Application

HONEYWELL MICRONIK 200 APPLICATION

&RQWHQWV

3DJH

CONTROLLER APPLICATION OVERVIEW

GENERAL

1R

'LVFKDUJH$LU7HPSHUDWXUH&RQWURORI9HQWLODWLRQ6\VWHPV

3DJH

'

CONTROL OF HOT WATER HEATING COIL OR CHILLED WATER COOLING COIL


FOR FULL OUTSIDE AIR PLANTS

'

'

CONTROL OF HOT WATER HEATING COIL OR CHILLED WATER COOLING COIL


IN RECIRCULATION AIR VENTILATION SYSTEMS

'

'

SEQUENCE CONTROL OF AN ENERGY RECOVERY SYSTEM WITH


A HOT WATER HEATING COIL

'

'

SEQUENCE CONTROL OF AN ENERGY RECOVERY SYSTEM WITH


A CHILLED WATER COOLING COIL

'

'

SEQUENCE CONTROL OF HOT WATER HEATING COIL AND CHILLED WATER


COOLING COIL AND TWO POSITION (OPEN/CLOSED) DAMPER CONTROL

'

'

SEQUENCE CONTROL OF ENERGY RECOVERY SYSTEM, HOT WATER HEATING


AND CHILLED WATER COOLING COILS

'

'

SEQUENCE CONTROL OF MIXED AIR DAMPERS AND HOT WATER HEATING COIL

'

'

SEQUENCE CONTROL OF MIXED AIR DAMPERS AND CHILLED WATER COOLING COIL

'

'

SEQUENCE CONTROL OF MIXED AIR DAMPERS, HOT WATER AND


CHILLED WATER VALVES

'

'

CONTROL OF ELECTRIC AIR HEATER BATTERY OR DIRECT EXPANSION


COOLING SYSTEM (UP TO 6-STAGES/STEPS)

'

'

SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL

'

'

SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER


COOLING COIL AND TWO POSITION (OPEN/CLOSE) DAMPER CONTROL

'

'

SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL

'

'

SEQUENCE CONTROL OF ENERGY RECOVERY SYSTEM, ELECTRIC AIR HEATER AND


CHILLED WATER COOLING COIL

'

'

SEQUENCE CONTROL OF ENERGY RECOVERY SYSTEM, ELECTRIC AIR HEATER AND


CHILLED WATER COOLING COIL

'

'

SEQUENCE CONTROL OF MIXED AIR DAMPERS, ELECTRIC AIR HEATER AND


CHILLED WATER COOLING COIL

'

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

1R

5RRP5HWXUQ$LU7HPSHUDWXUH&RQWURO

3DJH

R1

ROOM/CONTROL WITH LOW LIMIT DISCHARGE AIR TEMPERATURE CONTROL OR ROOM/RETURN


AIR DISCHARGE AIR TEMPERATURE CASCADE CONTROL OF A HOT WATER HEATING COIL OR
CHILLED WATER COOLING COIL FOR FULL OUTSIDE AIR PLANTS

R1-1

R2

ROOM/CONTROL OF HOT WATER HEATING COIL OR CHILLED WATER COOLING COIL IN


RECIRCULATION AIR VENTILATION SYSTEMS

R2-1

R3

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF AN


ENERGY RECOVERY SYSTEM WITH A HOT WATER HEATING COIL

R3-1

R4

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF


AN ENERGY RECOVERY SYSTEM WITH A CHILLED WATER COOLING COIL

R4-1

R5

ROOM/DISCHARGE AIR CASCADE SEQUENCE CONTROL OF HOT WATER HEATING COIL AND
CHILLED WATER COOLING COIL AND TWO POSITION (OPEN/CLOSED) DAMPER CONTROL

R5-1

R6

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ENERGY RECOVERY


SYSTEM, HOT WATER HEATING AND CHILLED WATER COOLING COILS

R6-1

R7

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS


AND HOT WATER HEATING COIL

R7-1

R8

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS


AND CHILLED WATER COOLING COIL

R8-1

R9

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS,


HOT WATER AND CHILLED WATER VALVES

R9-1

R10

ROOM/CONTROL WITH LOW LIMIT DISCHARGE AIR TEMPERATURE CONTROL OR ROOM/RETURN


AIR - DISCHARGE AIR TEMPERATURE CASCADE CONTROL OF ELECTRIC AIR HEATER BATTERY
OR DIRECT EXPANSION COOLING SYSTEM (UP TO 6-STAGES/STEPS)

R10-1

R11

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ELECTRIC AIR


HEATER AND CHILLED WATER COOLING COIL

R11-1

R12

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ELECTRIC AIR


HEATER AND CHILLED WATER COOLING COIL AND TWO POSITION (OPEN/CLOSE) DAMPER
CONTROL

R12-1

R13

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ELECTRIC AIR


HEATER AND CHILLED WATER COOLING COIL

R13-1

R14

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ENERGY RECOVERY


SYSTEM, ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL

R14-1

R15

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ENERGY RECOVERY


SYSTEM, ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL

R15-1

R16

ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS,


ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL

R16-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

1R

+RWDQGFKLOOHG:DWHU'LVWULEXWLRQ6\VWHP&RQWURO

3DJH

W1

OUTSIDE AIR TEMPERATURE COMPENSATED SUPPLY WATER FLOW TEMPERATURE CONTROL

W1-1

W2

OUTSIDE AIR TEMPERATURE COMPENSATED HOT WATER FLOW TEMPERATURE CONTROL


WITH HIGH OR LOW LIMIT RETURN FLOW TEMPERATURE CONTROL

W2-1

W3

ROOM TEMPERATURE - SUPPLY HOT WATER TEMPERATURE CASCADE CONTROL

W3-1

&21752//(5$33/,&$7,2129(59,(:
The R7426A controller provides one output with one mode of operation, heating or cooling, and is suitable for the following
applications:

Space or return air temperature control

Discharge air temperature control

Space or return air temperature control with low limit discharge air temperature control

Cascade control of space or return air and discharge air temperature

Cascade control of space air and supply water temperature

Outside air compensated supply water temperature control with or without low or high limit return water
temperature control

Constant supply water temperature control with or without return water temperature limit control

The R7426B,C controllers provide three outputs for sequence control of heating, mixed air dampers or energy recovery
systems and cooling and are suitable for the following applications:

Space or return air temperature control

Discharge air temperature control

Cascade control of space or return air and discharge air temperature

Additional control function:

Compensation by outside air temperature of main setpoint, e.g. compensated space, return or discharge air
temperature

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

*(1(5$/

237,216)25$//$33/,&$7,216
Remote Control Point Adjustment (CPA). The controller control point can be remotely adjusted through a range of 5K using
a control point adjustment potentiometer in discharge air applications or a room sensor with control point adjustment
potentiometer in room control applications connected to terminals 2&4. The configuration parameter C.05 (CPATYP) has to be
set to 1, 2 or 4 in accordance to the used potentiometer resistance range.
Remote Setpoint Adjustment (RSA). The controller setpoint can be remotely adjusted through a range of 15...30C using a
room sensor with setpoint adjustment potentiometer connected to terminals 2&4. The configuration parameter C.05 (CPATYP)
has to be set to 3.
Comfort/Standby Mode. The controllers provide occupied and unoccupied temperature setpoints. Connecting a room
temperature sensor with occupied/unoccupied switch or a presence sensor to the controller occupancy input terminals 1&4
allows to change the controller into Comfort (closed contact) or Standby (open contact) mode.
Summer/Winter Compensation. When an outside air temperature sensor (T3) is connected to terminals 7&8 winter and/or
summer compensation of the main setpoint can be performed.
Summer/Winter Changeover. The occupancy input, terminals 1&4 on the R7426A controllers can alternatively be used to
switch the controller between summer (cooling) and winter (heating) operation in applications using a common valve for heating
and cooling control. In summer operation the controller provides a direct acting output (Y1), with an increase in the controlled
variable, i. e. room temperature increases, the output increases. In winter operation the controller output (Y1) is reverse acting,
with a decrease in the controlled variable the output increases. Summer/Winter changeover function is activated by setting the
configuration parameter C.15 (Y1CTRF) to 2. A potential free contact or strap-on thermostat connected to terminals 1&4 is
used to switch the controller mode to cooling (contact closed) or heating (contact open) control.

237,21621&21752//(56:,7+2875($/7,0(&/2&.
Controller ON/OFF Operating Mode. Connecting an external time clock or manual switch to the controller Plant/System
ON/OFF input terminals 9&10, the controller can be switched ON or OFF. In the OFF operating mode the controller
automatically generates zero position output signals on all outputs to drive the valve and damper actuators into the fully closed
position. In mixed air damper applications the outdoor and exhaust air dampers are closed and the return air damper is fully
open. The time clock also switches the fan(s) OFF and drives the damper actuators (6) in full outside air applications into the
closed position by an external installed relay, if the dampers are not controlled by the controller. In full outside air applications
the fan(s) switch ON after a time delay to allow the dampers time to open.
NOTE: For Terminals 9&10 see the following Figure

without Real Time Clock


ON/OFF

9
10

Plant /
System

Day/Night Setpoint Operation. An external time clock connected to the controller occupancy input terminals 1&4 provides
day/night main temperature setpoint control determined by the programmed offset parameter value P.16 (SOFFS) for those
heating or ventilation systems operating 24 hour per day.

6$)(7<)25$33/,&$7,21612'72'$1'5725
Safe Operation of Electric Heater Battery. The high limit thermostat (7) installed close to the electric heater battery switches
the electric air heater OFF at temperatures above its adjustable setpoint.
The air flow switch (10) also switches the electric heater battery OFF in the event of fan failure (no air flow). Alternatively, the
differential air pressure switch (9) across the discharge air fan can be used for the same function.
Filter Monitoring. The differential air pressure switch (8) closes a contact to issue an alarm at a differential pressure above its
adjustable setpoint to indicate that the filter is dirty and in need of maintenance.
Fan Monitoring. The differential air pressure switch (9) switches the fan motor OFF at a differential pressure below its
adjustable setpoint to indicate no air flow. An external time delay relay overrides the fan monitoring function for a short period
during start-up to avoid false alarms. The monitoring function is re-established after the adjustable time delay period.

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

237,2162)287387 < 23(5$7,21)25$33/,&$7,21612 %<


6(/(&7,212)<02'(
&RQWURORI(OHFWULF+HDWLQJ&RQILJXUDWLRQ3DUDPHWHU&<&75) 


VWDJH2Q2II6HTXHQFH&RQWURO<0RGH 

)XQFWLRQDO'LDJUDP

:LULQJ&RQQHFWLRQV

R7426A
Y1

Step2 on
Power

Step1 on

o pen /
O U T2

24V

20

21

out2
out1

on

close /
O U T1

22

off

24Vac Relays
25 30

65 70

100 %

Y1

Stage



VWDJH%LQDU\&RGHG2Q2II6HTXHQFH&RQWURO<0RGH 

)XQFWLRQDO'LDJUDP

:LULQJ&RQQHFWLRQV

R7426A
Step3 on
Step2 on

Y1

Power

Step1 on

o pen /
O U T2

24V

20

21

close /
O U T1

22

out2
out1

on

24Vac Relays

off
20 25

45 50

70 75

100 %

Y1

Stage

1
3



7LPH3URSRUWLRQDO&RQWUROE\3XOVH:LGWK0RGXODWHG2XWSXW<0RGH 

)XQFWLRQDO'LDJUDP

:LULQJ&RQQHFWLRQV

R7426A

The diagram shows as example, 60% Output Signal with


Motor RuntimeY1 set to 50 sec:

Y1

out1/out2
on

o pen /
O U T2

24V

20

21

22

A2

A1

off
30

50

70 80

100 sec

close /
O U T1

Note:
OUT1 or OUT2
or both can be
used to drive
Solid State Relays

Solid State Relay


RN1L40M25

Y1

L1

L2

100...440Vac

2Q2II&RQWURORI&RROLQJ&RQILJXUDWLRQ3DUDPHWHU&<&75) 


VWDJH2Q2II6HTXHQFH&RQWURO<0RGH 

See functional diagram and wiring connections of option 1 for electric heating.

