Anda di halaman 1dari 9

Energy Conversion and Management 86 (2014) 379387

Contents lists available at ScienceDirect

Energy Conversion and Management


journal homepage: www.elsevier.com/locate/enconman

Heat exchanger inventory cost optimization for power cycles with one
feedwater heater
Bilal Ahmed Qureshi, Mohamed A. Antar, Syed M. Zubair
Mechanical Engineering Department, KFUPM Box # 1474, King Fahd University of Petroleum & Minerals, Dhahran 31261, Saudi Arabia

a r t i c l e

i n f o

Article history:
Received 6 March 2014
Accepted 7 May 2014

Keywords:
Inventory
Heat exchanger
Thermoeconomic
Optimization
Feedwater heater

a b s t r a c t
Cost optimization of heat exchanger inventory in power cycles with one open feedwater heater is undertaken. In this regard, thermoeconomic analysis for an endoreversible power cycle with an open feedwater
heater is shown. The scenarios of constant heat rejection and addition rates, power as well as rate of heat
transfer in the open feedwater heater are studied. All cost functions displayed minima with respect to the
high-side absolute temperature ratio (h1). In this case, the effect of the Carnot temperature ratio (U1),
absolute temperature ratio (n) and the phase-change absolute temperature ratio for the feedwater heater
(U2) are qualitatively the same. Furthermore, the constant heat addition scenario resulted in the lowest
value of the cost function. For variation of all cost functions, the smaller the value of the phase-change
absolute temperature ratio for the feedwater heater (U2), lower the cost at the minima. As feedwater
heater to hot end unit cost ratio decreases, the minimum total conductance required increases.
2014 Elsevier Ltd. All rights reserved.

1. Introduction
Using feedwater heaters, also called regenerators, to enhance
efciency of steam power plants is a standard practice in industry
and, therefore, thermoeconomic analysis of such systems is
important. Feedwater heaters can either be open or closed type.
When the heat is transferred from the steam (bled from the turbine) to the feedwater by mixing, it is considered an open type.
The advantages offered include a higher efciency of the power
plant due to a rise in the average temperature of heat addition.
Next, it helps to prevent boiler corrosion by providing an easy
way to remove air that leaks into the condenser. Also, it lowers
the volume ow in the nal turbine stages. For further details,
the work of Babcock & Wilcox [1] may be consulted along with
textbooks on Thermodynamics such as Cengel and Boles [2].
Authors such as Bejan [3,4] addressed the issue of heat exchanger inventory allocation for different situations such as maximizing
the efciency. The Carnot model developed by Bejan [4] was used
by Antar and Zubair [5] to study cost optimization of power plant
heat exchanger inventory for a specied power output. The total
inventory reached a minimum when the unit cost ratio attained
unity. Sahin and Kodal [6] carried out thermoeconomic optimization of endoreversible heat engines using a new thermoeconomic
optimization criterion i.e. power output per unit total cost.
Corresponding author. Tel.: +966 3 860 3135.
E-mail address: smzubair@kfupm.edu.sa (S.M. Zubair).
http://dx.doi.org/10.1016/j.enconman.2014.05.028
0196-8904/ 2014 Elsevier Ltd. All rights reserved.

Analytical equations for optimum working uid temperatures,


specic power output, thermal efciency and distribution of heat
exchanger areas were determined. The effect of relative fuel cost
was also discussed. This new criteria was later used by the authors
for irreversible heat engines [7] as well. Using prot maximization
as the objective function, exergoeconomic performance optimization of a nite-time irreversible Carnot engine was investigated
by Chen et al. [8]. The authors derived relevant formulae concerning prot and efciency for this purpose.
Bandyopadhyay et al. [9] studied combined cycle power plant
cost optimization using irreversible Carnot-like heat engines. It
was found that the yearly plant cost rose along with a decline in
power output as the number of stages was increased. For offdesign conditions in combined cycle gas turbine power plants,
Rovira et al. [10] performed thermoeconomic optimization in heat
recovery steam generators. Based on design conditions, negligible
difference was found in the optimization results when compared
to those obtained from usual thermoeconomic models except for
the fact that, with the new model, a minor decrease was seen in
the amortization cost and design efciency. For combined cycle
power plants, genetic algorithms have also been used for the purpose of thermoeconomic optimization [1113]. Using the Second
Law of Thermodynamics, Silveira and Tuna [14] presented a thermoeconomic functional analysis method. Four cogeneration systems were analyzed and the system consisting of a gas turbine
with heat recovery steam generator only was found to have the
lowest exergetic production cost. Al-Sulaiman et al. [15,16]

