Anda di halaman 1dari 130

I n f o r m e T cn i c o D i ci e m b r e 2 0 1 1

ESTUDIO DE VERIFICACIN Y
COORDINACIN DE
PROTECCIONES

Preparado Para :

Servicios Especializados de
Ingeniera DIgSILENT Limitada
Av. Bicentenario 4063, Depto. 112-D,
Vitacura, Santiago
Tel.: +56 9 97797093
Fax: +56 2 9536385

Contacto:
Celso A. Gonzlez G.
e-mail:
celso.digsilent@manquehue.net

Rev 0

CHI-DT-NT-10-2011

Informe Tc nic o

Pgina 2

0 nd ice

ndice
ndice ............................................................................................................................................................... 3
1

Resumen Ejecutivo .................................................................................................................................. 5

Introduccin ........................................................................................................................................... 7

2.1

Generalidades ........................................................................................................................................................... 9

Objetivo y Alcance de los Estudios ..........................................................................................................10

3.1

Acerca de los Tipos de Esquemas de Protecciones .................................................................................................... 10

Antecedentes y Consideraciones del Estudio ...........................................................................................12

4.1

Horizonte de Anlisis ............................................................................................................................................... 12

4.2

Topologa y Expansin de Cada SM .......................................................................................................................... 12

4.2.1

Sistema Elctrico de Punta Arenas ....................................................................................................................... 12

4.2.2

Sistema Elctrico de Puerto Natales ..................................................................................................................... 14

4.2.3

Sistema Elctrico de Porvenir ............................................................................................................................... 15

4.2.4

Sistema Elctrico de Puerto Williams .................................................................................................................... 17

4.3

Herramienta de Simulacin ...................................................................................................................................... 18

Aspectos Normativos Relacionados con el Estudio de Verificacin y Coordinacin de Protecciones ..........19

5.1

Instalaciones de Generacin .................................................................................................................................... 19

5.2

Instalaciones de Transmisin ................................................................................................................................... 19

5.3

Responsabilidad de la Empresa Edelmag .................................................................................................................. 19

Protecciones Consideradas en el Estudio ................................................................................................20

6.1

Esquemas de Protecciones Punta Arenas .................................................................................................................. 21

6.1.1

Instalaciones de Generacin ................................................................................................................................ 21

6.1.2

Instalaciones de Transmisin ............................................................................................................................... 21

6.1.3

Instalaciones de Clientes ..................................................................................................................................... 22

6.2

Esquema de Protecciones Sistema Puerto Natales ..................................................................................................... 23

6.2.1

Instalaciones de Generacin ................................................................................................................................ 23

6.2.2

Instalaciones de Transmisin ............................................................................................................................... 23

6.2.3

Instalaciones de Clientes ..................................................................................................................................... 24

6.3

Esquema de Protecciones Sistema Porvenir .............................................................................................................. 25

6.3.1

Instalaciones de Generacin ................................................................................................................................ 25

6.3.2

Instalaciones de Transmisin ............................................................................................................................... 25

6.3.3

Instalaciones de Clientes ..................................................................................................................................... 26

Informe Tc nic o

Pgina 3

0 nd ice

6.4

Esquema de Protecciones Sistema Puerto Williams .................................................................................................... 26

6.4.1

Instalaciones de Generacin ................................................................................................................................ 26

6.4.2

Instalaciones de Transmisin ............................................................................................................................... 27

6.4.3

Instalaciones de Clientes ..................................................................................................................................... 27

Desarrollo de los Estudios ......................................................................................................................28

7.1

Determinacin del tiempo mximo de despeje de fallas en instalaciones de Edelmag .................................................. 28

7.2

Estudios de Cortocircuitos ........................................................................................................................................ 30

7.2.1

Resultados para SM Punta Arenas ........................................................................................................................ 30

7.2.2

Resultados para SM Puerto Natales ...................................................................................................................... 31

7.2.3

Resultados para SM Porvenir .............................................................................................................................. 31

7.2.4

Resultados para SM Puerto Williams.................................................................................................................... 31

7.2.4.1
7.3

Comentarios: ................................................................................................................................................. 32

Corrientes de Carga por Alimentador ........................................................................................................................ 32

7.3.1
7.4

Comentarios ....................................................................................................................................................... 33
Verificacin de la Coordinacin................................................................................................................................. 34

7.4.1

Coordinacin de Protecciones en Alimentadores .................................................................................................... 34

7.4.2

Coordinacin de Protecciones en Lnea de 66 kV ................................................................................................... 35

7.4.2.1

Verificacin Coordinacin de Protecciones en Lnea 66 kV ................................................................................ 36

7.4.2.1.1

Caso sin generacin en central Punta Arenas (Caso de Mayor Probabilidad) ................................................. 36

7.4.2.1.2

Caso con generacin en central en Punta Arenas (Caso de menor Probabilidad) ........................................... 36

7.4.3

Coordinacin de Protecciones en Generadores ...................................................................................................... 37

7.4.4

Comentarios y Conclusiones Estudios de Verificacin de Protecciones .................................................................... 39

Conclusiones ..........................................................................................................................................41

Referencias ............................................................................................................................................42

Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje ..................................................................43

Anexo 2 Curvas de Coordinacin Alimentadores ......................................................................................50

Anexo 3 Curvas de Coordinacin de Lnea de Transmisin .......................................................................99

Anexo 4 Curvas de Coordinacin de Protecciones de Generadores .........................................................103

Informe Tc nic o

Pgina 4

1 Resumen Ejecutivo

1 Resumen Ejecutivo
En el presente informe se describen los resultados de la verificacin de la coordinacin efectuada
en los esquemas de protecciones de cada Sistema Mediano de propiedad de la Empresa Elctrica
de Magallanes S.A., Edelmag, esto es: Punta Arenas, Puerto Natales, Porvenir y Puerto Williams.
El estudio en cuestin resulta en una obligacin normativa, impuesta por la NT. La ejecucin y
desarrollo de los estudios le corresponde a las empresas propietarias u operadoras de sistemas
elctricos medianos, a quienes stas designen y debern estar a disposicin de la Comisin
Nacional de Energa y la Superintendencia, en una fecha que tambin est determinado por la
misma norma. Para los efectos de la ejecucin del mencionado estudio, la Empresa Elctrica de
Magallanes S.A., en adelante Edelmag, ha encargado a Digsilent Limitada, en adelante Digsilent, el
desarrollo del estudio referido.
En este informe tcnico se aportan los criterios de diseo, anlisis y resultados asociados con el
Estudio de Verificacin y Coordinacin de Protecciones, efectuado en cada Sistema Mediano.
Se entiende por verificacin de coordinacin de protecciones en un sistema, a un sistema de
protecciones que se encuentre bien concebido y ajustado de manera de asegurar un
comportamiento adecuado, de alta selectividad, rpido y confiable ante perturbaciones, procurando
dentro de lo posible, otorgar los respaldos necesarios y suficientes a otras instalaciones del sistema.
Por adecuado se entiende un esquema de alta sensibilidad que permita detectar cualquier tipo de
fallas que ocurran en la zona protegida, de alta selectividad que permita discriminar cual es el
equipo o componente fallado, rpido para proceder en forma automtica al retiro del equipo fallado
y confiable, es decir, que slo opere cuando efectivamente ha ocurrido una falla.
El estudio deba efectuar los siguientes anlisis:

Determinar el tiempo mximo para despeje de falla, cuyo valor no podr ser superado por
las protecciones que operan como esquema primario.

Verificar el cumplimiento de los estndares impuesto en el Captulo N 3 y 5 de la NT. La


verificacin de la coordinacin de los equipos de protecciones exigida en la NT se efectu
mediante simulaciones estticas (Flujos y cortocircuitos), sobre escenarios que representan
adecuadamente la operacin esperada de cada SM.

El estudio consider analizar tanto las protecciones de los transformadores, unidades generadoras,
lneas de transmisin, as como tambin las instalaciones de clientes (Protecciones de
alimentadores).
La simulacin del esquema de protecciones se efectu mediante la modelacin digital de cada
proteccin en el programa de simulacin y anlisis Power Factory. Toda la informacin
proporcionada de tipo de proteccin, modelo, fabricante y ajustes de protecciones fue provista por
la empresa Edelmag.
El estudio en cuestin determin lo siguiente:

Informe Tcnico

Pgina 5

1 Resumen Ejecutivo

En general los ajustes actuales definidos en cada tipo de instalacin, esto es,
Alimentadores, Transmisin y Generacin, no requieren ser modificados, salvo ajustes
menores en algunos generadores, para evitar poner en riesgo la estabilidad del sistema.

En cada uno de los anlisis se ha verificado que se cumple la debida coordinacin de


protecciones. En efecto, para fallas que ocurren aguas debajo de cada alimentador se
aprecia que la falla es despejada por los propios alimentadores, los cuales responden de
manera ms rpida que los generadores y sistemas de transmisin. Para este tipo de fallas,
las protecciones de transmisin y generacin slo actan como respaldo ante fallas en el
correcto despeje de la falla.

Para fallas que ocurren aguas arriba de los alimentadores, las protecciones de los
alimentadores no participan, dado que las protecciones no registran aportes de corrientes
de falla desde los alimentadores hacia el punto de falla, lo cual se debe a que los
alimentadores no poseen generadores aguas abajo que contribuyan con corrientes de falla.

Para las lneas de transmisin se ha determinado que el esquema de protecciones opera


adecuadamente, por cuanto despeja en forma rpida las fallas que se origina en la lnea, y
acta como respaldo para fallas que ocurran fuera de la propia instalacin. Esta verificacin
se efectu para diferentes configuraciones de generacin en los extremos de la lnea.

En el caso de las unidades generadoras se ha verificado la correcta operacin de su


esquema de protecciones, actuando selectivamente y con tiempos acordes a cada falla que
se presente en el sistema, salvo los cambios que se plantean en algunos generadores del
SM Punta Arenas. En efecto, para fallas que ocurren en las proximidades de la barra donde
la unidad se conecta, la proteccin acta en forma rpida. En cambio para fallas ms
alejadas acta con tiempos que permiten el despeje de las instalaciones que se encuentran
en fallas, actuando estas protecciones como respaldo sino ocurre el despeje exitoso.

En todos los casos se verific que los esquemas de protecciones no actan para las
mximas corrientes de carga esperadas en el periodo 2010-2014.

En resumen, se ha verificado el correcto desempeo del esquema de protecciones en las


instalaciones de los Sistemas Medianos operados por la empresa Edelmag.

De los anlisis efectuados y de los resultados obtenidos se concluye que el sistema de


protecciones ya implementado ms los ajustes que han definido en los estudios que ha
encargado recientemente Edelmag, se ajusta a los requerimientos que impone la Norma
tcnica, por cuanto cumple a cabalidad con la debida coordinacin de protecciones.

En todas las instalaciones se aprecia que el esquema de protecciones acta en forma


rpida para fallas que ocurren en la propia instalacin, adems de prestar respaldo remoto
para fallas que ocurren en otras instalaciones del sistema. En el caso de los alimentadores
para la operacin de los reconectadores.

Aunque no se visualiza modificar el esquema de protecciones en el periodo 2011-2014, se


plantea revisar el esquema una vez que los estudios que ha encargado la empresa Edelmag
se encuentren finalizados.

Informe Tcnico

Pgina 6

2 Introduccin

2 Introduccin
La Norma Tcnica de Seguridad y Calidad de Servicio para Sistemas Medianos[1], dictada por la
Autoridad en el mes de febrero del ao 2006, en adelante, NTSyCS SM, establece a la empresas
propietarias/Operadoras de Sistemas Medianos, la ejecucin de Estudios para realizar la
programacin del Control de Tensin, el Control de Frecuencia y el PRS, para el conjunto de
instalaciones de los Sistemas Medianos, los cuales debern estar a disposicin de la Comisin
Nacional de Energa y la Superintendencia.
Se entiende por Sistemas Medianos, en adelante SM, a los sistemas elctricos cuya capacidad
instalada de generacin es menor de 200 MW y mayor a 1,5 MW. Con esta parcializacin de los
sistemas, los estudios se efectuarn para los Sistemas Elctricos de propiedad de Edelmag para los
siguientes SM: Punta Arenas, Puerto Natales, Porvenir y Puerto Williams.
En trminos especficos las exigencias de la NTSyCS SM establece la ejecucin de los siguientes
estudios:

Figura 1. Estudios exigidos por la NTSyCS de SM


Para cada estudio se solicita en concreto lo siguiente:

EDAC: Deber determinar el nivel ptimo y localizacin de desconexin de carga. El


objetivo es evitar colapso por frecuencia y tensin con la activacin de esquemas de
desconexin para estados de operacin distinto del Estado Normal.

Control de Frecuencia y Determinacin de Reservas: Tiene por objeto efectuar una


verificacin del cumplimiento de los estndares SyCS establecidos en el Captulo N 5. En
particular debe determinarse un porcentaje de reserva ptimo que se utilizar para efectuar
la asignacin de la reserva entre las unidades generadoras participantes del CPF y del CSF.

Informe Tcnico

Pgina 7

2 Introduccin

Control de Tensin y Requerimientos de Potencia Reactiva: Tiene por objeto


efectuar una verificacin del cumplimiento de los estndares de SyCS establecidos en el
Captulo N 5, adems de determinar el perfil ptimo de tensiones y los requerimientos de
potencia reactiva para las Instalaciones Transmisin, con resolucin semestral para un
horizonte de operacin de 48 meses.

Restricciones en Instalaciones de Transmisin: Se debe identificar las potencias


mximas que se pueden transmitir por las lneas de transmisin que la Empresa identifique
como crticas para garantizar frente a la ocurrencia de las contingencias indicadas que se
establecen en el Artculo 5-36 de la presente NT.

Estudio de PSR: El objetivo del PRS es que con posterioridad a un Apagn Total o
Apagn Parcial, sea posible establecer los mecanismos que permitan de una manera segura
y organizada, restablecer el suministro elctrico en todas las Islas Elctricas afectadas en el
menor tiempo posible, considerando las Cargas Crticas. Los Estudios se realizarn con una
periodicidad de cada cuatro aos, salvo que se estime necesario un tiempo para su
actualizacin parcial o completa.

Estudio de Continuidad: Determinar los ndices de continuidad FMIK y TTIK del SM, para
un horizonte de operacin de 12 meses.

Verificacin de Coordinacin de Protecciones: Tiene por objeto confirmar que el


desempeo de los rels de proteccin de las lneas de transmisin, transformadores de
potencia y unidades generadoras cumple con las exigencias de SyCS establecidas en la
presente NT.

Estos estudios se deben realizar con una periodicidad de cada cuatro aos, salvo que se estime
necesario un tiempo para su actualizacin parcial o completa. De acuerdo con esta exigencia los
estudios consideran un horizonte de anlisis tambin de cuatro aos, aos 2011-2014, para as ser
consistente con la exigencia normativa. Cabe mencionar que desde la vigencia de la NTSCS SM,
esta es la segunda oportunidad en que se llevan a cabo los anlisis, correspondiendo en esta
oportunidad una revisin de los estudios que ya realizaron las empresas propietarias de Sistemas
Medianos en el ao 2007.
Algunos de estos estudios estn directamente relacionados entre s, as como otros resultan
complementa independientes. Respecto del primer grupo de estudios, se debe definir un estudio
que inicie los anlisis cuyos resultados sean la entrada para los otros. En este sentido existe una
directa relacin entre los estudios de EDAC (por subfrecuencia y subtensin) con los estudios de
Control de Frecuencia, Control de Tensin y de Restricciones en el Sistema de
Transmisin. En cambio los estudios de Continuidad, PRS y de Protecciones se pueden abordar en
forma completamente independiente, por cuanto resultan de distinta naturaleza tcnica que los
anteriores.
El estudio que se aborda en este informe corresponde al Estudio de Verificacin de
Coordinacin de Protecciones.

Informe Tcnico

Pgina 8

2 Introduccin

2.1 Generalidades
En la operacin de los sistemas se debe procurar que toda instalacin de suministro de energa
elctrica provea la calidad de suministro en condiciones ptimas de seguridad, continuidad y
economa. La operacin de los sistemas elctricos frente a la aparicin de contingencias debe ser
capaz de proteger tanto las instalaciones como la vida de las personas que se pueden encontrarse
expuestas.
Un sistema de protecciones bien concebido debe estar ajustado de manera de asegurar un
comportamiento adecuado, de alta selectividad, rpido y confiable ante perturbaciones y procurar,
dentro de lo posible, otorgar los respaldos necesarios y suficientes a otras instalaciones del sistema.

Por adecuado se entiende un esquema de alta sensibilidad que permita detectar cualquier
tipo de fallas que ocurran en la zona protegida, de alta selectividad que permita discriminar
cual es el equipo o componente fallado, rpido para proceder en forma automtica al
retiro del equipo fallado y confiable, es decir, que slo opere cuando efectivamente ha
ocurrido una falla.

En el caso del presente estudio se verificar la correcta coordinacin de las protecciones en los
distintos Sistemas Medianos que opera la Empresa Edelmag y el nivel de cumplimiento con los
estndares impuesto en la Norma Tcnica de Seguridad y Calidad de Servicio para Sistemas
Medianos[1], en adelante, NT.
En este documento se describen los criterios de diseo, anlisis y resultados asociados con el
Estudio de Verificacin y Coordinacin de Protecciones, efectuado en cada Sistema Mediano. Se
entiende por sistemas medianos, en adelante SM, a los sistemas elctricos cuya capacidad instalada
de generacin es menor de 200 MW y mayor a 1,5 MW. Con esta parcializacin de los sistemas, los
estudios se efectuarn para los Sistemas Elctricos de: Punta Arenas, Puerto Natales, Porvenir y
Puerto Williams.
La verificacin de coordinacin de cada proteccin y su respaldo hacia otras instalaciones se realiza
en base a los criterios establecidos en la NT y de acuerdo con la informacin y experiencia
adquirida por la empresa Edelmag en la operacin de sus sistemas elctricos.
Para los efectos de la ejecucin del mencionado estudio, la Empresa Elctrica de Magallanes S.A.,
en adelante Edelmag, ha encargado a Digsilent Limitada, en adelante Digsilent, el desarrollo de los
estudios referidos, empresa que asume la ejecucin de los mismos.

Informe Tcnico

Pgina 9

3 Objetivo y Alcance de los Estudios

3 Objetivo y Alcance de los Estudios


El objetivo del presente estudio, impuesto por la NT1, es: Confirmar que el desempeo de los rels

de protecciones de las lneas de transmisin, transformadores de potencia y unidades generadoras


cumple con las exigencias de SyCS establecidas en la presente NT.
El estudio deber verificar el cumplimiento de los estndares impuesto en el Captulo N 3 y 5 de la
NT, dicho cuerpo normativo en el Captulo N 3 impone caractersticas de diseo mnimo para las
instalaciones que operan en sincronismo, entre estas las caractersticas de los elementos de
proteccin de las instalaciones. En cambio, en el Captulo N 5 se definen los estndares de
operacin para las distintas condiciones operativas que puede presentar un sistema elctrico, esto
es Normal, de Alerta y Emergencia, condiciones que el estudio deber verificar.
La verificacin de la coordinacin de los equipos de protecciones exigida en la NT se efectuar
mediante simulaciones estticas (Flujos y cortocircuitos), sobre escenarios que representen
adecuadamente la operacin esperada de cada SM.
El estudio considera estudiar las siguientes instalaciones:

Protecciones de los transformadores

Unidades generadoras

Lneas de transmisin

Instalaciones de clientes (Protecciones de alimentadores).

3.1 Acerca de los Tipos de Esquemas de Protecciones


Los tipos de protecciones en los sistemas elctricos se dividen en protecciones del tipo Unitario y
No Unitario. Los primeros basan su operacin en la medida de magnitudes elctricas en los
terminales del equipo protegido, no requieren coordinacin con otros equipos del sistema y no
prestan respaldo remoto (respaldo de otras instalaciones del sistema elctrico), son
intrnsecamente selectivos y por lo tanto su operacin puede ser instantnea, un ejemplo de estas
protecciones son las protecciones diferenciales.
Los sistemas de protecciones No Unitarios basan su operacin en la medida de las magnitudes
elctricas en slo uno de los terminales del equipo protegido. Como ests magnitudes pueden
variar para una misma falla segn su configuracin del sistema, su zona de proteccin no est
claramente delimitada a priori. Esto impide que por razones de selectividad (coordinacin) con otras
protecciones, que operen en forma instantnea, al menos para algunas ubicaciones de la falla. Este
tipo de protecciones se presta para dar respaldo a las protecciones de equipos adyacentes,
asegurando su operacin selectiva por medio del ajuste de retardos de tiempos intencionales. Un
ejemplo de este tipo de protecciones son las protecciones de distancia y de sobrecorriente.

Se refiere a la exigencia impuesta en el artculo 6-3, literal c), que menciona el objetivo del estudio de
Verificacin de Coordinacin de Protecciones.

Informe Tcnico

Pgina 10

3 Objetivo y Alcance de los Estudios

El estudio en cuestin estar orientado en verificar la coordinacin de las protecciones del tipo No
Unitario y en forma especial las protecciones de distancia, si las hubiere, y las protecciones de
sobrecorriente (residual y de fase), sean stas direccionales no direccionales.
En consideracin que los Sistemas Medianos operados por Edelmag, ya cuentan con esquemas de
protecciones operativos y con ajustes definidos, se proceder en este estudio a revisar si los ajustes
ya establecidos permiten una adecuada coordinacin de las distintas instalaciones ante fallas en el
sistema elctrico.
En forma especfica la NT establece que el estudio de Coordinacin de Protecciones debe establecer
tiempos de actuacin de protecciones, los cuales se revisarn una vez determinados los tiempos
reales de operacin de protecciones en cada una de las instalaciones. En caso que los tiempos
actuales de operacin resulten excesivos o no permitan la coordinacin adecuada con otras
instalaciones se propondrn soluciones de mejora.
En concreto, la revisin de la coordinacin de las protecciones se efectuar en base a los anlisis de
la informacin aportada por Edelmag y teniendo en consideracin los tipos, caractersticas y
especificaciones de ajustes de las protecciones actualmente en servicio en las instalaciones de los
Sistemas medianos.

