80801.3.0
Preface
PV Powered
Contact Information
PV Powered, Inc.
150 SW Scalehouse Loop
Bend, OR 97702
Tel: 541-312-3832
Customer Service and Technical Support: 1-877-312-3832
Fax: 541-383-2348
www.pvpowered.com
email: support@pvpowered.com
PREFACE
PV Powered designs, manufactures, and markets the solar power industrys most
reliable photovoltaic solar inverter solutions. Weve assembled a highly experienced
solar power electronics design team. Our vision is to spur the widespread adoption and
success of solar power, by assisting our distributors, dealers and installers in this dynamic
market while ensuring that our products are the best supported, easiest to install, and
most reliable solar inverters in the industry. Our innovative approach to performance
monitoring provides secure and easy access to system performance and inverter status
over the Internet.
DANGER
WARNING
The Warning statement is used to inform the installer/operator of a situation requiring serious attention. Failure to heed this warning may result in serious injury or death to personnel and destruction of equipment.
CAUTION
The Caution statement is used to inform the installer/operator of a situation requiring attention. Failure to heed this Caution may result in injury to personnel and damage
to equipment.
ii
A/D
ANSI
CFM
DSP
EMI
Electromagnetic Interference
ESD
GFDI
IEEE
IGBT
LOTO
Lockout Tagout
MCM
MPPT
NEC
NFPA
PCB
PLL
PPE
PV
Photovoltaic
PWM
VFD
iii
Document Copyright
Grid Tied Residential Inverter Installation and Operations Manual (Models 1100, 2000,
2500, 2800, 3000, 3500, 4600, 4800, 5200) 2008 PV Powered. All rights reserved.
This manual may not be reproduced or distributed without written permission from PV
Powered.
iv
Table of Contents
4. Operations ....................................................................................................................17
4.1 Start Up Procedures .....................................................................................................17
4.2 Inverter Front Panel Status Indicators ........................................................................18
5. Maintenance and Troubleshooting .............................................................................21
5.1 Red and Green LED Lights ON ..................................................................................21
5.2 Ground Fault ................................................................................................................21
5.3 Displayed Fault Codes .................................................................................................22
6. Limited Warranty ........................................................................................................25
6.1 Term of Coverage ........................................................................................................25
6.2 Coverage ......................................................................................................................25
6.3 What is Not Covered....................................................................................................26
6.4 Disclaimer and Limitation of Liability ........................................................................26
6.5 Arbitration ....................................................................................................................27
6.6 Miscellaneous Provisions ............................................................................................28
7. Return Procedure.........................................................................................................29
7.1 Information about Your System ...................................................................................29
Appendix A- Specications ...............................................................................................31
Index ..................................................................................................................................33
TABLE
of CONTENTS
3. Installation ......................................................................................................................5
3.1 Mounting and Anchoring ...............................................................................................5
3.2 Electrical Connections ...................................................................................................7
Faulted .............................................................................................................22
Starting Up From a Faulted State ....................................................................22
AC Voltage High/DC Voltage Low Fault ........................................................23
Power Low Fault .............................................................................................23
Table 3-1
Table 3-2
Table 3-3
Table 3-4
vi
The PV Powered Grid Tied Residential Inverters is a utility interactive inverter for
photovoltaic (PV) systems.
The inverter is tied to an electrical source provided by the local utility company as well
as to the PV system. The inverter contains everything needed to convert the DC voltage
generated by the PV arrays into the AC voltage required to power a house.
This manual provides information necessary for the successful installation and use of the
PV Powered Grid Tied Residential Inverters.
1.1 General Safety
IMPORTANT SAFETY INSTRUCTIONS: This product has been engineered and manufactured to ensure your personal safety. Improper use may result in potential electrical
shock or burns. Read and follow all instructions for installation, use and servicing of
this product. Read all safety warnings before installing or operating the inverter.
CAUTION
Before connecting the inverter to the electrical utility grid, your utility
company must grant approval. Only qualied electricians should make the
connection.