380

B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

Nomenclature
A
F
G
K
k1
_
m
Q_
s
T
U

area (m2)
non-dimensional cost function ()
unit cost conductance ratio ()
non-dimensional quantity dened by Eq. (15f) ()
ratio of feedwater heater to condenser entropy
change ()
mass ow rate (kg s1)
rate of heat transfer (kW)
specic entropy (kJ kg1 K1)
absolute temperature (K)
overall heat transfer coefcient (kW m2 K1)

Greek

c
U1
U2

total cost ($)


unit conductance cost ($kW1 K)
Carnot temperature ratio ()
phase-change absolute temperature ratio for the
feedwater heater ()

performed thermoeconomic optimization of three trigeneration


systems using organic Rankine cycles. Formulations were presented and the systems examined which revealed that, from the
three systems, the solar trigeneration system offered the best thermoeconomic performance. Abusoglu and Kanoglu [17] reviewed
exergoeconomic optimization and analysis for combined heat
and power systems. A comparison of the advantages and disadvantages regarding important thermoeconomic methodologies found
in the literature were made.
Xiong et al. [18] performed thermoeconomic optimization of a
600 MWe pulverized-coal-red power plant using oxy-combustion. A 10% increase in unit thermoeconomic product costs was
seen due to the extra power utilization for the oxy-combustion
system and another 10% due to its other related costs such as operation and maintenance, investment as well as interest. Bassily [19]
performed cost optimization of commercial combined cycle power
plants with triple-pressure reheating. It was determined that, for a
400 MW power plant, an annual saving of about $29.2 million
could be obtained by optimizing the net revenue.
Rosen and Dincer [20] thermoeconomically examined an electrical generating station fueled by coal based on capital cost only. They
emphasized that the reason for this is that the capital cost is often
the most signicant cost component and costs other than that are
often proportional to it. Thus, qualitative agreement is expected.
For the design and analysis of energy systems, Silveira et al. [21] presented a thermoeconomic optimization methodology using the
exergetic production cost as the objective function. Depending on
the energy system analyzed, the various costs included operational
and capital cost for a given amount and type of exergy. Seyyedi et al.
[22] provided a new approach for optimization of thermal power
plants based on the exergoeconomic analysis and structural optimization method. Important advantages of this new method are its
applicability to large complex thermal systems and rapid convergence. Considering various objective functions based on nite-time
thermodynamics and thermoeconomics, Durmayaz et al. [23] presented an extensive review on optimization of thermal systems.
The conclusion of the authors was that nite-time thermoeconomic
analysis needed more work in fundamental theory development and
applications as it was still in its early stages.
It was found through the literature review that, for the endoreversible case of a power cycle with one feedwater heater, cost optimization has not been considered for design and performance

high-side absolute temperature ratio ()


average preheating absolute temperature ratio ()
absolute temperature ratio ()

h1
h2
n

Subscripts
01
at condenser
02
at phase-change in feedwater heater
a
constant rate of work
b
constant rate of heat rejection from the condenser
C
reversible compartment
c
constant rate of heat addition in the boiler
d
constant rate of heat transfer in the open feedwater
heater
H
hot end
L
cold end
min
minimum
OFH
open feedwater heater
tot
total

evaluation purpose. Therefore, this paper aims to develop the relevant endoreversible models and then perform thermoeconomic
analysis of this system. The scenarios of constant heat addition
and rejection rates, power as well as rate of heat transfer in the
open feedwater heater will be studied.
2. Mathematical framework
Following the methodology of Bejan [4] and Antar and Zubair
[5], the endoreversible form of the power cycle with one open
feedwater heater is now considered. The schematic of system
under consideration is shown in Fig. 1(a) while Fig. 1(b) shows
its T-s diagram. The purpose of the current study is to determine
the minimum of the total cost of conductance (UA) for the following scenarios: constant rate of heat addition, power, heat transfer
in the preheater and heat rejection. The Heat Exchanger Inventory
Cost Equation (HEICE) can be written in terms of heat exchanger
unit cost parameters as [5]:

