Installation calculation report

1
Full

Page 2/28

Project: 1

28/12/2014

Page 3/28

Content

Project description.................................................................................................................. 4
1.1

Project general settings................................................................................................................... 4

1.2

Settings for wiring device calculation............................................................................................ 4

1.3

List of loads...................................................................................................................................... 4

Installation general design.....................................................................................................6


2.1

List of devices.................................................................................................................................. 6

Calculation notes.................................................................................................................. 14
3.1

Source circuits............................................................................................................................... 14

3.2

Generator circuits.......................................................................................................................... 23

3.3

LV Source circuits.......................................................................................................................... 23

3.4

UPS circuits.................................................................................................................................... 24

3.5

Surge Arrester circuits................................................................................................................... 24

3.6

Capacitor bank circuits.................................................................................................................. 24

3.7

Feeder circuits................................................................................................................................ 24

3.8

LV Transformer circuits................................................................................................................. 25

3.9

Couplers circuits............................................................................................................................ 27

3.10

Generic load circuits................................................................................................................. 27

3.11

Lighting load circuits................................................................................................................ 27

3.12

Power socket load circuits....................................................................................................... 28

3.13

Motor starter combination........................................................................................................ 28

3.14

Busbar circuits.......................................................................................................................... 29

3.15

Busbar trunking system circuits............................................................................................. 29

3.16

Busbar trunking system circuits............................................................................................. 29

3.17

Lighting Busbar trunking system circuits..............................................................................29

Project: 1

28/12/2014

Page 4/28

1 Project description
1.1 Project general settings
Installation standard

IEC60364

Calculation standard
Circuit breaker standard
Frequency

TR50480
IEC 60947-2
50 Hz

1.2 Settings for wiring device calculation


Maximal CSA

300 mm

1.3 List of loads


Name
AA 16
AA 13

Name
EA 15

Name
MA 14
MA 17

Project: 1

1.3.1 Generic loads


Sr (kVA)
Pr (kW) Ir (A)
69.3
58.9
100
165
140
238

Cos
0.85
0.85

Nbr
1
1

1.3.2 Lighting distribution


Type of lamp P Lamp (W)
P ballast (W)
Standard
150
0
incandescent
lamp
1.3.3 Motor loads
Sr (kVA)
Pr (kW) Ir (A)
135
118
195
24.2
20.9
35

Cos
0.87
0.86

Nbr
1
1

Polarity
3Ph+N
3Ph+N

Non linear load THDi 3 (%)


No
0
No
0

Nb of lamp/light
2

Polarity
3Ph
3Ph

Nb of light
10

Non linear load THDi 3 (%)


No
0
No
0

28/12/2014

Page 5/28

2 Installation general design


2.1 List of devices
Name

2.1.1 MV/LV transformer


Nbr Range
Insulation

TA 9

Name

Trihal

Dry-type

Sr (kVA)

ukrT (%) Connection U2 (V) SEA

400

2.1.2 LV backup generator


Nbr Sr (kVA)
xd (%)

G 12

100

20

Switchboard
name
UC 11

WC 10

Name

2.1.4
Nbr

QA 14

QA 9

QA 17

QA 16

QA 13

QA 15

QA 12

Circuit breaker
Range Rating (A)
Designation
Compact
250
NSX NSX250F
Compact
630
NSX NSX630F
Compact
100
NSX NSX100F
Acti9 C120 - 100
C120H
Compact
250
NSX NSX250B
Acti9 iC60 - 6
iC60H
Compact
160
NSX NSX160B

x0 (%)

U (V)

SEA

30

400

TN-S

Rating (A)
0.00

Rb
(m)
10000

IP
Undefined

Ks

Polarity

SEA

Equipotential bounding

3Ph+N

TN-S

With

Poles

Trip unit/Curve

3P3d

MA

4P4d

Micrologic 5.3 A

3P3d

Micrologic 2.2 M

4P4d

4P4d

Micrologic 2.2

4P4d

4P4d

Micrologic 5.2 A

2.1.5 Cable schedule


Name Nbr Incomer Feeder Type
WD 17 1
QA 17 MA 17 Multi-core

Insulation L (m)
XLPE
75

WD 14 1

QA 14

MA 14

Multi-core

XLPE

39

WD 16 1

QA 16

AA 16

Multi-core

XLPE

36

WD 13 1

QA 13

AA 13

Multi-core

XLPE

35

WD 15 1

QA 15

EA 15

Multi-core

XLPE

15

Project: 1

TN-S

xd (%)