Informe Tcnico

Pgina 11

4 Antecedentes y Consideraciones del Estudio

4 Antecedentes y Consideraciones del Estudio


El estudio que a continuacin se presenta se efectuar para cada uno de los sistemas elctricos
medianos de propiedad de Edelmag. En consideracin que cada sistema elctrico se encuentra
aislados unos de otros se analizarn cada uno por separado y considerando sus propias
caractersticas, no obstante, estarn incluidos en un nico informe.
A continuacin se mencionan y describen todos los antecedentes y las consideraciones tenidas en
cuenta para el desarrollo del estudio. Los antecedentes que se indican en el estudio fueron
provistos por Edelmag, en cambio las consideraciones utilizadas en el estudio corresponden a
criterios formulados por el Consultor Digsilent y a la experiencia de la empresa Edelmag en la
operacin de sus sistemas Elctricos.

4.1 Horizonte de Anlisis


El estudio en cuestin se efectuar para un horizonte de anlisis de 4 aos, considerando el periodo
del 2011 al 2014. Para dicho periodo se escoger los escenarios representativos de demanda
mxima y mnima que determinen el rango de operacin de las protecciones de cada instalacin.

4.2 Topologa y Expansin de Cada SM


Para los estudios se utiliza la topologa elctrica de cada Sistema Mediano disponible al mes de
octubre del ao 2011, ms todas las incorporaciones de instalaciones de generacin y transmisin
que se estim necesario en los estudios de planificacin de la expansin de los sistemas medianos.
A continuacin se detallan las instalaciones de generacin, transmisin y clientes consideradas en
cada sistema elctrico.

4.2.1 Sistema Elctrico de Punta Arenas


El sistema elctrico de Punta Arenas est constituido bsicamente por dos subsistemas, Tres
Puentes y central Punta Arenas. Tres Puentes est formado por dos barras principales, una de 11,5
KV que corresponde a una barra de generacin y otra de 13,2 kV que abastece alimentadores de
cargas y que tambin cuenta con inyeccin de generacin. Ambas barras se conectan a travs de
un transformador 13,2/11,5 kV de 20 MVA. Por su parte central Punta Arenas posee una barra de
13,2 kV, donde se concentran alimentadores de consumos y un centro de generacin, aunque estas
ltimas usualmente no son despachadas por criterios econmicos, transformndose dicha barra en
una de retiros de energa.
Los subsistemas se interconectan mediante una lnea de transmisin, de simple circuito, en 66 kV
de unos 8,15 km y se conecta en un extremo mediante un transformador de 66/12 kV de 33 MVA y
en el otro uno de 66/13,8 kV tambin de 33 MVA. La capacidad trmica de la lnea de transmisin

Informe Tcnico

Pgina 12

4 Antecedentes y Consideraciones del Estudio

es de 48 MVA (0,42 kAmp), no obstante, queda limitada por la capacidad de los transformadores
de los extremos.

DIgSILENT

Este Sistema Mediano cuenta con recursos de potencia reactiva shunt (banco de condensadores y
reactores) por un monto de 2,0 MVAr que se ubica en la barra de Punta Arenas. Este sistema no
cuenta con esquemas EDAC por subtensin. La topologa del sistema se aprecia en la siguiente figura.

13.2 kV P.A..

13.2 kV T.P..
Consumo AL-X10B

MG CATERPILLAR
~
G

Consumo AL-1

Unidad N 5 T.P.

Consumo AL-X10A
Consumo AL-7
Consumo AL-8A

11.5 kV
Autotransformador N 2

Trafo N 4 - C.T.P.

Autotransformador N 6

Consumo AL-9
Consumo AL-8B

Shunt/Filter

~
G

Trafo N 3 - C.T.P.

Unidad N 2 T.P.

~
G

Consumo AL-4

Consumo AL-2

Unidad N 3 T.P.
Consumo AL-5

Trafo N 7 C.P.A.

Line(1)
AWG 3/0 C..

Consumo AL-3

Celdas 11.5 kV
Consumo AL-X11
XConsumo AL-13
52D1

52CS3

Celdas 13.2 kV G.E.

23 kV

Consumo AL-6

HITACHI 24 MW
52DT1

Trafo N 1 C.T.P.

~
G

YConsumo COCAR - Ingesur

XConsumo AL-12

Unidad N 1 T.P.

Trafo N 6 C.P.A.
Lnea de unin en 23 kV
AWG 3/0 Cu (167.8 MCM)

Lnea de respaldo para PRS

52 DS

CENTRAL PUNTA ARENAS

G
~

Trafo N 5 - C.P.A.

Celdas 11.5 kV Rhona

Unidad N 5 P.A.

SOLAR MARS 10.5 MW

G
~

Trafo N 4 - C.P.A.

Line(2)
AWG 3/0 C..

Unidad N 4 P.A.

~
G

Trafo N 5 C.T.P.

Unidad N 4 T.P.

Breaker

~
G

Unidad N 7 T.P.

15 MW

Trafo N 1 - C.P.A.

Trafo N 3 - C.P.A.

~
G

13.7 MW

Trafo N 2 - C.P.A.

13.2 kV

SOLAR TITAN

Unidad N 9 T.P.

G
~

G
~

Unidad N 3 P.A.

Unidad N 2 P.A.

G
~
Unidad N 1 P.A.

~
G

GE 10.7 MW

Unidad N 8 T.P.

Estudios de la Norma de Seguridad y Calidad


Periodo de Evaluacin 2011 - 2014
Diagrama Unilineal
PowerFactory 14.0.525

Project: EDELMAG SA
Graphic: RED
Date:

10/29/2011

Annex: P. ARENAS

Figura 2. Unilineal Sistema Elctrico Punta Arenas


Las unidades generadoras que componen este sistema son las siguientes:
CENTRALES GENERADORAS SM PUNTA ARENAS
N

Descripc.

Tipo

CENTRAL TRES PUENTES


1
2
3
4
5
7
8
9

Unidad Hitachi a GAS


Motor-Generador Caterpillar DIESEL - PA
Motor-Generador Caterpillar DIESEL - PA
Unidad Solar Mars a GAS
Motor-Generador Caterpillar a GAS
Unidad Solar Titn a GAS
Turbina a GAS GE 12.22 MVA
T.G. SOLAR TITAN

CENTRAL PUNTA ARENAS

Informe Tcnico

Pmx

Observacin

MW
THD
MD
MD
TI-Gas
MG
TI
THD
TI-GAS

24,00
1,46
1,46
10,50
2,726
13,70
10,997
15,02

Existente
Existente
Existente
Existente
Existente
Existente
Existente
Existente

MW

Pgina 13

4 Antecedentes y Consideraciones del Estudio

SULZER

MD

1,400

Existente

SULZER

MD

1,400

Existente

SULZER

MD

1,400

Existente

G. ELECTRIC

THD

6,700

Unidades de respaldo

G. ELECTRIC

THD

6,500

Unidades de respaldo

Cuadro 1 Unidades que componen el SM Punta Arenas

4.2.2 Sistema Elctrico de Puerto Natales


El sistema elctrico de Puerto Natales est constituido bsicamente por una barra principal en 13,2
kV, donde se conectan las unidades generadoras y los alimentadores. En este sistema elctrico no
existen lneas de transmisin y transformadores de transmisin, excepto los propios de las unidades
generadoras.
Este sistema mediano no cuenta con recursos de potencia reactiva shunt (banco de condensadores
y reactores), as como tampoco con esquemas EDAC por subtensin.

DIgSILENT

La topologa del sistema es la siguiente:

C1 - Linea 3b

AL1-6

AL1-5

AL3-2

AL4-2

C3 - Linea 2

AL1-3

C2 - Linea 2

C1 - Linea 2a

C1 - Linea 2b

AL2-2
AL1-2

AL3-1

AL4-1

C1 Linea 1b

C1 - Linea 1a

AL2-1

Linea C4 - 2

AL1-4

AL1-1

Alimentador - 4

Alimentador 3
S. Auxiliar

Alimentador - 1

Alimentador - 2

SS.AA

89 CT

13.2 kV II
89 CTD F4

Fusible(1)

Trafo N 4

Trafo N 5

Fusible

Jenbacher

Trafo N 10

Jenbacher 416

13.2 kV

AutoTrafo

G
~

Generador N 10

Generador N 5

PALMERO

T.G. SOLAR 5

G
~
Generador N 4

Lnea

G
~

Lnea(1)

Trafo N 09

Trafo N 11

G
~

Trafo N 3

Trafo Waukesha 8

Generador N 6

M.D. CATERPILLAR

T.G. SOLAR 4
G
~

G
~

Generador N 2

G
~

G
~

G
~

G
~

Generador N 11

Generador N 9

Generador N 8

Generador N 3

JENBACHER 612

JENBACHER

WAUKESHA

Generador N 1

MD MORSE

WAUKESHA

Estudios de la Norma de Seguridad y Calidad


Periodo de Evaluacin 2011 - 2014
Diagrama Unilineal
PowerFactory 14.0.525

Project: EDELMAG SA
Graphic: RED
Date: 10/29/2011
Annex: P.NATALES

Figura 3. Unilineal Sistema Elctrico Puerto Natales

Informe Tcnico

Pgina 14

4 Antecedentes y Consideraciones del Estudio

Las unidades generadoras que componen este sistema son:


CENTRALES GENERADORAS SM PUERTO NATALES
N

Descripc.

Tipo

CENTRAL PUERTO NATALES


MD

10
11

JM612 1

2
3
4
5
6
8
9

Observacin

MW

Motor-Generador DIESEL (150 kW) F.Morse


Palmero 1.36 MW
Motor-Generador DIESEL (300 kW) F.Morse
Motor-Generador a GAS - Waukesha
Turbina Solar Saturno a GAS
Turbina Solar Saturno a GAS
Motor-Generador Caterpillar a DIESEL-PN
Motor-Generador a GAS - Waukesha
Jenbacher 1.42 MW

Pmx

Unidad de respaldo

MD

0,150
1,360
0,300
1,175
0,800
0,800
1,500
1,175
1,420

MG

1,816

Disponible 2012

MD
MG
TI-Gas
TI-Gas
MD
MG
MG

Unidad de respaldo
Existente
Existente
Existente
Existente
Existente
Existente
Existente

Cuadro 2 Unidades que componen el SM Puerto Natales

4.2.3 Sistema Elctrico de Porvenir


El sistema elctrico de Porvenir, al igual que el de Puerto Natales, est constituido bsicamente por
una barra principal en 13,8 kV, donde se conectan las unidades generadoras y los alimentadores.
En este sistema elctrico no existen lneas de transmisin ni transformadores, excepto los propios
de las unidades generadoras.
Este sistema mediano no cuenta con recursos de potencia reactiva shunt (banco de condensadores
y reactores), as como tampoco con esquemas EDAC por subtensin.
La topologa del sistema es la siguiente:

Informe Tcnico

Pgina 15

DIgSILENT

4 Antecedentes y Consideraciones del Estudio

C2 - Linea 2
Alimentadores..

Alimentador 2 - Carga 2

Alimentador 4 - Carga 1

Alimentador - 3
Alimentadores..

Alimentador - 2
Alimentadores..

Alimentador - 1
Alimentadores..

Alimentador 3 - Carga 1

Alimentador - 4
Alimentadores..

Alimentador 2 - Carga 1
Alimentador 1 (SACOR)

89 CT
89-CT3-F
HV 63A
Trafo N 2

Trafo N 3

89-CT4-F
HV 63A
Trafo N 4

89-CT5-F
HV 63A
Trafo N 5

89-CT1-F
HV 63A

89-CT6-F
HV 63A
Trafo N 6

Trafo N 1

89-CT7-F
HV 63A
Trafo TG1..

89-CT8-F
HV 63A

89-CT7-F(1)
HV 63A
Trafo TG11

Trafo N 10

89-CT9-F
HV 63A
Trafo TG1..

89-CT2-F
HV 63A

13.8_B
13.8_A

G
~

G
~

G
~

Unidad N 1

Unidad N 2

Unidad N 3

MD CATERPILLAR
MD DEUTZ
G
~

G
~

G
~

Unidad N 9

Unidad N 10

Unidad N 7

CAT - GAS JENBACHER 416

WAUKESHA

G
~
Unidad N 6

WAUKESHA

G
~

G
~

G
~

Unidad N 5

Unidad N 8

Unidad N 4

CAT - DIESEL

PALMERO

WAUKESHA

Estudios de la Norma de Seguridad y Calidad


Periodo de Evaluacin 2011 - 2014
Diagrama Unilineal
PowerFactory 14.0.525

Project: EDELAMG SA
Graphic: RED
Date: 10/29/2011
Annex: PORVENIR

Figura 4. Unilineal Sistema Elctrico Porvenir


Las unidades generadoras que componen este sistema son:
CENTRALES GENERADORAS SM PORVENIR
N

Descripc.
CENTRAL PORVENIR

Tipo Pmx
MW
MD

Motor-Generador Caterpillar DIESEL 1- PO


Motor-Generador Deutz DIESEL - PO
Motor-Generador Deutz DIESEL - PO
Motor-Generador a GAS - Waukesha - PO
Motor-Generador Caterpillar DIESEL 2- PO
Motor-Generador a GAS - Waukesha -PO
Motor-Generador a GAS - Waukesha -PO
Palmero 1.36 MW
Motor-Generador Caterpillar DIESEL - PA

10

GE Jenbacher JM416 1

MG

1
2
3
4
5
6
7
8

MD
MD
MG
MD
MG
MG
MD
MG

0,500
0,200
0,200
0,875
0,920
1,175
1,175
1,360
0,923
1,131

Observacin
Unidades de respaldo
Unidades de respaldo
Unidades de respaldo
Existente
Existente
Existente
Existente
Existente
Existente
Disponible 2012

Cuadro 3 Unidades que componen el SM Porvenir

Informe Tcnico

Pgina 16

4 Antecedentes y Consideraciones del Estudio

4.2.4 Sistema Elctrico de Puerto Williams


El sistema elctrico de Puerto Williams, est constituido bsicamente por una barra principal en
13,2 kV, donde se conectan las unidades generadoras y los alimentadores. En este sistema elctrico
no existen lneas de transmisin ni transformadores, excepto los propios de las unidades
generadoras y alimentadores.
Este sistema mediano no cuenta con recursos de potencia reactiva shunt (banco de condensadores
y reactores), as como tampoco con esquemas EDAC por subtensin.

DIgSILENT

La topologa del sistema es la siguiente:

Alimentador 1
89 CT

Carga Alimentador 3

Alimentador - 3

Carga Alimentador 1

Alimentador - 2

Carga Alimentador 2

13.2 kV II

G
~
Generador N 6

89 CTD F4
Trafo N 3

Trafo N 2
Lnea

G
~
Generador N 5

Trafo N 01

G
~
Generador N 4

Fusible(1)

Jenbacher

Trafo N 05

13.2 kV

M.D. CUMMINS
G
~
Generador N 7

G
~

G
~

Generador N 1

M.D. CATERPILLAR N 1

M.D. Detroit N 3
G
~

Generador N 2

M.D. CATERPILLAR N 2

Generador N 3

M.D. CATERPILLAR N 3

Estudios de la Norma de Seguridad y Calidad


Periodo de Evaluacin 2011 - 2014
Diagrama Unilineal
PowerFactory 14.0.525

Project: EDELMAG SA
Graphic: RED
Date: 10/29/2011
Annex: P.WILLIAMS

Figura 5. Unilineal Sistema Elctrico Puerto Williams


Las unidades generadoras que componen este sistema son:

Informe Tcnico

Pgina 17

4 Antecedentes y Consideraciones del Estudio

CENTRALES GENERADORAS SM PUERTO WILLIAMS


N

Descripc.
CENTRAL PORVENIR

1
2
3
4
5
6
7

Tipo Pmx Observacin


MW

MotorGenerador Caterpillar Diesel 3508B


MotorGenerador Caterpillar Diesel PW3508
Motor-Generador Diesel Caterpillar (PW)
Motor-Generador Cummins Diesel PW
Motor-Generador Cummins Diesel PW
Motor-Generador Deutz Diesel PW
Motor-Generador Deutz Diesel PW

MD
MD
MD
MD
MD
MD
MD

0,590
0,500
0,360
0,282
0,282
0,252
0,252

Existente
Existente
Existente
Existente
Existente
De Respaldo
De Respaldo

Cuadro 4 unidades que componen el SM Puerto Williams

Notas Importantes:

En relacin con el tipo de unidades generadoras, las abreviaciones tienen el siguiente


significado.
MD

Motor Diesel

MG

Motor a Gas

TI

Turbina a gas Industrial

THD Turbina a gas Heavy Duty

Las Unidades generadoras que segn el plan ptimo de expansin deban ser retiradas de cada
sistema elctrico, dado que ya haban cumplido su fecha de retiro, se han mantenido en las bases
de datos, por cuanto dichas unidades se utilizan en la actualidad como unidades de respaldo.

4.3 Herramienta de Simulacin


Los estudios aludidos consideran realizar sendas simulaciones estticas del sistema elctrico de
Edelmag. Para tales efectos, tanto en lo referente a estudios de flujos de potencia, cortocircuitos,
coordinacin de protecciones, se utilizar el programa Power Factory Versin 14.1.525 de
DIgSILENT GmbH (u otra superior), simulador digital de amplio uso en el sector elctrico chileno.
Para ello se emplear la ms completa modelacin de los sistemas elctricos de Edelmag existente
en la actualidad, cuya topologa para SM se indic en trminos grficos en las figuras N 2, 3, 4 y 5
respectivamente.

Informe Tcnico

Pgina 18

5 Aspectos Normativos Relacionados con el Estudio

de Verificacin y

Coordinacin de Protecciones

5 Aspectos Normativos Relacionados con el


Estudio de Verificacin y Coordinacin de
Protecciones
El estudio debe efectuar lo siguiente: ..Confirmar que el desempeo de los rels de protecciones

de las lneas de transmisin, transformadores de potencia y unidades generadoras cumple con las
exigencias de SyCS establecidas en la presente NT. (Artculo 6-3, literal c).

5.1 Instalaciones de Generacin


La proteccin de las unidades generadoras y sus conexiones con el SM debe cumplir con las
exigencias mnimas especificadas a continuacin: (Artculo 3-4, literal b)
i)

ii)

iii)

iv)

El tiempo mximo para despeje de falla en ningn caso podr exceder los valores
lmites resultantes del Estudio de Verificacin de Coordinacin de Protecciones
sealado en el Ttulo 6-2 de la presente NT, el cual ser determinado por la
Empresa.
Para el caso de unidades generadoras que se incorporan al SM, el tiempo mximo
para despeje de falla deber ser determinado en forma previa a la conexin de la
unidad generadora.
Cada unidad generadora conectada al SM, deber disponer de la proteccin de
respaldo para fallas en Instalaciones de Transmisin, debiendo la Empresa disponer
de proteccin para fallas que ocurran en las instalaciones de la unidad generadora.
Los tiempos de despeje de fallas de estas protecciones sern coordinados por la
Empresa, pero en ningn caso podrn exceder los valores lmites resultantes del
Estudio de Verificacin de Coordinacin de Protecciones sealado en el Ttulo 6-2 de
la presente NT.
El ajuste de los rels y de las protecciones que afecten al rea del Punto de
conexin deber estar coordinado en forma previa a la conexin de acuerdo a lo que
establezca el Estudio que desarrolle la Empresa para tal efecto.

5.2 Instalaciones de Transmisin


Las Instalaciones de Transmisin debern estar equipadas con protecciones elctricas que sean
capaces de aislar selectivamente el componente fallado. Los tiempos de actuacin de estas
protecciones debern estar en concordancia con el Estudio de Verificacin de Coordinacin de
Protecciones sealado en el Ttulo 6-2 de la presente NT. (Artculo 3-13)

5.3 Responsabilidad de la Empresa Edelmag


La Empresa deber comprobar el estado de conservacin y mantenimiento de las protecciones
elctricas del SM y verificar que sus ajustes y parmetros corresponden a los valores resultantes del
Estudio de Verificacin de Coordinacin de Protecciones establecido en el Ttulo 6-2 de la presente
NT. (Artculo 4-14).

Informe Tcnico

Pgina 19

6 Protecciones Consideradas en el Estudio

6 Protecciones Consideradas en el Estudio


De acuerdo con la informacin proporcionada por Edelmag, a continuacin se indican las
protecciones que se analizar su coordinacin en este estudio. Para cada proteccin de cada SM, se
indica el tipo de proteccin y los ajustes ya definidos.
Las protecciones estn separadas en protecciones de instalaciones de Generacin, Transmisin (en
los casos en que existan instalaciones de transformacin y lneas) e instalaciones de Clientes
(alimentadores).
Al respecto para los ajustes de protecciones de cada uno de los SM y en consideracin que la
empresa Edelmag se encontraba, en el momento del desarrollo de este estudio, en proceso de
actualizar los estudios de protecciones de cada SM, se intento utilizar dicha informacin para
verificar el comportamiento de los esquemas y ajustes de protecciones, especialmente por cuanto
este estudio debe abarcar un horizonte de 4 aos, periodo en el cual ya debieran estar
incorporados los ajustes de los estudios que se estn desarrollando. En este sentido la situacin es
la siguiente:

Para los SM de Puerto Natales y Porvenir se utiliz los resultados del estudio de Anlisis del
Sistema de Protecciones, documentado en el documento Informe Protecciones Natales VI.
doc y Informe Protecciones Porvenir. doc, efectuado por la Empresa Digsilent.

Para el SM de Puerto Williams se uso la informacin proporcionado por Edelmag en los


documentos Ajustes Protecciones Puerto Williams.doc.

Para el SM de Punta Arenas se utiliz la propuesta que est desarrollando la empresa


Digsilent, especialmente la propuesta de ajustes para los alimentadores. Para el caso de los
ajustes de los generadores se ha utilizado por el momento los ajustes actuales que estn
contenidos en las bases de datos de Power Factory.

En general los nuevos estudios de protecciones que se estn realizando en la actualidad


contemplan modificaciones en los esquemas de protecciones de los alimentadores de cada SM, con
la finalidad de coordinar adecuadamente con las protecciones de los reconectadores,
mantenindose pocas modificaciones en los ajustes de los generadores.
A continuacin se informa acerca de los ajustes de cada instalacin de los distintos SM.