When exposed to light, photovoltaic (PV) arrays create electrical energy that
could cause a hazardous condition. To avoid this, completely cover the surface
of all PV arrays with opaque (dark) material before wiring them.
Do not touch the heat sink located at the top of the inverter, temperatures can
exceed 158F (70oC).
1. INTRODUCTION
& SAFETY
NOTE: A locking tab has been designed into Grid Tied Residential Inverters
It is the sole responsibility of the end user to provide a locking
mechanism that utilizes the tab and secures the cover on the
inverter.
CAUTION
Read all safety warnings and instructions before installing or operating the inverter.
2. Planning
The inverter is suitable for both indoor and outdoor installation; the inverter
enclosure has a NEMA 3R rating.
The optimum location of the inverter is outside, shielded from direct exposure to sunlight (i.e. not on the south facing side of the building).
The heat sink temperatures can exceed 158F (70oC). The inverter must be
installed so that people will not touch the top of the unit.
The following clearances are recommend for proper placement of the inverter:
A minimum of 36 inches between the bottom of the inverter box and the
ground.
Visibility of the operating LEDs and display located at the top front of the
inverter box should also be considered.
If the inverter is installed in an enclosed space, adequate ventilation must be
provided.
2. PLANNING
WARNING
Before drilling holes to mount the inverter, verify that there are no electrical wires or
plumbing in the area
3. Installation
1. Locate the wall studs in the desired location and align the mounting bracket over the
studs. Mark the mounting holes. Ensure that locations A and B (see Figure 3-1) are
aligned over the wall studs.
2. VERIFY THE BRACKET IS LEVEL. Ensure points A and B are aligned with the wall
studs. Drill 1/8 pilot holes for the screws.
Use heavy-duty 1/4 inch x 2 inch coarse thread lag screws to secure points A and
B to the wall.
Use an 1/8 screw to secure point C (see Figure 3-1).
3. Carefully hang the inverter on the upper part of the bracket. The hooks located at the
rear of the inverter should hang over the bracket.
4. Verify inverter is level.
5. For the PVP4600, PVP4800, or PVP5200 models, remove the four screws on the lower
lid to access the electrical connections.
6. Locate the two inverter mounting holes below the power board (see Figure 3-2).
Insert the two mounting screws through the inverter and tighten securely.
3. INSTALLATION
There are no user serviceable parts in the upper portion of the inverter.
1. Locate the wall studs in the desired location and align the mounting bracket over a single
stud. Mark the mounting holes ensuring holes C, D, E and F are directly over the single
stud (see Figure 3-2).
2. VERIFY THE BRACKET IS LEVEL. Ensure points C through F are aligned with the
wall studs. Drill 1/8 pilot holes for the screws.
Use heavy-duty 1/4 x 2 coarse thread lag screws to secure points C through F to
the wall.
Use an 1/8 screw to secure points A and B (See Figure 3-2).
E
F
Mounting Hole
3. Carefully hang the inverter on the upper part of the bracket. The hooks located at the rear
of the inverter should hang over the bracket.
4. Verify inverter is level.
5. Remove the front cover of the inverter by unscrewing the four cover screws located
around the front perimeter of the inverter.
6. Locate the inverter mounting hole below the power board (see Figure 3-3). Insert the
mounting screw through the inverter and tighten securely.
NOTE: Leave the inverter cover off to allow for electrical connection
described in 3.2 Electrical Connections.
CAUTION
The National Electrical Code (NEC) requires that the inverter be connected to a
dedicated circuit with no other outlets or devices connected to the same circuit.
See NEC Section 690-64(b)(1). The NEC also places limitations on the size of the
inverter and the manner in which it is connected to the utility grid. See NEC Section
690-64(b)(2).
To reduce the risk of re, connect the inverter to the appropriate size breaker (See
Table 3-1 for required branch circuit protection). Maximum branch-circuit overcurrent protection calculated in accordance with the National Electrical Code (NEC),
ANSI/NFPA 70.