2.1.3 LV switchboards and busbar


Switchboard name
Range
UC 11
No preference
Busbar name

420

Rb
(m)
10000

RCD

L1/L2/L3
1x16
Copper
1x70
Copper
1x25
Copper
1x70
Copper
1x1.5

1x25
Copper
1x70
Copper
1x1.5

RCD class

PE/PEN
1x16
Copper
1x35
Copper
1x16
Copper
1x35
Copper
1x4 Copper
28/12/2014

Page 6/28

WD 12 1

G 12

QA 12

Multi-core

XLPE

WD 9

TA 9

QA 9

Multi-core

XLPE

2.1.6 MV Cable
Name Nbr Designation CSA (mm) Icc (A)
MVWD 1
NA
1 x 240 Al 21.3
9

Project: 1

In (A)
418

Copper
1x35
Copper
1x300
Copper

Copper
1x35
Copper
1x300
Copper

1x16
Copper
1x150
Copper

Un (kV)
24

28/12/2014

Page 7/28

3 Calculation notes
3.1 Source circuits
3.1.1 Circuit Source 9
MV power supply
W9
Max. upstream short circuit power 500 MVA
Min. upstream short circuit power 250 MVA
MV Cable
MVWD 9
Parameters
Length
10 m
Type of cable
Single core
Ib
12 A
Nb of conductor per phase
1
Cross section area
1 x 240 Al mm
Core
Aluminium
Short circuit withstand
21.3 kA
Assigned voltage
20 kV
Insulation voltage
24 kV
MV/LV transformer
Range
Technology
Rated power
ukrT
Type of losses
PkrT
System earthing arrangement
MV Connection
LV Connection
No load secondary voltage Ur0
Ur LV
Rb (neutral grounding)
Ra (mass grounding)
Sizing information
Cable
Parameters
Length
Max length
Installation method

TA 9
Trihal
Dry-type
400 kVA
6%
Normal
4.8 kW
TN-S
D
yn
420V
400V
NA
NA
UkrT and PkrT calculated by system
WD 9

5m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
577 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1

Project: 1

28/12/2014

Page 8/28

A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

Standard table reference


Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x300 mm
Copper
621 A
1x300 mm
Copper
621 A
1x150 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 10.31
8.92

10.31

6.87

7.79

7.93 0.00

Operating mode emergency


(kA) 9.48
8.21
9.48

NA

NA

NA

Synthesis for all operating mode


(kA) 10.31
8.92
10.31

6.87

7.79

7.93 0.00

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Circuit breaker
Ib
Distance from origin

QA 9
577 A
NA

Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr

Sized by system
Compact NSX
NSX630F
630 A
36 kA
NA
NA
NA
4P4d
Micrologic 5.3 A
630 A

Project: 1

578 A
16 s
28/12/2014

Page 9/28

Short delay settings


Isd current
Tsd
Instantaneous tripping
Ii current

5780 A
0s
6930 A

Discrimination Results
UpStream

Discrimination Limit

Operating mode Normal


NA

Discrimination can't be determinated : no


upstream Lv Breaker

Operating mode emergency


NA

Design current
IL1

Discrimination can't be determinated : no


upstream Lv Breaker

IL2

IL3

IN

Operating mode Normal


(A)
458.557
457.518

457.518

1.04

Operating mode emergency


(A)
0.000
0.000

0.000

Synthesis for all operating mode


(A)
458.557
457.518
457.518
Voltage drop
Cumulated from upstream

1.04
Circuit

Operating mode Normal


0.136
U3L (%)
0.157
UL1L2 (%)
0.157
UL2L3 (%)
0.157
UL3L1 (%)
0.136
UL1N (%)
0.136
UL2N (%)
0.136
UL3N (%)

0.136
0.157
0.157
0.157
0.136
0.136
0.136

Operating mode emergency


0.000
U3L (%)
0.000
UL1L2 (%)
0.000
UL2L3 (%)
0.000
UL3L1 (%)
0.000
UL1N (%)
0.000
UL2N (%)
0.000
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Project: 1

