BROAD CENTRAL AIR CONDITIONING (ABSORPTION LiBr+H2O)

BROAD X NON-ELECTRIC CHILLER


MODEL SELECTION & DESIGN MANUAL

Function
! Cooling, heating, hot water

(dedicatedly or simultaneously)

Application
Provide chilled/heating water for
large-scale buildings
!
Produce chilled water over 5C
and heating water below 95C
!

Cooling capacity
! 23-11,630kW(6.6-3,307Rt)

Energy sources

!Natural gas, town gas, biogas,


diesel, recycled oil
!
gas/oil dual fuel, gas & waste heat
hybrid (multiple energy)
!
waste heat from power generation
industrial waste streams (steam,
hot water, exhaust, etc)

2011.06. SI

CONTENTS
Non-electric Chiller

The Absorption Principle

Direct-fired Absorption Chiller Performance Data

Packaged Direct-fired Absorption Chiller Performance Data

HTG(high temp generator)Enlarged Model!Performance Data

Performance Curves

Model Selection & Ordering

Supply List

Steam Chiller Performance Data

Packaged Steam Chiller Performance Data

Packaged Hot W/Exhaust Chiller Performance Data

11

Packaged Single-stage Steam/Hot W/Exhaust Chiller Performance Data

12

Packaged Multi-energy Chiller Performance Data

13

Model Selection Curves

15

Micro Non-electric Chiller

17

Performance Data

18

Model Selection & Ordering

19

Performance Curves

19

Design & Construction Tips

20

Dimensions

20

P&I Diagram

33

Scope of Supply/Work

39

Machine Room Construction Tips

40

Piping System

41

Control System

42

Exterior Wiring Diagram

43

List of Control System Installation

44

Transportation Tips

45

Lifting & Leveling Tips

46

Comparison

BZ200

47

Energy saving comparison

47

General Comparison

48


Non-electric
Chiller (chiller+pumpset)

hot water!!91071

1. high temperature
generator (HTG)

2. low temperature
generator (LTG)
3. condenser
4. absorber
5. evaporator
6. high temperature
heat exchanger
7. low temperature
heat exchanger





chiller

hot water pump

heating water!76066

heating water pump

chilled water!8025
hot water!91071

hot water pump

chilled water pump

cooling water pump

auto dosing

pumpset

water softener

cooling
tower

1. high temperature
generator (HTG)

;HISL


;HISL

JVUJLU[YH[LKZVS\[PVU
heat energy

KPS\[LKZVS\[PVU
YLMYPNLYHU[^H[LY
YLMYPNLYHU[Z[LHT
JOPSSLK^H[LY
JVVSPUN^H[LY
OV[^H[LY
MSV^TL[LY

heat energy

ZVS\[PVU
]HWVY
JVUKLUZLK^H[LY
OLH[PUN^H[LY
OV[^H[LY
UVVWLYH[PVU
MSV^TL[LY

The cooling principle

The heating principle

The input heat energy heats LiBr solution to 140C and generate vapor, which is then condensed into water by
cooling water. When the refrigerant water enters evaporator (in high vacuum condition), its temperature goes down
immediately to 5C. And it is sprayed over the copper tubes, and chilled water from 14C drop down 7C to make
cooling. The water absorbs heat from air conditioning system and evaporates, then is absorbed by concentrated
LiBr solution from the generators. The cooling water takes away the heat and rejects it into the air. Diluted solution is
pumped into HTG and LTG separately to be heated to begin the process all over again.

The input heat energy heats the LiBr solution. The vapor produced by the solution heats the heating water or hot
water in tubes, while condensate returns to the solution to be heated and the cycle repeats. As "separate heating" is
adopted, the heating cycle becomes very simple, just like a vacuum boiler. Therefore, the life span of the chiller can
be doubled.

Notes: Lithium Bromide is high water absorbent salt nontoxic and harmless.

A separate heat exchanger can provide dedicated hot water while cooling or heating operation is stopped.
So, only BROAD has the unique technology in the world that can realize "three functions in one unit".

Direct-fired Absorption Chiller (P-DFA) Performance Data

General Conditions:

Fuel: natural gas, biogas, diesel or gas/oil dual fuel


Mode

BZ

Cooling capacity

kW

20

Heating capacity

kW

Hot water capacityR>

30

50

75

100

125

150

200

233 349 582 872 1163 1454 1745 2326

104 kcal/h 20

30

50

75

100

125

150

200

250

300

400

500

600

800

1000

2908

3489

4652

5815

6978

9304

11630

250

300

400

500

600

800

1000

179 269 449 672 897

1121 1349 1791

2245

2687

3582

4489

5385

7176

8967

80

500

1000

1200

1600

120 200 300 400

600

800

Chilled water
m 3/h

Flow rate
Pressure drop

kPa

28.6 42.9 71.4 107 143

179

214

286

357

429

571

714

857

1143

1429

30

30

40

40

50

50

50

60

60

60

60

30

30

30

30

Cooling water
m 3/h

Flow rate
Pressure drop

kPa

48.8 73.3 122 183 244

305

366

488

610

733

977

1221

1465

1953

2442

50

50

50

50

60

60

60

70

70

70

70

50

50

50

50

Heating water
m 3/h

Flow rate
Pressure drop
Hot water

kPa

m 3/h
Flow rate
kPa
Pressure drop
Natural gas consumption

15.3 23.1 38.5 57.9 77.1

96.4 116

153

193

231

308

385

463

617

771

20

20

30

30

40

40

50

50

60

60

20

20

20

20

20

3.4

5.2

8.6

12.9 17.2

21.5 25.8

34.4

43.0

51.6

68.8

20

20

20

20

20

20

30

30

40

40

20

Cooling

m 3/h

16.9 25.4 42.2 63.4 84.5 106

127

169

212

254

340

424

509

679

848

Heating

m 3/h

19.2 28.8 48.1 71.9 96.1

144

192

241

288

384

481

577

769

961

Hot water

m 3/h

8.5

12.8 21.4 32.0 42.7 53.5 64

85

107

128

171

120

kW

2.5

4.2

5.8

6.1

9.8

9.8

11.6

16.7

16.7

21.7

25.2

31.9

40.7

49.9

63.3

1.1

1.3

2.6

3.2

3.9

4.9

5.6

8.0

9.0

11.7

13.5

17.0

21.6

28.7

34.7

Unit ship. wt.t

7.0

10

12

14

17

19

26

31

Main shell ship. wt. t

15

20

24

28

29

30

7.4

10.6 13

Power demand
Solution wt.

HTG. wt.t /
Operation wt.t

5.3

11

13

14

17

20

28

16

19

22

29

35

42

50

63

76

89

107

Packaged Direct-fired Absorption Chiller (P-DFA)


Mode

BZY 20 30

Cooling capacity
Pumpset

50

75

100 125 150 200 250

300

400 500

600

800

1000

kW 233 349 582 872 1163 1454 1745 2326 2908 3489 4652 5815 6978 9304 11630

Chilled water pump


External head
Power demand

mH2O
kW

22 22
4

24

24

27

27

27

28

28

28

32

32

32

32

7.5 7.5 15

22

15

22

30

37

44

60

60

110

110

150

180

Cooling water pump


External head
Power demand

mH2O

10

10

15

15

15

15

15

16

16

16

17

17

17

17

kW

7.5 7.5 15

10

15

22

22

37

44

44

60

90

110

150

180

mH2O

15

15

Hot water pump


External head

15

15

15

15

15

15

4.4

4.4

4.4

6.0

6.0

7.4 15.6 15.6 32.2 33.0 47.0 56.4 78.4 92.4 110

126

200

220

300

360

0.6 0.8 0.9 3.8 3.8 4.2

9.8

5.9/8.6 6.1/8.8 6.1/9.8 9.6/9.8

Power demand

kW

0.4 0.6 0.6 2.2 3.0 3.0

Total power demand

kW

Operation wt.
Power demand

t
kW

/
/

8.1

Operation wt.

Ventilation power demand kW

0.3 0.3 0.3 1.0 1.5

1.5

1.5

1.5

2.0

2.0

2.0

2.0

3.0

3.0

3.0

Weight

0.5 0.7 0.8 3.4 3.4 3.9

3.9

5.2

5.6

6.3

6.8

11.0

11.5

14.5 15.5

Electricity
Total power demand
kW
and water
consumption Water demand for cooling t/h

11

7.4

Enclosure

2.5 4.5 5.1 /

7.1

Cooling
tower

5.5 11

4.3

15.7 32.7 32.7 39.3 44.3 58.3 69.5 96.6 111.1 133.7 153.2 233.9 263.7 352.9 426.3
0.6 0.9 1.5 2.0 3.0 3.8

4.5

6.0

7.5

12

15

18

24

30

1. Rated chilled W outlet/inlet temp:


7C/14C
2. Rated cooling W outlet/inlet temp:
37C/30C
3. Rated heating W outlet/inlet temp:
65C/55C
4. Rated hot W outlet/inlet temp: 80C/60C
5. Lowest permitted outlet temperature for
chilled water: 5C
6. Highest permitted outlet temperature for
heating/hot water: 95C
7. Lowest permitted inlet temperature for
cooling water: 10C
8. Adjustable chilled water flowrate:
50%~120% Adjustable heating/hot water
flowrate: 65%~120%
9. Pressure limit for chilled W, cooling W,
heating W, hot W: 0.8MPa (except special
order)
10. Adjustable load: 5%~115%
11. Fouling factor for chilled W, cooling W,
heating W, hot W: 0.086m 2K/kW
12. Natural gas consumption is calculated:
10kWh/m3 (8600kcal/m3)
13. Standard natural gas pressure is 16~50kPa
(1600~5000mmH2O), lower or higher
pressure can be accommodated to
special orders
14. LiBr Solution concentration: 52%. Solution
weight is included in unit shipment weight.
15. Rated exhaust temp for cooling: 160C
Rated exhaust temp for heating: 145C
16. Machine room ambient temperature:
5~43C, humidity !85%
17. Standard climate conditions for cooling
operation: temp 36C, relative humidity 50%
(wet bulb 27C)
18. Heating capacity and hot water capacity
refer to the capacity in separate operation,
which is adjustable within this range
19. Power demand of cooling, heating, hot
W is under rated working condition.
20. Rated cooling COP: 1.36
Rated heating COP: 0.93
21. Life design: 25 years
Notes: Technical specification is based upon
Japanese Industry Standard JIS B 8622
"Absorption Chiller" or based upon ARI
560 standard "AbsorptionWater Chilling
And Water Heating Packages"

HTG(high temp generator)Enlarged


Model!Performance Data
Mode Enlarged Heating Consumption Mode Enlarged Heating Consumption
Models capacity
Models capacity
kW

m 3/h

BZ

H1

215

23.0

150

H2

251

H3
H4

BZ
20

30

50

75

100

125

kW

m 3/h

H1

1614

173

26.9

H2

1883

202

287

30.7

H3

2152

230

323

34.6

H4

2421

259

H1

323

34.6

H1

2152

230

H2

377

40.3

H2

2511

269

H3

430

46.1

H3

2869

307

H4

484

51.8

H4

3228

346

H1

538

57.7

H1

2690

289

H2

628

67.3

H2

3138

337

H3

717

77

H3

H4

807

86

H1

807

86

H2

942

101

H3

1076

115

H4

1211

129

H1

1076

115

H2

1255

135

H3

1435

154

H4

1614

173

H1

1345

144

H2

1569

168

H3

1793

192

H4

2018

216

200

250

300

400

500

3587

386

H4

4035

434

H1

3228

346

H2

3766

403

H3

4304

461

H4

4842

518

H1

4304

461

H2

5021

538
614

H3

5739

H1

5380

577

H2

6277

673

Notes: Heating capacity increases by 20% for each stage of HTG


enlargement. No change with pumpset and metal
enclosure specs.

Packaged DFA Performance Curves

Model Selection & Ordering


Function selection!

Split shipment

BROAD chillers are classified into standard type


(cooling-heating-hot water), A/C type (cooling-heating)
and cooling only type.

!!If

Fuel selection
applicable to a DFA can be: natural gas, town
gas, LPG, bio-gas, light oil or recycled oil.
!!Natural gas and recycled oil are priority.
!!Applicable to gas/oil (for special orders)

!!The

chiller normally will be split into two pieces as


main shell and HTG. 3 pipes must be connected at
jobsite. Customers need to prepare welding facilities,
nitrogen and provide necessary help.

!!Fuels

!!Different

fuel matches different burner.

Load selection
!!Building

cooling/heating load cannot be estimated, as


it is more closely related to building insulation and room

Control
!!BROAD

chiller and its pumpset are equipped with


complete control function, including internet monitoring.
users have a building management system(BMS),
the BMS control interface can be selected as an
optional supply. If the BMS interface is not ordered
along with the chiller, it can be purchased later.

!!If

function than to building area.


!!Model

selection is mainly determined by cooling load. If


the heating load is not enough, a HTG enlarged model
should be selected.
!!An extra boiler is recommended to meet the excessive
heating requirement when heating load exceeds 1.3
times of cooling load.

Quantity
!!The

Note: electricity consumption means the


consumption of the chiller and pumpset.

COP

Nomenclature

Rated COP:1.36

C![!Z!311!Y!ElI2Gb

IPLV COP:1.56
Load

COP

Factor

1.360

0.01

Result
0.014

A 100%
B

75%

1.569

0.42

0.659

C 50%

1.619

0.45

0.729

D 25%

1.308

0.12

0.157

Note: The integrated part load value (IPLV)


reflects chiller's actual COP in operation.

Environmental
Protection Features
Operating Noise dB(A)

High pressure type (details in below table)


H1 20% more heating capacity
Function: k-cooling-heating type, d-cooling only,
default is heating, cooling and hot water
Fuel type: B -oil C-LPG D- natural gas E-town gas
BROAD non-electric chiller design code
(X indicates 10)
Cooling capacity: 10 4 kcal/h
Y-packaged chiller
Chiller type: Z-direct-fired(code of other types
available in Performance Data pages)
Product: B-BROAD
Codes for high pressure type:

Model BYZ

20p50 75p200 250

DFA

57

58

60

pumpset
cooling tower
V\[ZPKLLUJSV\YL

57

57

59

0.81p1.2MPa

Chilled water Cooling


code
water code
Fa
Ma

62

64

66

1.21p1.6MPa

Fb

Mb

42

43

44

1.61p2.0MPa

Fc

Mc

2.01p2.4MPa

Fd

Md

,TPZZPVUZ!
COCO0.02%
NOx46ppm(O$5%
Special

order: equipped electrostatic

cleaner on exhaust port, and emission is


almost zero

fewer units, the lower initial investment and


operation cost (as the chillers COP will be higher and
water systems electric consumption will be lower at
part load).
!!2 units are recommended for one system (the total capability
equals to required load). No need to have standby unit. One
unit can be considered for buildings that allow chiller stop
once a year.