Informe Tcnico

Pgina 20

6 Protecciones Consideradas en el Estudio

6.1 Esquemas de Protecciones Punta Arenas


6.1.1 Instalaciones de Generacin
Ajuste 50

Ajustes 51

Punta Arenas
Tiempo Definido
Generador

Proteccin

TT/CC

Trip [A] Trip [A]


sec

pri

Tiempo Inverso

Tiempo Definido
Trip [A] Trip [A]

Trip [A] Trip [A]


TMS [s]

sec

pri

TMS [s]

2000/5

Curva de Tiempo

TMS [s]

1200

IEC Normal Inversa (255-3)

0,54

5,8875

942

ANSI/IEEE Mode Inversa

4,25

170

ANSI/IEEE Inversa

sec

pri

Unidad Hitachi a GAS

Unidad Solar Mars a GAS

800/5

Unidad Caterpillar a GAS

200/5

Unidad Solar Titn a GAS

1200/5

40

9600

5,4

1296

IEC Normal Inversa (255-3)

0,8

Turbina a GAS GE 12.22 MVA

800/5

5,8

928

5,75

920

IEC Normal Inversa (255-3)

0,07

T.G. SOLAR TITAN

1200/5

3,6

864

IEC Very Inversa

11

25

1000

Cuadro 5 Resumen Protecciones generadores SM Punta Arenas

6.1.2 Instalaciones de Transmisin


Sobrecorriente Residual
Ajuste 50N

Ajustes 51N

Linea de transmisin 66 kV
Tiempo Definido
N
1
2

Subestacin

TT/CC

Trip [A] Trip [A]

Tiempo Inverso

Tiempo Definido
Trip [A] Trip [A]

Trip [A] Trip [A]

sec

pri

TMS [s]

sec

pri

TMS [s]

sec

pri

Curva de Tiempo

TMS [s]

Tres Puentes

400/5

8,4

672

0,04

5,25

420

1,58

126,4

IEC Normal Inversa (255-3)

0,05

Punta Arenas

400/5

8,4

672

0,04

5,25

420

1,58

126,4

IEC Normal Inversa (255-3)

0,05

Cuadro 6 Resumen Ajustes de 50/51N Lnea de Transmisin

Informe Tcnico

Pgina 21

6 Protecciones Consideradas en el Estudio

Sobrecorriente Direccional de fase


Ajuste 67
Linea de transmisin 66 kV
Tiempo Inverso

Tiempo Definido
N

Subestacin

TT/CC

Tres Puentes

Punta Arenas

Direccin Trip [A] Trip [A]

Trip [A] Trip [A]

sec

pri

Curva de Tiempo

TMS [s]

Direccin

sec

pri

TMS [s]

400/5

7,6

608

0,5

Forward

3,99

319,2

IEC Normal Inversa (255-3)

0,07

Forward

400/5

1,48

116

0,04

Forward

0,84

67,2

IEC Normal Inversa (255-3)

0,07

Forward

400/5

9,2

736

0,04

Forward

400/5

7,6

608

0,5

Forward

3,99

319,2

IEC Normal Inversa (255-3)

0,07

Forward

400/5

1,48

116

0,04

Forward

0,84

67,2

IEC Normal Inversa (255-3)

0,07

Forward

400/5

9,2

736

0,04

Forward

Cuadro 7 Resumen Ajustes de 67 Lnea de Transmisin

6.1.3 Instalaciones de Clientes


En el siguiente cuadro se resume la informacin de protecciones asociada a los alimentadores de
Clientes.
Ajustes 51

Ajustes 51N

Punta Arenas
Tiempo Definido
Trip [A] Trip [A]
Alimentador Proteccin

Tipo

TT/CC

Tiempo Inverso
Trip [A] Trip [A]

TMS [s]
sec

pri

Tiempo Definido
Trip [A] Trip [A]

Curva de Tiempo
sec

TMS [s]

pri

TMS [s]
sec

pri

51/51N

P141 Alstom 500/5

300

0,2

IEC Normal Inversa (255-3)

100

0,60

51/51N

P141 Alstom 500/5

400

0,2

IEC Normal Inversa (255-3)

100

0,60

51/51N

P141 Alstom 500/5

300

0,2

IEC Normal Inversa (255-3)

100

0,60

51/51N

P141 Alstom 500/5

12

1200

0,05

300

IEC Normal Inversa (255-3)

0,095

100

0,60

51/51N

P141 Alstom 500/5

22

2200

0,05

300

IEC Normal Inversa (255-3)

0,010

100

0,60

51/51N

P141 Alstom 500/5

12

1200

0,2

300

IEC Normal Inversa (255-3)

0,120

100

0,60

51/51N

P141 Alstom 500/5

12

1200

0,05

300

IEC Normal Inversa (255-3)

0,075

100

0,60

51/51N

P141 Alstom 500/5

300

0,2

IEC Normal Inversa (255-3)

100

0,60

51/51N

P141 Alstom 500/5

300

0,2

IEC Normal Inversa (255-3)

100

0,60

10

51/51N

P141 Alstom 500/5

300

0,2

IEC Normal Inversa (255-3)

100

0,60

11

51/51N

P141 Alstom 500/5

12

1200

0,075

100

0,60

300

IEC Normal Inversa (255-3)

0,075

Cuadro 8 Informacin de Proteccin de clientes sistema Punta Arenas

Informe Tcnico

Pgina 22

6 Protecciones Consideradas en el Estudio

6.2 Esquema de Protecciones Sistema Puerto Natales


6.2.1 Instalaciones de Generacin
En el cuadro siguiente se resume la informacin de protecciones de los generadores
Ajuste 50

Ajustes 51

Ajustes 51N

Puerto Natales
Tiempo Definido
N

Generador

TT/CC

Trip [A] Trip [A]

Trip [A] Trip [A]

Curva de Tiempo

sec

pri

TMS [s]

sec

pri

TMS [s]

Motor-Generador DIESEL (300 kW) F.Morse

400/5

15

1200

560

0,82

Motor-Generador a GAS - Waukesha

200/5

20

800

Turbina Solar Saturno a GAS

200/5

20

800

Turbina Solar Saturno a GAS

100/5

Motor-Generador Caterpillar a DIESEL-PN

400/5

15

1200

Motor-Generador a GAS - Waukesha

5000/5

10

3000/5

16,5

sec

TMS [s]

pri

Trip [A] Trip [A]


sec

pri

TMS [s]

80

0,05

360

IEC Normal Inversa (255-3)

0,08

40

0,05

360

IEC Normal Inversa (255-3)

0,08

40

0,05

180

IEC Normal Inversa (255-3)

0,08

20

0,05

17,5

350

0,3

560

0,82

80

0,05

10000

4,5

4500

0,82

1000

0,05

9900

4200

IEC Normal Inversa (255-3)

Cuadro 9 Resumen protecciones generador SM Puerto Natales

6.2.2 Instalaciones de Transmisin


En este sistema no existen instalaciones de transmisin para los cuales evaluar la coordinacin de protecciones.

Informe Tcnico

Tiempo Definido

Trip [A] Trip [A]

10 Jenbacher 1.42 MW

Tiempo Inverso

Tiempo Definido

Pgina 23

0,09

6 Protecciones Consideradas en el Estudio

6.2.3 Instalaciones de Clientes


En el siguiente cuadro se resume la informacin de protecciones asociada a los alimentadores de Clientes.
Ajustes 51

Ajustes 51N

Puerto Natales
Tiempo Inverso
Alimentador Proteccin

Tipo

TT/CC

Trip [A] Trip [A]


sec
pri

Tiempo Definido

Curva de Tiempo

TMS [s]

Trip [A] Trip [A]


Trip [A] Trip [A]
TMS [s]
TMS [s]
sec
pri
sec
pri

51/51N

P141 Alstom 100/5

80

IEC Normal Inversa

0,10

32,5

650

0,06

20

0,48

51/51N

P141 Alstom 100/5

60

IEC Normal Inversa

0,14

32,5

650

0,06

20

0,45

51/51N

P141 Alstom 100/5

80

IEC Normal Inversa

0,10

32,5

650

0,06

20

0,45

51/51N

P141 Alstom 100/5

60

IEC Normal Inversa

0,14

32,5

650

0,06

20

0,45

Cuadro 10 Informacin de Proteccin de clientes sistema Puerto Natales

Informe Tcnico

Tiempo Definido

Pgina 24

6 Protecciones Consideradas en el Estudio

6.3 Esquema de Protecciones Sistema Porvenir


6.3.1 Instalaciones de Generacin
En el cuadro siguiente se resume la informacin de protecciones de los generadores

Ajuste 50

Ajustes 51

Ajustes 51N

Porvenir
Tiempo Definido
N
1
4

Generador

Caterpillar DIESEL 1- PO
Waukesha - PO

TT/CC
1000/5

Trip [A] Trip [A]


sec

pri

TMS
[s]

20

4000

0,05

Tiempo Inverso

Tiempo Definido
Trip [A] Trip [A]
sec

pri

Trip [A] Trip [A]


TMS
[s]

Curva de Tiempo
sec

pri

TMS [s]

1000

0,85

2000/5

2000

0,85

2000

IEC Normal Inversa

0,15

Caterpillar DIESEL 2- PO

500/5

2,5

250

0,85

2,5

250

IEC Normal Inversa

0,16

Waukesha -PO

2500/5

2500

0,85

2500

IEC Normal Inversa

0,16

Waukesha -PO

2500/5

2500

0,85

2500

IEC Normal Inversa

0,16

Palmero 1.36 MW

3000/5

15

9000 0,05

3000

0,85

Caterpillar DIESEL - PA

2000/5

23

9200 0,05

2000

0,85

2500/5

17

8500 0,05

2500

0,85

10 GE Jenbacher JM416 1

Trip [A] Trip [A]


sec

pri

20

4000

0,05

16

16

8000

En este sistema no existen instalaciones de transmisin para los cuales evaluar la coordinacin de protecciones.

sec

pri

TMS
[s]

1,6

660

IEC Normal Inversa 0,35

1,5

750

IEC Normal Inversa 0,34

3000

IEC Normal Inversa 0,16

Curva de Tiempo

0,05

8000 0,05

6.3.2 Instalaciones de Transmisin

Pgina 25

Trip [A] Trip [A]


TMS
[s]

Cuadro 11 Resumen protecciones generador SM Porvenir

Informe Tcnico

Tiempo Inverso

Tiempo Definido

6 Protecciones Consideradas en el Estudio

6.3.3 Instalaciones de Clientes


En el siguiente cuadro se resume la informacin de protecciones asociada a los alimentadores de
Clientes.
Ajustes 51

Ajustes 51N

Porvenir
Tiempo Inverso

Tiempo Definido

Trip [A] Trip [A]


Alimentador Proteccin

Tipo

TT/CC

Trip [A] Trip [A]


Curva de Tiempo TMS [s]

sec

pri

Tiempo Definido
Trip [A] Trip [A]

TMS [s]
sec

pri

TMS [s]
sec

pri

51/51N

P141 Alstom

50/5

50

Kyle 112

65

650

0,05

10

0,5

51/51N

P141 Alstom

50/5

70

Kyle 112

65

650

0,05

10

0,5

51/51N

P141 Alstom

50/5

50

Kyle 112

65

650

0,05

10

0,5

51/51N

P141 Alstom

50/5

50

Kyle 112

65

650

0,05

10

0,5

Cuadro 12 Informacin de Proteccin de clientes sistema Porvenir

6.4 Esquema de Protecciones Sistema Puerto Williams


6.4.1 Instalaciones de Generacin
Unidad generadora

Unidad Generadora

Unidad N 1 Caterpillar 3508B

Unidad N 3 Caterpillar

Interruptor 52G1, Cutler Hammer, Digitrip

Interruptor 52G3, Merlin Gerin, STR38S

In: 1600 Amp.

In: 800Amp.

Long delay setting: 0.8

Io: 0.8

Long delay time: 2

Ir: 0.85

Short delay setting: 3

Im: 8

Short delay time: 0.5*

Tm: 0.4

Instantaneous: OFF

I: 7

Unidad N 2 Caterpillar 3508

Unidad N 6 Cummins - Petbow

Interruptor 52G2, Merlin Gerin, STR28D

Interruptor 52G6, Merlin Gerin, STR38S

In: 1600 Amp.

In: 800Amp.

Ir: 1

Io: 0.8

Im: 10

Ir: 0.85
Im: 8
Tm: 0.4
I: 7

Cuadro 13 Informacin de protecciones de Unidades generadoras en sistema Puerto Williams

Informe Tcnico

Pgina 26

6 Protecciones Consideradas en el Estudio

6.4.2 Instalaciones de Transmisin


En este sistema no existen instalaciones de transmisin para los cuales evaluar la coordinacin de
protecciones.

6.4.3 Instalaciones de Clientes


En el siguiente cuadro se resume la informacin de protecciones asociada a los alimentadores de
Clientes.
Ajustes 51

Ajustes 51N

Tiempo Inverso

Tiempo Inverso

Puerto Williams
Trip [A] Trip [A]
Alimentador Proteccin

Tipo

TT/CC

Trip [A] Trip [A]


Curva de Tiempo TMS [s]

sec

pri

Curva de Tiempo TMS [s]


sec

pri

51/51N

NOVA Form 5 1000/1

0,02

20

Kyle 104

1,0

0,01

10

Kyle 104

0,5

51/51N

NOVA Form 5 1000/1

0,02

20

Kyle 104

1,0

0,01

10

Kyle 104

0,5

51/51N

NOVA Form 5 1000/1

0,02

20

Kyle 104

1,0

0,01

10

Kyle 104

0,5

Cuadro 14 Informacin de Proteccin de clientes sistema Puerto Williams

Informe Tcnico

Pgina 27

7 Desarrollo de los Estudios

7 Desarrollo de los Estudios


En primer trmino el estudio considera efectuar una determinacin del tiempo mximo para
despeje de fallas que debern poseer las protecciones de los distintos elementos, generacin,
transmisin y consumos, los cuales debern estar determinados en funcin de la prdida de
estabilidad de cada sistema.
Posteriormente se determinarn los niveles de cortocircuito en cada Sistema Mediano, en
condiciones de demanda mnima y mxima, con la finalidad de obtener las mximas corrientes de
falla que se espera en cada condicin de demanda. Dichos valores permitirn aportar una idea de si
los ajustes de cada proteccin se encuentran suficientemente bien determinados, adems de
obtener el crecimiento de estos valores en el periodo 2011-2014.
En tercer trmino est contemplado modelar las protecciones en el simulador Power Factory y
determinar para diferentes situaciones de fallas la efectiva coordinacin de las protecciones. Esta
verificacin se efectuar mediante el aporte de curvas de operacin aportadas por las propias
protecciones simuladas en Power Factory.

7.1 Determinacin del tiempo mximo de despeje de fallas en


instalaciones de Edelmag
A continuacin y cumpliendo con uno de los puntos bsicos que establece la NT para este estudio,
se determinar el tiempo mximo para despeje de falla que se deber cumplir para los distintos
tipos de instalaciones, el tiempo mximo deber ser determinado de tal forma que no implique
poner en riesgo la operacin de los Sistemas Medianos.
Segn la propia NTSyCS de SM, el tiempo de Tiempo mximo para despeje de falla corresponde al

Tiempo transcurrido desde el momento del inicio de la falla hasta la extincin del arco en el
interruptor, para fallas que ocurran en los equipamientos de la unidad generadora directamente
conectados al SM o en las instalaciones o equipamientos de las Instalaciones de Transmisin.
Para tal efecto la determinacin del tiempo mximo para despeje de fallas se determinar como:

Se considerar el comportamiento de los sistemas de control de tensin y frecuencia de


cada unidad generadora, por cuanto influyen directamente en el comportamiento dinmico
del sistema interconectado ante fallas severas.

El tiempo mximo de despeje de falla se determinar para las contingencias de mayor


severidad, esto es, fallas del tipo trifsicas en puntos cercanos de las barras de los
generadores. Lo anterior con diferentes duraciones de las fallas aplicadas.

Se medir en cada caso el ngulo rotrico de las unidades generadoras, adoptando para
dicha variable un valor mximo de 120 para la primera excursin angular, medidos
respecto de una referencia angular nica representativa de la posicin del eje inercial de
cada SM. Dicho valor representar el valor lmite sobre el cual se estima prdida de
estabilidad de las unidades generadoras.

Informe Tcnico

Pgina 28

7 Desarrollo de los Estudios

La determinacin anterior se efectuar para los despachos de generacin que se presentan con
mayor probabilidad en la operacin de cada sistema. Con la finalidad de obtener un nico valor
representativo del periodo se efectuar una revisin con la operacin estimada para al ao 2014.
De acuerdo con el tamao de los Sistemas Medianos, se determinarn tiempos mximos de despeje
de falla para dos tipos de SM. Uno para el SM de Punta Arenas y otro para los dems SM.
En el cuadro siguiente se resume la operacin de los SM para las fallas aplicadas y para los
diferentes tiempos de despeje de las mismas. El detalle grfico de estas simulaciones se encuentra
incorporadas en el Anexo N1 de este informe.
SM Punta Arenas
Tiempo de Despeje de falla Mayor ngulo rotrico

Estabilidad dinmica

seg

[ ]

2,00

179

Inestable

1,50

138

Inestable

1,45

126

Inestable

1,40

114

Estable

1,35

107

Estable

1,25

90

Estable

Cuadro 15 Determinacin tiempo de despeje SM Punta Arenas


Otros Sistemas Medianos
Tiempo de Despeje de falla Mayor ngulo rotrico

Estabilidad dinmica

seg

[ ]

1,50

175

Inestable

1,30

175

Inestable

1,00

111 (*)

Inestable

0,90

97 (*)

Inestable

0,80

70

Estable

0,60

70

Estable

Cuadro 16 Determinacin tiempo de despeje Otros SM

(*): Se observa que pese a que se obtiene un valor mximo del ngulo en la primera oscilacin
menor a 120 , el sistema sigue un comportamiento inestable.

Informe Tcnico

Pgina 29

7 Desarrollo de los Estudios

De acuerdo con los resultados obtenidos e indicados en los cuadros anteriores y considerando un
grado de seguridad en la determinacin del tiempo mximo de despeje de fallas, se propone utilizar
para cada SM un tiempo mximo de despeje de fallas de:
Tiempo mximo de despeje de Falla (TMdF)
TMdF

Sistemas Medianos

[seg]

Punta Arenas

1,35

Otros Menores

0,8

Cuadro 17 TMdF propuestos

7.2 Estudios de Cortocircuitos


A continuacin se presentan los resultados de las simulaciones de cortocircuitos esperadas para
cada uno de los sistemas medianos. Los niveles de cortocircuitos determinados corresponden a
fallas en barras principales de cada SM.
Los niveles de cortocircuito se determinan para la condicin de demanda mxima y mnima que se
presentan anualmente en cada Sistema Mediando en el periodo 2011-2014.
La determinacin de los niveles de cortocircuito se efecta bajo la Norma Internacional IEC, con
factores de tensiones de prefalla de 1,1 sobre tensiones nominales para el caso de cortocircuitos en
demanda mxima y de 1,0 para cortocircuitos en demanda mnima. Los clculos se efectan sin
impedancias de falla.

7.2.1 Resultados para SM Punta Arenas


Niveles de Cortocircuitos Sistema Punta Arenas
Mnima
Ao

Barras

Monofsico

Mxima

Trifsico

Monofsico

Trifsico

MVA

kA

MVA

kA

MVA

kA

MVA

kA

13.2 kV P.A.

64,60

2,83

49,30

2,16

86,96

3,80

68,71

3,01

2011 13.2 kV T.P.

78,36

3,43

85,50

3,74

115,85

5,07

158,28

6,92

11.5 kV T.P.

130,00

6,53

151,11

7,59

215,53 10,82 405,76 20,37

13.2 kV P.A.

72,00

3,15

55,13

2,41

86,96

3,80

68,71

3,01

2012 13.2 kV T.P.

88,48

3,87

102,80

4,50

115,85

5,07

158,28

6,92

11.5 kV T.P.

160,30

8,05

214,71 10,78 215,53 10,82 405,76 20,37

13.2 kV P.A.

72,00

3,15

55,13

2,41

86,96

3,80

68,71

3,01

2013 13.2 kV T.P.

88,48

3,87

102,80

4,50

115,85

5,07

158,28

6,92

11.5 kV T.P.

160,30

8,05

214,71 10,78 215,53 10,82 405,76 20,37

13.2 kV P.A.

72,00

3,15

55,13

2,41

86,96

3,80

68,71

3,01

2014 13.2 kV T.P.

88,48

3,87

102,80

4,50

115,85

5,07

158,28

6,92

11.5 kV T.P.

160,30

8,05

214,71 10,78 215,53 10,82 405,76 20,37

Cuadro 18 Niveles de Cortocircuito SM Punta Arenas

Informe Tcnico

Pgina 30

7 Desarrollo de los Estudios

7.2.2 Resultados para SM Puerto Natales


Niveles de Cortocircuitos Sistema Puerto Natales
Mnima
Ao Barras Monofsico

Mxima

Trifsico

Monofsico

Trifsico

MVA

kA

MVA kA

MVA

kA

MVA kA

2011 13.2 kV

16,66

0,73

11,22

0,49

41,61

1,82

28,55

1,25

2012 13.2 kV

21,65

0,95

14,64

0,64

43,86

1,92

30,11

1,32

2013 13.2 kV

21,15

0,92

14,28

0,62

50,30

2,20

34,70

1,52

2014 13.2 kV

21,15

0,92

14,28

0,62

50,30

2,20

34,70

1,52

Cuadro 19 Niveles de Cortocircuito SM Puerto Natales

7.2.3 Resultados para SM Porvenir


Niveles de Cortocircuitos Sistema Porvenir
Mnima
Ao Barras Monofsico Trifsico
MVA

kA

MVA kA

Mxima
Monofsico

Trifsico

MVA

kA

MVA kA

2011

13.2 kV

16,11

0,67

10,86

0,45

32,69

1,37

22,35

0,94

2012

13.2 kV

15,87

0,66

10,70

0,45

32,44

1,36

22,17

0,93

2013

13.2 kV

15,87

0,66

10,70

0,45

32,44

1,36

22,17

0,93

2014

13.2 kV

15,87

0,66

10,70

0,45

32,44

1,36

22,17

0,93

Cuadro 20 Niveles de Cortocircuito SM Porvenir

7.2.4 Resultados para SM Puerto Williams


Niveles de Cortocircuitos Sistema Puerto Williams
Mnima
Ao Barras Monofsico
MVA

kA

Mxima

Trifsico
MVA kA

Monofsico
MVA

kA

Trifsico
MVA kA

2011

13.2 kV

4,68

0,20

3,17

0,14

9,75

0,43

6,72

0,29

2012

13.2 kV

4,68

0,20

3,17

0,14

9,75

0,43

6,72

0,29

2013

13.2 kV

4,68

0,20

3,17

0,14

9,75

0,43

6,72

0,29

2014

13.2 kV

4,68

0,20

3,17

0,14

9,75

0,43

6,72

0,29

Cuadro 21 Niveles de Cortocircuito SM Puerto Williams

Informe Tcnico

Pgina 31

7 Desarrollo de los Estudios

7.2.4.1

Comentarios:

En muchos casos se presentan idnticos valores de nivel de cortocircuito en el periodo


2011-2014, lo cual indica que las unidades que abastecen la demanda son las mismas,
aunque con un nivel distinto de despacho de generacin, sin embargo, para las corrientes
de fallas el nivel de generacin no resulta relevante.

