1. - CONCEPTUAL DESIGN.................................................4
1.1. Identify the location of the building...................................4
1.2. Plan View and Elevation....................................................4
4. LOAD COMBINATION.................................................34
4.1. Girder Moment................................................................35
4.2. Girder Shear Due To Moment Only..................................35
4.3. Column Moment..............................................................36
4.4. Column Axial Force..........................................................36
4.5. Load Combination Girder Moment...................................39
4.6. Load Combination Column Moment.................................40
4.7. Load Combination Column Axial Force............................41
5. - DESIGN OF MEMBERS...............................................42
5.1. Critical Load Acting in Members......................................42
5.1.1 - Calculus of the critical moment and axial force for the case of exterior
and interior columns from R-7 to 5-4...........................................................45
5.1.2 - Calculus of the critical moment and axial force for the case of exterior
and interior columns from 4-3 to 2-1...........................................................47
6. STRUCTURAL DETAILS..............................................76
6.1. Connections....................................................................76
6.2. Column Splice.................................................................78
6.3. Column Base Plate..........................................................79
6.4. Interior Shear Walls.........................................................81
6.5. Composite Slab...............................................................82
8. ANSYS ANALYSIS......................................................85
8.1 Static analysis..................................................................... 85
8.1.1. Materials.................................................................................................. 85
8.1.2. Mesh......................................................................................................... 85
8.1.3. Loads........................................................................................................ 86
8.1.4. Results..................................................................................................... 86
Bibliography...................................................................95
1. Conceptual Design
1.1 Introduction
Design of 8 story building is required of office building located in Tucson,
Arizona. The dimensions of the building are as shown 90x120. In this report
will find in details the calculations for the design of the 8 floors and roof with
all the moments details and the choice of the member after the trial and
error based on the (live, dead, wind, seismic load).
Type of weight
Self-weight of the
slab (4 thick slab
density=144
[p/qft])
Self-weight of the
frame
Floor finish(hard
wood)
Ceiling(Fiber Board)
Mechanical
equipment
Water proofing
Misc. weights
Floor 2-8
weight
weight [kip/ft]
[p/sqft]
48
1.44
weight
[p/sqft]
48
Roof
weight [kip/ft]
1.44
16
0.48
16
0.48
0.12
1
4
0.03
0.12
0.15
7
80
0.21
2.4
1
5
75
0.03
0.15
2.25
In Figure 2.2 is shown how the dead load is acting in the frame.
1, A t 200 ft 2
R1= 1.2 0.003 A t ,200 ft 2< A t <600 ft 2
0.6, A t 600 ft 2
1, F 4 inch/ ft
R2= 1.2 0.05 F , 4 inch/ft < F< 12inch/ft
0.6, F 12 inch/ft
Where At is the roof area, in our case 90x120=1080 ft2. R1=0.6.
F is the # of inches of rise/ft. This building has a flat roof so R2=1.0.
Type of weight
20 R1 R2=200.61
Minimum
distributed load
Partition wall
Floor 2-8
weight
weight [kip/ft]
[p/sqft]
50
1.5
8
58
0.24
1.74
weight
[p/sqft]
12
12
In Figure 2.3 is shown how the dead load is acting in the frame.
Roof
weight [kip/ft]
0.36
0.36
Kz
K zt
topography coefficient
Kd
wind speed
importance factor
The following table contains the values of the above constants according
to the handout (pg. 20.):
Table 2.3 Wind load constants (windward side)
Kz
Consta
nt
Value
z
K z =2.01
zg
see
belo
w
z=15, z< 15
z=z , z 15
K zt
Kd
0.8
5
v
[mp
h]
90
1.1
5
Cp
0.8
5
(L/B=0.
75)
0.8
( ){
Floor
#
AW floor #
[p/sqft]
R
8
7
123.62
159.83
153.6
Load acting
on a typical
frame
(width 30 ft)
[kip]
3.71
4.79
4.61
6
5
4
3
2
146.67
138.8
129.61
118.42
103.63
4.4
4.16
3.89
3.55
3.11
Roof
According to the handout (pg. 20.):
Since h/L1 Cp=-1.3 (0h/2). The reduction factor is 0.8 since the roof
area is larger than 1000 sqft.
Since h/L1 Cp=-0.7 (h/2L).
G=0.85 (Rigid Structure)
p=q z (h)G C p
(0h/2) the uplift is -0.542 kip/ft
(h/2L) the uplift is -0.365 Kip/ft
It is important to note that these forces acting in the roof due to wind, are
not considered in the design due that they are acting in the vertical direction
and the weight of the structure is acting in the opposite direction and it is
much bigger, thus this loads practically dont have a significant contribution
for the response.
Leeward side
According to the handout (pg. 20.):
Since L /B0.75 Cp=-0.5
G=0.85 (Rigid Structure)
p=q z (h)G C p
Floor
R
8
7
6
5
4
3
2
AL floor #
[p/sqft]
-8.68
-8.68
-8.68
-8.68
-8.68
-8.68
-8.68
-8.68
Load
[kip]
-0.26
-0.26
-0.26
-0.26
-0.26
-0.26
-0.26
-0.26
S MS =F a S S
Ss : Short period spectral response acceleration ( S s = 0.35g in Tucson area)
According to page 35 of the handout (and the exception), the building is in
Site Class D.
Table 2.2.2.1 shown below represent values for F a. Using straight-line
interpolation, the value of Fa required for this building can be calculated.
Table 2.2.2.1
2
2
S DS = S MS= 0.532 g=0.355 g
3
3
According to pages 43 to 47 of the handout, the response modification factor,
R, is found to be equal to 4 since an ordinary steel moment frame is sufficient
for a 8 story building.
According to page 33, the building is in Seismic Use Group II and thus has an
Importance Factor, I, of 1.25.
Hence the nominal value for the seismic response coefficient, Cs, is:
S
0.355 g
C s= DS =
=0.111 g
R / I 4 /1.25
S1, the 1-second period spectral response acceleration, is found to be 0.1g in
the Tucson area.
The maximum considered earthquake spectral response acceleration at 1second period, SM1, is determined using the following equation:
S M 1=F v S 1
Table 2.2.2.2 shown below represents values for Fv. Using straight-line
interpolation, the value of Fv for this building can be calculated.
Table 2.2.2.2
Then,
2
2
S D 1= S M1 = 0.24 g=0.16 g
3
3
1.16+ 1.723
=1.44 sec
2
Therefore, the upper limit value for Cs is found using the following equation:
C s=
SD1
0.16 g
=
=0.0347
R
4
T ( ) 1.44(
)
I
1.25
Finally, the lower limit value for C s is found using the following equation:
F x =C vx V
W x hkx
C vx =
wi hik
i=1
Where
W x:
or assigned to level l or x.
hi
And
hx
k=
1 if T 0.5 s
2if T 2.5 s
1 2 if 0.5 s <T <2.5 s
wx
hx
w x hx
C vx
Fx
Pi
[ ]
[kip]
[ft ]
[kipft]
[kip]
[kip]
894.24
104
825074.4
0.247767 62.228
904.32
92
696771.3
904.32
80
567367.5
904.32
68
446797
904.32
56
335860.2
904.32
44
235612.1
904.32
32
147534.2
917.76
20
75031.43
7237.92
Floor
3330048
12.4456
In Figure 2.7 we can see how these forces are acting per level in our typical
frame.
