The features of the tuning of filters, connected with the tertiary windings of converter transformers, is considered. It is shown that such a connection is effective, but encounters difficulties due to the fact that the tunable
filters have impedances as low as the external circuits. A theory and practical methods are given on how to
overcome these difficulties. Positive results, obtained when tuning the filters in the Vyborg dc installation are
described.
Keywords: Switched converters, converter substations, converter transformers, harmonics, filters, filter tuning, dc installation.
119
1570-145X/08/4202-0119 2008 Springer Science + Business Media, Inc.
120
L. L. Balyberdin et al.
330 kV on the rectifier
side and 400 kV
on the inverter side
=5
35 kV
MF
AF
Q = 10 MV A
= 11
40
= 13
30
= 23
10
=5
10
= 11
20
= 13
15
= 23 Q = 10 MV A
(1)
Tuning of Higher Harmonic Filters Connected to the Tertiary Windings of Converter Transformers
121
Zf.eq,
4
f
3
A
AG
RW1
RW2
2
1
a
2I/3
AG
I/3
100
w3
IKT 2IKT/3
IKT/3
f
f
IKT IKT/3
700
900
w3KT
w3KT
w3KT
arrive at the position for which the frequencies of all the local minima of the equivalent impedance of the filter will be
close to the frequencies of the canonical harmonics of the
converter current, which is being filtered
fi fcan.
3
2 R T2
1100
w3
500
f, Hz
w3
I/3
300
U 2 - U 02
I
3
2K T2
Zm ,
(2)
(3)
this indicates that the filter has been exactly tuned to the frequency fi. By switching the seal of the filter reactors we can
(4)
The fact that the sum (1) is not accessible for direct physical measurements is not the only difficulty when using the
minimum of this sum (this is also the case for the minimum
of the mutual impedance between the rectifier windings), as
a criterion of the optimum tuning of the filter connected to
the tertiary windings of the converter transformers. An additional difficulty in using these criteria is the fact that the
quantity Ztr + Zbf occurs in them, shifting the zeros of the
equivalent reactance of the filter as a whole with respect to
the zeros of the reactances of the individual filter sections. If
the tertiary windings of the transformers are situated between
the network and rectifier windings, these zero shifts can be
taken into account using the following approximate relation:
Zf.eq(fcan) Zf.eq(fi)
2( f can - f i ) X r ( f i )
,
fi
(5)
122
L. L. Balyberdin et al.
p, %
40
40
30
kd.norm, %
15
10
32
2.0 kd, %
20
I150.norm
10
5
10
4
2
p, %
40
10 12
20 I150, A
45
30
I>250.norm
20
p, %
20 I>250, A
60
40
Ips.norm
20
In Fig. 3 we show the frequency characteristic of the filters in the Vyborgsk substation Zf.eq(f) averaged over several
measurements in different converter units. We were able to
plot it in sections close to the points of local minima. To obtain the frequency characteristic outside these sections one
must have an audio generator of higher power. But we did
not feel that there was any practical need for this.
In Fig. 4 we show histograms of all the normalized indicators of the non-sinusoidality of the currents and voltages of
the 400 kV Vyborg Yullikkyalya power line taken during
the year of operation (with the exception of periods when the
system was under repair). Not one of the indicators exceeds
the norm.
Progress in designing reactors, controllable under load,
enables us to assume that in the future it will be possible to
use such reactors not only to compensate reactive power but
also in filters. This will enable the filters to be tuned directly
under operating conditions by monitoring the effect achieved
during the tuning itself. This is important both for simplifying the tuning technology but also for increasing its quality.
REFERENCES
15
5
Ips, A
Fig. 4. Histograms of the normalized indicators of non-sinusoidality of the currents and voltages in the 400 kV lines emerging from
the Vyborg substation: p is the duration of the current flow of this
value during the period being tracked; kd is the distortion coefficient;
I150 is the real value of the currents in the line in the 50 200 Hz harmonic frequency band; I>250 is the real value of the currents in the
line at a frequency above 250 Hz; and Ips is the psophometric value
of the currents in the line.