C cH UAH cL UAL cOFH UAOFH

where cH, cL, and cOFH are unit cost of conductance for the boiler,
condenser and preheater, respectively, such that C has units of
dollars. Next,

Q_ H UAH T H  T HC

Q_ L UAL T 01  T L

Q_ OFH UAOFH T 02  T OFH

4a

whereT OFH is the average preheating temperature and is given by:

T OFH T 02  DT OFH;av g

4b

where DTOFH,avg is the average amount of preheating and considered


as half of the total achieved. Putting Eqs. (2)(4) in Eq. (1) results in

C cH

Q_ H
Q_ L
Q_ OFH
cL
cOFH
T H  T HC
T 01  T L
DT OFH;av g

Dividing throughout by cH, we get

cH

c
c
Q_ H
Q_ L
Q_ OFH
L
OFH
T H  T HC cH T 01  T L
cH DT OFH;av g

381

B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

_ 02 T 02 s6  s3
Q_ OFH m

_ 01 T 01 s7  s1
m
Q_ L

10

We see from Fig. 1(b) that, in general, (s6  s3) = k1(s7  s1) where k1
can be any number less than one. Now, Eq. (10) becomes

_ 02 T 02
m
Q_ OFH
k1
_ 01 T 01
m
Q_ L

11

Applying the Clausis inequality to the internally reversible cycle


gives us

Q_ H
Q_ L

;
T HC T 01

12a

Q_ L
T 01

Q_ H T HC

12b

Combining Eqs. (11), (12a), (12b), we get

_ 02 T 02
m
Q_ OFH
k1
_
_
m
01 T HC
QH

13

Putting Eqs. (12b) and (13) into Eq. (8), we get after dividing the
right hand side by TH/TH,

2
3
_ 02 T 02
T 01
m
k
1
Q_ H 4 1
_
T
m T

GL T HC T GOFH DT 01 HC 5
01
OFH;av g
cH T H 1  TTHC
 TL
T

14

TH

Introducing the following non-dimensional quantities:

h1

T HC
TH

15a

h2

DT OFH;av g
TH

15b

U1

T 01
T HC

15c

U2

T 02
T HC

15d

Fig. 1. Endoreversible power cycle with an open feedwater heater: (a) Schematic
and (b) T  s diagram.

Let

cL
cH

GL and

cOFH
cH

GOFH , thus Eq. (6) becomes

Q_ H
Q_ L
Q_ OFH

GL
GOFH
cH T H  T HC
T 01  T L
DT OFH;av g

cH

"
Q_ H

1
Q_ L =Q_ H
Q_ OFH =Q_ H
GL
GOFH
T H  T HC
T 01  T L
DT OFH;av g

15e
_ 02
m
_ 01
m

15f

Putting Eqs. (15a), (15b), (15c), (15d), (15e), (15f) into Eq. (14), and
multiplying both sides by TH gives us

cH

T H Q_ H

1
U1
K U2
GL
GOFH
1  h1
U1 h1  n
h2

16

Beginning from Eq. (16), the next section discusses the following
scenarios: constant power, heat addition and rejection capacities as
well as heat transfer rate in the open feedwater heater.