28/12/2014

Page 10/28

3.2 Generator circuits


3.2.1 Circuit Source 12
LV generator
G 12
Rated power
100 kVA
Subtransient reactance xd
20 %
Transient reactance xd
30 %
Zero sequence reactance x0
6%
System earthing arrangement
TN-S
Ur
400 V
Rb (neutral grounding)
NA
Ra (mass grounding)
NA
Cable
WD 12
Parameters
Length
5m
Max length
NA
Installation method
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
144 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Standard table reference
A-52-20
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
Short circuit current
Ik3max
Ik2max
Project: 1

1x35 mm
Copper
158 A
1x35 mm
Copper
158 A
1x16 mm
Copper
Ik1max

Ik2min

Ik1min

Ief

Ief2min
28/12/2014

Page 11/28

Operating mode Normal


(kA) 0.86
0.75

0.78

NA

NA

NA

NA

Operating mode emergency


(kA) 0.79
0.69
0.72

0.40

0.62

0.62 0.00

Synthesis for all operating mode


(kA) 0.79
0.69
0.72

0.40

0.62

0.62 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Circuit breaker
Ib
Distance from origin

QA 12
144 A
NA

Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current

Sized by system
Compact NSX
NSX160B
160 A
25 kA
NA
NA
NA
4P4d
Micrologic 5.2 A
160 A

Discrimination Results
UpStream

145 A
16 s
435 A
0s
720 A
Discrimination Limit

Operating mode Normal


NA

Discrimination can't be determinated : no


upstream Lv Breaker

Operating mode emergency


NA

Design current
IL1

Discrimination can't be determinated : no


upstream Lv Breaker

IL2

Operating mode Normal


(A)
0.000
0.000
Project: 1

IL3
0.000

IN
0
28/12/2014

Page 12/28

Operating mode emergency


(A)
121.500
121.500

121.500

Synthesis for all operating mode


(A)
121.500
121.500
121.500
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


0.000
U3L (%)
0.000
UL1L2 (%)
0.000
UL2L3 (%)
0.000
UL3L1 (%)
0.000
UL1N (%)
0.000
UL2N (%)
0.000
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Operating mode emergency


0.193
U3L (%)
0.223
UL1L2 (%)
0.223
UL2L3 (%)
0.223
UL3L1 (%)
0.193
UL1N (%)
0.193
UL2N (%)
0.193
UL3N (%)

0.193
0.223
0.223
0.223
0.193
0.193
0.193

Project: 1

28/12/2014

Page 13/28

3.3 Generic load circuits


3.3.1 Circuit Load 16
Circuit breaker
QA 16
Ib
100 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 C120
C120H
100 A
15 kA
NA
NA
NA
4P4d
B
100 A
100 A
NA
400 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 9
NSX630F
Micrologic 5.3 A
630 A / 4P4d

Full Discrimination

Operating mode emergency


QA 12
NSX160B
Micrologic 5.2 A
160 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 16

Project: 1

36 m
110 m
31
E
Multi-core cables on horizontal
perforated tray
28/12/2014

Page 14/28

Type of cable
Nb of additional touching circuits
Insulation
Ambient temperature
Level of third harmonic THDI
Ib
Sizing constraint
Sizing Information

Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

Multi-core
0
XLPE
30 C
0%
100 A
Voltage drop
The CSA of cable WD 16 has been
increased from 16 to 25 to comply with
the voltage drop in the circuit.
Sized with Ir
1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x25 mm
Copper
127 A
1x25 mm
Copper
127 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 10.13
8.78

