Anda di halaman 1dari 4

electrical-engineering-portal.

com

http://electrical-engineering-portal.com/an-overview-of-grounding-system-grounded

An Overview Of Grounding System (Grounded)


Asif Eqbal

An Overview Of Grounded Grounding System (on photo: Grounded solar panel by J.E.M. Solar; jemsolar.com)

Continued from technical article: An Overview Of Grounding System (Ungrounded)

Topics covered

Solidly grounded system


Let us assume that R phase (Phase-3 in figure-3) is shorted to ground than:
If = Current through shorted path (Fault current)
In = Current through neutral to earth connection
Icy = Capacitive current returning via the network Phase-2 (Y phase)-earth capacitances
IcB = Capacitive current returning via the network Phase-1 (B phase)-earth capacitances
We can write:

If = In + IcY + IcB + Ir // Equation-08


Where Ir = Current returning via network insulation resistance which is
always negligible
In case of LV, system voltage available between phase and earth is
415/1.732 = 240V. Resistance of earth plate, grounding connections
etc is of the order of 1.5 Ohms so the earth current is limited to
approximately 240/1.5 =160 Amperes . This is not very high magnitude
hence any intentional impedance is not required in neutral to earth
connection.
As per equation -08 for If one can see that if IcY and IcB is negligible
than If = In which is the case in LV system. At 415V level capacitive
ground currents are not significant hence we can write:

Figure 3 - Solidly grounded system

If = In for solidly earthed LV system // Equation-09


Go back to Index
Top

Resistance grounded system


In case of MV system (3.3kV onwards to 33kV)
voltage between phase and earth is high. Also
capacitive charging current is not large enough to
compensate the same, so earth fault current is likely to
be excessive.
Hence resistance is connected between neutral to
ground connection. Current through neutral is limited
to 100-400 Amperes.
Figure 4 - Resistance grounded system

Restricting the earth fault current / current


through neutral
Although all the component of power system at MV level are rated at full MV system fault level, for instance:
Winding of transformer ,
Cables,
Bus ducts,
Rotating machine winding, etc.
Than what is getting protected by restricting the earth fault current/current through neutral?
The neutral of transformer or generator are grounded through impedance, the principal element of which is
resistance. This method is used when the earth fault current would be too large if not restricted (e.g.) MV
Generators. Here, a resistor is connected intentionally between the neutral and earth. This is to limit the earth
fault current.
Go back to Index

The reasons to limit the earth fault current


The reasons to limit the earth fault current are:
1. In rotating electrical machines like motors and generators, if the earth fault current is high, as in the case of
solid earthing, the core damage would be high. To limit the damage to the core, machine manufacturers allow only
a limited ground fault current.
This is given in the form of a core damage curve.
2. A typical value would be 25A-100A for 1 second. This value is used as a guide in selecting NGR and setting
stator earth fault relays in generator protection.
3. Winding damage in rotating electrical machines is not of serious concern (Though windings are rated for full
fault level). The repairs to winding damages can be done by the local re-winder. But, in case of core damage,
repairs cannot be carried out at site. The machine has to be sent back to the manufacturers works for repairs thus
resultingin prolonged periods of loss of production.
Since rotating electrical machines are not present in voltage levels from 22kV onwards, these systems are
usually solidly grounded.
4. X0/X1 ratio of the system also decides type of neutral earthing. If the corresponding X0/X1 ratio falls under
that predefined range. It is a choice between to weather to deal with higher voltage or higher current while under
short circuit. Effectively earthed lowers the over voltage limit of the healthy phases while another phase is short
circuited to earth. But the ground fault current is very high.
That means system will need a high capacity breaker but insulation system has to be moderate BIL rating.
But as the neutral to earth impedance increases ground fault current reduces but doing so the over voltage factor
will rise even up to 1.73 times! So requires a breaker with low current capacity but a HIGH BIL for all insulation
system.
Let us assume that R phase (Phase-1 in figure-4) is shorted to ground than:
If = Current through shorted path (Fault current)
In = Current through neutral to earth connection
Icy = Capacitive current returning via the network Phase-2 (Y phase)-earth capacitances
IcB = Capacitive current returning via the network Phase-3 (B phase)-earth capacitances
Repeating equation-8 we can write:
If = In + IcY + IcB + Ir
Neglecting Ir and substituting the following:
In = -V1/Rn (Negative sign indicates that capacitive charging & discharging current are in phase opposition to
current through neutral)
IcY + IcB = Total capacitive charging and discharging current of healthy phase = j3CwV1 from equation-07
Phasor diagram representation will be:
So finally after substitution of In and IcY + IcB expression for ground fault current in MV system would be:
If = -V1/Rn + j3CwV1 // Equation -10
Magnitude of ground fault current will be:

|If| = |V1|(I/Rn)2+ 9C2w2


Go back to Index
Top

System earthing at EHV level


In case of HV system (above 33kV) Capacitive ground current is large
enough to neutralize the earth fault currents hence no resistance is
required in neutral to earth connection.
Solid grounding is universally adopted for following reasons:
Figure 5 - Phasor Diagram

1. As we already understood that it is a choice between weather to deal


with higher voltage or higher current while under short circuit. At EHV level
if we opt for higher voltage than due to higher costof insulation at EHV selection of higher voltage will not be a
viable idea.
It is better to opt for higher current by selecting solid grounding.
2. Rotating machines are not present at EHV system so there is no use of limiting the ground fault current as we
do in MV system. Even if rotating machines are present because of higher voltage capacitive ground current is
also large enough to neutralize the earth fault current.
Go back to Index

References:
1. Industrial electrical network design guide By Schneider electric
2. Switchgear protection & power system By Sunil S Rao, Khanna publications
3. EARTHING: Your questions answered By Geoff Cronshaw
4. IEEE Recommended Practice for Electric Power Distribution for Industrial Plants

Anda mungkin juga menyukai