Inverter Model
PVP1100
PVP2000
PVP2500
PVP2800
PVP3000
PVP3500
PVP4600
PVP4800
PVP5200
2 pole 15A
2 pole 20A
2 pole 20A
2 pole 20A
2 pole 20A
2 pole 30A
2 pole 30A
2 pole 30A
The inverter is factory-calibrated to the voltage and frequency limits specied in Table
3-2. This adjustable range can be set by PV Powered eld technicians.
Condition
Factory
Setting
132.0
105.6
144.0
60.0
264.0
Adjustable Range
(VAC) Models 2500,
3500, 4600, 4800, 5200
132.0 - 138.0
99.6 - 105.6
144.0 - 150.0
54.0 - 60.0
Adjustable Range
(VAC) Models 1100,
2000, 2800, 3000
132.0 - 142.0
95.6 - 105.6
144.0 - 156.0
< 60.0
Maximum
Trip Time(s)
< 1 second
< 2 seconds
< 160ms
< 160ms
211.0
228.8
183.0
59.3 Hz
60.5 Hz
n/a
n/a
< 160ms
< 160ms
Do not proceed with the electrical connection of the inverter until it has been properly
mounted.
WARNING
WARNING
Make sure the main breaker in the main utility breaker box is switched OFF before
wiring the inverter. This breaker should be switched ON only after all wiring has been
completed as described in this manual.
WARNING
Follow the order listed below to wire the inverter. Failure to do so may result in
hazardous voltages or disconnection of contacts.
IMPORTANT: When mounting the inverter outside, use rain-tight or wet-location conduit
hubs that comply with the requirements in the Standard for Fittings for Conduit and Outlet
Boxes, UL 514B.
Terminal connections for the inverter are located inside the inverter on the circuit board at
the bottom of the cabinet. The AC and DC terminals accept wires up to 6 AWG.
CAUTION
The input and output circuits are isolated from the enclosure. System grounding,
when required by Sections 690-41, 690-42, and 690-43 of the National Electric Code
(NEC), ANSI/NFPA 70-1999, is the responsibility of the installer.
Separation of Circuits
The lower part of the inverter circuit board is divided into three sections:
1. The left side is dedicated to the low voltage DC communications.
2. The center is dedicated to the AC.
3. The right side is dedicated to the DC.
Each section has two to three knockouts. UL 1741 standard requires a straight run of
wire, with no loops or crossover to the other circuits (sections) and low voltage versus
high voltage in each section.
1. Left knockouts (up to the divider) are for low voltage communications only
(PVM1010 Data Monitoring Module).
2. Center knockouts are for AC.
3. Right knockouts are for DC.
Grounding
A single-point ground connection is located in the lower right-hand side of the inverter
cabinet. This is where the PV array grounding wire is terminated. The AC ground
connection is terminated next to the Line 1 and Line 2 connections on the circuit board.
The PV ground connector is attached to the cabinet with a 10-32 bolt. This ground lug is
provided to allow for the PV safety ground to be bonded to the cabinet. This is the only
place the PV ground should be connected to the inverter.
Do not tie the safety ground to the PV array positive or negative. That would defeat
the PV ground fault protection circuit. Refer to Figure 3-8 for additional information.
See Table 3-3 for appropriate sizing of the grounding electrode. Use the maximum
current AC or DC - whichever is larger - and multiply it by 1.25 to get the maximum
current rating per NEC 690.
Maximum
Current Rating
15
20
30
40
60
8
8
8
8
8
Aluminum
Copper Clad
6
6
6
6
6
10
Control pcb
GF Detect Circuit
PV
DC input
120/240 VAC
60Hz
1A
Line
Filter
L1
20 A SB
DC
Power
Supply
PV GND
L2
GND
GND
The purpose of the Ground Fault Interrupter (GFI) circuit is to detect a ground fault
(unintended current ow from the PV arrays to earth ground).