9.97

3.81

2.69

2.22 0.00

Operating mode emergency


(kA) 0.79
0.69
0.72

0.39

0.60

0.59 0.00

Synthesis for all operating mode


(kA) 10.13
8.78
9.97

0.39

0.60

0.59 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
Project: 1

AA 16
400 V
28/12/2014

Page 15/28

S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

69.3 kVA
58.9 kW
100 A
0.85
3Ph+N
1
1
No
0
NA
IL3

IN

Operating mode Normal


(A)
100.000
100.000

100.000

Operating mode emergency


(A)
100.000
100.000

100.000

Synthesis for all operating mode


(A)
100.000
100.000
100.000
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


1.457
U3L (%)
1.683
UL1L2 (%)
1.683
UL2L3 (%)
1.683
UL3L1 (%)
1.457
UL1N (%)
1.457
UL2N (%)
1.457
UL3N (%)

1.321
1.526
1.526
1.526
1.321
1.321
1.321

Operating mode emergency


1.515
U3L (%)
1.749
UL1L2 (%)
1.749
UL2L3 (%)
1.749
UL3L1 (%)
1.515
UL1N (%)
1.515
UL2N (%)
1.515
UL3N (%)

1.321
1.526
1.526
1.526
1.321
1.321
1.321

Synthesis for all operating mode


1.515
U3L (%)
1.749
UL1L2 (%)
1.749
UL2L3 (%)
1.749
UL3L1 (%)
1.515
UL1N (%)
1.515
UL2N (%)
1.515
UL3N (%)

Project: 1

28/12/2014

Page 16/28

3.3.2 Circuit Load 13


Circuit breaker
QA 13
Ib
238 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX250B
250 A
25 kA
NA
NA
NA
4P4d
Micrologic 2.2
250 A
240 A
16 s
2400 A
0.02 s
3000 A
Discrimination Limit

Operating mode Normal


QA 9
NSX630F
Micrologic 5.3 A
630 A / 4P4d

Full Discrimination

Operating mode emergency


NA

Discrimination can't be determinated : no


upstream Lv Breaker

Cable
Parameters
Length
Max length
Installation method

WD 13

35 m
60.6 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
238 A

Project: 1

28/12/2014

Page 17/28

Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

Iz
Sized with Ir
1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x70 mm
Copper
246 A
1x70 mm
Copper
246 A
1x35 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 10.13
8.78

9.97

5.49

4.93

3.82 0.00

Operating mode emergency


(kA) NA
NA
NA

NA

NA

NA

Synthesis for all operating mode


(kA) 10.13
8.78
9.97

5.49

4.93

3.82 0.00

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Project: 1

AA 13
400 V
165 kVA
140 kW
238 A
0.85
3Ph+N
1
1
No
0
NA
28/12/2014

Page 18/28

Design current
IL1

IL2

IL3

IN

Operating mode Normal


(A)
238.000
238.000

238.000

Operating mode emergency


(A)
0.000
0.000

0.000

Synthesis for all operating mode


(A)
238.000
238.000
238.000
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


1.326
U3L (%)
1.531
UL1L2 (%)
1.531
UL2L3 (%)
1.531
UL3L1 (%)
1.326
UL1N (%)
1.326
UL2N (%)
1.326
UL3N (%)

1.190
1.374
1.374
1.374
1.190
1.190
1.190

Operating mode emergency


0.193
U3L (%)
0.223
UL1L2 (%)
0.223
UL2L3 (%)
0.223
UL3L1 (%)
0.193
UL1N (%)
0.193
UL2N (%)
0.193
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Synthesis for all operating mode


1.326
U3L (%)
1.531
UL1L2 (%)
1.531
UL2L3 (%)
1.531
UL3L1 (%)
1.326
UL1N (%)
1.326
UL2N (%)
1.326
UL3N (%)

Project: 1

28/12/2014

Page 19/28

3.4 Lighting load circuits


3.4.1 Circuit Load 15
Circuit breaker
QA 15
Ib
5.2 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60H
6A
15 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 9
NSX630F
Micrologic 5.3 A
630 A / 4P4d