For gravity loads only we can use the Jonh T. DeWolf method.
The method is valid unless the ratio of adjacent spans approaches 2.
Points of contraflexure of beams are assumed to be at locations shown
in Figure 3.1 and the maximum moment will be at the end of beam.
Select beam sizes and determine I/L for each beam.
Thus, following the method above mentioned we get the location of the
points of contraflexure for our typical frame as is show in Figure 3.2.
For this typical frame we have that L1= 30, L2= 30 and L3=30. Then doing
all the calculations showed in Figure 3.1, we got the Figure 3.2 where you can
see the points of contraflexure of the typical frame under analysis.
As we know the locations of the flexural points and the load acting in each
level we can compute the moments acting through each beam, as follows:
-
Span B-C
Span C-D
Span E-F
Span F-G
Span G-H
As our frame is a symmetric one and because the dead load acting from
level 7 to level 2 is the same, the analysis for all other spans of the typical
frame are the same as for the level 7, we can see more clearly this in Figure
3.3, on the next page.
Span B-C
Span C-D
Span E-F
Span F-G
Span G-H
MH= (1.74 ) ( 3 )
Thus, from level 7 to 2 we have the same live load acting and the same
dimensions for the spans, so the calculation should be the same and are
more clearly showed in Figure 3.4.
The horizontal shears on each level are distributed between the columns of
that floor according to assumption (3).
The moment in each column is equal to the column shear multiplied by half
the column height according to assumption (2).
The girder moments are determined by applying moment equilibrium
equation to the joints: by noting that the sum of the girder moments at any
4
5
joint equals the sum of the column moments at that joint. These calculations
are easily made by starting at the upper left joint and working joint by joint
across to the right end.
The shear in each girder is equal to its moment divided by half the girder
length. This is according to assumption (1).
Finally, the column axial forces are determined by summing up the beam
shears and other axial forces at each joint. These calculations again are easily
made by working from left to right and from the top floor down.
Thus, the analysis is limited just to obtain the horizontal shear acting in each floor
and then perform the corresponding static analysis to obtain the shears and
moments acting in the girders and columns, just making equilibrium in each point. A
spreadsheet in Excel 2010 program was developed to compute all this variables
(Attached in a CD at the end of the project). Next the shear by level is obtained and
we show some images about how does it works.
Next the Wind Load Analysis is developed, we should not forget that we start the
analysis from top to bottom and that as we are advancing from level to level the
corresponding horizontal shear H will be bigger, i.e. the level 2 will have the
biggest value of H with respect to the others floors, we can see more in detail this
in Figure 3.9 which show us the moment diagrams for the case of Wind Load.
-
Roof Level
For the roof level we have a lateral force acting PR=3.97k, thus we have that:
PR=H+2H+2H+H
PR=6H
H=PR/6=3.97/6=0.66k
In Figure 3.6 we can see more in detail the corresponding structural analysis for this
level.
-
8th Level
For the 8th level we have a lateral force acting of P8=9.02, thus we have that:
P8=H+2H+2H+H
P8=6H
H=P8/6=9.02/6=1.5k
From level 7th to 3rd the same calculations were performed due that these levels are
completely symmetric and thus a same procedure is followed. Thus we just show
the corresponding horizontal shear for each one of these levels.
-
Level 7th
P7=H+2H+2H+H
H=P7/6=13.89/6=2.315k
P6=6H
H=P6/6=18.55/6=3.09k
Level 6th
P6=H+2H+2H+H
-
P7=6H
Level 5th
P5=H+2H+2H+H
-
P4=6H
H=P4/6=27.12/6=4.52k
P3=6H
H=P3/6=30.93/6=5.155k
P2=6H
H=P2/6=34.3/6=5.72k
Level 3rd
P3=H+2H+2H+H
-
H=P5/6=22.97/6=3.83k
Level 4th
P4=H+2H+2H+H
-
P5=6H
Level 2nd
P2=H+2H+2H+H
Then the moments are calculated by finding the shear force in the column and
beam. The results are shown in the table below:
In Figure 3.8 we can see the structural analysis for this level.
Figure 3.8 Structural Analysis for 2nd Level Wind Load Case
Until this point we have computed the moments in girders and columns for the Wind
Load case, now we show this values schematically in Figure 3.9 in a more
compressively manner.
For the case of seismic load the same procedure that for wind load is used (Portal
Method), thus the shear and moments are computed for each level following the
same steps and the analysis is performed from top to bottom of the typical frame.
-
Roof Level
For the roof level we have a lateral force acting PR=12.45k (Check Table 2.10), thus
we have that:
PR=H+2H+2H+H
-
PR=6H
H=PR/6=12.45/6=2.07k
8th Level
We have that for the 8th level a lateral load P8=22.95k is acting, thus the
corresponding horizontal shear H can be computed as follows:
P8=H+2H+2H+H
P8=6H
H=P8/6=22.95/6=3.83k
The same procedure is developed for levels 7 th to 3rd due to the size of girders and
columns are identical, i.e. our typical frame is completely symmetric.
-
Level 7th
P7=H+2H+2H+H
-
P5=6H
H=P5/6=43.32/6=7.22k
P4=6H
H=P4/6=46.87/6=7.81k
P3=6H
H=P3/6=49.1/6=8.18k
P2=6H
H=P2/6=50.23/6=8.37k
Level 3rd
P3=H+2H+2H+H
-
H=P6/6=38.25/6=6.38k
Level 4th
P4=H+2H+2H+H
-
P6=6H
Level 5th
P5=H+2H+2H+H
-
H=P7/6=31.51/6=5.25k
Level 6th
P6=H+2H+2H+H
-
P7=6H
Level 2nd
P2=H+2H+2H+H
Then the moments are calculated by finding the shear force in the column and
beam. The results are shown in the table below:
Figure 3.12 Structural Analysis for 2nd Level Seismic Load Case
Up to this point of the calculation we have all the moments acting in columns and
girders, thus for a better understanding we show it schematically in Figure 3.13.