Pressure limit

Flowrate selection
!!BROAD

pumpset adopts a large temperature difference


and low flowrate design so as to save power consumption
dramatically.
!!BROAD designs the pump head according to its
profound experience.
!!If the head is proved to be insufficient, BROAD will
enlarge the pump free of charge.

Pressure selection
!!The

standard pressure limit for chilled/heating/cooling


water is 0.8MPa. Information about high pressure type is
available on page 5.
!!0.81-1.2MPa system: select high pressure type.
1.21-1.6MPa system: either extra pressure type, or
secondary heat exchanger, to be comprehensively
evaluated. >1.6MPa system: secondary heat exchange.

limited by access of customers machine room

(or limited by container transportation), split shipment


can be chosen.

Machine room location


!!On

the floor or on building rooftop.


limited by facilities, the chiller and the pumpset can
be installed in basement while cooling tower on the
floor, on stilt or on building top.
!!Metal enclosure does not apply to basement installation.
!!The chiller and pumpset are installed in the same
metal enclosure so as to minimize piping length.
!!If

Lead time
!!

BYZ150: 2-6 months


4-8 months

!!BYZ200-BYZ400:
!!

BYZ500: 8-12 months

!!

Warranty
Free warranty is to cover 12 months from commissioning
or 18 months from shipment, whichever comes earlier.
BROAD provides paid service in the whole life span.
Service price list is available upon request.


BZY200

Packaged DFA Supply List


Products

Category Item

Remarks

Chiller

Main shell Main shell body

Includes LTG, condenser, evaporator, absorber, cold/heat insulation

Auto purge/vent system

Includes falling head auto purge device, auto air vent device

Solution pump, refrigerant Welded canned type


pump
Low temp heat exchanger Plate type including heat insulation
HTG

Motor valve

Refrigerant motor valve, auto purge valve, etc.

HTG shell

Includes HTG body, front/rear flue chamber, frame base, etc.

High temp heat exchanger Plate type

Control
system

Solution
Pumpset
system

Pumpset

Enclosure /

Water heater

For heating & hot water, N.A. for cooling only type

Thermostatic valve

1 piece each for heating water & hot water constant temp. control.
N.A. for cooling only type

Enclosure

Encloses HTG shell, high temperature heat exchanger and water


heater. (Removable)

Burner

Includes gas valve trains, filter, safety devices, muffler, etc.

Gas flow meter

For accurate measuring of the gas consumption. N.A. for non


gas-fired type

Chiller control cabinet

Includes low voltage components, special circuit board,


microprocessor or PLC, etc.

Touch screen

For operation (central control for BY20 BY30 & BY50)

External control elements

Includes temperature & pressure sensors, flow switches, solution


level probes and actuators

Inverters

Solution pump inverter and refrigerant pump inverter

Network gateway

For Internet monitoring

BMS interface(optional)

Connects to BMS system through dry contact or serial communication

LiBr solution

Includes corrosion inhibitor and energy intensifier.

Chilled/heating water pump Two pumps (BY20, BY30, BY50 only one pump)
Cooling water pump

Two pumps (BY20, BY30, BY50 only one pump)

Hot water pump

Two pumps (BY20, BY30, BY50 only one pump)


N.A. for cooling only and cooling-heating types

Pumpset piping

Includes zero resistance filter, zero resistance check valve, soft


connectors, valves and vibration isolator

Enclosure piping*

Includes all piping within the system to the external connections

Piping accessories in
enclosure

Includes flow switches, vent valves and their sockets,


and soft connectors.

Motor drain valve

When water quality becomes poor, this valve automatically drains


the cooling water. It also drains cooling water automatically in
winter to avoid freeze.

Cooling/heating switch

N.A. for cooling only type

Chilled/heating water
check valve

N.A. for cooling only type

Flow meter

Includes gas, chilled/heating W, cooling W, hot W flow meters. For


accurate measuring of the load.

Water softener

For hard water softening (optional for BZY20 & BZY30 BZY50)

Auto dosing device

Automatically charge biocide corroision inhibitor and antisludge to the


cooling water

Pumpset control cabinet

Includes cooling W pump and cooling tower fan inverters (no inverter
for3 cooling fans), soft starter, low voltage electric parts, etc.

Electric wiring*

Includes wires, cables, cable conduit, cable supporters, etc.

Metal enclosure

Fiber reinforced plastics shell with insulation

Accessories

Includes ventilation and gas leakage detector (for gas type only)

Notes : 1. * means only standard size is available. For any size change, please specify it in purchase orders.
2. Supply list of waste heat chillers is almost the same as DFA supply list. The main difference of waste heat
chillers lies in HTG. Supply list will be provided separately when the order is placed.



Steam Chiller Performance Data

BSY: Steam from power generation or industrial waste streams


Mode

BS

Cooling capacity

kW

10 4 kcal/h

20

75

100

233 349 582

30

50

872

1163 1454 1745

2326 2908 3489 4652 5815 6978

9304 11630

20

75

100

200

800

30

50

125

150

125

150

200

250

300

250

400

300

400

500

500

600

600

800

1000

1000

Chilled W
3

m /h

Flowrate

kPa

Pressure drop

28.6 42.9 71.4

107

143

179

214

286

357

429

571

714

857

1143 1429

30

30

30

30

40

40

50

50

50

60

60

60

48.8 72.3 122

183

244

305

366

488

610

733

977

1221 1465

1953 2442

50

50

50

50

60

60

60

70

70

30

30

60

Cooling W
m 3/h

Flowrate

50

50

50

248 372

619

931

1240 1553 1866 2486 3112 3734 4983 6227 7473

9967 12455

kW

1.7

3.2

4.3

4.6

6.8

Solution weight

0.8

1.1

1.9

2.6

3.0

4.1

4.6

6.7

7.5

Unit ship. wt

5.9

7.5

11.5

14

16

21

26

Main shell ship. wt

HTG. wt

Operation weight

4.5

6.6

8.5

10

13

16

18

24

Pressure drop

kPa

Steam consumption kg/h


Power demand

50

6.8

6.8

10.2

10.2 11.7

70

70

Performance Curves

Nomenclature

The same as packaged direct-fired chiller. Please


refer to P5 for details.

C!T!Z!311!Y!1/9.Gb
Steam inlet pressure: 0.8 MPa
BROAD non-electric chiller design code

Load

Y-packaged chiller
COP

Factor

Result

100%

1.410

0.01

0.014

75%

1.627

0.42

0.683

C 50%

1.679

0.45

0.756

1.356

0.12

0.163

25%

17.7

20.7

25.9 34.9

9.9

11.2

14.6 17.5

22.7 28.2

15

20

24

28

29

30

11

13

Operating Noise

dB(A)

30

35

43

54

63

75

85

Model BYS

20~50

75~200

250

52

53

53
59

Mode

BSY 20

Cooling capacity

kW 233 349 582 872 1163 1454 1745 2326 2908 3489 4652 5815 6978

Pumpset

75

Cooling capacity: 104 kcal/h

IPLV COP:1.62

100 125 150 200 250 300 400 500

600

800

1000

9304 11630

Chiller type: S (steam type)


Product: B-BROAD
Note: High pressure type (see P5)

Model Selection & Ordering


Steam selection

Note:The integrated part load value (IPLV)


reflects chiller's actual COP in operation.
Condition & formula base on ARI560

Steam chiller

30 50

(X indicates 10 )

Rated COP:1.41

13.2

Packaged Steam Chiller Performance Data

High pressure type

COP

Please specify saturated steam pressure and temperature. The


temperature of overheated steam should be 180C (except
special order)

Pumpset

57

57

Cooling tower

62

outside enclosure

51

52

53

Other factors
Load, quantity, flow, pressure, split shipment, control, machine
room, location, ordering and warranty are the same as those of
packaged direct-fired chillers. Please refer to P6 for details.

Supply list

Refer to packaged DFA supply list on P7.

Chilled/heating W . pump
External head

mH2O 22

Power demand

kW 4

22 22

24

24

27

27

27

28

28

28

32

32

32

32

7.5 7.5

15

15

22

30

37

44

60

60

110

110

150

180

10 10

15

15

15

15

15

16

16

16

Cooling W . pump
External head

mH2O 10

Enclosure

17

17

17

kW 3

7.5 7.5

15

15

22

22

37

44

44

60

90

110

150

180

Total power demand

kW 7

15

30

30

44

52

74

88

104

120

200

220

300

360

t 0.5 0.7 0.8 3.3 3.3

3.6

3.7

6.3

6.6

7.2

8.8

5.9/8.6 6.1/8.8 6.1/9.8 9.6/9.8

Operation weight
Cooling
tower

17

Power demand

Power demand

t 2.5 4.5 5.1 /

Ventilation power demand kW 0.3 0.3 0.3 1.0 1.5

1.5

1.5

1.5

2.0

2.0

2.0

2.0

3.0

3.0

3.0

t 0.5 0.7 0.8 3.4 3.4

3.9

3.9

5.2

5.6

6.3

6.8

11.0

11.5

14.5

15.5

Operation weight

Weight
Electricity
Total power demand
and water
consumption Water demand for cooling

kW 5.5 11

15

11

kW 14.5 30.6 30.6 35.6 38.3 52.3 60.3 85.7 100.2 117.7 135.2 219.7 243.7 328.9 397.9
t/h 0.6 0.9 1.5 2.0 3.0

3.8

4.5 6.0

7.5

12

15

18

24

30

General Conditions:
1. Rated saturated steam pressure: 0.8 MPa, rated
condensate temp: 95C
2. Rated chilled W outlet/inlet temp: 7C/14C
3. Rated cooling W outlet/inlet temp: 37C/30C
4. Lowest permitted outlet temperature for chilled
water: 5C
5. Lowest permitted inlet temperature for cooling
water: 10C
6. Steam pressure upper limit 110%
7. Adjustable chilled water flowrate: 50%~120%
8. Pressure limit for chilled W, cooling W:
0.8MPa (except special order)

9. Adjustable load: 5%~115%


10. Fouling factor for chilled W, cooling W:
0.086 m 2 K/kW
11. LiBr Solution concentration: 52%. Solution weight is
included in unit ship, wt.
12. Machine room ambient temperature:
5~43C,humidity !85%
13. Standard climate conditions for cooling operation:
36C, relative humidity 50% (wet bulb 27C)
14. Rated cooling COP: 1.41
15. Life design: 25 years

BS500





Packaged Hot W/Exhaust chiller

Performance Data

Packaged Single-stage Steam/Hot W . /Exhaust Chiller


Performance Data !BDSY/BDHY/BDEY: steam/hot water/exhaust

BHY/BEY: hot water/exhaust from power generation or industrial waste streams


(pumpset, enclosure data are the same as steam chiller)!

(pumpset, enclosure data are the same as steam chiller)!

Code Mode Cooling Heating Chilled W


Cooling W
heating W
Hot Exhaust consump. Power Solution Unit Main HTG. Chiller
capacity capacity
demand wt.
ship. shell wt. operation
water
Flowrate Pressure Flowrate Pressure Flowrate Pressure
Cooling Heating
weight
wt. ship
condrop
drop
drop
wt.
sump.
kW

20 233
30 349
50 582
75 872
100 1163
BH
125 1454
150 1745
hot
water 200 2326
180C 250 2908
300 3489
400 4652
500 5815
600 6978
800 9304
1000 11630
Twostage
hot
water
chiller

kW

m3/h

kPa

m3/h

kPa

m3/h

kPa

m3/h kg/h

kg/h

kW

/
/
/
/
/
/
/
/
/
/
/
/
/
/
/

28.6
42.9
71.4
107
143
179
214
286
357
429
571
714
857
1143
1429

30
30
30
30
30
30
40
40
50
50
50
60
60
60
60

48.8
72.3
122
183
244
305
366
488
610
733
977
1221
1465
1953
2442

50
50
50
50
50
50
50
50
60
60
60
70
70
70
70

/
/
/
/
/
/
/
/
/
/
/
/
/
/
/

/
/
/
/
/
/
/
/
/
/
/
/
/
/
/

10.1
15.2
25.2
37.8
50.5
63.2
76
101
127
152
203
253
304
406
507

/
/
/
/
/
/
/
/
/
/
/
/
/
/
/

1.7
3.2
4.3
4.6
6.8
6.8
6.8
10.2
10.2
11.7
13.2
17.7
20.7
25.9
34.9

1.0
1.2
2.2
2.8
3.4
4.4
4.9
7.1
7.8
10.6
12.1
14.8
18.1
24.2
30.5

4.5
6.2
8
9.5
12
14
16
21
26
/
/
/
/
/
/

/
/
/
/
/
/
/
/
/
15
20
24
28
29
30

/
/
/
/
/
/
/
/
/
6
7
9
11
14
17

5
6.9
9
11
13
15
18
24
30
35
45
55
66
79
92

50

13.1

20

Two20
stage
30
exhaust
chiller 50

233

153

28.6

1527

1527

1.7

1.5

6.5 /

349

230

42.9

30

72.3

50

19.6

20

2300

2300

3.2

2.2

8.9 /

9.6

582

384

71.4

30

122

50

32.7

20

3814

3814

4.3

3.5

12 /

12.5

75

872

575

107

30

183

50

49.0

20

5732

5732

4.6

4.4

14 /

16

767

143

30

244

50

65.4

20

7639

7639

6.8

5.7

18 /

20

959

179

30

305

50

81.8

20

9566

9566

6.8

6.6

22 /

24

BE

exhaust 100 1163


500C

125 1454

30

48.8

/
/
/
/
/
/
/
/
/
/
/
/
/
/
/

150 1745

1151

214

40

366

50

98

20

11494 11494

6.8

7.6

25 /

27

200 2326

1534

286

40

488

50

131

30

15310 15310

10.2

10.8

33 /

36

250 2908

1918

357

50

610

60

163

30

19165 19165

10.2

12.1

13

12 42

300 3489

2301

429

50

733

60

196

40

22999 22999

11.7

15.8

15

15 50

400 4652

3068

571

50

977

60

262

40

30688 30688

13.2

18.2

20

18 62

500 5815

3835

714

60

1221

70

327

50

38349 38349

17.7

23.0

24

21 75

600 6978

4602

857

60

1465

70

394

50

46024 46024

20.7

29.1

28

25 91

800 9304

6137

1143

60

1953

70

523

60

61381 61381

25.9

36.5

29

32 110

1000 11630 7671

1429

60

2442

70

654

60

76703 76703

34.9

41.0

30

40 125

General Conditions:
1. Rated hot W inlet/outlet temp for hot W
chiller:180C/165C
2. Rated exhaust inlet/outlet temp for exhaust
chiller: 500C/160C
3. Rated chilled W outlet/inlet temp: 7C/14C
4. Rated cooling W outlet/inlet temp: 37C/30C
5. Rated heating W outlet/inlet temp for two-stage
exhaust chiller: 65C/55C
6. Lowest permitted outlet temperature for chilled
water: 5C
7. Lowest permitted inlet temperature for cooling
water: 10C
8. Adjustable chilled water flowrate: 50%~120%
9. Pressure limit for chilled/cooling water:
0.8MPa (except special order)

10. Adjustable load: 5%~115%


11. Fouling factor for chilled water, cooling W: 0.086 m2 K/kW
12. LiBr Solution concentration: 52%, solution weight is
included in unit shipment wt.
13. Machine room ambient temperature: 5~43C,
humidity !85%
14. Rated cooling COP: 1.41
15. Rated heating COP for exhaust chiller: 0.93
16. Life design: 25 years
17. Please refer to P5, P6 & P7 for performance curve,
model selection & ordering and supply list information.

