8" 35 mm

2 3/8"
60 mm
open

4 /4"
108 mm
1

5 5/8"
143 mm
open

ORDERING INFORMATION
Catalog prefix
Catalog
Number

Description

Reset Operation

OLMTL

Time Reset with LED Display

Indicator auto-resets to normal after a four hour time


duration. Indicator may also be manually reset using an
FTT test tool.

OLMVF

Voltage Reset with Flag Display

Indicator auto-resets to normal after system voltage restoration. Reset requires 5kV minimum voltage to operate.
Reset operation time is proportional to system voltage.

OLMVL

Voltage Reset with LED Display

Example: at 15kV, reset occurs 30 seconds after system


voltage restoration.

OLMVOL

Voltage Operated, Time Reset,


LED Display

Indicator auto-resets after a four hour time duration.


Longer time resets are available upon request.

Catalog Suffix
Catalog
Number

Description

LT

All fused taps use LOW trip rating.


For 200 amp. Overhead applications, use LOW trip rating.

HT

For 600 amp. Overhead applications, use HIGH trip rating.

NOTE: For overhead bulk feeder applications, use HIGH or LOW trip ratings (whichever is greater than the minimum

PG-PC-E-0907

pickup setting of the related protection device).

AccQTrip and AccQClamp are trademarks of Quality Indications, Inc.

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

41

PROTECTION AND CONTROL


Fault Indicator Accessories

Fault Indicator Accessories

Field Test Tool permits field testing and reset


of fault indicators and provides assurance that
the indicator is properly functioning. The test
tool is lightweight, portable and incorporates a
built-in magnet which operates the indicator trip
and reset functions. The unit is equipped with
provisions for hotstick handling and operation.

Fault Indicators

fo-cable06

FTT

Remote Fiber Optic Indicator for Underground


Fault Indicators with LED Display can be
extended to the outside of enclosures and/or
vaults for ease of access and fault location.
All the hardware for mounting the remote end
of the cable to the enclosure is included. The
display has a large reflective bolt to enhance
visibility.

description

catalog number

42

FTT

Field Test Tool, overall dimensions 2" wide x 3" high x 5/8" deep

FO-CABLE06

Remote Fiber Optic Indicator for UFI

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


V2

V2

V2 Standard Features
Test Point Mounted Neon Voltage Indicators
provide a convenient, visual method for
determining the energized status of underground
distribution circuits. The indicator consists of a
self-powered voltage sensor connected to a neon
light that flashes when energized. Flash rate
is proportional to the system voltage and the
same indicator may be used for 5kV thru 35kV
applications.
Units are designed to mount directly to 200
& 600 amp elbows, splices and other cable
accessory components equipped with IEEE
386 Standard capacitive test points. Indicators
include a universal mounting provision
allowing installation on test point products as
manufactured by Elastimold and others.

V2

dimensions

3
/8"
10 mm

3 1/4"
83 mm

2"
51 mm
1 3/4"
44 mm

Test Point
Test Point Mounting Provision
Flashing Neon Light
Indicates Energized
Status

Self-Powered Flashing Neon Display

Provision for Hotstick


Installation and Removal
EPDM Molded
Rubber Housing

Elastimold Voltage Indicators are self-powered


from the test point and are provided with
a 20-year long life neon bulb. A reflective
background surrounds the bulb to provide
increased brightness. Flash rate per minute
is proportional to the phase to phase system
voltage with output as follows:

V2-TB

Voltage & Flash Rate


5kV voltage

20 flash rate

25kV voltage

140 flash rate


10kV voltage

40 flash rate

30kV voltage

160 flash rate

15kV voltage

70 flash rate

35kV voltage

180 flash rate

20kV voltage

100 flash rate

Voltage Indicator Test Box permits field


testing of V2 Voltage Indicators and provides
assurance that the indicator is properly
functioning. The test box is lightweight, portable
and self-powered by replaceable C-size batteries.
The unit includes a standard Elastimold
test point, a push to test button, a green LED
operation indicating light and a rugged, impact
resistant plastic housing.

