Conductor
crosssectional
area
Reference Method C
(clipped direct)
Reference Method E
(in free air or on a perforated
cable tray horizontal or vertical
1 two
core cable,
single phase
a.c. or d.c.
2
(mm)
Reference Method D
(direct in groundor in ducting in
ground, in or around buildings)
TECHNICAL INFORMATION
1 two
core cable,
single phase
a.c. or d.c.
4
(A)
(A)
1.5
27
2.5
4
6
10
16
36
49
62
85
110
25
35
50
70
95
1 two
core cable,
single phase
a.c. or d.c.
6
(A)
(A)
(A)
(A)
23
29
25
25
21
31
42
53
73
94
39
52
66
90
115
33
44
56
78
99
33
43
53
71
91
28
36
44
58
75
146
180
219
279
338
124
154
187
238
289
152
188
228
291
354
131
162
197
251
304
116
139
164
203
239
96
115
135
167
197
120
150
185
240
300
392
451
515
607
698
335
386
441
520
599
410
472
539
636
732
353
406
463
546
628
271
306
343
395
446
223
251
281
324
365
400
787
673
847
728
TABLE 4E4B
NOTES:
1. Where a conductor
operates at a temperature
exceeding 70C it must
be ascertained that the
equipment connected to
the conductor is suitable
for the conductor operating temperature (see
Regulation 512.1.2).
7
2. Where cables in this
table are connected to
equipment or accessories
designed to operate at a
temperature not exceeding 70C, the current
ratings given in the equivalent table for 70C thermoplastic insulated cables
(Table 4D4A) must be
used (see also Regulation
523.1)
Conductor
crosssectional
area
Two-core
cable, d.c.
Two-core cable,
single-phase a.c.
(mm)
(mV/A/m)
(mV/A/m)
(mV/A/m)
1.5
31
31
27
2.5
4
6
10
16
19
12
7.9
4.7
2.9
19
12
7.9
4.7
2.9
16
10
6.8
4.0
2.5
25
35
50
70
95
1.85
1.35
0.98
0.67
0.49
1.85
1.35
0.99
0.67
0.50
0.160
0.155
0.155
0.150
0.150
1.90
1.35
1.00
0.69
0.52
1.60
1.15
0.86
0.59
0.43
0.140
0.135
0.135
0.130
0.130
1.65
1.15
0.87
0.60
0.45
120
150
185
240
300
0.39
0.31
0.25
0.195
0.155
0.40
0.32
0.26
0.20
0.16
0.145
0.145
0.145
0.140
0.140
0.42
0.35
0.29
0.24
0.21
0.34
0.28
0.22
0.175
0.140
0.130
0.125
0.125
0.125
0.120
0.37
0.30
0.26
0.21
0.185
400
0.120
0.13
0.140
0.190
0.115
0.120
0.165
All tables are reproduced by kind permission of The Institution of Engineering & Technology from IEE Regs, 17th Edition However, it should be noted that in
order to apply these tables correctly, reference is required to appendix 4 of the 17th edition of the wiring regualtions which may be obtained from: Institution
of Engineering & Technolgy, Michael Faraday House,Six Hills Way, Stevenage, Hertfordshire, ENGLAND, SG1 2AY.
272
SOUTH EAST
Erith (Head Office)
Tel: 01322 441165
Fax: 01322 440492
SOUTH WEST
Bristol
Tel: 0117 966 6333
Fax: 0117 953 3602
WALES
Cardiff
Tel: 02920 450044
Fax: 02920 464724
MIDLANDS
Birmingham
Tel: 0121 321 1745
Fax: 0121 355 5320
EASTERN
Peterborough
Te l : 0 1 7 3 3 5 5 8 4 8 5
Fax: 01733 56 2 0 1 5
NORTH
Leeds
Tel: 0113 2533565
Fax: 0113 253 6373
NORTH WEST
Manchester
Tel: 01204 793111
Fax: 01204 797977
NORTH EAST
Teesside
Tel: 01642 678633
Fax: 01642 674487