Exhaust Exhaust Solution Unit Main Chiller


Code Model Cooling Chilled W
Cooling W
Steam
Hot
ship. shell operation
consump. water consu- consu- wt.
capacity
Flowrate Pressure Flowrate Pressure
mp.
wt. ship. weight
consu- mp.
drop
drop
wt.
mp.
Singlestage
steam
chiller
BDS
steam
0.1MPa

Singlestage
hot
water
chiller
BDH
hot
water
98C

Singlestage
exhaust
chiller
BDE
exhaust
300C

20
30
50
75
100
125
150
200
250
300
400
500
600
20
30
50
75
100
125
150
200
250
300
400
500
600

kW

m3/h

kPa

m3/h

kPa

kg/h

m3/h

kg/h

kW

233
349
582
872
1163
1454
1745
2326
2908
3489
4652
5815
6978
209
302
512
767
1023
1279
1535
2046
2558
3069
4092
5115
6138

28.6
42.9
71.4
107
143
179
214
286
357
429
571
714
857
25.2
37.6
62.9
94.2
125
157
188
251
313
376
503
628
754

30
30
30
30
30
30
40
40
50
50
50
60
60
25
25
25
25
25
25
30
30
40
40
40
50
50

64.7
97.1
162
243
324
405
486
647
809
971
1295
1618
1942
59.5
87.3
146
218
291
364
437
582
728
873
1164
1455
1746

50
50
50
60
60
60
60
60
70
70
70
90
90
50
50
50
60
60
60
60
70
70
70
70
90
90

456
688
1146
1714
2288
2863
3438
4581
5728
6876
9167
11465
13757
/
/
/
/
/
/
/
/
/
/
/
/
/

/
/
/
/
/
/
/
/
/
/
/
/
/
24.4
36
60
90
120
150
180
240
300
361
481
601
722

/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/

2.5
2.5
2.5
5.3
5.7
5.7
5.7
8.6
10.1
10.1
13.9
13.8
17.5
2.5
2.5
2.5
5.3
5.7
5.7
5.7
8.6
10.1
10.1
13.9
13.8
17.5

0.7
0.8
1.7
2.2
2.4
3.2
3.5
5.5
6.0
8.2
8.9
11.7
14.5
0.7
0.8
1.7
2.2
2.4
3.2
3.5
5.5
6.0
8.2
8.9
11.7
14.5

3.5
4.5
6.5
8.5
10.5
12.5
14
20
23.5
28
32
/
/
3.5
4.5
6.5
8.5
10.5
12.5
14
20
23.5
28
33
/
/

/
/
/
/
/
/
/
/
/
/
/
27
29
/
/
/
/
/
/
/
/
/
/
/
28
30

4
5.1
7
9.5
11.5
14
16
22
26
31
37
44
49
4
5.1
7
9.5
11.5
14
16
22
26
31
37
44
50

20

233

28.6

30

64.7

50

5621

2.5

0.8

4.4

30

349

42.9

30

97.1

50

8474

2.5

1.2

5.5

50

582

71.4

30

162

50

14128

2.5

2.1

7.6

75

872

107

30

243

60

21138

5.3

2.5

10

100

1163

143

30

324

60

28218

5.7

2.8

11

12.5

General Conditions:
1. Rated saturated steam pressure for BDS chiller
0.1 MPa. Rated condensate temperature for BDS
chiller: 95C
2. Rated hot W inlet/outlet temp for single-stage
hot W chiller: 98C/88C
3. Rated exhaust inlet/outlet temp for single-stage
exhaust chiller: 300C/130C
4. Rated chilled W outlet/inlet temp: 7C/14C
5. Rated cooling W outlet/inlet temp: 37C/30C
6. Lowest permitted outlet temperature for chilled
water: 5C
7. Lowest permitted inlet temperature for cooling
water: 10C
8. Adjustable chilled water flowrate: 50%~120%
9. Pressure limit for chilled/cooling water:
0.8MPa (except special order)

10. Adjustable load: 5%~115%


11. Fouling factor for chilled W, cooling W: 0.086 m2 K/kW
12. LiBr Solution concentration: 50%. Solution weight is
included in unit shipment wt.
13. Machine room ambient temperature:
5~43C, humidity !85%
14. Rated COP: single-stage steam chiller and exhaust chiller:
0.79, single-stage hot W chiller: 0.76
15. Life design: 25 years
16. Please refer to P5, P6 & P7 for performance curve, model
selection & ordering and supply list information.





Packaged Multi-energy Chiller

Performance Data

BZEY/BHEY/BZHEY: gas (oil) and waste heat hybrid (multi-energy chiller)


(pumpset, enclosure data are the same as DFA)!
Code

Exhaust
&
directfired
chiller

Mode Cooling Heating Hot


Hhilled W
Heating water Hot water
Cooling W
Power
Solution
capacity capacity water
Flowrate Pressure Flowrate Pressure Flowrate Pressure Flowrate Pressure demand wt.
capacity
drop
drop
drop
drop
20

kW

kW

kW

m3/h

kPa

m3/h

kPa

m3/h

kPa

m3/h

kPa

kW

233

179

80

28.6

30

15.3

20

3.4

20

48.8

50

2.5

1.3
1.6

30

349

269

120

42.9

30

23.1

20

5.2

20

73.3

50

4.2

50

582

449

200

71.4

30

38.5

20

8.6

20

122

50

5.8

2.8

75

872

672

300

107

30

57.9

20

12.9

20

183

50

6.1

3.5

100

1163

897

400

143

30

77.1

17.2

20

244

50

9.8

125
exhaust 150
500C 200
gas/oil
250

1454

1121

500

179

30

96.4

20

21.5

20

305

50

9.8

5.4

1745

1349

600

214

40

116

20

25.8

20

366

50

11.6

6.1

2326

1791

800

286

2908

2245

1000

357

50

193

30

43.0

30

610

60

16.7

10.0

300

3489

2687

1200

429

50

231

40

51.6

40

733

60

21.7

12.7

400

4652

3582

1600

571

50

308

40

68.8

977

60

25.2

14.9

500

5815

4489

714

60

385

50

1221

70

31.9

19.0

600

6978

5385

857

60

463

50

1465

70

40.7

23.1

800

9304

7176

1143

60

617

60

1953

70

49.9

30.2

1000 11630

8967

1429

60

771

60

2442

70

63.3

36.2

20

233

153

28.6

30

11.6

15

52.5

50

1.7

1.6

30

349

230

42.9

30

19.6

20

73.3

50

3.2

2.3

50

582

384

71.4

30

29.3

15

131

50

4.3

3.6

75

872

575

107

30

43.8

15

196

50

4.6

4.5

BZE

Hot W &
exhaust
chiller
BHE
exhaust
500C
hot W
98C

Hot W &
exhaust
&
directfired
chiller
BZHE

40

153

20

30

34.4

30

40

488

50

16.7

4.4

8.5

100

1163

767

143

30

58.4

15

262

50

6.8

5.8

125

1454

959

179

30

73.0

15

327

50

6.8

6.8

150

1745

1151

214

200

2326

1534

286

40

117

25

525

50

10.2

11.0

250

2908

1918

357

50

146

25

655

60

10.2

12.6

300

3489

2301

429

50

175

35

787

60

11.7

40

88.2

15

393

50

6.8

7.8

Energy consump
Cooling

Heating

Hot water

NG Exhaust Hot W NG Exhaust NG

Exhaust

Unit Main HTG. Operation


ship. shell wt. wt.
wt. ship
wt.

m3h kg/h

m3/h m3/h kg/h

m3/h kg/h

16.9 458

8.5

6.3

19.2

458

458

25.4 690

28.8 690

12.8

690

8.2

8.6

42.2 1144

48.1

1144

21.4

1144

11

11.5

63.4 1720

71.9

1720

32.0

1720

14

15

84.5 2292

96.1

42.7

2292

18

19

106 2870

120

2870

53.5

2870

21

22.5

127 3448

144

3448

2292

64

3448

23

25

31

169 4593

192

4593

85

212 5749

241

5749

107

5749

13

14

41

254 6900

288

6900

128

6900

4593

15

15

47

34

340 9206

384

9206

171

9206

20

16

57

424 11505

481

11505

24

21

72

509 13807

577

13807

28

26

86

679 18414

769

18414

29

24

95

848 23011

961

23011

30

34

114

1527

6.6

1527

6.6

2300

9.9

2300

9.0

9.7

3814

16.4

3814

12

12.7

5732

24.7

5732

15

7639

32.9

7639

19

20.5

9566

41.1

9566

22.5 /

25

11494

25.5 /

16

49.3

11494

15310

65.8

15310

34

37

19165

82.2

19165

13

14

43

28

16.2

22999

98.7

22999

15

21

57

400

4652

3068

571

50

233

35

1049

60

13.2

18.7

30688

132

30688

20

22

67

500

5815

3835

714

60

293

45

1311

70

17.7

23.7

38349

164

38349

24

29

85

29.8

46024

197

46024

28

61381

263

61381

29

42

120

76703

329

76703

30

47

133

6.6

19.2

458

8.5

458

6.5

600

6978

800

9304

4602

857

60

351

45

1573

70

20.7

6137

1143

60

467

55

2097

70

25.9

37.2

1000 11630

7671

1429

60

584

55

2622

70

34.9

42.0

20

179

80

28.6

30

15.3

20

3.4

20

52.5

50

2.5

1.4

233

30

349

269

120

42.9

30

23.1

20

50

582

449

200

71.4

30

38.5

20

8.6

20

131

50

5.8

2.9

75

872

672

300

107

30

57.9

20

12.9

20

196

50

6.1

3.6

20

78.7

50

4.2

1.7

100

1163

897

400

143

30

77.1

17.2

20

262

50

9.8

125

1454

1121

500

179

30

96.4

20

21.5

20

327

50

9.8

5.6

150

1745

1349

600

214

40

116

20

25.8

20

393

50

11.6

6.3

exhaust 200
500C
250
hot W
300
98C
400

2326

1791

800

286

20

5.2

4.5

40

153

30

34.4

30

525

50

16.7

8.7

2908

2245

1000

357

50

193

30

43.0

30

655

60

16.7

10.5

3489

2687

1200

429

50

231

40

51.6

40

787

60

21.7

13.1

4652

3582

1600

571

50

308

40

68.8

40

1049

60

25.2

15.4

500

5815

4489

714

60

385

50

1311

70

31.9

19.7

600

6978

5385

857

60

463

50

1573

70

40.7

23.8

800

9304

7176

1143

60

617

60

2097

70

49.9

30.9

8967

1429

60

771

60

2622

70

63.3

37.2

1000 11630

16.9 458

37

109

25.4 690

9.9

28.8 690

12.8

690

8.6

9.2

42.2 1144

16.4

48.1

1144

21.4

1144

11.5 /

12.2

63.4 1720

24.7

71.9

1720

32.0

1720

15

16

84.5 2292

32.9

96.1

2292

42.7

2292

19

106 2870

41.1

120

2870

53.5

2870

22

24

127 3448

49.3

144

3448

64

3448

24.5 /

26.5

169 4593

65.8

192

4593

85

4593

33

212 5749

82.2

241

5749

107

5749

13

15

43

254 6900

98.7

288

6900

128

6900

15

16

49
60

20

36

340 9206

132

384

9206

171

9206

20

19

424 11505

164

481

11505

24

25

76

509 13807

197

577

13807

28

30

91

679 18414

263

769

18414

29

37

109

848 23011

329

961

23011

30

50

131

General Conditions:
1. Rated chilled W outlet/inlet temp:
7C/14C
2. Rated cooling W outlet/inlet temp:
37C/30C
3. Rated heating W outlet/inlet temp:
65C/55C
4. Rated hot W outlet/inlet temp:
80C/60C
5. Lowest permitted outlet temperature
for chilled water: 5C
6. Highest permitted outlet temperature
for heating/ hot water: 95C
7. Lowest permitted inlet temperature for
cooling water: 10C
8. Adjustable chilled water flowrate:
50%~120%
9. Adjustable heating/hot water flowrate:
65%~120%
10. Pressure limit for chilled W, cooling W,
heating W, hot W 0.8MPa (except
special order)
11. Adjustable load: 5%~115%
12. Fouling factor for chilled W, cooling W,
heating W, hot W: 0.086m2 K/kW
13. LiBr Solution concentration: 52%.
Solution weight is included in unit ship. wt.
14. Natural gas consumption is calculated:
10kWh/m3(8600kcal/m3).
15. Standard natural gas pressure is
16~50kPa (1600~5000mmH2O), lower
or higher pressure can be accommodated to special orders
16. Machine room ambient temperature:
5~43C, humidity 85%
17. Standard climate conditions for cooling
operation: 36C, relative humidity
50%(wet bulb 27C)
18. Exhaust provides 30% of the total
capacity per standard design
of BZE/BZHE. Over 30% can be
accommondated into special orders.
19. Energy consumption is for seperate
operation of heat source and fuel
20. Life design: 25 years
21. Please refer to P5, P6 & P7 for
performance curve, model selection &
ordering and supply list information





Model Selection Curves

( orange means the rated value )

chilled/cooling water temp, cooling capacity, COP

)A

)+/

)+,

)/

Notes: The figure in blue is COP. In calculation, 3 COP


values are added and then divided by 3. e.g.
1. Cooling capacity is 100%, cooling water temp. is
28 , then chilled water temp. is 6.2 ,COP is1.358,i.
e.(1.36+1.382+1.332)/3=1.358
2. Chilled water temp. is 10 , cooling water temp. is
30 , then cooling capacity is 116%, COP=1.374
3. Cooling capacity is 90%, chilled water is 6, then
cooling water temp is 30 , COP=1.352

):

),

)+:

5V[L!;OLMPN\YLPUIS\LPZ*67
)/),)+/)+,)+:
*HSJ\SH[PVUPZ[OLZHTL^P[O)A
Notes: The figure in blue is COP. In calculation, 4 COP
values are added and then divided by 4. e.g.
1. Cooling capacity is 100%, steam pressure 0.6 MPa,
cooling water temp. is 28 , then chilled water temp.
is 8.2 ,COP is 1.399,i.e.(1.41+1.42+1.35+1.416)/4=1.399
2. Steam pressure 0.7 MPa, chilled water temp. is 8 ,
cooling water temp. is 28 , then cooling capacity is
106%, COP=1.402
3. Cooling capacity is 90%, steam pressure 0.8 MPa,
chilled water is 6 , then cooling water temp. is 30.5 ,
COP=1.396 (steam pressure 0.8 MPa)

):TVKLSZ


Micro
Non-electric Chiller(villa air conditioning)



Performance Data
Mode

BCT23

BCT70

BCT115

70

115

Cooling capacity

kW 23
9[ 6.6

20

33

Heating capacity

kW 23

70

115

Hot W . capacity

kW 7.7

39

39

A/C water
Chilled water O/temp
Heating water O/I temp
Flowrate
External head

7/14

7/14

7/14

57/50

57/50

57/50

m 3/h 2.9
mH 2 O 8

8.6

14.3

11

12

80/60

80/60

1.68

1.68

Hot W .
Primary heating water O/I temp
Flowrate

80/60
m 3/h

0.33

NG consumption
Cooling

m 3/h 2.1

6.4

10.5

Heating

m 3/h 2.6

7.8

13.0

Hot W .

m 3/h 0.9

4.3

4.3

Electricity for cooling

kW 1.8

5.2

7.2

Electricity for heating

kW 0.7

1.7

2.3

Water for cooling

t/h 0.06

0.18

0.30

Electricity and water consumption

65

65

Ship. weight

kg 550

1650

2480

A/C W hold-up volume

kg 10

32

48

Operating noise

dB(A) 63

Others:
1. Fuel: NG, Town gas, LPG, Light oil, please specify it in purchase orders.
2. Natural gas consumption is calculated 10 kWh/m3 (8,600 kcal/m3).
3. Standard gas pressure: 200~650 mmH2 O. Pressure release valve has to be installed if the
pressure is higher than the standard.
4. Standard condition for cooling: 36C , humidity 50%.
5. Permitted condition: summer 45C winter -30C.
6. Lowest permitted outlet temp. for chilled W: 5C. Pressure limit for chilled/ heating/ hot W: 40 mH2 O.
7. Hot W can only be used after secondary heat exchange, otherwise it gets scaled.
8. Single phase power for BCT23 and 3 phase for BCT70/115.
9. Rated cooling COP: 110% Rated heating COP: 88%.

Design & Construction Tips!

Model Selection & Ordering

Performance Curves



Micro Non-electric Chiller Dimensions

!!!!BROAD

recommendations are as follows:


1 unit for buildings 300m2
1~2 units for buildings 2000m2
2~3 units for buildings > 2000m2
For year-round non-stop operation, at least 2
units are recommended, but standby units are not
recommended. Several units can be incorporated
into an integrated system.
!!!!Lead time: 2~4 months for small quantity orders.
Orders greater than 300 units, take at least 4 months.

Mode

BCT23

1350

830

2230

2000

115

390

770

680

22

42

15

15

22

800

BCT70

2250

1610

2230

2500

145

905

1055

1460

35

67

35

15

35

1000

BCT115

2770

1610

2230

2500

145

1020

1460

1460

35

67

35

15

35

1000

Note: All units are in mm.





Packaged DFA

Packaged DFA Dimensions (with metal machine room)

BZY20

BZY75 g BZY100 g BZY125 g BZY150 g BZY200 g


BZY250gBZY300gBZY400

BZY30gBZY50

Notes:
1. The weight is evenly distributed on each
plinth of the chiller and pumpset.
2. If there is a space limitation, the cooling
tower can be placed on the top of
the metal machine room, but the structure
shall be re-designed.
3. The metal enclosure shown here is not the
best solution. Customer who has enough
space can build outdoor metal machine
room with service access inside. BROAD
can provide design drawings upon request.
Mode
BZY75
BZY100
BZY125
BZY150
BZY200
BZY250
BZY300
BZY400
Mode
BZY75
BZY100
BZY125
BZY150
BZY200
BZY250
BZY300
BZY400

A
10000
10000
11500
11500
12500
13500
14000
14500
N
2
2
3
3
3
3
3
3

B
4500
4500
4500
4500
5000
5000
5500
6000
O
5400
5400
5400
5400
6000
6000
6500
7000

C
3235
3235
3675
3675
4150
4240
4260
4880
P
10700
10700
12200
12200
13200
14200
14700
15200

D
640
745
575
575
695
540
740
625
Q
1500
1500
2000
2000
2000
2000
2500
3000

E
1955
1905
2045
2045
2215
2215
2215
2485
R
4154
5207
6125
6125
7343
8560
8560
7373

F
755
630
820
965
965
965
1030
1100
S
2055
2040
2115
2115
2505
2560
2580
2588

G
2700
2900
2900
2900
3200
3200
3450
3700
T
3113
3124
3656
3656
3656
3651
3651
5739

H
1075
1200
1330
1330
1585
1670
1755
1850
U
3235
2340
2250
2230
2500
1995
2255
3000

I
4000
4000
5000
5000
5000
6000
6000
6000
V
3912
4318
6070
6070
6401
6833
6833
6833

J
1755
1705
1845
1845
2015
2015
2015
2285
W
DN150
DN150
DN200
DN200
DN250
DN250
DN300
DN300

K
2575
2525
2665
2705
2875
2875
3035
3265
X
DN200
DN200
DN250
DN250
DN300
DN350
DN350
DN400

L
860
900
785
775
965
795
1045
905
Y
DN65
DN65
DN80
DN80
DN125
DN125
DN125
DN150

M
2300
2600
2600
2800
3400
3400
3700
4000
Z
4600
4600
5250
5250
5750
6250
6500
6500





Packaged DFA Dimensions(with metal machine room)

Packaged DFA Dimensions (with enclosure)

BZY500gBZY600gBZY800gBZY1000

BZY75gBZY100gBZY125gBZY150gBZY200gBZY250
BZY300gBZY400gBZY500gBZY600gBZY800gBZY1000

Notes:
1. The weight is evenly distributed on each
plinth of the chiller and pumpset.
2. If there is a space limitation, the cooling
tower can be placed on the top of
the metal machine room, but the structure
shall be re-designed.
3. The metal enclosure shown here is not the
best solution. Customer who has enough
space can build outdoor metal machine
room with service access inside. BROAD
can provide design drawings upon request.
4. If multi-units use single-deck machine room,
the scope of supply is the same as that of
double-deck machine room
Mode

BZY500

17000

6500

4500

3000

12885

3290

3652

3325

6833

960

BZY600

19500

6500

17210

3375

3652

4110

6833

1165

BZY800

19500

7200

5500

3500

14840

3485

5739

3415

6833

1065

BZY1000

21200

7200

5500

5000

4000

3500

18485

3560

5739

3670

6833

1405

Model

BZY500

3260

4100

1310

8000

7560

1350

1210

BZY600

4000

5665

13000

1835

3900

1445

8000

2500

1490

1350

BZY800

4000

5565

13000

2000

4500

1715

8000

2500

1440

1300
1370

Notes:
1. Dimension is outline machine room.
2. That equipment & foundation is the same
as single-deck machine room.
3. Chiller & pumpsets locate in downstairs
and cooling tower locate in upstairs.

Dimensions of double-deck machine room


Code

BZY75gBZY100

11500

5500

9000

3300

10000

4500

BZY125gBZY150

Mode

13000

6800

10000

3800

11500

4500

BZY200

14000

6800

11000

4200

12500

5000

BZY250BZY300gBZY400
16000

8000

11500

4900

14500

7500

BZY500gBZY600
BZY2002gBZY2502
BZY800

21000

9500

12500

5100

19500

9000

21000

10500

12500

5600

19500

10000

BZY1000

25000

11500

13500

5600

21200

11000

BZY4002
BZY6002gBZY4003

21000

20000

12500

5100

21000

20000

BZY752gBZY1002

BZY1252gBZY1502

BZY3002gBZY2003

BZY1000

4000

6905

13000

2340

4500

1710

10000

1500

1530

Model

BZY500

4600

1360

1500

905

3800

17900

7600

DN350

DN400

BZY600

4600

1360

1500

1115

4200

20400

7600

DN400

DN450

BZY8002gBZY5003

21000

21000

12500

5600

21000

21000

BZY800

5000

1360

1500

1335

4600

20400

8300

DN450

DN500

10

BZY10002

25000

22000

13500

5600

25000

22000

BZY1000

5000

1360

1500

1295

4600

22150

8300

DN450

DN500





Packaged DFA Dimensions (with enclosure)

DFA Dimensions

BZY75gBZY100gBZY125gBZY150
BZY200gBZY250gBZY300gBZY400gBZY500

BZ75gBZ100gBZ125gBZ150

Mode

BZY75

8825

2630

2950

BZY100

9000

2630

2950

DN200

DN150

DN40

DN65

350350

2830

2480

Mode

BZY125

10100

3180

2970

DN250

DN200

DN40

DN80

400400

3380

2540

BZ75

5420

2150

2510

DN200

DN150

DN25

DN100

DN65

320320

BZY150

10100

3250

3400

DN250

DN200

DN40

DN80

440440

3450

2740

BZ100

5420

2450

2510

DN200

DN150

DN40

DN125

DN65

350350

BZY200

10800

3560

3400

DN300

DN250

DN50

DN125

560560

3800

3180

BZ125

6550

2450

2510

DN250

DN200

DN40

DN150

DN80

400400

BZY250

11400

3560

3440

DN350

DN250

DN50

DN125

560560

3800

3180

BZ150

6600

2650

2930

DN250

DN200

DN40

DN150

DN80

440440

BZY300

12600

3800

3440

DN350

DN300

DN65

DN125

610610

4000

3560

Mode

BZY400

12750

4200

3800

DN400

DN300

DN65

DN150

710710

4400

4000

BZ75

400

600

BZY500

16000

4000

3800

DN400

DN350

DN80

790790

4600

4000

BZ100

400

BZ125

400

2700

BZ150

2900

Mode

2900

BZ75

4000

Mode

BZY75

1100

BZY100

1350

L
4855
6100

D
DN200

E
DN150

F
DN25

G
DN65

H
320320

3970

1930

200

850

400

4000

2900

1930

150

850
870

400
400

4000
5000

I
2830

S
1075
1200
1330

J
2100

2100

2300

210

440

2220

1250

490

600

2100

2300

260

525

2215

1450

490

600

2100

2300

260

520

2090

1550

540

500

700

2400

2705

275

515

2505

1550

3180

650

300

220

200

100

540

2300

380

BZY125

1350

6400

3700

2000

90

BZY150

1450

6400

3700

2000

870

400

5000

1330

2900

BZ100

4000

3180

650

285

240

210

100

2600

380

BZY200

1590

6450

4350

2140

190

900

400

5000

1500

3200

BZ125

5000

3220

1370

640

260

220

110

2600

380

BZY250

1590

7350

4050

2140

190

800

400

6000

1300

3200

BZ150

5000

3220

1370

620

260

220

110

2800

220

BZY300

2000

8800

3800

1500

240

1100

400

6000

1755

3450

BZY400

2000

8950

3800

1500

200

1100

400

6000

1850

3700

BZY500

2000

10900

5100

2140

420

1100

500

8000

2000

4600





DFA Dimensions
BZ200gBZ250gBZ300gBZ400gBZ500

Mode

BZ600gBZ800gBZ1000

BZ200

6600

3200

3000

DN300

DN250

DN50

DN200

DN125

560560

2470

500

BZ250

7700

3200

3000

DN350

DN250

DN50

DN200

DN125

560560

2510

500

BZ300

7950

3530

3000

DN350

DN300

DN65

DN200

DN125

610610

2490

500

Mode

BZ400

7950

3850

3400

DN400

DN300

DN65

DN250

DN150

710710

2905

650

BZ600

9800

3870

3700

BZ500

9700

4100

3400

DN400

DN350

DN80

DN250

790790

2945

650

BZ800

9850

4370

3910

DN500

DN450

DN65

DN250

710710

3420

BZ1000

11580

4370

3910

DN500

DN450

DN80

DN250

790790

3460

Mode

BZ200

430

295

2360

2670

725

285

2100

3000

60

BZ250

415

310

2350

2650

725

340

2100

3400

60

U
400
400

5000

Mode

6000

BZ600

615

340

L
2765

D
DN450

E
DN400

F
DN65

G
DN200

H
610610

I
2910

3310

870

305

2260

4500

8000

BZ300

525

310

2390

2650

735

410

2400

3400

60

400

6000

BZ800

695

330

3145

3630

925

410

2050

4500

8000

BZ400

565

325

2720

3020

790

435

2550

3400

60

400

6000

BZ1000

695

330

3145

3630

925

410

2050

5000

10000

BZ500

575

315

2720

3020

750

480

2500

4300

70

500

8000

Mode

BZ200

540

3250

1350

560

1680

315

270

135

3300

BZ800

690

1540

3300

1965

345

1850

4150

700

BZ250

590

3250

2240

750

1650

315

270

135

3300

BZ1000

690

1580

3300

1965

400

2100

4300

780

BZ300

590

3250

2240

725

1750

315

270

135

3700

BZ400

590

3300

2215

675

1850

360

305

150

4000

BZ500

590

3300

3570

1985

2100

400

4100

Mode

BZ600

640

T
1520

3250

2015

300

1750

3900

700



HTG Enlarged Model Dimensions


BZ75gBZ100gBZ125gBZ150

BZ200gBZ250gBZ300gBZ400

HTG Enlarged H3,H4 dimensions (HTG Enlarged H1,H2 is the same size with standard models)

HTG Enlarged H3,H4 dimensions (HTG Enlarged H1,H2 is the same size with standard models)

(Refer to P26 of the DFA standard model for dimensions not shown in the drawing)!

(Refer to P27 of the DFA standard model for dimensions not shown in the drawing)!