Factoring out Q_ H , we get

K k1

C
7

TL
TH

#
8

Now, from Fig. 1(b), we see that

_ 01 T OFH s3  s2
Q_ OFH m

9a

_ 02 T 02 s6  s3
Q_ 36 m

9b

_ 01 T 01 s7  s1
Q_ L m

9c

But Q_ OFH Q_ 36 since they are exchanging heat with each other
exclusively in the feedwater heater. Thus,

3. Results and discussion


In those situations in which the unit cost conductance ratios are
considered unity, it is expected that minimization of the dimensionless HEICE will result in the same for the total conductance
(UAtot).
3.1. Constant power
The non-dimensional equation resulting from dividing Eq. (16)
by the power is:

382

B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

Fa

cH W_

TH



1
U1
K U2
Q_ H
GL
GOFH
_ 1  h1
U1 h1  n
h2
W

Keeping Fig. 1(a) in mind


Thermodynamics, we get

and

using

the

_ Q_ H  Q_ L
W

First

17
Law

of

18

_ is the total power consumed by the pumps. Now, dividing


where W
both sides by Q_ H gives us

_
W
Q_ L
1
Q_ H
Q_ H

19

Putting Eq. (12) in Eq. (19) gives us

_
W
T 01
1
_
T HC
QH

20a

The reciprocal of the above equation gives us

1
Q_ H

01
_
1  TTHC
W

20b

Combining Eqs. (15c) and (20b) and putting them into Eq. (17)
results in

Fa



1
1
U1
K U2
GL
GOFH
1  U1 1  h1
U1 h1  n
h2

21

Eq. (21) is the non-dimensional HEICE for an endoreversible


power cycle with one open feedwater heater for the constant
power output scenario. We see that there is a direct relationship
between Fa and n as well as U2 and an inverse one with respect
to h2 and, thus, these parameters do not exhibit minima. It is
unclear whether minima exist with respect to U1 and h1. Determining the derivative of Fa with respect to U1 and then equating
it to zero gives us:



@F a
1
1
U1
K U2

GL
GOFH
@ U1 1  U1 1  h1
U1 h1  n
h2
"
#
n
 GL
U1 h1  n2
0

22a

or

U1;min

cn

p
n1 c  cn
1 ch1

22b

where


1
K U2 1
GOFH
1  h1
h2 GL

Fig. 2(a) shows a plot of the cost function Fa against U1 for different
values of n. It is found that the minimum value of U1 as well as the
cost rise as n increases. The reason for the increasing cost is evident
from Eq. (21) where n is seen in the second term inside the brackets
only. As n increases, this term increases in value and, thus, Fa as well.
Regarding the minimum value of U1 (that provides a minimum cost),
it can be seen from Eq. (22b) that this is due to the fact that U1,min is
directly proportional to n. Furthermore, this shows that a lower ambient temperature would result in a lower cost if all other quantities
remained the same. Fig. 2(b) shows a plot of the cost function Fa
against U1 for different values of h1. It is found that the minimum
value of U1 decreases as h1 increases but the cost rises. The reason
for the increasing cost is understood from Eq. (21) where h1 is seen
in the rst and second terms inside the brackets. The rst term containing h1 is the dominant term, therefore, as h1 increases, this term
increases in value and, thus, Fa as well. Regarding the minimum value

Fig. 2. Dimensionless HEICE for specied power versus U1: (a) effect of varying n,
(b) effect of varying h1 and (c) effect of varying U2.

of U1, it can be seen from Eq. (22b) that this is due to the fact that
U1,min is inversely proportional to h1. Also, the (1 + c) term, which
contains h1 as well, dominates the quantities containing c in the
numerator. Furthermore, this shows that a higher furnace temperature may result in a lower cost if all other quantities remained the
same. Fig. 2(c) shows a plot of the cost function Fa against U1 for different values of U2. It was noted that lower values of U2 produced
lower costs while the minimum value of U1 was not affected by
change in U2. The reason for the decreasing cost is understood from
Eq. (21) where U2 is seen in the last term inside the bracket only
and directly proportional to Fa. Regarding the minimum value of U1
not changing signicantly, it can be explained from the fact that
the effect of variation in U2 is very small on c. Furthermore, this
shows that a lower feedwater heater temperature (T02) may result
in a lower cost if all other quantities remained the same.

