I.
INTRODUCTION
II.
The new generation proposed by XXXXXXXXXXXXXX is sited at about the midpoint of EPEs Afton-Luna 345 kV and will be interconnected to a new substation
(called DEMTAP1 345 kV, in the post-project powerflow cases used for the
feasibility portion of this study). Therefore, the Luna-Afton 345 kV line was
assumed to be tapped into this substation (see feasibility study report for details
on configuration assumed) at about its midpoint such that this line becomes the
Luna-DEMTAP1 and DEMTAP1-Afton 345 kV lines in the post-project scenarios
(assuming the Deming Energy project in).
The two generators will be connected to the 345 kV transmission through a
single 217 MVA, 13.8/345 kV step-up transformer. The step-up transformer has
an impedance of 8 % on a 130 MVA base. The step-up transformer impedance
modeled in the short circuit analysis was:
Z (step-up) = 0.0031 + J0.06146 per unit (100 MVA base)
The new generators have the following reactance values on the generator MVA
base:
Xd = Direct Axis Synchronous Reactance = 2.321 per unit
Xd = Direct Axis Transient Reactance = 0.247 per unit
Xd = Direct Axis Subtransient Reactance = 0.171 per unit
These reactance values were converted to a 100 MVA base and used to model
the new generators in the short circuit study.
In addition to the new Deming Energy generation, four other viable generation
projects were added in the analysis. These generation project were:
These additional generators were modeled in the study to provide a worst case
scenario in the event that they are interconnected into EPEs system before the
Deming Energy generation is interconnected.
Maximum fault currents were then determined at the Demtap1 345 kV bus and
other southern New Mexico substations of interest or importance.
These included :
Afton 345 kV
Arroyo 345 kV
DEMTAP1 345 kV
Diablo 345 kV
Luna 345 kV
Newman 345 kV
Diablo 115 kV
Luna 115 kV
Newman 115 kV
Rio Grande 115 kV
Rio Grande 69 kV
The resulting fault current was then compared to the circuit breaker interruption
ratings of the breakers at each of the above mentioned substations.
III.
The circuit breakers used in the Southern New Mexico System at 345 kV, 115
kV, and 69 kV buses vary between the substations. The following is a list of the
existing circuit breakers, along with the interruption rating, at each of the
pertinent substations:
Breaker
Substation
Afton
Breaker
Voltage
345
345
345
345
345
345
Number
6498B
3348B
7628B
4548B
8578B
9728B
Arroyo
345
345
345
345
345
345
345
2418B
2458B
4348B
3018B
5428B
7548B
2098B
Demtap1
Diablo
345
345
345
1888B
2138B
2258B
40,000
40,000
40,000
Luna
345
345
345
345
345
345
345
345
345
01982
03082
04182
07482
09682
08582
10682
11782
15082
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
Interruption
Rating (Amps)
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
Breaker
Substation
Newman
Breaker
Voltage
345
345
345
345
Number
2448B
6018B
8378B
0538B
Diablo
115
115
115
115
115
115
1586B
1636B
1706B
1806B
2876B
4326B
40,000
40,000
40,000
40,000
40,000
31,500
Luna
115
115
115
32162
34362
33262
20,000
20,000
20,000
Newman
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
11950
11101
15601
N-115-1
11951
11401
N-115-7
11957
N-115-8
11952
11601
N-115-3
11953
15501
N-115-19
11967
N-115-20
N-115-21
11968
N-115-22
N-115-23
11969
N-115-24
N-115-2
Interruption
Rating (Amps)
40,000
40,000
40,000
40,000
40,000
50,000
40,000
40,000
40,000
40,000
43,000
43,000
43,000
40,000
50,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
40,000
Breaker
Substation
Rio Grande
Rio Grande
Breaker
Voltage
115
115
115
115
115
115
115
115
115
115
115
115
Number
1516B
3316B
4456B
4616B
1766B
2296B
2426B
5146B
1126B
2186B
3856B
5376B
69
69
69
69
69
69
69
69
69
69
69
69
69
69
5009
5003
5907
5005
5006
5007
5701
5501
1254B
5601
5918
5401B
5010
5032
Interruption
Rating (Amps)
40,000*
23,000
23,000
40,000
40,000
23,000
23,000
40,000
40,000*
23,000
23,000
40,000
40,000*
40,000*
24,000
40,000
40,000
26,000
31,500
31,500
31,500
31,500
40,000
31,500
40,000
40,000
The short circuit analysis was first performed with no new Deming Energy
generation (all other viable generation projects in). This gave the base case
fault duties of the circuit breakers. Then the Deming Energy generation was
modeled and the short circuit study was re-run (all other viable generation
projects in). The incremental between these two studies gave the impact of the
new generators on the existing circuit breakers in the Southern New Mexico
system. The short circuit (fault) currents for each case at all of the possibly
impacted substations are:
Three Phase Line to Ground:
Substation Faulted
Afton 345 kV Bus
Arroyo 345 kV Bus
Demtap1 345 kV Bus
Diablo 345 kV Bus
Luna 345 kV Bus
Newman 345 kV Bus
Diablo 115 kV Bus
Luna115 kV Bus
Newman 115 kV Bus
Rio Grande 115 kV Bus
Rio Grande 69 kV Bus
No Deming Energy
Generation Project
Fault Current (Amps)
7,928.0
5,812.0
NA
5,295.0
11,758.0
7,778.0
18,968.0
9,831.0
24,414.0
20,529.0
19,438.0
Substation Faulted
Afton 345 kV Bus
Arroyo 345 kV Bus
Demtap1 345 kV Bus
Diablo 345 kV Bus
Luna 345 kV Bus
Newman 345 kV Bus
Diablo 115 kV Bus
Luna115 kV Bus
Newman 115 kV Bus
Rio Grande 115 kV Bus
Rio Grande 69 kV Bus
No Deming Energy
Generation Project
Fault Current (Amps)
6,904.0
5,079.0
NA
4,846.0
40,000.0
7,927.0
19,092.0
11,546.0
28,894.0
22,334.0
22,953.0
V. Certification
This Short Circuit Analysis was performed pursuant with a
Transmission/Generation Feasibility Study requested by XXXXXXXXXXXXXX.
The generator, step-up transformer and new transmission line parameters were
supplied by XXXXXXXXXXXXXXX. The Short Circuit Analysis was performed by
El Paso Electric Company.