Mode

Mode

BZ75

5420

2250

2510

DN40

DN125

DN65

350350

2215

BZ200

6600

3200

3000

DN50

DN200

DN125

560560

2470

500

3000

BZ100

5420

2410

2510

DN40

DN150

DN80

400400

2090

BZ250

7700

3300

3000

DN65

DN200

DN125

610610

2490

500

3400

BZ125

6550

2500

2510

DN40

DN150

DN80

440440

2110

BZ300

7950

3670

3000

DN65

DN250

DN150

710710

2690

500

3400

BZ150

6600

2650

2930

DN50

DN200

DN125

560560

2530

BZ400

7950

4010

3400

DN80

DN250

790790

2945

650

3400

Mode

Mode

BZ75

4000

3180

650

285

220

200

100

2400

BZ200

5000

540

3250

1655

160

335

280

150

3150

6000

590

3250

2240

725

335

280

150

3250

BZ100

4000

3220

750

20

260

210

110

2600

BZ250

BZ125

5000

3220

1370

620

260

220

110

2800

BZ300

6000

590

3300

2215

675

400

300

200

3750

BZ150

5000

3250

1350

560

335

280

150

2900

BZ400

6000

590

3300

2200

635

400

4200





Steam Chiller Dimensions

BS200gBS250gBS300gBS400
BS500gBS600gBS800gBS1000

BS75gBS100gBS125gBS150

Mode

BS75

5420

1900

2510

DN200

DN150

DN40

440

210

400

BS100

5420

2100

2510

DN200

DN150

DN50

525

260

400

BS125

6550

2200

2510

DN250

DN200

DN50

520

260

400

BS150

6600

2300

2930

DN250

DN200

DN65

515

275

500

Mode

BS75

600

2100

2300

1250

1080

4000

490

2000

380

BS100

600

2100

2300

1450

900

4000

490

2300

380

BS125

600

2100

2300

1550

900

5000

540

2300

380

BS150

700

2400

2705

1550

1325

5000

540

2400

220

Mode

BS200

6600

2850

3000

DN300 DN250

DN40

DN80

550

430

295

2360

2670

725

BS250

7700

2850

3000

DN350

DN250

DN40

DN80

550

415

310

2350

2650

725

BS300

7950

3340

3000

DN350

DN300 DN50

DN100

550

525

310

2390

2650

735
790

BS400

7950

3480

3400

DN400 DN300 DN50

DN100

600

565

325

2720

3020

BS500

9700

3480

3400

DN400 DN350

DN50

DN125

600

575

315

2720

3020

750

BS600

9800

3640

3700

DN450

DN400 DN65

DN125

600

615

340

2765

3310

870

BS800

9850

4050

3910

DN500 DN450

DN65

DN150

600

695

330

3145

3630

925

BS1000

11580

4050

3910

DN500 DN450

DN65

DN150

600

695

330

3145

3630

925

Mode

BS200

285

2100

3000

60

1165

400

5000

540

200

1200

3000

700

BS250

340

2100

3400

60

1165

400

6000

590

200

1200

3000

700

BS300

410

2400

3400

60

1165

400

6000

590

200

1350

3400

700

BS400

435

2550

3400

60

1400

400

6000

590

300

1400

3500

700

BS500

480

2500

4300

70

1400

500

8000

590

300

1400

3500

700

BS600

305

2260

4500

70

1400

500

8000

640

300

1400

3700

700

BS800

410

2050

4500

70

1690

500

8000

690

300

1700

4100

700

BS1000

410

2050

5000

70

1690

500

10000

690

300

1700

4100

780

Note: Some dimension drawings are not included in this manual. Please request from BROAD or download CAD files
from www.broad.com.





Packaged DFA P&I Diagram

Packaged Steam Chiller


(similar for BSY: steam chiller, BHY: hot W chiller, BEY: exhaust chiller)

ZF

RP
SP
VP
LQFJ
F22
F24
F25

ZG

ZF

ZG

ZD

ZD

A/C W
hot W

G9

G9

G9

cooling
w pump

auto dosing
device

W softner

ZE

ZE

G9 G9
G G W5
ZE
W2

F26

G9

W3 G

A/C W
pump

BF2
BF3
BF4

hot w pump

**

YB
KF
BM

ZD

city water

ZC
ZD

ZB

JOW6
JOW7

ZD

Pumpset control cabinet

heating w heater**

G3:

ZB3

G26

U5

G4

C3

condenser

U26

refrigerant pump
solution pump
air vent pump
cooling tower fan
auto purge valve
refrigerant motor valve
hot water thermostatic
valve**
heating water thermostatic
valve*
fuel gas main solenoid valve
fuel gas work solenoid valve
fuel gas ignition solenoid
valve
drain motor valve
control cabinet fan
burner

U28

SE

C2 C4 C2B U3 U3B

G2:

G36

F1

HTG

F2

ZL2

U21

F3
F4

U6

CD

U6B

U25

CN

G38

HTHE

U4

TH2

CG3
Q2

G35
G32

G31

TQ
U23

G:
SQ

QS

JOW4

G5

Auto purge/vent system

LTHE

up!G26
G25

U22

JOW2

CG:
H4

H2

CG9

G27

G24

G22
G23

CBT

building automation system (optional)

F21
F27
F28
F29
F30
YA1

DDT

Multi-unit control interface(optional)

YA2

U:

fuel gas
machine room draft fan

F20

LG

internet

(supplied with enclosure)

fuel oil

Notes:
1.
chiller scope
2. Parts marked with ** are not applicable
to cooling/heating type, and those
marked with * & ** are not applicable
to cooling only type.

F13
F14
F15
F16
F17
F18
F19

CG2

T9 for outdoor installation

U24

UT

W4 G

G7

G21

QMD chiller control cabinet


ZL4

G8

Q3

G6

G33

WQ

TH3

F8
F9
F10
F11
F12

CG5 CG4

G39

ZL5

F5
F6
F7

ZL3

evaporator

absorber

U2

G2

3. Line type:
actuator output
sensor input
communication

ZF

ZD

Sensors:

INV1 solution pump inverter


INV3 refrigerant pump inverter
INV5 cooling tower inverter
(for 2 fans)
INV6 cooling W pump inverter
touch screen
TS
PLC programmable logic
controller

T1
T2
T2A
T3
T4
T5
T6
T7
T9
T10
T11

Controlled Objects:

ZG

refrigerant pump
solution pump
air vent pump
cooling tower fan
auto purge valve
refrigerant motor valve
heating W thermostatic
valve*
F38 heat source motor valve
(exhaust motor valve is
optional)
YB drain motor valve
KF control cabinet fan
RP
SP
VP
LQFJ
F22
F24
F26

ZD
A/C W

G9

G9

G9

G9
G W2

W3 G
ZE

ZE

city water

ZC
ZD

ZB

JOW6
Pumpset control cabinet
JOW7

ZD

discharge valve
water makeup valve
manual water
makeup valve
CG1 HTG compound
gauge
CG2 Main shell
compound gauge
RD rupture disc
YD
YE
YF

ZB3

T12
T13
T14
T15
B1
B1A
B2
B3
GY
YK1
YK2
YK3
YK4
V1
V2
V5
V6
S
P

FE
BF1
BF8
BF9
P1
P2
PR
G1
G3
YA
YC

chilled /heating W. switch


valve
chilled/heating W outlet
single valve*
steam angle valve
concentrated solution
angle valve
diluted solution angle valve
HTG concentration
regulating valve
LTG concentration
regulating valve
water system shutoff valve
refrigerant sampling valve
LTHE sampling valve
HTHE sampling valve
diluted solution sampling
valve
main purge valve
direct purge valve
HTG purge valve
sampling purge valve
balance valve
main shell pressure
detecting valve
HTG pressure detecting
valve
vacuum vent valve &
mannual valve
nitrogen charging valve
chilled water drain valve
cooling water drain valve
heating water drain valve*
hot water drain valve**
hot water pressure release
valve**
heating water pressure
release valve*
auto water make up valve
fuel gas ball valve
fuel oil filter discharge valve,
fuel oil filter vent valve
lower limit pressure switch
upper limit pressure switch
fuel gas pressure regulator
gas filter
oil filter
auto air vent
manual drain valve

LTG

SE HZ

HTG

G4

condenser

U26

heating W heater*

G26

C3 U5

Others:

DH2

G29
G3

ZG

G3:

HZ

U7

G3

Control Devices:

GF

GF
ZF

**

ZB2

G41

DH3

MRGK

chilled W inlet temp sensor


chilled W outlet temp sensor
chilled W calibration temp sensor
cooling W inlet temp sensor
cooling W outlet temp sensor
HTG temp sensor
heat source outlet temp sensor
heat source inlet temp sensor
ambient temp. sensor
HTG crystallization sensor
LTHE diluted solution inlet temp.
sensor
LTG crystallization sensor
control cabinet temp sensor
heating W inlet temp sensor*
heating W outlet temp sensor*
chilled W flow switch
chilled W flow switch
cooling W flow switch
chilled W flow switch
pressure control
HTG solution level probe
refrigerant level probe
non-condensable gas sensor
auto vent probe
A/C W flow meter
cooling W flow meter
condensate flow meter
(optional)
heat source W flow meter
(optional)
conductivity sensor
differential pressure sensor
(optional)

hot w heater

U27

G37

LTG

G28

G28 G28
MRGK

A/C W pump

Controlled objects:
GF

GF

G28

cooling W pump

T1 chilled W inlet temp sensor


T2 chilled W outlet temp sensor
T2A chilled W calibration temp
sensor
T3 cooling W inlet temp sensor
T4 cooling W outlet temp sensor
T5 HTG temp sensor (to PLC)
T5A HTG temp control (to burner)
T6 exhaust temp sensor
T9 ambient temp sensor
T10 HTG crystallization sensor
T11 LTHE diluted solution inlet temp
sensor
T12 LTG crystallization sensor
T13 control cabinet temp sensor
T14 heating W inlet temp sensor*
T15 heating W outlet temp sensor*
T16 hot w inlet temp sensor**
T17 hot w outlet temp sensor**
B1 chilled W flow switch
B1A chilled W flow switch
B2 cooling W flow switch
B3 chilled W flow switch
GY pressure control
YK1 HTG solution level probe
YK2 refrigerant level probe
YK3 non-condensable gas sensor
YK4 auto air vent probe
V1 chilled/heating W flowmeter
V2 cooling W flowmeter
V3 gas flowmeter
V4 hot W flowmeter
S
conductivity sensor
P differential pressure sensor
(optional)
SG1 burner gas leakage sensor
SG2 machine room gas leakage
sensor

W softener

MRGK

INV1 solution pump inverter


INV3 refrigerant pump inverter
INV5 cooling tower inverter
(for 2 fans)
INV6 cooling water pump
inverter
TS
touch screen
PLC programmable logic
controller
BC burner control

auto dosing device

G28

G28 G28
MRGK

Sensors:

G3

C2 C4

C2B

U3

DH2

Others:

H5

F1
F2
F3
F4

G2:

ZL2

G37
U8

DH3
U3B

steam inlet

G49

G29 U21

U6

G3

heat source W inlet


U7 exhaust inlet

G
W7 heat source W outlet

U25

exhaust outlet

HTHE

G2

U2

G38

U4

absorber

ZL3

evaporator

G47
G46

G39

G35
G5

G32

ZL5

G:

G31
TQ
G8

Auto purge/vent system

G28

Control devices:

up!G26 G33
G25

LTHE

U7
G

U22

G7

G21

G27

G24

G22
G23
T9 for outdoor installation

U24

UT

G48

U23

JOW2

QMD chiller control cabinet


ZL4

G6

condensate heat
exchanger

JOW4

SQ

U:

LG

WQ

CBT building automation system (optional)

draft fan

Internet

DDT multi-unit control interface (optional)

Notes:
1.
chiller scope.
2. The components marked with for steam chiller, and marked
with for exhaust chiller, for hot W chiller.
3. The components marked with * are N.A with cooling only models.

4. Line type:

W6 condensate
outlet

chilled/heating W switch valve


A/C W outlet check valve*
steam angle valve
concentrated solution angle
valve
F5 diluted solution angle valve
F6 HTG concentration regulating
valve
F7 LTG concentration regulating
valve
F8 water system shutoff valve
F9 refrigerant sampling valve
F10 LTHE sampling valve
F11 HTHE sampling valve
F12 diluted solution sampling valve
F13 main purge valve
F14 direct purge valve
F15 HTG purge valve
F16 sampling purge valve
F17 balance valve
F18 main shell pressure detecting
valve
F19 HTG pressure detecting valve
F20 vacuum vent valve & mannual
valve
F21 nitrogen charging valve
F27 chilled W drain valve
F28 cooling W drain valve
F29 heating W drain valve
F35 steam trap
F36 condensate by-pass valve
F37 anti-freeze drain valve
YA2 heating W pressure release valve
FE auto W make-up valve
YA auto air vent
YC manual drain valve
YD discharge valve
YE W make-up valve
YF manual W make-up valve
CG1 HTG compound gauge
CG2 main shell compound gauge
G4 filter (N/A for exhaust chiller)
RD rupture disc

actuator signal output


sensor signal input
communication





Packaged Single-stage Steam Chiller

Packaged Exhaust & Direct-fired Chiller

(similar for BDSY: Single-stage steam chiller, BDHY: Single-stage hot W chiller, BDEY: Single-stage
exhaust chiller)

GF

ZG

Controlled Objects:

ZG

ZF

G9

ZD

G9

W3 G

G
ZE

ZE

ZC
ZD

ZB

W2

YB
KF

A/C W pump

city water

RP
SP
A/C W VP
AP
LQFJ
F22
F24
F38

G9

G9

cooling W pump

W softener

auto chemical dosing device

ZD

refrigerant pump
solution pump
air vent pump
absorption pump
cooling tower fan
auto purge valve
refrigerant motor valve
heat source motor valve
(exhaust motor valve is
optional)
drain motor valve
control cabinet fan

Control devices:

Sensors:

INV1 solution pump inverter


T1
INV3 refrigerant pump inverter T2
INV5 cooling tower inverter
T2A
T3
(for 2 fans)
INV6 cooling W pump inverter T4
TS
T5
PLC touch screen
T6
programmable logic
T7
controller
T9
T11

MRGK

GF
ZF

Control Devices:

G28

G28

T12
T13
B1
B1A
B2
B3
GY
YK1
YK2
YK3
YK4
V1
V2
V5
S
P

chilled W inlet temp sensor


chilled W outlet temp sensor
chilled W calibration temp sensor
cooling W inlet temp sensor
cooling W outlet temp sensor
generator temp sensor
heat source W outlet temp sensor
heat source W inlet temp sensor
ambient temp sensor
heat exchanger diluted solution inlet
temp sensor
generator crystallization sensor
control cabinet temp sensor
chilled W flow switch
chilled W flow switch
cooling W flow switch
chilled W flow switch
pressure control
generator solution level probe
refrigerant level probe
non-condensable probe
auto purge sensor
A/C W flow meter
cooling W flow meter
condensate flow meter(optional)
heat source W flow meter
conductivity sensor
differential pressure sensor(optional)

G28

G9

G9

ZL2

U8

U6
U3B

DH3

U7

G29

U2

G38

concentration regulating valve


W system shut-off valve
refrigerant sampling valve
concentrated solution sampling
valve
F12 diluted solution sampling valve
F13 main purge valve
F14 direct purge valve
F16 sampling purge valve
F17 balance valve
F18 pressure detecting valve
F20 vacuum vent valve & mannual
valve
F21 nitrogen charging valve
F27 chilled W drain valve
F28 cooling W drain valve
FE auto W make-up valve
YA auto vent valve
YC manual drain valve
YD discharge valve
YE W make-up valve
YF manual W make-up valve
CG2 compound gauge
G4 filter(N/A for exhaust type)

absorber

evaporator

H5
G
W6

steam inlet
heat source W inlet
exhaust inlet

G49
condensate outlet
heat source W outlet
exhaust outlet

ZL3

U4

G39
G35
G32

ZL5

G:

G31

Auto purge/vent system

TQ

U23

W2 G

G9
GW5

A/C W
pump
Q

ZC
ZD

ZD

SQ

ZB3

G3:

SE HZ

C3 U5

G4 G37

G3

C2 C4

C2B

U3

U7

DH3

U3B

HTG

G3

G29

DH2

exhaust inlet

U7C

U21

U6
CD

U6B

U2

G38

absorber

evaporator

exhaust
outlet

CN

ZL3

HTHE

U4

G39

Others:!