4. LOAD COMBINATION
Based on AISC Specification sections B3.3 and B3.4 [2], the required strength (P u,
Mu, Vu, etc. for LRFD) is determined for the appropriate load magnitudes, load
factors and load combinations given in the applicable building code. These are
usually based on ASCE/SEI 7 [3], which may be used when there is no applicable
building code. The common loads found in the building structures are:
1
2
D = Dead Load
L = Live Load due to Occupancy
3
4
5
6
7
For Load and Resistance Factor Design (LRFD), structures, components and
foundations shall be designed so that their design strength equals or exceeds the
effects of the factored loads in the following combinations:
1
2
3
4
5
6
7
1.4D
1.2D
1.2D
1.2D
1.2D
0.9D
0.9D
+
+
+
+
+
+
1.6L +0.5(Lr or S or R)
1.6(Lr or S or R) + (L or 0.5W)
1.0W + L + 0.5(Lr or S or R)
1.0E + L + 0.2S
1.0W
1.0E
There is an exception which can be taken into account: the load factor on L in
combinations 3, 4, and 5 is permitted to equal 0.5 for all occupancies in which L is
less than or equal to 100 psf, with exception of garages or areas occupied as places
of public assembly. For this project this exception will be taken into account due that
this is an office building and the maximum Live Load L is equal to 58 psf, thus the
factor L shall be changed by 0.5L in load combinations 3, 4, and 5.
Due that load combination 6 and 7 never will control in this design can be omitted
and just take into account the effects of load combinations 1, 2, 3, 4 and 5. Also,
due that Tucson, AZ is not a zone very affected by the snow S and the rain R, these
two factors will be omitted for effects of the design. Thus, the load combinations for
the design of this Office Building will be:
1
2
3
4
5
1.4D
1.2D
1.2D
1.2D
1.2D
+
+
+
+
1.6L +0.5Lr
1.6Lr + (0.5L or 0.5W)
1.0W + 0.5L + 0.5Lr
1.0E + 0.5L
EXTERIOR GIRDERS
D
LR
197.7
4
31.6
5
204.1
2
INTERIOR GIRDERS
LR
3.97
12.45
168.0
1
26.8
6
3.97
12.45
147.9
9
12.9
9
35.4
179.1
7
129.9
1
12.9
9
35.4
204.1
2
147.9
9
22.9
1
54.47
179.1
7
129.9
1
22.9
1
54.47
204.1
2
147.9
9
32.4
4
69.77
179.1
7
129.9
1
32.4
4
69.77
204.1
2
147.9
9
41.5
2
81.57
179.1
7
129.9
1
41.5
2
81.57
204.1
2
147.9
9
50.0
9
90.19
179.1
7
129.9
1
50.0
9
90.19
204.1
2
147.9
9
58.0
5
95.97
179.1
7
129.9
1
58.0
5
95.97
204.1
2
147.9
9
88.1
132.8 179.1
2 7
129.9
1
88.1
132.8
2
Figure 4.1 Girder Shear Due to Moment Only: a). Gravity load Case, b). Lateral Load Case
Floor
LR
INTERIOR GIRDERS
LR
4.725
0.76
0.265
0.830
0.265
0.830
3.96
2.87
0.866
2.360
0.866
2.360
3.96
2.87
1.527
3.631
1.527
3.631
3.96
2.87
2.163
4.651
2.163
4.651
3.96
2.87
2.768
5.438
2.768
5.438
3.96
2.87
3.339
6.013
3.339
6.013
3.96
2.87
3.870
6.398
3.870
6.398
3.96
2.87
5.873
8.855
5.873
8.855
EXTERIOR COLUMNS
D
LR
INTERIOR COLUMNS
E
LR
R-8
55.99
8.96
3.97
12.45
29.73
4.79
7.94 24.89
8-7
42.66
30.93
9.02
22.96
24.95
9.04
18.04 45.91
7-6
42.66
30.93
13.89
31.51
24.95
9.04
27.78 63.03
6-5
42.66
30.93
18.55
38.25
24.95
9.04
37.1 76.51
5-4
42.66
30.93
22.97
43.32
24.95
9.04
45.94 86.64
4-3
42.66
30.93
27.12
46.87
24.95
9.04
54.24 93.75
3-2
42.66
30.93
30.93
49.1
24.95
9.04
61.86 98.20
30.93
57.17
83.72
9.04
114.3 167.4
3
4
2-1
42.66
24.95
Figure 4.2 Tributary area for interior and exterior column cases.
In Table 4.4 WT represents the weight supported for each column and is
calculated as follows:
Weight due to Dead Load (D) in Exterior Columns Roof Case (R-8)
(30ft)(15ft)(75psf) + (30ft)(3ft)(10psf)= 34.65 Kip
Weight due to Dead Load (D) in Exterior Columns 8th to 2nd floor case (8-7 to 2-1)
LR
Fl
oo
r
WT
GS
TOTA
L
W
T
G
S
TOT
AL
W
T
G
S
TOT
AL
W
T
GS
TOT
AL
W
T
GS
R8
34.
65
4.7
25
39.3
75
5.
4
0.
76
6.1
6
0.2
65
0.26
5
0.8
30
0.83
87
39.
6
3.9
6
82.9
35
6.1
6
26
.1
2.
87
28.9
7
0.8
66
1.13
1
2.3
60
3.19
76
39.
6
3.9
6
126.
495
6.1
6
26
.1
2.
87
28.9
7
1.5
27
2.65
8
3.6
31
6.82
1
65
39.
6
3.9
6
170.
055
6.1
6
26
.1
2.
87
57.9
4
2.1
63
4.82
1
4.6
51
11.4
72
54
39.
6
3.9
6
213.
615
6.1
6
26
.1
2.
87
86.9
1
2.7
68
7.58
9
5.4
38
16.9
1
43
39.
6
3.9
6
257.
175
6.1
6
26
.1
2.
87
115.
88
3.3
39
10.9
28
6.0
13
22.9
23
32
39.
6
3.9
6
300.
735
6.1
6
26
.1
2.
87
144.
85
3.8
70
14.7
98
6.3
98
29.3
21
TOT
AL
21
39.
6
3.9
6
344.
295
6.1
6
26
.1
2.
87
173.
82
5.8
73
20.6
71
8.8
55
38.1
76
INTERIOR COLUMNS
D
Fl
oo
r
WT
GS
R8
67.
5
87
72
76
72
65
LR
TOTA
L
W
T
G
S
TOT
AL
W
T
G
S
TOT
AL
67.5
10
.8
10.
8
139.
5
10.
8
52
.2
52.
2
211.
5
10.
8
52
.2
104
.4
72
283.
5
10.
8
52
.2
54
72
355.
5
10.
8
52
.2
43
72
427.
5
10.
8
52
.2
32
72
499.
5
10.
8
52
.2
21
72
571.
5
10.
