These notes are part of RAD Trainings domestic ACS natural gas training programme. They cover the
underpinning knowledge requirements for the ventilation of domestic natural gas appliances. An up-to-date version
is available from www.radmidlands.co.uk
These notes are for information only and should not be used instead of normative documents or as a substitute
for manufacturers instructions. RAD Training (Midland) Ltd. accepts no responsibility for any consequences of the
usage of these notes or the reliance on any information within them.
Contents
Page
Topic
10
13
14
Air vents
Measuring an air vent
Air bricks
15
16
18
19
20
Glossary
Page 1 of 20
Normative documents
Use manufacturers instructions to find the ventilation requirements of specific appliances
wherever possible.
British Standard 5440-2:2009 gives general information on ventilation requirements for
domestic natural gas appliances.
The Gas Industry Unsafe Situations Procedure Edition 6 (AMD 1 & 2) details the procedures
for dealing with dangerous or potentially dangerous gas installations including incorrect
ventilation.
The Building Regulations Part J (Heat Producing Appliances) 2010 describes the legal
requirements of heating appliance installations.
The Gas Safety (Installation and Use) Regulations 1998 describes the legal requirements of gas
installations.
Page 2 of 20
Open flue appliances remove air from the room. This causes
depressurisation of the room which can help to draw in fresh air
through vents, etc.
Page 3 of 20
Room sealed appliances are sealed from the room. This means that
the room does not need ventilation for combustion air.
Note: Do not use heat output for ventilation calculations. Heat output is a measure of
heat produced by an appliance. Heat input is a measure of the amount of gas used.
There are two forms of kilowatt, net and gross. All calculations in these notes are based on kW
net.
Heat inputs for modern gas appliances will be given in kW net in manufacturers data. Older
appliances may have figures in kW gross (and may not indicate either net or gross).
If you have a kW gross figure you can convert it to kW net with the following formula:
heat input (kW net) = heat input (kW gross) 1.1
Page 4 of 20
Adventitious air
Some air may come into a room from outside through gaps around window and door frames
and through floorboards. This is called adventitious ventilation.
In modern and renovated properties double glazing and draught-proofing has reduced this
source of air. The heating engineer must decide whether adventitious air is available or not.
If adventitious air is available the ventilation requirement (for open flue appliances only) can be
reduced by 35 cm2.
Note: Reducing the ventilation by 35 cm2 is equivalent to taking off 7 kW from the
appliance heat input. Many open flue appliances of heat input 7 kW or under do not
need purpose-provided ventilation if adventitious air is available.
DFEs are a special case of open flue gas fire. They are usually
in the form of a basket or tray housed within a chimney.
Air vents for DFEs should not be situated inside the chimney.
Page 5 of 20
Page 6 of 20
Maximum
allowable
heat input
Cooker, grill,
or hotplate
n/a
Instantaneous
Water heater
11 kW
Fire / space
heater in a
habitable
room
Fire / space
heater in a
hallway,
landing etc.
45 watt
per m3
90 watt
per m3
Room
volume
m3
less than 5
5 to 10
more than 10
less than 5
5 to 10
>10 to 20
more than 20
100
0 if there is a door to outside, 50 if not
none
installation not permitted
100
50
none
must be at least
the heat input
kW of appliance
multiplied by
22 . 22
must be at least
the heat input
kW of appliance
multiplied by
11 . 11
Openable
window or
equivalent
needed?
YES
YES
YES
YES
Page 7 of 20
Page 8 of 20
Others
e.g. cookers, flueless water heaters, open flue water heaters
The first step is to put every gas appliance in the room into one of these three categories.
The second step is to calculate the ventilation requirement of each category in turn:
Open Flue Space Heaters
Find the total heat input (kW net) of all the appliances in this category.
Multiply by 5
Subtract 35 (if adventitious air is available)
The result is the ventilation requirement for this category in square centimetre.
Note: For DFEs do not use heat input to calculate the ventilation.
Instead, add 100 cm2 to the total and do not take off adventitious
allowance from the total.
Flueless Space Heaters
The ventilation requirement for this category is the total of all the individual ventilation
requirements of the flueless space heaters in the room.
Others (non-space heaters)
The ventilation requirement for this category is equal to the largest individual ventilation
requirement of the non-space heaters in the room.
The third step is to determine which of the three categories has the largest requirement. This
will be equal to the room ventilation requirement.
Ventilation of Domestic Natural Gas Appliances
Page 9 of 20
b) c)
none
a)
Note: An openable window is needed because there is a flueless appliance in the room.
Page 10 of 20
b) d)
none
a) c)
Note: An openable window is needed because there is a flueless appliance in the room.