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

237,2162)287387 < 23(5$7,21)25$33/,&$7,2161272%<


6(/(&7,212)<02'(
&RQWURORI(OHFWULF+HDWLQJ<0RGH 


VWDJH2Q2II6HTXHQFH&RQWURO<0RGH 

)XQFWLRQDO'LDJUDP

:LULQJ&RQQHFWLRQV

R7426B
Step2 on

Y3

Power

Step1 on

o pen /
O U T2

24V

26

27

out2
out1

on

close /
O U T1

28

off

24Vac Relays
25 30

65 70

100 %

Y3

Stage



VWDJH%LQDU\&RGHG2Q2II6HTXHQFH&RQWURO<0RGH 

)XQFWLRQDO'LDJUDP

:LULQJ&RQQHFWLRQV

R7426B
Step3 on
Step2 on

Y3

Power

Step1 on

o pen /
O U T2

24V

26

27

close /
O U T1

28

out2
out1

on

24Vac Relays

off
20 25

45 50

70 75

100 %

Y3

Stage

1
3



7LPH3URSRUWLRQDO&RQWUROE\3XOVH:LGWK0RGXODWHG2XWSXW<0RGH 

)XQFWLRQDO'LDJUDP

:LULQJ&RQQHFWLRQV

R7426B

The diagram shows as example, 60% Output Signal with


Motor RuntimeY3 set to 50 sec:

Y3
o pen /
O U T2

24V

26

27

28

A2

A1

out1/out2
on

off
30

50

70 80

100 sec

c los e /
O U T1

Solid State Relay


RN1L40M25

Y3

L1
100...440Vac

EN3C-0161 0698R0-MA

L2

Note:
OUT1 or OUT2
or both can be
used to drive
Solid State Relays

HONEYWELL MICRONIK 200 APPLICATION

2Q2II&RQWURORI&RROLQJ<PRGH 


VWDJH2Q2II6HTXHQFH&RQWURO<0RGH 

)XQFWLRQDO'LDJUDP

:LULQJ&RQQHFWLRQV

R7426B
Step2 on

Y2

Power

Step1 on

out2
out1

on

o pen /
O U T2

24V

23

24

close /
O U T1

25

off

24Vac Relays
25 30

65 70

100 %

Y3

Stage

237,2166(48(1&(23(5$7,21)25$33/,&$7,2161272
$SSOLFDWLRQ1R 6HOHFWLRQ<0RGH DQG<PRGH <0RGH <0RGH 
4-stage On/Off sequence control of cooling (Output Y1 & Y3) and 2-stage On/off sequence control of electric heating (Output
Y2). The wiring connections are the same as shown in application example no. 10.

$SSOLFDWLRQ1R 6HOHFWLRQ<0RGH DQG<PRGH <0RGH <0RGH 


4-stage On/Off sequence control of cooling (Output Y1 & Y3) and modulating control of heating valve. The wiring connections
are the same as shown in application example no. 11.

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

*5$3+,&$/6<0%2/6
Supply Air Fan
or
Return Air Fan

MicroniK 200
Controller

12

13

Duct Temperature Sensor


or
Outside Air Sensor,
Duct Mounting

Room Air Sensor

14

Heating Coil

Outdoor Air Sensor,


Wall Mounting

15

Energy Recovery Coil

Immersion Temperature
Sensor

16

Cooling Coil

Freeze Protection or
High Limit Thermostat in
Elektric Heating
Applications

17

Electric Heater

Remote Setpoint
Adjustment Potentiometer

18

Radiator

Room Air Sensor


with Remote Setpoint
Adjustment

19

Recirculation Pump

Room with
e. g. Room Air Sensor
and
Remote Setpoint
Adjustment Potentiometer

T
9

20

Filter

Damper Actuator

M
A
B

21

Valve/Actuator
3 - Way

AB
A
10

11

Differential Pressure
Switch

AB
23

Air Flow Switch

NOTE: Connections shown with dotted lines are options.

EN3C-0161 0698R0-MA

Valve/Actuator
2 - Way

22

24Vac/230Vac Relays
or
Solid State Relay
(Electric Current Valve)

HONEYWELL MICRONIK 200 APPLICATION

&21752/2)+27:$7(5+($7,1*&2,/25&+,//(':$7(5&22/,1*&2,/
'
)25)8//2876,'($,53/$176
A heating and ventilation system with constant discharge air temperature control is used where the base heating load is met by
radiators and the ventilation system provides the supply of fresh outside air.
In cooling applications it is also used to supply fresh outside air using a constant supply air temperature control system.

EA
6 M

11

0A
T
3

M
6

Y1
4

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor (1) measures the
actual value and the controller (4) compares this value with the desired
setpoint. If a deviation between the two values exists, the controller generates a
3-position control signal to reposition the valve (5) to maintain the desired
discharge air temperature. In heating applications the controller output is
reverse acting and direct acting for cooling applications.
Freeze Protection. The freeze protection thermostat (7) switches the heating
coil pump ON - if OFF - at temperatures below its adjustable setpoint. In parallel
it provides a digital input signal to the controller (4) to switch the fan(s) OFF and
close the dampers by an external installed relay logic and fully open the heating
valve (5) to prevent the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal
controller real time clock the different operating control modes Comfort,
Standby, Night or OFF are selected. In the OFF operating mode the controller
automatically fully closes the heating valve (5), switches the fan(s) OFF and
thereby closes the dampers (6) by an external installed relay logic.

Y1 (%)
100

Cooling

Heating

0
0
CTRP1 Ystart
Xp

Xw
T1

If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

D1-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

T6046A

T7411A/T7416A

11

T7412B

T7411A

NC C

2
CPA/
SPA

6
1

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426A

Y1
24V 24V

op en/
O U T2

24V

clo se/
O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5

ML6420A Heating or
Cooling

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426A1016 or
R7426A1008

Temperature Controller with clock or


without clock

ML6420A3007 and
V5.....A.....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D1-2

HONEYWELL MICRONIK 200 APPLICATION

&21752/2)+27:$7(5+($7,1*&2,/25&+,//(':$7(5&22/,1*&2,/
'
,15(&,5&8/$7,21$,59(17,/$7,216<67(06
Recirculation air systems with outside air compensated discharge air temperature control are used for ventilation in factories,
storage areas, department stores, etc. or for ventilation of machinery such as computers.

T
3
11

T
1
5

Y1
4

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor (1) measures
the actual value and the controller (4) compares this value with the actual
control point. The control point comprises the setpoint value which is
continuously compensated by the outside air temperature sensor (3) value.
If a deviation between the two values exists, the controller (4) generates a
3-position control signal to reposition the valve (5) to maintain the desired
discharge air temperature. In heating applications the controller output is
reverse acting and direct acting for cooling applications.
Time Control. Depending on the programmed time schedule of the internal
controller real time clock the different operating control modes Comfort,
Standby, Night or OFF are selected. In the OFF operating mode the
controller automatically fully closes the heating valve (5) and switches the fan
OFF.

Y1 (%)
100

Cooling

Heating

0
0
CTRP1 Ystart
Xp

Xw
T1

If the controller switches from OFF to ON mode the Plant/System On/Off


output switches the fan ON and the controller provides automatic control.

D2-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

T7416A

11

T7411B

T7411A/T7416A

2
CPA/
SPA

6
1

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426A

Y1
24V 24V

op en/
O U T2

24V

clo se/
O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5

ML6420A Heating or
Cooling

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

T7416A1006

Outside Air Temperature Sensor, Wall Mounting

R7426A1016 or
R7426A1008

Temperature Controller with clock or


without clock

ML6420A3007 and
V5.....A.....

Valve Actuator and


Valve

237,216
Item

Quantity

Part Number

Description

11

T7411B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D2-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)$1(1(5*<5(&29(5<6<67(0:,7+$+27:$7(5+($7,1*&2,/ '
For use with ventilation systems comprising of an energy (heat) recovery system and a heating coil.

10

EA
6

M
p

5b

11

0A
T
3

p
8

p
9

5a

Y3
Y1

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4) compares
this value with the desired setpoint. If a deviation between the
two values exists, the controller generates a 3-position control
signal on output Y1or Y3 to reposition either the energy
recovery valve (5b) or the heating valve (5a) in sequence to
maintain the desired discharge air temperature.
In an air-glycol-air heat recovery system it is important, to avoid
icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch
indicates icing of the coil, the control valve (5b) will be closed
by an additional field mounted relay. Return air and warm water
will be circulated through the exhaust air heat recovery coil to
melt the ice deposits.

Y (%)
100
Heating
Y3

Energy
Recovery
Y1
1/4 Xp

0
0
CTRPH
XpH

0
CTRP1

Xwh/Xw
T1

Xp

Freeze Protection. The freeze protection thermostat (7)


switches the heating coil pump ON, - if OFF - at temperatures below its adjustable setpoint. In parallel it provides a digital input
signal to the controller (4) to fully open the heating valve (5a), to switch OFF the fan(s) and close the dampers (6) by an
external installed relay logic to protect the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

D3-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

NC C

T6046A

T7411A/T7416A

11

T7412B

T7411A

6
1

2
CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

Y2
clo se/ op en/
O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5b

ML6420A Energy Recovery

5a

ML6420A Heating Valve

24V

3 - Way Valve

24V

2 - Way Valve

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a+5b

ML6420A3007 and
V5....A....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D3-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)$1(1(5*<5(&29(5<6<67(0:,7+$&+,//(':$7(5&22/,1*&2,/ '
For use with ventilation systems comprising of an energy (heat/cool) recovery system and a cooling coil.

10

EA
6

M
p

5b

11

0A
T
3

M
p

5a

Y2
Y1

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4)
compares this value with the desired setpoint. If a deviation
Y (%)
between the two values exists, the controller generates a
100
3-position control signal on output Y1 or Y2 to reposition
either the energy recovery valve (5b) or the cooling valve (5a)
Energy
in sequence to maintain the desired discharge air
Recovery
temperature.
Y1
MINPOS
If the actual temperature is below the setpoint, the controller
modulates via output Y1 the heat recovery valve (5b) into the
0
open position.
0
0
If the actual temperature exceeds the setpoint by more than
CTRP1 CTRPC
25% of the throttling range (Xp1) - dead band between
Xp
heating and cooling - the controller starts to open the energy
recovery valve (5b) to reclaim cooling energy. If the
temperature continues to increase and the energy recovery
valve is fully open, the controller (4) generates an output signal via Y2 to open the cooling coil valve (5b).

Cooling
Y2
0

Xwc/Xw

XpC

T1

In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5b) will be closed by an
additional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt the
ice deposits.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

D4-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

T7411A/T7416A

11

T7412B

T7411A

2
CPA/
SPA

6
1

T1

T2

9 10 11 12 13 14
ON/
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

Y2
clo se/ op en/
O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5b

5a

ML6420A Energy Recovery

2 - Way Valve

24V

3 - Way Valve

24V

ML6420A Cooling Valve

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a+5b

ML6420A3007 and
V5....A....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Temperature Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D4-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)+27:$7(5+($7,1*&2,/$1'&+,//(':$7(5&22/,1*&2,/
'
$1'7:2326,7,21 23(1&/26(' '$03(5&21752/
For use with ventilation system comprising of heating and cooling coils with full outside air dampers.

EA
6

M
p

11

0A
T
3

M
6

T
1

5b

5a

Y3

Y2

Y1
4

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4)
compares this value with the desired setpoint. If a deviation
between the two values exists, the controller generates a 3position control signal to reposition the heating or cooling
valves to maintain the desired discharge air temperature.
If the temperature is below the heating setpoint the heating
valve (5a) modulates via output Y3 and if the temperature is
above the cooling setpoint the cooling valve (5b) modulates
via output Y2 to maintain the desired discharge air
temperature.

Y (%)
100

Cooling
Y2

Heating
Y3
0
0

Damper Control. If the controller switches from OFF to ON


mode (Comfort, Standby or Night) the controller drives the
damper actuators to the open position via output Y1.
If the controller switches to the OFF mode, it drives the
dampers and valves automatically to their closed positions.

XpH

0
CTRPH CTRP1 CTRPC
Xp

0
XpC

Xwh/Xwc
T1

Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a) and close
the dampers (6) and cooling valve (5b) - if open - to prevent the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b) and dampers (6) and switches the fan(s) OFF.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a 3 minute time delay to allow the dampers time to
open. As alternative the end-position switches of the damper actuators can be used to start the fan.

D5-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
NC C

T6046A

T7411A/T7416A

11

T7412B

T7411A

6
1

2
CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426B

Y1
XWrh

24V 24V

open/
OUT2

24V

Y2
close/ open/
OUT1 OUT2

24V

Y3
close/ open/
OUT1 OUT2

24V close/
OUT1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
6

230Vac
ML6184E Damper open/closed

5b

5a

ML6420A Cooling Valve

Brown White Green

3 - Way Valve

24V

2 - Way Valve

24V

ML6420A Heating Valve

3 - Way Valve

24V

2 - Way Valve

24V

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a+5b

ML6420A3007 and
V5....A....

Valve Actuator and


Valve

ML6184E1009

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Temperature Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D5-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)(1(5*<5(&29(5<6<67(0+27:$7(5+($7,1*
'
$1'&+,//(':$7(5&22/,1*&2,/6
For use with ventilation system comprising of an energy (heat/cool) recovery system, heating and cooling coils.