8
52
.2
W
T
GS
TOT
AL
W
T
GS
0.2
65
0.26
5
0.8
30
0.83
0.8
66
1.13
1
2.3
60
3.19
1.5
27
2.65
8
3.6
31
6.82
1
156
.6
2.1
63
4.82
1
4.6
51
11.4
72
208
.8
2.7
68
7.58
9
5.4
38
16.9
1
3.3
39
10.9
28
6.0
13
22.9
23
313
.2
3.8
70
14.7
98
6.3
98
29.3
21
365
.4
5.8
73
20.6
71
8.8
55
38.1
76
261
TOT
AL
1.4D
276.8
1.2D+1.6L+
0.5LR
253.113
1.2D+1.6LR+(0.5L
or 0.5W)
289.913
1.2D+1.0W+0.5L
+0.5LR
257.083
1.2D+1.0E
+0.5L
249.738
36
8
285.7
68
481.728
318.939
331.929
354.339
285.7
68
481.728
318.939
341.849
373.409
285.7
68
481.728
318.939
351.379
388.709
285.7
68
481.728
318.939
360.459
400.509
285.7
68
481.728
318.939
369.029
409.129
285.7
68
481.728
318.939
376.989
414.909
285.7
68
481.728
318.939
407.039
451.759
INTERIOR GIRDERS
Flo
or
1.4D
1.2D+1.6L+
0.5LR
1.2D+1.6LR+(0.5L
or 0.5W)
1.2D+1.0W+0.5L
+0.5LR
1.2D+1.0E
+0.5L
215.0
42
246.573
219.012
214.062
235.214
422.8
6
279.959
292.949
315.359
250.838
422.8
6
279.959
302.869
334.429
250.838
422.8
6
279.959
312.399
349.729
250.838
422.8
6
279.959
321.479
361.529
250.838
422.8
6
279.959
330.049
370.149
250.838
422.8
6
279.959
338.009
375.929
250.838
422.8
6
279.959
368.059
412.779
250.838
1.4D
1.2D+1.6L+
0.5LR
R-8
78.38
6
78.02
8-7
59.72
4
7-6
1.2D+1.6LR+(0.5L
or 0.5W)
1.2D+1.0W+0.5L
+0.5LR
1.2D+1.0E+
0.5L
81.524
75.638
79.638
100.68
66.657
75.677
89.617
59.72
4
100.68
66.657
80.547
98.167
6-5
59.72
4
100.68
66.657
85.207
104.907
5-4
59.72
4
100.68
66.657
89.627
109.977
4-3
59.72
4
100.68
66.657
93.777
113.527
3-2
59.72
4
100.68
66.657
97.587
115.757
2-1
59.72
4
100.68
79.777
123.827
150.377
1.2D+1.0W+0.5L
+0.5LR
1.2D+1.0E+
0.5L
INTERIOR COLUMNS
Flo
or
1.4D
1.2D+1.6L+
0.5LR
1.2D+1.6LR+(0.5L
or 0.5W)
R-8
41.62
2
38.071
47.31
46.011
60.566
8-7
34.93
44.404
38.96
52.5
80.37
7-6
34.93
44.404
43.83
62.24
97.49
6-5
34.93
44.404
48.49
71.56
110.97
5-4
34.93
44.404
52.91
80.4
121.1
4-3
34.93
44.404
57.06
88.7
128.21
3-2
34.93
44.404
60.87
96.32
132.66
2-1
34.93
44.404
87.105
148.79
201.9
1.4D
1.2D+1.6L+
0.5LR
1.2D+1.6LR+(0.5L
or 0.5W)
1.2D+1.0W+0.5L
+0.5LR
1.2D+1.0E
+0.5L
R-8
55.12
5
50.33
57.2385
50.648
48.08
8-7
116.1
09
148.954
123.863
118.4442
117.197
7-6
177.0
93
201.226
176.135
172.5486
173.1
6-5
238.0
77
299.85
242.892
241.9012
244.508
5-4
299.0
61
398.474
309.649
311.9798
316.703
4-3
360.0
45
497.098
376.406
382.7436
389.473
3-2
421.0
29
595.722
443.163
454.1446
462.628
2-1
482.0
13
694.346
509.92
527.9492
538.24
INTERIOR COLUMNS
Flo
or
1.4D
1.2D+1.6L+
0.5LR
1.2D+1.6LR+(0.5L
or 0.5W)
1.2D+1.0W+0.5L
+0.5LR
1.2D+1.0E
+0.5L
R-8
94.5
86.4
98.4125
86.718
81.83
8-7
195.3
256.32
210.78
200.2572
196.69
7-6
296.1
426.24
323.28
314.5896
312.821
6-5
396.9
596.16
435.78
429.6852
429.972
5-4
497.7
766.08
548.28
545.5068
547.91
4-3
598.5
936
660.78
662.0136
666.423
3-2
699.3
1105.92
773.28
779.1576
785.321
2-1
800.1
1275.84
885.78
898.7052
906.676
5. - DESIGN OF MEMBERS
The design of this building is composed basically for three kind of structural (W
shapes) members: Girders, Columns and Beams. Girders are designed taking into
account the critical bending moment acting on them, for the case of Columns
design we must consider the critical axial load and bending moment, and when the
Beam design is performed the maximum moment acting along the beam due to
gravity load will control the design. Also it is important to point out that for Girders
and Beams the Shear and Deflection must be checked. All the above mentioned is
clearly explained in the next sections.
same thing happens for the case of interior girders. This can be checked next in
Table 4.5.
Floor
R
8
7
6
5
4
3
2
Floor
R
8
7
6
5
4
3
2
Floor
R
8
7
6
57.2385
148.954
201.226
299.85
398.474
497.098
595.722
694.346
Interior Column Axial
Force
98.4125
256.32
426.24
596.16
766.08
936
1105.92
1275.84
Exterior Column
Moment
81.524
100.68
100.68
104.907
5
4
3
2
Floor
R
8
7
6
5
4
3
2
Floor
R
109.977
113.527
115.757
150.377
Interior Column
Moment
60.566
80.37
97.49
110.97
121.1
128.21
132.66
201.9
Exterior Girder
Moment
289.913
481.728
481.728
481.728
481.728
481.728
481.728
481.728
Floor
Interior Girder
Moment
8
7
6
5
4
3
R
8
7
6
5
4
246.573
422.86
422.86
422.86
422.86
422.86
3
2
422.86
422.86
Lb
L p , for this case Cb=1.0 and we are using for the W sections Steel Grade 50, thus
we can easily get the ideal W section for the girder under consideration using Table
3-10 (Page 3-99) Available Moment vs. Unbraced Length, of the Steel Construction
Manual (SCM) [2]. We just need to look for a section which
b M n Mr
entering
with Lb=0 .
Once the adequate W section is chosen, the section must be checked against Shear,
this is performed satisfying the next equation:
v0.6F yA wC v Vr
Where v = Shear Resistance Factor = 1.00; Fy = Ultimate Strength of the Member;
Aw = Area of the web; Cv = Web Shear Coefficient = 1 (for rolled I-shaped members
with h/tw 2.24
E/ Fy=53.95
form, and must be satisfied for all the section beams chosen.
