AUTOMATIC MAINS FAILURE UNIT

KO

AMF 4.0
Therefore, the user can monitor these
values as analog values on the front panel
without the need to use separate gauges.
The system also monitors the mains values
continuously, also in sleep mode, it detects
all alarm conditions and the last 10 alarm
status can be displayed on the unit display.
All configuration parameters are adjustable
from the control unit menu. The user can
choose to download pre-stored gauge data
from the menu for well known brands and
this allows easy tuning of the control unit for
any generator application.

FEATURES

AMF 4.0 series genset control units are designed and manufactured
according to CE regulations and offers automatic engine starting,
stopping, metering and generator protection and transfer switch
operations. The system provides full AMF (Auto mains Failure)
functions. It can be operated in Automatic, Test and Manual modes.
The control unit has 5 digital displays (each display has 3 digit 7segment LED display), which allows all the measured engine and
alternator values to be monitored simultaneously. This makes the
classical analog type panel meters redundant, hence saving cost and
introducing very accurate reading of all engine and alternator data.
The following digital data can be monitored from the front panel of the
unit:
Three phase mains and generator voltage sensing (true rms)
Three phase generator current (true rms A, KA)
Mains and generator frequency (Hz)
DC battery voltage (DC volts)
Oil pressure (bar)
Engine temperature (Celsius or Fahrenheit)
Engine working hour time (Hour)
Oil pressure and temperature sensors can either be of analog type or
switch type. By means of analog sensors, engine control and
monitoring can be made more accurately.
The engine oil pressure and coolant temperature values are also
displayed in analog bar-graph displays as well as digital displays.

Automatic and Manual start/stop


sequence for diesel engines

Automatic control of mains (MCB)


and generator (GCB) circuit breakers

Mains monitoring, automatic start,


stop and transfer switch functions

True RMS voltage


measurements
for
generator

Failure monitoring and control

Recording of the last 10 failure


alarms

Operating hours and service hours


timing functions

Analog engine temperature and oil


pressure measurement and display

Battery saving sleep mode feature


(active monitoring during sleep mode)

Adjustable operating modes and


timings via extensive parameter
menu

Special calibration menu


analog measurement inputs

Remote Start control input

CE compliant design and production

and current
mains
and

Pre-glow heater control


Manuel, automatic and test modes
Five 3-digit, 7 segment LED digital
measurement displays

for

all

High reliability concept design (MTBF


> 50.000 hours)

EN-KO Electronic Control Systems


10006 Sok. No:64 A.O.S.B Cigli-zmir/TURKIYE
Tel: +90 (232) 3767806 (Pbx)
Fax: +90 (232) 3767792
E-Mail: info@enkoelektronik.com
Web: www.enkoelektronik.com

AMF 4.0 E.003.R0 Specifications are subject to change without notice.

DESCRIPTION

AMF 4.0 AUTOMATIC MAINS FAILURE


PROTECTION FUNCTIONS

SPECIFICATIONS

Engine start/stop failure

Power Supply

9-35VDC
140 mA (relays in off position)

Operating Temperature

-10C / +70C

Relative Humidity

10% - 95% non-condensing

Relay Outputs

Cranking, fuel solenoid, alarm,


preheat and auxiliary relays;
contact rating max. 12V/24VDC
3 A, Mains and Generator
contactor relays contact rating
max. 250VAC/10 A

Voltage Measurement

20 - 300VAC

Frequency Measurement

1.0 Hz 99.0 Hz

Current Measurement

.../5 A current inputs (current


transformer should be used)

Connection

Screw type terminal sockets

Measurement Accuracy

Phase voltages
Frequency
Phase currents

Charge Excitation Current

80mA @ 12VDC
160mA@ 24VDC

Housing

High temperature proof


PPO GF %20

Engine coolant temperature analog input

Protection Class

IP 52 (Front side)

Engine oil pressure and temperature switch input

Weight

600 gr. (aprox.)

Charge alternator input

Dimensions (WxHxD)

192x144x62 mm

Cranking relay output

Panel Cut Out

186x138 mm

Mounting Installation

Front panel mounted with rear


metal screw fixings
Max. allowable mounting panel
thickness 3mm

Over/Under engine speed failure


Over/Under alternator voltage failure
Over/Under frequency protection
Over current (overload) failure
High engine temperature failure
Charge alternator failure warning
Low oil pressure failure
Periodic service time warning
Auxiliary input failure

INPUTS / OUTPUTS
3 phase mains voltage measurement inputs
3 phase generator voltage measurement inputs
3 phase generator current measurement inputs
12 / 24 Vdc battery supply input
Engine oil pressure analog input

Pre-glow heater relay output


Fuel solenoid relay output
Generator circuit breaker (GCB) relay output

: 2%
: 0.1Hz
: 2%

Mains circuit breaker (MCB) relay output

MOUNTING AND INSTALLATIONS

Alarm relay output


2 programmable auxiliary relay output
2 programmable auxiliary relay input

CONNECTION DIAGRAM
AMF 4.0 CONNECTION DIAGRAM
LOAD
MAINS
R

GENERATOR
U

22 23 24 25 14

12

26 27 28 29 13

30 31

NEGATIVE TERMINAL OF BATTERY


SHOULD BE GROUNDED

D+WL

16

17

18

Dimensions in mm

19

Configurable Input 4

21

Configurable Input 3

20

Temperature Sender

10

Configurable Input 2
(Default Temperature Switch)

Charge

Configurable output 3

Com 2
Fuel Selenoid

Preheating Ralay

Crank Relay

Battery

Crank

Oil Pressure sender

15

Configurable output 2

Configurable output 1
(Default Horn)

AMF 4.0

Emergency
Stop

Power Supply

Mains Contactor Relay

2 1

32 33 34 35

Generator Current
Inputs

Generator Contactor
Relay

Configurable Input 1
(Default Oil Pressure Switch)

11

EN-KO Electronic Control Systems


10006 Sok. No:64 A.O.S.B Cigli-zmir/TURKIYE
Tel: +90 (232) 3767806 (Pbx)
Fax: +90 (232) 3767792
E-Mail: info@enkoelektronik.com
Web: www.enkoelektronik.com