PG-PC-E-0907

Basic Operation
1. Mount

the Neon Voltage Indicator to the
test point provision on the test box.
2. Push

and hold the test button to energize
the test point. The green LED light will
flash indicating that battery voltage
is sufficient and that the test box is
operating properly.
3. C
 ontinue holding the test button until
the Neon Voltage Indicator begins to
flash. If flashing does not occur after
approximately 30 seconds, then the
Neon Voltage Indicator is defective
and should be discarded.

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

43

Voltage Indicators

Designs feature compact, shielded and sealed,


corrosion resistant construction. The indicator
is enclosed in a durable EPDM molded rubber
housing and includes a built-in pulling eye for
easy hotstick installation and removal of the
indicator from the test point.

PROTECTION AND CONTROL


PD35 Voltage & Phasing Indicator
PD35 is used for determining the correct

Voltage Indicators

phasing and energized status of single


and three-phase underground distribution
circuits, rated 5kV thru 35kV. The unit has
been specifically designed for use on 200
& 600 amp elbows, splices and other cable
accessory components equipped with IEEE
386 Standard capacitive test points. The tool
eliminates direct exposure to high-voltage
while using established indirect test methods
for capacitance-coupled, cable connection
test points.
The Phase & Voltage Indicator is designed for
hotstick operation and includes universal end
fittings for convenient mounting to existing
hotsticks. The unit is lightweight, portable
and self-powered by a built-in, replaceable,
standard 9-volt battery. The tool features
rugged, impact resistant construction and
easy to read LED indicator lights. Advanced
low impedance, solid state circuitry provides
accurate and reliable readings with sensitivity
as low as 1.5kV phase to ground.

1. Attach the metered probe to a hotstick


and connect the BLACK ground lead.

Elbow Connectors
with Test Point
Provisions

2. Switch the meter to the ON position.


The red LED power light will illuminate
indicating that battery voltage is sufficient.
All other LED indicators will momentarily
light up showing that the meter is
operating properly.

Non-Metered Probe
Universal End Fitting
Attachment to Hotstick

Red Phase Lead with


Plug In Connections
between Metered Probe
and Non-Metered Probe

3. To test for voltage:


Touch the metered probe to the test point
on the cable connection.
The amber PHASE 1 LED indicator light
will illuminate showing that the high-
voltage circuit is energized.
4. To test for proper phasing:
Attach the non-metered probe to an
additional hotstick and connect the RED
phase lead from the metered probe to the
non-metered probe.
Touch one probe to the test point on one
of the cable connections. Touch the other
probe to the test point on the other cable
connection.

44

Black Ground Lead with


Plug In Connection to
Metered Probe and Clip On
Connection to Ground

Metered Probe

The amber PHASE 1 and PHASE 2 LED


indicator lights will illuminate showing
that each of the high-voltage circuits are
energized.
If the circuits are IN PHASE the green LED
will illuminate.
If the circuits are OUT of PHASE the red
LED will illuminate.

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Ordering Information

Ordering Information
ORDERING INFORMATION
Catalog
Number

Description

V2

Voltage Indicator with Neon Display

V2TB

Voltage Indicator Test Box

PD35

Voltage & Phasing Indicator

V2
Voltage Indicators

PD-35

V2-TB

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

45

PROTECTION AND CONTROL


Product Application

Product Application

Underground Arresters
Voltage surges that exceed the BIL rating of
the distribution system components will cause
damage to the installed equipment. To protect
against these surges, overhead surge arresters
are widely used. Their application is understood
since overhead lines and equipment are directly
affected by voltage surges (e.g. lightning).
However, the use of overhead arresters alone
will not guarantee proper protection
of the insulation in the underground
portion of an electrical distribution system.
The let-through surge from the riser pole
arresters into the underground systems could
be enough to cause damage to the aging
equipment insulation.