Slo en sistema de Punta Arenas, se aprecia un crecimiento en el nivel de cortocircuito,


tanto trifsico como monofsico. En los dems sistemas se observan valores similares en
cada ao.

7.3 Corrientes de Carga por Alimentador


A continuacin se indican las corrientes de carga mxima por alimentador de cada sistema
elctrico, lo cual permitir determinar sobre qu valor de corriente deben ajustarse los primeros
ajustes de operacin de protecciones.
Los valores indicados en tabla corresponden al mayor valor que cada alimentador alcanza en el
periodo 2011-2014, y que por el nivel de crecimiento de los consumos estos se presentan en el ao
2014.
Corrientes de Carga Mxima por Alimentadores
Demanda Mxima

Alimentador
MVA

Fp

KAmp

Kamp Total

Alimentador-1

AL-1

4,579

0,986

0,219

219

Alimentador-2

AL-2

4,579

0,998

0,225

225

Alimentador-3

AL-3

5,309

0,96

0,263

263

Alimentador-4

AL-4

3,848

0,992

0,187

187

Alimentador-5

AL-5

4,384

0,99

0,199

199

Alimentador-6

AL-6

2,435

0,983

0,116

116

Alimentador-7

AL-7

2,776

0,968

0,133

133

SM Punta Arenas

AL-8A

2,557

0,958

0,125

AL-8B

2,557

0,958

0,124

AL-9

5,017

0,961

0,243

AL-X10A

1,364

0,954

0,064

AL-X10B

1,364

0,954

0,064

Alimentador-X11

AL-X11

2,776

0,958

0,133

133

Alimentador-12

AL-12

2,435

0,983

0,108

108

Alimentador-13

AL-13

2,728

0,954

0,124

124

Alimentador-8
Alimentador-9
Alimentador-10

249
243
128

Cuadro 22 Nivel mximo de corriente de carga en Alimentadores SM Punta Arenas

Informe Tcnico

Pgina 32

7 Desarrollo de los Estudios

Corrientes de Carga Mxima por Alimentadores


Demanda Mxima

Alimentador
MVA

Fp

KAmp

AL1-1

0,242

0,936

0,012

AL1-2

0,242

0,936

0,012

AL1-3

0,242

0,936

0,012

AL1-4

0,242

0,936

0,012

AL1-5

0,242

0,936

0,012

AL1-6

0,242

0,936

0,012

AL2-1

0,486

0,991

0,022

AL2-2

0,486

0,991

0,022

AL3-1

0,863

0,96

0,04

AL3-2

0,863

0,96

0,04

AL4-1

0,582

0,965

0,027

AL4-2

0,582

0,965

0,027

SM Puerto Natales

Alimentador 1

Alimentador 2
Alimentador 3
Alimentador 4

Amp Total

72

44

80

54

Cuadro 23 Nivel mximo de corriente de carga en Alimentadores SM Puerto Natales

Corrientes de Carga Mxima por Alimentadores


Demanda Mxima

Alimentador
MVA

Fp

KAmp

Amp Total

AL1

0,49

0,964

0,021

21

AL2-1

0,223

0,89

0,011

22

AL2-2

0,223

0,89

0,011

AL3

1,85

0,953

0,081

AL4

0,842

0,994

0,036

SM Porvenir

Alimentador 1
Alimentador 2
Alimentador 3
Alimentador 4

81
36

Cuadro 24 Nivel mximo de corriente de carga en Alimentadores SM Porvenir

Corrientes de Carga Mxima por Alimentadores


Demanda Mxima

Alimentador
MVA

Fp

KAmp

Amp Total

AL1

0,49

0,964

0,021

AL2

0,223

0,89

0,011

0,953

0,081

21
11
81

SM Puerto Williams

Alimentador 1
Alimentador 2
Alimentador 3

AL3

1,85

Cuadro 25 Nivel mximo de corriente de carga en Alimentadores SM Puerto Williams

7.3.1 Comentarios
El nivel de carga mximo esperado en el periodo 2011-2014 permite verificar si los ajustes de las
protecciones deben modificar sus ajustes para adecuarse al crecimiento de la demanda. Este valor
define el punto para el cual la proteccin no debe activarse.

Informe Tcnico

Pgina 33

7 Desarrollo de los Estudios

7.4 Verificacin de la Coordinacin


La verificacin de la coordinacin de protecciones se efectuar mediante el anlisis de curvas de
operacin. Para tal efecto se modelar cada proteccin con el simulador Power Factory. En los
casos que por obsolescencia tecnologa no se puedan representar mediante un modelo digital,
sern modeladas por un modelo aproximado.
En primer trmino se evaluar el nivel de coordinacin de las protecciones de los alimentadores y
posteriormente las correspondientes a sistemas de transmisin y generadores.

7.4.1 Coordinacin de Protecciones en Alimentadores


Para fallas que ocurran aguas abajo de los alimentadores, estas deben ser despejadas por cada
alimentador. Se debe verificar en cada caso que estas protecciones resultan ms rpidas en operar
que las correspondientes de los generadores o de otras instalaciones de transmisin. Especialmente
para los SM donde no existen sistemas de transmisin y tanto la generacin como los
alimentadores se conectan en una barra comn.
Como los alimentadores no poseen generacin aguas abajo que contribuyan con aportes de
corriente a las fallas que se originen en el sistema elctrico, no se requiere especificar
direccionalidad a las protecciones de sobrecorrientes.
Adicionalmente, las fallas que suceden en un alimentador, sus efectos, no provocan problemas en
otros alimentadores, es decir, sus protecciones no se enteran de la sobrecorriente en otros puntos.
El efecto directo, de no ser despejada adecuadamente la falla en el alimentador se produce sobre
todas las unidades generadoras, las cuales actuarn de acuerdo con sus tiempos de despeje.
A continuacin se informa acerca de los tiempos de actuacin de las protecciones de los
alimentadores ante fallas que se registren en sus propias instalaciones. Estos tiempos sern
posteriormente contrastados con los tiempos de operacin de protecciones de los generadores y as
verificar la correcta coordinacin de protecciones en cada alimentador.
La informacin base que respalda el resumen de los cuadros siguientes se encuentra en el Anexo
N 02, donde se aportan las curvas de operacin de protecciones de cada alimentador y su punto
de operacin (tiempo de actuacin) ante la falla.

Informe Tcnico

Pgina 34

7 Desarrollo de los Estudios

Operacin de Protecciones de Alimentadores


Corriente de falla

Corriente Carga
Alimentador Descripcin

Falla Trifsica

Verificacin
Falla Monofsica

Mxima
0 Ohms T Operacin 20 Ohms T Operacin 0 Ohms T Operacin 20 Ohms T Operacin Coordinacin
SM Punta Arenas

Amp

KA

mseg

KA

mseg

KA

mseg

KA

mseg

Protecciones

AL-1

Alimentador-1

219

1,831

300

0,381

300

2,086

620

0,383

620

Ok

AL-2

Alimentador-2

225

1,276

300

0,585

300

1,389

620

0,355

620

Ok

AL-3

Alimentador-3

263

1,998

300

0,387

300

2,200

620

0,389

620

Ok

AL-4

Alimentador-4

187

3,068

140

0,391

2498

2,686

620

0,391

620

Ok

AL-5

Alimentador-5

199

3,599

120

0,397

248

3,071

620

0,397

620

Ok

AL-6

Alimentador-6

116

3,068

290

0,391

3155

2,686

620

0,391

620

Ok

AL-7

Alimentador-7

133

3,068

170

0,391

1972

2,686

620

0,391

620

Ok

AL-8

Alimentador-8

249

1,998

300

0,387

300

2,310

620

0,389

620

Ok

AL-9

Alimentador-9

243

2,193

300

0,393

300

2,580

620

0,396

620

Ok

AL-10

Alimentador-10

128

1,998

300

0,387

300

2,310

620

0,391

620

Ok

AL-11

Alimentador-11

133

1,988

155

0,391

1972

2,686

620

0,389

620

Ok

Amp

KA

mseg

KA

mseg

KA

mseg

KA

mseg

Protecciones

AL-1

Alimentador-1

72

1,286

245

0,348

470

1,692

600

0,357

600

Ok

AL-2

Alimentador-2

44

1,222

190

0,339

406

1,564

570

0,348

570

Ok

AL-3

Alimentador-3

80

1,286

245

0,348

470

1,692

570

0,357

570

Ok

AL-4

Alimentador-4

54

1,286

180

0,348

394

1,692

570

0,357

570

Ok

Amp

KA

mseg

KA

mseg

KA

mseg

KA

mseg

Protecciones

520

Ok

SM Puerto Natales

SM Porvenir
AL-1

Alimentador-1

21

0,831

125

0,33

104

1,147

520

0,352

AL-2

Alimentador-2

22

0,831

105

0,33

107

1,147

520

0,352

520

Ok

AL-3

Alimentador-3

81

0,927

102

0,38

104

1,357

520

0,41

520

Ok

AL-4

Alimentador-4

36

0,831

102

0,33

104

1,147

520

0,352

520

Ok

Amp

KA

mseg

KA

mseg

KA

mseg

KA

mseg

Protecciones

SM Puerto Williams
AL-1

Alimentador-1

21

0,288

100

0,216

100

0,418

100

0,269

100

Ok

AL-2

Alimentador-2

11

0,288

100

0,216

100

0,418

100

0,269

100

Ok

AL-3

Alimentador-3

81

0,288

100

0,216

100

0,418

100

0,269

100

Ok

Cuadro 26 Resumen Operacin de Protecciones en Alimentadores

7.4.2 Coordinacin de Protecciones en Lnea de 66 kV


Esta medicin se efectuar slo en las instalaciones de transmisin del Sistema Mediano
correspondiente a Punta Arenas, por cuanto es el nico sistema que cuenta con este tipo de
instalaciones.
En este sistema, el de Punta Arenas, cuenta con una lnea de transmisin de 66 kV (compuesta con
dos transformadores en sus extremos) que permite la conexin de la barra de Tres Puentes 11,5 kV
y la barra de Central Punta Arenas 13,2 kV. Los transformadores de los extremos son de 33 MVA.
Informe Tcnico

Pgina 35

7 Desarrollo de los Estudios

7.4.2.1

Verificacin Coordinacin de Protecciones en Lnea 66 kV

Esta lnea de 66 kV que est compuesta en cada extremo por dos transformadores 66/13,2 kV (en
central Punta Arenas) y 66/11,5 kV (en Central Puentes) de 33 MVA, cuenta con un esquema de
protecciones idnticos en cada extremo y que est compuesto por:

Para fallas entre fases protecciones de sobrecorriente direccionales (67), ubicado en los
extremos de la lnea.

Para fallas residuales por protecciones de sobrecorriente residual (51N) que se encuentran
ubicadas en la parte de baja tensin de cada transformador.

Las protecciones de sobrecorriente direccionales cuentan con tres ajustes, uno de tiempo inverso
(normalmente inverso) y dos ajustes de tiempo definido. De igual manera la proteccin de
sobrecorriente residual.
A continuacin se revisar el esquema de protecciones para diferentes tipos de configuracin de
generacin entre central Punta Arenas y central Tres Puentes.

7.4.2.1.1

Caso sin generacin en central Punta Arenas (Caso de Mayor Probabilidad)

Para este caso se espera que el esquema de protecciones se comporte de la siguiente manera:

Para corrientes de carga la recta de corrientes debe quedar fuera de la zona de operacin
de cada proteccin. Uno de los extremos no la debe observar, dada su direccionalidad.

De existir una falla en la lnea, el extremo central Punta Arenas no ver la falla, dado que
desde su extremo no hay contribucin de corrientes hacia la falla (ausencia de generacin
en este extremo). En cambio, el extremo central Tres Puentes debe provocar la apertura en
un tiempo mnimo.

Para cualquier falla aguas arriba de la barra 66 kV de central Tres Puentes las protecciones
de sobrecorriente direccional no vern las fallas. En efecto, la proteccin de 66 kV en
central Tres Puentes ve la falla hacia atrs y la del extremo Punta Arenas 66 kV no ve
corrientes de falla por ausencia de generacin.

Para fallas que ocurran aguas debajo de la barra 66 kV Central Punta Arenas, la proteccin
de dicho extremo ver la falla hacia atrs y el del extremo 66 kV Tres Puentes si registrar
la falla, pero debe operar en un tiempo de respaldo.

7.4.2.1.2

Caso con generacin en central en Punta Arenas (Caso de menor Probabilidad)

Para esta configuracin de centrales el esquema se debe comportar como sigue:

Para la corriente de carga, la recta de corrientes, debe quedar fuera de la zona de


operacin de cada proteccin. Uno de los extremos no la debe observar, dada su
direccionalidad. La corriente de carga sigue la direccin del rea que es excedentaria en
generacin.

Informe Tcnico

Pgina 36

7 Desarrollo de los Estudios

En este caso, de existir una falla en la lnea, la falla se aprecia desde ambos extremos,
dado que desde ambos existe contribucin de corriente hacia el punto de falla.

Para fallas que ocurran fuera de la lnea, una de las protecciones ver la falla, dado que la
otra la observa en reversa.

Mediante simulaciones se determinar si el esquema de protecciones se comporta como el


indicado.
Corriente de Carga
Caso
Estudio

Verificacin

Zona Operacin
Extremo T. Puentes

Coordinacin

Extremo P. Arenas

Protecciones

Caso 1

No

No

Ok

Caso 2

No

No

Ok

Falla en lnea
Caso
Estudio

Verificacin

Zona Operacin
Extremo T. Puentes

Coordinacin

Extremo P. Arenas

Protecciones

Caso 1

Si

No

Ok

Caso 2

Si

Si

Ok

Falla en 66 KV PA
Caso
Estudio

Verificacin

Zona operacin
Extremo T. Puentes

Coordinacin

Extremo P. Arenas

Protecciones

Caso 1

Si

No

Ok

Caso 2

Si

No

Ok

Falla en 66 KV TP
Caso
Estudio

Verificacin

Zona operacin
Extremo T. Puentes

Coordinacin

Extremo P. Arenas

Protecciones

Caso 1

No

Si

Ok

Caso 2

No

Si

Ok

Cuadro 27 Resumen Operacin Esquema de protecciones de lnea 66 kV

La informacin de respaldo se encuentra en el Anexo N 3, a modo de curvas de operacin para


cada estudio.

7.4.3 Coordinacin de Protecciones en Generadores


Para verificar la efectividad en la coordinacin de protecciones de las unidades generadoras se
procedi a simular digitalmente las diferentes protecciones que cada unidad posee. En algunos
casos fue necesario asimilar la proteccin mediante un modelo aproximado, lo cual se debi
principalmente a que algunas unidades son de tecnologa electrodinmica y no cuentan con
modelos representativos de su operacin.
El procedimiento de verificacin de la coordinacin de la proteccin es el siguiente:

Informe Tcnico

Pgina 37

7 Desarrollo de los Estudios

Se determina un flujo de carga con demanda mxima en cada sistema, lo cual permite
verificar que con los aumentos de la carga esperada en el periodo 2011-2014 no se activen
zonas de operacin de protecciones.

Se efectan fallas cercanas y alejadas de la barra donde se conecta cada generador, esto
permite determinar el tiempo de operacin de la proteccin y comparacin con los dems
tiempos de operacin de otras instalaciones, especialmente con la operacin de
protecciones de los alimentadores.

En un mismo grfico se han incluido las corrientes de flujos de carga, corrientes de fallas
cercanas y alejadas, ms la curva de operacin de las protecciones. Esto permite
determinar los tiempos de operacin de cada proteccin.

Slo se ha modelado las protecciones de sobrecorrientes entre fases (51) por cuanto la
mayora de las unidades generadoras slo posee este tipo de protecciones de
sobrecorriente.

A continuacin se aporta en un cuadro resumen la operacin de los generadores de cada sistema,


con que se cont con informacin para efectuar la simulacin.
Operacin de Protecciones Unidades Generadoras
Unidad
Sistema

Generadora
Unidad Hitachi a GAS

Punta Arenas

Puerto Natales

Porvenir

Puerto Williams

Flujo de Carga

Falla Alejada

Falla Cercana

Amp

seg

kA

mseg

KA

994

2,519

5059

7,623

2007

Coordinacin

mseg Protecciones
Ver Nota

Unidad Solar Mars a GAS

516

1,161

7440

3,513

1227

OK

Unidad Caterpillar a GAS

131

0,777

567

0,83

512

OK

Unidad Solar Titn a GAS

657

2,992

6737

7,851

3053

Ver Nota

Turbina a GAS GE 12.22 MVA

253

1,065

3356

3,327

376

OK

T.G. SOLAR TITAN

709

1,379

2897

4,172

301

OK

Motor-Generador DIESEL (300 kW) F.Morse

191

0,917

840

1,436

120

OK

Motor-Generador a GAS - Waukesha

83

0,660

917

0.977

120

OK

Turbina Solar Saturno a GAS

89

0,660

917

0,977

120

OK

Turbina Solar Saturno a GAS

25

0,335

897

0,440

320

OK

Motor-Generador Caterpillar a DIESEL-PN

191

0,916

840

1,436

120

OK

Motor-Generador a GAS - Waukesha

1869

7,819

850

10,497

130

OK

Jenbacher 1.42 MW

2464

12,748

850

12,302

120

OK

Caterpillar DIESEL 1- PO

723

3,014

970

5,234

170

OK

Waukesha - PO

802

4,866

970

9,161

680

OK

0,615

970

1,045

772

OK

Caterpillar DIESEL 2- PO

161

Waukesha -PO

1574

0,655

970

12,302

692

OK

Waukesha -PO

1574

0,655

970

5,343

170

OK

Palmero 1.36 MW

2252

0,655

970

5,343

170

OK

Caterpillar DIESEL - PA

524

7,280

870

14,215

170

OK

GE Jenbacher JM416 1

1519

6,356

970

11,839

170

OK

MotorGenerador Caterpillar Diesel 3508B

783

2,328

558

6,176

153

OK

Informe Tcnico

Pgina 38

7 Desarrollo de los Estudios

MotorGenerador Caterpillar Diesel PW3508

437

2,162

464

5,234

117

OK

Motor-Generador Diesel Caterpillar (PW)

469

1,163

559

3,768

133

OK

Motor-Generador Deutz Diesel PW

369

1,710

519

2,446

310

OK

Cuadro 28 Resumen Operacin de Protecciones Unidades generadoras

Nota: Los Valores de tiempo de operacin destacados indican que para fallas cercanas la proteccin
opera con tiempos de operacin por sobre lo indicado en los anlisis de tiempo Mximo de despeje
de falla (1135 mseg), lo cual requiere ser ajustado. Sin corresponder a una descoordinacin de
protecciones, lo anterior pone en riesgo la estabilidad del sistema.
La informacin de respaldo se encuentra incluida en el Anexo N4, a modo de curvas de operacin
por cada simulacin efectuada.

7.4.4 Comentarios y Conclusiones Estudios de Verificacin de Protecciones


Los comentarios que se emiten a continuacin resultan vlidos para los cuatro Sistemas Medianos
analizados:
Se ha efectuado una verificacin de la efectiva coordinacin de las protecciones para cada una de
las instalaciones que conforman cada sistema mediano. De los resultados obtenidos se concluye
como relevante lo siguiente:

En general los ajustes actuales definidos en cada tipo de instalacin, esto es,
Alimentadores, Transmisin y Generacin, no requieren ser modificados, salvo ajustes
menores en algunos generadores, para evitar poner en riesgo la estabilidad del sistema.

En cada uno de los anlisis se ha verificado que se cumple la debida coordinacin de


protecciones. En efecto, para fallas que ocurren aguas debajo de cada alimentador se
aprecia que la falla es despejada por los propios alimentadores, los cuales responden de
manera ms rpida que los generadores y sistemas de transmisin. Para este tipo de fallas,
las protecciones de transmisin y generacin slo actan como respaldo ante fallas en el
correcto despeje de la falla.

Para fallas que ocurren aguas arriba de los alimentadores, las protecciones de los
alimentadores no participan, dado que las protecciones no registran aportes de corrientes
de falla desde los alimentadores hacia el punto de falla, lo cual se debe a que los
alimentadores no poseen generadores aguas abajo que contribuyan con corrientes de falla.

Para las lneas de transmisin se ha determinado que el esquema de protecciones opera


adecuadamente, por cuanto despeja en forma rpida las fallas que se origina en la lnea, y
acta como respaldo para fallas que ocurran fuera de la propia instalacin. Esta verificacin
se efectu para diferentes configuraciones de generacin en los extremos de la lnea.

En el caso de las unidades generadoras se ha verificado la correcta operacin de su


esquema de protecciones, actuando selectivamente y con tiempos acordes a cada falla que
se presente en el sistema, salvo los cambios que se plantean en algunos generadores del

Informe Tcnico

Pgina 39

7 Desarrollo de los Estudios

SM Punta Arenas. En efecto, para fallas que ocurren en las proximidades de la barra donde
la unidad se conecta, la proteccin acta en forma rpida. En cambio para fallas ms
alejadas acta con tiempos que permiten el despeje de las instalaciones que se encuentran
en fallas, actuando estas protecciones como respaldo sino ocurre el despeje exitoso.

En todos los casos se verific que los esquemas de protecciones no actan para las
mximas corrientes de carga esperadas en el periodo 2010-2014.

En resumen, se ha verificado el correcto desempeo del esquema de protecciones en las


instalaciones de los Sistemas Medianos operados por la empresa Edelmag.

Informe Tcnico

Pgina 40

8 Conclusiones

8 Conclusiones
Se ha efectuado un completo estudio acerca de la efectiva coordinacin del esquema de
protecciones con que cuenta cada instalacin de los sistemas mediando que opera la empresa
Edelmag.
Para tal efecto se procedi a simular digitalmente en el programa computacional de anlisis Power
Factory, el esquema de protecciones que fuera informado por Edelmag.
Tal cual lo determina la normativa vigente, se determin los tiempos mximos de despeje de falla
para los sistemas medianos.
Efectuada la modelacin se procedi a efectuar la verificacin solicitada por la normativa vigente,
para lo cual se simul diversas configuraciones de demanda y topologa de transmisin y
generacin, estudiando especialmente aquellos escenarios que presentan mayor probabilidad de
presentarse en la operacin de los sistemas elctricos.
De los anlisis efectuados y de los resultados obtenidos se concluye que el sistema de protecciones
ya implementado ms los ajustes que se han definido en los estudios que ha encargado
recientemente Edelmag, se ajusta a los requerimientos que impone la Norma tcnica, por cuanto
cumple adecuadamente con la debida coordinacin de protecciones.
En todas las instalaciones se aprecia que el esquema de protecciones acta en forma rpida para
fallas que ocurren en la propia instalacin, adems de prestar respaldo remoto para fallas que
ocurren en otras instalaciones del sistema. En el caso de los alimentadores para la operacin de los
reconectadores.
Aunque no se visualiza modificar el esquema de protecciones en el periodo 2011-2014, se plantea
revisar el esquema una vez que los estudios que ha encargado la empresa Edelmag se encuentren
finalizados.