383

B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

The function Fa seems to have a minimum with respect to the


parameter h1. Putting oFa/ oh1 equal to zero and solving, we get

h1;min

p 
 p
1 n GL  1 U1 GL  GL

GL  1
U1

23

It should be noted that Eq. (23) is identical to the respective derivative found by Antar and Zubair [5] though they did not plot it.
Fig. 3(a) shows the effect of different values of n as Fa varies against
h1. It is found that the optimum point of h1 shifts to a greater value
as n increases as well as the cost. This behavior is similar to that found
in Fig. 2(a). As can be seen from Eq. (23), this is simply due to the fact
that n is directly proportional to h1,min. Fig. 3(b) shows the effect of different values of U1 as Fa varies against h1. It is seen that the cost function and h1,min shift to a lower value as U1 increases. This is because

U1 is inversely proportional to h1,min (See Eq. (23)) and, as far as the


cost is concerned, it can be explained from the fact that, in Eq. (21),
the second term inside the brackets is dominant and the term outside
is not signicantly affected by the variation in U1. It shows that
increasing the condenser temperature may result in a lower cost if
all other quantities remained the same. Fig. 3(c) shows a plot of the
cost function Fa against h1 for different values of U2. It is found that
the minimum value of U1 is not affected by change in U2 and this is
because the term U2 does not exist in the expression for h1,min. It
was noted that higher values of U2 produced higher costs and the reasons are the same as was explained earlier for Fig. 2(c). Furthermore,
it shows that a lower feedwater heater temperature may result in a
lower cost if all other quantities remained the same.
3.2. Constant heat rejection rate
The non-dimensional cost equation resulting from dividing Eq.
(16) by the condenser heat transfer rate is:

Fb

cH Q_ L

TH



1
U1
K U2
Q_ H
GL
GOFH
U1 h1  n
h2
Q_ L 1  h1

24

After the relevant substitutions, we get

Fb

U1

1
U1
K U2
GL
GOFH
1  h1
U1 h1  n
h2


25

Eq. (25) is the non-dimensional HEICE for an endoreversible power


cycle with one open feedwater heater for the constant heat rejection rate scenario. We wish to nd out whether the function Fb
has minima with respect to n, U1, U2, h1 and h2. Fb is directly proportional to n as well as U2 and inversely proportional to h2 and,
thus, no minima exist. Determining the derivative of Fb with respect
to U1 and then equating it to zero gives us:



@F b
1
1
U1
K U2

GL
GOFH
@ U1 U1 1  h1
U1 h1  n
h2
"
#
n
GL
U1 h1  n2
0

26

In the above equation, all terms are positive and, therefore, a practical minimum is not possible. The result of taking the derivative of
Fb with respect to h1, in this case, is identical to Eq. (23). Fig. 4(a)(c)
are plotted for conditions identical to those of Fig. 3(a)(c). It is
found that the behavior for this cost function is qualitatively the
same as Fa and the only difference is in the values. It can be
explained from the fact that the terms inside the brackets for both
the cost functions are identical while there is a minor difference in
the term outside it for both the cost functions are identical while
there is a minor difference in the second bracketed term.
3.3. Constant heat addition rate
The non-dimensional cost equation resulting from dividing Eq.
(16) by the boiler heat transfer rate is:

Fc

cH Q_ H

TH

1
U1
K U2
GL
GOFH
1  h1
U 1 h1  n
h2


27

Eq. (27) is the non-dimensional HEICE for an endoreversible power


cycle with one open feedwater heater for the constant heat addition
rate scenario. No minima exist for Fc with respect to n, U2 and h2.
Determining the derivative of Fc with respect to U1 and then equating it to zero gives us:
Fig. 3. Dimensionless HEICE for specied power versus h1: (a) effect of varying n, (b)
effect of varying U1 and (c) effect of varying U2.

@F c
n

0
@ U1 n  U1 h1 2

28

384

B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

Fig. 4. Dimensionless HEICE for specied heat rejection rate versus h1: (a) effect of
varying n, (b) effect of varying U1 and (c) effect of varying U2.