For the GFI circuit to function as designed, the PV array safety ground must be connected only at the ground terminals provided.
Bonding the safety ground to the grounded leg of the array anywhere but through the
inverter will bypass the GFI circuit. This creates an unsafe operating condition.
The GFI works by using a fuse to connect or bond the PV array negative (or the PV
array positive if using a positively grounded array) to earth ground through the 1A
fuse.
If current is greater than 1A between the grounded array terminal and the earth
ground, the fuse will blow. A blown or open fuse will disconnect the PV arrays
from their ground reference and interrupt the ground fault current. In this situation,
the inverter will cease operation and display a fault message as shown in Figure 3-7.
11
If the inverter displays Ground Fault, turn OFF the AC and DC to the inverter and refer to
the fault examples in this manual.
PV Ground
WARNING: Replace the GFI fuse with the same type and rating of
Replace the GFI fuse with the same type and rating of fuse. The inverter uses only
Littelfuse KLKD001 1A/600V.
The inverter is connected to the electrical grid using 3 wires - LINE 1, LINE 2 and
GROUND.
WARNING
Ensure the main 240V (or 208V for the PVP2800 and PVP4600 or 120 for PVP1100
or PVP1100EVR) breaker at the circuit breaker panel is switched OFF before connecting to the AC terminal block.
To wire the inverter to the main utility grid, follow these steps and refer to Figure 3-9:
1. Run the conduit from the main breaker panel to the bottom of the inverter. Insert the
tting in the center opening of the inverter and fasten it with a locking nut.
2. Feed the LINE 1, LINE 2 and GROUND wires through the conduit and into a center
opening of the inverter.
3. Connect the GROUND wire to the terminal marked earth ground inside the
inverter.
4. Connect the LINE 2 wire to the terminal marked line 2 inside the inverter.
5. Connect the LINE 1 wire to the terminal marked line inside the inverter.
6. Ensure all connections are wired correctly and properly torqued. Tighten the terminal block screws to 0.5 Nm (0.37 ft/lb).
NOTE: In the PVP1100 units. Line 1 wire is the only phase voltage wire.
LINE 2 is neutral and LINE 3 is the AC GROUND.
Figure 3-9 AC Wiring for the Line 1, Line 2 and Ground Wires
13
WARNING
Before proceeding with the DC wiring, completely cover the surface of all PV panels
with dark material to avoid the production of electrical current.
WARNING
Make sure the polarity and the PV panel voltage between the positive and the negative cable connectors of the PV panels are correct before connecting the panels to the
DC terminal block on the power distribution board.
The PV array open circuit voltage should be at or below the listed voltages in Table 3-4
under all circumstances. Each DC input to the DC terminal block must be less than the
voltages listed in Table 3-4.
Inverter
Model
Maximum Inverter
Start Voltage
Absolute Maximum
Input Voltage
PVP1100
450VDC
500VDC
PVP2000
450VDC
500VDC
PVP2500
450VDC
500VDC
PVP2800
450VDC
500VDC
PVP3000
450VDC
500VDC
PVP3500
450VDC
500VDC
PVP4600
450VDC
500VDC
PVP4800
450VDC
500VDC
PVP5200
450VDC
500VDC
The PV array open circuit voltage should be at or below 500 VDC under all
circumstances. Each DC input to the DC terminal block must be less than 500 VDC.
DC Connections
Each DC input connection must carry the same input voltage. The inverter allows up to
three connections for both the positive and negative poles.
To wire the DC inputs from the PV array to the inverter (see Figure 3-11):
1. Calculate the maximum open circuit voltage (Voc) for each series of modules based
on the VOC_TC, in accordance with the expected lower temperature, and accepted
industry practice.
14
NOTE: For all temperature conditions, the Voc for each series
connection must total less than the VDC indicated in Table
3-4 for all residential inverter models.
Review the PV panels data sheet for operating temperature ranges.