Full Discrimination

Operating mode emergency


NA

Discrimination can't be determinated : no


upstream Lv Breaker

Cable
Parameters
Length
Max length
Installation method

WD 15

15 m
241 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0

Project: 1

28/12/2014

Page 20/28

Insulation
Ambient temperature
Level of third harmonic THDI
Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

XLPE
30 C
0%
5A
Iz
Sized with Ir
1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x1.5 mm
Copper
23 A
1x1.5 mm
Copper
23 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 10.13
8.78

9.97

0.78

0.46

0.66 0.00

Operating mode emergency


(kA) NA
NA
NA

NA

NA

NA

Synthesis for all operating mode


(kA) 10.13
8.78
9.97

0.78

0.46

0.66 0.00

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Project: 1

EA 15
400 V
3.6 kVA
3 kW
5.2 A
1
1
1
28/12/2014

Page 21/28

Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

3Ph+N
Standard incandescent lamp
10
2
150 W
0W
5.2 A
No
0
NA
IL3

IN

Operating mode Normal


(A)
5.196
3.897

3.897

1.3

Operating mode emergency


(A)
0.000
0.000

0.000

Synthesis for all operating mode


(A)
5.196
3.897
3.897
Voltage drop
Cumulated from upstream

1.3
Circuit

Operating mode Normal


0.669
U3L (%)
0.696
UL1L2 (%)
0.619
UL2L3 (%)
0.696
UL3L1 (%)
0.802
UL1N (%)
0.669
UL2N (%)
0.669
UL3N (%)

0.533
0.539
0.462
0.539
0.666
0.533
0.533

Operating mode emergency


0.193
U3L (%)
0.223
UL1L2 (%)
0.223
UL2L3 (%)
0.223
UL3L1 (%)
0.193
UL1N (%)
0.193
UL2N (%)
0.193
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Synthesis for all operating mode


0.669
U3L (%)
0.696
UL1L2 (%)
0.619
UL2L3 (%)
0.696
UL3L1 (%)
0.802
UL1N (%)
0.669
UL2N (%)
0.669
UL3N (%)

Project: 1

28/12/2014

Page 22/28

3.5 Motor starter combination


3.5.1 Circuit Motor Load 14
Circuit breaker
QA 14
Ib
NA
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Compact NSX
NSX250F
250 A
36 kA
NA
NA
NA
3P3d
MA
220 A
220 A
NA
2420 A
NA
NA
Discrimination Limit

Operating mode Normal


QA 9
NSX630F
Micrologic 5.3 A
630 A / 4P4d

Full Discrimination

Operating mode emergency


NA

Discrimination can't be determinated : no


upstream Lv Breaker

Contactor
Designation
Type of coordination

LC1F225
LC1F225
T1

Thermal relay
Designation
Ir

LR9F5371
LR9F5371
195

Cable
Parameters
Length
Max length
Installation method

WD 14

Project: 1

39 m
51.7 m
31
28/12/2014

Page 23/28

E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
195 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Standard table reference
A-52-20
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x70 mm
Copper
246 A
1x35 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 10.13
8.78

0.00

5.34

0.00

3.56 0.00

Operating mode emergency


(kA) NA
NA
NA

NA

NA

NA

Synthesis for all operating mode


(kA) 10.13
8.78
0.00

5.34

0.00

3.56 0.00

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor
Startup type
U
Mechanical power
Startup current Id/Ir
Transient current Id/Ir
Ir for sizing
Project: 1

MA 14
Direct
400 V
110 kW
7.2
<=19
195 A
28/12/2014

Page 24/28

Sr for sizing
Pr for sizing
cos
Polarity
Number of circuit
Ku (mode Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

135 kVA
118 kW
0.87
3Ph
1
1
No
0%
NA
IL3

IN

Operating mode Normal


(A)
195.000
195.000

195.000

Operating mode emergency


(A)
0.000
0.000

0.000

Synthesis for all operating mode


(A)
195.000
195.000
195.000
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