As all terms in the equation are clearly positive on one side, therefore, no minimum exists. The result of taking the derivative of Fc
with respect to h1, in this case, is identical to Eq. (23). Fig. 5(a)(c)
are plotted for conditions identical to those of Fig. 3(a)(c). It is
found that the behavior for this cost function is qualitatively the
same as Fa and the only difference is in the values. The reason for
this is that the quantities inside the brackets for both the cost
functions (i.e. Fa and Fc) are identical while there is a small
difference outside it which is a multiplying factor only.

Fig. 5. Dimensionless HEICE for specied heat addition rate versus h1: (a) effect of
varying n, (b) effect of varying U1 and (c) effect of varying U2.

Substituting Eqs. (13), (15d) and (15f) in Eq. (29a), we get

Fd

cH Q_ OFH

TH

1
K U2

1
U1
K U2
GL
GOFH
1  h1
U1 h1  n
h2


29b

3.4. Constant heat transfer rate in feedwater heater

The function Fd is also found to have no minimum with respect to n


and h2 as it is clearly inversely proportional to them. Determining
the derivative of Fd with respect to U1 and then setting it equal to
zero results in Eq. (28) and, therefore, no minimum exists. Now,
determining the derivative of Fd with respect to U2 and equating
it to zero gives:

The non-dimensional cost equation resulting from dividing Eq.


(16) by the rate of heat transfer in the open feedwater heater is:



@F d
1
1
1
U1
K U2
GOFH


G
L
OFH
h2 U2 K U22 1  h1
@ U2
U1 h1  n
h2

Fd

cH Q_ OFH

TH



Q_ H
1
U1
K U2
GL
GOFH
U1 h1  n
h2
Q_ OFH 1  h1

29a

0
or, after simplication, gives

30a

385

B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

@F d
1
U1

GL
0
@ U2 1  h1
U1 h1  n

30b

As all terms in the equation are clearly positive, therefore, no minimum exists. Finally, oFd/oh1was found to be the same as in Eq. (23).
Fig. 6(a)(c) are plotted for conditions identical to those of Fig. 3(a)
(c). It is found that the behavior for this cost function is qualitatively
the same as Fa and the only difference is in the values. This is due to
the fact that the quantities inside the brackets for both the cost
functions (i.e. Fa and Fd) are the same and, although the term outside it is different, it only acts a multiplying factor resulting in a
change of value but not the behavior.

and this scenario is chosen due to its practical nature. Optimum


values for U1 and h1 will be determined from Eqs. (22b) and (23),
respectively.
In order to provide an illustrative example for the purpose of
showing model applicability, it is required that ratios of the conductance costs of each heat exchanger to the total cost be determined. For the sake of brevity, only the nal expressions are
shown below:

cH UAH
C

cL UAL
3.5. Effect of unit cost ratios


1
U1 1  h1
K U2 1  h1
1 GL
GOFH
h2
U1 h1  n


1 U1 h1  n
GOFH K U2 U1 h1  n
1
GL U1 1  h1
GL h2
U1

31

1
32

The purpose of the analysis in this section is determining the


minimum of the total conductance for specied power production

Fig. 6. Dimensionless HEICE for specied heat transfer rate in the feedwater heater
versus h1: (a) effect of varying n, (b) effect of varying U1 and (c) effect of varying U2.

Fig. 7. Example of all conductances versus unit cost ratio of cold to hot end: (a) at
GOFH = 1, (b) at GOFH = 0.5 and (c) at GOFH = 0.1.

386

B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387

Table 1
Comparison of Antar and Zubair [5] with current work for total conductance required.

a
b

GL ccL
H

UAtota

UAtotb (GOFH = 1)

UAtotb (GOFH = 0.5)

UAtotb (GOFH = 0.1)

0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
2
3
4
5
6
7
8
9
10

26.783
22.895
21.380
20.599
20.148
19.875
19.711
19.616
19.568
19.555
20.148
21.067
21.999
22.895
23.748
24.559
25.333
26.073
26.783

79.403
73.261
70.878
69.654
68.949
68.525
68.270
68.123
68.050
68.029
68.922
70.272
71.610
72.870
74.047
75.149
76.183
77.160
78.084