Underground Arresters

Elastimold MOV Surge Arresters provide highvoltage lightning and switching surge protection
of transformers, cable, equipment and other
components typically located on underground
power distribution systems. Proper placement,
voltage selection and coordination with riser
pole arresters minimizes damaging surge
voltages by improving protective margins.
Typical applications include installing an
arrester at the end of a radial system or at
both ends of an open point on a loop system.
Additional arresters can be added at strategic
locations upstream from the endpoint for
optimum protection.

shielded, fully submersible


and are equipped with IEEE
386 interfaces for convenient
energized connection with other
200 amp loadbreak or deadbreak
components up to 35kV. Arresters
are available in three styles: Elbow
(ESA), Parking Stand (PSA) and
Bushing (BSA). The PSA and BSA arresters
permit direct connection, eliminating the
need for additional accessories.
ESA Elbow Arresters are also available with
a 200 amp deadbreak interface for mating
with other deadbreak accessories.
The following tables highlight the different
installation options using Bushing and
Parking Stand Arresters where Elbow
Arresters are normally used. Using BSAs
and PSAs will contribute to save space
inside transformers and improve operability.

benefit/description

Feature

46

Thomas & Betts Elastimold


Metal Oxide Varistor (MOV)
Surge Arresters are fully

IEEE 386 interfaces

Convenient energized connection with other 200 amp loadbreak or deadbreak components

EPDM molded rubber construction

Fully shielded, fully submersible

Compact

Allow installation in existing cabinetry

Elbow (ESA), Parking Stand (PSA)


and Bushing (BSA) styles available

Ease of application and installation

Direct connection on PSA and BSA

Eliminates the need for additional accessories

#4 AWG ground lead tethered


to the jacket

Withstands 10,000 amp for 10 cycles without fusing


Controls end plug when ejected, preventing uncontrolled trajectory
Maintains the housing shield ground connection after failure

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Product Application

Product Application
installation options

BSA Bushing
Surge Arrester
Bushing
Well

Loadbreak
Bushing Insert

Loadbreak
Feed-Thru Insert
ESA Elbow
Surge Arrester
Underground Arresters

Feed-Thru

Parking
Stand

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PSA Parking
Stand Arrester

47

PROTECTION AND CONTROL


Product Application
LOOP-FEED CIRCUIT

Product Application
(TYPE 2 TRANSFORMER)

ELBOW ARRESTER
AND PARKING STAND
ARRESTER

TWO ELBOW ARRESTERS


AND A FEED-THRU
This is one approach
using elbow arresters
only. (One of the elbow
arresters could be
mounted on the H1A
bushing if allowable by
operating procedures.)

This approach can


reduce overcrowding
(by eliminating the
feed-thru device).
This is desirable in a
mini-pad transformer.

BUSHING ARRESTER AND PARKING STAND ARRESTER*


This approach is best for increasing operability and reducing
transformer overcrowding
The bushing arrester allows
the source cable to be
positioned on H1A which
conforms with some
operating practices.
Potential interference between
an elbow arrester on H1B and a
cable parked on P is eliminated.
Underground Arresters

A bushing arrester mounted on


H1A can be directed downward
without interference.

The bushing arrester requires


significantly less space than
an elbow arrester used with a
feed-thru insert.
Operability is enhanced
because the open point can
be closed by moving the
parked cable to H1B without
removing an arrester.

*Transformers must be specified with bushing wells.

ADDITIONAL MARGIN OF PROTECTION


An additional margin of protection may be gained by
adding an arrester at the next transformer upstream on
each side of the open point. This application is dependent on the system voltage and condition of the cable.

OR

If an additional arrester is added in the circuit, it can be


an elbow arrester in combination with a feed-thru insert
or it can be a bushing arrester. Use of bushing arrester
will reduce tranformer faceplate overcrowding.

OTHER CONFIGURATIONS
Other configurations are possible such as specifying a
bushing arrester on every transformer. This will allow the
open point to be quickly and easily moved to any point in the
circuit while maintaining the surge protection (without moving
all of the portable surge arresters).

48

The externally mounted bushing arrester provides the surge


protection benefits without the negative factors of a under
oil arrester.

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Product Application / Ratings

Product Application
RADIAL-FEED CIRCUIT (END POINT )
SINGLE-BUSHING TRANSFORMER
To add surge protection to a single-bushing transformer, utilize a
bushing arrester or an elbow arrester with a feed-thru insert.

TWO-BUSHING TRANSFORMER
To add surge protection to a two-bushing transformer at the end point
of a radial-feed circuit, add an elbow arrester to the unoccupied
bushing or utilize a bushing arrester.