0.6F yA w Vr
The last parameter that must be checked before to consider a W section completely
appropriate for the design is Deflection. The deflection of the girder should be less
than or equal to the allowable deflection, the deflection must be checked out for a
simply supported beam and for a double fixed beam cases, i.e. the both of the
following equations must be satisfied.
4
5W L L
Span
a=
384 EI
360
W L L4
Span
For a doubly beam lower bound ( max ) =
a=
384 EI
360
Where
( max ) = Maximum deflection under live load (not from load combination);
Selection of the appropriate W section for the 2 nd to 8th Level Exterior Girder Cases:
We have acting a bending moment
the SCM with a value of
122). For this section
Lb=0
M r=481.73 kft
b M n =503 kft
thus
b M n Mr
is correctly satisfied.
Now checking Shear for the W24x55 section, we have that nominal shear strength
is:
23.6
0.395
v V n=0.60F yA w = ( 0.60 ) 50
kip
W T =W D +W L =
k
(4.14 )( 30 ft )
W L
ft
V r= T =
=62.1kip
2
2
v V n V r
is clearly
satisfied.
Now checking Deflection for the W24x55 section, we have that the distributed live
load acting in the beam is
W L=
is
a=
Span 30 ft
=
=0.083 ft=1 , thus checking simply supported beam deflection,
360 360
we have:
5 W L L4 5(1.74 12)(3012)4
( max )=
=
=0.82
384 EI
384290001330
( max ) a is satisfied,
Then
( max )=
W L L4 (1.74 12)(3012) 4
=
=0.16
384 EI 384290001330
Then
( max ) a
Lb=0
M r=289.91 k ft
b M n =358 kft
thus
b M n Mr
is correctly satisfied.
Now checking Shear for the W21x44 section, we have that nominal shear strength
is:
20.7
0.35
v V n=0.60F yA w = ( 0.60 ) 50
kip
W T =W D +W L =
W L
V r= T =
2
( 2.61
k
)(30 ft )
ft
=39.15 kip
2
v V n V r
is clearly
satisfied.
Now checking Deflection for the W21x44 section, we have that the distributed live
load acting in the beam is
W L=
is
a=
Span 30 ft
=
=0.083 ft=1 , thus checking simply supported beam deflection,
360 360
we have:
5 W L L4 5(0.36 12)(3012)4
( max )=
=
=0.26
384 EI
38429000843
( max ) a is satisfied,
Then
( max )=
W L L4 (0.36 12)(3012) 4
=
=0.05 Then
384 EI
38429000843
( max ) a
Lb=0
M r=422.86 kft
b M n Mr
is correctly satisfied.
Now checking Shear for the W21x55 section, we have that nominal shear strength
is:
20.8
0.375
v V n=0.60F yA w = ( 0.60 ) 50
kip
W T =W D +W L =
k
(4.14 )( 30 ft )
W L
ft
V r= T =
=62.1kip
2
2
v V n V r
is clearly
satisfied.
Now checking Deflection for the W21x55 section, we have that the distributed live
load acting in the beam is
W L=
is
a=
Span 30 ft
=
=0.083 ft=1 , thus checking simply supported beam deflection,
360 360
we have:
5 W L L4 5(1.74 12)(3012)4
( max )=
=
=0.96
384 EI
384290001140
( max ) a is satisfied,
Then
( max )=
W L L4 (1.74 12)(3012) 4
=
=0.19 Then
384 EI 384290001140
( max ) a
Lb=0
M r=246.57 kft
b M n =358 kft
thus
b M n Mr
is correctly satisfied.
Now checking Shear for the W21x44 section, we have that nominal shear strength
is:
20.7
0.35
v V n=0.60F yA w = ( 0.60 ) 50
kip
W T =W D +W L =
W L
V r= T =
2
( 2.61
k
)(30 ft )
ft
=39.15 kip
2
v V n V r
is clearly
satisfied.
Now checking Deflection for the W21x44 section, we have that the distributed live
load acting in the beam is
W L=
a=
is
Span 30 ft
=
=0.083 ft=1 , thus checking simply supported beam deflection,
360 360
we have:
5 W L L4 5(0.36 12)(3012)4
( max )=
=
=0.26
384 EI
38429000843
( max ) a is satisfied,
Then
( max )=
W L L4 (0.36 12)(3012) 4
=
=0.05 Then
384 EI
38429000843
( max ) a
K x =1.2(assumed)
K x Lx =1.220=24 ft
K y =0.8 ;
;
;
Lx =20 ft ;
L y =20 ft
Lb=20 ft
K y L y =0.820=16 ft
M rx=150.377 kft
and
Pr=694.346 k
M ltx
B 1=1.0
and
but for this case as we dont have side sway in the y direction
and
Pr=694.346 k
As we know that the design of columns is restrained to W14 sections and for this
case
obtain a value
we
Now using the interaction equations for columns subjected to axial and flexure
forces, we have that:
p P r +b x M r 1.0
It is important to note that for all the design of members of the typical frame always
the condition
pPr 0.2
Thus entering to Table 6-1 of the Steel Construction Manual (SCM) with a value of
K y L y =0.820=16 ft
Check W14x90 -;
K y L y =16 ft ;
Lb=20 ft
Kx
value every
time the W section is changed. In the SCM is stated that for moment resisting
frames we can obtain the K value using the alignment chart, but before use it we
also need the value of the parameter G for each union in the column, thus the value
of G can be computed as follows:
Ic
G=
joint,
Lc
Lg
Lg
Lc=
Where
Ic=
Lg=
Ig=
Moment
Longitude of all
girders which intercept at the joint, in Figure 5.5 we can see this more clearly.
Lc 1=1 2 ft=1 44 ,
Lc 2=20 ft=240 ,
Ic 1=Ic 2=Ic ,
Ic
Ic=1240
K x Lx =1. 7520=35 ft ;
K y L y =16 ft ;
K x Lx
=21.08
rx /ry
p=1. 18 x 103
(w.r.t.
interaction equation:
K x Lx ),
K x =1.75
Lb=20 ft , KxLx/KyLy=2.19 therfore x is
b x =1.65 x 103
(w.r.t.
