Bulletin 71.

1:119
December 2008

Type 119 Control Valve

W3735-1

W3745-1

Figure 1. Type 119 Control Valve

Figure 2. Type 119 Control Valve Sectional

Introduction

Easy Leak DetectionVent hole between body


and actuator stem seals allows detection of body or
actuator seal leakage.

The Type 119 control valve (Figure 1) is used for


on-off or throttling control of non-corrosive or mildly
corrosive liquids and gases. It is designed to meet
low-pressure liquid and gas application requirements
in many varied industries.

Easily Adjusted SpringThe Type 119 spring is


adjusted by rotating the adjusting screw on the
top of the spring case.

If the control valve requires maintenance, the trim


can be exposed by removing two bolts and lifting
the actuator assembly off the valve body without
disassembling the actuator. The entire procedure
can be performed with an adjustable wrench.

Easy MaintenanceThe control valve can be


completely disassembled without removing the
valve body from the line.

Features

Sour Gas Service CapabilityOptional materials


are available for applications handling sour gases.
These constructions comply with the
recommendations of NACE International MR0175.

D100006X012

Easy InstallationCompact, lightweight


construction permits easy handling and installation.

Low LeakageThe composition disk assembly


provides positive shutoff, minimizing seat leakage
when downstream demand is zero.

www.emersonprocess.com/regulators

Bulletin 71.1:119
Specifications
Body Sizes and End Connection Styles(1)

3/4, 1, or 1-1/4-inch NPT

Spring Case and Bonnet Vents



1/4-inch NPT female

Maximum Inlet Pressure(2)



150 psig (10,3 bar)

Construction Materials

Standard Construction

Valve Body: Cast iron

Spring Case: Aluminum

Bonnet: Aluminum

Disk Holder Assembly: Aluminum and Nitrile (NBR)

(standard), Stainless steel and Nitrile (NBR) or

Stainless steel and Fluorocarbon (FKM)

Orifice: Aluminum (standard) or Stainless steel

Diaphragm: Nitrile (NBR) or Fluorocarbon (FKM)

O-Rings: Nitrile (NBR) (standard) or
Fluorocarbon (FKM)

Stem Wiper: Polytetrafluoroethylene (PTFE)

Adjusting Screw: Steel

Spring: Steel

Maximum Pressure Drop(2)



150 psig (10,3 bar) for all port diameters
Maximum Spring Case Pressure

150 psig (10,3 bar)
Spring Ranges

See Table 1
Material Temperature Capabilities(2)

With Nitrile (NBR): -20 to 180F (-29 to 82C)

With Fluorocarbon (FKM): 0 to 250F
(-18 to 121C)

Note: Not for use with hot water or ammonia.
Orifice Size and Flow Coefficients

See Table 2
Pressure Setting Adjustment

May be adjusted throughout each spring range

by rotating the adjusting screw
Valve Plug Travel

3/16-inch (4,8 mm)
Actuator Pressure Connection

1/4-inch NPT female

NACE Construction
Body: Steel
Disk Holder Assembly: Aluminum/
Fluorocarbon (FKM)
Diaphragm/Stem Assembly: Aluminum/
Fluorocarbon (FKM)
O-Rings and Internal Retaining Rings:
Fluorocarbon (FKM)

Approximate Weight

6 pounds (3 kg)

1. End connections threaded to various national or international thread standards can usually be supplied. Contact the local Sales Office.
2. The pressure and temperature limits in this bulletin and any applicable code limitation should not be exceeded.

Installation
The Type 119 control valve may be installed in any
position, but normally the actuator is vertical above
the valve body. Install the valve body such that
the direction of the process flow matches the flow
direction arrow on the side of the body.
Each control valve has a screened vent in the spring
case and in the valve bonnet. On indoor installations,
these vents should be piped outdoors with the shortest,
straightest pipe of the largest practical diameter.

Table 1. Spring Selection


spring ranges,
psig (bar)
3 to 15
5 to 20
5 to 35
30 to 60

(0,21 to 1,0)
(0,34 to 1,4)
(0,34 to 2,4)
(2,1 to 4,1)

spring
part number

spring
color code

1D892327022
1D751527022
1D665927022
1D7455T0012

Red
Silver
Blue
Green

For both indoor and outdoor installation the vents or


vent pipe must be protected from debris, weather,
condensation, or anything else that might clog it.
Overall dimensions are shown in Figure 3.