2. Keep track of the array positive and negative leads and mark them clearly.
3. Route the PV array leads through the far right opening in the inverter.
4. Connect each series positive DC lead to the positive terminals of the power
distribution board.
WARNING
5. Connect the negative DC leads directly to the negative terminal on the power
distribution board.
6. Connect the ground wire(s) to the ground lug.
WARNING
Do not connect or disconnect the jumper while the inverter is supplied with
DC or AC power.
7. Remove the 1A fuse and select the negative or positive grounding jumper included
with the inverter (see Figure 3-10).
Positive ground
jumper has a
red wire
Negative ground
jumper has a
black wire
8. Install the grounding jumper (see Figure 3-11) with the white wire on the right into
connector J3 on the power board.
15
Fuse Clips
PV Negative
PV Positive
9. Conrm that the DC disconnect is turned OFF and remove the material from the array.
10. With a voltmeter, check the PV array positive leads in the DC disconnect and conrm
that the voltage is positive when referenced to the negative leads. The reading should
match your series Voc total.
11. Measure the DC voltage potential between the two fuse clips (see Figure 3-11) for the
1A fuse.
12. The voltage should be less than 25 volts absolute value. The DC and AC disconnects
can be turned OFF and the 1A fuse installed.
If the voltage is outside of this range (-25V to 25V), wait 10 minutes and check
again.
If (after 10 minutes) the voltage is still not in the range of -25V to 25V, check for
a ground fault or other incorrect wiring.
If the problem persists, contact PV Powered Technical Support at
1-877-312-3832.
16
4. Operations
Before turning on the inverter, ensure that the front panel is closed properly.
WARNING
The heat sink can reach temperatures in excess of 158F (70C). Do not touch the heat
sink when in use, and do not place anything on top of the heat sink.
4.1 Start up Procedures
To start up the inverter, complete the following steps in the order indicated:
1. Turn the AC breaker ON.
2. Verify that the RED LED light is illuminated.
3. Verify the PV is wired in accordance with the grounded scheme (either positive or
negative). Conrm that the PV array open circuit voltage is at or below the level
specied in Table 3-4.
4. Turn the DC disconnect ON.
17
4. OPERATIONS
WARNING
The inverter has two LED indicator lights visible through the upper left corner of the
front panel. These lights indicate the inverters status.
If the inverters operating environment is safe to export power into the AC grid, the
GREEN LED is illuminated.
If the operating environment moves outside the safe operating limits governed by UL
1741, IEEE 1547, and IEEE 519, the RED LED indicator is illuminated.
When clouds reduce the amount of available sunlight or when portions of the PV
array are covered with debris.
Any time the DC output from the PV array drops below the inverters minimum DC
operating voltage, the inverter turns OFF.
When the array is once again exposed to enough sunlight, the GREEN LED illuminates,
the inverters auto-start feature begins, and after ve minutes the inverter begins to export
power.
18
If the RED LED continues to illuminate when there is sufcient sunlight for operation,
verify that no wiring connections are loose. If the wiring is tight, see 5. Maintenance and
Troubleshooting for additional information.
The vacuum uorescent display (VFD) indicates the inverters status and real-time
power output into the AC Grid. This display provides the following information:
19
The display will change screens every two seconds to show a different set of information
as shown in Figures 4-1 and 4-2.
PVP 3500
Start in 269 sec
0 Watts
3212 kWh
240 VAC
297 VDC
Screen 1
Screen 2
Screen 3
PVP 3500
1245 Watts
3212 kWh
241 VAC
255 VDC
Screen 1
Screen 2
Screen 3
If a fault occurs, the display also provides a corresponding fault code. Refer to
5. Maintenance and Troubleshooting for additional information.
20
The RED LED illuminates any time the DC voltage is below the inverters startup
DC voltage, such as at night. The RED LED blinks if the inverter has had a fault
condition, and the vacuum uorescent display (VFD) displays a fault code. Possible
faults are listed in Table 5-1.