Lb ), checking with
Check W14x99
Ic=1110 4
K x Lx =1.720=34 ft ;
K y L y =16 ft ;
K x =1.7
Lb=20 ft , KxLx/KyLy=2.19 therfore x is
K x Lx
=20.48
rx /ry
K x Lx ),
b x =1.49 x 103
Lb ), checking with
(w.r.t.
interaction equation:
B 2 M ltx=0
B 1 as follows:
Cmx =0.60.4 (
M1
)
M 2 , and we know that the
Pex
Pex=
B1
318 00 x 10 4
=3833.91k , then putting all this values in the equation to obtain
(1. 72 012)2
B 1=
C mx
0.2
=
=0.2 4
Pr
694.346
1
1
3833.91
P ex
But
B 1 1.0
OK
K x =1.2(assumed)
K y =0.8 ;
K x Lx =1.220=24 ft
Lx =20 ft ;
L y =20 ft
Lb=20 ft
K y L y =0.820=16 ft
M rx=201.9 kft
and
Pr=1275.84 k
and
but for this case as we dont have side sway in the y axis so
B 1=1.0
M r=( 1.0 )( 201.9 )=201.9 kft
and
Pr=1275.84 k
As we know that the design of columns is restrained to W14 sections and for this
case
obtain a value
we
Now using the interaction equations for columns subjected to axial and flexure
forces, we have that:
Thus entering to Table 6-1 of the Steel Construction Manual (SCM) with a value of
K y L y =0.820=16 ft
Kx
value every
time the W section is changed. In the SCM is stated that for moment resisting
frames we can obtain the K value using the alignment chart, but before use it we
also need the value of the parameter G for each union in the column, thus the value
of G can be computed as follows:
Ic
G=
joint,
Lc
Lg
Lg
Lc=
Where
Ic=
Lg=
Ig=
Moment
Longitude of all
girders which intercept at the joint, in Figure 5.5 we can see this more clearly.
Lc 1=12 ft =144 ,
Lc 2=20 ft=240 ,
Ic 1=Ic 2=Ic ,
Ic 1 Ic 2
1
1
1
1
+
Ic (
+
)
(
+
)
Lc 1 Lc 2
Lc 1 Lc 2
144 240
G A=
=
=Ic
=( 1.75 x 103) Ic
Ig 1 Ig 2
Ig 1 Ig 2
1140 1140
+
+
+
Lg1 Lg2
Lg 1 Lg 2
360 360
Where
Ic
Ic=1710 4
K x Lx =1.5420=30.8 ft ;
critical since rx/ry=1.59.
K y L y =16 ft ;
K x =1.54
Lb=20 ft , KxLx/KyLy=1.925 therefore x is
K x Lx
=19.37
rx /ry
b x =0.956 x 10
(w.r.t.
Lb ), checking with
interaction equation:
not good!
Check W14x159
Ic=1900 4
K x Lx =1.5 620=31.2 ft ;
critical since rx/ry=1.60.
p=0.611 x 103
K y L y =16 ft ;
K x =1.56
Lb=20 ft , KxLx/KyLy=1.95 therefore x is
K x Lx
=19.5
rx /ry
(w.r.t. ( KL ) y ),
b x =0.956 x 10
(w.r.t.
Lb ), checking with
interaction equation:
B 2 M ltx=0
B 1 as follows:
Cmx =0.60.4 (
M1
)
M 2 , and we know that the
Cmx =0.60.4 ( 1 )=0.2 , we
Pex
Pex=
544 00 x 104
=3880.85 k , then putting all this values in the equation to
2
(1.562012)
obtain
B 1=
B1
C mx
0.2
=
=0.2 9
Pr
1275.84
1
1
3880.85
P ex
But
B 1 1.0
good!
K x =2.0 (assumed);
K x Lx =2 .012=24 ft
K y =1.0 ;
;
Lx =12 ft ;
K y L y =1.012=12 ft
L y =12 ft
Lb=12 ft
From section 5.1 the critical values for axial force and bending moment in the
column are the following.
M rx=109.977 kft
and
Pr=398.474 k
M ltx
but for this case as we dont have side sway in the column,
and
B 1=1.0
M r=( 1.0 )( 109.977 ) =109.977 kft
and
Pr=398.474 k
As we know that the design of columns is restrained to W14 sections and for this
case
obtain a value
we
Now using the interaction equations for columns subjected to axial and flexure
forces, we have that:
K y L y =12 ft ;
Lb=12 ft
Kx
value every
time the W section is changed. In the SCM is stated that for moment resisting
frames we can obtain the K value using the alignment chart, but before use it we
also need the value of the parameter G for each union in the column, thus the value
of G can be computed as follows:
Ic
G=
joint,
Lc
Lg
Lg
Lc=
Where
Ic=
Lg=
Ig=
Moment
Longitude of all
girders which intercept at the joint, in Figure 5.5 we can see this more clearly.
Lc 1=12 ft =144 ,
Lc 2=12 ft=144 ,
Ic 1=Ic 2=Ic ,
Ic
Ic=640
K x Lx =2 .2512=27 ft ;
K y L y =12 ft ;
GB =10.0
K x =2.2
Lb=12 ft , KxLx/KyLy=2.25 therefore y is
p=1.60 x 10
(w.r.t.
K y L y ),
b x =2.49 x 103
(w.r.t.
Lb ), checking with
interaction equation:
good!
B 2 M ltx=0
B 1 as follows:
Cmx =0.60.4 (
M1
)
M 2 , and we know that the
Pex
Pex=
18300 x 10
=10502.75 k , then putting all this values in the equation to obtain
2
(1.01112)
B1
B 1=
C mx
0.2
=
=0.21
Pr
398.474
1
1
10502.75 k
P ex
But
B 1 1.0
good!
K x =1.0 ;
K y =1.0 ;
K x Lx =1.012=12 ft
Lx =12 ft ;
L y =12 ft
K y L y =1.012=12 ft
Lb=12 ft
M rx=121.1 k ft
and
Pr=766.08 k
M ltx
but for this case as we dont have side sway in the column,
and
B 1=1.0
M r=( 1.0 )( 121.1 )=121.1 k ft
and
Pr=766.08 k
As we know that the design of columns is restrained to W14 sections and for this
case
obtain a value
we
Now using the interaction equations for columns subjected to axial and flexure
forces, we have that:
Thus entering to Table 6-1 of the Steel Construction Manual (SCM) with a value of
K y L y =K x Lx =1.012=12 ft
Check W14x90 -
for
K y L y =12 ft ;
Kx
value every
time the W section is changed. In the SCM is stated that for moment resisting
frames we can obtain the K value using the alignment chart, but before use it we
also need the value of the parameter G for each union in the column, thus the value
of G can be computed as follows:
Ic
G=
joint,
Lc
Lg
Lg
Lc=
Where
Ic=
Ig=
Moment
Lg=
Longitude of all
girders which intercept at the joint, in Figure 5.5 we can see this more clearly.
Lc 1=12 ft =144 ,
Lc 2=12 ft=144 ,
Ic1=Ic 2=Ic ,
Ic
Ic=999 4
K x Lx =2 .1812=2 6.16 ft ;
critical since rx/ry=1.66.
K y L y =12 ft ;
K x Lx
=15.76
rx /ry
GB =10.0
K x =2.18
Lb=12 ft , KxLx/KyLy=2.18 therefore x is
p=1.01 x 103
(w.r.t.
K y L y ),
b x =1.55 x 10
(w.r.t.
Lb ), checking with
interaction equation:
good!