10 p

EA
6

M
p

5c

11

0A
T
3

M
6

p
8

T
p

5b

5a

Y3

Y2

Y1
4

)81&7,21$/'(6&5,37,21

Y (%)
100

Energy
Temperature Control. The discharge air temperature sensor
Recovery
(1) measures the actual value and the controller (4) compares
Heating
Cooling
Y1
Y3
Y2
this value with the desired setpoint. If a deviation between the
two values exists, the controller generates a 3-position control
signal to reposition either the energy recovery valve (5c) or the
heating valve (5a) or the cooling valve (5b) in sequence to
0
maintain the desired discharge air temperature.
0
0
0 Xwh/Xwc/Xw
If the actual temperature is below the setpoint, the controller
CTRPH
CTRP1
CTRPC
modulates first via output Y1 the heat recovery valve (5c) into
XpH
Xp
T1
XpC
the open position and if fully open, the heating valve (5a) is
opened in sequence via output Y3. If the actual temperature
increases the sequence of operation is reversed.
If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating and
cooling - the controller starts to open the energy recovery valve (5c) to reclaim cooling energy. If the temperature continues to
increase and the energy recovery valve is fully open the controller (4) generates an output signal via Y2 to open the cooling coil
valve (5b).
In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5c) will be closed by an
additional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt the
ice deposits.

Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a), to switch
OFF the fan(s) and thereby to close the damper actuators by an external installed relay logic to protect the heating coil from
freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a, 5b and 5c) and switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

D6-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

T6046A

T7411A/T7416A

11

T7412A

T7411A

NC C

2
CPA/
SPA

6
1

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426B

Y1
X

Wrh

24V 24V

op en/
O U T2

24V

Y2
clo se/ op en/
O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
5c

230Vac
ML6420A Energy Recovery

5b

ML6420A Cooling Valve

5c

ML6420A Heating Valve

24V

1
2

24V

24V

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a+5b+5c

ML6420A3007 and
V5....A....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D6-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)0,;('$,5'$03(56$1'+27:$7(5+($7,1*&2,/ '
For use with ventilation systems comprising of mixed air dampers and a heating coil.

EA
M
6
6

11

0A
T
3

M
6

p
8

p
9

Y3
Y1
4

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4) compares
this value with the desired setpoint. If a deviation between the
two values exists, the controller generates two 0(2)10Vdc
control signals in sequence via outputs Y1 and Y3
corresponding to the 0100% correctional signal to reposition
the mixed air dampers or the heating valve to maintain the
desired discharge air temperature.
The minimum outside air damper position adjustment
(MINPOS) on the controller determines the position to which
the outside air damper will be driven even though the
temperature input condition demands that it should drive to the
fully closed position.

Y (%)
100

1/4 Xp
Heating
Y3

Damper
Y1

MINPOS
0
0
XpH

CTRPH

0
CTRP1

Xwh/Xw

CTRPC
T1

Xp

Freeze Protection. The freeze protection thermostat (7)


switches the heating coil pump ON - if OFF - at temperatures
below its adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5),
to close the outside and exhaust air dampers (6) and to switch OFF the fan(s) to protect the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the heating valve (5) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.

D7-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

T6046A

T7411A/T7416A

11

T7412A

T7411A

NC C

2
CPA/
SPA

6
1

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426C

Y2

Y1
X

Wrh

24V 24V

0..1 0V
2..1 0V

24V 24V

0..1 0V
2..1 0V

Y3

24V 24V 0..1 0V 24V 24V


2..1 0V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
6

230Vac
ML7284E Mixed Air Dampers

ML7420A Heating Valve

Green Brown White

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

ML7420A3006 and
V5....A....

Valve Actuator 0(2)...10Vdc and


Valve

ML7284E1006 or
ML7174E2007

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm
24Vac, 8Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Temperature Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D7-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)0,;('$,5'$03(56$1'&+,//(':$7(5&22/,1*&2,/ '
Used with ventilation system comprising of mixed air dampers and a cooling coil.

EA
M
6
6

11

0A
T
3

M
6

Y2
Y1

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4) compares
1/4 Xp
this value with the desired setpoint. If a deviation between the
Y (%)
two values exists, the controller generates two 0(2)10Vdc
100
Damper
control signals in sequence via outputs Y1 and Y2
Y1
corresponding to the 0100% correctional signal to reposition
the mixed air dampers (6) or cooling valve (5) to maintain the
desired discharge air temperature.
MINPOS
If the actual temperature is below the setpoint, the controller
modulates via output Y1 the mixed air dampers up to the
0
minimum position.
0
0
If the actual temperature exceeds the setpoint by more than
CTRP1
CTRPC
25% of the throttling range (Xp1) - dead band between heating
Xp
and cooling - the controller starts to close the outside and
exhaust air dampers and opens the return air damper. If the
temperature continues to increase and the mixed air dampers
reach the minimum position, the controller (4) generates an output signal via Y2 to open the cooling coil valve (5).

Cooling
Y2

Xwc/Xw

XpC

T1

The minimum outside air damper position adjustment (MINPOS) on the controller determines the position to which the outside
air damper will be driven even though the temperature input condition demands that it should drive to the fully closed position.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the cooling valve (5) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.

D8-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

T7411A/T7416A

11

T7412A

T7411A

2
CPA/
SPA

6
1

T1

T2

T3

9 10 11 12 13 14
ON/ 24V
OFF

R7426C

Y1
X

Wrh

24V 24V

0..1 0V
2..1 0V

24V 24V

Y2
0..1 0V
2..1 0V

Y3

24V 24V 0..1 0V 24V 24V


2..1 0V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
6

230Vac
ML7284E Mixed Air Dampers

ML7420A Cooling Valve

Green Brown White

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

ML7420A3006 and
V5....A....

Valve Actuator 0(2)...10Vdc and


Valve

ML7284E1006 or
ML7174E2007

Damper Actuator

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm
24Vac, 8Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Temperature Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D8-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)0,;('$,5'$03(56+27:$7(5$1'&+,//(':$7(59$/9(6 '
Use with ventilation system comprising of mixed air dampers, heating and cooling coils.

EA
M
6

11

M
6

0A
T
3

M
6

p
8

T
p

5b

5a

Y3

Y2

Y1
4

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor
1/4 Xp
Y (%)
(1) measures the actual value and the controller (4) compares
100
this value with the desired setpoint. If a deviation between the
Damper
Y1
two values exists, the controller generates three 0(2)10Vdc
control signals in sequence via outputs Y1, Y2 and Y3
Cooling
Heating
corresponding to the 0100% correctional signal to reposition
Y2
Y3
the mixed air dampers and heating and cooling valves to
MINPOS
maintain the desired discharge air temperature.
0
If the actual temperature is below the setpoint, the controller
0
0
0 Xwh/Xwc/Xw
generates first a 0(2)...10Vdc control signal via output Y1 to
CTRPH
CTRP1 CTRPC
reposition the mixed air damper (6). If the temperature
T1
XpH
Xp
XpC
continues to decrease and the mixed air dampers reached the
minimum position (MINPOS), the controller generates a
0(2)...10Vdc control signal via output Y3 to drive the heating valve (5a). If the temperature increases the sequence of operation
is reversed.
If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating and
cooling - the controller starts to close the mixed air damper (6). If the temperature continues to increase and the mixed air
dampers reached the minimum position (MINPOS), the controller (4) generates a 0(2)...10Vdc control signal via Y2 to position
the cooling valve (5b).
The minimum outside air damper position adjustment (MINPOS) on the controller determines the position to which the outside
air damper will be driven even though the temperature input condition demands that it should drive to the fully closed position.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a), to close
the outside and exhaust air dampers (6) and cooling valve - if open - and to switch OFF the fan(s) to prevent the heating coil
from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.

D9-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

T6046A

T7411A/T7416A

11

T7412A

T7411A

NC C

2
CPA/
SPA

6
1

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426C

Y2

Y1
X

Wrh

24V 24V

0..1 0V
2..1 0V

24V 24V

0..1 0V
2..1 0V

Y3

24V 24V

0..1 0V
2..1 0V

24V 24V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
6

230Vac
ML7284E Mixed Air Dampers

5b

ML7420A Cooling Valve

5a

ML7420A Heating Valve

Green Brown White

2
3

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

5a+5b

ML7420A3006 and
V5....A....

Valve Actuator 0(2)...10Vdc and


Valve

ML7284E1006 or
ML7174E2007

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm
24Vac, 8Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Temperature Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D9-2

HONEYWELL MICRONIK 200 APPLICATION

&21752/2)(/(&75,&$,5+($7(5%$77(5<25',5(&7(;3$16,21&22/,1*6<67(0
'
837267$*(667(36


Used with ventilation system using electric air heating, where the base heating load is met by a radiator heating system and
the ventilation system is used to ensure the supply of outside air.
Instead of electric heating, the controller can be used to control up to 6-stages of direct expansion cooling. The controller can
be configured to provide sequence control of electric heating and cooling as follows:
-

Heating mode:

Cooling mode:

4 stages, sequentially switched steps to operate external relays or


4 binary coded switching outputs to provide up to 15 load steps.
2 stages, sequentially switched steps to operate external relays.

EA
M
6

11

0A
T
3

M
6

10

Y1/Y2/Y3
4

)81&7,21$/'(6&5,37,21

Y1/Y2/Y3 (%)

Cooling

100

Temperature Control. The discharge air temperature sensor (1) measures the
actual value and the controller (4) compares this value with the desired setpoint.
If a deviation between the two values exists, the controller selects the number of
stages/steps required to maintain the desired discharge air temperature.
When configured for heating and cooling sequence operation, the controller will
first select the heating or cooling mode and than the number of stages/steps
required.

Heating

0
0
CTRP1 Ystart
Xp

Time Control. Depending on the programmed time schedule of the internal


controller real time clock the different operating control modes Comfort, Standby,
Night or OFF are selected. In the OFF operating mode the controller
automatically switches OFF the selected number of stages/steps and the fan(s)
and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time
delay by an external installed time delay relay. This allows the dampers time to
open. As alternative to the time delay relay the end-position switches of the
damper actuators can be used to start the fan.

Step6 on
Step5 on

Power

Step2 on
Step1 on
on
off

6 signal sequence of
Y3/Y2/Y1 out1/out2

10 15 25 30

D10-1

Xw
T1

70 75 85 90 100 %
Y3/Y2/Y1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

T7411A/T7416A

11

T7412B

T7411A

2
CPA/
SPA

6
1

T1

T2

9 10 11 12 13 14
ON/
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

Y2
clo se/ op en/
O U T1 O U T2

Y3

24V

clo se/ op en/


O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5

24Vac Relays
Heating or Cooling

Stage

Heating: 4 Linear or 15 Binary


Plus 2 Cooling

Stage

Stage
Stage

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

1 or
6

RY6

Auxiliary Relay Module with 6 relays or


24Vac coil

ML6184E1009 or
ML6684E1008

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D10-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)(/(&75,&$,5+($7(5$1'&+,//(':$7(5&22/,1*&2,/ '


Use with ventilation system comprising of an electric air heater and a cooling coil.

EA
M
6

11

0A
T
3

M
6

V
10

T
5b

5a

Y2
Y1/Y3
4

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor (1)
measures the actual value and the controller (4) compares this
value with the desired setpoint. If a deviation between the two
values exists, the controller selects the corresponding number of
stages/steps (up to 4 stages linear or 15 stages binary) for
heating or generates a 3-position control signal to reposition the
cooling valve to maintain the desired discharge air temperature.

Y (%)
100

If the temperature is below the heating setpoint the heating


stages are switched via output Y3 and Y1 and if the temperature
is above the cooling setpoint, the cooling valve (5b) is modulated
via output Y2.

Time Control. Depending on the programmed time schedule of


the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In
the OFF operating mode the controller automatically switches
OFF the selected number of heating stages/steps or closes the
cooling valve (5b), switches the fan(s) OFF and thereby closes
the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch
ON after a time delay by an external installed time delay relay.
This allows the dampers time to open. As alternative to the time
delay relay the end-position switches of the damper actuators
can be used to start the fan.

D11-1

Cooling
Y2

Heating
Y1/Y3

0
CTRPH CTRP1

XpH

Xwh/Xwc

CTRPC

Xp

T1

XpC
Step4 on

Power

Step3 on
Step2 on
Step1 on

Y1 out2
Y1 out1
Y3 out2
Y3 out1

on
off
20 25

40 45

60 65

80 85

100 %

Y3/Y1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

11

T7412B

T7411A

2
CPA/
SPA

6
1

T1

T2

9 10 11 12 13 14
ON/
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

Y2
clo se/ op en/
O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5a

24Vac Relays
Heating: 4 Linear or 15 Binary

5b

ML6420A Cooling Valve

Stage

3 - Way Valve

24V

24V

2 - Way Valve

Stage

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a

1 or
4

RY4

Auxiliary Relay Module with 4 relays or


24Vac coil

5b

ML6420A3007 and
V5...A....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D11-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)(/(&75,&$,5+($7(5$1'&+,//(':$7(5&22/,1*&2,/$1'7:2
'
326,7,21 23(1&/26( '$03(5&21752/


For use with ventilation system comprising of an electric air heater and a cooling coil with full outside air dampers.