2. The light on the right is a GREEN LED.
A ground fault happens because the grounded conductor of the PV array is broken
in the DC disconnect. Ground faults are typically caused by a pinched wire connecting some part of the array or DC wiring to earth ground.
A less likely cause is limited to multiple inverter installations, when the array
strings are mismatched.
Example: Inverter A has the positive from array 1 and the negative from
array 2.
21
5. MAINTENANCE
& TROUBLESHOOTING
The GREEN LED illuminates any time the DC voltage is above the inverters
DC start voltage and all operational parameters are met. When the GREEN light
illuminates, the inverter tries to invert power from the PV array.
3. Check for continuity (ohms). It should be zero or 1-2 ohms. If the meter indicates no
continuity, then a ground fault likely exists.
4. If the fuse is blown, replace it with a like fuse rated at 600VDC and 1A. DO NOT
insert the new fuse until there is no ground fault present.
5. Check the DC voltage between the grounded terminal of the array and earth ground.
The voltage should be less than 25 volts with the GFI fuse removed. If the voltage is
higher than that, check the array wiring (there may be a ground fault). For the best
results, perform this test with the DC disconnect ON and OFF. If you are not comfortable conducting this test, DO NOT ATTEMPT IT.
6. Make sure the grounded leg of the PV array is not broken in the DC disconnect.
0 Watts
1400 kWh
Screen 1
267 VAC
300 VDC
Screen 2
Screen 3
PVP 3500
Start in 269 sec
Screen 1
Screen 2
0 W
1400 kW-hr
240 VAC
300 VDC
Screen 3
Screen 4
22
NOTE: In this case the fault refers to the last fault detected.
If the inverter is in a faulted state, the RED LED blinks and the VFD scrolls through the
screens shown in the faulted example above. The text of the fault describes the specic fault
condition that the inverter experienced.
If the inverter is no longer experiencing the condition that caused it to fault (e.g. the AC
voltage climbs above 264V then drops below 264V), the RED LED stops blinking and the
inverter starts the ve minute count-down timer. During these ve minutes, the display will
also show the last fault.
Multiple Faults
If the inverter detects multiple faults at one time, the inverter displays the text of the rst
fault detected.
For multiple faults, the numerical values of the fault codes are added as shown in Figure 5-3.
Figure 5-3 displays the AC Voltage High fault (1000 0400), plus a DC Voltage Low fault
(1000 0020). This might occur at night, when the panel voltage is low (because of darkness)
and the utility voltage was above the limits dened in Table 3-2.
Figure 5-4 shows a Power Low fault. After the fault occurrence, the inverter had a DC
Voltage High fault. In this case, the display added the fault codes 0200 0000 plus 1000 0040
to become 1200 0040.
If the faults have the same rst digit (such as 1000 XXXX) the 1 remains the same and only
the second block of four numbers will add to the original fault code.
WARNING
These servicing instructions are for qualied personnel only. To reduce the risk of
electric shock, do not perform any servicing other than that specied in the operating
instructions unless you are qualied.
23
Fault Codes
Fault Code
VFD Text
Fault Description
8000 0000
Power Module
4000 0000
Power Module
1000 0800
PLL Fault
The inverter was unable to match the grid frequency. This is usually
caused by an unstable power grid.
1000 0400
AC Voltage High
1000 0200
AC Voltage Low
1000 0100
AC Freq Low
1000 0080
AC Freq High
1000 0020
DC Voltage Low
The DC voltage is below the startup voltage. This fault is only seen in
conjunction with another fault (ex. 1000 0220 is an AC low and a DC
low fault). DC could be low because of low light conditions or the DC
disconnect is turned off.
1000 0010
DC Voltage High
1000 0002
1000 0001
Power Supply +5
0400 0000
Ground Fault
The inverter detected that the GFI fuse is blown. This fault requires an
AC power cycle to reset.
