TRANSMISSION
Evaluation of the percentage voltage
unbalance seen by the load will give an
indication of the maximum impedance
mismatch of the phase conductors
that can be tolerated before the 2%
unbalance limit of NRS 048-2 [6] is
exceeded.
Results for the solution of the network of
Fig. 3 using impedance and voltage values
from Table 1 are shown in Table 2.
Fig. 2: Simplified network model used to study circulating currents due to
mismatched phase impedances on an MV feeder.
Symbol
22 kV
11 kV
Comment
12,7 kV0
6,35 kV0
Phase-to-neutral voltages
Line
impedance
ZL1 = ZL2
0,5 /km50
0,5 /km50
ZL0
1,6 /km70
1,6 /km70
Source / Trfr
ZT1 = ZT2
4,84 90
1,21 90
Assume 10 MVA, Z
= 10%
EG transformer
ZT1 = ZT2
7,26 90
1,82 90
Source
ZT0
6,53 90
1,63 90
Source
earthing
impedance
ZNER0
17,5 0
8,75 0
EG earthing
impedance
ZNER0
35 0
17.5 0
Case 1: Standard
360 A NER
350 0
175 0
Case 2: 36 A NER
Load
impedance
ZLD1 = ZLD2*
96,8 0,131 A
24,20,
262 A
48,4 0,
262 A
N/A
*Assume ZLD1 = ZLD2 for resistive loads. For motor loads ZLD1 < ZLD2
TRANSMISSION
360 A NER at EG facility
36 A NER at EG facility
Voltage level
Network load
3I0 (A)
VS2/VS1 (%)
3I0 (A)
VS2/VS1 (%)
22 kV
10 MVA
2,13
0,93
0,32
0,93
22 kV
5 MVA
1,14
0,49
0,17
0,49
11 kV
5 MVA
3,87
1,77
0,60
1,77
Table 2: Circulating 3I0 current and voltage unbalance due to multiple MV neutral earths.
Conclusion
I t i s p r e f e r r e d t h a t M V- c o n n e c t e d
embedded Generators do not provide a
point of neutral earthing to the networks to
which they connect. In cases where the EG
facility requires an MV neutral earth, and
where the EG facility is distant from the
source substation, the problems associated
with multiple neutral earthing can be
overcome by switching the EG neutral
earth when required.. This paper served
to investigate aspects of an alternative
neutral earthing option: that of applying
a permanent high resistance earth at the
EG facility. The high resistance earthing
philosophy requires that sensitive earth
fault protection be provided for times of
islanded EG operation. This typically requires
specialised, and sometimes directional,
protection that is largely redundant during
times when the facility operates in parallel
with the grid. Equally, the advantages of
high resistance earthing are not available
during times of grid-connection. Overall,
protection of the EG facility in islanded- and
grid-supplied modes presents a number of
challenges that may be overcome using
modern protection relays, but which may
be more complex and more costly than
the alternative of switching the EG facilitys
neutral earth.
Acknowledgements
The author acknowledges assistance from
Hendri Geldenhuys, Olaf van Abo, and Dave
Duncan. This paper was presented at the
Southern African Power System Protection
Conference 2008 and is reprinted with
permission.
References
[1] A N S I / I E E E S t a n d a r d 1 4 2 - 1 9 8 2 : I E E E
Recommended practice for Grounding of
Industrial and Commercial Power Systems.
IEEE Green Book, p.25.
[2] Eskom Distribution Standard SCSASACB6 Rev.0,
Medium voltage system earthing practice.
[3] Eskom Distribution Standard 34-1765 Rev.0,
Distribution Standard for the interconnection
of Embedded Generation.
[4] Energy Networks Association (UK), Engineering
Technical Report 113 Rev 1 - 1995: Notes of
Guidance for the Protection of Embedded
Generating Plant up to 5 MW for Operation
in Parallel with Public Electricity Suppliers
Distribution Systems, energynetworks.org.
[5] C F Wagner & R D Evans, Symmetrical
Components, McGraw-Hill Book Company,
London, 1933, pp. 377-9.
[6] NRS 048-2: 2003, Electricity supply Quality
of supply Part 2: Voltage characteristics,
compatibility levels, limits and assessment
methods.
[7] F Sautriau. Neutral earthing in an industrial HV
network, Merlin Gerin Technical Specification
No. 62, April 1996. Downloaded from www.
technical-publications.schneiderelectric. com,
August 2008.
[8] S van Zyl. Protection-class Current Transformer
accuracy in the load current range, Presented
at the 2008 Southern African Power System
Protection Conference, Midrand, 12 14
November 2008.
[9] Alstom T&D. Network Protection & Automation
Guide. First edition, pp.344-5, 2002.