G4: H5

U9

ZL2

U25

G2

CG4

CG5
TH2

G35
G:
G32

ZL5

CG3

SQ

LTHE

G21

G27

G22
G23

chiller control cabinet

WQ

UT

G8
G7

JOW2

G24

QMD

G6

CG9
H2

U22

up!G26 G33
G25

CG:
H4

G5

U23

TQ

Q2
Q3

QS

JOW4

G31

U24

LG

W4 G
CG2

T9 for outdoor
U: installation

BQ
U22

G27

G8
chiller control cabinet

G24

G21
G23

U24

UT

U:

QMD

WQ

Internet

T9 for outdoor
installation

LG

CBT

building automation system (optional)

DDT

multi-unit control interface (optional)

Notes:
3. Line type:
1.
chiller scope.
2. The components marked with for steam chiller, and
marked with for exhaust chiller, for hot W chiller.

actuator signal output


sensor signal input
communication

building automation system (optional) CBT


TH3
multi-unit control interface (optional) DDT
draft fan
(supplied with enclosure)

internet

chilled W inlet temp sensor


chilled W outlet temp sensor
chilled W calibration temp sensor
cooling W inlet temp sensor
cooling W outlet temp sensor
HTG temp sensor (to PLC)
HTG temp control (to burner)
exhaust temp sensor
waste heat outlet temp sensor
exhaust inlet temp sensor
ambient temp sensor
HTG crystallization sensor
LTHE diluted solution inlet temp sensor
LTG crystallization sensor
control cabinet temp sensor
heating W inlet temp sensor*
heating W outlet temp sensor*
hot W inlet temp sensor**
hot W outlet temp sensor**
chilled W flow switch
chilled W flow switch
cooling W flow switch
chilled W flow switch
pressure control
HTG solution level probe
refrigerant level probe
non-condensable sensor
auto air vent probe
chilled/heating W flowmeter
cooling W flowmeter
gas flowmeter
hot W flowmeter
conductivity sensor
differential pressure sensor (optional)
burner gas leakage sensor
machine room gas leakage sensor

G36 G2:

LTG

condenser

U26

ZL4

JOW2

ZL4

draft fan

JOW4

LTHE

G33
G25

ZE

cooling
w pump

ZB

Auto purge/vent system

HZ
generator
condenser

U3

G9

G9

ZE

city water

F7
F8
F9
F10

C2B

ZG

W3 G

Others:

C2 C4

ZF

ZD

Sensors:!

T1
T2
T2A
T3
T4
T5
T5A
T6
T6A
T8
T9
Controlled
objects:
ZD
T10
RP refrigerant pump
T11
A/C W
SP solution pump
T12
VP air vent pump
T13
hot W
cooling
tower
fan
LQFJ
T14
G9
F22 auto purge valve
T15
F24 refrigerant motor valve
T16
ZE
F25 hot water thermostatic valve**
T17
F26 heating water thermostatic valve* B1
hot w pump**
BF2 fuel gas main solenoid valve
B1A
BF3 fuel gas work solenoid valve
B2
ZD
BF4 fuel gas ignition solenoid valve
B3
YB drain motor valve
GY
KF control cabinet fan
YK1
BM burner
YK2
JOW6 Pumpset
YK3
JOW7 control
YK4
cabinet
V1
V2
V3
V4
S
hot w heater**
heating w heater**
U28
U27
P
ZB2
SG1
G26
G41
SG2

GF

ZG

INV1 solution pump inverter


INV3 refrigerant pump inverter
INV5 cooling tower inverter
(for 2 fans)
INV6 cooling water pump inverter
TS touch screen
PLC programmable logic controller
BC burner control

G28

MRGK

JOW6
Pumpset control cabinet
JOW7

ZD

C3 U5

G28 G28

MRGK

GF
ZF

W softener

G28
MRGK

auto dosing device

G28

fuel gas

fuel oil

Notes:
1.
chiller scope
3. Line type:
2. Parts marked with ** are not applicable to cooling/
actuator output
heating type, and those marked with * & ** are not
sensor input
applicable to cooling only type.
communication

F1 chilled/heating W switch valve


F2 chilled/heating W outlet single valve*
F3 steam angle valve
F4 concentrated solution angle valve
F5 diluted solution angle valve
F6 HTG concentration regulating valve
F7 LTG concentration regulating valve
F8 water system shutoff valve
F9 refrigerant sampling valve
F10 LTHE sampling valve
F11 HTHE sampling valve
F12 diluted solution sampling valve
F13 main purge valve
F14 direct purge valve
F15 HTG purge valve
F16 sampling purge valve
F17 balance valve
F18 main shell pressure detecting valve
F19 HTG pressure detecting valve
F20 vacuum vent valve & mannual valve
F21 nitrogen charging valve
F27 chilled water drain valve
F28 cooling water drain valve
F29 heating water drain valve*
F30 hot water drain valve**
YA1 hot water pressure release valve**
YA2 heating water pressure release valve*
FE auto water make up valve
BF1 fuel gas ball valve
BF8 fuel oil filter discharge valve,
BF9 fuel oil filter vent valve
P1 lower limit pressure switch
P2 upper limit pressure switch
PR fuel gas pressure regulator
G1 gas filter
G3 oil filter
YA auto air vent
YC manual vent valve
YD discharge valve
YE water makeup valve
YF manual water makeup valve
CG1 HTG compound gauge
CG2 Main shell compound gauge
RD rupture disc





Packaged Multi-energy Chiller

Micro Non-electric Chiller

(similar for BZHEY: Hot W, exhaust & direct-fired chiller)

G28

G28 G28

MRGK

G28
MRGK

ZG

ZG

ZF

ZD

ZD
A/C W
hot W

W softener

auto dosing device

G9

G9

G9

W3 G

G9

ZE

ZE

cooling
w pump

G9

W2 G G W5

G9
ZE
hot w pump**

A/C W
pump

ZD

city water

ZC

Sensors:!

INV1 solution pump inverter


INV3 refrigerant pump inverter
INV5 cooling tower inverter
(for 2 fans)
INV6 cooling water pump inverter
TS
touch screen
PLC programmable logic controller
BC burner control

T1
T2
T2A
T3
T4
T5
T5A
T6
T7
T8
T9
T10
T11

Controlled objects:

GF
ZF

vent

Control devices:

RP
SP
VP
LQFJ
F22
F24
F25
F26
F38
F39
BF2
BF3
BF4
YB
KF
BM

refrigerant pump
solution pump
air vent pump
cooling tower fan
auto purge valve
refrigerant motor valve
hot water thermostatic valve**
heating water thermostatic valve*
heat source W motor valve
exhaust motor valve(optional)
fuel gas main solenoid valve
fuel gas work solenoid valve
fuel gas ignition solenoid valve
drain motor valve
control cabinet fan
burner

ZD

ZB

JOW6
JOW7

ZD

Pumpset
control
cabinet

hot w heater**

heating w heater** U28

ZB3

G3:

G26

C3 U5

condenser

U26

LTG

U27

U7

U21

SG1
SG2

ZB2 U7B G49 H5 heat source


W inlet

G41
HZ
SE
DH2
G36 G2:

G4
G37

heat source
W outlet

T12
T13
T14
T15
T16
T17
B1
B1A
B2
B3
GY
YK1
YK2
YK3
YK4
V1
V2
V3
V4
S
P

chilled W inlet temp sensor


chilled W outlet temp sensor
chilled W calibration temp sensor
cooling W inlet temp sensor
cooling W outlet temp sensor
HTG temp sensor (to PLC)
HTG temp control (to burner)
exhaust temp sensor
heat source W inlet temp sensor
exhaust inlet temp sensor
ambient temp sensor
HTG crystallization sensor
LTHE diluted solution inlet temp
sensor
LTG crystallization sensor
control cabinet temp sensor
heating W inlet temp sensor*
heating W outlet temp sensor*
hot W inlet temp sensor**
hot W outlet temp sensor**
chilled W flow switch
chilled W flow switch
cooling W flow switch
chilled W flow switch
pressure control
HTG solution level probe
refrigerant level probe
non-condensable gas sensor
auto air vent probe
chilled/heating w flowmeter
cooling W flowmeter
gas flowmeter
hot W flowmeter
conductivity sensor
differential pressure sensor
(optional)
burner gas leakage sensor
machine room gas leakage
sensor

Auto purge/vent system

C2 C4

C2B

U3

U3B

DH3
G29

HTG

hot air
U9

hot W

U8

X3

W8

V5

[IG

3
G

C4

V2

21

G6

V7

STC

STK

CD

U6

anti-sludge

hot W
W9

fuel inlet

X2

G2

G5

GE

:
ZDH

W7
G

U: U3

A/C W

biocide

[IG
GC

U22

5
L[H

V3

GB

net cable

ZDH

power cable
G4

Others:

chilled/heating W switch valve


chilled/heating W outlet single
U7C
ZL2
valve*
G3
F3 steam angle valve
exhaust outlet F4 concentrated solution angle valve
F5 diluted solution angle valve
U25
U6
F6 HTG concentration regulating valve
U6B
CD
F7 LTG concentration regulating valve
F8 water system shutoff valve
ZL3
CN
U2
G2
evaporator
absorber
F9 refrigerant sampling valve
F10 LTHE sampling valve
G38
F11 HTHE sampling valve
CG4
U4
CG5
HTHE
F12 diluted solution sampling valve
TH2
G39
F13 main purge valve
G35
G:
CG3
F14 direct purge valve
Q2
F15 HTG purge valve
Q3
JOW4
F16 sampling purge valve
CG:
QS
ZL5
G32 G31
F17 balance valve
SQ
TQ
G6
U23
G5
F18 main shell pressure detecting valve
H4
LTHE
U22
F19 HTG pressure detecting valve
CG9
G33
H2
F20 vacuum vent valve & mannual valve
G8
F21 nitrogen charging valve
G21
up G26
F27 chilled water drain valve
JOW2
G7
W4 G
F28 cooling water drain valve
G25
G27
F29 heating water drain valve*
G22
CG2
F30 hot water drain valve**
G23
chiller control cabinet
YA1 hot water pressure release valve**
ZL4 G24
U24
YA2 heating water pressure release
UT
T9 for outdoor
QMD
U:
valve*
installation
LG
WQ
FE auto water make up valve
BF1 fuel gas ball valve
BF8 fuel oil filter discharge valve
BF9 fuel oil filter vent valve
building
automation
system
(optional)
CBT
fuel gas fuel oil
TH3
draft fan
P1 lower limit pressure switch
internet
DDT multi-unit control interface (optional)
P2 upper limit pressure switch
(supplied with enclosure)
PR fuel gas pressure regulator
G1 gas filter
G3 oil filter
G4 waste heat filter
Notes: 1.
chiller scope
3. Line type:
YA auto air vent
2. Parts marked with ** are not applicable
YC manual vent valve
actuator output
YD discharge valve
to cooling/heating type, and those
YE water makeup valve
sensor
input
marked with * & ** are not applicable
YF manual water makeup valve
to cooling only type.
communication
CG1 HTG compound gauge
CG2 Main shell compound gauge
RD rupture disc
G3

vent

U7

ZS

V4

SQ

exhaust inlet F1

GF

G3

ZE

F2

U2

C2 C3

GD

A/C W

MRGK

MRC

LUTC

water make-up

V6

U4

TQ

timing drain

5V[L!
1 HTG
2 LTG
3 condenser
4 evaporator
5 absorber
6 HTHE
7 LTHE
8 cooling tower
9 auto purge device
10 hot W . heater*

SP
RP
KTSB
LQB
RSB
LQFJ
RSJ
F1
F2
F3
F4
F5
V6

solution pump
refrigerant pump
chilled/heating W pump
cooling W pump
hot W pump
cooling tower fan
burner
cooling/heating switch
vent three-way valve
vent reflow valve
HTG concentration
regulating valve
vacuum vent valve &
mannual valve
chilled/heating W
flowmeter

V7
V8
YR
YD
FE

heating W flow meter


gas flowmeter
refrigerant valve
drain device( timer on)
water make-up floating
ball valve
YCG cooling water quality
stabilizer valve(manual)
FA non-condensable
chamber purge
valve(manual)
FB direct purge
valve(manual)
FC solution valve(manual)
FD fuel valve(manual)

ZHF
KZG
BC
T1
T2
T3
T5
T6
T7
T8
T9

check valve
outdoor control cabinet
burner control
A/C W inlet temp sensor
A/C W outlet temp sensor
cooling W inlet temp
sensor
HTG temp sensor (to PLC)
ambient temp sensor
exhaust temp sensor
hot W temperature sensor
A/C W calibration temp
sensor

Notes:
1. Parts marked with " * " are for hot water, not applicable to cooling-heating type.
Parts marked with " ** " are for heating operation, not applicable to cooling only type.

T11
W1
W2
B1
B2
B3
U1
U2
U3
U4
U5
U6

control cabinet temp sensor


HTG temp switch
hot W temp switch
A/C W flow switch
A/C W flow switch
hot W flow switch
HTG solution level probe
refrigerant level probe
non-condensable sensor
LTG crystallization sensor
cooling W level probe
vent over level probe

2. Line type:
actuator output
sensor input



Scope of Supply/Work

Machine Room Construction Tips


BROAD Customer Remarks

Electric
engineering

Construction
& installation

Welding machine and nitrogen to be provided by


customers . Customers need to pay BROAD for joint.

3 phase, 4 wires

Grounding

Place special grounding terminal with grounding


resistance 4 near water system control cabinet

Foundation

Enclosure should be installed after foundation is


completed.

Installation of metal enclosure

Pipe connection between


chiller and pumpset

Pipe connection between


chiller and cooling tower

External piping installation

Power supply to enclosure


Internet connection

Chiller insulation

Piping insulation in enclosure

Network cable to the enclosure is to be provided by users

Antifreezing

Commissioning Jobsite chiller commissioning

Operation &
maintenance

Operator training on site

Regular maintenance

Ventilation: poor ventilation leads to high humidity


in the machine room, which may erode the unit. So
serious attention should be paid to ventilation in the
machine room. Please ventilate 2X machine rooms
ever y hour and make up the combustion air. The
volume of combustion air for a DFA is estimated at
1.3 m 3 for every kW fuel.