0200 0000
Power Low
The inverter shut down because it was producing less than 60W for 5
minutes. It will try to restart in 10 minutes.
0100 0000
CPU Fault
0040 0000
Over Current
Safety protection.
0020 0000
Pre-charge
0004 0000
Heatsink Temp
The heat sink is above or below the operating limits of -15oF to 200oF
(-25oC to 95oC).
0002 0000
Watchdog Fault
0001 0000
Ambient Temp
24
6. Limited Warranty
PV Powered, Inc. provides a limited warranty for your residential or commercial inverter
and optional data monitoring module for defects caused by material or manufacturing
aws. The inverter and the data monitoring module must be installed and maintained by a
qualied installer in order for the warranty to be valid.
6.2 Coverage
PV Powered will, at its option, use new and/or reconditioned parts in performing
warranty repair and in building replacement products. PV Powered reserves the right to
use parts or products of original or improved design in the repair or replacement. If PV
Powered repairs or replaces a product, its warranty continues for the remaining portion
of the original warranty period or 90 days from the date of the return shipment to the
customer, whichever period expires later. All replaced products and all parts removed
from repaired products become the property of PV Powered.
For defects covered by this limited warranty, PV Powered will provide, at no additional
cost to the customer, both parts and labor necessary to repair the product, and return
shipment to the customer via a PV Powered selected, non-expedited, surface freight
carrier within the United States and Canada.
25
6. LIMITED
WARRANTY
PV Powered will, at its option, repair or replace the defective component(s) free of
charge, provided that you notify PV Powered of the defect during the warranty period,
have a dated proof of purchase, and PV Powered determines that the defect is covered
by the limited warranty set forth above. PV Powered reserves the right to inspect the
defective component(s) and determine if the defect is due to material or manufacturing
aws. PV Powered also reserves the right to charge a fee for service time expended if the
defect is not due to material or manufacturing aw or is not for some other reason subject
to this limited warranty.
Improper installation.
Improper maintenance.
Exposure to unsuitable environmental conditions (including but not limited to damage due to lightning strikes, storm, re, ood, etc.).
Negligence or accidents.
This warranty also does not cover costs related to the removal, installation, or
troubleshooting of your electrical systems.
26
6.5 Arbitration
IN THE EVENT OF A DISPUTE BETWEEN PV POWERED AND ANY PURCHASER
COVERED UNDER THIS WARRANTY, TO THE MAXIMUM EXTENT ALLOWED
BY LAW, THE PURCHASER AGREES TO RESOLVE ANY AND ALL SUCH
DISPUTES USING BINDING ARBITRATION IN ACCORDANCE WITH THE
RULES AND PROCEDURES OF THE ARBITRATION SERVICE OF PORTLAND,
INC., AND JUDGMENT UPON AWARD RENDERED PURSUANT TO SUCH
ARBITRATION SHALL BE BINDING ON THE PARTIES. THE LOCATION FOR
ANY ARBITRATION HEARINGS SHALL BE BEND, OREGON. THE PRICE FOR
THE INVERTER OR PVM1010 DEVICE AND PV POWEREDS OBLIGATIONS
UNDER THIS EXPRESS LIMITED WARRANTY ARE CONSIDERATION FOR THIS
BINDING ARBITRATION PROVISION.
27
28
7. Return Procedure
Before returning the product directly to PV Powered, you must rst obtain a Return
Materials Authorization Number (RMA) from PV Powered. You must also pre-pay for
shipping. When you contact a PV Powered representative, please have the following
information ready:
1.
2.
3.
When you return the product to PV Powered, PV Powered advises that you use the
original packaging or its equivalent, and that you fully insure the shipped product. PV
Powered is not responsible for damage to the product due to improper packaging.
On the packaging, please include the following:
1.
Clearly mark the Return Materials Authorization Number (supplied by PV Powered) on the outside of the box.
2.
3.
4.
Ship the product prepaid to the address provided by your PV Powered representative.