B 2 M ltx=0
B 1 as follows:
Cmx =0.60.4 (
M1
)
M 2 , and we know that the
Pex
Pex =
18300 x 104
=10502.75 k , then putting all this values in the equation to
(2.181212)2
obtain
B 1=
B1
C mx
0.2
=
=0.21
Pr
766.08
1
1
10502.75 k
P ex
But
B 1 1.0
good!
K x =1.0 ;
K y =1.0 ;
K x Lx =1.012=12 ft
Lx =12 ft ;
L y =12 ft
Lb=12 ft
K y L y =1.012=12 ft
M rx=100.68 k ft
and
Pr=201.226 k
M ltx
but for this case as we dont have side sway in the column,
and
B 1=1.0
M r=( 1.0 )( 100.68 k )=100.68 k kft
and
Pr=201.226 k
As we know that the design of columns is restrained to W14 sections and for this
case
obtain a value
bav =1.47 x 10
we
Now using the interaction equations for columns subjected to axial and flexure
forces, we have that:
K y L y =K x Lx =1.012=12 ft
Check W14x38 -
for
K y L y =12 ft ;
Kx
value every
time the W section is changed. In the SCM is stated that for moment resisting
frames we can obtain the K value using the alignment chart, but before use it we
also need the value of the parameter G for each union in the column, thus the value
of G can be computed as follows:
Ic
G=
Lc
Lg
Lg
joint,
Lc=
Ic=
Where
Lg=
Ig=
Moment
Longitude of all
girders which intercept at the joint, in Figure 5.5 we can see this more clearly.
Lc 1=12 ft =144 ,
Lc 2=12 ft=144 ,
4
Ig 1=W 21 x 44=843
Ic1=Ic 2=Ic ,
Ic 1 Ic 2
1
1
1
1
+
Ic (
+
)
(
+
)
Lc 1 Lc 2
Lc 1 Lc 2
144 144
G A=
=
=Ic
=( 5.93 x 103 ) Ic
Ig 1
Ig 1
843
Lg 1
Lg1
360
Where
Ic
Ic=385 4
K x =2.18
K x Lx =2.1812=26.16 ft ;
GB =10.0
K y L y =12 ft ;
p=3.73 x 10
(w.r.t.
K y L y ),
b x =5.0 x 103
Lb ), checking with
(w.r.t.
interaction equation:
Ic=428
K y L y =12 ft ;
Lb=12 ft
GB =10.0
K x =2.2
K x Lx =2. 212=26.4 ft ;
Not good!
K y L y =12 ft ;
K y L y ),
Lb ), checking with
interaction equation:
good!
B 2 M ltx=0
B 1 as follows:
Cmx =0.60.4 (
M1
)
M 2 , and we know that the
Pex
Pex=
12300 x 10
=5931.71k , then putting all this values in the equation to obtain
2
(2.21212)
B1
B 1=
C mx
0.2
=
=0.21
Pr
201.226
1
1
5931.71k
P ex
But
B 1 1.0
good!
K x =2.0 assumed ;
K y =1.0 ;
K x Lx =2 .012=24 ft
Lx =12 ft ;
L y =12 ft
Lb=12 ft
K y L y =1.012=12 ft
M rx=97.49 kft
and
Pr=426.24 k
M ltx
and
but for this case as we dont have side sway in the column,
B 1=1.0
M r=( 1.0 )( 97.49 ) =97.49 kft
and
Pr=426.24 k
As we know that the design of columns is restrained to W14 sections and for this
case
obtain a value
we
Now using the interaction equations for columns subjected to axial and flexure
forces, we have that:
preq
Thus entering to Table 6-1 of the Steel Construction Manual (SCM) with a value of
K y L y =K x Lx =1.012=12 ft
Check W14x61-
for
K y L y =12 ft ;
Kx
value every
time the W section is changed. In the SCM is stated that for moment resisting
frames we can obtain the K value using the alignment chart, but before use it we
also need the value of the parameter G for each union in the column, thus the value
of G can be computed as follows:
Ic
G=
joint,
Lc
Lg
Lg
Lc=
Where
Ic=
Lg=
Ig=
Moment
Longitude of all
girders which intercept at the joint, in Figure 5.5 we can see this more clearly.
Lc 1=12 ft =144 ,
Lc 2=12 ft=144 ,
Ic 1=Ic 2=Ic ,
Ic
Ic=640 4
K x =2.1
K x Lx =2.112=25.2 ft ;
GB =10.0
K y L y =12 ft ;
K y L y ),
b x =2.49 x 10
Lb ), checking with
(w.r.t.
interaction equation:
good!
B 2 M ltx=0
B 1 as follows:
Cmx =0.60.4 (
M1
)
M 2 , and we know that the
Pex
Pex=
18300 x 10 4
=10502.75 k , then putting all this values in the equation to
(2.11212)2
obtain
B 1=
B1
C mx
0.2
=
=0.21
Pr
426.24
1
1
10502.75 k
P ex
But
B 1 1.0
good!
For the building under consideration we have two cases of beams, the first one
when the member is considered an exterior beam and the second one when the
member is considered an interior beam, this is shown in Figure 5.11. Also in this
Figure we can see the tributary area for each beam in which the load will be acting,
these areas are equal to (10ft) (30ft) = 300 ft2 and (5ft) (30ft) = 150 ft2 for the
exterior and interior beams respectively.
It is important to note that the beams are designed just for Dead and Live Load and
no load combinations are required for this design. Also, since we have same Dead
and Live load for the 2nd to 7th Levels but different for the Roof Level, and each level
present two kinds of beams (exterior and interior), the total number of beam
designs is four for all the building.
The selection of the adequate W section will be restrained to W16 or W18 sizes
depending on the availability of the section to resist the moment required, also this
restriction is made because the beams must be connected with the girders and thus
Beams size should be smaller than the Girders size.
Once the adequate W section is chosen, the section must be checked against Shear
and Deflection in the same way that for girders.
Selection of the appropriate W section for the Exterior Beam Roof Level Case:
The distributed load acting in this beam is
W T =W D +W L =
Lb=0
b M n =165.75 kft
then entering to
thus
b M n Mr
is
correctly satisfied.
Now checking Shear for the W16x26 section, we have that nominal shear strength
is:
For this W section h/tw=56.8 then the realtion h/tw 2.24
satisfied and we need another procedure to compute
Cv
E/ Fy=53.95
is not
1.10
k v =5
and then
( 5 ) ( 29000 )
=59.24 then we have a value for C v =1.0 and
50
v =0.9
thus
15.7
0.250
kip
V r=
WT L
=
2
satisfied.