EA
M
6

11

0A
T
3

M
6

V
10

T
5b

5a

Y2

Y3

Y1

)81&7,21$/'(6&5,37,21

Y (%)
100

Temperature Control. The discharge air temperature sensor


(1) measures the actual value and the controller (4) compares
this value with the desired setpoint. If a deviation between the
two values exists, the controller generates a pulse width
modulated output signal on output Y3 to control the solid state
relay (5a) or a 3-position control signal on output Y2 to
reposition the cooling valve (5b) to maintain the desired
discharge air temperature.
If the temperature is below the heating setpoint the solid state
relay(s) (5a) is modulated via output Y3 and if the temperature
is above the cooling setpoint the cooling valve (5b) is
modulated via output Y2.
Damper Control. If the controller switches from OFF to ON
mode (Comfort, Standby or Night) the controller drives the
damper actuators to the open position via output Y1.
If the controller switches to the OFF mode, it drives the
dampers and valves automatically to their closed positions.

Cooling
Y2

Heating
Y3
0
0

0
CTRPH CTRP1

XpH

Xwh/Xwc

CTRPC

Xp

T1

XpC

out1/out2

on

off
30

50

70

80

100 sec

Y3

Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically generates
on all outputs a 0% output signal to switch OFF the electric air heater, to fully close the cooling valve (5b) and dampers (6)
and to switch OFF the fan(s).
If the controller switches from OFF to ON mode, the fan(s) switch ON after a 3 minute time delay to allow the dampers time to
open. As alternative the end-position switches of the damper actuators can be used to start the fan.

D12-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

11

T7412B

T7411A

6
1

CPA/
SPA

T1

2
4

T2

9 10 11 12 13 14
ON/
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

Y2
clo se/ op en/
O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
6
5b

ML6184E Damper open/closed

Brown White Green

ML6420A Cooling Valve

3 - Way Valve

24V

2 - Way Valve

24V

1
A2 A1

5a

RN1L40M25 Solid State Relay (Current Valve)

L1

T1

100...440Vac

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a

up to 3

RN1L40M25

Solid State Relay (Current Valve)

5b

ML6420A3007 and
V5...A....

Valve Actuator and


Valve

ML6184E1009

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

3 or 4

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D12-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)(/(&75,&$,5+($7(5$1'&+,//(':$7(5&22/,1*&2,/ '


Used with ventilation system comprising of an electric air heater and a cooling coil.

EA
M
6

11

0A
T
3

M
6

V
10

T
5b

5a

Y2
Y3
4

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4)
compares this value with the desired setpoint. If a deviation
between the two value exists, the controller generates two
0(2)...10Vdc control signals in sequence via outputs Y2 and
Y3 corresponding to the 0...100% correctional signal to drive
the electric current valve (5a) for proportional control of the
electric air heater or to reposition the cooling valve (5b) to
maintain the desired discharge air temperature.

Y (%)
100

Cooling
Y2

Heating
Y3

If the temperature is below the heating setpoint the controller


generates a control signal on output Y3 to control the electric
current valve (5a) and if the temperature is above the cooling
setpoint, the controller generates a control signal on output
Y2 to position the cooling valve (5b).

0
0
XpH

0
CTRPH CTRP1 CTRPC
Xp

Xwh/Xwc

XpC

T1

Time Control. Depending on the programmed time schedule


of the internal controller real time clock the different operating control modes Comfort, Standby, Night or OFF are selected. In
the OFF operating mode the controller automatically generates 0% output signals on Y2 and Y3 to switch OFF the electric
heater, to close the cooling valve (5b) and to switch OFF the fan(s) by the Plant/System On/Off output and thereby close the
dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

D13-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

T7411A/T7416A

11

T7412B

T7411A

2
CPA/
SPA

6
1

T1

T2

T3

9 10 11 12 13 14
ON/ 24V
OFF

R7426C

Y2

Y1
X

24V 24V

Wrh

0..1 0V
2..1 0V

24V 24V

0..1 0V
2..1 0V

Y3

24V 24V

0..1 0V
2..1 0V

24V 24V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5b

ML7420A Cooling Valve

5a

R7425A/B Current Valve

2
8

10

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

5a

R7425A/B

Electric Current Valve

5b

ML7420A3006 and
V5....A....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

3 or 4

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D13-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)(1(5*<5(&29(5<6<67(0(/(&75,&$,5+($7(5$1'
'
&+,//(':$7(5&22/,1*&2,/


For use with ventilation system comprising of an energy (heat/cool) recovery system, an electric air heater and a cooling coil.

10 p

EA
6

M
p

5c

12

0A
T
3

M
6

p
8

11 5b

5a

Y3

Y2

Y1
4

)81&7,21$/'(6&5,37,21

Y (%)
100

Temperature Control. The discharge air temperature sensor (1)


measures the actual value and the controller (4) compares this
value with the desired setpoint. If a deviation between the two
values exists, the controller generates the corresponding control
signals to maintain the desired discharge air temperature.
If the actual temperature is below the setpoint the controller (4)
generates first a 3-position control signal via output Y1 to
reposition the energy recovery valve (5c) to reclaim heating
energy. If the temperature continues to decrease and the energy
recovery valve is fully open, the controller generates a pulse
width modulated output via output Y3 to drive the solid state relay
(5a) for proportional control of the electric air heater. If the
temperature increases the sequence of operation is reversed.

Heating
Y3

Energy
Recovery
Y1
1/4 Xp

Cooling
Y2

0
0
CTRPH
XpH

on

0
CTRP1
Xp

0 Xwh/Xwc/Xw
CTRPC
XpC

T1

out1/out2

If the actual temperature exceeds the setpoint by more than 25%


off
of the throttling range (Xp1) - dead band between heating and
30
50
70 80
100 sec Y3
cooling - the controller starts to open the energy recovery valve
(5c) to reclaim cooling energy. If the temperature continues to
increase and the energy recovery valve is fully open the controller (4) generates an output signal via Y2 to open the cooling coil
valve (5b).
In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5c) will be closed by an
additional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt the
ice deposits.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5b and 5c) and switches the electric air heater and the fan(s) OFF and thereby close the dampers (6) by an external
installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

D14-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

12

T7412B

T7411A

6
1

CPA/
SPA

T1

2
4

T2

9 10 11 12 13 14
ON/
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

Y2
clo se/ op en/
O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5c

ML6420A Energy Recovery Valve

5b

ML6420A Cooling Valve

24V

3 - Way Valve
2 - Way Valve

24V

24V

1
A2 A1

5a

RN1L40M25 Solid State Relay (Current Valve)

L1

T1

100...440Vac

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a

up to 3

RN1L40M25

Solid State Relay (Current Valve)

5b + 5c

ML6420A3007 and
V5....A....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

11

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

12

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D14-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)(1(5*<5(&29(5<6<67(0(/(&75,&$,5+($7(5$1'
'
&+,//(':$7(5&22/,1*&2,/


For use with ventilation system comprising of an energy (heat/cool) recovery system, an electric air heater and a cooling coil.

10

EA
6

M
p

5c

12

0A
T
3

M
6

11 5b

5a

Y1

Y3

Y2
4

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4) compares
this value with the desired setpoint. If a deviation between the
two values exists, the controller generates in correspondence
to the 0...100% correctional signal 0(2)...10Vdc control signals
in sequence via outputs Y1, Y2 and Y3 to position the energy
recovery or cooling valves or to drive the electric current valve
to maintain the desired discharge air temperature.

Y (%)
100
Heating
Y3

Energy
Recovery
Y1
1/4 Xp

Cooling
Y2

If the actual temperature is below the setpoint, the controller


0
0
0 Xwh/Xwc/Xw
generates first a 0(2)...10Vdc control signal via output Y1 to
CTRPH
CTRP1
CTRPC
reposition the energy recovery valve (5c) to reclaim heating
XpH
Xp
XpC
T1
energy. If the temperature continues to decrease and the
energy recovery value is fully open, the controller generates a
0(2)...10Vdc control signal via output Y3 to drive the electric current valve (5a) for proportional control of the electric air heater.
If the temperature increases the sequence of operation is reversed.
If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating and
cooling - the controller starts to open the energy recovery valve (5c) to reclaim cooling energy. If the temperature continues to
increase and the energy valve is fully open, the controller (4) generates a 0(2)...10Vdc control signal via Y2 to position the
cooling valve (5b).
In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5c) will be closed by an
additional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt the
ice deposits.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5b and 5c) and switches the electric air heater and the fan(s) OFF and thereby close the dampers (6) by an external
installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

D15-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

12

T7412B

T7411A

2
CPA/
SPA

6
1

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426C

Y2

Y1
X

24V 24V

Wrh

0..1 0V
2..1 0V

24V 24V

0..1 0V
2..1 0V

Y3

24V 24V

0..1 0V
2..1 0V

24V 24V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5c

ML7420A Energy Recovery Valve

5b

ML7420A Cooling Valve

5a

R7425A/B Current Valve

2
3

2
8

10

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

5a

R7425A/B

Electric Current Valve

5b + 5c

ML7420A3006 and
V5....A....

Valve Actuator 0(2)...10Vdc and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

11

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

12

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D15-2

HONEYWELL MICRONIK 200 APPLICATION

6(48(1&(&21752/2)0,;('$,5'$03(56(/(&75,&$,5+($7(5
'
$1'&+,//(':$7(5&22/,1*&2,/


For use with ventilation system comprising mixed air dampers, an electric air heater and a cooling coil.

EA
M

6
6

11

0A
T
3

M
6

V
10

T
5b

5a

Y3

Y1

Y2
4

)81&7,21$/'(6&5,37,21
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4) compares
this value with the desired setpoint. If a deviation between the
two values exists, the controller generates in correspondence to
the 0...100% correctional signal 0(2)...10Vdc control signals in
sequence via outputs Y1, Y2 and Y3 to position the mixed air
dampers or cooling valve or to drive the electric current valve to
maintain the desired discharge air temperature. If the actual
temperature is below the setpoint, the controller generates first
a 0(2)...10Vdc control signal via output Y1 to reposition the
mixed air damper (6). If the temperature continues to decrease
and the mixed air dampers reached the minimum position
(MINPOS), the controller generates a 0(2)...10Vdc control
signal via output Y3 to drive the electric current valve (5a) for
proportional control of the electric air heater. If the temperature
increases the sequence of operation is reversed.

1/4 Xp

Y (%)
100
Damper
Y1

MINPOS

Cooling
Y2

Heating
Y3

0
0
CTRPH
XpH

0
CTRP1
Xp

0 Xwh/Xwc/Xw
CTRPC
XpC

T1

If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating and
cooling - the controller starts to close the mixed air damper (6). If the temperature continues to increase and the mixed air
dampers reached the minimum position (MINPOS), the controller (4) generates a 0(2)...10Vdc control signal via Y2 to position
the cooling valve (5b).
The minimum outside air damper position adjustment (MINPOS) on the controller determines the position to which the outside
air damper will be driven even though the temperature input condition demands that it should drive to the fully closed position.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically generates
0Vac (0%) control signals via output Y1, Y2 and Y3 to fully close the outside and exhaust air dampers (6) and the cooling valve
(5b), open the return air damper and to switch OFF the electric air heater via the current valve (5a). In addition the fans are
switched OFF by the Plant/System On/Off output.
If the controller switches from OFF to ON mode, the Plant/System On/Off output switches the fans ON and the controller
provides automatic control.

D16-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

11

T7412B

T7411A

2
CPA/
SPA

6
1

T1

T2

T3

9 10 11 12 13 14
ON/ 24V
OFF

R7426C

Y1
X

24V 24V

Wrh

0..1 0V
2..1 0V

24V 24V

Y2
0..1 0V
2..1 0V

Y3

24V 24V

0..1 0V
2..1 0V

24V 24V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
6

ML7284E Mixed Air Dampers

5b

ML7420A Cooling Valve

5a

R7425A/B Current Valve

Brown White Green

2
8

10

(48,30(17/,67
Item

Quantity

Part Number

Description

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

5a

R7425A/B

Electric Current Valve

5b

ML7420A3006 and
V5....A....

Valve Actuator 0(2)...10Vdc and


Valve

ML7284E1006 or
ML7174E1006

Damper Actuator

L4064K1006

High Limit Thermostat

8+9

DPS-Series

Differential Air Pressure Switch

10

DPS-Series

Differential Air Pressure Switch

24Vac, 0...10Vdc, 17Nm or


24Vac, 0...10Vdc, 8Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

11

T7412B1057 or
43182690-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

D16-2

HONEYWELL MICRONIK 200 APPLICATION

5220&21752/:,7+/2:/,0,7',6&+$5*($,57(03(5$785(&21752/2552205(7851$,5
',6&+$5*($,57(03(5$785(&$6&$'(&21752/2)$+27:$7(5+($7,1*&2,/25 5
&+,//(':$7(5&22/,1*&2,/)25)8//2876,'($,53/$176
A heating and ventilation system with room/return air temperature control and low limit discharge air or cascade control is used
where the base heating load is met by radiators and the ventilation system provides the supply of fresh outside air.
In cooling applications it is also used to supply fresh outside air using the same temperature control system as for heating
control.