7.1 Information about Your System
29
7. RETURN
PROCEDURE
Note the following information for your records, and retain your dated proof of
purchase:
Notes
30
Appendix A - Specifications
The specications detailed below are expected operational parameters, and should
be used in designing your PV system in accordance with the NEC.
PVP1100
EVR
PVP1100
PVP2000
EVR
115VDC450VDC
150VDC450VDC
115VDC450VDC
115VDC380VDC
150VDC380VDC
10A
8A
Specications
PVP2500
PVP2800
150VDC450VDC
140VDC450VDC
180VDC450VDC
115VDC380VDC
150VDC380VDC
140VDC380VDC
180VDC380VDC
18A
14A
20A
16A
211V264V
183V229V
240V
208V
< 2.0A
8.4A
< 2.0A
0.95 - 1.0
0.99 - 1.0 at
>50% Power
PVP2000
500VDC
26A
105.6V132.5V
211V264V
59.3Hz-60.5Hz
120V
240V
60Hz
9.5A
9A
12A
15
14A
20
26A
20A
1100
20A
2000
2500
2800
1100
2000
2500
2800
Enclosure
Dimensions (W x D x H)
16 x 7.5 x 21.75
Weight (lbs.)
55lbs
65lbs
Cooling
Relative Humidity
0% to 100% Condensing
-25oC to + 40oC
70lbs
NEMA 3R
UL 1741, IEEE 1547, IEEE 519, IEEE 929, IEEE 620
APPENDIX A
31
Specications
PVP3000
PVP3500
PVP4600
PVP4800
PVP5200
500VDC
170VDC-450VDC
200VDC450VDC
205VDC450VDC
200VDC450VDC
240VDC450VDC
170VDC-380VDC
200VDC380VDC
205VDC380VDC
200VDC380VDC
240VDC380VDC
18A
18A
25A
26A
25A
183V229V
211V264V
211V264V
240V
240V
26A
26A
211V264V
211V264V
240V
240V
48A
59.3Hz-60.5Hz
208V
60Hz
< 2.0A
8.4A
0.99 - 1.0 at
>50% Power
0.95 - 1.0
13A
15A
23A
20
30
20A
3000
3500
4600
26A
4800
5200
3000
3500
4600
4800
5200
Steel - NEMA 3R to UL 50
Standards
Aluminum - NEMA 3R to UL 50
Standards
Dimensions (W x D x H)
16 x 7.5 x 21.75
Weight (lbs.)
80lbs
Enclosure
85lbs
Cooling
135lbs
Relative Humidity
0% to 100% Condensing
-25oC to +40oC
NEMA 3R
Listings
Abnormal Specications
The specications listed below are classied as abnormal and are not representative of
normal operation.
Abnormal Specications
Momentary current transient obtained
during abnormal operation
PVP1100
EVR
PVP1100
PVP2000
EVR
Abnormal Specications
Momentary current transient obtained
during abnormal operation
PVP2000
PVP2500
PVP2800
88 A-pk
166 A-pk /
0.608 ms
0A
PVP3000
PVP3500
PVP4600
PVP4800
PVP5200
166 A-pk /
0.608 ms
88 A-pk
88 A-pk
88 A-pk
88 A-pk
0A
32
Index
A
Acronyms and Abbreviations iii
INDEX
C
Connecting DC Wires/PV Panels 14
DC Connections 14
Open Circuit Calculations 14
Connecting the Inverter to the Electrical Grid 12
Contact Information i
F
Fault Codes 24
G
GFI Circuit 11
Grounding 10
I
Islanding Prevention- Electrical Safety Features 2
L
LED Indicator Lights 18
Location and Clearances 3
M
Multiple Faults 23
R
Revisions and Certication ii
S
Safety Information and Conventions ii
Designation of Danger, Warning and Caution ii
Separation of Circuits 10
V
Vacuum Fluorescent Display (VFD) 19
Normal Display Cycle 20
Voltage and Frequency Limits 8
33
34