Page 11 of 20
3. A room of 70 m3 contains:
a) a DFE of heat input 5.6 kW net
b) a flueless gas fire of heat input 2.9 kW net
First step, put the appliances into their categories:
Open Flue Space Heaters:
Flueless Space Heaters:
Others:
a)
b)
none
Note: An openable window is needed because there is a flueless appliance in the room.
Page 12 of 20
Air vents
Ventilation for gas appliances shall be provided by air vents which:
shall be permanently open, not closable.
shall not have a mesh or flyscreen. These become easily blocked by dust or lint.
shall be of rigid construction. Soft aluminium vents are not permitted because it is
possible for householders to press shut the openings to stop draughts.
should have openings on their smallest side of between 5 mm and 10 mm. Smaller holes
can easily be blocked by dust and lint. Larger holes may allow the entry of vermin.
If the free area is not marked on the vent it is possible to measure and calculate it. For
example, if each hole in the vent above measures 180 x 6 mm, the total free area of the vent
can be calculated as follows:
Each opening = 180 mm x 6 mm = 1080 mm2
1080 mm2 x 11 openings = 11880 mm2
Convert mm2 to cm2 by dividing by 100:
11880 mm2 100 = 118.80 cm2
If a vent has sloping vanes it is important to measure the internal size of the openings, not the
external size:
correct measurement
= 10 mm
Page 13 of 20
Air bricks
Air bricks are an acceptable form of ventilation but the amount of free air they provide is not
great (typically 20 to 40 cm2).
Air bricks normally have tapered openings with the visible side of the brick having larger holes
than the side opening into the wall cavity. This makes free area difficult to measure (because it
is determined by the smaller, non-visible openings). This problem can be solved by inserting a
drill bit of known diameter. Progressively larger bits can be inserted to find the size of the
opening:
Page 14 of 20
Open flue
Room sealed
Vents to outside
Vents to room
Vents to outside
Vents to room
high level
10
10
low level
10
20
10
Ventilation may be ducted into a compartment from a ventilated roof space. Separate ducts
should be provided to both high and low level. The cross-sectional area of ducts shall be at
least equal to the area of the vents they serve. A ventilated roof space may be considered as
outside air if it is sufficiently ventilated (see BS 5250) but otherwise should be treated as an
internal space.
In the case of an open flue appliance in a compartment vented to a room, the room must be
ventilated according to the usual requirements of the appliance.
Compartments shall not be used to house open flue appliances in a bathroom or shower room.
Compartment air vents shall not communicate with a bathroom or shower room.
Page 15 of 20
room
air
room
air
room
air
outside
air
outside
air
Installation A unacceptable: the two vents are communicating with different spaces.
Installation B acceptable
Installation C unacceptable: no high level ventilation is provided.
Page 16 of 20
4. Are the following compartment installations, in which ventilation is ducted from a wellventilated roof space, acceptable or not?
duct
cross section
150 cm2
150 cm2
vent
30 kW
heat input
room sealed
boiler
150 cm2
vent
150 cm2
vent
30 kW
heat input
room sealed
boiler
duct
cross section
100 cm2
150 cm2
vent
150 cm2
vent
30 kW
heat input
room sealed
boiler
duct
cross section
150 cm2
150 cm2
vent
A correct.
B incorrect. Cross sectional area of duct is too small for the vent size.
C incorrect. Vents cannot share a duct.
Page 17 of 20
If ventilation is taken through more than one internal wall the internal air vents should
be 50% bigger than the external vent (which is sized normally).
Internal air vents should be positioned at low level, no higher than 450 mm from the
floor. This is to slow the passage of smoke and poisonous gases in the event of a fire.
air
path
Not a bathroom or shower room
Note: The above calculation assumes that the room containing the water heater has
adventitious air available directly.
Page 18 of 20
Convert to:
m3/h
m3/h
Convert
from:
ft3/h
BTU/h
kW gross
kW net
x 35.35
x 36764
x 10.77
x 9.80
x 1040
3.28
3.61
3412
3753
ft3/h
35.35
BTU/h
36764
1040
kW
gross
10.77
x 3.28
x 3412
kW net
9.80
x 3.61
x 3753
1.1
x 1.1
For example to convert a boilers heat input from 42000 BTU / h into kW net:
With your left hand find BTU/h in the Convert from section. With your right hand find kW net
in the Convert to section. Move your hands across and down respectively. They will intersect
at the required conversion formula.
Page 19 of 20
Glossary
Adventitious air
Air vent
Carbon monoxide
Carbon dioxide
CO
CO2
Combustion air
Compartment
Complete combustion
Flue
Free area
Gas
Heat input
Incomplete combustion
Natural gas
Oxygen
Space heater
Vent
Ventilation
Vitiation
Page 20 of 20