EA
M

1a

T 1b
1c

0A
T
3

M
6

T
2

Y1
4

)81&7,21$/'(6&5,37,21

Y1 (%)
100

Temperature Control With Low Limit Control. The return or room air
temperature sensor (1a, b or c) and the discharge air temperature sensor (2)
measure the actual values and the controller (4) compares these values with the
desired setpoints (W1) and (Wlim). If a deviation between these values exists, the
lowest deviation signal of both is selected by the controller. Depending on this
deviation signal the controller generates a 3-position control signal to reposition
the valve (5) to maintain the desired room or discharge air temperature. In
heating applications the controller output is reverse acting and direct acting for
cooling applications.

Cooling

Heating

0
0
CTRP2

Ystart

Xw
T2

Xp

Cascade Temperature Control. The return or room air temperature sensor (1a, b
or c) measures the actual value and the controller (4) compares this value with the desired setpoint (W1) of the master loop.
Depending on the deviation an internal setpoint for the submaster loop, the discharge air temperature, is calculated. At zero
deviation the discharge air temperature is controlled at the programmed setpoint (Wcas) and if a deviation exists, the discharge
air setpoint is altered. The reset span of the discharge air setpoint is limited by the reset span adjustment (Rcas) and the limit
setting (Wlim).
The discharge air temperature sensor (2) measures the actual value and the controller compares this value with the desired
internal calculated setpoint. If a deviation exists, the controller generates a 3-position control signal to reposition the valve (5) to
maintain the desired discharge air temperature. In heating applications the controller output is reverse acting and direct acting
for cooling applications.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to switch the fan(s) OFF and close the
dampers by an external installed relay logic and fully open the heating valve (5) to prevent the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the heating valve (5), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

R1-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
7

T6046A

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

2
CPA/
SPA

T1

T2

NC C

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426A

Y1
24V 24V

op en/
O U T2

24V

clo se/
O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5

ML6420A Heating or Cooling

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426A1016 or
R7426A1008

Temperature Controller with clock or


without clock

ML6420A3007 and
V5.....A.....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R1-2

HONEYWELL MICRONIK 200 APPLICATION

5220&21752/2)+27:$7(5+($7,1*&2,/25&+,//(':$7(5&22/,1*&2,/,1
5
5(&,5&8/$7,21$,59(17,/$7,216<67(06
Recirculation air systems with room or return air temperature control are used for ventilation in factories, storage areas,
department stores, etc.

1a

T 1b
1c

Y1
4

)81&7,21$/'(6&5,37,21
Temperature Control. The return or room air temperature sensor (1a, b or c)
measures the actual value and the controller (4) compares this value with the
desired setpoint. If a deviation between the two values exists, the controller
(4) generates a 3-position control signal to reposition the valve (5) to maintain
the desired room or return air temperature. In heating applications the
controller output is reverse acting and direct acting for cooling applications.
Time Control. Depending on the programmed time schedule of the internal
controller real time clock the different operating control modes Comfort,
Standby, Night or OFF are selected. In the OFF operating mode the
controller automatically fully closes the heating valve (5) and switches the fan
OFF.
If the controller switches from OFF to ON mode the Plant/System On/off
output switches the fan ON and the controller provides automatic control.

R2-1

Y1 (%)
100

Cooling

Heating

0
0
CTRP1 Ystart
Xp

Xw
T1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

2
CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426A

Y1
24V 24V

op en/
O U T2

24V

clo se/
O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5

ML6420A Heating or Cooling

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

1a

T7411A1001
T7411A1019
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length


300mm length
Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

R7426A1016 or
R7426A1008

Temperature Controller with clock or


without clock

ML6420A3007 and
V5.....A.....

Valve Actuator and


Valve

1b or
1c

EN3C-0161 0698R0-MA

R2-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)
5
$1(1(5*<5(&29(5<6<67(0:,7+$+27:$7(5+($7,1*&2,/
For use with ventilation systems comprising of an energy (heat) recovery system and a heating coil.

11

EA
M

5b

1a

T 1b
1c

0A
T
3

M
6

T
2

5a

Y3

Y1

)81&7,21$/'(6&5,37,21

Y (%)
100

Energy
Temperature Control. The return or room air temperature
Recovery
Heating
sensor (1a, b or c) measures the actual value and the controller
Y1
Y3
1/4 Xp
(4) compares this value with the desired setpoint (W1) of the
master loop. Depending on the deviation an internal setpoint for
the submaster loop, the discharge air temperature, is
calculated. At zero deviation the discharge air temperature is
0
controlled at the programmed setpoint (Wcas) and if a
0
0
0
Xwh/Xw
deviation exists, the discharge air setpoint is altered. The reset
CTRPH
CTRP2
span of the discharge air setpoint is limited by the reset span
T2
XpH
Xp
adjustment (Rcas) and the limit setting (Wlim).
The discharge air temperature sensor (2) measures the actual
value and the controller (4) compares this value with the desired internal calculated setpoint. If a deviation between the two
values exists, the controller generates a 3-position control signal on outputs Y1 and Y3 to reposition either the energy recovery
valve (5a) or the heating valve (5b) in sequence to maintain the desired discharge air temperature.

In an air-glycol-air heat recovery system it is important, to avoid icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5b) will be closed by an
additional, field mounted relay. Return air and warm water will be circulated through the exhaust air heat recovery coil to melt
the ice deposits.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON, - if OFF - at temperatures below
its adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a), to
switch OFF the fan(s) and close the dampers (6) by an external installed relay logic to protect the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

R3-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
7

T6046A

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

2
CPA/
SPA

T1

T2

NC C

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426B

Y2

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

clo se/ op en/


O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
5b

ML6420A Energy
Recovery

5a

ML6420A Heating Valve

230Vac

24V

3 - Way Valve

24V

2 - Way
Valve

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a+5b

ML6420A3007 and
V5.....A.....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R3-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)
5
$1(1(5*<5(&29(5<6<67(0:,7+$&+,//(':$7(5&22/,1*&2,/
For use with ventilation systems comprising of an energy (heat/cool) recovery system and a cooling coil.

11

EA
M

5b

1a

T 1b
1c

0A
T
3

M
6

2
5a

Y2

Y1

)81&7,21$/'(6&5,37,21
Temperature Control. The return or room air temperature
sensor (1a, b or c) measures the actual value and the
controller (4) compares this value with the desired setpoint
(W1) of the master loop. Depending on the deviation an
internal setpoint for the submaster loop, the discharge air
temperature, is calculated. At zero deviation the discharge air
temperature is controlled at the programmed setpoint (Wcas)
and if a deviation exists, the discharge air setpoint is altered.
The reset span of the discharge air setpoint is limited by the
reset span adjustment (Rcas) and the limit setting (Wlim).

Y (%)
100
Energy
Recovery
Y1
MINPOS

Cooling
Y2

0
0
0
Xwc/Xw
The discharge air temperature sensor (2) measures the
CTRP2 CTRPC
actual value and the controller (4) compares this value with
the desired internal calculated setpoint. If a deviation
T2
Xp
XpC
between the two values exists, the controller generates a 3position control signal on output Y1or Y2 to reposition either
the energy recovery valve (5b) or the cooling valve (5a) in sequence to maintain the desired discharge air temperature.

Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

R4-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b
1a

T7412A
T7411A

2
CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

Y3

Y2
clo se/ op en/
O U T1 O U T2

24V

clo se/ op en/


O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
5b

5a

ML6420A Energy
Recovery

230Vac

3 - Way
Valve
2 - Way
Valve

24V

24V

ML6420A Cooling Valve

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a+5b

ML6420A3007 and
V5.....A.....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R4-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,5&$6&$'(6(48(1&(&21752/2)+27:$7(5+($7,1*&2,/$1'
5
&+,//(':$7(5&22/,1*&2,/$1'7:2326,7,21 23(1&/26(' '$03(5&21752/
For use with ventilation system comprising of heating and cooling coils with full outside air dampers.

EA
6

1a

T 1b
1c

0A
T
3

M
6

p
8

5b

p
9

5a

Y1

Y3

Y2
4

)81&7,21$/'(6&5,37,21

Y (%)

100
Temperature Control. The return or room air temperature
sensor (1a, b or c) measures the actual value and the
controller (4) compares this value with the desired setpoint
(W1) of the master loop. Depending on the deviation an
internal setpoint for the submaster loop, the discharge air
Cooling
Heating
Y3
Y2
temperature, is calculated. At zero deviation the discharge air
temperature is controlled at the programmed setpoint (Wcas)
0
and if a deviation exists, the discharge air setpoint is altered.
0
0
0 Xwh/Xwc
The reset span of the discharge air setpoint is limited by the
CTRPH CTRP2 CTRPC
reset span adjustment (Rcas) and the limit setting (Wlim).
XpH
Xp
XpC
T2
The discharge air temperature sensor (2) measures the
actual value and the controller (4) compares this value with
the desired internal calculated setpoint. If a deviation
between the two values exists, the controller generates a 3-position control signal to reposition the heating or cooling valve to
maintain the desired discharge air temperature.

If the temperature is below the heating setpoint the heating valve (5a) is modulated via output Y3 and if the temperature is
above the cooling setpoint the cooling valve (5b) is modulated via output Y2 to maintain the desired discharge air temperature.
Damper Control. If the controller switches from OFF to ON mode (Comfort, Standby or Night) the controller drives the damper
actuators to the open position via output Y1.
If the controller switches to the OFF mode it drives the dampers and valves automatically to their closed positions.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a) and close
the dampers (6) and cooling valve (5b) if open - to prevent the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b) and dampers (6) and switches the fan(s) OFF.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a 3 minute time delay to allow the dampers time to
open. As alternative the end-position switches of the damper actuators can be used to start the fan.

R5-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
7

T6046A

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

2
CPA/
SPA

T1

T2

2
NC C

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426B

Y2

Y1
X

Wrh

24V 24V

op en/
O U T2

24V

clo se/ op en/


O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
6
5b

230Vac
ML6184E Damper Open-Closed
ML6420A Cooling Valve

Brown White Green

3 - Way Valve

24V

24V

2 - Way Valve
5a

ML6420A Heating Valve

3 - Way Valve

24V

2 - Way Valve

24V

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a+5b

ML6420A3007 and
V5.....A.....

Valve Actuator and


Valve

ML6184E1009

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R5-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)(1(5*<5(&29(5<
5
6<67(0+27:$7(5+($7,1*$1'&+,//(':$7(5&22/,1*&2,/6
For use with ventilation system comprising of an energy (heat/cool) recovery system, heating and cooling coils.

10

EA
6

M
5c

1a

T 1b
1c

0A
T
3

M
6

5a

T 5b

T
p

Y3

Y2

Y1
4

)81&7,21$/'(6&5,37,21

Y (%)
100

Energy

Temperature Control. The return or room air temperature


Recovery
Heating
Cooling
sensor (1a, b or c) measures the actual value and the controller
Y1
Y3
Y2
(4) compares this value with the desired setpoint (W1) of the
master loop. Depending on the deviation an internal setpoint for
the submaster loop, the discharge air temperature, is
calculated.
0
The discharge air temperature sensor (2) measures the actual
0
0
0 Xwh/Xwc/Xw
value and the controller (4) compares this value with the
CTRPH
CTRP2
CTRPC
desired internal calculated setpoint. If a deviation between the
XpH
Xp
XpC
T2
two values exists, the controller generates a 3-position control
signal to reposition either the energy recovery valve (5c) or the
heating valve (5a) or the cooling valve (5b) in sequence to maintain the desired discharge air temperature. If the actual
temperature is below the setpoint, the controller modulates first via output Y1 the heat recovery valve (5c) into the open
position and if fully open, the heating valve (5a) is opened in sequence via output Y3. If the actual temperature increases the
sequence of operation is reversed.
If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating and
cooling - the controller starts to open the energy recovery valve (5c) to reclaim cooling energy. If the temperature continues to
increase and the energy recovery valve is fully open the controller (4) generates an output signal via Y2 to open the cooling coil
valve (5b).
In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5c) will be closed by an
additional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt the
ice deposits.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a), to switch
OFF the fan(s) and thereby to close the damper actuators by an external installed relay logic to protect the heating coil from
freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a, 5b and 5c) and switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.
R6-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
7

T6046A

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

2
CPA/
SPA

T1

T2

2
NC C

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426B

Y2

Y1
X

24V 24V
Wrh

op en/
O U T2

24V

clo se/ op en/


O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
5c

230Vac
ML6420A Energy Recovery
3 - Way Valve
2 - Way Valve

5b

5a

ML6420A Cooling Valve

24V

24V

3 - Way Valve

24V

2 - Way Valve

24V

3 - Way Valve

ML6420A Heating Valve

2 - Way Valve

24V

24V

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a+5b+5c

ML6420A3007 and
V5.....A.....