! Humidity:

Machine room humidity must be lower than


85%. Higher humidity may impair insulation of electrical
components.

! Chiller

! Please

capacity:
a. The machine room foundation load is recommended
as 1.5 times of the operation weight.
b. Make sure that the foundation is level without sinking
or overload (for rooftop installation).
c. The load of a chiller is evenly distributed on the
contact surface between the frame base rolling
steel and the plinth.

machine room.

!Anchor

above the drainage.


Includes chilled/heating water pipes, hot water pipes,
water make-up and drain pipes, energy source
pipes.

Water anti-freeze treatment is recommended when


the ambient temp is below 0C.

refer to dimension drawings for plinth dimensions.

!Load

! Drainage:

b. All discharge pipes and drain pipes must be visible

service space

Foundation

a. Chiller foundation must be on a high level in the


BY400 model, a crane must be provided by
customer

factory-mounted

pipeline insulation

Machine rooms must be well ventilated with temp.


humidity control and drain functions. It contains the
service space.
Attention should be paid to machine room built by
customers:

c. Machine room in basement must be built above


a water ditch, which is equipped with an auto levelcontrolled submerged pump.
! Temperature:

Machine room temperature must be


controlled within 5 -43C. Lower temperature may
crack copper tubes and water box when the chiller is
shut off; higher temperature may damage electrical
components. Thermometer and over temperature

bolts:
a. Chiller can be placed on the foundation directly
without bolts (if there is a strong earthquake source
or special anti-vibration requirement, please specify
in a purchase order).
b. Anchor bolts must be pre-installed for pumpset
foundation per dimension drawings.

alarm must be installed in machine room.

User provides energy and air conditioning load.


Customers need to pay BROAD for commissioning.
Paid service contract can be signed after the
warranty period.

service space

right

F
rear

front

tube service clearance


(can be at the front/rear side)

Jobsite handling (main shell,


pumpset)
Joint (for split shipment)

BROAD can arrange transportation upon request.

1500

Transportation factory to port


and location
port to jobsite

Machine room

1000

Item

1300

Category

left

1500

1500

Service space:
Mode 20

unit: mm
50

75

100

125

150

200

250

300

400

500

600

800

1000

2300

3200

3700

3700

4500

4500

4500

5500

5500

5500

7000

7000

7000

9000

650

800

900

1100

1150

1300

1700

1700

1950

2100

2400

2400

2600

2600

1. If the machine room is smaller than the above size, please contact BROAD for a solution.
2. F, G is the tube service clearance that can use space of water pumps, doors or windows and
can also be shared by 2 chillers.
3. It is recommended that the height of the machine room be 500mm higher than that of chillers.





Control System

Gas system

standard pressure is 16 -50kPa. Lower or higher


pressure can be accommodated to special orders.
valve should be installed at the lowest part of gas
pipes. All connecting pipes must be cleaned and tested
for air tightness with 0.6Mpa air when gas piping system
is completed.
! When two or more units are connected in parallel, a
buffer pipe (with diameter 3-6 times of the main pipe)
must be installed at the main pipe to avoid flameout
due to gas low pressure caused by simultaneous startup.
Manual drain valve should be equipped at the bottom
of the buffer tube.
! Customers are required to inform BROAD of the fuel
type, heating value and pressure so that a burner can
be properly selected and the gas pipe diameter can be
notified to customers. Then customers can design filter,
flow meter, ball valve, diffuser tube and pressure meter.
BROAD is responsible for installation of gas train valves
within supply scope. External gas piping system is to be
installed by customers to 1m distance from the burner.
!The ball valve of BROAD gas valve train must be closed if
customers need to test piping pressure so that gas train
valve will not be damaged by high pressure.
! A gas leakage alarm (acting value must be set 20%
lower than danger value lower limit) must be equipped
in machine room and be linkage controlled with draft
fans. Machine room must be well ventilated all the time.
! Drain

Oil system
! Oil

system includes oil storage tank, oil pump, daily oil


tank, oil filter and metering instruments. Oil tank should be
equipped with oil check nozzle, air vent (breather valve),
oil refill valve, oil level sensor and drain valve. The lowest oil
level of daily oil tank must be 0.1m higher than the burner.
! Oil pipe should be copper pipe or seamless steel pipe
and leakage test should be taken at 0.8MPa min.
!
Medium filters are to be installed at inlet and outlet of oil
storage tank. The filters should have enough section area,
and should be convenient to install/uninstall and drain.
!Oil tank should be equipped with precision metering device.

Steam system
! The

supply of the steam should be pressure-stable. The


upper limit should not be over 110% of the rated pressure.
If the pressure may exceed the upper limit, a regulating
valve should be equipped in the pipeline.
! Safety valve should be fixed in the steam inlet pipeline.
The protection value is adjusted as 110%-130% of its
working pressure. The safety valve should be connected
to outdoor to avoid the overpressure of the system.
! Condensed water should be able to drain smoothly.
Condensed water can be stored in an open tank beside
the chiller, and then pumped back to the boiler by a
condensed water pump or steam trap pressurizer.

! When

the distance between cooling tower and


machine room is3 0 m, the cooling water pipe
diameter can follow the dimension drawing. If its
30-90m, the pipe diameter shall be one size larger. If
its >90m , the pipe diameter shall be two size larger.
! In water system, zero resistance filter with section
area 8-15 times larger than pipe section area instead
of Y-shape filters shall be used to minimize the water
resistance.
! Soft connector must be installed at inlet/outlet of
chilled/cooling water and hot water system. The
weight of the external piping system can never be
borne by the chiller.
! The installation site of the cooling tower should be
far from heat source and power, especially should
be at least 6m far from the chimney, or the chimney
should be 2m higher than the top of the cooling
towe r. Othe r w i se the ex haust may access the
cooling tower and cause corrosion to copper tubes
inside the chiller.
! Piping requirements: all pipes and valves should not
go across the space above the chiller to avoid chiller
damage caused by pipe installation, maintenance
or leakage.
! Secondar y heat exchange hot water system is
recommended for areas with very hard water.
! Hot W. system for BY20,BY50 must adopt secondary
heat exchange.

heating W ambient temp


outlet temp sensor(installed outside
sensor
under eaves)
T15

rain cover

! The

wind shield

inspection door

sweeping
door
condensate drain

fouling
collector
discharge
pipe
inserted in
water

An exhaust system!illustration
Ventilation system is included in machine room supply
if BROAD packaged chiller is ordered.

alarm

enclosure
temp sensor
TY0
fireprotection
linkage

machine
room
control
cabinet

29
BROAD DFA

internet

chiller power cable


power

control
cabinet

1#chilled/
heating W
pump
2#chilled/
heating W
pump
1#cooling W
pump

multi-units control
interface( max. 4
units)

! It

lightning rod

enclosure
draft fan

SG2

T9

11

is recommended independent stack be used for


each chiller. If chillers have to share a common stack
due to space limitation, the shared stack must be
inserted type and the main stack must be bigger
and higher to avoid any interference from each
other. Exhaust motor valve shall be installed for each
exhaust duct to avoid corrosion caused by exhaust
entering into chillers that are not in operation.
! The exhaust volume is dependent on the fuel heat
input. It is estimated at 1.55m3 per kW fuel input. 3-5m/s
flue gas flow velocity in the stack is recommended.
Fouling collector should be installed at flue duct inlet
to the chiller to prevent condensate from flowing
directly into the chiller. The indoor flue duct must be
insulated. For high outdoor steel stack, insulation shall
be done to maintain the up force of flue. No insulation
is required for low outdoor steel exhaust stack. Try to
locate the exhaust outlet as far as possible from the
cooling tower, or 2m higher than the cooling tower.
Otherwise the flue gas may get into cooling tower
and damage the chiller.
! The rated exhaust temperature is 160C. However,
selection of insulation mater ials and design of
f i re i so l at i o n a rea s h o u l d be ba sed o n 3 0 0 C
temperature for safety concern.

touch screen( installed gas leakage


detector(gas
in place convenient
fired type)
for operation)

TS

Exhaust system

Water system

initial filling of the chilled/heating water must be


with soft water. The leakage rate should be less than 10%
every year, or else large amount of city water makeup
will cause water system fouling.
!Minor leakage in chilled/heating water system is made up
from the expansion water tank. An open expansion water
tank instead of a closed expander is recommended
for pressure balance. The water expansion volume is
calculated as 4% of total water volume in the system.
! Chiller, pump set and cooling tower should be in one to
one correspondence to achieve more energy saving.
!BROAD packaged chiller (pumpset) has introduced auto
dosing system to solve the conventional problems with
cooling water system such as corrosion inhibitor and
biocide, especially legionnaire. There is a motor drain
valve at the bottom of cooling water system (It's with
BROAD packaged chiller supply).

heating W

customer selfpurchased
pumpset,
cooling tower

2#cooling W
pump
packaged
water
distribution
system
control
cabinet

1#hot W
pump
2#hot W
pump
anti-sludging
agent pump
biocide
pump

T17
hot W outlet
temp sensor
hot W .

dry contact
serial
communication
ProfiBus
ModBus
Host Link
BACnet
Lonwork
various other
communication
protocols

10m

! The

10m

Piping System

power cable
control wire
sensor wire

cooling W
drain valve
1#cooling
tower fan

communication cable
telephone line or network

n#cooling
tower fan

cable

Notes:
1. BROAD Packaged chiller control system includes control interfaces for chiller, pumpset, cooling tower, outdoor
enclosure, internet remote monitoring, BMS and multiple-unit control,etc.
2. Pumpset and cooling tower control interface and water distribution system control cabinet are supplied with
pumpset. Enclosure control cabinet and relevant electrical parts are supplied with enclosure.
3. The customers who order several standard packaged chillers can choose multiple-unit control interface, which
can automatically control the number of operational chillers according to load changes.
4. BMS control interface includes "Serial Communication" and "Dry-contact" options. Serial Communication
interface can be either HostLink, ModBus, ProfiBus, BACnet or Lonwork protocol. They are all options.
5. If the customer does not order pumpset, standard control interface for pumpset and cooling tower will be provided.





Exterior Wiring Diagram

List of Control System Installation

Power

M2!M3!M4!O!QF

Item

Chiller control cabinet


packaged pumpset, cooling
tower control interface
chiller power

communication control

chilled W 3-level
protection!
control interface for non-BROAD
pump set and cooling tower
chilled W 3-level
protection!
1# A/C W pump
on/off
2# A/C W pump
on/off
power
on
1# cooling runnW pump
ing
frequency
2# cooling W
pump running
on/off
power
on
cooling fan running
frequency
hot W pump
on/ off
antisludge pump
on/off
biocide pump
on/off
cooling W drain
valve on/off

M2
M3
M4
O
QF

MZ12
MZ13
MZ14
O111
QF

W2,

WJ,

DBOI

DBOI

ESBJ
DBOM
W2.
761
762

ESBJ
DBOM
W2.
1127
W2,

ML2V
ML2W
ML2X

NL2

1# A/C W . pump

ML3W
ML3V
ML3X

NL3

2# A/C W . pump

MR2V
MR2W
MR2X

NR2

1# cooling W . pump

MR3V
MR3W
MR3X

NR3

2# cooling W . pump

NX2

1# hot W . pump

Packaged
water
MX2V
distribution
MX2W
system
MX2X
control
cabinet

761
762
711
719
712
71:
713
721
731
732
J5,
J5.

MX3V
MX3W

NX3

2# hot W . pump

NU13
O12

NU

antisludge pump

NT13
O12

NT

biocide pump

MX3X

714
722
715
723
733
734
J6,
J6.

GQ13
GQ14
O12

cooling W . drain valve

MG2V
MG2W
MG2X

716
724
763
764
76:
771
766
767
768

M[12
M[13
M[14
O
QF

MGoV
MGoW
MGoX

121
122

ambient temp

21B
21C
21C

multi-unit
control
interface
(optional)

CEI
CEM
TIME

touch screen
communication
interface

BMS control
on
dry contact
(optional)

dilution off
fault
BMS on

M2
M3
M4
O
QF

ZU1
ZU2
ZU2

BMS off

internet interface

n# cooling tower fan

gas leakage sensor

!TH3

GM
GO

NG
draft fan

Z2M
Z2O
connect
other
units( max.
4 units)

machine room lighting

fire-protection
linkage
shielded cable
non-shielded cable
touch screen

751
752
753
755
754
756
757
758
W2,
337
338

BROAD standard packaged


chiller supply scope

Notes:
BMS control
system

communication cable

SK56

NGo

Z35,

121
122

TE9
TE7
SE3
SE2

communication interface
(optional)

1# cooling tower fan

enclosure
temp sensor

metal enclosure Z35.


Z135
interface
safety linkage!

NG2

connection
to internet

1. BROAD Packaged pumpset control interface


and water distribution system control
cabinet will not be supplied if pumpset is
not ordered, but a control interface for user
self-purchased pumps and cooling tower is
available. Enclosure control cabinet and
relevant electronic devices are not supplied
if enclosure is not ordered.
2. If customers source pumpsets, cooling towers
locally, there must be 3-level chilled water
protection and a cooling water pump linkage.