1.236
U3L (%)
1.427
UL1L2 (%)
1.427
UL2L3 (%)
1.427
UL3L1 (%)
0.136
UL1N (%)
0.136
UL2N (%)
0.136
UL3N (%)

1.100
1.270
1.270
1.270
0.000
0.000
0.000

Operating mode emergency


0.193
U3L (%)
0.223
UL1L2 (%)
0.223
UL2L3 (%)
0.223
UL3L1 (%)
0.193
UL1N (%)
0.193
UL2N (%)
0.193
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Startup Voltage drop


UStartUp

3.944

3.5.2 Circuit Motor Load 17


Circuit breaker
QA 17
Ib
NA
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Project: 1

Sized by system
Compact NSX
NSX100F
100 A
36 kA
NA
NA
NA
3P3d
28/12/2014

Page 25/28

Trip unit designation


Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Micrologic 2.2 M
50 A
36 A
5s
252 A
0.03 s
750 A
Discrimination Limit

Operating mode Normal


QA 9
NSX630F
Micrologic 5.3 A
630 A / 4P4d

Full Discrimination

Operating mode emergency


QA 12
NSX160B
Micrologic 5.2 A
160 A / 4P4d

392 A

Contactor
Designation
Type of coordination

LC1D40A
LC1D40A
T1

Cable
Parameters
Length
Max length
Installation method

WD 17

75 m
252 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
35 A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 17 has been
increased from 4 to 16 to comply with the
voltage drop in the circuit.
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14

Project: 1

28/12/2014

Page 26/28

1
A-52-16
1
D-52-1
1
A-52-20
1
1

Soil thermal resistivity factor


Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x16 mm
Copper
100 A
1x16 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 10.13
8.78

0.00

1.57

0.00

0.95 0.00

Operating mode emergency


(kA) 0.79
0.69
0.00

0.38

0.00

0.51 0.00

Synthesis for all operating mode


(kA) 10.13
8.78
0.00

0.38

0.00

0.51 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Asynchronous LV Motor
Startup type
U
Mechanical power
Startup current Id/Ir
Transient current Id/Ir
Ir for sizing
Sr for sizing
Pr for sizing
cos
Polarity
Number of circuit
Ku (mode Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

MA 17
Direct
400 V
18.5 kW
7.2
<=19
35 A
24.2 kVA
20.9 kW
0.86
3Ph
1
1
No
0%
NA
IL3

IN

Operating mode Normal


(A)
35.000
35.000

35.000

Operating mode emergency


(A)
35.000
35.000

35.000

Project: 1

28/12/2014

Page 27/28

Synthesis for all operating mode


(A)
35.000
35.000
35.000
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


1.630
U3L (%)
1.882
UL1L2 (%)
1.882
UL2L3 (%)
1.882
UL3L1 (%)
0.136
UL1N (%)
0.136
UL2N (%)
0.136
UL3N (%)

1.494
1.725
1.725
1.725
0.000
0.000
0.000

Operating mode emergency


1.687
U3L (%)
1.948
UL1L2 (%)
1.948
UL2L3 (%)
1.948
UL3L1 (%)
0.193
UL1N (%)
0.193
UL2N (%)
0.193
UL3N (%)

1.494
1.725
1.725
1.725
0.000
0.000
0.000

Startup Voltage drop


UStartUp

3.125

3.6 Busbar circuits


3.6.1
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit WC 10
WC 10
UC 11
No preference
0
Undefined
Protection name

Protection type

Load 13

QA 13

NSX250B

Motor Load 14

QA 14

NSX250F

Load 15

QA 15

iC60H

Load 16

QA 16

C120H

Motor Load 17

QA 17

NSX100F

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Ief2min

Operating mode Normal


Project: 1

28/12/2014

Page 28/28

(kA) 10.13

8.78

9.97

6.88

7.81

7.94 0.00

Operating mode emergency


(kA) 0.79
0.69
0.72

0.40

0.62

0.62 0.00

Synthesis for all operating mode


(kA) 10.13
8.78
9.97

6.88

7.81

7.94 0.00

Calculation results in accordance with CENELEC technical report TR50480.