Valve Actuator and


Valve

ML6184E1009
ML6184E1008

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R6-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)
5
0,;('$,5'$03(56$1'+27:$7(5+($7,1*&2,/
For use with ventilation systems comprising of mixed air dampers and a heating coil.

EA
T

M
6
6

1a

T 1b
1c

0A
T
3

M
6

p
8

Y3
Y1
4

)81&7,21$/'(6&5,37,21
Temperature Control. The return or room air temperature
sensor (1a, b or c) measures the actual value and the
controller (4) compares this value with the desired setpoint
(W1) of the master loop. Depending on the deviation an
internal setpoint for the submaster loop, the discharge air
temperature, is calculated. At zero deviation the discharge air
temperature is controlled at the programmed setpoint (Wcas)
and if a deviation exists, the discharge air setpoint is altered.
The reset span of the discharge air setpoint is limited by the
reset span adjustment (Rcas) and the limit setting (Wlim).

Y (%)
100

1/4 Xp
Heating
Y3

Damper
Y1

MINPOS
0

Xwh/Xw
0
0
0
The discharge air temperature sensor (2) measures the actual
CTRPH CTRP2
CTRPC
value and the controller (4) compares this value with the
T2
XpH
Xp
desired internal calculated setpoint. If a deviation between the
two values exists, the controller generates two 0(2)10Vdc
control signals in sequence via outputs Y1 and Y3
corresponding to the 0100% correctional signal to reposition the mixed air dampers or the heating valve to maintain the
desired discharge air temperature. The minimum outside air damper position adjustment (MINPOS) on the controller
determines the position to which the outside air damper will be driven even though the temperature input condition demands
that it should drive to the fully closed position.

Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5), to close
the outside and exhaust air dampers (6) and to switch OFF the fan(s) to protect the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the heating valve (5) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.

R7-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
7

T6046A

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

2
CPA/
SPA

T1

T2

2
NC C

T3

9 10 11 12 13 14
ON/ 24V
OFF

R7426C

Y1
X

24V 24V

Wrh

0..1 0V
2..1 0V

24V 24V

Y3

Y2
0..1 0V
2..1 0V

24V 24V

0..10V
2..10V

24V 24V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
green brown white

ML7284E Mixed Air Dampers

ML7420A Heating Valve

24V 24V

3 1 2
Y 24V 24V

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

ML7420A3006 and
V5.....A.....

Valve Actuator 0(2)...10Vdc and


Valve

ML7284E1006 or
ML7174E2007

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
24Vac , 8Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R7-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)
5
0,;('$,5'$03(56$1'&+,//(':$7(5&22/,1*&2,/
Used with ventilation system comprising of mixed air dampers and a cooling coil.

EA
T

M
6
6

1a

T 1b
1c

0A
T
3

M
6

Y2
Y1
4

)81&7,21$/'(6&5,37,21
Temperature Control. The return or room air temperature
sensor (1a, b or c) measures the actual value and the controller
(4) compares this value with the desired setpoint (W1) of the
master loop. Depending on the deviation an internal setpoint for
the submaster loop, the discharge air temperature, is
calculated. At zero deviation the discharge air temperature is
controlled at the programmed setpoint (Wcas) and if a
deviation exists, the discharge air setpoint is altered. The reset
span of the discharge air setpoint is limited by the reset span
adjustment (Rcas) and the limit setting (Wlim).

1/4 Xp

Y (%)
100
Damper
Y1

MINPOS

Cooling
Y2

Xwc/Xw
0
0
0
The discharge air temperature sensor (2) measures the actual
CTRP2
CTRPC
value and the controller (4) compares this value with the
T2
Xp
XpC
desired internal calculated setpoint. If a deviation between the
two values exists, the controller generates two 0(2)10Vdc
control signals in sequence via outputs Y1 and Y2
corresponding to the 0100% correctional signal to reposition the mixed air dampers (6) or cooling valve (5) to maintain the
desired discharge air temperature. The minimum outside air damper position adjustment (MINPOS) on the controller
determines the position to which the outside air damper will be driven even though the temperature input condition demands
that it should drive to the fully closed position.

Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the cooling valve (5) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.

R8-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

2
CPA/
SPA

T1

T2

T3

9 10 11 12 13 14
ON/ 24V
OFF

R7426C

Y1
X

24V 24V

Wrh

0..1 0V
2..1 0V

24V 24V

Y3

Y2
0..1 0V
2..1 0V

24V 24V

0..10V
2..10V

24V 24V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
green brown white

ML7284E Mixed Air Dampers

24V 24V

3 1 2
Y 24V 24V

ML7420A Cooling Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

ML7420A3006 and
V5.....A.....

Valve Actuator 0(2)...10Vdc and


Valve

ML7284E1006 or
ML7174E2007

Damper Actuator

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
24Vac , 8Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R8-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)0,;('$,5'$03(56
5
+27:$7(5$1'&+,//(':$7(59$/9(6
Use with ventilation system comprising of mixed air dampers, heating and cooling coils.

EA
T

M
6
6

1a

T 1b
1c

0A
T
3

M
6

5b

p
9

5a

Y1

Y3

Y2
4

)81&7,21$/'(6&5,37,21
Temperature Control. The return or room air temperature
sensor (1a, b or c) measures the actual value and the controller
1/4 Xp
Y (%)
(4) compares this value with the desired setpoint (W1) of the
100
master loop. Depending on the deviation an internal setpoint for
Heating
Damper
the submaster loop, the discharge air temperature, is
Y3
Y1
calculated. At zero deviation the discharge air temperature is
controlled at the programmed setpoint (Wcas) and if a deviation
Cooling
Y2
exists, the discharge air setpoint is altered. The reset span of
MINPOS
the discharge air setpoint is limited by the reset span
adjustment (Rcas) and the limit setting (Wlim).
0
0
0
0 Xwh/Xwc/Xw
The discharge air temperature sensor (2) measures the actual
CTRPH
CTRP2
CTRPC
value and the controller (4) compares this value with the
T2
XpH
Xp
XpC
desired internal calculated setpoint. If a deviation between the
two values exists, the controller generates three 0(2)10Vdc
control signals in sequence via outputs Y1, Y2 and Y3
corresponding to the 0100% correctional signal to reposition the mixed air dampers or heating or cooling valve to maintain
the desired discharge air temperature. The minimum outside air damper position adjustment (MINPOS) on the controller
determines the position to which the outside air damper will be driven even though the temperature input condition demands
that it should drive to the fully closed position.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a), to close
the outside and exhaust air dampers (6) and cooling valve - if open - and to switch OFF the fan(s) to prevent the heating coil
from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.

R9-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
7

T6046A

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

2
CPA/
SPA

T1

T2

2
NC C

T3

9 10 11 12 13 14
ON/ 24V
OFF

R7426C

Y2

Y1
X

24V 24V

Wrh

0..1 0V
2..1 0V

24V 24V

0..1 0V
2..1 0V

Y3

24V 24V 0..10V 24V 24V


2..10V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
6

ML7284E Mixed Air Dampers

5b

ML7420A Cooling Valve

5a

ML7420A Heating Valve

green brown white

24V 24V

3 1 2
Y 24V 24V
3 1 2
Y 24V 24V

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

5a+5b

ML7420A3006 and
V5.....A.....

Valve Actuator 0(2)...10Vdc and


Valve

ML7284E1006
ML7174E2007

Damper Actuator

T6046A1006 or
FT015 or FTB015

Freeze Protection Thermostat

8+9

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
24Vac, 8Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R9-2

HONEYWELL MICRONIK 200 APPLICATION

5220&21752/:,7+/2:/,0,7',6&+$5*($,57(03(5$785(&21752/2552205(7851$,5
',6&+$5*($,57(03(5$785(&$6&$'(&21752/2)(/(&75,&$,5+($7(5%$77(5<25 5
',5(&7(;3$16,21&22/,1*6<67(0 837267$*(667(36
Used with ventilation system using electric air heating, where the base heating load is met by a radiator heating system and the
ventilation system is used to ensure the supply of outside air.
Instead of electric heating, the controller can be used to control up to 6-stages of direct expansion cooling.
- Heating mode:
4 stages, sequentially switched steps to operate external relays or
4 binary coded switching outputs to provide up to 15 load steps.
- Cooling mode:
2 stages, sequentially switched steps to operate external relays.

EA
T

M
6

T 1b

1a

1c

0A
T
3

M
6

p
8

p
9

T
2

10

Y1/Y2/Y3
4

)81&7,21$/'(6&5,37,21

Y1/Y2/Y3 (%)
Cooling

100

Temperature Control With Low Limit Control. The return or room air
temperature sensor (1a, b or c) and the discharge air temperature sensor (2)
measure the actual values and the controller (4) compares these values with the
desired setpoints (W1) and (Wlim). If a deviation between these values exists, the
lowest deviation signal of both is selected by the controller. Depending on this
deviation signal the controller selects the number of stages/steps required to
maintain the desired room or return air or low limit discharge air temperature.
Cascade Temperature Control. The return or room air temperature sensor (1a,
b or c) measures the actual value and the controller (4) compares this value with
the desired setpoint (W1) of the master loop. Depending on the deviation an
internal setpoint for the submaster loop, the discharge air temperature, is
calculated.
The discharge air temperature sensor (2) measures the actual value and the
controller compares this value with the desired internal calculated setpoint. If a
deviation exists, the controller selects the number of stages/steps required to
maintain the desired discharge air temperature.
For both applications the controller output is reverse acting for heating mode and
direct acting for cooling mode.
When configured for heating and cooling sequence operation, the controller will
first select the heating or cooling mode and than the number of stages/steps
required.

Heating

0
0
CTRP1/2
Ystart

Xw
T1/2

Xp
Step6 on
Step5 on

Power

Step2 on
Step1 on
on
off

6 signal sequence of
Y3/Y2/Y1 out1/out2
10 15 25 30

70 75 85 90 100 %
Y3/Y2/Y1

Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically switches
OFF the selected number of stages/steps and the fan(s) and thereby closes the dampers (6) by an external installed relay
logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

R10-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

2
CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

Y2
clo se/ op en/
O U T1 O U T2

Y3

24V

clo se/ op en/


O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5

24Vac Relays
Heating or Cooling

Stage

Heating: 4 Linear or 15 Binary

Stage 4

Plus 2 Cooling

Stage

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

1 or
6

RY6

Auxiliary Relay Module with 6 relays


24Vac coil relays

ML6184E1009
ML6684E1008

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R10-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/
5
2)(/(&75,&$,5+($7(5$1'&+,//(':$7(5&22/,1*&2,/


Use with ventilation system comprising of an electric air heater and a cooling coil.

EA
T

M
6

T 1b

1a

1c

0A
T
3

M
6

T
p

T
2

10
5b

7
5a

Y2
Y1/Y3
4

)81&7,21$/'(6&5,37,21

Y (%)
100

Temperature Control. The return or room air temperature


sensor (1a, b or c) measures the actual value and the controller
(4) compares this value with the desired setpoint (W1) of the
master loop. Depending on the deviation an internal setpoint for
the submaster loop, the discharge air temperature, is
calculated. At zero deviation the discharge air temperature is
controlled at the programmed setpoint (Wcas) and if a deviation
exists, the discharge air setpoint is altered. The reset span of
the discharge air setpoint is limited by the reset span
adjustment (Rcas) and the limit setting (Wlim).
The discharge air temperature sensor (2) measures the actual
value and the controller (4) compares this value with the
desired internal calculated setpoint. If a deviation between the
two values exists, the controller selects the corresponding
number of stages/steps (up to 4 stages linear or 15 stages
binary) for heating or generates a 3-position control signal to
reposition the cooling valve to maintain the desired discharge
air temperature.

Cooling
Y2

Heating
Y1/Y3
0
0

0
CTRPH CTRP2

XpH

Xp

T2

XpC
Step4 on

Power

Step3 on
Step2 on
Step1 on

Y1 out2
Y1 out1
Y3 out2
Y3 out1

on
off

If the temperature is below the heating setpoint the heating


stages are switched via output Y3 and Y1 and if the
temperature is above the cooling setpoint, the cooling valve
(5b) is modulated via output Y2.

Xwh/Xwc

CTRPC

20 25

40 45

60 65

80 85

100 %

Y3/Y1

Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically switches
OFF the selected number of heating stages/steps, closes the cooling valve (5b), switches the fan(s) OFF and thereby closes
the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

R11-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

Y2
clo se/ op en/
O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5a

24Vac Relays
Heating: 4 Linear or 15 Binary

5b

ML6420A Cooling Valve

Stage

3 - Way Valve
2 - Way Valve

2
1

24V

24V

1 Stage

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a

1 or
4

RY4

Auxiliary Relay Module with 4 relays


24Vac coil relays

5b

ML6420A3007 and
V5...A....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

3 or 4

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R11-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)(/(&75,&$,5+($7(5$1'
5
&+,//(':$7(5&22/,1*&2,/$1'7:2326,7,21 23(1&/26( '$03(5&21752/


For use with ventilation system comprising of an electric air heater and a cooling coil with full outside air dampers.

