Anda di halaman 1dari 4

RTU560 product line

Real Time Clock 560RTC01


Data sheet

Ext. GPS antenna

GPS
receiver

FR
ST

+24V
MIN1
+
MIN2
-

monitoring
minute pulse
transmitter
monitoring

Application
A remote terminal unit RTU560 can be synchronized with the
time information received from the global positioning system
(GPS) satellites using the module 560RTC01. The RTU560 reads
the time and date from the module 560RTC01 and synchronizes
its internal time to the standard time by the means of a minute
pulse. The use of the module 560RTC01 ensures that process
information from several terminal units are synchronized, when
they include time information.

LS
MN

Alarm
k1
RS 232

serial

RTU system bus


Figure 1: Block diagram 560RTC01

Characteristics
Reliable receipt of the GPS signal is possible when the antenna
is mounted to a place where it receives in minimum one satellite.
The normal case will be that it receives four satellites. This is
possible when the antenna is mounted on top of a building so
it "sees" most of the sky.
The GPS receiver calculates its position and synchronizes to the
GPS during receiving the information from the satellites. Once it
has calculated its position, it starts to synchronize the RTU by
generating the minute pulse and sending the absolute time to
the RTU560 CPU via the RTU system bus.
The communication unit (CMU) synchronizes itself to the GPS
time by the leading edge of the minute pulse MIN1. The CMU
reads the time and date via the RTU system bus.

In case of GPS signal drop outs the clock on the 560RTC01


will continue working using a highly accurate quartz clock. An
internal battery allows the 560RTC01 to continue operation ( 10
years), even when the RTU station is switched off. After power
up the RTU560 has thereby a valid time in at once.
If the GPS signal fails for more than 2.5 h or as long as the
560RTC01 is not synchronized, the alarm relay contact closes.
In addition to the minute pulse output for synchronization of the
RTU560, there is one further minute pulse output which is interfaced to the module via optocoupler (MIN2).
At each minute the time, date and status (33 bytes) will be read
out via the serial data interface RS232.
On the front panel of the real-time clock 560RTC01 there are
four light emitting diodes indicating the following operating statuses:
ST: Summary alarm of the board
FR: Free-Running
560RTC01 is not synchronized with the GPS
LS: Lock Status
The 560RTC01 has calculated its position from the information received from four satellites. Its position is locked.
MN: Minute pulse
Flashes with each minute pulse

2 | 1KGT 150 418 V004 1 - Real Time Clock 560RTC01

Technical data

Preciseness

In addition to the RTU500 series general technical data, the following applies:
Mechanical layout
Dimensions

Free running

0.1 ppm = 110-7 = 9 ms/day


(after more than 24 hours of GPS operation)

Environmental conditions
160 mm x 100 mm, 3HE euro card
format
4R (20 mm) front panel

Housing type

Printed circuit board

Mounting

for mounting in RTU560 racks

Weight

0,3 kg

Nominal operating temperature range:

0C... 70C

EN 60068-2-1, -2-2, -2-14


Relative humidity

5 ... 95 %

EN 60068-2-30

(non condensing)

Ordering information
560RTC01 R0001

1KGT006700R0001

Electrical Layout
Receiver

Type:
five channel C/A code receiver

Antenna

Type:
Active antenna- / Converter-unit
Cable:
max. 200 m with
RG58 standard coax cable

Interfaces

Minute pulse:

Accessories ordering information


Antenna

1KGT 006 800 R0001

23AN02 R0001
Antenna cable

1KGT 006 900 R00XX

23AC02 R00XX:

XX = Length in meter
Default length:
20 or 50 m

2 x opto-coupler output
MIN2:
24 V DC / 20 mA load
MIN1:
opto-coupler output
Prepared for TSY input of CMU
Alarm output

Contact (NC)
560RTC01 not synchronized or
GPS signal drop out > 2.5 h

Alarm contact

Max. switching voltage: 60 VDC


Max. current: 0,5 A DC
Max. power: 10 W

Battery

Capacity: 10 years

Serial output (RS232)

Baudrate:
9600 Bit/s
Character format:
8 bit / 1 stopbit / even parity

Current consumption for power supplied via RTU560 backplane


5 V DC

700 mA

24 V DC

Preciseness
Minute pulse

2 sec, in the first 20 minutes


500 nsec, 20 minutes after synchronization

Real Time Clock 560RTC01 - 1KGT 150 418 V004 1 | 3

ABB AG
Power Systems Division
P.O. Box 10 03 51
68128 Mannheim, Germany

Note:
The specifications, data, design or other information contained in this document
(the Brochure) - together: the Information - shall only be for information purposes and shall in no respect be binding. The Brochure does not claim to be exhaustive. Technical data in the Information are only approximate figures. We re-

www.abb.com/substationautomation

serve the right at any time to make technical changes or modify the contents of
this document without prior notice. The user shall be solely responsible for the
use of any application example or information described within this document.
The described examples and solutions are examples only and do not represent
any comprehensive or complete solution. The user shall determine at its sole
discretion, or as the case may be, customize, program or add value to the ABB
products including software by creating solutions for the end customer and to
assess whether and to what extent the products are suitable and need to be adjusted or customized.
This product is designed to be connected to and to communicate information
and data via a network interface. It is the users sole responsibility to provide and
continuously ensure a secure connection between the product and users or end
customers network or any other network (as the case may be). The user shall establish and maintain any appropriate measures (such as but not limited to the installation of firewalls, application of authentication measures, encryption of data, installation of anti-virus programs, etc) to protect the product, the network,
its system and the interface against any kind of security breaches, unauthorized
access, interference, intrusion, leakage and/or theft of data or information. ABB
AG is not liable for any damages and/or losses related to such security breaches,
any unauthorized access, interference, intrusion, leakage and/or theft of data or
information.
ABB AG shall be under no warranty whatsoever whether express or implied and
assumes no responsibility for the information contained in this document or for
any errors that may appear in this document. ABB AG's liability under or in connection with this Brochure or the files included within the Brochure, irrespective
of the legal ground towards any person or entity, to which the Brochure has been
made available, in view of any damages including costs or losses shall be excluded. In particular ABB AG shall in no event be liable for any indirect, consequential or special damages, such as but not limited to loss of profit, loss of production, loss of revenue, loss of data, loss of use, loss of earnings, cost of capital or cost connected with an interruption of business or operation, third party
claims. The exclusion of liability shall not apply in the case of intention or gross
negligence. The present declaration shall be governed by and construed in accordance with the laws of Switzerland under exclusion of its conflict of laws rules
and of the Vienna Convention on the International Sale of Goods (CISG).
ABB AG reserves all rights in particular copyrights and other intellectual property
rights. Any reproduction, disclosure to third parties or utilization of its contents in whole or in part - is not permitted without the prior written consent of ABB AG.
Copyright ABB 2014
All rights reserved

4 | 1KGT 150 418 V004 1 - Real Time Clock 560RTC01

Anda mungkin juga menyukai