Informe Tcnico

Pgina 41

9 Referencias

9 Referencias
[1] Norma Tcnica de Seguridad y Calidad de Servicio para Sistemas Medianos, Comisin Nacional
de Energa Enero 2006
[2] Procedimientos, Edelmag-Digsilent, Abril 2007
[3] Estudio de verificacin de Coordinacin de Protecciones, Digsilent Ltda, ao 2001
[4] Informe final Proteccin Punta Arenas II, de Digsilent, 2011 (informe preliminar)
[5] Informe final Proteccin Natales (V I), de Digsilent, 2011
[6] Informe final Proteccin Porvenir(V I), de Digsilent, 2011
[7] Ajuste Protecciones Puerto Williams, de Edelmag Agosto 2010

Informe Tcnico

Pgina 42

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

ANEXOS

1 Anexo 1 Grficos Determinacin


Tiempo Mximo de Despeje

Informe Tcnico

Pgina 43

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

DIgSILENT

Para Sistema de Punta Arenas


200,00

2.713 s
178.626 deg

SISTEMA INESTABLE

100,00

0,00

-100,00

2.713 s
-179.552 deg

-200,00
0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica

Subplot/Diagramm
Fall Trifsica: Tdespeje 2.0 seg

Date: 12/9/2011
Annex: /22
DIgSILENT

Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla


200,00

SISTEMA INESTABLE

100,00

0,00

-100,00

2.613 s
-138.050 deg

-200,00
0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla

Informe Tcnico

Subplot/Diagramm
Fall Trifsica: Tdespeje 1.5 seg

Date: 12/9/2011
Annex: /22

Pgina 44

DIgSILENT

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

200,00

SISTEMA ESTABLE

100,00

0,00

-100,00
2.313 s
-90.647 deg

-200,00
0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica

Subplot/Diagramm
Fall Trifsica: Tdespeje 1.25 seg

Date: 12/9/2011
Annex: /22
DIgSILENT

Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla


200,00

SISTEMA ESTABLE

100,00

0,00

-100,00

2.433 s
-106.782 deg

-200,00
0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla

Informe Tcnico

Subplot/Diagramm
Fall Trifsica: Tdespeje 1.35 seg

Date: 12/9/2011
Annex: /22

Pgina 45

DIgSILENT

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

200,00

SISTEMA ESTABLE

100,00

0,00

-100,00

2.443 s
-114.784 deg

-200,00
0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica

Subplot/Diagramm
Fall Trifsica: Tdespeje 1.4 seg

Date: 12/9/2011
Annex: /22
DIgSILENT

Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla


200,00

SISTEMA INESTABLE

100,00

0,00

-100,00

2.523 s
-126.041 deg

-200,00
0,0000

3,9865

7,9730

11,960

15,946

[s]

19,933

Unidad N 1 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 4 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 5 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 7 T.P.: Rotor angle with reference to reference machine angle in deg
Unidad N 9 T.P.: Rotor angle with reference to reference machine angle in deg

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas 2014: Tiempo Mximo de Despeje de Falla

Informe Tcnico

Subplot/Diagramm
Fall Trifsica: Tdespeje 1.45 seg

Date: 12/9/2011
Annex: /22

Pgina 46

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

DIgSILENT

Para Otros Sistema Medianos


200,00

SISTEMA ESTABLE

1.605 s
69.503 deg

100,00

0,00

-100,00

-200,00
-0,000

0,999
1,999
Generador N 11: Rotor angle with reference to reference machine angle in deg
Generador N 3: Rotor angle with reference to reference machine angle in deg
Generador N 8: Rotor angle with reference to reference machine angle in deg
Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

Estudios Norma Tcnica

Angulo

Falla Trifsica: Tiempor de despeje 0.6 seg

4,997

Date: 12/9/2011
Annex: /6
DIgSILENT

Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla

[s]

200,00

SISTEMA ESTABLE

1.809 s
70.534 deg

100,00

0,00

-100,00

-200,00
-0,000

0,999
1,999
Generador N 11: Rotor angle with reference to reference machine angle in deg
Generador N 3: Rotor angle with reference to reference machine angle in deg
Generador N 8: Rotor angle with reference to reference machine angle in deg
Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla

Informe Tcnico

Falla Trifsica: Tiempor de despeje 0.8 seg

[s]

Angulo

4,997

Date: 12/9/2011
Annex: /6

Pgina 47

DIgSILENT

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

200,00

SISTEMA INESTABLE

1.991 s
96.681 deg
100,00

0,00

-100,00

-200,00
-0,000

0,999
1,999
Generador N 11: Rotor angle with reference to reference machine angle in deg
Generador N 3: Rotor angle with reference to reference machine angle in deg
Generador N 8: Rotor angle with reference to reference machine angle in deg
Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

Estudios Norma Tcnica

200,00

Angulo

Falla Trifsica: Tiempor de despeje 0.9 seg

4,997

Date: 12/9/2011
Annex: /6
DIgSILENT

Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla

[s]

2.288 s
175.474 deg
SISTEMA INESTABLE

100,00

0,00

-100,00

-200,00
-0,000

0,999
1,999
Generador N 11: Rotor angle with reference to reference machine angle in deg
Generador N 3: Rotor angle with reference to reference machine angle in deg
Generador N 8: Rotor angle with reference to reference machine angle in deg
Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla

Informe Tcnico

Falla Trifsica: Tiempor de despeje 1.5 seg

[s]

Angulo

4,997

Date: 12/9/2011
Annex: /6

Pgina 48

DIgSILENT

1 Anexo 1 Grficos Determinacin Tiempo Mximo de Despeje

200,00

SISTEMA INESTABLE

2.053 s
110.732 deg
100,00

0,00

-100,00

-200,00
-0,000

0,999
1,999
Generador N 11: Rotor angle with reference to reference machine angle in deg
Generador N 3: Rotor angle with reference to reference machine angle in deg
Generador N 8: Rotor angle with reference to reference machine angle in deg
Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

Estudios Norma Tcnica

Angulo

Falla Trifsica: Tiempor de despeje 1.0 seg

4,997

Date: 12/9/2011
Annex: /6
DIgSILENT

Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla

[s]

200,00
2.288 s
175.474 deg

SISTEMA INESTABLE

100,00

0,00

-100,00

-200,00
-0,000

0,999
1,999
Generador N 11: Rotor angle with reference to reference machine angle in deg
Generador N 3: Rotor angle with reference to reference machine angle in deg
Generador N 8: Rotor angle with reference to reference machine angle in deg
Generador N 9: Rotor angle with reference to reference machine angle in deg

2,998

3,998

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales: Tiempo mximo de despeje de falla

Informe Tcnico

Falla Trifsica: Tiempor de despeje 1.3 seg

[s]

Angulo

4,997

Date: 12/9/2011
Annex: /6

Pgina 49

2 Anexo 2 Curvas de Coordinacin Alimentadores

2 Anexo 2 Curvas de Coordinacin


Alimentadores

ANEXOS

Informe Tcnico

Pgina 50

2 Anexo 2 Curvas de Coordinacin Alimentadores

Curvas de Operacin para Fallas entre Fases

Informe Tcnico

Pgina 51

10

X =218,521 pri.A

I =1831,070 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

A01-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

A01-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s
[s]

[s]

1988.579 pri.A
0.300 s

1
968.236 pri.A
0.700 s
0.220 s

0,1

1000

[pri.A]

10000

0,1
13,20 kV 100

13.2 kV P.A.\AL 1\A01-51

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
X =224,756 pri.A

10

[pri.A]

10000

13.2 kV P.A.\AL 1\A01-51N


Alimentador 1
Falla Trifsica sin impedancia de falla

I =1276,338 pri.A

Date: 12/5/2011
Annex:
DIgSILENT

0,01
13,20 kV 100

10
A02-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

A02-51
Ipset: 4,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s
[s]

[s]

986.684 pri.A
0.700 s

1801.995 pri.A
0.300 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 2\A02-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 2\A02-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 2

Falla Trifsica sin impedancia de falla

[pri.A]

10000

Date: 12/5/2011
Annex:

Pgina 52

X =263,108 pri.A

10

I =1997,986 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10
A03-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

A03-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

837.751 pri.A
0.700 s
1

0.620 s
2621.841 pri.A
0.300 s

0.220 s

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 3\A03-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 3\A03-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
X =186,807 pri.A

10

[pri.A]

Alimentador 3
Falla Trifsica sin impedancia de falla

I =3068,171 pri.A

10000

Date: 12/5/2011
Annex:
DIgSILENT

0,1

10

A04-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,09
Tripping Time: 0,279 s

A04-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

[s]

[s]

740.999 pri.A
0.690 s

3305.817 pri.A
0.140 s

0,1

0,1
0.070 s

A04-51
Ipset: 12,00 sec.A
Tset: 0,05 s
Tripping Time: 0,070 s

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 4\A04-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 4\A04-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 4

Falla Trifsica sin impedancia de falla

[pri.A]

10000

Date: 12/5/2011
Annex:

Pgina 53

X =198,779 pri.A

10

I =3598,988 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

A05-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

[s]

[s]
A05-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,01
Tripping Time: 0,050 s

921.655 pri.A
0.690 s

3443.853 pri.A
0.120 s

0,1

0,1

0.050 s

100
13.2 kV T.P.\AL 5\A05-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 5\A05-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
10

X =115,702 pri.A

Alimentador 5
Falla Trifsica sin impedancia de falla

I =3068,171 pri.A

[pri.A]

10000

Date: 12/5/2011
Annex:
DIgSILENT

0,01
13,20 kV
10

10

A06-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,12
Tripping Time: 0,353 s

A06-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

[s]

[s]
809.674 pri.A
0.690 s
1

4800.966 pri.A
0.290 s

0,1

0.220 s

0,1
13,20 kV 100

1000
13.2 kV T.P.\AL 6\A06-51

10000

[pri.A]

100000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 6\A06-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 6

Falla Trifsica sin impedancia de falla

[pri.A]

10000

Date: 12/5/2011
Annex:

Pgina 54

X =132,996 pri.A

10

I =3068,171 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10
A07-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

A07-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,08
Tripping Time: 0,221 s

[s]

[s]

716.165 pri.A
0.720 s

5588.206 pri.A
0.170 s

0,1

0,1
0.070 s

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 7\A07-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 7\A07-51N

1000

Estudios Norma Tcnica


X =248,467 pri.A

10

Alimentador 7
Falla Trifsica sin impedancia de falla

I =1997,986 pri.A

10000

Date: 12/5/2011
Annex:
DIgSILENT

Estudio EVCP SM Punta Arenas

[pri.A]

10

A08-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s
A08-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

782.538 pri.A
0.700 s

1801.995 pri.A
0.300 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 08\A08-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 08\A08-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 8

Falla Trifsica sin impedancia de falla

[pri.A]

10000

Date: 12/5/2011
Annex:

Pgina 55

X =243,290 pri.A

10

I =2193,308 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

A09-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

A09-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s
[s]

[s]

766.695 pri.A
0.700 s
1

1729.769 pri.A
0.300 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 9\A09-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 9\A09-51N

1000

Estudios Norma Tcnica


X =128,437 pri.A

10

Alimentador 9
Falla Trifsica sin impedancia de falla

I =1997,986 pri.A

10000

Date: 12/5/2011
Annex:
DIgSILENT

Estudio EVCP SM Punta Arenas

[pri.A]

10

A10-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s
A10-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

902.995 pri.A
0.700 s

1
535.431 pri.A
0.300 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 10\A10-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 10\A10-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 10

Falla Trifsica sin impedancia de falla

[pri.A]

10000

Date: 12/5/2011
Annex:

Pgina 56

X =132,668 pri.A

10

I =3068,171 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

A11-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,08
Tripping Time: 0,221 s

A11-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

[s]

[s]

977.078 pri.A
0.680 s

7751.722 pri.A
0.155 s
1

0,1

0.095 s

A11-51
Ipset: 12,00 sec.A
Tset: 0,08 s
Tripping Time: 0,095 s

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 11\A11-51

1000

[pri.A]

10000

0,1
13,20 kV 100

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

[pri.A]

10000

13.2 kV T.P.\AL 11\A11-51N


Alimentador 11
Falla Trifsica sin impedancia de falla

Date: 12/5/2011
Annex:

Pgina 57

10

X =218,521 pri.A
I =380,584 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

A01-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

A01-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s
[s]

[s]

1988.579 pri.A
0.300 s

1
968.236 pri.A
0.700 s
0.220 s

0,1

1000

[pri.A]

10000

0,1
13,20 kV 100

13.2 kV P.A.\AL 1\A01-51

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Alimentador 1
Falla Trifsica con impedancia de falla 20 Ohms

X =224,756 pri.A
I =585,140 pri.A

10

[pri.A]

10000

13.2 kV P.A.\AL 1\A01-51N


Date: 12/8/2011
Annex:
DIgSILENT

0,01
13,20 kV 100

10
A02-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s
A02-51
Ipset: 4,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

986.684 pri.A
0.700 s

1801.995 pri.A
0.300 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 2\A02-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 2\A02-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 2

Falla Trifsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/8/2011
Annex:

Pgina 58

X =263,108
I =386,753
pri.A pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10
A03-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

A03-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

837.751 pri.A
0.700 s
1

0.620 s
2621.841 pri.A
0.300 s

0.220 s

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 3\A03-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 3\A03-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Alimentador 3
Falla Trifsica con impedancia de falla 20 Ohms

X =186,807 Ipri.A
=391,226 pri.A

10

[pri.A]

10000

Date: 12/8/2011
Annex:
DIgSILENT

0,1

10
A04-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,09
Tripping Time: 2,498 s

A04-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

[s]

[s]
2.498 s

740.999 pri.A
0.690 s

3305.817 pri.A
0.140 s

0,1

0,1

A04-51
Ipset: 12,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 4\A04-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 4\A04-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 4

Falla Trifsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/8/2011
Annex:

Pgina 59

X =198,779I pri.A
=397,348 pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

A05-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

[s]

[s]
A05-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,01
Tripping Time: 0,248 s

921.655 pri.A
0.690 s

0.248 s

3443.853 pri.A
0.120 s

0,1

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 5\A05-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 5\A05-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
10

Alimentador 5
Falla Trifsica con impedancia de falla 20 Ohms

X =115,702 pri.A
I =391,226 pri.A

[pri.A]

10000

Date: 12/8/2011
Annex:
DIgSILENT

0,1

10
A06-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,12
Tripping Time: 3,155 s

A06-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

[s]

[s]

3.155 s

809.674 pri.A
0.690 s
1

4800.966 pri.A
0.290 s

0,1

0,1
13,20 kV 100

1000
13.2 kV T.P.\AL 6\A06-51

10000

[pri.A]

100000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 6\A06-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 6

Falla Trifsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/8/2011
Annex:

Pgina 60

X =132,996 pri.A I =391,226 pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10
A07-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

A07-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,08
Tripping Time: 1,972 s

[s]

[s]

1.972 s
716.165 pri.A
0.720 s

5588.206 pri.A
0.170 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV T.P.\AL 7\A07-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 7\A07-51N

1000

Estudios Norma Tcnica


X =248,467
I =386,753
pri.A pri.A

10

Alimentador 7
Falla Trifsica con impedancia de falla 20 Ohms

10000

Date: 12/8/2011
Annex:
DIgSILENT

Estudio EVCP SM Punta Arenas

[pri.A]

10

A08-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s
A08-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

782.538 pri.A
0.700 s

1801.995 pri.A
0.300 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 08\A08-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 08\A08-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 8

Falla Trifsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/8/2011
Annex:

Pgina 61

X =243,290
I =393,077
pri.A pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

A09-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

A09-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s
[s]

[s]

766.695 pri.A
0.700 s
1

1729.769 pri.A
0.300 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 9\A09-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 9\A09-51N

1000

Estudios Norma Tcnica


X =128,437 pri.A I =386,753 pri.A

10

Alimentador 9
Falla Trifsica con impedancia de falla 20 Ohms

10000

Date: 12/8/2011
Annex:
DIgSILENT

Estudio EVCP SM Punta Arenas

[pri.A]

10

A10-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s
A10-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

902.995 pri.A
0.700 s

1
535.431 pri.A
0.300 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 10\A10-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 10\A10-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 10

Falla Trifsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/8/2011
Annex:

Pgina 62

X =132,668 pri.A I =391,226 pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10
A11-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,08
Tripping Time: 1,972 s

A11-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 9999,999 s

[s]

1.972 s
[s]

977.078 pri.A
0.680 s

7751.722 pri.A
0.155 s
1

0,1

A11-51
Ipset: 12,00 sec.A
Tset: 0,08 s
Tripping Time: 9999,999 s

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 11\A11-51

1000

[pri.A]

10000

0,1
13,20 kV 100

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

[pri.A]

10000

13.2 kV T.P.\AL 11\A11-51N


Alimentador 11
Falla Trifsica con impedancia de falla 20 Ohms

Date: 12/8/2011
Annex:

Pgina 63

I =347,626 pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

51
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,10
Tripping Time: 0,470 s

51N
Ipset: 1,00 sec.A
Tset: 0,48 s
Tripping Time: 9999,999 s

[s]

[s]

0.470 s
1

0,1

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 9999,999 s
0,01
13,20 kV 10

100
1000
13.2 kV\AL C1 (Interruptor principal)\51

[pri.A]

0,1
10000 13,20 kV 10

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51N

Estudios Norma Tcnica


I =1286,283 pri.A

10

Alimentador 1

Falla a Trifsica con impedancia de falla de 20 Ohms

Date: 12/3/2011
Annex:
DIgSILENT

Estudios EVCP SM Puerto Natales

1000

10

51
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,10
Tripping Time: 0,245 s

51N
Ipset: 1,00 sec.A
Tset: 0,48 s
Tripping Time: 9999,999 s

[s]

[s]

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 0,080 s

1
0.245 s

0,1
0.080 s

0,01
13,20 kV 10

100
1000
13.2 kV\AL C1 (Interruptor principal)\51

[pri.A]

0,1
10000 13,20 kV 10

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51N

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

Informe Tcnico

Alimentador 1
Falla a Trifsica

1000

Date: 12/3/2011
Annex:

Pgina 64

I =339,394 pri.A

100

100

51
IEC 255-3 very inverse
Ipset: 3,00 sec.A
Tpset: 0,14
Tripping Time: 0,406 s

[s]

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

[s]
51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 9999,999 s

10

10

0.406 s

0,1

0,1

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 9999,999 s
0,01
13,20 kV 10

100
13.2 kV\C 4\51

1000

[pri.A]

0,01
10000 13,20 kV 10

100
13.2 kV\C 4\51N

Estudios Norma Tcnica


I =1222,417 pri.A

100

10000

Date: 12/3/2011
Annex:

100

51
IEC 255-3 very inverse
Ipset: 3,00 sec.A
Tpset: 0,14
Tripping Time: 0,099 s

[s]

Alimentador 2

Falla a Trifsica con impedancia de falla de 20 Ohms

[pri.A]

DIgSILENT

Estudios EVCP SM Puerto Natales

1000

[s]
51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 9999,999 s

10

10

0.099 s
0.080 s

0,1

0,01
13,20 kV 10

100
13.2 kV\C 4\51

1000

0,1

[pri.A]

0,01
10000 13,20 kV 10

100
13.2 kV\C 4\51N

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

Informe Tcnico

1000

Alimentador 2
Falla a Trifsica

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 65

I =347,626 pri.A
51
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,10
Tripping Time: 0,470 s

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10
51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 9999,999 s

[s]

[s]

1
51
Ipset: 32,50 sec.A
0.470Tset:
s
0,06 s
Tripping Time: 9999,999 s

0,1

0,01
13,20 kV 10

0,1

100
13.2 kV II\AL 03\51

1000

[pri.A]

0,01
10000 13,20 kV 10

100
13.2 kV II\AL 03\51N

Estudios Norma Tcnica


I =1286,283 pri.A

10

Alimentador 3

Falla a Trifsica con impedancia de falla de 20 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:
DIgSILENT

Estudios EVCP SM Puerto Natales

1000

10

51
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,10
Tripping Time: 0,245 s

51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 9999,999 s

[s]

[s]

1
51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 0,080 s

0,1

0,1
0.080 s

0,01
13,20 kV 10

100
13.2 kV II\AL 03\51

1000

[pri.A]

0,01
10000 13,20 kV 10

100
13.2 kV II\AL 03\51N

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

Informe Tcnico

1000

Alimentador 3
Falla a Trifsica

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 66

I =347,626 pri.A

100

100

51
IEC 255-3 very inverse
Ipset: 3,00 sec.A
Tpset: 0,14
Tripping Time: 0,394 s

[s]

[s]

10

10

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 9999,999 s

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 9999,999 s

0.394 s

0,1

0,01
13,20 kV 10

0,1

100
13.2 kV II\AL01\51

1000

[pri.A]

0,01
10000 13,20 kV 10

100
13.2 kV II\AL01\51N

Estudios Norma Tcnica


I =1286,283 pri.A

100

10

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 0,080 s

0,1

0,01
13,20 kV 10

1000

[pri.A]

51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 9999,999 s

0,01
10000 13,20 kV 10

100
13.2 kV II\AL01\51N

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

Informe Tcnico

Annex:

0,1

0.080 s

100
13.2 kV II\AL01\51

Date: 12/3/2011

[s]

10

10000

100

51
IEC 255-3 very inverse
Ipset: 3,00 sec.A
Tpset: 0,14
Tripping Time: 0,099 s

[s]

Alimentador 4

Falla Trifsica con impedancia de falla de 20 Ohms

[pri.A]

DIgSILENT

Estudios EVCP SM Puerto Natales

1000

1000

Alimentador 4
Falla a Trifsica

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 67

10

X = 21,374 pri.A

I =330,454 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10
A01_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 9999,999 s

A01_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,042 s

[s]

[s]