EA
T

1a

T 1b
1c

0A
T
3

M
6

T
p

V
2

10
5b

5a

Y3

Y2

Y1

)81&7,21$/'(6&5,37,21

Y (%)
100

L1

T1

Temperature Control. The return or room air temperature sensor


100...440Vac
(1a, b or c) measures the actual value and the controller (4)
compares this value with the desired setpoint (W1) of the master
Cooling
Heating
loop. Depending on the deviation an internal setpoint for the
Y3
Y2
submaster loop, the discharge air temperature, is calculated. At
0
zero deviation the discharge air temperature is controlled at the
0
0
0 Xwh/Xwc
programmed setpoint (Wcas) and if a deviation exists, the
CTRPH CTRP2 CTRPC
discharge air setpoint is altered. The reset span of the discharge
XpH
Xp
XpC
T2
air setpoint is limited by the reset span adjustment (Rcas) and the
limit setting (Wlim).
out1/out2
on
The discharge air temperature sensor (2) measures the actual
value and the controller (4) compares this value with the desired
internal calculated setpoint. If a deviation between the two values
off
exists, the controller generates a pulse width modulated output
30
50
70 80
100 sec Y3
signal on output Y3 to drive one or up to three solid state relays
(5a) in parallel for proportional control of the electric air heater or a
3-position control signal on output Y2 to reposition the cooling valve (5b) to maintain the desired discharge air temperature.
If the temperature is below the heating setpoint the solid state relay(s) (5a) is modulated via output Y3 and if the temperature is
above the cooling setpoint the cooling valve (5b) is modulated via output Y2.
Damper Control. If the controller switches from OFF to ON mode the controller drives the damper actuators (6) to the open
position via output Y1.
If the controller switches to OFF mode the controller drives the dampers automatically to the closed position.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically generates
on all outputs a 0% output signal to switch OFF the electric air heater, to fully close the cooling valve (5b) and dampers (6) and
to switch OFF the fan(s).
If the controller switches from OFF to ON mode, the fan(s) switch ON after a 3 minute time delay to allow the dampers time to
open. As alternative the end-position switches of the damper actuators can be used to start the fan.

R12-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b
1a

T7412A
T7411A

CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

op en/
O U T2

24V

Y2
clo se/ op en/
O U T1 O U T2

24V

Y3
clo se/ op en/
O U T1 O U T2

24V clo se/


O U T1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
6
5b

ML6184E Damper
Open-Closed
ML6420A Cooling Valve

230Vac

Brown White Green

3 - Way Valve

24V

2 - Way Valve

24V

1
A2 A1

5a

RN1L40M25 Solide State Relay (Current Valve)

L1

T1

100...440Vac

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a

up to 3

RN1L40M25

Solid State Relay (Current Valve)

5b

ML6420A3007 and
V5...A....

Valve Actuator and


Valve

ML6184E1009

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

3 or 4

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R12-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)
5
(/(&75,&$,5+($7(5$1'&+,//(':$7(5&22/,1*&2,/


Used with ventilation system comprising of an electric air heater and a cooling coil.

EA
T

M
6

1a

T 1b
1c

0A
T
3

M
6

T
p

T
2

10
5b

5a
Y2
Y3
4

)81&7,21$/'(6&5,37,21

Y (%)
100

Temperature Control. The return or room air temperature


sensor (1a, b or c) measures the actual value and the
controller (4) compares this value with the desired setpoint
(W1) of the master loop. Depending on the deviation an
internal setpoint for the submaster loop, the discharge air
temperature, is calculated. At zero deviation the discharge air
temperature is controlled at the programmed setpoint (Wcas)
and if a deviation exists, the discharge air setpoint is altered.
The reset span of the discharge air setpoint is limited by the
reset span adjustment (Rcas) and the limit setting (Wlim).

Cooling
Y2

Heating
Y3
0
0
XpH

0
CTRPH CTRP2
Xp

Xwh/Xwc

CTRPC
XpC

T2

The discharge air temperature sensor (2) measures the


actual value and the controller (4) compares this value with
the desired internal calculated setpoint. If a deviation between the two values exists, the controller generates two 0(2)...10Vdc
control signals in sequence via outputs Y2 and Y3 corresponding to the 0...100% correctional signal to drive the electric current
valve (5a) for proportional control of the electric air heater or to reposition the cooling valve (5b) to maintain the desired
discharge air temperature.
If the temperature is below the heating setpoint the controller generates a control signal on output Y3 to control the electric
current valve (5a) and if the temperature is above the cooling setpoint, the controller generates a control signal on output Y2 to
position the cooling valve (5b).
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically generates
0% output signals on Y2 and Y3 to switch OFF the electric heater , to close the cooling valve (5b) and to switch OFF the fan(s)
by the Plant/System On/Off output and thereby close the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

R13-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b

T7412A

1a

T7411A

1
1
5

CPA/
SPA

T1

T2

T3

9 10 11 12 13 14
ON/
OFF

R7426C

Y1
X

24V 24V

Wrh

0..1 0V
2..1 0V

24V 24V

Y2
0..1 0V
2..1 0V

Y3

24V 24V

0..10V
2..10V

24V 24V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac

3
5b

ML7420A Cooling Valve

5a

R7425A/B

24V 24V

8
Y

10

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

5a

R7425A/B

Electric Current Valve

5b

ML7420A3006 and
V5....A....

Valve Actuator 0(2)...10Vdc and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

3 or 4

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R13-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)(1(5*<5(&29(5<
5
6<67(0(/(&75,&$,5+($7(5$1'&+,//(':$7(5&22/,1*&2,/


For use with ventilation system comprising of an energy (heat/cool) recovery system, an electric air heater and a cooling coil.

10

EA
T

M
6

1a

5c

T 1b
1c

0A
T
3

M
6

T
p

V
2

11
5b

5a

Y1

Y3

Y2
4

)81&7,21$/'(6&5,37,21

Y (%)
100

Energy

Temperature Control. The return or room air temperature sensor


Recovery
Heating
Cooling
Y1
(1a, b or c) measures the actual value and the controller (4)
Y3
Y2
compares this value with the desired setpoint (W1) of the master
loop. Depending on the deviation an internal setpoint for the
submaster loop, the discharge air temperature, is calculated.
0
The discharge air temperature sensor (2) measures the actual value
0
0
0 Xwh/Xwc/Xw
and the controller (4) compares this value with the desired internal
CTRPH
CTRP2
CTRPC
calculated setpoint. If a deviation between the two values exists, the
XpH
Xp
XpC
T2
controller generates the corresponding control signals to maintain
the desired discharge air temperature.
out1/out2
If the actual temperature is below the setpoint the controller (4)
on
generates first a 3-position control signal via output Y1 to reposition
the energy recovery valve (5c) to reclaim heating energy. If the
off
temperature continues to decrease and the energy recovery valve is
fully open, the controller generates a pulse width modulated output
30
50
70 80
100 sec Y3
via output Y3 to drive the solid state relay (5a) for proportional control
of the electric air heater. If the temperature increases the sequence of operation is reversed.
If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp2) dead band between heating
and cooling the controller starts to open the energy recovery valve (5c) to reclaim cooling energy. If the temperature
continues to increase and the energy recovery valve is fully open the controller (4) generates an output signal via Y2 to open
the cooling coil valve (5b).
In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5c) will be closed by an
additional, field mounted relay. Return air and warm water will circulatethrough the heat recovery exhaust air coil to melt the
ice deposits.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5b and 5c) and switches the electric air heater and the fan(s) OFF and thereby close the dampers (6) by an external
installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.

R14-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b
1a

T7412A
T7411A

2
CPA/
SPA

3
T1

T2

9 10 11 12 13 14
ON/
OFF

T3

R7426B

Y1
X

24V 24V

Wrh

o pe n /
OUT2

24V

Y2
c lo s e/ o pe n /
OUT1 OUT2

Y3

24V c lo s e/ o pe n / 24V c lo s e/
OUT1 OUT2

OUT1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
5c
5b

ML6420A Energy
Recovery Valve
ML6420A Cooling Valve

230Vac

24V

3 - Way Valve

24V

2 - Way Valve

24V

1
A2 A1

5a

RN1L40M25 Solide State Relay (Current Valve)

L1

T1

100...440Vac

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426B1014 or
R7426B1006

Temperature Controller with clock or


without clock

5a

RN1L40M25

Solid State Relay, up to 3 possible for higher loads

5b + 5c

ML6420A3007 and
V5....A....

Valve Actuator and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

11

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R14-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)(1(5*<5(&29(5<
5
6<67(0(/(&75,&$,5+($7(5$1'&+,//(':$7(5&22/,1*&2,/


For use with ventilation system comprising of an energy (heat/cool) recovery system, an electric air heater and a cooling coil.

10

EA
T

M
6

1a

5c

T 1b
1c

0A
T
3

M
6

T
p

V
2

11
5b

5a

Y3

Y2

Y1
4

)81&7,21$/'(6&5,37,21

Y (%)
100

Ene rgy

Temperature Control. The return or room air temperature


Recove ry
Heating
Cooling
Y1
sensor (1a, b or c) measures the actual value and the controller
Y3
Y2
1/4 Xp
(4) compares this value with the desired setpoint (W1) of the
master loop. Depending on the deviation an internal setpoint for
the submaster loop, the discharge air temperature, is
calculated. At zero deviation the discharge air temperature is
0
controlled at the programmed setpoint (Wcas) and if a
0
0
0 Xwh/Xwc/Xw
deviation exists, the discharge air setpoint is altered. The reset
CTRPH CTRP2
CTRPC
span of the discharge air setpoint is limited by the reset span
XpC
XpH
Xp
T2
adjustment (Rcas) and the limit setting (Wlim).
The discharge air temperature sensor (2) measures the actual
value and the controller (4) compares this value with the desired internal calculated setpoint. If a deviation between the two
values exists, the controller generates in correspondence to the 0...100% correctional signal 0(2)...10Vdc control signals in
sequence via outputs Y1, Y2 and Y3 to position the energy recovery or cooling valve or to drive the electric current valve to
maintain the desired discharge air temperature.
If the actual temperature is below the setpoint, the controller generates first a 0(2)...10Vdc control signal via output Y1 to
reposition the energy recovery valve (5c) to reclaim heating energy. If the temperature continues to decrease and the energy
recovery valve is fully open, the controller generates a 0(2)...10Vdc control signal via output Y3 to drive the electric current
valve (5a) for proportional control of the electric air heater. If the temperature increases the sequence of operation is reversed.
If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp2) - dead band between heating and
cooling - the controller starts to open the energy recovery valve (5c) to reclaim cooling energy. If the temperature continues to
increase and the energy recovery valve is fully open, the controller (4) generates a 0(2)...10Vdc control signal via Y2 to posi tion
the cooling valve (5b).
In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5c) will be closed by an
additional, field mounted relay. Return air and warm water will circulatethrough the heat recovery exhaust air coil to melt the ice
deposits.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5b and 5c) and switches the electric air heater and the fan(s) OFF and thereby close the dampers (6) by an external
installed relay logic. If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external
installed time delay relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches
of the damper actuators can be used to start the fan.

R15-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b
1a

T7412A
T7411A

2
CPA/
SPA

T1

T2

T3

9 10 11 12 13 14
ON/ 24V
OFF

R7426C

Y1
X

24V 24V

Wrh

0 ..1 0 V
2 ..1 0 V

24V 24V

Y2
0 ..1 0 V
2 ..1 0 V

Y3

24V 24V

0 ..1 0 V
2 ..1 0 V

24V 24V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5c

3 1 2
Y 24V 24V

ML7420A Energy
Recovery Valve

5b

ML7420A Cooling Valve

5a

R7425A/B

3
Y

24V 24V

8
Y

10

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

5a

R7425A/B

Electric Current Valve

5b + 5c

ML7420A3006 and
V5....A....

Valve Actuator 0(2)...10Vdc and


Valve

ML6184E1009 or
ML6684E1008

Damper Actuator

L4064K1006

High Limit Thermostat

8+9+10

DPS-Series

Differential Air Pressure Switch

11

DPS-Series

Differential Air Pressure Switch

24Vac, 17Nm or
230Vac, 17Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R15-2

HONEYWELL MICRONIK 200 APPLICATION

5220',6&+$5*($,57(03(5$785(&$6&$'(6(48(1&(&21752/2)0,;('$,5'$03(56
5
(/(&75,&$,5+($7(5$1'&+,//(':$7(5&22/,1*&2,/


For use with ventilation system comprising of mixed air dampers, an electric air heater and a cooling coil.