Chiller

Chiller and
pumpset
grounding
Chiller power

Touch screen

Network
monitoring

Installation position and Material


requirement
Grounding resistance 4 Grounding wire

Source
BROAD
scope
Customer /

Control cabinet of chiller 5-core cable


and water system
(10m standard
supply)

BROAD

Anywhere in office (on


the wall or desk) humidity
0-85%
(no condensate),
temperature 0 - 30C
Chiller control cabinet

BROAD

BMS interface
(optional)

Chiller control cabinet

Ambient
temperature
sensor

Ventilation and avoid


direct sunlight

Heating W outlet
temperature
sensor,
hot W outlet
temperature
sensor
Pumpset Installation of
water distribution
system control
cabinet
and power
connection
Wiring between
chiller and water
distribution
system control
cabinet
Wiring between
pumpset and
water distribution
system control
cabinet

At heating W/ hot W
pipe outlet side 10m
away from the chiller

5-core shielded
cable
(30m standard
supply)
Network cable

Wiring
inside chiller
control
cabinet
Wiring
inside chiller
control
cabinet

Customer Wiring
inside chiller
control
cabinet
Communication Customer Wiring
cable (for serial
inside chiller
communication),
control
11-core cable (for
cabinet
dry contact)
BROAD
Chiller
3-core cable
(standard cable is
control
10m)
cabinet
wiring
3-core cable
BROAD
Wiring
(standard cable is
10m)

Customer scope
Grounding setup
and wiring
Cable
installation

Cable
installation

Cable
installation,
wiring at building
side
Cable
installation,
wiring at network
side
Temperature
sensor installation
wiring*
Temperature
sensor
installation

Water distribution system Installation bolts


control cabinet
5-core cable

Customer Wiring
Cable &
inside chiller control cabinet
control
installation
cabinet

Between chiller and


Cable supply as
water distribution system per packaged
control cabinet
chiller

BROAD

Wiring
Cable
inside chiller installation
control
cabinet

Between water
distribution system
control cabinet and
pumpset

BROAD

Wiring
Cable
inside chiller installation
control
cabinet

Cable supply
as per standard
pumpset





Transportation Tips

Lifting & Leveling Tips

Shipping status

! Lifting

! BY20

is to be shipped in one piece, while BY30 BY50 in two


pieces.
! BY75-1000 chiller and pumpset are to be shipped
separately.
! BY75-400: pumpset and control cabinet are to be
shipped in 3 pieces.BY500-1000: pumpset and control
cabinet are to be shipped in 3-5 pieces (A/C water
pumpset, cooling water pumpset and control cabinet)
! All equipment can be containerized as per "Container
Arrangement Reference".
! Chillers BZ75, BE75, BS100(Max. width 2.1m) in single
piece.
! Other units will be in 2-4 pieces shipment.
! If limited by site space or machine room access, small
unit can also be split shipment (or split with steel frame),
or steel-joint split shipment (i.e. the main shell and HTG

are split and soldered by steel plates, which will be


cut off before entering the machine room).
! When the unit reaches the machine room, the split
pieces need to be connected by BROAD welders.
The customer needs to prepare welding facilities,
nitrogen and other necessary help.
! Solution is charged into the chiller when a unit is
shipped in one piece, and packed separately for
split shipment or for single-piece shipment with unit
shipping weight over 32 tons.
! BROAD can arrange transportation and insurance
on behalf of customers. If the customer chooses
to arrange by themselves, please refer to BROAD
Chiller Packing & Transportation Regulations for
container arrangement and safe transportation.

Container arrangement reference:


Mode

BZ

With BY pump BYZ enclosure


set

BE

BS(BH)

BZHE

BDH(S)

20

20GP*

/*

40HQ(BY20)*

20GP*

20GP*

20GP*

20GP*

40HQ*

20GP

40OT2

40HQ

20GP2

40OT2

40HQ*

40HQ

40HQ*

40HQ+20GP*

125

40HQ+20GP

40GP

40OT2

40HQ+20GP

150

40OT+20GP

40GP

40OT2+20GP 40OT+20GP

40OT

40OT2

200

40OT+20OT

40GP+20GP 40OT2+20GP 40OT+20OT

40OT+20GP

40OT2

250

40OT2

40GP+20GP 40OT2+20GP 40OT2

40OT2

40OT2

300

40OT2

40GP+20GP 40OT3

400

40OT2
+20GP

40GP2

40OT3+20GP 40OT2+40GP 40OT2

500

40OT2
+20GP

40GP2

40OT3
+20GP

40OT3

40OT2
+20GP

40OT2
+40GP

600

40FR
+40OT2
+20GP

40GP2
+20GP

40FR+40OT2
+20GP

40FR+40OT
+20GP

40FR+40OT2
+20GP

800

40FR2
+40OT2
+40GP

40GP3
+20GP

40FR2
+40OT2
+40GP+20GP

40FR2
+40OT
+40GP

40FR2+40OT2
+40GP+20GP

1000

40FR2
+40OT2
+40GP
+20GP

40GP3
+20GP

40FR+40OT2
+40GP2

40FR2
+40OT1
+40GP

40FR2+40OT2
+40GP2

50
75
100

20GP*

/*

40HQ(BY50)*

20GP*

20GP*

40HQ*

20GP*

40HQ+20GP

40HQ+20GP 40HQ 2

40OT2+20GP 40OT2

40HQ*
40HQ*

40HQ*
40OT*

must be done by qualified lifting companies


that are properly insured.
crane must be suppor ted by crossties and
firm foundation to prevent it from sinking. Check
the crane steel ropes and hooks before lifting to
prevent any accident. The lifting intersection angle
must be less than 90. It is strictly prohibited to lift
the chiller with a single steel rope. When the chiller
is lifted 20mm above the carriage or the ground, it
should be kept for a little while. Lift the chiller slowly if
everything is OK.
!
The landing of the chiller must be with care. Crash
landing is strictly forbidden! As the unit is a vacuum
device, any impact on the chiller is strictly forbidden!
! When moving the chiller, only round steels or thick
steel tubes can be used as rollers instead of wooden
sticks. Only drag the dragging hole on the rolling
steel do not place forces on other part of the chiller.
Lift the unit first with jacks under the rolling steel
before rigging. Both sides of HTG and main shell must
be lifted simultaneously.
! Before the chiller is located, concrete foundation
plinths must be molded and leveled.
! Then locate the chiller without bolts. (If there is a
strong vibration source or a special anti-vibration
requirement, it should be stated before ordering).
The pumpset shall be fixed by anchor bolts. The
foundation must be level and solid to make sure no
sink or overload (when the unit is installed on the roof).
! The

! For

multiple chillers of split shipment, please make


sure the original matching between HTG and the
main shell. Please locate the chiller according to
chiller joint drawing and make sure the joint gap is
less than 1.5mm.
! After chiller locating, please adjust leveling and
lay thin steel plate where it is uneven to guarantee
compact contact between the chiller and base.
Take tube sheet as the leveling point and make front/
rear and left/right leveling (check level height of
every part by acrylic tube). It should be leveled within
0.8/10 0 0 both lengthwise and sidewise. Leveling
must be done within 2 hours after locating the chiller,
otherwise the chiller base will be damaged.
! The chiller must be located levelly and its steel frame
bases must match the plinth, the weight of the chiller
must be evenly balanced on the plinth. Otherwise,
the chiller may be twisted slowly, which will finally
result in damage due to leakage.
!The chiller should be protected by full time personnel
during transportation & installation. No access to
the chiller or valves for unauthorized persons. Valves
of the chiller are forbidden to be screwed. If the
machine room is under construction, protective
measures are needed to avoid damage or dirt to the
chiller. Do not scrape the paint or insulation layer.

40OT*

40OT*
40OT*

Sketch of leveling and foundation

40OT2+20GP 40OT+20GP*
40OT2+40GP 40FR+20GP*

Leveling sketch

Foundation sketch
Points for leveling(on tube sheet)

40FR+20GP*

Notes: 1. Models marked with " * " are in one-piece shipment, and the rest in split shipment.
2. For chillers over model 500 (main shell weight exceeds requirement), there might be some changes
as per actual condition.
3. In case some countries may have limitation on dimension and weight, loading shall be arranged
accordingly.
4. BCT container arrangement:
!!
! 20GP: BCT16:13 units; or BCT23:10 units; or BCT70:3 units; or BCT115:2 units;
!!
! 40GP: BCT16:13 units; or BCT23:20 units;
!!
! 40HQ: BCT70:7 units; or BCT115:4 units.

rubber sheet)6 21nn*


steel plate)6 21nn*
filling with concrete
after leveling

Rolling steel

concrete foundation
(steel plate can also be used
for plinth above the ground)

Dragging hole

Lifting sketch

<90

# 

Lifting
sketch

# 


Comparison



Energy saving comparison

General Comparison

Compared with conventional machine room mode, BROAD packaged pumpset system reduces the rated power
demand by 40-60%, and the operating electricity consumption by 60-75% (the electricity for pumpset only amounts to
2-5% of the rated cooling capacity.)

Examples on power consumption comparison


!

BY50 type (pumpset for 582kW/165Rt chillers)

Power consuming parts

Conventional machine room mode


power demand

30 kW

7.5 kW

27.5 kW

Cooling tower fan

11 kW

11 kW

311 kW

22 kW

7.5 kW

7.5 kW

Total

63 kW

26 kW

17 kW (annual)

10.8%

4.47%

2.92%

Annual operating consumption

190 MWh

52 MWh (power saving is 73%)

Electric Chillers

High
Chillers are less expensive but
customers self-purchased
water distribution system costs high.
Need separate hot water system.
Prevalently oversized
equipment selection.

Higher
Electricity demand is 8-10 times
more than that of non-electric
chillers.
Need boiler (and boiler room)
for heating.
High investment on water
distribution system.
Prevalently oversized
equipment selection.

Function

Two functions in one unit

Only one function Heat pump


has two functions, but its
heating capacity is reduced
dramatically or even lost when
the ambient temperature is low.

Energy
Efficiency

power demand

operating power consumption

Cooling capacity

180 kW

44 kW

1144 kW

Cooling tower fan

37 kW

37 kW

637 kW

Chilled/heating W pump

110 kW

60 kW

3060 kW

Total

327 kW

141 kW

100 kW (annual)

Electricity/cooling capacity

9.4%

4.04%

2.86%

Annual operating consumption

1000 MWh

300 MWh (power saving is 70%)


Reliability

Pursuing zero fault


The annual tube freezing rate in evaporator
is as low as 0.05%, as it is equipped with 3-level
temperature sensors, 3-level flow switches and
ultrasonic flow meters.
Separate heating reduces number of parts
involved in heating by 80%+, and doubles the
lifespan of the main shell.
Auto purge/ vent prevents metals from
corrosion and makes sure no cooling capacity
decrease.
Water distribution system is factory made so
that industrialization of central air conditioning
is materialized.All aspects from designing to
component quality control, production,
testing, site commissioning and maintenance
are integrated into a uniform quality control
system.
All materials and components are outsourced
from worlds top manufacturers (quality comes
first at any time).

Many faults
Number of moving parts is
several times more than that of
non-electric chillers, and they
are easy to be damaged.
Water distribution system is
designed individually,
purchased separately and
installed by non-professionals
with great quality risks.
Since it does not include
cooling water auto treatment
device, the copper tubes that
easily get scaled must be
cleaned by acids, which
will easily cause attenuation or
even puncture of the copper
tubes.

Safety

Risk free
Risky
The worlds only non-electric chiller with complete Not completely certified.
No comprehensive
American and European safety certificates
High temperature generator is equipped with
8-level mechanical and electronic anti-explosion
devices to ensure explosion free (even in case of
sabotage).
Cooling water system is with auto biocide device
to eliminate legionnaires' disease

Uncertain

Customers are worry-free & carefree.


A single purchase order to solve all ordering,
installation and operation problems
Automatic operation of the equipment and
system makes full-time operator unnecessary.
Provide life-long maintenance & repair, or even
operation management service (energy
management contract). Life-long quality
commitment.

BY1000 type (pumpset for 11630kW/3307Rt chillers)


power demand

operating power consumption

Cooling capacity

550 kW

180 kW

30180 kW

Cooling tower fan

110 kW

110 kW

22110 kW

Chilled/heating W pump

440 kW

180 kW

90180 kW

Total

1100 kW

470 kW

250 kW (annual)

Electricity/cooling capacity

9.5%

4.04%

2.15%

Annual operating consumption

3300 MWh

750 MWh (power saving is 77%)

Packaged pumpset system

Notes: 1. Calculation of annual operating power consumption is based upon cooling operation, 5 months per year
and 20 hours per day.
2. Operating consumption is the result of using inverters and shifting between two pumps, while the power
consumption of conventional pump system equals to the power demand.

Why electricity saving &


!

Saving from design: 1. Many innovations reduce the resistance from filters, valves and piping to almost zero.
2. Specially designed pumps optimize head and flow rate to system design.
Saving from operation: 1. BROAD leads the world in inverter control system design and operation. Standard
designs incorporate inverter-controlled cooling water pump(s) and cooling tower fan(s) which are automatically
adjusted according to load and ambient temperature. 2. Two pumps combined or separate operation by
software analyzer. 3. Actual power consumption during operation is 30-60% of the rated design.

Energy saving is visible.

Not energy-saving.
Energy mode not energy-saving.
No flow meters.
No energy efficiency
display(not out of technical
reasons,probably not willing to
take the responsibility).
Tear & wear of moving parts
causing energy efficiency
decrease.

Packaged pumpset system

Power consumption equipment Conventional machine room type


power demand

Three functions in one unit


Provide cooling, heating and hot water
simultaneously or dedicatedly, and automatically
adjust all temperatures.

Energy consumption is not


transparent.
No flow meters.
(fuel, chilled/heating water, cooling water, hot
No energy efficiency display
water) to reflect the energy efficiency directly
(not out of technical reasons,
or indirectly.
The touch screen real time displays (and records)
probably not willing to take the
responsibility).
cooling capacity and energy efficiency.
Dozens of energy saving patents assure initial
No auto air vent device so
and long-term energy efficiency, such as auto
energy efficiency drops
purge and air vent (without a vacuum pump
periodically.
in the life span), plate heat exchanger,upward
spraying, refrigerant anti-overflow, turbulator in
fire tubes, etc.
Cooling water system is equipped with water
softner and biocide & antisludge auto dosing
device to eliminate energy waste and cooling
capacity decrease caused by fouling.
Conduct yearly energy consumption investigation
and diagnosis to each user.
BROAD chillers are proven that at least 50% more
energy saving per our energy investigation to
thousands of users.

BY300 type (pumpset for 3489kW/992Rt chillers)

Power consumption equipment Conventional machine room type


power demand

Other Non-electric Chillers

operating power consumption

electricity/cooling capacity

BROAD Non-electric Chillers

Packaged pumpset

power demand
Cooling water pump
Chilled/heating W pump

Mode

Investment Low
Chiller price is high but water distribution
system invests low. (design + equipment +
installation + commissioning +machine
room)
Small footprint.
Smaller equipment selection

Ultrasonic flow meters are installed on all pipes

Numerous faults
Annual tube freezing rate
exceeds 5%.
Main shell heating brings many
faults and short life design.
No auto air vent device causes
periodical cooling capacity and
energy efficiency decrease.
Water distribution system is
designed individually, purchased
separately and installed by nonprofessionals with great quality
risks.
Since it does not include cooling
water auto treatment device, the
copper tubes that get scaled
must be cleaned by acid, which
will easily cause attenuation or
even puncture of the copper
tubes.

Anti-explosion measures.
No biocide dosing

Customers are not carefree.


Customers are not carefree.
Purchase and installation of water
Purchase and installation of
distribution system are troublesome. water distribution system are
The whole system is a combination
troublesome.
The whole system is a
of products from many
manufacturers, making it impossible combination of products from
to actualize automation.
many manufacturers,
Poor after-sale service.
making it impossible to actualize
automation.
Poor after-sale service.

ISO9001

BROAD central air conditioning has obtained all certification of ISO,CE, UL, ETL,

ASME, and other international certication

N

To preserve forest & water sources,


pls imitate us to adopt compact
layout & thin paper printing

BROAD Town , Changsha , China 410138 , www.broad.com


Tel +86-731-84086688 Fax 731-84611357

2011.06