Bulletin 71.1:119
Universal NACE Compliance
4.12
(105)

Optional materials are available for applications


handling sour gases. These constructions comply
with the recommendations of NACE International sour
service standards.
The manufacturing processes and materials used by
Fisher Controls assure that all products specified for
sour gas service comply with the chemical, physical,
and metallurgical requirements of NACE MR0175 and/
or NACE MR0103. Customers have the responsibility
to specify correct materials. Environmental limitations
may apply and shall be determined by the user.

Ordering Information

8.00
(203)
MAXIMUM

3/4, 1, OR
1-1/4-INCH NPT

When ordering, specify:


1.53
(39)

Application Information
1. Controlled fluid
a. Type (include chemical analysis, if possible)
b. Temperature (normal and maximum anticipated)
c. Specific gravity

2.12
(54)

INCHES
(mm)

4.00
(102)

A2952-1

Figure 3. Dimensions

2. Range of flowing inlet pressures


3. Pressure drops
a. Range of flowing pressure drops
b. Maximum drop at shutoff

Control Valve Information

4. Flow rates
a. Minimum controlled flow
b. Normal flow
c. Maximum flow

Refer to the Specifications section on page 2, and


carefully review the description to the right of each
specification. Indicate your choice whenever a
selection is offered.

5. Input signal range to actuator

Table 2. Type 119 Valve Flow Coefficients


valve travel,
inch (mm)

3/16 (4,8)

orifice size,
inch (mm)

3/4-inch body

1-inch body

1-1/4-inch Body

Cv

Cg

C1

Cv

Cg

C1

Cv

Cg

C1

1/8 (3,2)

0.43

12.5

29.1

0.43

12.5

29.1

0.43

12.5

29.1

3/16 (4,8)

0.95

27.8

29.3

0.95

27.8

29.3

0.95

27.8

29.3

1/4 (6,4)

1.70

48.3

28.4

1.70

48.3

28.4

1.70

48.3

28.4

5/16 (7,9)

2.64

76.5

29.0

2.64

76.5

29.0

2.64

76.5

29.0

3/8 (9,5)

3.22

104

32.3

3.3

105

31.8

3.57

106

29.7

1/2 (13)

4.7

176

37.4

5.0

178

35.6

5.75

183

31.8

9/16 (14)

5.6

213

38.0

5.9

218

36.8

7.2

230

31.9

Bulletin 71.1:119

Industrial Regulators

Natural Gas Technologies

TESCOM

Emerson Process Management


Regulator Technologies, Inc.

Emerson Process Management


Regulator Technologies, Inc.

Emerson Process Management


Tescom Corporation

USA - Headquarters
McKinney, Texas 75069-1872 USA
Tel: 1-800-558-5853
Outside U.S. 1-972-548-3574

USA - Headquarters
McKinney, Texas 75069-1872 USA
Tel: 1-800-558-5853
Outside U.S. 1-972-548-3574

USA - Headquarters
Elk River, Minnesota 55330-2445 USA
Tel: 1-763-241-3238

Asia-Pacific
Shanghai, China 201206
Tel: +86 21 2892 9000

Asia-Pacific
Singapore, Singapore 128461
Tel: +65 6777 8211

Europe
Bologna, Italy 40013
Tel: +39 051 4190611

Europe
Bologna, Italy 40013
Tel: +39 051 4190611
Gallardon, France 28320
Tel: +33 (0)2 37 33 47 00

Middle East and Africa


Dubai, United Arab Emirates
Tel: +971 4811 8100

Europe
Selmsdorf, Germany 23923
Tel: +49 (0) 38823 31 0

For further information visit www.emersonprocess.com/regulators


The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls, Inc., a
business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Process Management does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson
Process Management product remains solely with the purchaser.

Emerson Process Management Regulator Technologies, Inc., 1990, 2008; All Rights Reserved

Anda mungkin juga menyukai