EA
T

M
p

6
6

1a

T 1b
1c

0A
T
3

M
6

T
p

5b

10

5a

Y1

Y2

Y3

)81&7,21$/'(6&5,37,21
Y (%)

1/4 Xp

Temperature Control. The return or room air temperature


100
Damper
sensor (1a, b or c) measures the actual value and the controller
Y1
(4) compares this value with the desired setpoint (W1) of the
master loop. Depending on the deviation an internal setpoint for
Cooling
Heating
the submaster loop, the discharge air temperature, is
Y2
Y3
calculated. At zero deviation the discharge air temperature is
MINPOS
controlled at the programmed setpoint (Wcas) and if a deviation
0
exists, the discharge air setpoint is altered. The reset span of
0
0
0 Xwh/Xwc/Xw
the discharge air setpoint is limited by the reset span
CTRPH
CTRP2 CTRPC
adjustment (Rcas) and the limit setting (Wlim).
T2
XpH
Xp
XpC
The discharge air temperature sensor (2) measures the actual
value and the controller (4) compares this value with the desired
internal calculated setpoint. If a deviation between the two values exists, the controller generates in correspondence to the
0...100% correctional signal 0(2)...10Vdc control signals in sequence via outputs Y1, Y2 and Y3 to position the mixed air
dampers or cooling valve or to drive the electric current valve to maintain the desired discharge air temperature.
If the actual temperature is below the setpoint, the controller generates first a 0(2)...10Vdc control signal via output Y1 to
reposition the mixed air damper (6). If the temperature continues to decrease and the mixed air dampers reached the minimum
position (MINPOS), the controller generates a 0(2)...10Vdc control signal via output Y3 to drive the electric current valve (5a)
for proportional control of the electric air heater. If the temperature increases the sequence of operation is reversed. If the
actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp2) - dead band between heating and
cooling - the controller starts to close the mixed air damper (6). If the temperature continues to increase and the mixed air
dampers reached the minimum position (MINPOS), the controller (4) generates a 0(2)...10Vdc control signal via Y2 to position
the cooling valve (5b).
The minimum outside air damper position adjustment (MINPOS) on the controller determines the position to which the outside
air damper will be driven even though the temperature input condition demands that it should drive to the fully closed position.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically generates
0Vac (0%) control signals via output Y1, Y2 and Y3 to fully close the outside and exhaust air dampers (6) and the cooling valve
(5b), open the return air damper and to switch OFF the electric air heater via the current valve (5a). In addition the fans are
switched OFF by the Plant/System On/Off output.
If the controller switches from OFF to ON mode, the Plant/System On/Off output switches the fans ON and the controller
provides automatic control.

R16-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7411A/T7416A

T7411A

1c

T7412C

1c

T7412B

1b
1a

T7412A
T7411A

2
CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426C

Y1
24V 24V

X Wrh

0 ..1 0V
2 ..1 0V

24V 24V

Y3

Y2
0 ..1 0V
2 ..1 0V

24V 24V 0..10V 24V 24V


2..10V

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
6

ML7284E Mixed Air Dampers

5b

ML7420A Cooling Valve

5a

R7425A/B

green brown white

24V 24V

3 1 2
Y 24V 24V
8
Y

10

(48,30(17/,67
Item

Quantity

Part Number

Description

1a or
1b or
1c

T7411A1001 or
T7412A1018 or
T7412B1057
T7412C1030

Duct Temperature Sensor 135mm length or


Room Temperature Sensor or
Room Temperature Sensor with CPA
Room Temperature Sensor with CPA and Occupancy Switch

T7411A1001 or
T7411A1019

Duct Temperature Sensor 135mm length or


Duct Temperature Sensor 300mm length

R7426C1012 or
R7426C1004

Temperature Controller with clock or


without clock

5a

R7425A/B

Electric Current Valve

ML7420A3006 and
V5....A....

Valve Actuator 0(2)...10Vdc and


Valve

ML7284E1006 or
ML7174E1006

Damper Actuator

L4064K1006

High Limit Thermostat

8+9

DPS-Series

Differential Air Pressure Switch

10

DPS-Series

Differential Air Pressure Switch

24Vac, 0...10Vdc, 17Nm or


24Vac, 0...10Vdc, 8Nm

237,216
Item

Quantity

Part Number

Description

T7411A1027 or
T7416A1006

Outside Air Sensor, Duct Mounting or


Wall Mounting

EN3C-0161 0698R0-MA

R16-2

HONEYWELL MICRONIK 200 APPLICATION

2876,'($,57(03(5$785(&203(16$7('6833/<:$7(5)/2:7(03(5$785(&21752/ :
Used in heating systems in which hot water is used as a heating medium, being circulated to the locations where heat is
required e.g. radiator heating systems or heating coils in ventilation or air conditioning systems. The controller is also suitable
for chilled water supply temperature control.

B
A
4

AB
1

T
2

Y1
3

)81&7,21$/'(6&5,37,21
Temperature Control. The supply water flow temperature sensor (1) measures
the actual value and the controller (4) compares this value with the actual control
point. The control point comprises the basic setpoint value which is continuously
compensated by the outside air temperature sensor (2) value. If a deviation
between the two values exists, the controller (3) generates a 3-position control
signal to reposition the valve (4) to maintain the desired supply water temperature.

Y1 (%)
100

Cooling

In heating applications the controller output is reverse acting and a positive winter
compensation authority is used, with decreased outside air temperature the
control point is increased.
In cooling applications the controller output is direct acting and a negative summer
compensation authority is used, with increased outside air temperature the control
point is decreased.

Heating

0
0
CTRP1 Ystart
Xp

Xw
T1

Time Control. Depending on the programmed time schedule of the internal


controller real time clock the different operating control modes Comfort, Standby,
Night or OFF are selected. In the Standby or Night mode the main temperature setpoint is decreased by the programmed offset
values SOFFS (Standby) or NOFFS (Night).
If the configuration parameter C.04 (Ctrltyp) is set to Hi2, automatically the pump switches OFF at outside air temperatures
above 8C, if the valve is closed for more than 5 minutes during Comfort, Standby or Night mode.
In the OFF operating mode the controller automatically closes the valve (4) and switches the pump OFF.

W1-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
2

T7416A

T7412B

T7413A

2
CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426A

Y1
24V 24V

open/
OUT2

24V

close/
OUT1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
4

ML6420A
Heating or Cooling Valve

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

1
plus 1

T7413A1009 or
T7413A1066
43193884-001

Immersion Temperature Sensor with Brass Well, 135mm length or


Immersion Temperature Sensor for chilled water applications
Brass Well, 135mm length

T7416A1006

Outside Air Temperature Sensor, Wall Mounting

R7426A1016 or
R7426A1008

Temperature Controller with clock or


without clock

ML6420A3007 and
V5.....A.....

Valve Actuator and


Valve

237,216
Item

Quantity

Part Number

Description

T7412B1057 or
43193982-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

W1-2

HONEYWELL MICRONIK 200 APPLICATION

2876,'($,57(03(5$785(&203(16$7('+27:$7(5)/2:7(03(5$785(&21752/
:
:,7++,*+25/2:/,0,75(7851)/2:7(03(5$785(&21752/
Used in radiator heating systems to control the supply water flow temperature depending on the outside air temperature with
minimum limitation of the boiler return flow temperature to prevent corrosion due to condensation of flue gases or maximum
limitation of the return temperature in district heating systems.

T
2
B
A
5

AB
1

T
3

Y1
4

)81&7,21$/'(6&5,37,21
Temperature Control. The supply water flow temperature sensor (1) and return
water flow temperature sensor (2) measures the actual values and the controller
(4) compares these values with the actual control point and the desired limit
setpoint (Wlim). The control point comprises the basic setpoint value which is
continuously compensated by the outside air temperature sensor (3) value. If a
deviation between these values exists, the controller selects the highest or lowest
deviation signal in correspondence with the selected limit function.
Depending on this deviation signal the controller generates a 3-position control
signal to reposition the valve (5) to maintain the desired supply or return water
flow temperature.

Y1 (%)
100

Cooling

Heating

The controller output has to be configured reverse acting for heating applications
and the desired positive winter compensation authority determines the reset effect
on the main setpoint (W1).

0
CTRP1 Ystart
Xp

Xw
T1

Time Control. Depending on the programmed time schedule of the internal


controller real time clock the different operating control modes Comfort, Standby, Night or OFF are selected. In the Standby or
Night mode the main temperature setpoint is decreased by the programmed offset values SOFFS (Standby) or NOFFS (Night).
If the configuration parameter C.04 (Ctrltyp) is set to Hi2, automatically the pump switches OFF at outside air temperatures
above 8C, if the valve is closed for more than 5 minutes during Comfort, Standby or Night mode.
In the OFF operating mode the controller automatically closes the valve (5) and switches the pump OFF.

W2-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
3

T7416A

T7413A

T7412B

T7413A

2
CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426A

Y1
24V 24V

open/
OUT2

24V

close/
OUT1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5

ML6420A Heating Valve

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

1+2

T7413A1009

Immersion Temperature Sensor with Brass Well, 135mm length

T7416A1006

Outside Air Temperature Sensor, Wall Mounting

R7426A1016 or
R7426A1008

Temperature Controller with clock or


without clock

ML6420A3007 and
V5.....A.....

Valve Actuator and


Valve

237,216
Item

Quantity

Part Number

Description

T7412B1057 or
43193982-001

Remote Setpoint Adjustment Potentiometer, Wall Mounting or


Front Panel Mounting

EN3C-0161 0698R0-MA

W2-2

HONEYWELL MICRONIK 200 APPLICATION

52207(03(5$785(6833/<+27:$7(57(03(5$785(&$6&$'(&21752/ :
Used in radiator heating systems to control the supply water flow temperature depending on the room temperature.

T 1a
1b

B
A
4

AB

T
2

Y1
3

)81&7,21$/'(6&5,37,21
Temperature Control. The room air temperature sensor (1a or 1b) measures the
actual value and the controller (4) compares this value with the desired setpoint
(W1) of the master loop. Depending on the deviation an internal setpoint for the
submaster loop, the supply water flow temperature, is calculated. At zero
deviation the supply water flow temperature is controlled at the programmed
setpoint (Wcas) and if a deviation exists, the supply water setpoint is altered. The
reset span of the supply water setpoint is limited by the reset span adjustment
(Rcas) and the limit setting (Wlim).
The supply water flow temperature sensor (2) measures the actual value and the
controller (4) compares this value with the desired internal calculated setpoint.
If a deviation between the two values exists, the controller generates a 3-position
control signal to reposition the valve (5) to maintain the desired supply water flow
temperature.

Y1 (%)

Cooling

Heating

0
0
CTRP2

Xw
Ystart

T2

Xp

Time Control. Depending on the programmed time schedule of the internal


controller real time clock the different operating control modes Comfort, Standby, Night or OFF are selected. In the Standby or
Night mode the main temperature setpoint is decreased by the programmed offset values SOFFS (Standby) or NOFFS (Night).
If the configuration parameter C.04 (Ctrltyp) is set to Hi2, automatically the pump switches OFF, if the valve is closed for more
than 5 minutes during Comfort, Standby or Night mode.
In the OFF operating mode the controller automatically closes the valve (5) and switches the pump OFF. The night cycle
program compares the actual room temperature to the low cycle limits and either turns the heat and pump on or off or does
nothing. If the temperature is below the limit setpoint (NightLow) the controller opens fully the heating valve and switches the
pump ON. When the temperature reaches the other limit (1K differential), the valve closes and the pump switches OFF.

W3-1

EN3C-0161 0698R0-MA

HONEYWELL MICRONIK 200 APPLICATION

:,5,1*&211(&7,216
2

T7413A

1b

T7412C

1b

T7412B

1a

T7412A

1
3

CPA/
SPA

T1

T2

9 10 11 12 13 14
ON/ 24V
OFF

T3

R7426A

Y1
24V 24V

open/
OUT2

24V

close/
OUT1

15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
4

ML6420A Heating Valve

24V

3 - Way Valve

24V

2 - Way Valve

(48,30(17/,67
Item

Quantity

Part Number

Description

1a+1b

T7412A1018 or
T7412B1057

Room Temperature Sensor or


Room Temperature Sensor with CPA

T7413A1009

Immersion Temperature Sensor with Brass Well, 135mm length

R7426A1016 or
R7426A1008

Temperature Controller with clock or


without clock

ML6420A3007 and
V5....A....

Valve Actuator and


Valve

EN3C-0161 0698R0-MA

W3-2

HONEYWELL MICRONIK 200 APPLICATION

EN3C-0161 0698R0-MA

Honeywell Regelsysteme GmbH


Honeywellstr. 2-6
D-63477 Maintal
Tel. (0 61 81) 401-1
Fax (0 61 81) 401-400
Subject to change without notice. Printed in Germany.