0,1

0,1

0.042 s

100
13.8_A\AL01\A01_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_A\AL01\A01_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir
10

X = 21,374 pri.A

1000
Alimentador 1

Falla Trifsica con resistenciua de falla de 20 Ohms

I =830,663 pri.A

[pri.A]

10000

Date: 12/3/2011
Annex:
DIgSILENT

0,01
13,80 kV
10

10
A01_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 9999,999 s

A01_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,025 s

[s]

[s]

0,1

0,1

0.025 s

0,01
13,80 kV
10

100
13.8_A\AL01\A01_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_A\AL01\A01_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir

Informe Tcnico

1000
Alimentador 1

Falla Trifsica con resistenciua de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 68

10

X = 21,095 pri.A

I =330,454 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10
A02_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 9999,999 s
A02_51
KYLE 119 (cesar)
Ipset: 7,00 sec.A
Tpset: 1,00
Tripping Time: 0,073 s

[s]

[s]

0,1

0,1
0.073 s

100
13.8_B\AL02\A02_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL02\A02_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir
10

X = 21,095 pri.A

1000
Alimentador 2

Falla Trifsica con resistenciua de falla de 20 Ohms

I =830,663 pri.A

[pri.A]

10000

Date: 12/3/2011
Annex:
DIgSILENT

0,01
13,80 kV
10

10
A02_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 9999,999 s

A02_51
KYLE 119 (cesar)
Ipset: 7,00 sec.A
Tpset: 1,00
Tripping Time: 0,051 s
[s]

[s]

0,1

0,1

0.051 s

0,01
13,80 kV
10

100
13.8_B\AL02\A02_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL02\A02_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir

Informe Tcnico

1000
Alimentador 2

Falla Trifsica con resistenciua de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 69

10

X = 81,001 pri.A

I =379,733 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

A03_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,038 s

A03_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 9999,999 s

[s]

[s]

0,1

0,1

0.038 s

100
13.8_B\AL03\A03_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL03\A03_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir
10

X = 81,001 pri.A

1000
Alimentador 3

Falla Trifsica con resistenciua de falla de 20 Ohms

I =927,686 pri.A

[pri.A]

10000

Date: 12/3/2011
Annex:
DIgSILENT

0,01
13,80 kV
10

10

A03_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,024 s

A03_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 9999,999 s

[s]

[s]

0,1

0,1

0.024 s

0,01
13,80 kV
10

100
13.8_B\AL03\A03_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL03\A03_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir

Informe Tcnico

1000
Alimentador 3

Falla Trifsica con resistenciua de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 70

10

X = 35,822 pri.A

I =330,454 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10

A03_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 9999,999 s

A04_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,042 s
[s]

[s]

0,1

0,1

0.042 s

0,01
13,80 kV
10

100
13.8_B\AL04\A04_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL03\A03_51N

1000

Estudios Norma Tcnica

10

X = 35,822 pri.A

Alimentador 4
Falla Trifsica con resistenciua de falla de 20 Ohms

I =830,663 pri.A

10000

Date: 12/3/2011
Annex:
DIgSILENT

Estudio EVCP SM Porvenir

[pri.A]

10

A03_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 9999,999 s

A04_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,025 s
[s]

[s]

0,1

0,1

0.025 s

0,01
13,80 kV
10

100
13.8_B\AL04\A04_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL03\A03_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir

Informe Tcnico

1000
Alimentador 4

Falla Trifsica con resistenciua de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 71

10

X = 6,328 pri.A

I =215,563 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

100

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

[s]
51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 9999,999 s

[s]

10

0,1

0,1

0.011 s
0,01
13,20 kV 1

10
13.2 kV II\AL 03\51

100

[pri.A]

1000

0,01
13,20 kV 10

100

Estudios Norma Tcnica

1000

X = 6,328 pri.A

Alimentador 1

Falla Trifsica con resistencia de falla de 20 Ohms

I =288,437 pri.A

Date: 12/4/2011
Annex:
DIgSILENT

Estudio EVCP SM Puerto Williams


10

[pri.A]

13.2 kV II\AL 03\51N

100

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

[s]
51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 9999,999 s

[s]

10

0,1

0,1

0.011 s
0,01
13,20 kV 1

10
13.2 kV II\AL 03\51

100

[pri.A]

1000

0,01
13,20 kV 10

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams

Informe Tcnico

100

[pri.A]

1000

13.2 kV II\AL 03\51N

Alimentador 1
Falla Trifsica sin resistencia de falla

Date: 12/4/2011
Annex:

Pgina 72

10

X = 12,871 pri.A

I =215,563 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10
51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 9999,999 s

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s
[s]

[s]

0,1

0,1

0.011 s
0,01
13,20 kV 10

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51

1000

0,01
13,20 kV 10

Estudios Norma Tcnica

10

X = 12,871 pri.A

Alimentador 2

Falla Trifsica con resistencia de falla de 20 Ohms

I =288,437 pri.A

1000

Date: 12/4/2011
Annex:
DIgSILENT

Estudio EVCP SM Puerto Williams

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51N

10
51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 9999,999 s

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s
[s]

[s]

0,1

0,1

0.011 s
0,01
13,20 kV 10

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51

1000

0,01
13,20 kV 10

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams

Informe Tcnico

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51N

Alimentador 2
Falla Trifsica sin resistencia de falla

1000

Date: 12/4/2011
Annex:

Pgina 73

100

X = 17,680 pri.A

I =215,563 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

100

[s]

[s]

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

10

51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 9999,999 s

10

0,1

0,1

0.011 s
0,01
13,20 kV 10

100

[pri.A]

1000

0,01
13,20 kV 10

13.2 kV II\AL01\51

100

Estudios Norma Tcnica

1000

X = 17,680 pri.A

Alimentador 3

Falla Trifsica con resistencia de falla de 20 Ohms

I =288,437 pri.A

Date: 12/4/2011
Annex:
DIgSILENT

Estudio EVCP SM Puerto Williams


100

[pri.A]

13.2 kV II\AL01\51N

100

[s]

[s]

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

10

51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 9999,999 s

10

0,1

0,1

0.011 s
0,01
13,20 kV 10

100

[pri.A]

1000

0,01
13,20 kV 10

13.2 kV II\AL01\51

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams

Informe Tcnico

100

[pri.A]

1000

13.2 kV II\AL01\51N

Alimentador 3
Falla Trifsica sin resistencia de falla

Date: 12/4/2011
Annex:

Pgina 74

2 Anexo 2 Curvas de Coordinacin Alimentadores

Curvas de Operacin para Fallas Residuales

Informe Tcnico

Pgina 75

10

X =218,521 pri.A

I =2085,851 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =2085,851 pri.A

10

A01-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

A01-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s
[s]

[s]

1988.579 pri.A
0.300 s

1
968.236 pri.A
0.700 s
0.220 s

0.620 s

0,1

1000

[pri.A]

10000

0,1
13,20 kV 100

13.2 kV P.A.\AL 1\A01-51

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
X =224,756 pri.A

10

[pri.A]

10000

13.2 kV P.A.\AL 1\A01-51N


Alimentador 1

Date: 12/4/2011

Falla Monofsica sin impedancia de falla

I =1388,591 pri.A

Annex:
DIgSILENT

0,01
13,20 kV 100

3*I0 =1388,591 pri.A

10

A02-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s
A02-51
Ipset: 4,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s
[s]

[s]

986.684 pri.A
0.700 s

0.620 s

1801.995 pri.A
0.300 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 2\A02-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 2\A02-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 2

Falla Monofsica sin impedancia de falla

[pri.A]

10000

Date: 12/4/2011
Annex:

Pgina 76

X =263,108 pri.A

10

I =2309,670 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

10
A03-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

A03-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

837.751 pri.A
0.700 s
1

0.620 s
2621.841 pri.A
0.300 s

0.220 s

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 3\A03-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 3\A03-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
X =186,807 pri.A

10

[pri.A]

Alimentador 3
Falla Monofsica sin impedancia de falla

I =2685,545 pri.A

10000

Date: 12/4/2011
Annex:
DIgSILENT

0,1

3*I0 =2685,545 pri.A

10

A04-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,09
Tripping Time: 0,297 s

A04-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

[s]

[s]

740.999 pri.A
0.690 s

0.620 s

3305.817 pri.A
0.140 s

0,1

0,1
0.070 s

A04-51
Ipset: 12,00 sec.A
Tset: 0,05 s
Tripping Time: 0,070 s

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 4\A04-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 4\A04-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 4

Falla Monofsica sin impedancia de falla

[pri.A]

10000

Date: 12/4/2011
Annex:

Pgina 77

X =198,779 pri.A

10

I =3070,839 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =3070,839 pri.A

10

A05-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

[s]

[s]
A05-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,01
Tripping Time: 0,050 s

921.655 pri.A
0.690 s

0.620 s

3443.853 pri.A
0.120 s

0,1

0,1

0.050 s

100
13.2 kV T.P.\AL 5\A05-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 5\A05-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
10

X =115,702 pri.A

[pri.A]

Alimentador 5
Falla Monofsica sin impedancia de falla

I =2685,545 pri.A

10000

Date: 12/4/2011
Annex:
DIgSILENT

0,01
13,20 kV
10

3*I0 =2685,545 pri.A

10

A06-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,12
Tripping Time: 0,375 s

A06-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

[s]

[s]
809.674 pri.A
0.690 s
1

0.620 s

4800.966 pri.A
0.290 s

0,1

0.220 s

0,1
13,20 kV 100

1000
13.2 kV T.P.\AL 6\A06-51

10000

[pri.A]

100000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 6\A06-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 6

Falla Monofsica sin impedancia de falla

[pri.A]

10000

Date: 12/4/2011
Annex:

Pgina 78

X =132,996 pri.A

10

I =2685,545 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =2685,545 pri.A

10
A07-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

A07-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,08
Tripping Time: 0,234 s

[s]

[s]

716.165 pri.A
0.720 s

0.620 s

5588.206 pri.A
0.170 s

0,1

0,1
0.070 s

100
13.2 kV T.P.\AL 7\A07-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 7\A07-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
X =248,467 pri.A

10

Alimentador 7
Falla Monofsica sin impedancia de falla

I =2309,670 pri.A

[pri.A]

10000

Date: 12/4/2011
Annex:
DIgSILENT

0,01
13,20 kV
10

3*I0 =2309,670 pri.A

10

A08-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s
A08-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

782.538 pri.A
0.700 s

1801.995 pri.A
0.300 s

0.620 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 08\A08-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 08\A08-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 8

Falla Monofsica sin impedancia de falla

[pri.A]

10000

Date: 12/4/2011
Annex:

Pgina 79

X =243,290 pri.A

10

I =2580,345 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =2580,345 pri.A

10

A09-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

A09-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s
[s]

[s]

766.695 pri.A
0.700 s
1

0.620 s
1729.769 pri.A
0.300 s

0.220 s

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 9\A09-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 9\A09-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
X =128,437 pri.A

10

Alimentador 9
Falla Monofsica sin impedancia de falla

I =2309,670 pri.A

[pri.A]

10000

Date: 12/4/2011
Annex:
DIgSILENT

0,1

3*I0 =2309,670 pri.A

10

A10-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s
A10-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

902.995 pri.A
0.700 s

1
535.431 pri.A
0.300 s
0.620 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 10\A10-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 10\A10-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 10

Falla Monofsica sin impedancia de falla

[pri.A]

10000

Date: 12/4/2011
Annex:

Pgina 80

X =132,668 pri.A

10

I =2685,545 pri.A

3*I0 =2685,545 pri.A

10

A11-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,08
Tripping Time: 0,234 s

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

A11-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

[s]

[s]

977.078 pri.A
0.680 s

7751.722 pri.A
0.155 s
1

0.620 s

0,1

0.095 s

A11-51
Ipset: 12,00 sec.A
Tset: 0,08 s
Tripping Time: 0,095 s

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 11\A11-51

1000

[pri.A]

10000

0,1
13,20 kV 100

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

[pri.A]

10000

13.2 kV T.P.\AL 11\A11-51N


Alimentador 11
Falla Monofsica sin impedancia de falla

Date: 12/4/2011
Annex:

Pgina 81

10

X =218,521 pri.A
I =383,190 pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =383,190 pri.A

A01-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

A01-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s
[s]

[s]

1988.579 pri.A
0.300 s

1
968.236 pri.A
0.700 s
0.220 s

0.620 s

0,1

1000

[pri.A]

10000

0,1
13,20 kV 100

13.2 kV P.A.\AL 1\A01-51

1000

[pri.A]

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Alimentador 1
Falla Monofsica con impedancia de falla 20 Ohms

X =224,756
I =354,598
pri.A pri.A

10

10000

13.2 kV P.A.\AL 1\A01-51N


Date: 12/5/2011
Annex:
DIgSILENT

0,01
13,20 kV 100

3*I0 =354,598 pri.A

10

A02-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s
A02-51
Ipset: 4,00 sec.A
Tset: 0,20 s
Tripping Time: 9999,999 s
[s]

[s]

986.684 pri.A
0.700 s

0.620 s

1801.995 pri.A
0.300 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 2\A02-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 2\A02-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 2

Falla Monofsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/5/2011
Annex:

Pgina 82

X =263,108
I =389,330
pri.A pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =389,330 pri.A

10

A03-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

A03-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

837.751 pri.A
0.700 s
1

0.620 s

0.620 s

2621.841 pri.A
0.300 s

0.220 s

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 3\A03-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 3\A03-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Alimentador 3
Falla Monofsica con impedancia de falla 20 Ohms

X =186,807 Ipri.A
=390,692 pri.A

10

[pri.A]

10000

Date: 12/5/2011
Annex:
DIgSILENT

0,1

3*I0 =390,692 pri.A

10
A04-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,09
Tripping Time: 2,511 s

A04-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

[s]

[s]
2.511 s

740.999 pri.A
0.690 s

0.620 s

3305.817 pri.A
0.140 s

0,1

0,1

A04-51
Ipset: 12,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 4\A04-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 4\A04-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 4

Falla Monofsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/5/2011
Annex:

Pgina 83

X =198,779I pri.A
=396,901 pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =396,901 pri.A

10

A05-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

[s]

[s]
A05-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,01
Tripping Time: 0,249 s

921.655 pri.A
0.690 s

0.620 s

0.249 s

3443.853 pri.A
0.120 s

0,1

0,1

100
13.2 kV T.P.\AL 5\A05-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 5\A05-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
10

Alimentador 5
Falla Monofsica con impedancia de falla 20 Ohms

X =115,702 pri.A
I =390,692 pri.A

[pri.A]

10000

Date: 12/5/2011
Annex:
DIgSILENT

0,01
13,20 kV
10

3*I0 =390,692 pri.A

10
A06-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,12
Tripping Time: 3,172 s

A06-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

[s]

[s]

3.172 s

809.674 pri.A
0.690 s
1

0.620 s

4800.966 pri.A
0.290 s

0,1

0,1
13,20 kV 100

1000
13.2 kV T.P.\AL 6\A06-51

10000

[pri.A]

100000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 6\A06-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 6

Falla Monofsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/5/2011
Annex:

Pgina 84

X =132,996 pri.A I =390,692 pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =390,692 pri.A

10

A07-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

A07-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,08
Tripping Time: 1,982 s

[s]

[s]

1.982 s
716.165 pri.A
0.720 s

0.620 s

5588.206 pri.A
0.170 s

0,1

100
13.2 kV T.P.\AL 7\A07-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 7\A07-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
X =248,467
I =389,330
pri.A pri.A

10

Alimentador 7
Falla Monofsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/5/2011
Annex:
DIgSILENT

0,01
13,20 kV
10

0,1

3*I0 =389,330 pri.A

10

A08-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s
A08-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

782.538 pri.A
0.700 s

1801.995 pri.A
0.300 s

0.620 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 08\A08-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 08\A08-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 8

Falla Monofsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/5/2011
Annex:

Pgina 85

X =243,290
I =395,618
pri.A pri.A

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =395,618 pri.A

10

A09-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

A09-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s
[s]

[s]

766.695 pri.A
0.700 s
1

0.620 s
1729.769 pri.A
0.300 s

0.220 s

0,1

100
13.2 kV P.A.\AL 9\A09-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 9\A09-51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas
X =128,437 pri.A I =389,330 pri.A

10

Alimentador 9
Falla Monofsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/5/2011
Annex:
DIgSILENT

0,01
13,20 kV
10

0,1

3*I0 =389,330 pri.A

10

A10-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s
A10-51
Ipset: 3,00 sec.A
Tset: 0,20 s
Tripping Time: 0,220 s

[s]

[s]

902.995 pri.A
0.700 s

1
535.431 pri.A
0.300 s
0.620 s

0.220 s

0,1

0,01
13,20 kV
10

0,1

100
13.2 kV P.A.\AL 10\A10-51

1000

[pri.A]

10000

0,01
13,20 kV
10

100
13.2 kV P.A.\AL 10\A10-51N

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

1000
Alimentador 10

Falla Monofsica con impedancia de falla 20 Ohms

[pri.A]

10000

Date: 12/5/2011
Annex:

Pgina 86

X =132,668 pri.A I =390,692 pri.A

10

10
A11-51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,08
Tripping Time: 1,982 s

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =390,692 pri.A

A11-51N
Ipset: 1,00 sec.A
Tset: 0,60 s
Tripping Time: 0,620 s

[s]

1.982 s
[s]

977.078 pri.A
0.680 s

7751.722 pri.A
0.155 s
1

0.620 s

0,1

A11-51
Ipset: 12,00 sec.A
Tset: 0,08 s
Tripping Time: 9999,999 s

0,01
13,20 kV
10

100
13.2 kV T.P.\AL 11\A11-51

1000

[pri.A]

10000

0,1
13,20 kV 100

1000

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

[pri.A]

10000

13.2 kV T.P.\AL 11\A11-51N


Alimentador 11
Falla Monofsica con impedancia de falla 20 Ohms

Date: 12/5/2011
Annex:

Pgina 87

I =357,164 pri.A

10

3*I0 =357,164 pri.A

10

51
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,10
Tripping Time: 0,461 s

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

51N
Ipset: 1,00 sec.A
Tset: 0,48 s
Tripping Time: 0,500 s

[s]

[s]

0.461 s
1

0.500 s
0,1

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 9999,999 s

100
1000
13.2 kV\AL C1 (Interruptor principal)\51

[pri.A]

0,1
10000 13,20 kV 10

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

Alimentador 1

Falla Monofsica con impedancia de falla de 20 Ohms

I =1692,026 pri.A

10

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51N

Date: 12/3/2011
Annex:

3*I0 =1692,026 pri.A

10

51
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,10
Tripping Time: 0,227 s

1000

DIgSILENT

0,01
13,20 kV 10

51N
Ipset: 1,00 sec.A
Tset: 0,48 s
Tripping Time: 0,500 s

[s]

[s]

0.500 s
0,1
0.080 s

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 0,080 s
0,01
13,20 kV 10

100
1000
13.2 kV\AL C1 (Interruptor principal)\51

[pri.A]

0,1
10000 13,20 kV 10

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

Informe Tcnico

100
1000
13.2 kV\AL C1 (Interruptor principal)\51N

Alimentador 1

Falla Monofsica con impedancia de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 88

I =348,369 pri.A

100

[s]

3*I0 =348,369 pri.A

100

51
IEC 255-3 very inverse
Ipset: 3,00 sec.A
Tpset: 0,14
Tripping Time: 0,393 s

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

[s]
51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 0,470 s

10

10

1
0.470 s

0.393 s

0,1

0,1

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 9999,999 s

100
13.2 kV\C 4\51

1000

[pri.A]

0,01
10000 13,20 kV 10

100
13.2 kV\C 4\51N

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

[pri.A]

10000

Date: 12/3/2011
Annex:

3*I0 =1564,468 pri.A

100

51
IEC 255-3 very inverse
Ipset: 3,00 sec.A
Tpset: 0,14
Tripping Time: 0,099 s

[s]

Alimentador 2

Falla Monofsica con impedancia de falla de 20 Ohms

I =1564,468 pri.A

100

1000

DIgSILENT

0,01
13,20 kV 10

[s]
51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 0,470 s

10

10

1
0.470 s

0,1

0,1

0.080 s

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 0,080 s
0,01
13,20 kV 10

100
13.2 kV\C 4\51

1000

[pri.A]

0,01
10000 13,20 kV 10

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

Informe Tcnico

100
13.2 kV\C 4\51N

1000

Alimentador 2

Falla Monofsica con impedancia de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 89

I =357,164 pri.A
51
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,10
Tripping Time: 0,461 s

10

10

3*I0 =357,164 pri.A


51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 0,470 s

[s]

[s]

1
51
Ipset: 32,50 sec.A
0.461Tset:
s 0,06 s
Tripping Time: 9999,999 s

0.470 s

0,1

100
13.2 kV II\AL 03\51

1000

[pri.A]

0,01
10000 13,20 kV 10

100
13.2 kV II\AL 03\51N

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

Alimentador 3

Falla Monofsica con impedancia de falla de 20 Ohms

I =1692,026 pri.A

10

1000

10000

Date: 12/3/2011
Annex:

3*I0 =1692,026 pri.A

10

51
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,10
Tripping Time: 0,227 s

[pri.A]

DIgSILENT

0,1

0,01
13,20 kV 10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 0,470 s

[s]

[s]

1
51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 0,080 s

0,1

0.470 s

0,1
0.080 s

0,01
13,20 kV 10

100
13.2 kV II\AL 03\51

1000

[pri.A]

0,01
10000 13,20 kV 10

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

Informe Tcnico

100
13.2 kV II\AL 03\51N

1000

Alimentador 3

Falla Monofsica con impedancia de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 90

I =357,164 pri.A

100

100

51
IEC 255-3 very inverse
Ipset: 3,00 sec.A
Tpset: 0,14
Tripping Time: 0,382 s

[s]

3*I0 =357,164 pri.A

[s]

10

10

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 9999,999 s

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 0,470 s

1
0.470 s

0.382 s

0,01
13,20 kV 10

0,1

100
13.2 kV II\AL01\51

1000

[pri.A]

0,01
10000 13,20 kV 10

100
13.2 kV II\AL01\51N

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

10000

Date: 12/3/2011
Annex:

[s]

10

10

51
Ipset: 32,50 sec.A
Tset: 0,06 s
Tripping Time: 0,080 s

[pri.A]

3*I0 =1692,026 pri.A

100

51
IEC 255-3 very inverse
Ipset: 3,00 sec.A
Tpset: 0,14
Tripping Time: 0,099 s

[s]