CONVERSION OF A RADIAL-FEED TRANSFORMER


TO A LOOP-FEED, OPEN POINT TRANSFORMER
To convert a single-bushing transformer to a loop-feed, open-point
transformer, add a parking stand arrester and an elbow arrester in
combination with a feed-thru insert.

PROTECTIVE CHARACTERISTICS

High Current
Short Duration

All MOV Arresters withstand two


discharges of 40kA crest.

Low Current
Long Duration

All MOV Arresters withstand 20 surges of


75 amperes/2000 microsecond duration

Duty Cycle
Test

All MOV Arresters withstand 22


operations of 5kA crest at 8 x 20
microsecond duration while energized at
rated voltage for the initial 20 operations
and at maximum continuous operating
voltage (MCOV) for the final two
operations.

15kV
CLASS

25kV
CLASS

Following each of the preceding tests, MOV Arresters


demonstrate thermal recovery at MCOV.
35kV
CLASS

MCOV*
(kVrms)

Duty Cycle
Rating
(kVrms)

2.55
5.1
8.4
10.2
12.7
15.3
8.4
10.2
12.7
15.3
17.0
19.5
22.0
24.4

3
6
10
12
15
18
10
12
15
18
21
24
27
30

Maximum Discharge Voltage (kV crest)


8x20 microsecond current wave
1.5kA
10.5
20.5
30.5
40.0
48.0
56.5
30.5
40.0
48.0
56.5
65.5
78.5
87.5
95.5

3kA
11.0
21.5
32.5
42.5
51.0
60.0
32.5
42.5
51.0
60.0
69.5
83.5
93.0
101.5

5kA
11.5
23.0
34.5
45.0
54.0
64.0
34.5
45.0
54.0
64.0
74.0
89.0
99.0
108.0

10kA
13.0
25.5
38.5
50.0
60.0
71.0
38.5
50.0
60.0
71.0
82.5
99.0
110.0
120.0

20kA
14.5
30.0
43.5
56.5
68.0
80.5
43.5
56.5
68.0
80.5
93.0
112.0
124.5
136.0

* MCOV = Maximum Continuous Operating Voltage

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

49

Underground Arresters

RATINGS

PROTECTION AND CONTROL


Ordering Information

Ordering Information

ORDERING INFORMATION

To specify and order an MOV Surge Arrester:


1. D
 etermine the appropriate Maximum Continuous Operating Voltage (MCOV) for your
system voltage by using the Elastimold Arrester Application Table.

2. Specify the appropriate Elastimold part number from the Selection Chart.
selection chart

Arrester Application table


System Line-to-Line
Voltage kV rms

Nominal
2.40

Underground Arresters

15kV
CLASS

25kV
CLASS

4.16

MCOV* kVrms

Solidly
3-Wire
Grounded Ungrounded
Maximum Neutral
Circuits
Circuits
2.54
2.55
2.55
4.40

2.55

Picture

Description

BSA
Bushing
Surge Arrester
(includes
assembly
tool)