76.757
71.932
70.175
69.345
68.922
68.713
68.630
68.625
68.672
68.756
70.220
71.808
73.263
74.580
75.783
76.890
77.918
78.880
79.785

78.084
74.580
73.390
72.876
72.650
72.572
72.577
72.632
72.719
72.828
74.218
75.579
76.800
77.904
78.915
79.851
80.726
81.550
82.331

While taking into account the effect of the unit cost ratios, the
following conclusions can be made:
 Ratios of the conductance costs of each heat exchanger to the
total cost were attained.
 If cold and hot end heat exchanger unit costs are the same i.e.
GL = 1, the total conductance was minimized at GOFH = 1.
 At optimum conditions, the total conductance is not equally
divided among the heat exchangers. But when all unit cost
ratios are unity, the hot and cold end conductances are equal
in value.

Antar and Zubair [5].


Current work.

cOFH UAOFH
C

GOFH

h2
GL h2
U1
1

K U2 1  h1 GOFH K U2 U1 h1  n

 For variation of all F-values with respect to h1 and U1, the smaller the value of U2, lower the cost at the minima.
 For variation of all F-values with respect to h1, the effect of different values of n is qualitatively the same. This is found to be
respectively true for the effect of different values of U1 and
U2. Furthermore, in these cases, the constant heat addition scenario resulted in the lowest value cost function.
 For the system investigated, the minimum with respect to U1
exists only for the scenario of specied power cost function
i.e. Fa.
 No minima were found with respect to n, h2 and U2.

1
33

A comparison of the above equations with the work of Antar and


Zubair [5] clearly shows that, due to the presence of the feedwater
heater unit conductance ratio (GOFH) term, Eqs. (31) and (32) do not
reduce to mere dependence on GL. Now, we use the same values for
_ as used by Antar and Zubair [5], for our example
TH, cL, n and W;
(See Fig. 7(a)(c)). It should be noted that, in power systems, the
unit cost of the boiler (cH) would be higher than the other heat
exchangers. Therefore, it is appropriate to focus on values less than
unity for GOFH in our investigation. It is noted that, in Fig. 7(a)(c),
compared to Antar and Zubair [5], the total conductance curve is
slightly asymmetric. This is due to the fact that the conductance
of the feedwater heater is larger than the other heat exchangers
and varies non-linearly with GL. The difference at the ends is
1.32 kW/K when GOFH is unity; though it increase to 4.25 kW/K at
GOFH = 0.1. See Table 1 for a more detailed comparison. It is also
noted that when all unit cost ratios are at unity, the minimum total
conductance is also obtained at unity. The reason is that, in this
case, the unit cost of each heat exchanger becomes the same which,
in turn, results in all conductances inuencing the total cost (See Eq.
(1) by equal weightage. Another observation is that, as GOFH
decreases, the minimum of the total conductance required
increases and that it is obtained at lower values of GL. These variations are found to be non-linear such that when GOFH decreases
from 1 to 0.5, there is only a 0.88% increase in the minimum total
conductance while it increases by 5.7% when GOFH decreases from
0.5 to 0.1.
4. Conclusions
The optimization problem studied for power cycles with one
feedwater heater has two signicant minima i.e. h1 and U1. Some
important conclusions are as follows:
 Since the F-value is based on an endoreversible power cycle, for
specied temperatures and ow rates, it predicts the minimum
initial heat exchanger cost.
 All cost functions displayed a minimum for the parameter h1
that was the same for all cases. Only the value of the cost functions was different.

Acknowledgements
The authors acknowledge the support provided by King Fahd
University of Petroleum & Minerals through the project IN121042.