(0.435
k
)(30 ft )
ft
=6.525 kip
2
v V n V r
is clearly
Now checking Deflection for the W16x26 section, we have that the distributed live
load acting in the beam is
is
a=
W L=
Span 30 ft
=
=0.083 ft=1 , thus checking simply supported beam deflection,
360 360
we have:
4
5 W L L 5(0.06 12)(3012)4
( max )=
=
=0.13
384 EI
38429000301
Then
( max ) a is satisfied,
( max )=
W L L4 (0.06 12)(3012) 4
=
=0.03 Then
384 EI
38429000301
( max ) a is completely
satisfied
USE W16x26 GRADE 50 STEEL
Selection of the appropriate W section for the Interior Beam Roof Level Case:
The distributed load acting in this beam is
W T =W D +W L =
W T L2 (0.87)(30 2)
=
=97.88 k ft
8
8
M max=M r =97.88 k ft
Lb=0
b M n =165.75 kft
thus entering to
thus
b M n Mr
is
correctly satisfied.
Now checking Shear for the W16x26 section, we have that nominal shear strength
is:
15.7
0.250
kip
V r=
WT L
=
2
( 0.87
k
)(30 ft )
ft
=13.05 kip
2
v V n V r
is clearly
satisfied.
Now checking Deflection for the W16x26 section, we have that the distributed live
load acting in the beam is
is
a=
W L=
Span 30 ft
=
=0.083 ft=1 , thus checking simply supported beam deflection,
360 360
we have:
4
( max )=
5 W L L 5(0.12 12)(3012)4
=
=0.25 Then
384 EI
38429000301
( max ) a is satisfied,
W L L4 (0.12 12)(3012)4
( max )=
=
=0.05
384 EI
38429000301
Then
( max ) a is completely
satisfied
USE W16x26 GRADE 50 STEEL
Selection of the appropriate W section for the Exterior Beam 2 nd to 8th Level Case:
The distributed load acting in this beam is
W T =W D +W L =
W T L2 (0.69)(302 )
M max=
=
=77.625 kft
8
8
Lb=0
thus entering to
b M n =165.75 kft
thus
b M n Mr
is
correctly satisfied.
Now checking Shear for the W16x26 section, we have that nominal shear strength
is:
15.7
0.250
kip
W L
V r= T =
2
k
(0.69 )(30 ft )
ft
=10.35 kip
2
v V n V r
is clearly
satisfied.
Now checking Deflection for the W16x26 section, we have that the distributed live
load acting in the beam is
Span
W L=
30 ft
is a= 360 = 360 =0.083 ft=1 , thus checking simply supported beam deflection,
we have:
5 W L L4 5(0.29 12)(3012) 4
( max )=
=
=0.61
384 EI
38429000301
Then
( max ) a is satisfied,
( max )=
W L L4 (0.29 12)(3012)4
=
=0.12
384 EI
38429000301
Then
( max ) a is completely
satisfied.
USE W16x26 GRADE 50 STEEL
Selection of the appropriate W section for the Interior Beam 2 nd to 8th Level Case:
The distributed load acting in this beam is
W T =W D +W L =
M max=
W T L2 (1.38)(302 )
=
=155.25 kft
8
8
M max=M r =155.25 kft
Lb=0
thus entering to
b M n =165.75 kft
thus
b M n Mr
is
correctly satisfied.
Now checking Shear for the W16x26 section, we have that nominal shear strength
is:
15.7
0.250
kip
W L
V r= T =
2
k
(0.69 )(30 ft )
ft
=10.35 kip
2
v V n V r
is clearly
satisfied.
Now checking Deflection for the W16x26 section, we have that the distributed live
load acting in the beam is
Span
W L=
30 ft
is a= 360 = 360 =0.083 ft=1 , thus checking simply supported beam deflection,
we have:
5 W L L4 5(0.29 12)(3012) 4
( max )=
=
=0.61
384 EI
38429000301
Then
( max ) a is satisfied,
W L L4 (0.29 12)(3012)4
( max )=
=
=0.12
384 EI
38429000301
Then
( max ) a is completely
satisfied.
USE W16x26 GRADE 50 STEEL
For the ease of the above calculation needed to obtain the beam W sections, are
introduced Figures 5.12 and 5.23. In Figure 5.12 we can appreciate the beam
member W sections for the case of the Roof level and Figure 5.13 shows the beam
members W sections for the 8th to 2nd level cases.
Figure 5.12 Interior and Exterior Beam W16 sections for the Roof Level Case
Figure 5.13 Interior and Exterior Beam W16 sections for the 2nd to 8th Cases
The exterior girders from the 2nd floor till the roof are W24x55 sections
and the interior girders from the 2nd floor till the roof are W24x55 sections.
The exterior girders on the roof are W21x44 sections and the interior
girder on the roof is a W21x44 sections.
The length of all exterior girders is 30 ft and the length of all interior
girders is 30 ft.
The total weight of all the girders in the typical interior frame is:
{(2 girders/floor)*(30 ft/girder)*(55 lb/ft) +(1girder/floor)*(30ft/girder)*(55lb/ft)}*7
+ (2girders/floor)*(30 ft/girder)*(44 lb/ft) + (1 girder/floor)*(30ft/girder)*(44lb/ft)
= 38610 lb
( 40 beam ) 30
ft
lb
26 =31200lb
beam
ft
)( )
( 40 beam ) 30
ft
lb
26 =31200lb
beam
ft
)( )
Finally the total weight of all the beams in the building can be computed as follows:
6. STRUCTURAL DETAILS
In this section the structural details are shown with the help of figures, the
calculation of such details is beyond the scope of this final project but in general
these are the minimal details required in the structural engineering professional
field. These details are: Connections, Column Splice, Column base plate, Interior
shear wall and Composite slab.
6.1. Connections
For the case of connection, there are three types for this building: Girder-Column
Connection (Moment Connection), Beam-Girder Connection (Shear Connection) and
Beam-Column Connection (Shear Connection).
In Figure 5.14 we can appreciate how the girders must be connected to the columns
to form a moment connection, this is necessary because our typical frame is a Steel
Moment Resisting Frame (SMRF), thus the basic condition is that the connections for
such a frame must be moment connections.
Moment connections are designed to transfer bending moments, shear forces and
sometimes normal forces. The design strength and stiffness of a moment
connection are defined in relation to the strength and stiffness of the connected
members. The design strength of a moment connection may be full- strength or
partial-strength. Similarly the stiffness of a moment connection can be rigid or semirigid compared to the stiffness of the connected member. For this project the
connections are considered designed with full strength requirement and with rigid
stiffness. As is shown in Figure 5.14 five bolts are used to connect the flanges of the
girders with the plates fixed to the flanges of columns, six bolts for the web plate
and four bolts in each connection of the angles with columns.
For the case of beam-column connections the same procedure that for the beamgirder connection is followed, there are just two differences: The first one is that for
beam-column connection the shear plates must be reinforced with six bolts instead
of three and the second difference is that beams are connected to the flange of the
column instead to the web. We can clearly see this in Figure 5.16.