Alimentador 4

Falla Monofsica con impedancia de falla de 20 Ohms

I =1692,026 pri.A

100

1000

DIgSILENT

0,1

51N
Ipset: 1,00 sec.A
Tset: 0,45 s
Tripping Time: 0,470 s

1
0.470 s

0,1

0,01
13,20 kV 10

0,1

0.080 s

100
13.2 kV II\AL01\51

1000

[pri.A]

0,01
10000 13,20 kV 10

Estudios Norma Tcnica


Estudios EVCP SM Puerto Natales

Informe Tcnico

100
13.2 kV II\AL01\51N

1000

Alimentador 4

Falla Monofsica con impedancia de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 91

10

X = 21,374 pri.A

I =351,533 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =351,533 pri.A

10

A01_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 0,520 s

A01_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,040 s

[s]

[s]

0.520 s

0,1

0,1

0.040 s

100
13.8_A\AL01\A01_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_A\AL01\A01_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir
10

X = 21,374 pri.A

1000

[pri.A]

Alimentador 1
Falla Monofsica con resistenciua de falla de 20 Ohms

I =1147,403 pri.A

10000

Date: 12/3/2011
Annex:
DIgSILENT

0,01
13,80 kV
10

3*I0 =1147,403 pri.A

10
A01_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 0,520 s

A01_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,023 s

[s]

[s]

0.520 s

0,1

0,1

0.023 s

0,01
13,80 kV
10

100
13.8_A\AL01\A01_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_A\AL01\A01_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir

Informe Tcnico

1000
Alimentador 1

Falla Monofsica con resistenciua de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 92

10

X = 21,095 pri.A

I =351,533 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =351,533 pri.A

10

A02_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 0,520 s
A02_51
KYLE 119 (cesar)
Ipset: 7,00 sec.A
Tpset: 1,00
Tripping Time: 0,070 s
[s]

[s]

0.520 s

0,1

0,1
0.070 s

100
13.8_B\AL02\A02_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL02\A02_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir
10

X = 21,095 pri.A

1000

[pri.A]

Alimentador 2
Falla Monofsica con resistenciua de falla de 20 Ohms

I =1147,403 pri.A

10000

Date: 12/3/2011
Annex:
DIgSILENT

0,01
13,80 kV
10

3*I0 =1147,403 pri.A

10
A02_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 0,520 s

A02_51
KYLE 119 (cesar)
Ipset: 7,00 sec.A
Tpset: 1,00
Tripping Time: 0,049 s
[s]

[s]

0.520 s

0,1

0,1

0.049 s

0,01
13,80 kV
10

100
13.8_B\AL02\A02_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL02\A02_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir

Informe Tcnico

1000
Alimentador 2

Falla Monofsica con resistenciua de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 93

10

X = 81,001 pri.A

I =410,299 pri.A

3*I0 =410,299 pri.A

10

A03_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,036 s

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

A03_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 0,520 s

[s]

[s]

0.520 s

0,1

0,1

0.036 s

100
13.8_B\AL03\A03_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL03\A03_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir
10

X = 81,001 pri.A

1000

[pri.A]

Alimentador 3
Falla Monofsica con resistenciua de falla de 20 Ohms

I =1357,271 pri.A

Date: 12/3/2011
Annex:

3*I0 =1357,271 pri.A

10

A03_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,022 s

10000

DIgSILENT

0,01
13,80 kV
10

A03_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 0,520 s

[s]

[s]

0.520 s

0,1

0,1

0.022 s

0,01
13,80 kV
10

100
13.8_B\AL03\A03_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL03\A03_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir

Informe Tcnico

1000
Alimentador 3

Falla Monofsica con resistenciua de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 94

10

X = 35,822 pri.A

I =351,533 pri.A

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

3*I0 =351,533 pri.A

10

A04_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 0,520 s

A04_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,040 s
[s]

[s]

0.520 s

0,1

0,1

0.040 s

100
13.8_B\AL04\A04_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL04\A04_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir
10

X = 35,822 pri.A

1000

[pri.A]

Alimentador 4
Falla Monofsica con resistenciua de falla de 20 Ohms

I =1147,403 pri.A

10000

Date: 12/3/2011
Annex:
DIgSILENT

0,01
13,80 kV
10

3*I0 =1147,403 pri.A

10
A04_51N
Ipset: 1,00 sec.A
Tset: 0,50 s
Tripping Time: 0,520 s

A04_51
KYLE 112 (cesar)
Ipset: 5,00 sec.A
Tpset: 1,00
Tripping Time: 0,023 s
[s]

[s]

0.520 s

0,1

0,1

0.023 s

0,01
13,80 kV
10

100
13.8_B\AL04\A04_51

1000

[pri.A]

10000

0,01
13,80 kV
10

100
13.8_B\AL04\A04_51N

Estudios Norma Tcnica


Estudio EVCP SM Porvenir

Informe Tcnico

1000
Alimentador 4

Falla Monofsica con resistenciua de falla de 0 Ohms

[pri.A]

10000

Date: 12/3/2011
Annex:

Pgina 95

10

X = 6,328 pri.A

I =268,848 pri.A

3*I0 =268,848 pri.A

100

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

[s]
51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

[s]

10

0,1

0,1

0.011 s
10
13.2 kV II\AL 03\51

100

[pri.A]

0.011 s
1000

0,01
13,20 kV 10

100

1000

13.2 kV II\AL 03\51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams
10

[pri.A]

X = 6,328 pri.A

Alimentador 1

Falla Trifsica con resistencia de falla de 20 Ohms

I =417,574 pri.A

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

Date: 12/4/2011
Annex:
DIgSILENT

0,01
13,20 kV 1

3*I0 =417,574 pri.A

100

[s]
51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

[s]

10

0,1

0,1

0.011 s
0,01
13,20 kV 1

10
13.2 kV II\AL 03\51

100

0.011 s

[pri.A]

1000

0,01
13,20 kV 10

Informe Tcnico

[pri.A]

1000

13.2 kV II\AL 03\51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams

100

Alimentador 1

Falla Monofsica sin resistencia de falla

Date: 12/4/2011
Annex:

Pgina 96

X = 12,871 pri.A

I =268,848 pri.A

3*I0 =268,848 pri.A

10
51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s
[s]

[s]

0,1

0,1

0.011 s
0,01
13,20 kV 10

0.011 s

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51

1000

0,01
13,20 kV 10

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams
10

X = 12,871 pri.A

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51N

Alimentador 2

Falla Trifsica con resistencia de falla de 20 Ohms

I =417,574 pri.A

Date: 12/4/2011
Annex:

3*I0 =417,574 pri.A

10
51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s
[s]

[s]

0,1

0,1

0.011 s
0,01
13,20 kV 10

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51

0.011 s
1000

0,01
13,20 kV 10

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams

Informe Tcnico

1000

DIgSILENT

10

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

100
[pri.A]
13.2 kV\AL C1 (Interruptor principal)\51N

Alimentador 2

Falla Monofsica sin resistencia de falla

1000

Date: 12/4/2011
Annex:

Pgina 97

X = 17,680 pri.A

I =268,848 pri.A

3*I0 =268,848 pri.A

100

[s]

[s]

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

10

51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

10

0,1

0,1

0.011 s
0,01
13,20 kV 10

100

0.011 s

[pri.A]

1000

0,01
13,20 kV 10

13.2 kV II\AL01\51

100

1000

13.2 kV II\AL01\51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams
100

[pri.A]

X = 17,680 pri.A

Alimentador 3

Falla Monofsica con resistencia de falla de 20 Ohms

I =417,574 pri.A

Annex:

3*I0 =417,574 pri.A

100

[s]

Date: 12/4/2011
DIgSILENT

100

DIgSILENT

2 Anexo 2 Curvas de Coordinacin Alimentadores

[s]

51
KYLE 104
Ipset: 0,02 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

10

51N
KYLE 104
Ipset: 0,01 sec.A
Tpset: 1,00
Tripping Time: 0,011 s

10

0,1

0,1

0.011 s
0,01
13,20 kV 10

100

[pri.A]

0.011 s
1000

0,01
13,20 kV 10

13.2 kV II\AL01\51

Informe Tcnico

[pri.A]

1000

13.2 kV II\AL01\51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams

100

Alimentador 3

Falla Monofsica sin resistencia de falla

Date: 12/4/2011
Annex:

Pgina 98

3 Anexo 3 Curvas de Coordinacin de Lnea de Transmisin

ANEXOS

3 Anexo 3 Curvas de Coordinacin de


Lnea de Transmisin

Informe Tcnico

Pgina 99

DIgSILENT

3 Anexo 3 Curvas de Coordinacin de Lnea de Transmisin

3*I0 =1138,237 pri.A

100

51 Linea 66 TP(1)
Ipset: 5,25 sec.A
Tset: 1,00 s
Tripping Time: 1,020 s

[s]
51 Linea 66 TP
IEC 255-3 inverse
Ipset: 1,58 sec.A
Tpset: 0,05
Tripping Time: 0,156 s
10

1.020 s

0,1
0.060 s

0,01
66,00 kV 100

1000
L 66 TP\Cub_5\51 Linea 66 TP

[pri.A]

10000

L 66 TP\Cub_5\51 Linea 66 TP(1)

Estudios Norma Tcnica

50N/51N Ext Tres Puentes


Fallas Extremo Tres Puentes

Date: 12/9/2011
Annex:
DIgSILENT

Estudio EVCP SM Punta Arenas


X =755,831 pri.A

10

67 Linea 66 TP
IEC 255-3 inverse
Ipset: 3,99 sec.A
Tpset: 0,07
Tripping Time: 0,564 s

[s]

0.520 s

67 Linea 66 TP(1)
Ipset: 9,20 sec.A
Tset: 0,04 s
Tripping Time: 0,060 s

0,1

0.060 s

0,01
66,00 kV 100

1000
L 66 TP\Cub_5\67 Linea 66 TP

[pri.A]

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

10000

L 66 TP\Cub_5\67 Linea 66 TP(1)


67 Ext Tres Puentes
Fallas Monofsicas y Trifsicas

Date: 12/8/2011
Annex:

Pgina 100

DIgSILENT

3 Anexo 3 Curvas de Coordinacin de Lnea de Transmisin

XI =376,989
=370,829 pri.A

10
67 Linea 66 - PA
IEC 255-3 inverse
Ipset: 0,84 sec.A
Tpset: 0,07
Tripping Time: 0,279 s

[s]

0,1

0.060
0.060ss

67 Linea 66 - PA
Ipset: 1,45 sec.A
Tset: 0,04 s
Tripping Time: 0,060 s

0,01
66,00 kV 10

100

1000

[pri.A]

10000

C.P.A. - 66 kV\Cub_3\67 Linea 66 - PA

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

67 Ext Punta Arenas


Fallas Extremo Tres Puentes

Date: 12/9/2011
Annex:

Pgina 101

X =312,512 pri.A

10

DIgSILENT

3 Anexo 3 Curvas de Coordinacin de Lnea de Transmisin

X =833,115 pri.A
67 Linea 66 TP
IEC 255-3 inverse
Ipset: 3,99 sec.A
Tpset: 0,07
Tripping Time: 0,466 s

[s]
Falla en lnea

0.506 s

67 Linea 66 TP(1)
Ipset: 9,20 sec.A
Tset: 0,04 s
Tripping Time: 0,060 s

0,1

0.060 s

0,01
66,00 kV 100

1000
L 66 TP\Cub_5\67 Linea 66 TP

[pri.A]

Estudios Norma Tcnica


Estudio EVCP SM Punta Arenas

Informe Tcnico

10000

L 66 TP\Cub_5\67 Linea 66 TP(1)


67 Ext Tres Puentes
Fallas Monofsicas y Trifsicas

Date: 12/8/2011
Annex:

Pgina 102

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

ANEXOS

4 Anexo 4 Curvas de Coordinacin de


Protecciones de Generadores

Informe Tcnico

Pgina 103

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

Sistema Punta Arenas

Informe Tcnico

Pgina 104

X =993,754 pri.A

100

X =2519,386 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

I =7622,699 pri.A

51
IEC 255-3 inverse
Ipset: 3,00 sec.A
Tpset: 0,54
Tripping Time: 2,007 s

[s]

10

5.059 s

2.007 s

1
11,50 kV

100

1000

10000

[pri.A]

100000

Celdas 11.5 kV\G01\51

Estudios Norma Tcnica


X =516,216 pri.A

100

G1
Falla Trifsica cercana

X =1161,154 pri.A

Date: 12/4/2011
Annex:
DIgSILENT

Estudios EVCP SM Punta Arenas


I =3513,208 pri.A

51
ANSI/IEEE moderately inverse
Ipset: 5,89 sec.A
Tpset: 3,00
Tripping Time: 1,227 s

[s]

10
7.440 s

1.227 s
1

0,1
11,50 kV 100

1000

10000

[pri.A]

100000

Celdas 11.5 kV Rhona\G04\51

Estudios Norma Tcnica


Estudios EVCP SM Punta Arenas

Informe Tcnico

G4
Falla Trifsica cercana

Date: 12/4/2011
Annex:

Pgina 105

100

X =130,525 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

XI =776,583
=776,583
X =832,706
pri.A
pri.Apri.A

51-50
ANSI/IEEE inverse
Ipset: 4,25 sec.A
Tpset: 1,00
Tripping Time: 0,567 s
[s]

10

0.567 s
0.512 s

0,1
13,20 kV 100

1000

[pri.A]

10000

13.2 kV T.P.\G05\51-50

Estudios Norma Tcnica


X =657,238 pri.A

100

G5
Falla Trifsica cercana

X =2992,068 pri.A

Date: 12/4/2011
Annex:
DIgSILENT

Estudios EVCP SM Punta Arenas

X =7851,270 pri.A

51
IEC 255-3 inverse
Ipset: 5,40 sec.A
Tpset: 0,80
Tripping Time: 4,731 s
[s]

10
6.637 s

3.053 s

51
Ipset: 40,00 sec.A
Tset: 0,00 s
Tripping Time: 9999,999 s

0,1

0,01
11,50 kV 100

1000

10000

[pri.A]

100000

Extensin Celdas CTP\G07\51

Estudios Norma Tcnica


Estudios EVCP SM Punta Arenas

Informe Tcnico

G7
Falla Trifsica cercana

Date: 12/4/2011
Annex:

Pgina 106

10

X =252,740 pri.A

X =1064,388 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

XI =3326,764
=3326,764pri.A
pri.A

51-50
IEC 255-3 inverse
Ipset: 5,75 sec.A
Tpset: 0,07
Tripping Time: 0,376 s

3.356 s
[s]

51-50
Ipset: 10,60 sec.A
Tset: 0,00 s
Tripping Time: 0,020 s

0,1

0.020 s

0,01
11,50 kV 100

1000

10000

[pri.A]

100000

Extensin Celdas CTP\G08\51-50

Estudios Norma Tcnica


X =709,410 pri.A

100

G8
Falla Trifsica cercana

X =1378,831 pri.A

Date: 12/4/2011
Annex:
DIgSILENT

Estudios EVCP SM Punta Arenas


I =4171,816 pri.A

[s]

10

2.897 s

0.301 s

0,1
11,50 kV 100

1000

10000

[pri.A]

100000

Extensin Celdas CTP\G09\51

Estudios Norma Tcnica


Estudios EVCP SM Punta Arenas

Informe Tcnico

G9
Falla Trifsica cercana

Date: 12/4/2011
Annex:

Pgina 107

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

Sistema Puerto Natales

Informe Tcnico

Pgina 108

10

X =190,530 pri.A
X =1435,734 pri.A
51
Ipset: 7,00 sec.A
Tset: 0,82 s
Tripping Time: 0,840 s

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

X =3603,910 pri.A

10

Corriente de flujo de carga

[s]

[s]

51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

0.840 s
50
Ipset: 15,00 sec.A
Tset: 0,00 s
Tripping Time: 0,020 s

0,1

0,1
0.070 s

0.020 s

100
52G3\G03\50

1000

10000 [pri.A]
52G3\G03\51

100000

0,01
3,30 kV 10

100
52G3\G03\51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales
10

X = 83,404 pri.A

10000

G3
Falla Trifsica y Monofsica

I =977,354 pri.A
51
IEC 255-3 inverse
Ipset: 9,00 sec.A
Tpset: 0,08
Tripping Time: 0,555 s

100000

Date: 12/8/2011
Annex:

X =2631,750 pri.A

10

[s]

[pri.A]

DIgSILENT

0,01
3,30 kV 10

[s]
51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

51
Ipset: 20,00 sec.A
Tset: 0,00 s
Tripping Time: 0,020 s

0,1

0,1
0.070 s

0.020 s

0,01
3,30 kV 10

100
52G4\G04\51

1000

[pri.A]

10000

0,01
3,30 kV 10

100
52G4\G04\51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales

Informe Tcnico

1000

G4
Falla Trifsica y Monofsica

[pri.A]

10000

Date: 12/8/2011
Annex:

Pgina 109

10

X = 89,342 pri.A

I =977,354
51 pri.A
IEC 255-3 inverse
Ipset: 9,00 sec.A
Tpset: 0,08
Tripping Time: 0,555 s

[s]

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

X =2631,750 pri.A

10

[s]

51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

51
Ipset: 20,00 sec.A
Tset: 0,00 s
Tripping Time: 0,020 s

0,1

0,1
0.070 s

0.020 s

100
52G5\G05\51

1000

[pri.A]

10000

0,01
3,30 kV 10

100
52G5\G05\51N

1000

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales
10

X = 25,253 pri.A

G5
Falla Trifsica y Monofsica

I =439,847 pri.A

10

[pri.A]

10000

Date: 12/8/2011
Annex:
DIgSILENT

0,01
3,30 kV 10

X =130,181 pri.A

51
IEC 255-3 inverse
Ipset: 9,00 sec.A
Tpset: 0,08
Tripping Time: 0,621 s
[s]
51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

[s]

51
Ipset: 17,50 sec.A
Tset: 0,30 s
Tripping Time: 0,320 s

51
IEC 255-3 inverse
Ipset: 9,00 sec.A
Tpset: 0,08
Tripping Time: 0,621 s
0.320 s

0,1
13,20 kV 10

100
13.2 kV\G 06\51

1000

[pri.A]

0,1

0,01
10000 13,20 kV 10

0.070 s

100
13.2 kV\G 06\51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales

Informe Tcnico

1000

G6
Falla Trifsica y Monofsica

[pri.A]

10000

Date: 12/8/2011
Annex:

Pgina 110

10

X =190,530 pri.AI =1435,734 pri.A


51
Ipset: 7,00 sec.A
Tset: 0,82 s
Tripping Time: 0,840 s

X =3603,910 pri.A

10

[s]

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

[s]
51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

0.840 s

50
Ipset: 15,00 sec.A
Tset: 0,00 s
Tripping Time: 0,020 s

0,1

0,1
0.070 s

0.020 s

0,01
3,30 kV 10

100
52G8\G08\50

1000

10000 [pri.A]
52G8\G08\51

100000

0,01
3,30 kV 10

100
52G8\G08\51N

1000

Estudios Norma Tcnica

10

X =1869,434 pri.A

G8
Falla Trifsica y Monofsica

[pri.A]

100000

Date: 12/8/2011
Annex:
DIgSILENT

Estudio EVCP SM Puerto Natales

10000

X =12301,581
X 51-51N
=17410,497
pri.A
pri.A
Ipset: 4,50 sec.A
Tset: 0,82 s
Tripping Time: 0,850 s

[s]

51-51N
Ipset: 10,00 sec.A
Tset: 0,00 s
Tripping Time: 0,030 s

51-51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

In

0,1

0,01
0,40 kV 1000

0.080 s

0.080 s

0.030 s

0.030 s

10000

[pri.A]

100000

52G9\G09\51-51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales

Informe Tcnico

G9
Falla Trifsica y Monofsica

Date: 12/8/2011
Annex:

Pgina 111

10

X =1962,211 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

X =12301,581
X =17561,048
pri.A
pri.A
51
IEC 255-3 inverse
Ipset: 7,00 sec.A
Tpset: 0,09
Tripping Time: 0,580 s

[s]

1
51
Ipset: 16,50 sec.A
Tset: 0,00 s
Tripping Time: 0,020 s

0,1

0.020 s

0,01
0,40 kV 1000

0.020 s

10000

[pri.A]

100000

52G10\G10\51

Estudios Norma Tcnica


X =2464,369 pri.A

10

G10
Falla Trifsica y Monofsica

Date: 12/8/2011
Annex:
DIgSILENT

Estudio EVCP SM Puerto Natales

X =19009,250
X =26357,701
pri.A
pri.A
51-51N
Ipset: 4,50 sec.A
Tset: 0,82 s
Tripping Time: 0,850 s

[s]

51-51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

51-51N
Ipset: 10,00 sec.A
Tset: 0,00 s
Tripping Time: 0,030 s

In

0,1

0,01
0,40 kV 1000

10000

0.080 s

0.080 s

0.030 s

0.030 s

[pri.A]

100000

52G11\G11\51-51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales

Informe Tcnico

G11
Falla Trifsica y Monofsica

Date: 12/8/2011
Annex:

Pgina 112

10

X =190,530 pri.A
X =916,486 pri.A
51
Ipset: 7,00 sec.A
Tset: 0,82 s
Tripping Time: 0,840 s

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

Corriente de flujo de carga

[s]

[s]

51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

0.840 s
50
Ipset: 15,00 sec.A
Tset: 0,00 s
Tripping Time: 9999,999 s

0,1

0,01
3,30 kV 10

0,1

100
52G3\G03\50

1000

10000 [pri.A]
52G3\G03\51

100000

0,01
3,30 kV 10

100
52G3\G03\51N

1000

Estudios Norma Tcnica

10

X = 83,404 pri.A

G3
Falla Trifsica y Monofsica lejana

I =660,383 pri.A
51
IEC 255-3 inverse
Ipset: 9,00 sec.A
Tpset: 0,08
Tripping Time: 0,917 s

[pri.A]

100000

Date: 12/8/2011
Annex:
DIgSILENT

Estudio EVCP SM Puerto Natales

10000

10

[s]

[s]
51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s
0.917 s

51
Ipset: 20,00 sec.A
Tset: 0,00 s
Tripping Time: 9999,999 s

0,1

0,01
3,30 kV 10

0,1

100
52G4\G04\51

1000

[pri.A]

10000

0,01
3,30 kV 10

100
52G4\G04\51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales

Informe Tcnico

1000

G4
Falla Trifsica y Monofsica lejana

[pri.A]

10000

Date: 12/8/2011
Annex:

Pgina 113

10

X = 89,342 pri.A

I =660,383 pri.A
51
IEC 255-3 inverse
Ipset: 9,00 sec.A
Tpset: 0,08
Tripping Time: 0,917 s

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

[s]

[s]

0.917 s

51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

51
Ipset: 20,00 sec.A
Tset: 0,00 s
Tripping Time: 9999,999 s

0,1

0,01
3,30 kV 10

0,1

100
52G5\G05\51

1000

[pri.A]

10000

0,01
3,30 kV 10

100
52G5\G05\51N

Estudios Norma Tcnica

10

X = 25,253 pri.A

G5
Falla Trifsica y Monofsica lejana

I =334,839 pri.A

[pri.A]

10000

Date: 12/8/2011
Annex:
DIgSILENT

Estudio EVCP SM Puerto Natales

1000

10

51
IEC 255-3 inverse
Ipset: 9,00 sec.A
Tpset: 0,08
Tripping Time: 0,897 s
[s]
51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

[s]

51
Ipset: 17,50 sec.A
Tset: 0,30 s
Tripping Time: 9999,999 s

0.897 s

51
IEC 255-3 inverse
Ipset: 9,00 sec.A
Tpset: 0,08
Tripping Time: 0,897 s

0,1
13,20 kV 10

100
13.2 kV\G 06\51

1000

[pri.A]

0,1

0,01
10000 13,20 kV 10

100
13.2 kV\G 06\51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales

Informe Tcnico

1000

G6
Falla Trifsica y Monofsica lejana

[pri.A]

10000

Date: 12/8/2011
Annex:

Pgina 114

10

X =190,530 pri.A
I =916,486 pri.A
51
Ipset: 7,00 sec.A
Tset: 0,82 s
Tripping Time: 0,840 s

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

[s]

[s]
51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

0.840 s

50
Ipset: 15,00 sec.A
Tset: 0,00 s
Tripping Time: 9999,999 s

0,1

0,01
3,30 kV 10

0,1

100
52G8\G08\50

1000

10000 [pri.A]
52G8\G08\51

100000

0,01
3,30 kV 10

100
52G8\G08\51N

1000

Estudios Norma Tcnica

10

X =1869,434 pri.A

G8
Falla Trifsica y Monofsica lejana

I =7818,649 pri.A

[pri.A]

100000

Date: 12/8/2011
Annex:
DIgSILENT

Estudio EVCP SM Puerto Natales

10000

51-51N
Ipset: 4,50 sec.A
Tset: 0,82 s
Tripping Time: 0,850 s

[s]

51-51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

0.850 s

51-51N
Ipset: 10,00 sec.A
Tset: 0,00 s
Tripping Time: 9999,999 s

0,1

0,01
0,40 kV 1000

10000

[pri.A]

100000

52G9\G09\51-51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales

Informe Tcnico

G9
Falla Trifsica y Monofsica lejana

Date: 12/8/2011
Annex:

Pgina 115

X =2464,369 pri.A

10

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

I =12747,864 pri.A
51-51N
Ipset: 4,50 sec.A
Tset: 0,82 s
Tripping Time: 0,850 s

[s]

51-51N
Ipset: 1,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

51-51N
Ipset: 10,00 sec.A
Tset: 0,00 s
Tripping Time: 0,030 s

0,1

0.030 s

0,01
0,40 kV 1000

10000

[pri.A]

100000

52G11\G11\51-51N

Estudios Norma Tcnica

10

X =1962,211 pri.A

G11
Falla Trifsica y Monofsica lejana

Date: 12/8/2011
Annex:
DIgSILENT

Estudio EVCP SM Puerto Natales


I =7424,003 pri.A
51
IEC 255-3 inverse
Ipset: 7,00 sec.A
Tpset: 0,09
Tripping Time: 1,100 s

[s]

1.100 s
1
51
Ipset: 16,50 sec.A
Tset: 0,00 s
Tripping Time: 9999,999 s

0,1

0,01
0,40 kV 1000

10000

[pri.A]

100000

52G10\G10\51

Estudios Norma Tcnica


Estudio EVCP SM Puerto Natales

Informe Tcnico

G10
Falla Trifsica y Monofsica lejana

Date: 12/8/2011
Annex:

Pgina 116

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

Sistema Porvenir

Informe Tcnico

Pgina 117

10

X =723,266 pri.A

X =5233,824 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

X =15562,793 pri.A

10

G01_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

[s]

[s]

G01_51N
Ipset: 20,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s
1

G01_51
Ipset: 20,00 sec.A
Tset: 0,05 s
Tripping Time: 0,070 s

0.870 s

36380.387 pri.A
0.170 s
39005.104 pri.A
0.170 s

0,1

0,1
0.070 s
0.070 s

0,01
0,40 kV 100

1000
52G1\G01\G01_51

10000
[pri.A]
52G1\G01\G01_51-2

100000

0,01
0,40 kV 1000

10000

[pri.A]

100000

52G1\G01\G01_51N

Estudios Norma Tcnica

100

X =802,045 pri.A

G1
Falla Trifsicas y Monofsicas

X =9161,286 pri.A

Date: 12/8/2011
Annex:
DIgSILENT

Estudios EVCP SM Porvenir

X =21129,853 pri.A

100

G04_51N
IEC 255-3 inverse
Ipset: 1,65 sec.A
Tpset: 0,35
Tripping Time: 9999,999 s
[s]

[s]

G04_51
IEC 255-3 inverse
Ipset: 5,00 sec.A
Tpset: 0,15
Tripping Time: 0,680 s
10

10

G04_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s
13418.748 pri.A
0.970 s
1

0.870 s

1
0.794 s

0.680 s

0,1
0,40 kV 100

1000
52G4\G04\G04_51

10000
[pri.A]
52G4\G04\G04_51-2

100000

0,1
0,40 kV 100

1000
52G4\G04\G04_51N

Estudios Norma Tcnica


Estudios EVCP SM Porvenir

Informe Tcnico

10000

[pri.A]
G4

Falla Trifsicas y Monofsicas

100000

Date: 12/8/2011
Annex:

Pgina 118

100

X =161,188 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

X =1044,636 pri.A X =1487,769 pri.A

G05_51
IEC 255-3 inverse
Ipset: 2,50 sec.A
Tpset: 0,16
Tripping Time: 0,772 s

[s]

In

10

2496.575 pri.A
0.970 s

0.870 s
0.772 s

0.870 s

0.617 s

G05_51-2
Ipset: 2,50 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

0,1
3,30 kV 100

1000

[pri.A]

10000

52G5\G05\G05_51-2

Estudios Norma Tcnica


Estudios EVCP SM Porvenir
X =1574,117 pri.A

100

G5
Falla Trifsicas y Monofsicas

X =12301,581 pri.A

Date: 12/8/2011
Annex:
DIgSILENT

52G5\G05\G05_51

X =26247,791 pri.A

100

G06_51N
IEC 255-3 inverse
Ipset: 1,50 sec.A
Tpset: 0,34
Tripping Time: 9999,999 s
G06_51
IEC 255-3 inverse
Ipset: 5,00 sec.A
Tpset: 0,16
Tripping Time: 0,692 s

[s]

[s]

10

10

23374.478 pri.A
0.970 s

0.870 s

1
0.771 s

0.692 s

G06_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

0,1
0,40 kV 100

1000
52G6\G06\G06_51

10000
[pri.A]
52G6\G06\G06_51-2

100000

0,1
0,40 kV 100

1000
52G6\G06\G06_51N

Estudios Norma Tcnica


Estudios EVCP SM Porvenir

Informe Tcnico

10000

[pri.A]
G6

Falla Trifsicas y Monofsicas

100000

Date: 12/8/2011
Annex:

Pgina 119

100

X =1574,117 pri.A

X =5342,965 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

X =26247,791 pri.A

100
G07_51
IEC 255-3 inverse
Ipset: 5,00 sec.A
Tpset: 0,16
Tripping Time: 1,464 s

[s]

[s]

10

10

G07_51N
Ipset: 16,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

24445.576 pri.A
0.970 s

1.464 s
1

0.870 s

77068.781 pri.A
0.170 s

0,1
0,1
G07_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

0,01
0,40 kV 1000

10000
52G7\G07\G07_51

0.070 s

[pri.A]
52G7\G07\G07_51-2

100000

0,01
0,40 kV 1000

10000

[pri.A]

100000

52G7\G07\G07_51N

Estudios Norma Tcnica

G7
Falla Trifsicas y Monofsicas

X =2252,457 pri.A

100

Date: 12/8/2011
Annex:
DIgSILENT

Estudios EVCP SM Porvenir

X =12301,581 pri.A
X =17075,375 pri.A

G08_51
IEC 255-3 inverse
Ipset: 5,00 sec.A
Tpset: 0,16
Tripping Time: 0,783 s

[s]

10

25581.083 pri.A
0.970 s

0.870 s

88770.059 pri.A
0.170 s

0.870 s

G08_51
Ipset: 15,00 sec.A
Tset: 0,05 s
Tripping Time: 0,070 s

G08_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s
0,1
0.070 s

0,01
0,40 kV 1000

0.070 s

10000
52G08\G08\G08_51

[pri.A]

Estudios Norma Tcnica


Estudios EVCP SM Porvenir

Informe Tcnico

100000

52G08\G08\G08_51-2
G8
Falla Trifsicas y Monofsicas

Date: 12/8/2011
Annex:

Pgina 120

X =524,244 pri.A

10

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

XI =14215,166
=14215,166
X =19457,939
pri.A
pri.A
pri.A
G09-51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

[s]

In

0.870 s

0.870 s

87703.914 pri.A
0.170 s

0,1
0.070 s

0.070 s

G09-51
Ipset: 23,00 sec.A
Tset: 0,05 s
Tripping Time: 0,070 s

0,01
0,40 kV 100

1000

10000

[pri.A]

100000

52G9\G09\G09-51-2

Estudios Norma Tcnica


Estudios EVCP SM Porvenir
10

X =1519,113 pri.A

G9
Falla Trifsicas y Monofsicas

X =11838,911 pri.A

Date: 12/8/2011
Annex:
DIgSILENT

52G9\G09\G09-51

X =25663,821 pri.A

10

G10_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

[s]

[s]

G10_51N
Ipset: 16,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s
1

0.870 s

G10_51
Ipset: 17,00 sec.A
Tset: 0,05 s
Tripping Time: 0,070 s

55694.177 pri.A
0.170 s
73860.462 pri.A
0.170 s

0,1

0,1
0.070 s
0.070 s

0,01
0,40 kV 1000

10000
52G7(1)\G07\G10_51

[pri.A]
52G7(1)\G07\G10_51-2

100000

0,01
0,40 kV 1000

10000

[pri.A]

100000

52G7(1)\G07\G10_51N

Estudios Norma Tcnica


Estudios EVCP SM Porvenir

Informe Tcnico

G10
Falla Trifsicas y Monofsicas

Date: 12/8/2011
Annex:

Pgina 121

10

X =723,266 pri.A

I =3014,093 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10

G01_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

[s]

[s]

G01_51N
Ipset: 20,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s
1

G01_51
Ipset: 20,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

0.870 s

36380.387 pri.A
0.170 s
39005.104 pri.A
0.170 s

0,1

0,01
0,40 kV 100

0,1

1000
52G1\G01\G01_51

10000
[pri.A]
52G1\G01\G01_51-2

100000

0,01
0,40 kV 1000

10000

[pri.A]

100000

52G1\G01\G01_51N

Estudios Norma Tcnica

100

X =802,045 pri.A

G1
Falla Trifsicas y Monofsicas lejanas

I =4865,946 pri.A

Date: 12/8/2011
Annex:
DIgSILENT

Estudios EVCP SM Porvenir


100

G04_51N
IEC 255-3 inverse
Ipset: 1,65 sec.A
Tpset: 0,35
Tripping Time: 9999,999 s
[s]

[s]

G04_51
IEC 255-3 inverse
Ipset: 5,00 sec.A
Tpset: 0,15
Tripping Time: 1,170 s
10

10

G04_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s
13418.748 pri.A
0.970 s
1.170 s
1

0,1
0,40 kV 100

0.870 s

1000
52G4\G04\G04_51

10000
[pri.A]
52G4\G04\G04_51-2

100000

0,1
0,40 kV 100

1000
52G4\G04\G04_51N

Estudios Norma Tcnica


Estudios EVCP SM Porvenir

Informe Tcnico

10000

[pri.A]
G4

Falla Trifsicas y Monofsicas lejanas

100000

Date: 12/8/2011
Annex:

Pgina 122

100

X =161,188 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

I =615,230 pri.A

G05_51
IEC 255-3 inverse
Ipset: 2,50 sec.A
Tpset: 0,16
Tripping Time: 1,233 s

[s]

10

2496.575 pri.A
0.970 s

1.233 s
1

0.870 s

G05_51-2
Ipset: 2,50 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

0,1
3,30 kV 100

1000

[pri.A]

52G5\G05\G05_51

10000

52G5\G05\G05_51-2

Estudios Norma Tcnica


X =1574,117 pri.A

100

G5
Falla Trifsicas y Monofsicas lejanas

I =6547,377 pri.A

Date: 12/8/2011
Annex:
DIgSILENT

Estudios EVCP SM Porvenir


100

G06_51N
IEC 255-3 inverse
Ipset: 1,50 sec.A
Tpset: 0,34
Tripping Time: 9999,999 s
G06_51
IEC 255-3 inverse
Ipset: 5,00 sec.A
Tpset: 0,16
Tripping Time: 1,152 s

[s]

[s]

10

10

23374.478 pri.A
0.970 s

1.152 s
1

0.870 s

G06_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

0,1
0,40 kV 100

1000
52G6\G06\G06_51

10000
[pri.A]
52G6\G06\G06_51-2

100000

0,1
0,40 kV 100

1000
52G6\G06\G06_51N

Estudios Norma Tcnica


Estudios EVCP SM Porvenir

Informe Tcnico

10000

[pri.A]
G6

Falla Trifsicas y Monofsicas lejanas

100000

Date: 12/8/2011
Annex:

Pgina 123

100

X =1574,117 pri.A

I =6547,377 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

100
G07_51
IEC 255-3 inverse
Ipset: 5,00 sec.A
Tpset: 0,16
Tripping Time: 1,152 s

[s]

[s]

10

10

G07_51N
Ipset: 16,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

24445.576 pri.A
0.970 s

1.152 s
1

0.870 s

77068.781 pri.A
0.170 s

0,1
0,1
G07_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

0,01
0,40 kV 1000

10000
52G7\G07\G07_51

[pri.A]
52G7\G07\G07_51-2

100000

0,01
0,40 kV 1000

10000

[pri.A]

100000

52G7\G07\G07_51N

Estudios Norma Tcnica


X =2252,457 pri.A

100

G7
Falla Trifsicas y Monofsicas lejanas

Date: 12/8/2011
Annex:
DIgSILENT

Estudios EVCP SM Porvenir


I =6547,377 pri.A

G08_51
IEC 255-3 inverse
Ipset: 5,00 sec.A
Tpset: 0,16
Tripping Time: 1,424 s

[s]

10

25581.083 pri.A
0.970 s

1.424 s
1

88770.059 pri.A
0.170 s

0.870 s

G08_51
Ipset: 15,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

G08_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s
0,1

0,01
0,40 kV 1000

10000
52G08\G08\G08_51

[pri.A]

Estudios Norma Tcnica


Estudios EVCP SM Porvenir

Informe Tcnico

100000

52G08\G08\G08_51-2
G8
Falla Trifsicas y Monofsicas lejanas

Date: 12/8/2011
Annex:

Pgina 124

X =524,244 pri.A

10

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

I =7279,890 pri.A
G09-51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

[s]

0.870 s

87703.914 pri.A
0.170 s

0,1

G09-51
Ipset: 23,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

0,01
0,40 kV 100

1000

10000

52G9\G09\G09-51

[pri.A]

100000

52G9\G09\G09-51-2

Estudios Norma Tcnica

10

X =1519,113 pri.A

G9
Falla Trifsicas y Monofsicas lejanas

I =6356,070 pri.A

Date: 12/8/2011
Annex:
DIgSILENT

Estudios EVCP SM Porvenir


10

G10_51-2
Ipset: 5,00 sec.A
Tset: 0,85 s
Tripping Time: 0,870 s

[s]

[s]

G10_51N
Ipset: 16,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s
1

0.870 s

G10_51
Ipset: 17,00 sec.A
Tset: 0,05 s
Tripping Time: 9999,999 s

55694.177 pri.A
0.170 s
73860.462 pri.A
0.170 s

0,1

0,1

0,01
0,40 kV 1000

10000
52G7(1)\G07\G10_51

[pri.A]
52G7(1)\G07\G10_51-2

100000

0,01
0,40 kV 1000

10000

[pri.A]

100000

52G7(1)\G07\G10_51N

Estudios Norma Tcnica


Estudios EVCP SM Porvenir

Informe Tcnico

G10
Falla Trifsicas y Monofsicas lejanas

Date: 12/8/2011
Annex:

Pgina 125

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

Sistema Puerto Williams

Informe Tcnico

Pgina 126

100

X =782,971 pri.A

XI =6175,913
=6175,913 pri.A
pri.A

X =13429,457 pri.A

100

[s]

[s]

10

10

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

51N
IEC 255-3 inverse
Ipset: 1,65 sec.A
Tpset: 0,15
Tripping Time: 9999,999 s

51-51N
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,03
Tripping Time: 0,153 s

0.340 s

0.153 s

1000
52G1\G01\51-51N

10000

[pri.A]

100000

0,1
0,40 kV 100

1000
52G1\G01\51N

10000

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams
10

X =436,578 pri.A

G1
Fallas Trifsicas y Monofsicas

I =5233,824 pri.A

100000

Date: 12/8/2011
Annex:

X =12457,367 pri.A

100

[s]

50
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,02
Tripping Time: 0,117 s

[s]

[pri.A]

DIgSILENT

0,1
0,40 kV 100

51N(1)
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,10
Tripping Time: 9999,999 s

10

0.334 s
0.117 s
0,1

0,1

0,01
0,40 kV 100

1000
52G2\G02\50

10000

[pri.A]

100000

0,01
0,40 kV 100

1000
52G2\G02\51N(1)

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams

Informe Tcnico

10000

G2
Fallas Trifsicas y Monofsicas

[pri.A]

100000

Date: 12/8/2011
Annex:

Pgina 127

10

X =468,874 pri.A

I =3768,353 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

X =9814,087 pri.A

10

51N(1)
IEC 255-3 inverse
Ipset: 2,00 sec.A
Tpset: 0,10
Tripping Time: 9999,999 s

50
IEC 255-3 inverse
Ipset: 2,00 sec.A
Tpset: 0,03
Tripping Time: 0,133 s

[s]

[s]

0.272 s

0.133 s

1000
52G3(1)\G03\50

10000

[pri.A]

100000

0,1
0,40 kV 100

1000
52G3(1)\G03\51N(1)

10000

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams
100

X =369,191 pri.A

G3
Fallas Trifsicas y Monofsicas

I =2446,331 pri.A

[pri.A]

100000

Date: 12/8/2011
Annex:
DIgSILENT

0,1
0,40 kV 100

X =7633,405 pri.A

10

51N
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,06
Tripping Time: 9999,999 s

[s]

[s]

51
IEC 255-3 inverse
Ipset: 2,50 sec.A
Tpset: 0,04
Tripping Time: 0,310 s

10

0.265 s
0.310 s

0,1
0,40 kV 100

1000
52G6\G6\51

10000

[pri.A]

100000

0,1
0,40 kV 100

1000
52G6\G6\51N

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams

Informe Tcnico

10000

G6
Fallas Trifsicas y Monofsicas

[pri.A]

100000

Date: 12/8/2011
Annex:

Pgina 128

100

X =782,971I pri.A
=2327,698 pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

100

[s]

[s]

10

10

51N
IEC 255-3 inverse
Ipset: 1,65 sec.A
Tpset: 0,15
Tripping Time: 9999,999 s

51-51N
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,03
Tripping Time: 0,558 s

0.558 s

0,1
0,40 kV 100

1000
52G1\G01\51-51N

10000

[pri.A]

100000

0,1
0,40 kV 100

1000
52G1\G01\51N

10000

Estudios Norma Tcnica

10

X =436,578 pri.AI =2162,219 pri.A

Date: 12/8/2011
Annex:

100

[s]

50
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,02
Tripping Time: 0,464 s

[s]

G1

Fallas Trifsicas y Monofsicas lejanas

100000

DIgSILENT

Estudio EVCP SM Puerto Williams

[pri.A]

10

51N(1)
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,10
Tripping Time: 9999,999 s

0.464 s
1

0,1

0,1

0,01
0,40 kV 100

1000
52G2\G02\50

10000

[pri.A]

100000

0,01
0,40 kV 1000

10000

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams

Informe Tcnico

[pri.A]

100000

52G2\G02\51N(1)

G2
Fallas Trifsicas y Monofsicas

Date: 12/8/2011
Annex:

Pgina 129

10

X =468,874
I =1162,854
pri.A
pri.A

DIgSILENT

4 Anexo 4 Curvas de Coordinacin de Protecciones de Generadores

10
51N(1)
IEC 255-3 inverse
Ipset: 2,00 sec.A
Tpset: 0,10
Tripping Time: 9999,999 s

50
IEC 255-3 inverse
Ipset: 2,00 sec.A
Tpset: 0,03
Tripping Time: 0,559 s

[s]

[s]

0.559 s

0,1
0,40 kV 100

1000
52G3(1)\G03\50

10000

[pri.A]

100000

0,1
0,40 kV 100

1000
52G3(1)\G03\51N(1)

10000

Estudios Norma Tcnica

100

G3
Fallas Trifsicas y Monofsicas

X =369,191 pri.AI =1709,902 pri.A

100000

Date: 12/8/2011
Annex:
DIgSILENT

Estudio EVCP SM Puerto Williams

[pri.A]

10

51N
IEC 255-3 inverse
Ipset: 4,00 sec.A
Tpset: 0,06
Tripping Time: 9999,999 s

[s]

[s]

51
IEC 255-3 inverse
Ipset: 2,50 sec.A
Tpset: 0,04
Tripping Time: 0,519 s

10

0.519 s

0,1
0,40 kV 100

1000
52G6\G6\51

10000

[pri.A]

100000

0,1
0,40 kV 1000

10000

Estudios Norma Tcnica


Estudio EVCP SM Puerto Williams

Informe Tcnico

[pri.A]

100000

52G6\G6\51N

G6
Fallas Trifsicas y Monofsicas

Date: 12/8/2011
Annex:

Pgina 130

Anda mungkin juga menyukai