References
[1] The Babcock & Wilcox. Steam: its generation and use. 41st ed. Babcock &
Wilcox Company, 2005.
[2] Cengel YA, Boles MA. Thermodynamics: an engineering approach. 7th
ed. McGraw-Hill Inc.; 2010.
[3] Bejan A. Theory of heat transfer-irreversible power plants. Int J Heat Mass
Transf 1988;31:12119.
[4] Bejan A. Power and refrigeration plants for minimum heat exchanger
inventory. J Energy Resour Technol 1993;115:14850.
[5] Antar MA, Zubair SM. Thermoeconomic considerations in the optimum
allocation of heat exchanger inventory for a power plant. Energy Convers
Manag 2001;42:116979.
[6] Sahin B, Kodal A. Performance analysis of an endoreversible heat engine based
on a new thermoeconomic optimization criterion. Energy Convers Manag
2001;42:108593.
[7] Kodal A, Sahin B. Finite size thermoeconomic optimization for irreversible heat
engines. Int J Therm Sci 2003;42:77782.
[8] Chen L, Sun F, Wu C. Maximum-prot performance for generalized irreversible
Carnot-engines. Appl Energy 2004;79:1525.
[9] Bandyopadhyay S, Bera NC, Bhattacharyya S. Thermoeconomic optimization of
combined cycle power plants. Energy Convers Manag 2001;42:35971.
[10] Rovira A, Snchez C, Muoz M, Valds M, Durn MD. Thermoeconomic
optimisation of heat recovery steam generators of combined cycle gas turbine
power plants considering off-design operation. Energy Convers Manag
2011;52:18409.
[11] Baghernejad A, Yaghoubi M. Exergoeconomic analysis and optimization of an
Integrated Solar Combined Cycle System (ISCCS) using genetic algorithm.
Energy Convers Manag 2011;52:2193203.
[12] Ahmadi P, Dincer I. Thermodynamic analysis and thermoeconomic
optimization of a dual pressure combined cycle power plant with a
supplementary ring unit. Energy Convers Manag 2011;52:2296308.
[13] Kaviri AG, Jaafar MNM, Lazim TM. Modeling and multi-objective exergy based
optimization of a combined cycle power plant using a genetic algorithm.
Energy Convers Manag 2012;58:94103.
[14] Silveira JL, Tuna CE. Thermoeconomic analysis method for optimization of
combined heat and power systemspart II. Prog Energy Combust Sci
2004;30:6738.
[15] Al-Sulaiman FA, Dincer I, Hamdullahpur F. Thermoeconomic optimization of
three trigeneration systems using organic Rankine cycles: Part I
Formulations. Energy Convers Manag 2013;69:199208.
[16] Al-Sulaiman FA, Dincer I, Hamdullahpur F. Thermoeconomic optimization of
three trigeneration systems using organic Rankine cycles: Part II
Applications. Energy Convers Manag 2013;69:20916.

B.A. Qureshi et al. / Energy Conversion and Management 86 (2014) 379387


[17] Abusoglu A, Kanoglu M. Exergoeconomic analysis and optimization of
combined heat and power production: a review. Renew Sustain Energy Rev
2009;13:2295308.
[18] Xiong J, Zhao H, Zheng C. Thermoeconomic cost analysis of a 600 MWe oxycombustion pulverized-coal-red power plant. Int J Greenh Gas Control
2012;9:46983.
[19] Bassily AM. Numerical cost optimization and irreversibility analysis of the
triple-pressure reheat steam-air cooled GT commercial combined cycle power
plants. Appl Therm Eng 2012;40:14560.
[20] Rosen MA, Dincer I. Thermoeconomic analysis of power plants: an application
to a coal red electrical generating station. Energy Convers Manag
2003;44:274361.

387

[21] Silveira JL, Tuna CE, de Queiroz Lamas W, Aparecida de Castro Villela I. A
contribution for thermoeconomic modelling: a methodology proposal. Appl
Therm Eng 2010;30:173440.
[22] Seyyedi SM, Ajam H, Farahat S. A new approach for optimization of thermal
power plant based on the exergoeconomic analysis and structural
optimization method: application to the CGAM problem. Energy Convers
Manag 2010;51:220211.
[23] Durmayaz A, Sogut OS, Sahin B, Yavuz H. Optimization of thermal systems
based on nite-time thermodynamics and thermoeconomics. Prog Energy
Combust Sci 2004;30:175217.

Anda mungkin juga menyukai