Anda di halaman 1dari 4

SL.

NO

ITEM

DATA SHEET
UNITS
11kV VCB PANEL

1.0

General Particulars

1.1

Manufacture Name

Excel Power Switchgear

1.2

Applicable Standard

IEC 62271-100

1.3

Degree of Protection

IP4X

1.4

Overall Dimension for each switchgear


cubicle(Length x Depth x Heigth)

mm

1.5

Minimum clear draw out space required

mm

1200X1600X2175
1000

2.0

Construction feactures safety interlocks and


accessories provided as speccified
If No give details
Busbars

2.1

Material

Copper

2.2

Bare/Insulated

Insulated

2.3

Minimum clearance
(a) Phase to Phase
(b) Phase to Earth

1.7

2.4

Yes/No

mm
mm

Continuous current rating under site


conditions

Yes

130
80

As per specification

2.5

Temperature rise over design ambient


temperature for current rating as per 2.4

2.6

One second current rating

kA

25kA

2.7

Dynamic current withstand rating

kA

62.5kA peak

2.8

Voltage class of supporting and through


Bushings

kV

12kV/28kV/75kV

3.0

Circuit Breakers

3.1

Standard to which manufactured

IEC 62271-100

3.2

Type designation

EPS-C-11

3.3

Rated voltage and frequency

12kV,50Hz

3.4

Maximum Continuous Voltage

kV

12kV

3.5

Rated continuous current

As per specification

1/4

Less than 65 deg

SL.NO

ITEM

UNITS
11kV VCB PANEL
As per specification

3.6

Current Rating under site conditions

3.7

Maximum Temperature rise above specified


design ambient temperature when carrying
rated current as 3.7 above

3.8

Rated symmertrical interrupting current

kA

25kA

3.9

Making current capacity

kA

62.5kA peak

3.10

One second current carrying capacity

kA

25kA

3.11

3 Phase symmetrical interrupting capacity at


rated voltage

3.12

Power frequency withstand voltage

kV

28kV

3.13

Impulse withstand voltage for 1.2/50


Sec.Full wave

kV

75kV

3.14

Duty cycle of breaking capacity

3.15

Total interrupting time measured from trip


coil energisation

Cycle

3.16

Total interrupting time measured from


closing coil energisation

Cycle

3.17

Number of breaks per phase

3.18
a
b

Minimum clearance
Between poles
In air between live parts and earth

3.19

Switching over voltages generated by circuit


breaker when switching OFF Transformer at line to earth
no load
Not Applicable

3.20

Each breaker truck provided with a 'TEST'


position in addition to FULLY DRAWN OUT
and IN positions

3.21
a
b
c
d
e

Main contacts
Type
Material
Silver facing provided
Thickness of the facing
Design control pressure

3.22
a
b
c
d
e

Arcing Contacts
Type
Material
Silver facing provided
Thinkness of the facing
Design contact pressure

3.23

Electrical anti pumping feature provided

Less than 65 deg

MVA

500MVA

O-0.3sec-CO-3min-CO

no
mm
Per Unit
Peak

less than 3

less than 5
1

130mm
80mm

Yes/No
Yes

Butt Contact
Cu Cr
Yes/No Yes
mm
8 to 12 micron
Kg/mm*2 227Kg
Not Applicable

Yes/No
micron
Kg/mm*2
Yes/No
2/4

Yes

SL.NO

ITEM

UNITS
11kV VCB PANEL

3.24

Type of closing mechanism

Motor operated spring charged


electrical spring release coil

3.25

Method of closing during power failure

manual spring charging


mechanical close push button

3.26

Closing coil consumption at rated voltage

Watts

220Watts

3.27

Trip coil consumption at rated voltage

Watts

220Watts

3.28

Number of auxilary contacts

8 N/O + 8 N/C

3.29

Spring Charging meachanism

Motor operated spring charged


electrical spring release coil

3.30
a
b
c

Spring charging Motor


Rating
Watts
Speed
RPM
Class of insulation
Time required to charge the spring from fully
Sec.
discharged condition
Overload and short circuit protection
particulars

d
e

80Watts
7400RPM
As per standard
5 Sec.
HRC fuse

5.0

Current Transformers

5.1

Type(bar/wound/any other)

wound

5.2

Standard applicable

IS 2705

5.3

Class of Insulation

12kV/28kV/75kV

5.4

System Voltage and Frequency

5.5

Ratio

5.6
a
b

Burden
For protection
For Metering

VA
VA

15VA
15VA

5.7
a
b

Accuracy class
For protection
For Metering

VA
VA

5P10
CL 1

5.8

Short time current and duration

kA,Sec.

as per manufacturer's standard

5.9

Dynamic Rating

kA(peak)

as per manufacturer's standard

6.0

Voltage Transformers

6.1

Type

kV,Hz

11kV,50Hz
As per specification

Draw out
3/4

SL.NO

ITEM

UNITS
11kV VCB PANEL

6.2

Standard applicable

IS 3156

6.3

Type of Insulation

Resin cast

6.4

Ratio

11kV/RT3/110V/RT3

6.5

Connection

Star/Star

6.6

Rated output burden 1 -Phase

100VA

6.7

Rated Accuracy

VA

6.8

HV Fuse rating

6.9

HV Fuse rupturing capacity

6.10

LV Fuse rating

6.11

LV Fuse rupturing capacity

6.12

type of LV Fuse (cartride/Diazo)

HRC

6.13
a
b

Rated Voltage factor


Continuous
30 seconds

1.2 for continuous


1.5 for 30 sec

6.0

Relays(Type and Make)

6.1

Trip Relay(86)

JVS/JRV181

6.2

Numerical Comprehensive Protection relay


for O/C,E/F,Timer and Trip Supervision

Mikro/MK2200

6.4

Relay draw out type

Non draw out

6.5

Test Plugs/Terminals provided

Not provided

7.0

Drawings

7.1

Drawings submitted along with the bid

8.0

Test Certificates

8.1

Type test copies furnished with the bid

MVA
A
MVA

4/4

CL 1
3A
As per standard
4A
As per standard

Yes/No

Yes

Yes/No

Yes