5.10

Voltage
Class

Elastimold
Part Number

MCOV
kVrms

15kV

167BSA-3

2.55

15kV

167BSA-6

5.10

15kV

167BSA-10

8.40

15kV

167BSA-12

10.20

15kV

167BSA-15

12.70

15kV

167BSA-18

15.30

25kV

273BSA-10

8.40

25kV

273BSA-12

10.20

25kV

273BSA-15

12.70

25kV

273BSA-18

15.30

25kV

273BSA-21

17.00

Voltage
Class

Elastimold
Part Number

MCOV
kVrms

15kV

167ESA-3

2.55

15kV

167ESA-6

5.10

15kV

167ESA-10

8.40

15kV

167ESA-12

10.20

15kV

167ESA-15

12.70
15.30

4.80

5.08

5.10

5.10

6.90

7.26

5.10

8.40

8.32

8.80

5.10

8.40

12.47

13.20

8.40

15.30

13.20

13.97

8.40

15.30

13.80

14.50

8.40**

15.30

13.80

14.50

10.20

15.30

6.90

7.26

5.10

8.40

8.32

8.80

5.10

8.40

12.47

13.20

8.40

15.30

13.20

13.97

8.40

15.30

13.80

14.50

8.40**

15.30

13.80

14.50

10.20

15.30

20.78

22.00

12.70

20.78

22.00

15.30**

15kV

167ESA-18

25kV

273ESA-10

8.40

25kV

273ESA-12

10.20

25kV

273ESA-15

12.70

25kV

273ESA-18

15.30

23.00

24.34

15.30

24.94

26.40

15.30

24.94

26.40

17.00**

28.00

29.80

17.00

See Notes
1, 2, 3, 4

Picture

Description

ESA
Elbow
Surge Arrester

See Notes
2, 3, 5

25kV

273ESA-21

17.00

Voltage
Class

Elastimold
Part Number

MCOV
kVrms

SELECTION CHART NOTES:

15kV

167PSA-3

2.55

1) Elastimold PSA and BSA Arresters are equipped


with a fully rated 200A switching and fault close
loadbreak bushing.
2) Elastimold Arresters use high-strength, silver epoxy
bonded MOV blocks and shunted spring connections
for the best circuit connection.
3) A 36 inch free lead length #4 AWG ground lead
provided with each unit.
4) BSA installed by turning internal hex bolt (accessed
through the 200 amp Bushing Interface) with 5/16"
hex wrench and bent wire torque wrench supplied
with each unit.
5) For 15kV and 25kV Class deadbreak system
Elbow Arresters, use part number 156ESA with
the appropriate Duty Cycle rating.

15kV

167PSA-6

5.10

15kV

167PSA-10

8.40

15kV

167PSA-12

10.20

15kV

167PSA-15

12.70
15.30

* MCOV = Maximum Continuous Operating Voltage


** Preferred arrester MCOV for this system voltage.

50

Picture

Description

PSA
Parking Stand
Arrester

See Notes
1, 2, 3

15kV

167PSA-18

25kV

273PSA-10

8.40

25kV

273PSA-12

10.20

25kV

273PSA-15

12.70

25kV

273PSA-18

15.30

25kV

273PSA-21

17.00

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

PG-PC-E-0907

PROTECTION AND CONTROL


Ordering Information

Ordering Information
ORDERING INFORMATION

selection chart

Arrester Application table


System Line-to-Line
Voltage kV rms

35kV
CLASS

Nominal
23.00

MCOV* kVrms

34.50

36.51

22.00**

34.50

36.51

24.40

Voltage
Class

Elastimold
Part Number

MCOV
kVrms

BSA
Bushing
Surge Arrester

35kV

375BSA-24

19.50

35kV

375BSA-27

22.00

35kV

375BSA-30

24.40

Description

Voltage
Class

Elastimold
Part Number

MCOV
kVrms

ESA
Elbow
Surge Arrester

35kV

375ESA-24

19.50

35kV

375ESA-27

22.00

35kV

375ESA-30

24.40

Description

Voltage
Class

Elastimold
Part Number

MCOV
kVrms

PSA
Parking Stand
Arrester

35kV

375PSA-24

19.50

35kV

375PSA-27

22.00

35kV

375PSA-30

24.40

See Notes
1, 2, 3, 4

* MCOV = Maximum Continuous Operating Voltage


** Preferred arrester MCOV for this system voltage.

Picture

See Notes
2, 3

Picture

See Notes
1, 2, 3

SELECTION CHART NOTES:


1) Elastimold PSA and BSA Arresters are equipped with a fully rated 200A
switching and fault close loadbreak bushing.
2) Elastimold Arresters use high-strength, silver epoxy bonded MOV blocks and
shunted spring connections for the best circuit connection.
3) A 36 inch free lead length #4 AWG ground lead provided with each unit.
4) BSA installed by turning internal hex bolt (accessed through the 200 amp
Bushing Interface) with 5/16 hex wrench and bent wire torque wrench
supplied with each unit.
5) For 15kV and 25kV Class deadbreak system Elbow Arresters, use part number 156ESA with the appropriate Duty Cycle rating.

PG-PC-E-0907

Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com

51

Underground Arresters

Description

Picture

Solidly
3-Wire
Grounded Ungrounded
Maximum Neutral
Circuits
Circuits
24.34
22.00

PG-PC-E-0907
2007 Thomas & Betts Corporation